| 2007-06-25 11:24:25 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FACFLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTES |
| | |
| | |
| | |
| | 1.)WEATHERGUARD BUILDING PRODUCTS, INC. IS REQUIRED |
| | TO HAVE A CERTIFICATE OF AUTHORIZATION TO PRACTICE |
| | ENGINEERING AND THAT NUMBER IS TO BE INCLUDED ON EACH |
| | SHEET FAC61G16-23.002.A COPY OF THE PLAN HAS BEEN |
| | RETAINED. |
| | |
| | 2.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED, |
| | FAC9B72, WWW.FLORIDABUILDING.ORG.THE FLORIDA STATE |
| | PRODUCT APPROVAL FOR THE STORM PANELS IS EXPIRED (2001 |
| | CODE).PLEASE PRINT THE NEW APPROVAL, IF AVAILABLE, |
| | FROM THE WEBSITE.IF THE STORM PANELS DOES NOT HAVE A |
| | FLORIDA STATE PRODUCT APPROVAL, PLEASE ADVISE AND A |
| | LOCAL PRODUCT APPROVAL WILL BE ISSUED USING THE NOA. |
| | |
| | 3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED, |
| | FAC9B72, WWW.FLORIDABUILDING.ORG.A LOCAL PRODUCT |
| | APPROVAL APPLICATION IS REQUIRED.THE APPLICATION IS |
| | ATTACHED. |
| | |
| | 4.)ADDRESSED. |
| | |
| | 5.)THE ENGINEERING REFERS TO ASCE7-05.PLEASE SEE |
| | FBC CHAPTER 35; CORRECT REFERENCE IS ASCE7-02. |
| | |
| | 6.)SHEET 17, WIND LOAD CALCULATIONS, PARAMETERS, |
| | GIVES WIND SPEED 74MPH, EXPOSURE CLASSIFICATION BLANK. |
| | WHAT IS THIS? |
| | |
| | 7.)THIS WAS APPLIED FOR AS A SITE SPECIFIC.THIS IS |
| | GOOD FOR ONE JOB ONLY AS THE ENGINEERING WAS PRODUCED |
| | FOR ONE JOB.PLEASE NOTE THAT YOU MAY APPLY FOR LOCAL |
| | PRODUCT APPROVAL FOR THIS PRODUCT.ORIGINAL |
| | ENGINEERING WOULD THEN NOT BE REQUIRED FOR EACH JOB. |
| | |
| | 8.)CALCULATIONS WERE PROVIDED REGARDING PRESSURES |
| | (BAHAMA SHUTTERS).THERE IS A STATEMENT THAT THE |
| | DESIGN IS IMPACT.CODE COMPLIANCE FOR IMPACT |
| | RESISTANCE WAS NOT PROVIDED.SEE FBC1609.1.4, IMPACT |
| | PROTECTION TO MEET ONE OF THE STANDARDS LISTED.THE |
| | STANDARDS ARE TEST STANDARDS; NO TEST REPORT WAS |
| | SUBMITTED. |
| | |
| | 9.)THE MIAMI DADE NOA FOR THE BAHAMA SHUTTER IS |
| | PENDING.THERE IS A CURRENT REPORT AVAILABLE.PROVIDE |
| | THE CURRENT REPORT. |
| | |
| | 10.)THE ACCORDION SHUTTER NOA IS EXPIRED.FLORIDA |
| | STATE OR LOCAL PRODUCT APPROCAL REQUIRED.A LOCAL |
| | PRODUCT APPROVAL APPLICATION IS ATTACHED.IN ADDITION |
| | TO THE ENGINEERING SUBMITTED, PROOF OF A THIRD PARTY |
| | QUALITY ASSURANCE ENTITY IS REQUIRED.FAC9B72. |
| | |
| | 11.)ALL INFORMATION REQUIRED BY FAC61G15-23.002 IS |
| | REQUIRED ON EACH SHEET. |
| | |
| | 12.)TWO COMPLETE COLLATED SETS REQUIRED.REMOVE |
| | UNNECESSARY PAPERWORK.ONLY ONE INSTALLATION SCHEDULE |
| | WAS PROVIDED; TWO REQUIRED. |