Plan Review Details - Permit 06111087
Plan Review Stops For Permit 06111087
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-01-24 Cont ID  
Sent By mjacobs Date 2007-01-24 Time 13:53 Rev Time 0.00
Received By mjacobs Date 2007-01-24 Time 13:01 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-01-18 Cont ID  
Sent By mjacobs Date 2007-01-18 Time 18:52 Rev Time 0.00
Received By mjacobs Date 2007-01-18 Time 17:22 Sent To PC
Notes
2007-01-18 18:52:19BUILDING PLAN REVIEW
 PERMIT:06111087
 ADD: 701 S.ROSEMARY AVE
 CONT: VENTURA ARCH DEV.
 TEL: (561)856-6655
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 2ND
 ACTION: DENIED
  
 1) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 NOTE: THE FIRM LICENSE NUMBER IS STILL MISSING FROM
 SOME OF THE PAGES.
  
 2)INDICATE THE SUITE NUMBER ON THE ELEVATION DRAWINGS
 AS REQUIRED BY THE WEST PALM BEACH CITY CODE.
  
  
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-12-20 Cont ID  
Sent By mjacobs Date 2006-12-20 Time 18:02 Rev Time 0.00
Received By mjacobs Date 2006-12-20 Time 13:15 Sent To  
Notes
2006-12-20 18:02:06BUILDING PLAN REVIEW
 PERMIT:06111087
 ADD:701S. ROSEMARY AVE. #103
 CONT:VENTURA ARCHITECT & DEV.
 TEL: (561)856-6655
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW : 1ST
 ACTION: DENIED
  
  
 1) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2) W.P.B. AMENDMENTS 108.3* THE PERMIT VALUATION IS
 LOW. IF IN THE OPINION OF THE BUILDING OFFICAL THE
 CLAIMED VALUATION OF THE BUILDING ALTERATION APPERAS TO
 BE UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL
 BE DENIED. FOR PERMITTING PURPOSES, VALUATION OF
 BUILDINGS SHALL BE THE TOTAL REPLACEMENT VALUE TO
 INCLUDE
 STRUCTURAL,ELECTRIC,PLUMBING,MECHINICAL,INTERIOR
 FINISH,ARCHITECTURAL AND DESIGN FEES,MARKETING COSTS,
 ANDOVERHEAN AND PROFIT. OUR VALUATION REFERENCE IS
 ICC (BVD), MARSHALL-SWIFT AND MEANS COST ANALUSIS
 SERVICES.
  
 3)A TITLE BLOCK WITH THE INFORMATION SPECIFIED PER
 61G1-16.004 FAC SHALL BE PRESENT ON DRAWINGS ISSUED BY
 THE RESPONSIBLE ARCHITECT AND MUST,
 AT A MINIMUM CONTAIN
 1) FIRM NAME,ADDRESS AND TELEPHONE #
 2)FIRM LICENCE #
 3) NAME OF PROJECT
 4) DATE PREPARED
 5) A SPACE FOR SIGNATURE & DATED SEAL
 6)A SPACE FOR PRINTED NAME OF PERSON
 SEALING THE DOCUMENT
  
 4)AN ENGINEER PRACTICING THROUGH A DULYAUTHORIZED
 ENGINEERING BUSINESS SHALL INDICATE THEIR NAME AND
 LICENCE #, AS WELL AS THE NAME,ADDRESS AND CERTIFICATE
 OF AUTHORIZATION #ON EACH SHEET PER 61G15-23.002 (2)
 FAC
  
 5) F.S. 481.219.ALL FINAL CONSTRUCTION DOCUMENTS AND
 INSTRUMENTS OF SERVICE WHICH INCLUDE DRAWINGS,
 SPECIFICATIONS, PLANS, REPORTS, OR OTHER PAPERS OR
 DOCUMENTS INVOLVING THE PRACTICE OF ARCHITECTURE WHICH
 ARE PREPARED OR APPROVED FOR THE USE OF THE
 CORPORATION, LIMITED LIABILITY COMPANY, OR PARTNERSHIP
 AND FILED FOR PUBLIC RECORD WITHIN THE STATE SHALL BEAR
 THE SIGNATURE AND SEAL OF THE LICENSEE WHO PREPARED OR
 APPROVED THEM AND THE DATE ON WHICH THEY WERE SEALED.
  
 6)THE BREAKROOM SINK SHALL COMPLY WITH SECTION
 11-4.24 AND ALL SUB SECTIONS. SHOW CLEAR FLOOR SPACE ON
 SHEET A4 DETAIL 1. AND SHOW ALL REQUIREMENTS ON SHEET
 A5. DETAIL #7
  
 7)SUBMIT THE WALL DETAILS FOR THE NEW WALLS 3D AND 3A
 SHEET A1. WHAT'S THE WALL RATING FOR THE TECH CLOSET
 DETAIL #4 SHEET A3.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-01-24 Cont ID  
Sent By dpalmer Date 2007-01-24 Time 19:28 Rev Time 0.00
Received By dpalmer Date 2007-01-24 Time 19:08 Sent To PC
Notes
2007-01-24 19:29:42PLANS ARE STAMPED AND READY TO GO, NEEDS CITY PLACE
 STAMP ON E-3 ON BOTH SETS.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-01-23 Cont ID  
Sent By dpalmer Date 2007-01-23 Time 09:06 Rev Time 0.00
Received By dpalmer Date 2007-01-23 Time 08:31 Sent To  
Notes
2007-01-23 09:07:26*** UNSAT ***
  
 1) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED
 ARE NOT SIGNED, DATED OR SEALED BY THE DESIGNER OF
 RECORD. THEY ARE IN FACT PHOTO-COPIES OF SIGNED
 DOCUMENTS.
 PLEASE SEE FBC CHAPTER 13 WHICH REQUIRES THIS TO BE
 DONE ALONG WITH FS 481.221 FOR ARCHITECTS AND 471.025
 FOR ENGINEER'S.
 FBC 13-103.1.1, 13-103.1.1.1
  
 2) NOTE: PLEASE SEE *S* AND *S3* TYPE DEVICES ARE BEING
 CALLED OUT AS LEVITON DECORATYPE DEVICES WHICH WILL
 NOT WORK WITH THE LIGHTING CONTROL SYSTEM AS SHOWNAND
 WILL NOT PROVIDE THE OVER RIDE OR AUTOMATED TURN OFF AS
 REQUIRED PER 13-415.1.ABC.1.1, AND .1.2.
 PLEASE ADJUST THESE DEVICES, PLEASE LIST A COMPATIBLE
 DEVICE FOR SYSTEM AND PLEASE INDICATE THE MAXIMUM TIMES
 ON THE SYMBOL LEGEND.
 PLEASE SEE THIS CAN BE DONE BY ONLY REVISING THE
 DEVICES ON E-3
 PLEASE SEE THIS WAS NOT DONE.
  
 ** PLEASE KNOW AT 08:47 1/23/07 A CALLED WAS PLACED TO
 THE ENGINEER'S OFFICE TO GO OVER THESE COMMENTS. A
 MESSAGE WAS LEFT FOR MR. MIKE MARSHALL.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-01-15 Cont ID  
Sent By dpalmer Date 2007-01-15 Time 11:10 Rev Time 0.00
Received By dpalmer Date 2007-01-15 Time 08:56 Sent To  
Notes
2007-01-15 11:13:12*** UNSAT 2ND REVIEW***
  
 TD AMERITRADE
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW STILL
 NEED TO BE ADDRESSED ALONG WITH SOME NEW COMMENTS BASED
 ON CHANGES MADE TO PLANS.
  
 ** PLEASE SEE THE COMMENTS BELOW ARE TAKEN DIRECTLY
 FROM PREVIOUS REVIEW IN THE SAME NUMERICAL ORDER. THEY
 WILL CONTAIN A NO, OK, OR NO/OK.
 A) NO WILL BE FOLLOWED BY FURTHER EXPLANATION OF THE
 PREVIOUS COMMENT.
 B) OK, MAY REFERENCE TO ANY NEW NOTES, HOWEVER WILL
 HAVE PREVIOUS NOTE REMOVED.
 C) NO/OK, WILL BE FOLLOWED BY FURTHER EXPLANATION AS
 PART OF THE COMMENT MAY NOT HAVE BEEN ADDRESSED FULLY
 AND PART OF THE PREVIOUS COMMENT MAY BE OK.
  
 ** ANY NEW NOTES WILL BE AT THE BOTTOM AND IDENTIFIED
 AS*** NEW NOTES ***.
  
 ** PLEASE KNOW THAT A DETAILED RESPONSE TO THE COMMENTS
 IN THE SAME NUMERICAL ORDER WOULD HELP IN THE REVIEW
 PROCESS. PLEASE SEE THE RESPONSES DO NOT CORRELATE TO
 THE PREVIOUS REVIEW COMMENTS.
  
  
 1) NOTE:NO/OK. PLEASE SEE THAT MOST OF THE TITLE
 BLOCKS ON EACH SHEET WAS REVISED; HOWEVER PLEASE SEE
 COVER SHEET WHICH STILL CONTAINS THE ARCHITECTURAL FIRM
 WHICH DOES NOT CONTAIN A CERTIFICATE OF AUTHORIZATION
 NUMBER ALSO KNOWN AS A FIRM LICENSE NUMBER THROUGH THE
 DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION.
 THIS COMMENT IS MADE AS IT IS REQUIRED TO BE CORRECTED
 EVEN THOUGH IT WILL NOT AFFECT THE ELECTRICAL PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS FOR
 ARCHITECT AND ARCHITECTURAL FIRM AS REQUIRED UNDER
 FLORIDA ADMINISTRATIVE CODE 61G1-16.004 AND FLORIDA
 STATUTES 481.219
 PLEASE SEE MISSING FIRM LICENSE NUMBER ALSO KNOWN AS
 THE CERTIFICATE OF AUTHORIZATION NUMBER.
 PLEASE SEE MISSING THE PRINTED NAME AND LICENSE NUMBER
 OF THE ARCHITECT OF RECORD.
 ** THIS INFORMATION IS REQUIRED FOR ALL SHEETS AND FOR
 ALL TRADES WHETHER OR NOT COMMENT IS MADE BY OTHER
 TRADE REVIEWER(S).
  
 2) NOTE: OK.
  
 3) NOTE: OK.
  
 4) NOTE: OK.
  
 5) NOTE:OK/NO THIS WAS DONE; HOWEVER SEE COMMENTS
 BELOW AS THIS WILL BE REQUIRED FOR NEW ENERGY
 CALCULATIONS. PLEASE SEE TWO DIFFERENT SETS OF
 ENERGY/COM-CHECK SUBMISSIONS.
 ** THIS PREVIOUS NOTE VERBIAGE WILL BE LEFT FOR
 INFORMATION ONLY AS COMMENT WAS ADDRESSED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE ENERGY CALCULATIONS SUBMITTED SHALL BE
 SIGNED, DATED AND SEALED BY THE DESIGNER/ENGINEER
 RESPONSIBLE. PLEASE ALSO SEE OTHER COMMENTS BASED ON
 THESE SHEETS.
 PLEASE ALSO SEE SECTION ON THE ENERGY CALCULATIONS
 WHICH REQUIRES THE OWNER/AGENT TO ALSO SIGN.
  
 6) NOTE: OK.
  
 7) NOTE:NO. PLANS WERE SUBMITTED; HOWEVER COMPLIANCE
 WITH THE MINIMUM REQUIREMENTS OF THE SECTIONS GIVEN IN
 PREVIOUS REVIEW HAS NOT BEEN MET. PLEASE SEE THAT THE
 FBC CHAPTER 11 FOR ADA REQUIREMENTS EXCEED THAT OF THE
 NFPA-72 AND THE MORE RESTRICTIVE SHALL APPLY. PLEASE
 SEE THE LIGHTING LEVELS FOR STROBES MUST MEET
 11-4.28.3(4).
 PLEASE SEE THE MINIMUM LEVELS FOR AUDIBLE DEVICES ARE
 NOT SHOWN. PLEASE SEE 11-4.28.2.
 PLEASE SEE A NOTE WAS ADDED TO THE PLAN WHICH STATES A
 4.28 FOR ADA REQUIREMENTS? PLEASE SPECIFY THE CODE
 SECTIONS WHICH ARE RELEVANT AND AS GIVEN IN THIS TEXT
 NOTE AND PREVIOUS TEXT NOTES.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MINIMUM FIRE ALARM PLANS SHOWING LAYOUT OF
 NEW OR EXISTING DEVICES MEETING THE 2004 FBC AND 2002
 NFPA-72 SHALL BE SUBMITTED. PLEASE KNOW, EVEN AS SCOPE
 OF WORK IS REQUIRED UNDER SEPARATE PLANS AND PERMIT THE
 BASE SYSTEM SHALL BE SHOWN IN BASE BUILD OUT PLANS.
 PLEASE INDICATE NEW OR EXISTING HORN AND STROBES
 MEETING 2004 FBC 11-4.28.1,.2.3(4).
 PLEASE SEE .3(4) WHICH REQUIRE A MINIMUM OF 75 CANDELAS
 WHICH IS ABOVE THE MINIMUMS REQUIRED IN NFPA-72. FBC
 ADMIN SECTION 106.1.2, 106.1.1.1
  
 8) NOTE: OK, HOWEVER SEE NEW NOTES.
  
 9) NOTE:NO, PLEASE SEE THERE ARE NOW TWO SUBMITTED
 LIGHTING COMPLIANCE CALCULATIONS SUBMITTED. PLEASE SEE
 EITHER ONE CAN BE REVIEWED FOR COMPLIANCE AND
 COORDINATION WITH THE PLANS.
 PLEASE SEE ONE DOES NOT SUPPLY THE INFORMATION AND IS
 STILL INDICATING METHOD A AND IT IS NOT KNOWN TO THIS
 OFFICE HOW METHOD A APPLIES.
 PLEASE ALSO SEE A COM-CHECK VERSION WAS ALSO SUBMITTED
 WHICH STATES 90.1/2001 EDITION. PLEASE KNOW THAT ANY
 VERSIONS MUST BE DONE AND STATE THE 2004 FBC. PLEASE
 ALSO SEE THE OCCUPANCY SPECIFIED IN CALCULATIONS STATE
 "RETAIL". THIS IS NOT POSSIBLE AS THIS IS NOT A RETAIL
 SPACE. PLEASE SEE TABLES 415.2.C.1, 415.2.B.1, THESE
 TABLES DO CONTAIN THE OCCUPANCY AND USE AS REQUIRED.
 PLEASE BE SURE TO CORRELATE ALL OF THE FIXTURE WATTAGES
 WITH THAT WHICH IS PERMITTED.
 ** IF THIS WERE A RETAIL SPACE, THEN PLANS WOULD BE
 REQUIRED TO BE CHANGED TO MERCANTILE OCCUPANCY. PLEASE
 SEE ARCHITECTURAL SHEETS WHICH CONTAIN THE STATED
 OCCUPANCY.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE ENERGY CALCULATIONS SUBMITTED DO NOT
 CORRELATE WITH THE PLANS SUBMITTED. PLEASE SEE THE
 NUMBER OF FIXTURES AND WATTAGE DO NOT MATCH. THERE IS A
 SUBSTANTIAL DIFFERENCE.
 PLEASE SEE FBC 2004 13-415.2.ABC.1, AND PLEASE INDICATE
 THE MAXIMUM LIGHTING POWER DENSITIES.
 PLEASE KNOW, BASED ON METHOD "A" THIS WILL NOT GIVE YOU
 THE CORRECT INFORMATION AS NEEDED AS THE SQ FT WILL BE
 ENTERED UNDER 5K SQ FT.
 PLEASE ALSO SEE THE AREAS WHERE CONTROL MENTIONS
 MANUAL, INSTEAD OF THE REQUIRED AUTO SHUT OFF. PLEASE
 SEE THE FOLLOWING COMMENT.
  
 10) NOTE:NO/OK, PLEASE SEE SOME COMPLIANCE HAS BEEN
 MET HOWEVER THE OVER RIDES TIMES ON ALL DEVICES SHALL
 BE STATED. THE MAXIMUM TIMES WERE GIVEN ON PREVIOUS
 REVIEW DEPENDING ON THE DEVICE CHOSEN.
 PLEASE SEE SOME ROOMS WHICH ARE CONSIDERED SEPARATE
 SPACES DO NOT CONTAIN ANY CONTROL DEVICES AS REQUIRED
 PER 13-415.1.ABC.1.2.
 PLEASE ALSO SEE THE INGRESS/EGRESS AREA AT MAIN
 ENTRANCE, COULD NOT LOCATE ANY DEVICES TO OVER RIDE
 SYSTEM. 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE WHAT APPEARS TO BE A MOTION DEVICE SHOWN ON
 PLANS WHICH DOES NOT SHOW ANY CONNECTION POINT.
 (HALLWAY AREA).
 ** PLEASE SEE THE DETAIL PROVIDED FOR THE CONNECTION OF
 EMERGENCY AND EXIT LIGHTS. THE NOTE MENTIONS TO CONNECT
 AHEAD OF THE SWITCHING DEVICE; HOWEVER THE EM/EXT LTS
 AS SHOWN APPEAR TO BE SHOWN ON THE LOAD SIDE OF THE
 SWITCH IN DETAIL. PLEASE KNOW THAT THIS IS SOMETHING
 THAT IS COMMON AND SHOULD BE KNOWN, HOWEVER PLEASE KNOW
 THAT SINCE THE IMPLEMENTATION OF CHAPTER 13 OF THE FBC,
 THE AHJ HAS HAD NUMEROUS SITUATIONS WHERE THE EMERGENCY
 AND EXIT LIGHTS ARE BEING CONNECTED ON THE LOAD SIDE OF
 THE OCCUPANCY SENSORS, THE LOAD OF SIDE OF THE LCP AND
 THE OVER RIDES DEVICES.PLEASE ADJUST DETAIL OR CALL
 THIS REVIEWER TO GO OVER THIS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FBC CHAPTER 13, 13-415.1.ABC.1.1, .1.2 AND
 .1.3.
 PLEASE PROVIDE AN AUTOMATED MEANS OF SHUTTING OFF
 LIGHTING AFTER NORMAL SCHEDULED HOURS.
 PLEASE PROVIDE SYSTEM OR METHODS OF CONTROL. PLEASE BE
 SURE THAT ALL DEVICE SYMBOLS ON PLANS CORRELATE WITH
 THE SYMBOL LEGEND PROVIDE.
 PLEASE INDICATE THE MAXIMUM TIMES ON ANY OVER RIDE
 DEVICES AS REQUIRED.
 (PLEASE KNOW A MAXIMUM 30MINS IS PERMITTED ON OCCUPANCY
 TYPE DEVICES AND 4HRS MAX ON TIMER TYPE OVER RIDES).
 PLEASE PROVIDE TIME OF SCHEDULING.
 ETC.
  
 11) NOTE:OK. *** NOT TO BE USED OR CONTAIN EQUIPMENT
 AS DEFINED FOR AN IT ROOM.
  
 12) NOTE: NO/OK, PLEASE SEE A NOTE HAS BEEN ADDED TO
 PLANS AND THE WALLS SEEM TO HAVE BEEN MOVED AS PER
 SCALE THE CLEARANCE FOR EACH PANEL AND DIFFERENT
 VOLTAGES SEEM TO BE MET.
 PLEASE SEE HOWEVER THAT NOW THAT THE RISER HAS BEEN
 REVISED (SEE NEW MAIN), THE LOCATION OF NEW EQUIPMENT
 ADDED TO RISER WHICH IS STATED AS EXISTING IS NOT
 LOCATED ON PLANS. PLEASE SEE THAT VERIFICATION FOR
 COMPLIANCE WITH 110.26 STILL CAN NOT BE CONFIRMED.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE AS SHOWN ON PLANS, THE ELECTRICAL EQUIPMENT
 BEING NOTED AS EXISTING AND BEING NOTED IN AN EXISTING
 ELECTRICAL CLOSET DOES NOT MEET CODE. PLEASE SEE THE
 MINIMUM CLEARANCES FOR ALL EQUIPMENT SHALL MEET
 110.26.
 THIS ARE SHALL NOT BE STORAGE ALSO.
  
 13) NOTE: OK, HOWEVER SEE NOTE ABOVE WITH RESPECT TO
 CLEARANCES.
  
 14) NOTE: OK, HOWEVER SEE NOTE #12 ABOVE WITH RESPECT
 TO CLEARANCES.
  
 ** NEW NOTES **
  
 15) NOTE: PLEASE CLARIFY THE NEW LOCATION OF THE NEW
 LCP WHICH HAS BEEN ADDED TO PLANS. PLEASE CLARIFY IF
 THIS TYPE OF PANEL CONTAINS OVER CURRENT PROTECTION OF
 ANY KIND OR NOT? PLEASE KNOW IF IT DOES, IT WILL BE
 REQUIRED TO BE RELOCATED PER 110.26, 408.7, 240.24(C)
 AND (D).
  
 16) NOTE: PLEASE CLARIFY CIRCUITING FROM THE PANEL H TO
 THE LCP AS THE THERE IS NO SCHEDULE ETC SHOWN FOR
 THIS.
 PLEASE KNOW THE PANEL DIRECTORIES SHOULD BE SPECIFIC TO
 THE ROOMS AND AREAS IN WHICH THEY CIRCUITED TO. IE;
 OFFICE 1 RECEPTS, BREAKRM RECEPTS, ETC
  
 17) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 DESIGN PROFESSIONALS AND REPEAT COMMENTS FOR CODE
 COMPLIANCE. THIS IS ONLY A NOTICE GIVEN AT THIS TIME.
 ONE SET OF PLANS MAY BE RETAINED BY THE OFFICE AT THIS
 TIME.
  
 18) NOTE: PLEASE SEE THAT FEES OF $2.397.60 ARE DUE TO
 VALUE FOR SCOPE OF WORK ADJUSTMENT.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-12-17 Cont ID  
Sent By dpalmer Date 2006-12-17 Time 13:38 Rev Time 0.00
Received By dpalmer Date 2006-12-17 Time 12:41 Sent To  
Notes
2006-12-17 13:42:19*** UNSAT ***
  
 TD AMERITRADE
  
 ** PLEASE SEE COMMENTS BELOW ARE IN NO WAY ALL POSSIBLE
 COMMENTS FOR THE ISSUANCE AS SOME ITEMS NOT SUBMITTED
 OR CLARIFIED ON PLANS CAN BE REVIEWED FOR CODE
 COMPLIANCE AT THIS TIME.
 PLEASE KNOW THERE MAY BE COMMENTS ON THE FOLLOWING
 REVIEW BASED ON PLANS SUBMITTED AND POSSIBLE CHANGES
 MADE IN THE DESIGNS ETC.
  
 1) NOTE: PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS
 FOR ARCHITECT AND ARCHITECTURAL FIRM AS REQUIRED UNDER
 FLORIDA ADMINISTRATIVE CODE 61G1-16.004 AND FLORIDA
 STATUTES 481.219
 PLEASE SEE MISSING FIRM LICENSE NUMBER ALSO KNOWN AS
 THE CERTIFICATE OF AUTHORIZATION NUMBER.
 PLEASE SEE MISSING THE PRINTED NAME AND LICENSE NUMBER
 OF THE ARCHITECT OF RECORD.
 ** THIS INFORMATION IS REQUIRED FOR ALL SHEETS AND FOR
 ALL TRADES WHETHER OR NOT COMMENT IS MADE BY OTHER
 TRADE REVIEWER(S).
  
 2) NOTE: PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS
 FOR ENGINEER AND ENGINEERING FIRM AS REQUIRED UNDER
 FLORIDA ADMINISTRATIVE CODE 61G15-23.002 AND FLORIDA
 STATUTES 471.023.
 PLEASE SEE MISSING FIRM LICENSE NUMBER ALSO KNOWN AS
 THE CERTIFICATE OF AUTHORIZATION NUMBER.
 PLEASE SEE MISSING THE PRINTED NAME AND LICENSE NUMBER
 OF THE ENGINEER OF RECORD.
 ** THIS INFORMATION IS REQUIRED FOR ALL SHEETS AND FOR
 ALL TRADES WHETHER OR NOT COMMENT IS MADE BY OTHER
 TRADE REVIEWER(S).
  
 3) NOTE: PLEASE SEE ONLY ONE SET OF THE PLANS SUBMITTED
 ARE SIGNED AND SEALED BY THE ENGINEER OF RECORD. PLEASE
 SEE FAC 61G15-23.002 WHICH REQUIRED BOTH SETS AND ALL
 DOCUMENTS TO BE SIGNED, DATED AND SEALED.
  
 4) NOTE: PLEASE SEE BOTH THE ARCHITECTURAL AND
 ENGINEERING SHEETS WERE NOT DATED BY THE DESIGN
 PROFESSIONALS WHEN SIGNED AND SEALED AS REQUIRED IN
 SECTIONS AS NOTED ABOVE.
 FS 481, 471, FAC 61G15-23.002, 61G1-16.004.
 THIS IS REQUIRED OF ALL SHEETS AND TRADES.
  
 5) NOTE: PLEASE SEE ENERGY CALCULATIONS SUBMITTED SHALL
 BE SIGNED, DATED AND SEALED BY THE DESIGNER/ENGINEER
 RESPONSIBLE. PLEASE ALSO SEE OTHER COMMENTS BASED ON
 THESE SHEETS.
 PLEASE ALSO SEE SECTION ON THE ENERGY CALCULATIONS
 WHICH REQUIRES THE OWNER/AGENT TO ALSO SIGN.
  
 6) NOTE: PLEASE SEE THAT ALL OF THE FOLLOWING RELEVANT
 CODES SHALL BE STATED ON SAID PLANS. PLEASE KNOW,
 STATEMENTS WHICH MENTIONS "LATEST EDITION" SHALL NOT BE
 MADE AS CODE CHANGES AND DATE SUBMITTED DICTATE WHICH
 CODES PROJECT IS UNDER AND THE "LATEST ADOPTED EDITION"
 AT TIME OF APPLICATION MAY NOT BE RELEVANT.
 PLEASE SEE THE FOLLOWING SHALL BE LISTED AT A MINIMUM.
 PLEASE ALSO SEE ANY CODES WHICH MAY BE STATED FROM
 OTHER TRADES.
 2002 NFPA-70 (NEC), 2002 NFPA-72, 2003 NFPA-101 AND THE
 2004 FBC. THIS SHALL BE STATED ON THE ELECTRICAL PLANS
 ALSO.
  
 7) NOTE: PLEASE SEE MINIMUM FIRE ALARM PLANS SHOWING
 LAYOUT OF NEW OR EXISTING DEVICES MEETING THE 2004 FBC
 AND 2002 NFPA-72 SHALL BE SUBMITTED. PLEASE KNOW, EVEN
 AS SCOPE OF WORK IS REQUIRED UNDER SEPARATE PLANS AND
 PERMIT THE BASE SYSTEM SHALL BE SHOWN IN BASE BUILD OUT
 PLANS.
 PLEASE INDICATE NEW OR EXISTING HORN AND STROBES
 MEETING 2004 FBC 11-4.28.1,.2.3(4).
 PLEASE SEE .3(4) WHICH REQUIRE A MINIMUM OF 75 CANDELAS
 WHICH IS ABOVE THE MINIMUMS REQUIRED IN NFPA-72. FBC
 ADMIN SECTION 106.1.2, 106.1.1.1
  
 8) NOTE: PLEASE SEE THE TWO BATH ROOMS SHALL INDICATE A
 BATTERY BACK UP FIXTURE OF SOME SORT TO MEET NFPA-101
 7.8, 7.9.
 PLEASE SEE POSSIBLE COMMENTS FROM FIRE MARSHAL'S OFFICE
 ALSO.
  
 9) NOTE: PLEASE SEE ENERGY CALCULATIONS SUBMITTED DO
 NOT CORRELATE WITH THE PLANS SUBMITTED. PLEASE SEE THE
 NUMBER OF FIXTURES AND WATTAGE DO NOT MATCH. THERE IS A
 SUBSTANTIAL DIFFERENCE.
 PLEASEFBC 2004 13-415.2..ABC.1, AND PLEASE INDICATE
 THE MAXIMUM LIGHTING POWER DENSITIES.
 PLEASE KNOW, BASED ON METHOD "A" THIS WILL NOT GIVE YOU
 THE CORRECT INFORMATION AS NEEDED AS THE SQ FT WILL BE
 ENTERED UNDER 5K SQ FT.
 PLEASE ALSO SEE THE AREAS WHERE CONTROL MENTIONS
 MANUAL, INSTEAD OF THE REQUIRED AUTO SHUT OFF. PLEASE
 SEE THE FOLLOWING COMMENT.
  
 10) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.1.ABC.1.1,
 .1.2 AND .1.3.
 PLEASE PROVIDE AN AUTOMATED MEANS OF SHUTTING OFF
 LIGHTING AFTER NORMAL SCHEDULED HOURS.
 PLEASE PROVIDE SYSTEM OR METHODS OF CONTROL. PLEASE BE
 SURE THAT ALL DEVICE SYMBOLS ON PLANS CORRELATE WITH
 THE SYMBOL LEGEND PROVIDE.
 PLEASE INDICATE THE MAXIMUM TIMES ON ANY OVER RIDE
 DEVICES AS REQUIRED.
 (PLEASE KNOW A MAXIMUM 30MINS IS PERMITTED ON OCCUPANCY
 TYPE DEVICES AND 4HRS MAX ON TIMER TYPE OVER RIDES).
 PLEASE PROVIDE TIME OF SCHEDULING.
 ETC.
  
 11) NOTE: PLEASE SEE THE ROOM BEING NOTED AS THE "TECH
 ROOM" SEEMS TO POSSIBLY MEET CLASSIFICATION OF AN "IT"
 ROOM AS STATED IN NFPA-75 CHAPTER 2. PLEASE CLARIFY USE
 OF ROOM AND EQUIPMENT BEING INSTALLED. AS THE BUSINESS
 AND USE MOST CERTAINLY DOES INVOKE POSSIBLY "IT" ROOM
 REQUIREMENTS.
 PLEASE SEE CONSTRUCTION OF WALLS, REQUIREMENTS FOR
 DISCONNECTION OF POWER, AND POSSIBLE FIRE DAMPERS MAY
 BE REQUIRED.
 PLEASE SEE NFPA-75, AND NFPA-70 (NEC) 645.
  
 12) NOTE: PLEASE SEE AS SHOWN ON PLANS, THE ELECTRICAL
 EQUIPMENT BEING NOTED AS EXISTING AND BEING NOTED IN AN
 EXISTING ELECTRICAL CLOSET DOES NOT MEET CODE. PLEASE
 SEE THE MINIMUM CLEARANCES FOR ALL EQUIPMENT SHALL MEET
 110.26.
 THIS ARE SHALL NOT BE STORAGE ALSO.
  
 13) NOTE: PLEASE SEE THE CONDUCTORS AS SHOWN ON THE
 SECONDARY SIDE OF THE TRANSFORMER DO NOT MEET 310.16,
 AND 240.21C FOR THE RATINGS REQUIRED. PLEASE SEE THE
 NEXT COMMENT AS THE CONDUCTORS ON THE SECONDARY SIDE OF
 THE TRANSFORMER ARE REQUIRED TO TERMINATE IN OVER
 CURRENT PROTECTION.
 PLEASE SEE TAP RULES.
  
 14) NOTE: PLEASE SEE 408.16, 240.21 AS NOTED ABOVE,
 PANEL AS SHOWN ON RISER INDICATES THIS PANEL BEING OF
 MLO, WITH NO MCB. PLEASE VERIFY THIS AT THE JOB-SITE.
 PLEASE KNOW IF A MCB( MAIN CIRCUIT BREAKER) IS NOT
 LOCATED ON THE SECONDARY SIDE OF THE TRANSFORMER ONE
 WILL BE REQUIRED AND THE OVER CURRENT PROTECTION WILL
 NOT ONLY BE REQUIRED TOLIMIT THE LOAD ON THE
 CONDUCTORS AS SHOWN, IT WILL ALSO BE REQUIRED TO BE
 SIZED PER THE LOAD.
 240.4, 310.16
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-01-24 Cont ID  
Sent By mawillia Date 2007-01-24 Time 11:42 Rev Time 0.00
Received By mawillia Date 2007-01-24 Time 11:42 Sent To  
Notes
2007-01-24 11:45:02*****APPROVED*****
  
  
 ALL COMMENTS FROM PREVIOUS FIRE PLAN REVIEWS HAVE BEEN
 ADDRESSED.SHEETS E-1 AND FA-1 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-01-17 Cont ID  
Sent By mawillia Date 2007-01-17 Time 16:41 Rev Time 0.00
Received By mawillia Date 2007-01-17 Time 16:41 Sent To  
Notes
2007-01-17 17:00:05*****UNSAT*****
  
 THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN
 REVIEW (12/21/2006) STILL NEED TO BE ADDRESSED:
  
  
 6.SHOW THE SUITE NUMBER FOR THIS TENANT SPACE ON THE
 PROPER ELEVATION.AS PER WEST PALM BEACH CODE, NUMBERS
 SHALL BE NO LESS THAN 3" IN HEIGHT AND 1" IN WIDTH.
 ADD TO PLAN SHEET A5 ON THE APPROPIATE EXTERIOR
 ELEVATION.
  
 8.INDICATE ON THE PLANS THE LOCATION OF THE FIRE
 PROTECTION SYSTEMS (I.E. FIRE SPRINKLERS, SMOKE
 DETECTORS, ETC.) AND WHETHER THE LISTED SCOPE OF WORK
 WILL AFFECT THEIR OPERATION.PROVIDE A LAYOUT OF THE
 SPRINKLER SYSTEM.RECTIFY PLAN SHEET FA-1 IN REGARDS
 TO STROBES CANDELAS MINIMUM (SEE ELECTRICAL COMMENT
 #7)
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 SHEET INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-12-21 Cont ID  
Sent By mawillia Date 2006-12-21 Time 15:50 Rev Time 0.00
Received By mawillia Date 2006-12-21 Time 15:50 Sent To  
Notes
2006-12-21 16:49:08*****DENIED*****
  
  
  
 1.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE
 PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION SHALL COMPLY WITH NFPA 241.
  
 3.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID
 PROPERTY OR VICINITY THEREOF (INCLUDING FIRE LANES).
  
 4. COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 5.PLEASE INDICATE THE MINIMUM INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILING IN TERMS OF CLASS
 A, B, OR C IN ACCORDANCE WITH NFPA 101.
  
 6.SHOW THE SUITE NUMBER FOR THIS TENANT SPACE ON THE
 PROPER ELEVATION.AS PER WEST PALM BEACH CODE, NUMBERS
 SHALL BE NO LESS THAN 3" IN HEIGHT AND 1" IN WIDTH.
  
 7.PROVIDE A LIFE SAFETY PLAN SHEET TO INCLUDE ALL
 COMMON PATHS OF TRAVEL TO EXITS AND TO INCLUDE FIRE
 EXTINGUISHER LOCATIONS.
  
 8.INDICATE ON THE PLANS THE LOCATION OF THE FIRE
 PROTECTION SYSTEMS (I.E. FIRE SPRINKLERS, SMOKE
 DETECTORS, ETC.) AND WHETHER THE LISTED SCOPE OF WORK
 WILL AFFECT THEIR OPERATION.
  
 9.IF THE FIRE ALARM AND/OR FIRE SPRINKLER SYSTEM
 IS/ARE MODIFIED DUE TO THE SCOPE OF WORK, SEPARATE
 PERMIT AND PLANS WILL BE REQUIRED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 SHEET INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-03-07 Cont ID  
Sent By ptjomsto Date 2007-03-07 Time 10:32 Rev Time 0.00
Received By ptjomsto Date 2007-03-07 Time 10:32 Sent To  
Notes
2007-03-07 10:33:42REV/MECH GIVEN TO HAROLD MOSER

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-01-23 Cont ID  
Sent By dpalmer Date 2007-01-23 Time 08:24 Rev Time 0.00
Received By dpalmer Date 2007-01-23 Time 08:24 Sent To  
Notes
2007-01-23 08:25:11TO BOBBOARD SPACE #7

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-01-13 Cont ID  
Sent By adarroug Date 2007-01-13 Time 13:41 Rev Time 0.00
Received By adarroug Date 2007-01-13 Time 13:41 Sent To  
Notes
2007-01-17 09:03:28TO "BOB"#16
2007-01-13 13:41:49WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-12-28 Cont ID  
Sent By jleech Date 2006-12-28 Time 13:47 Rev Time 0.00
Received By jleech Date 2006-12-01 Time 14:24 Sent To  
Notes
2006-12-17 12:41:33TO BOB BOARD SPACE #16, B, F, M, E, P
2006-12-01 14:24:19WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-03-07 Cont ID  
Sent By hmoser Date 2007-03-07 Time 11:19 Rev Time 0.00
Received By hmoser Date 2007-03-07 Time 11:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-02-21 Cont ID  
Sent By hmoser Date 2007-02-21 Time 12:50 Rev Time 0.00
Received By hmoser Date 2007-02-21 Time 12:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-02-12 Cont ID  
Sent By hmoser Date 2007-02-12 Time 14:34 Rev Time 0.00
Received By hmoser Date 2007-02-12 Time 14:34 Sent To  
Notes
2007-02-13 07:09:43PLAN DENIED
 MARK DUCT SIZES ON MARKED DUCT ON PLANS
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-01-17 Cont ID  
Sent By tgordon Date 2007-01-17 Time 13:37 Rev Time 0.40
Received By tgordon Date 2007-01-17 Time 13:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-12-20 Cont ID  
Sent By tgordon Date 2006-12-20 Time 08:23 Rev Time 0.45
Received By tgordon Date 2006-12-20 Time 08:23 Sent To  
Notes
2006-12-20 08:25:24*** DENIED ***
 1) SEE ELECTRICAL REVIEW NOTES 1, 2, 3, 4, AND 5,
 PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-01-18 Cont ID  
Sent By jleech Date 2007-01-18 Time 14:05 Rev Time 0.00
Received By jleech Date 2007-01-18 Time 14:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-12-28 Cont ID  
Sent By jleech Date 2006-12-28 Time 13:51 Rev Time 0.00
Received By jleech Date 2006-12-28 Time 13:51 Sent To  
Notes
2006-12-28 14:02:57DENIED;
 1.PLEASE SEE ELECTRICAL PLAN REVIEW NOTES, 1, 2, 3, &
 4.
 2. PAGE P-1 SANITARY RISER DIAGRAM; THE TWO SINKS TO BE
 REMOVED ARE NOT SHOWN ON THE DEMO PLAN. PLEASE SHOW ON
 DEMO PAGE. ADD NOTE TO PLAN, NO DEAD ENDS PERMITED IN
 SANITARY DRAINAGE SYSTEM. SECTION 704.5.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved