Plan Review Details - Permit 06111069
Plan Review Stops For Permit 06111069
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-04-03 Cont ID  
Sent By kconrad Date 2007-04-03 Time 18:54 Rev Time 0.00
Received By kconrad Date 2007-04-03 Time 18:44 Sent To I
Notes
2007-04-03 18:56:17REVIEWED ENGINEERING SUBMITTAL LETTER REFERENCING
 MANSARD TRUSS FRAMING REPAIR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-01-10 Cont ID  
Sent By rmcdouga Date 2007-01-10 Time 06:35 Rev Time 0.00
Received By rmcdouga Date 2007-01-10 Time 06:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-01-08 Cont ID  
Sent By rmcdouga Date 2007-01-08 Time 17:38 Rev Time 0.00
Received By rmcdouga Date 2007-01-08 Time 17:38 Sent To  
Notes
2007-01-08 17:38:26DENIED BY BUILDING
  
 1) THE TRUSS ENGINEER IS REQUIRED TO PERSONALLY SIGN
 THE TRUSS DRAWINGS. A SIGNATURE STAMP OR COPIED
 SIGNATURE IS NOT ACCEPTABLE. SEE FAC 61G15-23.002.SEE
 NOTE #4 FROM FIRST REVIEW.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-12-20 Cont ID  
Sent By rmcdouga Date 2006-12-20 Time 14:59 Rev Time 0.00
Received By rmcdouga Date 2006-12-20 Time 14:59 Sent To  
Notes
2006-12-20 15:00:41DENIED BY BUILDING
  
 1)SUBMIT TWO SETS OF SIGNED , SEALED AND DATED
 ENGINEERING FOR EACH PERMIT. THE ENGINEER IS REQUIRED
 TO SPECIFY THE WIND DESIGN DATA FOR THIS WORK. SEE FBC
 1603.1.4.
  
 2) THE ROOF PITCH OF THE NEW TRUSSES IS SPECIFIED AS
 3/12. THIS IS INCORRECT. THE ACTUAL SLOPE IS 48/12 FOR
 THE MANSARD.PLEASE CORRECT.
  
 3) THE TRUSS DRAWINGS SHOW THE TRUSSES IN A DIFFERENT
 ORIENTATION THAN THE DESIGN INDICATES.THE LOADING AND
 RESISTANCES WILL BE DIFFERENT WHEN INSTALLED AS
 SPECIFIED. PLEASE CORRECT.
  
 4) THE TRUSS ENGINEER IS REQUIRED TO PERSONALLY SIGN
 THE TRUSS DRAWINGS. A SIGNATURE STAMP OR COPIED
 SIGNATURE IS NOT ACCEPTABLE. SEE FAC 61G15-23.002.
  
 5) SUBMIT PRODUCT APPROVALS FOR THE TRUSS CONNECTORS.
 SEE FS 553.842 AND RULE 9B-72.
  
 6)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-01-04 Cont ID  
Sent By adarroug Date 2007-01-04 Time 11:22 Rev Time 0.00
Received By adarroug Date 2007-01-04 Time 11:22 Sent To B
Notes
2007-01-04 11:22:13TO "RMCDOUGAL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-12-20 Cont ID  
Sent By rmcdouga Date 2006-12-20 Time 15:00 Rev Time 0.00
Received By rmcdouga Date 2006-12-01 Time 13:58 Sent To  
Notes
2006-12-13 11:24:29TO "KCONRAD" DESK
2006-12-01 13:59:15TO "LMARTINEZ" DESK/PER "RBROWN"