Plan Review Details - Permit 06120033
Plan Review Stops For Permit 06120033
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-06-25 Cont ID  
Sent By shill Date 2007-06-25 Time 11:21 Rev Time 0.00
Received By shill Date 2007-06-25 Time 11:21 Sent To  
Notes
2007-06-25 11:24:25****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FACFLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTES
  
  
  
 1.)WEATHERGUARD BUILDING PRODUCTS, INC. IS REQUIRED
 TO HAVE A CERTIFICATE OF AUTHORIZATION TO PRACTICE
 ENGINEERING AND THAT NUMBER IS TO BE INCLUDED ON EACH
 SHEET FAC61G16-23.002.A COPY OF THE PLAN HAS BEEN
 RETAINED.
  
 2.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED,
 FAC9B72, WWW.FLORIDABUILDING.ORG.THE FLORIDA STATE
 PRODUCT APPROVAL FOR THE STORM PANELS IS EXPIRED (2001
 CODE).PLEASE PRINT THE NEW APPROVAL, IF AVAILABLE,
 FROM THE WEBSITE.IF THE STORM PANELS DOES NOT HAVE A
 FLORIDA STATE PRODUCT APPROVAL, PLEASE ADVISE AND A
 LOCAL PRODUCT APPROVAL WILL BE ISSUED USING THE NOA.
  
 3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED,
 FAC9B72, WWW.FLORIDABUILDING.ORG.A LOCAL PRODUCT
 APPROVAL APPLICATION IS REQUIRED.THE APPLICATION IS
 ATTACHED.
  
 4.)ADDRESSED.
  
 5.)THE ENGINEERING REFERS TO ASCE7-05.PLEASE SEE
 FBC CHAPTER 35; CORRECT REFERENCE IS ASCE7-02.
  
 6.)SHEET 17, WIND LOAD CALCULATIONS, PARAMETERS,
 GIVES WIND SPEED 74MPH, EXPOSURE CLASSIFICATION BLANK.
 WHAT IS THIS?
  
 7.)THIS WAS APPLIED FOR AS A SITE SPECIFIC.THIS IS
 GOOD FOR ONE JOB ONLY AS THE ENGINEERING WAS PRODUCED
 FOR ONE JOB.PLEASE NOTE THAT YOU MAY APPLY FOR LOCAL
 PRODUCT APPROVAL FOR THIS PRODUCT.ORIGINAL
 ENGINEERING WOULD THEN NOT BE REQUIRED FOR EACH JOB.
  
 8.)CALCULATIONS WERE PROVIDED REGARDING PRESSURES
 (BAHAMA SHUTTERS).THERE IS A STATEMENT THAT THE
 DESIGN IS IMPACT.CODE COMPLIANCE FOR IMPACT
 RESISTANCE WAS NOT PROVIDED.SEE FBC1609.1.4, IMPACT
 PROTECTION TO MEET ONE OF THE STANDARDS LISTED.THE
 STANDARDS ARE TEST STANDARDS; NO TEST REPORT WAS
 SUBMITTED.
  
 9.)THE MIAMI DADE NOA FOR THE BAHAMA SHUTTER IS
 PENDING.THERE IS A CURRENT REPORT AVAILABLE.PROVIDE
 THE CURRENT REPORT.
  
 10.)THE ACCORDION SHUTTER NOA IS EXPIRED.FLORIDA
 STATE OR LOCAL PRODUCT APPROCAL REQUIRED.A LOCAL
 PRODUCT APPROVAL APPLICATION IS ATTACHED.IN ADDITION
 TO THE ENGINEERING SUBMITTED, PROOF OF A THIRD PARTY
 QUALITY ASSURANCE ENTITY IS REQUIRED.FAC9B72.
  
 11.)ALL INFORMATION REQUIRED BY FAC61G15-23.002 IS
 REQUIRED ON EACH SHEET.
  
 12.)TWO COMPLETE COLLATED SETS REQUIRED.REMOVE
 UNNECESSARY PAPERWORK.ONLY ONE INSTALLATION SCHEDULE
 WAS PROVIDED; TWO REQUIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-04-30 Cont ID  
Sent By shill Date 2007-04-30 Time 10:45 Rev Time 0.00
Received By shill Date 2007-04-30 Time 10:45 Sent To  
Notes
2007-04-30 10:46:25****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FROM PREVIOUS LIST:
  
 4.)COMPLETE THE ATTACHED INSTALLATION SCHEDULE OR
 PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-01-24 Cont ID  
Sent By shill Date 2007-01-24 Time 15:12 Rev Time 0.00
Received By shill Date 2007-01-24 Time 15:12 Sent To  
Notes
2007-01-24 15:28:03****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 1.)WEATHERGUARD BUILDING PRODUCTS, INC. IS REQUIRED
 TO HAVE A CERTIFICATE OF AUTHORIZATION TO PRACTICE
 ENGINEERING AND THAT NUMBER IS TO BE INCLUDED ON EACH
 SHEET FAC61G16-23.002.A COPY OF THE PLAN HAS BEEN
 RETAINED.
  
 2.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED,
 FAC9B72, WWW.FLORIDABUILDING.ORG.THE FLORIDA STATE
 PRODUCT APPROVAL FOR THE STORM PANELS IS EXPIRED (2001
 CODE).PLEASE PRINT THE NEW APPROVAL, IF AVAILABLE,
 FROM THE WEBSITE.IF THE STORM PANELS DOES NOT HAVE A
 FLORIDA STATE PRODUCT APPROVAL, PLEASE ADVISE AND A
 LOCAL PRODUCT APPROVAL WILL BE ISSUED USING THE NOA.
  
 3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED,
 FAC9B72, WWW.FLORIDABUILDING.ORG.A LOCAL PRODUCT
 APPROVAL APPLICATION IS REQUIRED.THE APPLICATION IS
 ATTACHED.
  
 4.)COMPLETE THE ATTACHED INSTALLATION SCHEDULE OR
 PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT.
  
 5.)THE ENGINEERING REFERS TO ASCE7-05.PLEASE SEE
 FBC CHAPTER 35; CORRECT REFERENCE IS ASCE7-02.
  
 6.)SHEET 17, WIND LOAD CALCULATIONS, PARAMETERS,
 GIVES WIND SPEED 74MPH, EXPOSURE CLASSIFICATION BLANK.
 WHAT IS THIS?
  
 7.)THIS WAS APPLIED FOR AS A SITE SPECIFIC.THIS IS
 GOOD FOR ONE JOB ONLY AS THE ENGINEERING WAS PRODUCED
 FOR ONE JOB.PLEASE NOTE THAT YOU MAY APPLY FOR LOCAL
 PRODUCT APPROVAL FOR THIS PRODUCT.ORIGINAL
 ENGINEERING WOULD THEN NOT BE REQUIRED FOR EACH JOB.
  
 8.)CALCULATIONS WERE PROVIDED REGARDING PRESSURES
 (BAHAMA SHUTTERS).THERE IS A STATEMENT THAT THE
 DESIGN IS IMPACT.CODE COMPLIANCE FOR IMPACT
 RESISTANCE WAS NOT PROVIDED.SEE FBC1609.1.4, IMPACT
 PROTECTION TO MEET ONE OF THE STANDARDS LISTED.THE
 STANDARDS ARE TEST STANDARDS; NO TEST REPORT WAS
 SUBMITTED.
  
  
  
  
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2006-12-07 Cont ID  
Sent By ssherman Date 2006-12-07 Time 10:33 Rev Time 0.00
Received By ssherman Date 2006-12-07 Time 10:33 Sent To  
Notes
2006-12-07 10:33:37HISTORICAL APPROVAL PER JILLIAN PAPA
 LEVEL 2ALREADY PAID $30

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-06-15 Cont ID  
Sent By adarroug Date 2007-06-15 Time 15:41 Rev Time 0.00
Received By adarroug Date 2007-06-15 Time 15:41 Sent To B
Notes
2007-06-15 15:41:29TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-04-25 Cont ID  
Sent By adarroug Date 2007-04-25 Time 13:25 Rev Time 0.00
Received By adarroug Date 2007-04-25 Time 13:25 Sent To B
Notes
2007-04-25 13:25:43TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-01-24 Cont ID  
Sent By shill Date 2007-01-24 Time 16:35 Rev Time 0.00
Received By shill Date 2006-12-07 Time 15:04 Sent To  
Notes
2006-12-07 15:04:46TO "MISC" BOX#1


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved