Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-12-28 Cont ID  
Sent By mperson Date 2006-12-28 Time 14:09 Rev Time 0.33
Received By mperson Date 2006-12-28 Time 14:09 Sent To PC
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-12-07 Cont ID  
Sent By mperson Date 2006-12-07 Time 16:28 Rev Time 0.44
Received By mperson Date 2006-12-07 Time 16:28 Sent To PC
Notes
2006-12-07 16:54:01DENIED
 REFERENCE: FBC-2004 FUEL GAS AND FBC-2004 CHAPTER 1
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN
 REVIEW TO MEET CODE COMPLIANCE:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: NOT ALL CORRESPONDING LENGTHS ARE INDICATED FOR
 THE INDICATED CUT SECTIONS.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 NOTE: NOT ALL PIPE MATERIALS OR SIZES ARE INDICATED ON
 DRAWING.
  
 3. PLEASE INDICATE THE TYPE OF GAS, (LP OR NATURAL) ON
 THE DRAWING.
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: IF THERE IS A CHANGE IN THE CORRESPONDING LENGTHS
 FROM COMMENT 1, PLEASE ADJUST THE LONGEST LENGTH ON THE
 RESUBMITTAL.
  
 5. PLEASE INDICATE THE DELIVERY PRESSURE (PSI) PER
 FBC-2004 FUEL GAS CODE SEC. 402.2 NATURAL GAS SPECIFY
 .5PSI OR 2 PSI ON THE DRAWINGS.
  
  
 6. IF DELIVERY PRESSURE IS 2PSI PLEASE SUBMIT
 MANUFACTURE SHEETS FOR MP REGULATORS TO VERIFY
 COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 7. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-12-19 Cont ID  
Sent By adarroug Date 2006-12-19 Time 10:48 Rev Time 0.00
Received By adarroug Date 2006-12-19 Time 10:48 Sent To G
Notes
2006-12-19 10:48:48TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-12-07 Cont ID  
Sent By mperson Date 2006-12-07 Time 16:54 Rev Time 0.00
Received By mperson Date 2006-12-01 Time 11:11 Sent To  
Notes
2006-12-01 11:11:51TO "G" BOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved