Plan Review Details - Permit 06120028
| Plan Review Stops For Permit 06120028 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2006-12-08 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-12-08 |
Time |
15:41 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2006-12-08 |
Time |
15:39 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-12-05 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-12-05 |
Time |
11:11 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2006-12-05 |
Time |
10:49 |
Sent To |
I |
|
| Notes |
| 2006-12-05 11:11:16 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | | | | 1} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, | | | METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT | | | COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED. | | | THE EQUIPMENT GROUNDING}CONDUCTOR MUST COMPLY WITH | | | 250.66. #4 MINIMUM FOR 200 AMPS. | | | | | | 2}225.32:THE DISCONNECTING MEANS SHALL BE INSTALLED | | | EITHER INSIDE OR OUTSIDE OF THE BUILDING OR STRUCTURE | | | SERVED OR WHERE THE CONDUCTORS PASS THROUGH THE | | | BUILDING OR STRUCTURE. THE DISCONNECTING MEANS SHALL BE | | | AT A READILY ACCESSIBLE LOCATION NEAREST THE POINT OF | | | ENTRANCE OF THE CONDUCTORS. FOR THE PURPOSES OF THIS | | | SECTION, THE REQUIREMENTS IN 230.6 SHALL BE PERMITTED | | | TO BE UTILIZED. | | | | | | 3} INDICATE THE SIZE OF THE SERVICE RISER. | | | | | | 4} THE GROUND BEING RAN FROM THE METER MUST BE REMOVED. | | | IT VIOLATES 250.6 AND PARALLELS THE GROUNDED NEUTRAL. | | | THE ISOLATED NEUTRAL MAY BE RUN WITH GROUND ONLY AFTER | | | THE FIRST MEAS OF DISCONNECT. | | | | | | 5} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-12-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-12-08 |
Time |
10:47 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-12-08 |
Time |
10:47 |
Sent To |
E |
|
| Notes |
| 2006-12-08 10:47:53 | TO "BTROBAUG" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-12-05 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-12-05 |
Time |
11:11 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2006-12-01 |
Time |
16:04 |
Sent To |
PC |
|
| Notes |
| 2006-12-01 16:05:04 | TO "E" BOX |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |