Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-03-27 Cont ID  
Sent By tgordon Date 2007-03-27 Time 16:32 Rev Time 0.25
Received By tgordon Date 2007-03-27 Time 16:32 Sent To  
Notes
2007-03-27 16:33:39*** PROVISO ***
 1) BALANCED RETURN AIR TO COMPLY WITH 2004 FBC/R
 M1602.4.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-12-05 Cont ID  
Sent By tgordon Date 2006-12-05 Time 16:39 Rev Time 0.30
Received By tgordon Date 2006-12-05 Time 16:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-12-01 Cont ID  
Sent By tgordon Date 2006-12-01 Time 16:01 Rev Time 0.25
Received By tgordon Date 2006-12-01 Time 16:01 Sent To  
Notes
2006-12-01 16:04:26*** DENIED ***
 1) RETURN AIR TRANSFER DUCTS ARE TO SMALL.
 BALANCED RETURN AIR.
 MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 2)ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN. PER FBC 104.2.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.