Plan Review Details - Permit 06111067
Plan Review Stops For Permit 06111067
Review Stop AD ADDRESSING
Rev No 4 Status P Date 2007-05-16 Cont ID  
Sent By lursu Date 2007-05-16 Time 10:24 Rev Time 0.00
Received By lursu Date 2007-05-16 Time 10:24 Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 3 Status F Date 2007-05-16 Cont ID  
Sent By lursu Date 2007-01-03 Time 08:46 Rev Time 5.55
Received By jwitmer Date 2007-01-03 Time 08:46 Sent To PC
Notes
2007-01-03 08:50:22NEW PCN TO BE ISSUED BY PAPA USING THE UNITY OF TITLE
 OF THESE THREE PARCELS:74 43 43 06 12 000 0081 , 74 43
 43 06 12 000 0070 AND 74 43 43 06 12 000 0062 WILL BE
 THE LOWEST OF ALL .THE PERMIT IS ATTACHED TO UNIT #
 0001 UNDER PCN = 74 43 43 06 12 000 0062.THE NEW SITE
 ADDRESS FOR THIS NEW HOTEL IS 2437 METROCENTRE BLVD E
 .
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 OFFICE:822-1239
 E-MAIL:[email protected]
  

Review Stop AD ADDRESSING
Rev No 2 Status P Date 2007-01-02 Cont ID  
Sent By lursu Date 2007-01-02 Time 10:52 Rev Time 0.00
Received By lursu Date 2007-01-02 Time 10:52 Sent To  
Notes
2007-01-02 10:54:47THE UNITY OF TITLE WAS RECEIVED .A NEW PCN MUST BE
 ISSUED BY PAPA, UNTIL THEN THE PERMIT CAN BE ATTACHED
 TO UNIT # 0003 UNDER PCN = 74 43 43 06 12 000 0070 WITH
 2437 METRCOCENTRE BLVD E.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2006-12-04 Cont ID  
Sent By lursu Date 2006-12-04 Time 13:10 Rev Time 0.00
Received By lursu Date 2006-11-30 Time 13:46 Sent To PC
Notes
2006-12-04 13:10:47THE SURVEY MUST BE SUPPLIED ( PDF FORMAT CAN BE SEND )
 ARE BOTH PARCELS( PCN = 74434306120000081 ANDPCN =
 74434306120000070) INCLUDED IN THIS PROJECT?IF SO A
 UNITY OF TITLE IS REQUIRED.
 WAS AT THIS LOCATION A DIFFERENT LAYOUT WITH MULTIPLE
 BUILDINGS NUMBERED BLDG A THRU F ?TWO PERMITS ARE OPEN
 FOR BLDGS F & E UNDER THE PCN = ...0070
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 E-MAIL:[email protected]
2006-11-30 13:47:03NEEDS ADDRESS AND PCN # FOR THIS LOCATION

Review Stop B BUILDING (STRUCTURAL)
Rev No 26 Status P Date 2009-07-31 Cont ID  
Sent By jwitmer Date 2009-07-31 Time 08:53 Rev Time 0.55
Received By jwitmer Date 2009-07-31 Time 08:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 25 Status F Date 2009-06-25 Cont ID  
Sent By jwitmer Date 2009-06-25 Time 15:19 Rev Time 0.22
Received By jwitmer Date 2009-06-25 Time 15:03 Sent To PC
Notes
2009-06-25 15:26:14 
 BUILDING PLAN REVIEW
 PERMIT: 06111067
 ADD: 2437 METROCENTRE BLVD
 CONT: AUTOBUILDERS
 TEL: (561)310-7735
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SPRINGHILL SUITES BY MARIOTT
 FIVE STORY/ 130 UNITS
  
 PHASING PLAN: ZONING & LANDSCAPING PLANS FAILED
 BUILDING CAN NOT STAMP PLANS UNTIL OTHER TRADE
 APPROVAL.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 24 Status F Date 2009-04-16 Cont ID  
Sent By jwitmer Date 2009-04-16 Time 14:40 Rev Time 2.22
Received By jwitmer Date 2009-04-16 Time 14:40 Sent To  
Notes
2009-04-16 16:57:38 
 BUILDING PLAN REVIEW
 PERMIT: 06111067
 ADD: 2437 METROCENTRE BLVD
 CONT: AUTOBUILDERS
 TEL: (561)310-7735
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SPRINGHILL SUITES BY MARIOTT
 FIVE STORY/ 130 UNITS
  
 REVISIONS: I D DRAWINGS
  
 ACTION: DENIED
  
  
 1) PARADIGM DESIGN GROUP,IS MISSING THEIR CERTIFICATE
 OF AUTHORIZATION FOR THEIR COMPANY NAME. THE FLORIDA
 DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION
 INDICATES THERE BEING TWO EXPIRED LICENSES FOR THE
 PAST. 481.219 F.S. CERTIFICATE OF AUTHORIZATION. THE
 TITLE BLOCK FOR ANY SHEET BEARING THE NAME OF AN
 ARCHITECT PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL
 SERVICES, SHALL INCLUDE THE CERTIFICATE OF
 AUTHORIZATION NUMBER. ADD THE NUMBER TO EACH SHEET.
  
 2) THE INTERIOR DESIGNER IS TO SIGN, SEAL AND DATE WHEN
 PLANS WERE SEALED. FLORIDA ADMINISTRATIVE CODE
 61G1-16.004 (5) A SPACE FOR THE SIGNATURE AND THE DATE
 SEALED.
  
 3) PLEASE CORRECT SHEET ID0.01 CODES/ SAFETY.
 3A) PLANS STATE THE WRONG CODE & YEAR.
 3B) THE WRONG BUILDING TYPE TABLE 503
 3C) BUILDING HEIGTH NOT PROVIDED TABLE 503
 3D) STORIES, NOT PROVIDED. TABLE 503
  
 4) PLEASE PROVIDE DOCUMENTATION FOR CARPET IN VERTICAL
 EXITS, EXIT PASSAGEWAYS AND EXIT ACCESS CORRIDORS.
 804.5.1 MINIMUM CRITICAL RADIANT FLUX. NOT LESS THAN
 CLASS II IN GROUPS A, B, E, H, I- 4, M, R-1, R-2 AND S.
 IN ALL OTHER AREAS, THE INTERIOR FLOOR FINISH SHALL
 COMPLY WITH THE DOC FF-1 ???PILL TEST??? (CPSC 16 CFR,
 PART 1630).
 EXCEPTION: WHERE A BUILDING IS EQUIPPED THROUGHOUT WITH
 AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH
 SECTION 903.3.1.1, CLASS II MATERIALS ARE PERMITTED IN
 ANY AREA WHERE CLASS I MATERIALS ARE REQUIRED AND
 MATERIALS COMPLYING WITH DOC FF-1 ???PILL TEST??? (CPSC
 16 CFR, PART 1630) ARE PERMITTED IN ANY AREA WHERE
 CLASS II MATERIALS ARE REQUIRED.
  
 5) SHEET ID7.02 WALL COVERINGS PER TABLE 803.5 AND
 SECTION 803.1, PLEASE PROVIDE THE FLAME SPREAD INDEX
 AND SMOKE DEVELOPMENT FOR EACH TYPE OF WALL COVERING
 DEPENDING ON OCCUPANCY PROUPING.
  
 6) SHEET ID3.00 & ID3.01 PLEASE PROVIDE COMPLIANCE WITH
 11-5.1 GENERAL. EXCEPT AS SPECIFIED OR MODIFIED IN THIS
 SECTION, RESTAURANTS AND CAFETERIAS SHALL COMPLY WITH
 THE REQUIREMENTS OF SECTION 11-4.1 TO SECTION 11-4.35.
 WHERE FIXED TABLES (OR DINING COUNTERS WHERE FOOD IS
 CONSUMED BUT THERE IS NO SERVICE) ARE PROVIDED, AT
 LEAST 5 PERCENT, BUT NOT LESS THAN ONE, OF THE FIXED
 TABLES (OR A PORTION OF THE DINING COUNTER) SHALL BE
 ACCESSIBLE AND SHALL COMPLY WITH SECTION 11-4.32 AS
 REQUIRED IN SECTION 11-4.1.3(18). IN ESTABLISHMENTS
 WHERE SEPARATE AREAS ARE DESIGNATED FOR SMOKING AND
 NONSMOKING PATRONS, THE REQUIRED NUMBER OF ACCESSIBLE
 FIXED TABLES (OR COUNTERS) SHALL BE PROPORTIONALLY
 DISTRIBUTED BETWEEN THE SMOKING AND NONSMOKING AREAS.
 IN NEW CONSTRUCTION, AND WHERE PRACTICABLE IN
 ALTERATIONS, ACCESSIBLE FIXED TABLES (OR COUNTERS)
 SHALL BE DISTRIBUTED THROUGHOUT THE SPACE OR FACILITY.
  
 7) SHEET ID 5.01SECTION A1 DOES NOT PROVIDE AT WHAT
 HEIGTH THE COUNTER TOP WILL BE LOCATED. 11-5.5 FOOD
 SERVICE LINES.
 FOOD SERVICE LINES SHALL HAVE A MINIMUM CLEAR WIDTH OF
 36 INCHES (915 MM), WITH A PREFERRED CLEAR WIDTH OF 42
 INCHES (1065 MM) TO ALLOW PASSAGE AROUND A PERSON USING
 A WHEELCHAIR. TRAY SLIDES SHALL BE MOUNTED NO HIGHER
 THAN 34 INCHES (865 MM) ABOVE THE FLOOR (SEE FIGURE
 53). IF SELF-SERVICE SHELVES ARE PROVIDED, AT LEAST 50
 PERCENT OF EACH TYPE MUST BE WITHIN REACH RANGES
 SPECIFIED IN SECTIONS 11-4.2.5 AND 11-4.2.6.
 11-5.6 TABLEWARE AND CONDIMENT AREAS.
 SELF-SERVICE SHELVES AND DISPENSING DEVICES FOR
 TABLEWARE, DISHWARE, CONDIMENTS, FOOD AND BEVERAGES
 SHALL BE INSTALLED TO COMPLY WITH SECTION 11-4.2 (SEE
 FIGURE 54).
  
 8) SHEET ID 5.02 FRONT RECEPTION DESK DETAIL B1 & B2
 PLEASE PROVIDE COMPLIANCE WTIH 11-7.2 (2) (III) III)
 EQUIVALENT FACILITATION SHALL BE PROVIDED (E.G., AT A
 HOTEL REGISTRATION COUNTER, EQUIVALENT FACILITATION
 MIGHT CONSIST OF:
 (1) PROVISION OF A FOLDING SHELF ATTACHED TO THE MAIN
 COUNTER ON WHICH AN INDIVIDUAL WITH DISABILITIES CAN
 WRITE, AND
 (2) USE OF THE SPACE ON THE SIDE OF THE COUNTER OR AT
 THE CONCIERGE DESK, FOR HANDING MATERIALS BACK AND
 FORTH).
  ALL ACCESSIBLE SALES AND SERVICE COUNTERS SHALL BE ON
 AN ACCESSIBLE ROUTE COMPLYING WITH SECTION 11-4.3.
 (3) ASSISTIVE LISTENING DEVICES. RESERVED.
  
 9) SHEET ID6.00 SERIES ID6.11 & ID6.12 BOTH SHEETS ARE
 ACCESSIBLE ROOMS AND THE KITCHENETTE DOES NOT INDICATE
 THE HEIGTH OF THE COUNTER TOP.11-9.2 (7) REQUIRES
 COUNTER TOPS TO BE NO HIGHER THAN 34".
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 23 Status P Date 2009-04-10 Cont ID  
Sent By jwitmer Date 2009-04-10 Time 13:09 Rev Time 0.77
Received By jwitmer Date 2009-04-10 Time 13:09 Sent To  
Notes
2009-04-10 13:14:16 
 BUILDING PLAN REVIEW
 PERMIT: 06111067
 ADD: 2437 METROCENTRE BLVD
 CONT: AUTOBUILDERS
 TEL: (561)310-7735
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SPRINGHILL SUITES BY MARIOTT
 FIVE STORY/ 130 UNITS
  
 REVISON:
 AC101 SITE PLAN (2) ONE FOR EACH HOTEL SPRINGHILL
 SUITES AND FOR HOMEWOOD SUITES.
 E-001 & E-002 BLDG ONLY FOR LIGHT POLES AND EPA
 RATINGOF FIXTURES.
 ACTION: REVIEWED
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 22 Status F Date 2009-04-06 Cont ID  
Sent By jwitmer Date 2009-04-06 Time 09:44 Rev Time 0.77
Received By jwitmer Date 2009-04-06 Time 09:44 Sent To  
Notes
2009-04-06 09:54:38BUILDING PLAN REVIEW
 PERMIT: 06111067
 ADD: 2437 METROCENTRE BLVD
 CONT: AUTOBUILDERS
 TEL: (561)310-7735
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SPRINGHILL SUITES BY MARIOTT
 FIVE STORY/ 130 UNITS
  
 1ST REVIEW REVISION# 4
 ACTION: DENIED
 A101, A101A, AR101, AR101A, A401 & AR401
  
 THE ORIGINAL ISSUED PLANS INDICATED A 1 HR RATED WALL
 THAT SEPERATED THE LAUNDRY WORK ROOM, THE SALES OFFICE
 FROM THE LOBBY AREAS. THE LOBBY IS A CONTINUATION OF
 THE FIRE RATED CORRIDOR
 REQUIRED UNDER TABLE 1016.1 OCCUPANT LOADS SERVED
 GREATER THAN 30 WITH OR WITHOUT SPRINKLERS REQUIRES A 1
 HR FIRE SEPERATION WALL. 1016.5 CORRIDOR CONTINUITY
 DOES ALLOW THE FOYER, LOBBY TO BE PART OF THE CORRIDOR
 SEE EXCEPTION.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE
 APPLICABLE.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 21 Status P Date 2009-03-16 Cont ID  
Sent By jwitmer Date 2009-03-16 Time 08:23 Rev Time 1.55
Received By jwitmer Date 2009-03-16 Time 08:23 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 20 Status P Date 2009-01-07 Cont ID  
Sent By jwitmer Date 2009-01-07 Time 11:17 Rev Time 0.77
Received By jwitmer Date 2009-01-07 Time 11:17 Sent To PC
Notes
2009-01-07 11:24:51 
 BUILDING PLAN REVIEW
 PERMIT: 06111067
 ADD: 2437 METROCENTRE BLVD
 CONT: AUTOBUILDERS
 TEL: (561)310-7735
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SPRINGHILL SUITES BY MARIOTT
 FIVE STORY/ 130 UNITS
 ENERGY CALC REVISION REVIEW - OK
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 19 Status P Date 2008-12-11 Cont ID  
Sent By jwitmer Date 2008-12-11 Time 09:53 Rev Time 2.00
Received By jwitmer Date 2008-12-11 Time 09:53 Sent To  
Notes
2008-12-11 09:54:04ROOF : 08110439
  
 BUILDING PROVISO:
  
  
 ENERGY CALCULATIONS TO BE REVISED TO REFLECT THE R-10
 MINIMUM VALUE.
 CONTRACTOR ATOWN RISK. 13-103.1.2 CODE COMPLIANCE
 CERTIFICATION.
  
 THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL
 CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE
 CODE, AS PER SECTION 553.907, FLORIDA STATUTES, PRIOR
 TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR
 RENOVATION.
  
 IF, DURING THE BUILDING.S CONSTRUCTION OR RENOVATION,
 ALTERATIONS ARE MADE IN THE BUILDING?S DESIGN OR IN
 MATERIALS OR EQUIPMENT INSTALLED IN THE BUILDING WHICH
 WOULD DIMINISH ITS ENERGY PERFORMANCE, AN AMENDED COPY
 OF THE COMPLIANCE CERTIFICATION SHALL BE SUBMITTED TO
 THE BUILDING OFFICIAL ON OR BEFORE THE DATE OF FINAL
 INSPECTION BY THE BUILDING OWNER OR HIS OR HER LEGALLY
 AUTHORIZED AGENT.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 18 Status F Date 2008-11-21 Cont ID  
Sent By jwitmer Date 2008-11-21 Time 10:30 Rev Time 1.22
Received By jwitmer Date 2008-11-21 Time 10:30 Sent To PC
Notes
2008-11-21 10:48:53 
 BUILDING PLAN REVIEW
 PERMIT: 06111067
 ADD: 2437 METROCENTRE BLVD
 CONT: AUTOBUILDERS
 TEL: (561)310-7735
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SPRINGHILL SUITES BY MARIOTT
 FIVE STORY/ 130 UNITS
  
 REVISION# 4 :
 DENIED
  
 1) SHEET A-106 REVISION INDICATES THE DELETION OF THE
 OVERFLOW SCUPPERS AND ADDITIONAL OVERFLOW ROOF DRAINS,
 THERE ARE TWO ISSUES:
  
 1A) FOR OVERFLOW ROOF DRAINS ARE TO ACT AS AN OVERFLOW
 SCUPPER WOULD, BY BEING PLACED 2" TO 4" ABOVE THE ROOF.
 IF THIS IS A EMERGENCY OVERFLOW IT WOULD ONLY BE USED
 IF THE MAINDRAIN IS CLOGGED OR PLUGGED. 1503.4.3
  
 1B) THE SECOND ISSUE HAS TO DO WITH THE PLUMBING ASPECT
 OF THE NEW SECONDARY DRAIN BEING THE EMERGENCY
 OVERFLOW. I SPOKE WITH KEN THE PLUMBING REVIEWER ON
 THIS MATTER. THE PLANS O NOT INDICATE WHERE THE
 SECONDARY DRAIN TERMINATES, DOES IT TIE BACK INTO THE
 MAIN SYSTEM, A SEPERATE SYSTEM THAT CONTINUES TO GRADE
 OR DOES IT TRAVEL BENEATH THE ROOF DECK AND TERMINATE
 OVER A WINDOW OR IN THE WALL WHERE IF WATETR IS FLOWING
 OUT OF THE PIPE IT WOULD BE NOTICED BY THE PERSONNEL
 AND KNOW THERE IS A PROBLEM ? ON THE NEXT SUBMITTAL
 PLEASE PROVIDE BOTH THE ARCHITECTURAL SHEETS AS WELL AS
 THE PLUMBING SHEETS TO CORRELATE THE REVISION BETWEEN
 THE TRADES, THANKS FOR YOUR COOPERATION ON THIS MATTER.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 17 Status P Date 2008-10-01 Cont ID  
Sent By jwitmer Date 2008-10-01 Time 16:24 Rev Time 0.77
Received By jwitmer Date 2008-10-01 Time 16:24 Sent To  
Notes
2008-10-01 16:25:35 
 BUILDING PLAN REVIEW
 PERMIT: 06111067
 ADD: 2437 METROCENTRE BLVD
 CONT: AUTOBUILDERS
 TEL: (561)310-7735
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SPRINGHILL SUITES BY MARIOTT
 FIVE STORY/ 130 UNITS
  
 REVIEWED
  
 WINDOW SHOP DRAWINGS CHAPION GLASS
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 16 Status P Date 2008-10-01 Cont ID  
Sent By jwitmer Date 2008-10-01 Time 16:21 Rev Time 1.33
Received By jwitmer Date 2008-10-01 Time 16:21 Sent To  
Notes
2008-10-01 16:24:03 
 BUILDING PLAN REVIEW
 PERMIT: 06111067
 ADD: 2437 METROCENTRE BLVD
 CONT: AUTOBUILDERS
 TEL: (561)310-7735
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SPRINGHILL SUITES BY MARIOTT
 FIVE STORY/ 130 UNITS
  
 REVIEWED:
 REVISION# 3; A302, S-303, S-307 & A-502
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 15 Status P Date 2008-08-26 Cont ID  
Sent By jwitmer Date 2008-08-26 Time 13:49 Rev Time 0.00
Received By jwitmer Date 2008-08-26 Time 13:49 Sent To  
Notes
2008-08-26 11:16:29 
 BUILDING PLAN REVIEW
 PERMIT: 06111067
 ADD: 2437 METROCENTRE BLVD
 CONT: AUTOBUILDERS
 TEL: (561)310-7735
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SPRINGHILL SUITES BY MARIOTT
 FIVE STORY/ 130 UNITS
  
 REVISIONS H & J
  
 ACTION:REVIEWED
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 14 Status F Date 2008-08-25 Cont ID  
Sent By jwitmer Date 2008-08-25 Time 11:40 Rev Time 1.22
Received By jwitmer Date 2008-08-25 Time 11:40 Sent To PC
Notes
2008-08-25 12:05:17 
 BUILDING PLAN REVIEW
 PERMIT: 06111067
 ADD: 2437 METROCENTRE BLVD
 CONT: AUTOBUILDERS
 TEL: (561)310-7735
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SPRINGHILL SUITES BY MARIOTT
 FIVE STORY/ 130 UNITS
 ACTION:DENIED
  
 1) CHAMPION GLASS SHOP DRAWINGS- COVEER SHEET HAND
 WRITTEN BESAM AUTOMATIC SLIDDING DOORS ( WHICH WAS
 SUBMITTED AT TIME OF PERMIT). BUT THE NOA 06-1211.11 IS
 FOR NABCO AUTOMATIC SLIDDING DOORS.
 ALSO SEE SHEET 5 OF 8 INDICATING NABCO DOORS. PLEASE
 CORRELATE PLANS AND PRODUCT APPROVALS.
  
 2) PLEASE CORRELATE EITHER THE SHOP DRAWINGS TO REFLECT
 THE ARCHITECTURAL SHEETS OR JUST THE OPPOSITE. IF THE
 SHOP DRAWINGS ARE CORRECT THEN NEW A-201, A-201A, A-202
 , A-202A & A-605 WILL NEED TO BE REVISED. A200 SERIES
 DOES NOT INDICATE OPERABLE WINDOWS ABOVE THE FIRST
 FLOOR, A605 INDICATES WITH A NOTE OPERABLE WINDOWS BUT
 IDENTIFIED ON THE A-200 SERIES SHEETS.
  
 3) SHOP DRAWING WINDOW A-8 IS INDICATED WITH AND
 WITHOUT A PTC UNIT WHERE AS A-605 ONLY SHOWS W-8 WITH A
 PTAC UNIT.
  
 PLEASE CORRELATE ALL PLANS TO REFLECT THE SAME MODEL OF
 WINDOW AND OR WINDOW AND PTAC UNIT.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 13 Status P Date 2008-08-25 Cont ID  
Sent By jwitmer Date 2008-08-25 Time 11:38 Rev Time 3.33
Received By jwitmer Date 2008-08-25 Time 11:38 Sent To  
Notes
2008-08-25 11:40:00 
 BUILDING PLAN REVIEW
 PERMIT: 06111067
 ADD: 2437 METROCENTRE BLVD
 CONT: AUTOBUILDERS
 TEL: (561)310-7735
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SPRINGHILL SUITES BY MARIOTT
 FIVE STORY/ 130 UNITS
  
 NEW PRODUCT APPROVALS REVIEWED
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status P Date 2008-07-31 Cont ID  
Sent By jwitmer Date 2008-07-31 Time 14:44 Rev Time 1.22
Received By jwitmer Date 2008-07-31 Time 14:44 Sent To PC
Notes
2008-07-31 14:45:01PRE-CAST SHOP DRAWINGS- SPRINGHILL SUITES

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status F Date 2008-07-03 Cont ID  
Sent By jwitmer Date 2008-07-03 Time 16:34 Rev Time 0.77
Received By jwitmer Date 2008-07-03 Time 16:34 Sent To PC
Notes
2008-07-03 16:38:30 
 BUILDING PLAN REVIEW
 PERMIT: 06111067
 ADD: 2437 METROCENTRE BLVD
 CONT: AUTOBUILDERS
 TEL: (561)310-7735
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SPRINGHILL SUITES BY MARIOTT
 FIVE STORY/ 130 UNITS
  
 SUBMITTAL ;DENIED
 PRECAST CONCRETE PLANK SHOP DRAWINGS:
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC... SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2008-06-03 Cont ID  
Sent By jwitmer Date 2008-06-03 Time 07:48 Rev Time 0.88
Received By jwitmer Date 2008-06-03 Time 07:48 Sent To PC
Notes
2008-06-03 07:50:43 
 BUILDING PLAN REVIEW
 PERMIT: 06111067
 ADD: 2437 METROCENTRE BLVD
 CONT: AUTOBUILDERS
 TEL: (561)310-7735
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SPRINGHILL SUITES BY MARIOTT
 FIVE STORY/ 130 UNITS
  
 STRUCTURAL STEEL SHOP DRAWINGS REVIEW:
  
 REVIEWED

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status F Date 2008-06-02 Cont ID  
Sent By jwitmer Date 2008-06-02 Time 17:07 Rev Time 1.33
Received By jwitmer Date 2008-06-02 Time 17:07 Sent To PC
Notes
2008-06-02 17:14:42 
 BUILDING PLAN REVIEW
 PERMIT: 06111067
 ADD: 2437 METROCENTRE BLVD
 CONT: AUTOBUILDERS
 TEL: (561)310-7735
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SPRINGHILL SUITES BY MARIOTT
 FIVE STORY/ 130 UNITS
  
 PRE-CAST CONCRETE PLANK SHOP DRAWING REVIEW
 ACTION: DENIED
  
 PRESTRESS HOLLOW CORE DESIGN CALCULATIONS:
 61G15-23.002(2)FL. ADMIN. CODE. A COVER SHEET OR
 INDEX SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED
 AND THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF
 THE PRODUCTION & PREPARATION OF EACH SECTION OF THE
 ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION
 ON THE COVER SHEET OR INDEX.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2008-05-28 Cont ID  
Sent By jwitmer Date 2008-05-28 Time 15:28 Rev Time 2.22
Received By jwitmer Date 2008-05-28 Time 15:28 Sent To  
Notes
2008-05-28 15:40:02BUILDING PLAN REVIEW
 PERMIT: 06111067
 ADD: 2437 METROCENTRE BLVD
 CONT: AUTOBUILDERS
 TEL: (561)310-7735
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SPRINGHILL SUITES BY MARIOTT
 FIVE STORY/ 130 UNITS
  
 REVISION "H"REVIEW
 ACTION:REVIEWED
  
 SHEETS:
 A-100
 A-101
 AR101
 AR101A
 AR102
 AR102A
 AR103
 AR103A
 AR104
 AR104A
 AR105
 AR105A
 A-301
 A-401
 A-411
 A-412
 AR-401
 AR-402
 AR411
 AR412
 A-604
 A-801 PROVISO: MICROWAVES IN ACCESSIBLE UNITS NEED TO
 MEET THE REACH RANGES 1-4.2.5 & 11-42..6 & 11.27.3
 A-802
 A-802
 A-803
 A-806 DETAIL# 4 PROVISO: MICROWAVES IN ACCESSIBLE UNITS
 NEED TO MEET THE REACH RANGES 1-4.2.5 & 11-42..6 &
 11.27.3
 A-807
 A-813
 A-814
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2008-05-28 Cont ID  
Sent By jwitmer Date 2008-05-28 Time 14:18 Rev Time 5.55
Received By jwitmer Date 2008-05-28 Time 14:18 Sent To  
Notes
2008-05-28 15:27:24 
 BUILDING PLAN REVIEW
 PERMIT: 06111067
 ADD: 2437 METROCENTRE BLVD
 CONT: AUTOBUILDERS
 TEL: (561)310-7735
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SPRINGHILL SUITES BY MARIOTT
 FIVE STORY/ 130 UNITS
  
 REVISION "H"REVIEW
 ACTION: DENIED
 SHEETS:
 1) A-101A : ELEVATOR LOBBY REVISION, DELTA H,DETAIL#
 7/ A702THIS REVISION IS NOT FOUND IN THE REVISION SET
 OF PLANS? ADDITIONAL INFORMATION REQUIRED, 106.1.2.
  
 2) A-102 A-102ELEVATOR LOBBY 234 INDICATES A GUEST
 PHONE NICHE, PLEASE PROVIDE COMPLIANCE WITH 11-4.31.2-
 11-4.31.9.
  
 3) A-102A ELEVATOR LOBBY 234 INDICATES A GUEST PHONE
 NICHE, PLEASE PROVIDE COMPLIANCE WITH 11-4.31.2-
 11-4.31.9.
  
 4) A-103 ELEVATOR LOBBY 334 INDICATES A GUEST PHONE
 NICHE, PLEASE PROVIDE COMPLIANCE WITH 11-4.31.2-
 11-4.31.9.
  
 5) A-103A ELEVATOR LOBBY 334 INDICATES A GUEST PHONE
 NICHE, PLEASE PROVIDE COMPLIANCE WITH 11-4.31.2-
 11-4.31.9.
  
 6) A104) ELEVATOR LOBBY 434 INDICATES A GUEST PHONE
 NICHE, PLEASE PROVIDE COMPLIANCE WITH 11-4.31.2-
 11-4.31.9.
  
 7) A-105 ELEVATOR LOBBY 534 INDICATES A GUEST PHONE
 NICHE, PLEASE PROVIDE COMPLIANCE WITH 11-4.31.2-
 11-4.31.9.
  
 8) A-105A ELEVATOR LOBBY 534 INDICATES A GUEST PHONE
 NICHE, PLEASE PROVIDE COMPLIANCE WITH 11-4.31.2-
 11-4.31.9.
  
 9) A-402 THE REFRIGARANT LINE WALLS DO NOT INDICATE THE
 TYPE OF WALL DESIGNATION. SEE ROOM # * 12 WILL NEED TO
 BE A 1 HR RATED WALL WITH A SOUND COEFFIICENT OF 50
 PLEASE PROVIDE WALL TYPE TAG.
 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 10) PROVISO: A-801 THE MICROWAVE WILL NEED TO MEET THE
 REACH RANGE REQUIREMENTS OF 11-4.2.5OR 11-4.2.6 AND
 11-4.27.3 CONTROLS AND OPERATING MECHANISMS HEIGTH
 REQUIREMENTS WITHIN THE HANDICAPPED UNITS.
  
 11) A-805 REGISTRATION STATION PLEASE PROVIDE DETAIL
 INDICATING COMPLIANCE WITH 11-7.2 (2) .
  
 12) A-806DETAIL# 4 FOR HANDICAPPED ACCESSIBLE ROOMS,
 THE MICROWAVE WILL NEED TO MEET THE REACH RANGE
 REQUIREMENTS OF 11-4.2.5OR 11-4.2.6 AND 11-4.27.3
 CONTROLS AND OPERATING MECHANISMS HEIGTH REQUIREMENTS.
  
 13) A-808 & A-811 TELEPHONES WILL NEED TO MEET THE
 REQUIREMERNTS OF 11-4.31.1- 11-4.31.9.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2008-03-14 Cont ID  
Sent By jwitmer Date 2008-03-14 Time 09:34 Rev Time 0.77
Received By jwitmer Date 2008-03-14 Time 09:34 Sent To  
Notes
2008-03-14 09:36:16 
 BUILDING PLAN REVIEW
 PERMIT: 06111067
 ADD: 2437 METROCENTRE BLVD
 CONT: AUTOBUILDERS
 TEL: (561)310-7735
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SPRINGHILL SUITES BY MARIOTT
 FIVE STORY/ 130 UNITS
  
 4THREVIEW
 ACTION: REVIEWED
  
  
 1-29D) COMPLIED
  
  
 BUILDING PROVISO:ROOF ASSEMBLIES
 FLAT ROOFS- CARLISLE ROOFINGWILL REQUIRE SEPERATE
 REVIEW AND PERMIT , SHOP DRAWINGS ARE TO BE PREPARED
 WITH ASSOCIATED PRESSURES.
  
  
 31-35) COMPLIED.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2008-03-11 Cont ID  
Sent By jwitmer Date 2008-03-11 Time 10:40 Rev Time 3.55
Received By jwitmer Date 2008-03-11 Time 10:40 Sent To  
Notes
2008-03-11 10:48:34 
 BUILDING PLAN REVIEW
 PERMIT: 06111067
 ADD: 2437 METROCENTRE BLVD
 CONT: AUTOBUILDERS
 TEL: (561)310-7735
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SPRINGHILL SUITES BY MARIOTT
 FIVE STORY/ 130 UNITS
  
 4THREVIEW
 ACTION: DENIED
  
  
 1-29C) COMPLIED
  
 29D)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR)
 OF PRODUCT TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 B) EXTERIOR WOOD DOORS DOOR 160A
 EXTERIOR HOLLOW METAL DOORS OUTSWING 132A, 147B
 EXTERIOR METAL DOOR INSWING - 631 TO ROOF
  
 F) ROOF ASSEMBLIES
 FLAT ROOFS- CARLISLE ROOFINGWILL REQUIRE SEPERATE
 REVIEW AND PERMIT , SHOP DRAWINGS ARE TO BE PREPARED
 WITH ASSOCIATED PRESSURES.
  
  
 31-34) COMPLIED.
  
  
 35) SHEET A-401, FIRST FLOOR, THE R2 UNITS ON THE FIRST
 FLOOR REQUIRE 2 EXITS AND THE EXIT ACCESS FOR ONE WAY
 IS THROUGH THE FRONT LOBBYBUT THE WALLS THERE ARE
 LOCATED BEHIND THE REGISTRATION DESK ARE INDICATED AS
 NON-RATED WALLS. PLEASE SEE 1016.5 CORRIDOR CONTINUITY,
 EXCEPTIONS: FOYERS, LOBBIES OR RECEPTION ROOMS
 CONSTRUCTED AS REQUIED FOR CORRIDORS SHALL NOT BE
 CONSTRUED AS INTERVENING ROOMS.THE LOBBY OR FOYEER
 ARE OK AS LONG AS THE WALL RATINGS ARE MAINTAINED.
 MISSING RATED WALL SECTIONS AT SALES OFFICE TO
 VESTIBULE AND BUFFET AREA.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-01-30 Cont ID  
Sent By jwitmer Date 2008-01-30 Time 07:52 Rev Time 6.50
Received By jwitmer Date 2008-01-30 Time 07:52 Sent To  
Notes
2008-01-30 09:45:52 
 BUILDING PLAN REVIEW
 PERMIT: 06111067
 ADD: 2437 METROCENTRE BLVD
 CONT: AUTOBUILDERS
 TEL: (561)310-7735
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SPRINGHILL SUITES BY MARIOTT
 FIVE STORY/ 130 UNITS
  
 3RDREVIEW
 ACTION: DENIED
  
  
 1-17C COMPLIED
  
 17-D) NOTE THE ELEVATOR DOORS ON THE DOOR SCHEDULE
 (*34) NOW INDICATE THIS TO BE A STORAGE CLOSET.
  
 18-29A) COMPLIED.
  
 29B-30 CAN NOT BE REVIEWED FOR WIND PRESSURES, SHEET
 S-101 ASCE 7-02 ANALYSIS INDICATES A "C" EXPOSURE WHICH
 IS CORRECT, THE BUILDINGS ROOF HEIGTH IS 54'-0, THE
 EXPOSURE COEFFICIENT IS 1.59( 1609..2.1(4) NOT 1.09.
 THIS WILL INCREASE PRESSURES SHOWN IN THE COMPENTS AND
 CLADDING TABLE!!! PLEASE RECALCULATE AND RE-REVIEW THE
 PRODUCT APPROVALS FOR POSITIVE AND NEGATIVE PRESSURES.
  
 31-32) BOTH WILL RELATE BACK TOTHE RECALCULATING
 PRESSURES TO THE EXPOSURE COEFFICIENT OF 1.59 PER
 1609.2.1.(4).
  
 33-34) COMPLIED.
  
 NEW COMMENT:
 35) SHEET A-401, FIRST FLOOR, THE R2 UNITS ON THE FIRST
 FLOOR REQUIRE 2 EXITS AND THE EXIT ACCESS FOR ONE WAY
 IS THROUGH THE FRONT LOBBYBUT THE WALLS THERE ARE
 LOCATED BEHIND THE REGISTRATION DESK ARE INDICATED AS
 NON-RATED WALLS. PLEASE SEE 1016.5 CORRIDOR CONTINUITY,
 EXCEPTIONS: FOYERS, LOBBIES OR RECEPTION ROOMS
 CONSTRUCTED AS REQUIED FOR CORRIDORS SHALL NOT BE
 CONSTRUED AS INTERVENING ROOMS.THE LOBBY OR FOYEER
 ARE OK AS LONG AS THE WALL RATINGS ARE MAINTAINED.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-10-03 Cont ID  
Sent By jjohnsto Date 2007-10-03 Time 16:52 Rev Time 6.00
Received By jjohnsto Date 2007-10-03 Time 16:48 Sent To  
Notes
2007-10-03 16:51:48CONSTRUCTION SERVICES DEPARTMENT
 200 SECOND STREET, 3RD FLOOR, WEST PALM BEACH,
 FLORIDA33401
 TEL:561-805-6713FAX:
 561-805-6731
  
 JAMES JOHNSTON, PERMIT NO 06111067
 BUILDING PLAN EXAMINERII PROJECT
 SPRINGHILL SUITES HILTON
 E-MAIL:JJOHNSTON @WPB.ORG ADDRESS
 2437 METROCENTREBOULEVARD E
  DATE OCTOBER 2, 2007
  
 BUILDINGPLANREVIEW
  
 F.S.713.13NOTICE OF COMMENCEMENT
 FILE NOTICE WITH THE CLERK OF COURT RECORDING DIVISION.
 IF THE WORK DESCRIBED IN THE NOTICE IS NOT COMMENCED
 WITHIN 90 DAYS OF FILING THE NOTICE WILL BECOME NULL
 AND VOID. SUBMIT THE NOTICE AT THE TIME OF PERMIT
 ISSUANCE AND POST A COPY AT THE JOB SITE BEFORE THE
 FIRST INSPECTION.
 COMMENT-NOTICE OF COMMENCEMENT HAS EXPIRED
  
 A-1 SOILREPORT
 THE SOILS AND BEARING CAPACITY LISTED IN THE REPORT
 FURNISHED BY MATEC APPEARED TO BE IN CONFLICT WITH THE
 FBC SECTION 1804 (SEE TABLE) SANDY SOILS. ANY
 INFORMATION PROVIDED REFERENCING THIS COMMENT WOULD BE
 APPRECIATED. PLEASE NOTE UPON SOIL PREPARATION AND
 COMPLETION A REPORT OF THE ACTUAL BEARING CAPACITY (IN
 SEVERAL AREAS) SHALL BE SUBMITTED FOR REVIEW PRIOR TO
 CONCRETE PLACEMENT IN THE FOUNDATION.THE MATEC REPORT
 STATES THE GUIDELINES FOR ACHIEVING THE BEARING
 CAPACITY AS A SUGGESTION.THE COMPLETION REPORT WILL
 ALLEVIATE ANY CONCERNS AND SUBSTANTIATE THAT THE
 CAPACITY HAS BEEN ACHIEVED.
  
 A-2 FLORIDA ADMINISTRATIVE CODE CHAPTER 61G15-23.001
 SEALS ACCEPTABLE TO THE BOARD
 ARCHITECT AND ENGINEER SEALS ARE TO BE A MINIMUM OF 2?
 COMMENT-ARCHITECT SEAL IS NOT IN COMPLIANCE WITH THIS
  
  
 A-2.1 61G1-16.002 ARCHITECTSEAL
 (1) THE SEAL SHALL CONTAIN THE NAME OF ONLY ONE
 ARCHITECT OR INTERIOR DESIGNER AND THE REGISTRATION
 NUMBER; THE SEAL OF THE ARCHITECT SHALL BE CIRCULAR,
 AND THE SEAL OF THE INTERIOR DESIGNER SHALL BE
 HEXAGONAL. BOTH SEALS SHALL BE AN IMPRESSION-TYPE METAL
 SEAL, APPROXIMATELY 2" IN DIAMETER WITH TWO CIRCULAR
 LINES BETWEEN WHICH LINES SHALL APPEAR, AT THE TOP, THE
 WORDS ?STATE OF FLORIDA? AND AT THE BOTTOM THE WORDS
 ?REGISTERED ARCHITECT? OR ?LICENSED INTERIOR DESIGNER,?
 WHICHEVER IS APPLICABLE.
 (2) ANY INDIVIDUAL WHO IS BOTH A REGISTERED ARCHITECT
 AND A LICENSED INTERIOR DESIGNER MUST USE A SEAL WHICH
 CONTAINS BOTH THE ARCHITECT AND INTERIOR DESIGN
 REGISTRATION NUMBERS, IN SUCH A MANNER:
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 A-3 109.3.6 THRESHOLD BUILDING.
 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OR ARCHITECT OF RECORD.
 THE STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLANS IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
 COMMENT- SUBMIT PLANS FOR COMPLIANCE WITH ABOVE
  
 A-3.1 109.3.6.4.4
 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED TO BE
 SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT?S OR ENGINEER?S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND CHAPTER 633, FLORIDA STATUTES.
  
 B-4 FIRE SPRINKLER
 THE FIRE SPRINKLER PLAN SHEETSFP-1 THRU FP-6 ARE NOT
 LISTED ON THE INDEX OF DRAWINGS SHEET G001
 COMMENT-PLEASE LIST IN THE APPROPRIATE SECTION
  
  
 C-5 FBC 1008.1 DOORS.
 MEANS OF EGRESS DOORS SHALL MEET THE REQUIREMENTS OF
 THIS SECTION. DOORS SERVING A MEANS OF EGRESS SYSTEM
 SHALL MEET THE REQUIREMENTS OF THIS SECTION AND SECTION
 1017.2 . DOORS PROVIDED FOR EGRESS PURPOSES IN NUMBERS
 GREATER THAN REQUIRED BY THIS CODE SHALL MEET THE
 REQUIREMENTS OF THIS SECTION. FOR ACCESSIBILITY
 PROVISIONS RELATED TO DOORS, REFER TO SECTIONS 11-4.1.3
 , 11-4.3.9 AND 11-4.13 .
 MEANS OF EGRESS DOORS SHALL BE READILY DISTINGUISHABLE
 FROM THE ADJACENT CONSTRUCTION AND FINISHES SUCH THAT
 THE DOORS ARE EASILY RECOGNIZABLE AS DOORS. MIRRORS OR
 SIMILAR REFLECTING MATERIALS SHALL NOT BE USED ON MEANS
 OF EGRESS DOORS. MEANS OF EGRESS DOORS SHALL NOT BE
 CONCEALED BY CURTAINS, DRAPES, DECORATIONS OR SIMILAR
 MATERIALS.
  
 C5.1 1008.1.1 SIZE OF DOORS.
 THE MINIMUM WIDTH OF EACH DOOR OPENING SHALL BE
 SUFFICIENT FOR THE OCCUPANT LOAD THEREOF AND SHALL
 PROVIDE A CLEAR WIDTH OF NOT LESS THAN 32 INCHES (813
 MM). CLEAR OPENINGS OF DOORWAYS WITH SWINGING DOORS
 SHALL BE MEASURED BETWEEN THE FACE OF THE DOOR AND THE
 STOP, WITH THE DOOR OPEN 90 DEGREES (1.57 RADIUS).
 WHERE THIS SECTION REQUIRES A MINIMUM CLEAR WIDTH OF 32
 INCHES (813 MM) AND A DOOR OPENING INCLUDES TWO DOOR
 LEAVES WITHOUT A MULLION, ONE LEAF SHALL PROVIDE A
 CLEAR OPENING WIDTH OF 32 INCHES (813 MM). THE MAXIMUM
 WIDTH OF A SWINGING DOOR LEAF SHALL BE 48 INCHES (1219
 MM) NOMINAL. MEANS OF EGRESS DOORS IN OCCUPANCY IN
 GROUP I-2 USED FOR THE MOVEMENT OF BEDS SHALL PROVIDE A
 CLEAR WIDTH NOT LESS THAN 41? INCHES (1054 MM). THE
 HEIGHT OF DOORS SHALL NOT BE LESS THAN 80 INCHES (2032
 MM).
 COMMENT- PLEASE SUBMIT DOOR HARDWARE ON DOOR SCHEDULE
 SHEET A-604
  
 C5.2 1008.1.8.1 HARDWARE.
 DOOR HANDLES, PULLS, LATCHES, LOCKS AND OTHER OPERATING
 DEVICES ON DOORS REQUIRED TO BE ACCESSIBLE BY CHAPTER
 11 SHALL NOT REQUIRE TIGHT GRASPING, TIGHT PINCHING OR
 TWISTING OF THE WRIST TO OPERATE.
  
 C-5.3 1008.1.8 DOOR OPERATIONS.
 EXCEPT AS SPECIFICALLY PERMITTED BY THIS SECTION EGRESS
 DOORS SHALL BE READILY OPERABLE FROM THE EGRESS SIDE
 WITHOUT THE USE OF A KEY OR SPECIAL KNOWLEDGE OR
 EFFORT.
  
 COMMENT-IDENTIFY HARDWARE FOR EACH DOOR ON DOOR
 SCHEDULE SHEET A604
 IDENTIFY ALL STAIRWAY DOORS AT EACH FLOOR ON DOOR
 SCHEDULE AND APPROPRIATE EXIT ACCESS REQUIRED HARDWARE
  
  
 C-5.4 DOORS MISSING
 DOORS201 THRU 229 ARE MISSING ONDOOR SCHEDULE SHEET
 604
 COMMENT PLEASE LIST ALL DOORS IN THIS PROJECT
 SEPARATELY WITH HOURLY RATING AND ALL HARDWARE.
 AS APPLICABLE.DO NOT LIST? TYPICAL ? AS A
 DESCRIPTION
  
 PLEASEIDENTIFYTHEDOORS ON EACH PLAN SHEET
 THROUGHOUT THE PLANSWITH A DOOR NUMBER THAT WILL
 CORROSPOND TO THE DOOR LIST WHICH SHALL INCLUDE FIRE
 RATING AND HARWARE
  
  
 D-6 1019.1.7 STAIRWAY FLOOR NUMBER SIGNS.
 A SIGN SHALL BE PROVIDED AT EACH FLOOR LANDING IN
 INTERIOR VERTICAL EXIT ENCLOSURES CONNECTING MORE THAN
 THREE STORIES DESIGNATING THE FLOOR LEVEL, THE TERMINUS
 OF THE TOP AND BOTTOM OF THE STAIR ENCLOSURE AND THE
 IDENTIFICATION OF THE STAIR. THE SIGNAGE SHALL ALSO
 STATE THE STORY OF, AND THE DIRECTION TO THE EXIT
 DISCHARGE AND THE AVAILABILITY OF ROOF ACCESS FROM THE
 STAIRWAY FOR THE FIRE DEPARTMENT. THE SIGN SHALL BE
 LOCATED 5 FEET (1524 MM) ABOVE THE FLOOR LANDING IN A
 POSITION WHICH IS READILY VISIBLE WHEN THE DOORS ARE IN
 THE OPEN AND CLOSED POSITIONS.
 PLEASE APPLY THIS CODE SECTION WHEN DESCRIBING HARDWARE
 FOR EMERGENCY DOORS ON DOOR SCHEDULE
 COMMENT-PLEASE DETAIL ONTHE PLAN SHEETS THAT ARE
 APPLICABLE
  
  
 ELEVATOR
 E-7 3002.4 ELEVATOR CAR TO ACCOMMODATE AMBULANCE
 STRETCHER.
 SHALL BE IDENTIFIED BY THE INTERNATIONAL SYMBOL FOR
 EMERGENCY MEDICAL SERVICES (STAR OF LIFE). THE SYMBOL
 SHALL NOT BE LESS THAN 3 INCHES (76 MM) HIGH AND SHALL
 BE PLACED INSIDE ON BOTH SIDES OF THE HOISTWAY DOOR
 FRAME.
 COMMENT-PLEASE SHOW DETAIL AND LOCATION ON PLANS.
  
 E-7.1 3003.2 FIRE-FIGHTERS? EMERGENCY OPERATION.
 ELEVATORS SHALL BE PROVIDED WITH PHASE I EMERGENCY
 RECALL OPERATION AND PHASE II EMERGENCY IN-CAR
 OPERATION IN ACCORDANCE WITH ASME A17.1.
 COMMENT -PLEASE NOTE ON PLANS
  
 E-8 COMMENT 17-D FROM PRIOR REVIEW AUGUST 8
 SHEET A-702 IS MISSING DOORS AND DESCRIPTION AS
 REQUESTED.
 COMMENT -PLEASE NOTE ALL DOORS ON THIS PROJECT ON PLANS
 AND DOOR SCHEDULE.
  
 E-9 COMMENT 20-B FROM PRIOR REVIEW AUGUST 8
 FBC 2303.1.4 WOOD STRUCTURAL PANELS.
 WOOD STRUCTURAL PANELS, WHEN USED STRUCTURALLY
 (INCLUDING THOSE USED FOR SIDING, ROOF AND WALL
 SHEATHING, SUBFLOORING, DIAPHRAGMS AND BUILT-UP
 MEMBERS), SHALL CONFORM TO THE REQUIREMENTS FOR THEIR
 TYPE IN DOC PS 1 OR PS 2. EACH PANEL OR MEMBER SHALL BE
 IDENTIFIED FOR GRADE AND GLUE TYPE BY THE TRADEMARKS OF
 AN APPROVED TESTING AND GRADING AGENCY. WOOD STRUCTURAL
 PANEL COMPONENTS SHALL BE DESIGNED AND FABRICATED IN
 ACCORDANCE WITH THE APPLICABLE STANDARDS LISTED IN
 SECTION 2306.1 AND IDENTIFIED BY THE TRADEMARKS OF AN
 APPROVED TESTING AND INSPECTION AGENCY INDICATING
 CONFORMANCE WITH THE APPLICABLE STANDARD. IN ADDITION,
 WOOD STRUCTURAL PANELS WHEN PERMANENTLY EXPOSED IN
 OUTDOOR APPLICATIONS SHALL BE OF EXTERIOR TYPE, EXCEPT
 THAT WOOD STRUCTURAL PANEL ROOF SHEATHING EXPOSED TO
 THE OUTDOORS ON THE UNDERSIDE IS PERMITTED TO BE
 INTERIOR TYPE BONDED WITH EXTERIOR GLUE, EXPOSURE 1.
  
 WOOD STRUCTURAL PANEL. A PANEL MANUFACTURED FROM
 VENEERS, OR WOOD STRANDS OR WAFERS, OR A COMBINATION OF
 VENEER AND WOOD STRANDS OR WAFERS, BONDED TOGETHER WITH
 WATERPROOF SYNTHETIC RESINS OR OTHER SUITABLE BONDING
 SYSTEMS. EXAMPLES OF WOOD STRUCTURAL PANELS ARE:
 PLYWOOD. A WOOD STRUCTURAL PANEL COMPRISED OF PLIES OF
 WOOD VENEER ARRANGED IN CROSS-ALIGNED LAYERS.
 COMMENT- IDENTIFY THE TYPE OF WOOD STRUCTURAL PANEL
 FROM THE CHART BELOW USING THE CORRECT NOMENCLATURE
  
  
 TABLE 2304.7(5)
 ALLOWABLE LOAD (PSF) FOR WOOD STRUCTURAL PANEL ROOF
 SHEATHING CONTINUOUS
 OVER TWO OR MORE SPANS AND STRENGTH AXIS PARALLEL TO
 SUPPORTS
 (PLYWOOD STRUCTURAL PANELS ARE 5-PLY, 5-LAYER UNLESS
 OTHERWISE NOTED) A ,B
 PANEL GRADE THICKNESS (INCH ) D MAXIMUM SPAN (INCHES)
  LOAD AT MAXIMUM SPAN (PSF)
  LIVE TOTAL
 STRUCTURAL I SHEATHING 7 / 16 24 20 30
  15 / 32 24 35 D 45 C
  1 / 2 24 40 C 50 C
  19 / 32, 5 / 8 24 70 80
  23 / 32 , 3 / 4 24 90 100
 SHEATHING, OTHER GRADES COVERED IN DOC PS 1 OR DOC PS2
  7 / 16 16 40 50
  15 / 32 24 20 25
  1 / 2 24 25 30
  19 / 32 24 40 C 50 C
  5 / 8 24 45 C 55 C
  23 / 32 , 3 / 4 24 60 C 65 C
 FOR SI: 1 INCH = 25.4 MM, 1 POUND PER SQUARE FOOT =
 0.0479 KN/M 2 .
 A. ROOF SHEATHING CONFORMING WITH THIS TABLE SHALL BE
 DEEMED TO MEET THE DESIGN CRITERIA OF SECTION 2304.7 .
  
 B. UNIFORM LOAD DEFLECTION LIMITATIONS 1 / 180 OF SPAN
 UNDER LIVE LOAD PLUS DEAD LOAD, 1 / 240 UNDER LIVE LOAD
 ONLY. EDGES SHALL BE BLOCKED WITH LUMBER OR OTHER
 APPROVED TYPE OF EDGE SUPPORTS.
 C. FOR COMPOSITE AND FOUR-PLY PLYWOOD STRUCTURAL PANEL,
 LOAD SHALL BE REDUCED BY 15 POUNDS PER SQUARE FOOT.
 D. IN NO CASE SHALL ANY ROOF SHEATHING BE LESS THAN 32
 / 16 SPAN INDEX, 19 / 32 - IN. WOOD STRUCTURAL PANEL
 FOR SPANS 16-INCHES OR MORE ON CENTER IN WIND SPEED
 REGIONS OF 110-140 MPH, EXPOSURE B. SPAN RATINGS AND
 PANEL THICKNESS HIGHLIGHTED IN THE TABLE SHALL NOT BE
 PERMITTED WHERE WIND SPEEDS EXCEED 100 MPH.
  
  
  
 F-10 COMMENT 21FROM PRIOR REVIEW AUGUST 8
 SHEET A-701THE PLAN REVIEWER?S COMMENT WAS ROOF
 ACCESS, PLANS INDICATE DOOR SWINGING IN AND OUT,
 PLEASE EXPLAIN?
 THE PLAN REVIEWER WAS DESCRIBING THE TWO DOORS
 DEPICTED, ONE DOOR SWINGING INTO THE STAIRWAY AND ONE
 DOOR SWINGING OUT TO THE ROOF.
 YOUR RESPONSE WAS ACCESS LADDER TO ROOF NOT
 PROVIDED.??????? ROOF ACCESS TO STAIRS???????
 PLEASE READ THESE COMMENTS TO AVOID REPETITIOUS WORK.
  
 ARE THE TWO DOORSINSTALLED AS A SAFETY FEATURE
 INCLUDING AN ALLOWABLE3 HOUR RATING ASDESCRIBED IN
 CHAPTER 10 ?
 AS REQUESTED ABOVE THAT INFORMATION SHALL BE PROVIDED
 IN THEREVISED DOOR SCHEDULEAS DOOR NO ? AAND DOOR
 NO? BWITH THEIR APPROPRIATE HARDWARE AND RATING.
  
  
 F-10.1 COMMENT 25FROM PRIOR REVIEW NOT ADDRESSED
 DOOR AND WINDOW
 DESCRIBE THE FASTENER TO BE USED FOR ANCHORING THE WOOD
 BUCK TO THE STRUCTURE.
 TYPE OF FASTENER,LENGTH OF FASTENER,SIDE OF
 FASTENER,DEPTH OF PENETRATION INTO THE STRUCTURE TO
 HOLD THE WOOD BUCK IN PLACE.
 WOOD BUCK INFORMATION REQUIRED,THICKNESS OF MEMBER,
 PRESERVATIVE REQUIRED FOR LUMBER IN CONTACT WITH
 MASONRY,
 COMMENTPLACE THIS INFORMATION ON SHEET A-604 AND
 A-605 DETAIL DESCRIPTION

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-05-16 Cont ID  
Sent By jwitmer Date 2007-05-16 Time 10:26 Rev Time 5.55
Received By jwitmer Date 2007-05-16 Time 10:14 Sent To PC
Notes
2007-05-16 10:29:10 
  
 BUILDING PLAN REVIEW
 PERMIT: 06111067
 ADD: 2437 METROCENTRE BLVD
 CONT: AUTOBUILDERS
 TEL: (561)310-7735
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SPRINGHILL SUITES BY MARIOTT
 FIVE STORY/ 130 UNITS
  
 2NDREVIEW
 ACTION: DENIED
  
 NOTE, THIS REVIEW IS FOR SPRINGHILL SUITES BUT THE
 RESPONCE COMENTS ARE
 HOMEWOOD SUITES!!!!!!!!!!!!!!!
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS
 NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE
 OF COMMENCEMENT
 AT THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 802.2.1 QUESTIONABLE SOIL. WILL REQUIRE (3) SIGNED AND
 SEALED ORIGINALS.
  
 WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN
 DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED,
 THE BUILDING OFFICIAL SHALL REQUIRE THAT THE NECESSARY
 INVESTIGATION BE MADE.
 SUCH INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS
 1802.4 THROUGH 1802.6 .
  
 4)2ND REQUEST,ADMINISTRATIVE CODE109.3.6
 THIS BUILDING IS CONSIDERED A THRESHOLD BUILDING,
 REQUIRING THREE SETS
 OF ALL DOCUMENTS TO BE SUBMITTED TO THE BUILDING
 DEPARTMENT, PLANS,
 REPORTS, SUBMITTALS AND OR PRODUCT APPROVALS.
  
 5)2ND REQUEST, THE THRESHOLD INSPECTION PLAN IS NOT
 TO BE A GUIDE
 BUT EXPLICIT INSTRUCTIONS DESIGN BY THE ENGINEER OF
 RECORD FOR THE THRESHOLD
 INSPECTOR TO FOLLOW. SINCE THIS IS A DOCUMENET
 CREATED
 BY THE ENGINEER IT IS TO BE SIGNED AND SEALED.FL S.
 S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN
 CY CLASSIFICATION AS DEINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 STRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE
 ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE
 OF A BUILDING PERMIT FOR THE
 CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURL INSPECTION
 PLAN IS TO PROVIDE SPECIFIC INSPECTION
 PROCEDURES AND SCHEDULES SO THAT THE
 BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 6)2ND REQUEST,
 WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 7)COMPLIED.
  
 8) 2ND REQUEST, I COULD NOT LOCATE A PLAN ANY PLAN
 AG002,
 THERE IS NO SUCH SHEET IN THE INDEX?109.3.10* IMPACT
 OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PERMORMED IN A MANNER
 SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS
 SUCH ACTIVITY IS PERMITTED TO AFFECT
 SAID PROPERTY PURSUANT TO A CONSENT BY
 THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE
 APPLICABLE PROPERTY OWNER.THIS INCLUDES
 BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF,
 DEBRIS, AND THE STORAGE OF CONSTRUCTION
 MATERIALS. NEW CONSTRUCTION ACTIVITY
 SHALL NOT ADVERSELY IMPACT HISTORIC
 SURFACE WATER DRAINAGE FLOWS SERVING
 ADJACENT PROPERTIES, & MAY REQUIRE
 SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES.ACCORDINGLY,
 DEVELOPERS, CONTRACTORS,
 AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR
 ITEMS, ON EXISTING PROPERTIES RESULTING
 IN A DECREASE IN EXCESS OF 800SQ FT OF
 PERMEABLE LAND AREA ON ANY PARCELL SHALL
 AS A PERMIT CONDITION, PROVIDE A
 PROFESSIONALLY PREPARED DRAINAGE PLAN
 CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 9)2ND REQUEST, I COULD NOT LOCATE A PLAN
 ANY PLAN AG002, THERE IS NO SUCH SHEET IN THE INDEX?
 109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 10) 2ND REQUEST, PRINTING THE ARCHITECTS NAME COMPLIES
 WITH COMMENT# 11.
 PFVS NEEDS TO BE REGISTERED WITH THE STAT AS A DBA
 "DOING BUSINESS AS" AND ALSO REGISTERED AS AN
 ARCHITECTURAL BUSINESS!!!!!!
 PFVS ARCHITECTURE PLANNING AND INTERIORS
 IS MISSING THE FIRMS CERTIFICATE OF AUTHORIZATION.
 481.219 F.S.CERTIFICATE OF AUTHORIZATION.THE TITLE
 BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL
 SERVICES, SHALL INCLUDE
 THE CERTIFICATE OF AUTHORIZATION
 NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 11)COMPLIED.
  
 12) 2ND REQUEST SHEET G.000 THIS SHEET INDICATES
 NIELSEN STRUCTURAL ENGINEERING
 AS ONE OF THE FIRMS WORKING ON THIS PROJECT BUT THEY
 ARE NOT NOTED ON THE STRUCTURAL SHEETS?106.1.2* IF
 NEILSEN STRUCTURAL ENGINEERING IS THE DESIGNER FOR THIS
 STRUCTURE THEY ARE THE ENGINEERING OF RECORD AND SINCE
 THEY ARE A ENGINEERING BUSINESS A CERTIFICATE OF
 AUTHORIZATION IS REQUIRED.
 471.023 FS CERTIFICATE OF AUTHORIZATION.THE TITLE
 BLOCK FOR ANY SHEET BEARING THE NAME OF AN ENGINEER
 PRACTICING UNDER A FICTITIOUS NAME, A CORPORATION, OR A
 PARTNERSHIP, OFFERING ENGINEERING SERVICES, SHALL
 INCLUDE THE
 CERTIFICATE OF AUTHORIZATION NUMBER. ADD THE NUMBER TO
 EACH SHEET.THIS MAY BE ADDED BY HAND.
  
 13) 2ND REQUEST, COMMENT NOT EVEN SHOWN ON THE COMMENT
 SHEET!!!
 SHEET G-000
 13A) 2ND RESPONCE, WHEN OVER 50 SPRINKLER HEADS ARE
 REQUIRED, THE SYSTEM IS TO BE DESIGNED BY A ENGINEER!!
 AGAIN FLORIDA STATUTES REQUIRE THE FIRE SPRINKLER PLANS
 TO BE PART OF THE
 PERMIT PACKAGE.
 THE PROJECT INDICATES THIS TO BE A (5) STORY, TYPE I-B
 SPRINKLERED BUILDING, THERE ARE NO PLANS FOR FIRE
 SPRINKLERS IN THE PLANS. FL S S 553.895(2) REQUIRES
 BUILDINGS 3 STORIES OR MORE TO HAVE FIRE SPINKLERS,
 SUBMIT PLANS FOR REVIEW BEFORE A PERMIT CAN BE ISSUED.
  
  
 14) SHEET A-401, COMPLIED.
 14B) NEW COMMENT THE ACCESS AISLE FOR THE DISSABLED
 PARKING DOES NOT SHOW A CURB CUT OR THE SIDEWALKS
 HAVING SLOPE DOWN TO THE ACCESS AISLE.
  
 15) 2ND REQUEST RESPONCE INDICATED SEE CHANGES ON
 A-401, NO CHANGE INDICATED,
 SHEET A-401, THE FRONT ENTRY DOORS (VESTIBULE) APPEAR
 TO BE HORIZONTAL SLIDING DOORS,
 PLEASE PROVIDE INFORMATION FOR MANUAL LY OPERATED
 (BREAK AWAY) IF LOSS OF POWER. SECTION 1008.1.3.3.
  
  
 16) SHEET A-101:
 16A-C) COMPLIED.
  
 16D) 2ND REQUEST, ROOM 136C LAUNDRY TERMINATION ROOM,
 THE ROOM REQUIRES A 1 HR FIRE RATING SHEET A-401
 ENLARGED PLAN IS MISSING RATED WALLS.707.13.4. 707.13.2
 MATERIALS. A SHAFT ENCLOSURE CONTAINING A REFUSE OR
 LAUNDRY CHUTE SHALL BE CONSTRUCTED OF MATERIALS AS
 PERMITTED BY THE BUILDING TYPE OF CONSTRUCTION. 16D)(1)
 PLEASE PROVIDE THE BLOCK WALL EQUIVALENT THICKNESS, SEE
 TABLE 721.3.2. PROVIDE DOCUMENTATION FROM THE BLOCK
 MANUFACTURER THE MODEL OF BLOCK TO BE USED AND THE
 EQUIVALENT THICKNESS.
 16D)(2)PLANS INDICATE THE USE OF U-438 TYPE WALL BUT
 THE DETAIL DOES NOT PROVIDE INFORMATION ON THE TYPE OF
 JOINT AT THE FLOOR AND CEILING. SEE 713.1.& 713.2.
  
 16E-G) COMPLIED.
  
 16H) 2ND REQUEST, THE PLANS (A-401 ENLARGED) ALSO
 INDICATE SUITES 104 & 106, THERE IS NO WALL TYPE
 IDENTIFICATION. PROVIDE THE STC RATING BETWEEN ROOM.
 RESPONSE SEE A-604 FOR REVISIONS.
 A-604 IS DOOR SCHEDULE. WALL TAG 3A WALL TYPEU-904 DOES
 NOT PROVIDE A STC RATING. WALL WALL TAG# 1A U465 ALSO
 DOES NOT INDICATE A STC RATING, A 3 5/8" METAL STUD
 WALL WITH 5/8" GYPSUM BOARD AND INSULATION ONLY HAS A
 STC RATING OF 46 WITH INSULATION,NOT 50STC.
  
 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION
 ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; RECESSED
 CABINETS; BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR
 EXHAUST DUCTS SHALL BE SEALED, LINED, INSULATED OR
 OTHERWISE TREATED TO MAINTAIN THE REQUIRED RATINGS.
 THIS REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT
 ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT
 FITTING TO THE FRAME AND SILL.
  
 16I) 2ND REQUEST, THIS SAME SITUATION SHALL OCCUR
 BETWEEN SUITES BETWEEN FLOORS, SHOW COMPLIANCE WITH:
 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 16J) COMPLIED.
  
 16K) 2ND REQUESTPLEASE PROVIDE LAUNDRY SHUTE DETAILS:
 707.13.2 MATERIALS.
 A SHAFT ENCLOSURE CONTAINING A REFUSE OR LAUNDRY CHUTE
 SHALL BE CONSTRUCTED OF MATERIALS AS PERMITTED BY THE
 BUILDING TYPE OF CONSTRUCTION.
  
 16L) COMPLIED.
  
 16M) 2ND REQUEST, SEE DETAIL# 2 SHEET A-701 UNDER THE
 STAIRS, PLEASE PROVIDE CODE COMPLIANCE FOR HEADROOM
 CLEARENCE UNDER STAIRWELLS,11-4.4.2 HEADROOM. WALKS,
 HALLS, CORRIDORS, PASSAGEWAYS, AISLES, OR OTHER
 CIRCULATION SPACES SHALL HAVE 80 INCHES (2030 MM)
 MINIMUM CLEAR HEAD ROOM [SEE FIGURE 11-8 (A)]. IF
 VERTICAL CLEARANCE OF AN AREA ADJOINING AN ACCESSIBLE
 ROUTE IS REDUCED TO LESS THAN 80 INCHES (2032 MM)
 (NOMINAL DIMENSION), A BARRIER TO WARN BLIND OR
 VISUALLY-IMPAIRED PERSONS SHALL BE PROVIDED [SEE FIGURE
 11-8 (C-1)].
  
 16N) 2ND REQUEST,SHEET A-101- A-105 ALL CORRIDORS WITH
 OCCUPANT LOAD GREATER THAN 10 (R-1)REQUIRES 1-HR
 RATED CORRIDORS WITH OPENING PROTECTIVES. PROVIDE DOOR
 IDENTIFICATION AND FIRE RATING. SEE SECTION 715.3. NEW
 STATEMENT IN 715.3 WE ARE LOOKING AT ALL FIRE RATED
 DOORS AND THE REQUIREMENTS OF NFPA 80 REQUIREMENTS
 INCLUDING DOOR CLOSERS & 715.3.3 DOOR ASSEMBLIES IN
 CORRIDORS WHICH REQUIRE SMOKE AND DRAFT CONTROL DOOR
 ASSEMBLIES TESTED IN ACCORDANCE WITH UL 1784 WITH AN
 ARTIFICIAL BOTTOM SEAL INSTALLED ACROSS THE FULL WIDTH
 OF THE BOTTOM OF THE DOOR ASSEMBLY.
  
 16O)COMPLIED.
  
 16P) 2ND REQUEST, PLEASE PROVIDE INFORMATION FOR
 ELEVATOR CARS TO ACCOMMODATE AMBULANCE STRETCHER.
 3002.4 ELEVATOR CAR TO ACCOMMODATE AMBULANCE
 STRETCHER.RESPONSE SEE A-702 I DO NOT SEE A DETAIL WITH
 THE STRETCHER REQUIREMENT?
 IN BUILDINGS FOUR STORIES IN HEIGHT OR MORE, AT LEAST
 ONE ELEVATOR SHALL BE PROVIDED FOR FIRE DEPARTMENT
 EMERGENCY ACCESS TO ALL FLOORS. SUCH ELEVATOR CAR SHALL
 BE OF SUCH A SIZE AND ARRANGEMENT TO ACCOMMODATE A
 24-INCH BY 76-INCH (610 MM BY 1930 MM) AMBULANCE
 STRETCHER IN THE HORIZONTAL, OPEN POSITION AND SHALL BE
 IDENTIFIED BY THE INTERNATIONAL SYMBOL FOR EMERGENCY
 MEDICAL SERVICES (STAR OF LIFE). THE SYMBOL SHALL NOT
 BE LESS THAN 3 INCHES (76 MM) HIGH AND SHALL BE PLACED
 INSIDE ON BOTH SIDES OF THE HOISTWAY DOOR FRAME.
  
  
  
 16Q) COMPLIED.
  
  
 16R) 2ND REQUEST,PLEASE PROVIDE INFORMATION FOR THE
 FIRE PUMP, SIZE OF PUMP, TYPE OF PUMP FUEL LOADS IF NOT
 ELECTRIC. THE PLUMBING SHEET P-401 AND ESHEET E-401 ALL
 MATCH EXCEPT FOR
 RPM'S THE ELECTRIC INDICATES 1800 WHILE THE PLUMBING
 SHEET INDICATES 3550? PLEASE PROVIDE HE SPRINKLER PLANS
 AND CALCULATIONS. 903.6.1ANY BUILDING WHICH IS OF
 THREE STORIES OR MORE IN HEIGHT SHALL BE EQUIPPED WITH
 AN APPROVED AUTOMATIC SPRINKLER SYSTEM INSTALLED IN
 ACCORDANCE WITH SECTION 903.1 .
  
 17) SHEET A-402
 17A) COMPLIED.
  
 17B) 2ND REQUEST, SHEET A-402 DETAIL# 7 ALSO INDICATES
 A RECESSED FIRE EXTINGUISHER CABINET, HOW IS THE 2 HR
 RATING BEING MAINTAINED? 106.1.2* SECOND REVIEW THIS
 DETAIL HAS NOW BEEN DELETED, PLEASE INDICATE HOW
 COMPLIANCE WITH A 2 HR FIRE RATING WILL BE ACHIEVED?
  
 17C) COMPLIED.
  
 17D) 2ND REQUEST, DETAIL # 1 IS NOW DELETED, SHEET
 A-402 DETAIL# 1, ELEVATOR LOBBY DOORS ARE NOT
 IDENTIFIED, FLOORS 2-5 INDICATE AS DOOR *34, DOOR
 SCHEDULE INDICATES "C" LABEL REQUIRES
 RATING ACCORDING TO TABLE 715.3. THESE DOORS ALSO
 INDICATE HOLD OPEN DEVICES, "E" SHEETS DO NOT INDICATE
 IF TIED TO SMOKE ALARM, SPRINKLER, ETC.
  
 17E) COMPLIED.
  
 18) 2ND REQUEST,A-201- A-202ELEVATIONS INDICATE THE
 USE OF EFISOR EPS (COMBUSTIBLE)TRIM ABOVE 40' ABOVE
 GRADE. BUILDING TYPE I-B.SHEETS A-301, A-302 & A-303.
 1406.2.2 ARCHITECTURAL TRIM.
 IN BUILDINGS OF TYPE I, II, III AND IV CONSTRUCTION
 THAT DO NOT EXCEED THREE STORIES OR 40 FEET (12 192 MM)
 IN HEIGHT ABOVE GRADE PLANE, EXTERIOR WALL COVERINGS
 SHALL BE PERMITTED TO BE CONSTRUCTED OF WOOD WHERE
 PERMITTED BY SECTION 1405.4 OR OTHER EQUIVALENT
 COMBUSTIBLE MATERIAL. COMBUSTIBLE EXTERIOR WALL
 COVERINGS, OTHER THAN FIRE-RETARDANT-TREATED WOOD
 COMPLYING WITH SECTION 2303.2 FOR EXTERIOR
 INSTALLATION, SHALL NOT EXCEED 10 PERCENT OF AN
 EXTERIOR WALL SURFACE AREA WHERE THE FIRE SEPARATION
 DISTANCE IS 5 FEET (1524 MM) OR LESS. ARCHITECTURAL
 TRIM THAT EXCEEDS 40 FEET (12 192 MM) IN HEIGHT ABOVE
 GRADE PLANE SHALL BE CONSTRUCTED OF APPROVED
 NONCOMBUSTIBLE MATERIALS AND SHALL BE SECURED TO THE
 WALL WITH METAL OR OTHER APPROVED NONCOMBUSTIBLE
 BRACKETS
  
 19) 2ND REQUEST, A-303 PARAPET DETAIL (NO EPS ABOVE
 40') DOESN'T INDICATE ANY FASTENING SYSTEM NOR
 STRUCTURAL INFORMATION NOR REFRENCE ANY STRUCTURAL
 SHEETS? 106.1.2 ADD INFO REQUIRED.
  
 20A) 2ND REQUEST PLEASE PROVIDE ELEVATION MARKERS, NO
 COMBUSTIBLE TRIM ABOVE 40',A-501 & A-502,PARAPET
 DETAIL DOESN'T INDICATE ANY FASTENING SYSTEM NOR
 STRUCTURAL INFORMATION NOR REFRENCE ANY STRUCTURAL
 SHEETS? 106.1.2 ADD INFO REQUIRED.
  
 20B) SHEET A-501 DETAIL# 1 ALSO INDICATES THE USE OF
 5/8" P.T. PLYWOOD ON THE WALL AS WELL AS 3/4" P.T.
 PLYWOOD ROOF SHEATHING. ARCHITECTURAL TRIM TO BE
 NON-COMBUSTILE 1406.2.2.
 ROOF SHEATHING TABLE 601 FOOTNOTE (C)(2) PLEASE PROVIDE
 ELEVATIONS OF VARIOUS DETAILS.
  
 21)2ND REQUEST,ROOF ACCESS SEE A-702 DETAIL# 5 PLANAS
 INDICATE DOOR SWINGING IN AND OUT, PLEASE EXPLAIN?
 106.1.2* ADD INFO REQUIRED.
  
 22) COMPLIED.
  
 23) 2ND REQUEST SHEET A-106AROOF DRAINS AND OVERFLOW
 DRAINS, WHERE IS THE OUTLET FOR THE OVERFLOW ROOF
 DRAINS? 106.1.2*ADD INFO REQUIRED.
  
 24) COMPLIED.
  
 25) 2ND REQUEST,A-604 & A-605 BOTH INDICATE THE USE
 OF WOOD BUCKS FOR WINDOWS AND DOORS. PLANS DO NOT
 INDICATE HOW THE BUCKS ARE TO BE FASTENED, 1714.5.4.1
 ANCHORING REQUIREMENTS.PLANS DO NOT SPECIFY THE
 DIAMETER OF THE TAPCON?
 WINDOW AND DOOR ASSEMBLIES SHALL BE ANCHORED IN
 ACCORDANCE WITH THE PUBLISHED MANUFACTURER?S
 RECOMMENDATIONS TO ACHIEVE THE DESIGN PRESSURE
 SPECIFIED. SUBSTITUTE ANCHORING SYSTEMS USED FOR
 SUBSTRATES NOT SPECIFIED BY THE FENESTRATION
 MANUFACTURER SHALL PROVIDE EQUAL OR GREATER ANCHORING
 PERFORMANCE AS DEMONSTRATED BY ACCEPTED ENGINEERING
 PRACTICE.
  
 1714.5.4.2 MASONRY, CONCRETE OR OTHER STRUCTURAL
 SUBSTRATE.
 WHERE THE WOOD SHIM OR BUCK THICKNESS IS LESS THAN 1 1
 / 2 INCHES (38 MM), WINDOW AND DOOR ASSEMBLIES SHALL BE
 ANCHORED THROUGH THE MAIN FRAME OR BY JAMB CLIP OR
 SUBFRAME SYSTEM, IN ACCORDANCE WITH THE MANUFACTURER?S
 PUBLISHED INSTALLATION INSTRUCTIONS. ANCHORS SHALL BE
 SECURELY FASTENED DIRECTLY INTO THE MASONRY, CONCRETE
 OR OTHER STRUCTURAL SUBSTRATE MATERIAL. UNLESS
 OTHERWISE TESTED, BUCKS SHALL EXTEND BEYOND THE
 INTERIOR FACE OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS PROVIDED. SHIMS SHALL BE
 MADE FROM MATERIALS CAPABLE OF SUSTAINING APPLICABLE
 LOADS, LOCATED AND APPLIED IN A THICKNESS CAPABLE OF
 SUSTAINING APPLICABLE LOADS. ANCHORS SHALL BE PROVIDED
 TO TRANSFER LOAD FROM THE WINDOW OR DOOR FRAME TO THE
 ROUGH OPENING SUBSTRATE.
 WHERE THE WOOD BUCK THICKNESS IS 1 1 / 2 INCHES (38 MM)
 OR GREATER, THE BUCK SHALL BE SECURELY FASTENED TO
 TRANSFER LOAD TO THE MASONRY, CONCRETE OR OTHER
 STRUCTURAL SUBTRATE AND THE BUCK SHALL EXTEND BEYOND
 THE INTERIOR FACE OF THE WINDOW OR DOOR FRAME. WINDOW
 AND DOOR ASSEMBLIES SHALL BE ANCHORED THROUGH THE MAIN
 FRAME OR BY JAMB CLIP OR SUBFRAME SYSTEM OR THROUGH THE
 FLANGE TO THE SECURED WOOD BUCK IN ACCORDANCE WITH THE
 MANUFACTURER?S PUBLISHED INSTALLATION INSTRUCTIONS.
 UNLESS OTHERWISE TESTED, BUCKS SHALL EXTEND BEYOND THE
 INTERIOR FACE OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS PROVIDED. SHIMS SHALL BE
 MADE FROM MATERIALS CAPABLE OF SUSTAINING APPLICABLE
 LOADS, LOCATED AND APPLIED IN A THICKNESS CAPABLE OF
 SUSTAINING APPLICABLE LOADS. ANCHORS SHALL BE PROVIDED
 TO TRANSFER LOAD FROM THE WINDOW OR DOOR FRAME ASSEMBLY
 TO THE SECURED WOOD BUCK.
  
 25A) WINDOW TYPE W3 INDICATES VARIOUS DETAILS, DETAIL#
 2& 3 INDICATES A HORIZONTAL MULLION BETWEEN THE WINDOW
 AND PTAC UNIT, THE DETAIL DOES NOT INDICATE HOW THE
 MULLION WILL BE TIED BACK INTO THE STRUCTURAL FRAME OF
 THE BUILDING?1707.4.5.2 MULLIONS SHALL BE DESIGNED
 TO TRANSFER THE DESIGN PRESSURE LOADS APPLIED BY THE
 WINDOW OR DOOR ASSEMBLIES TO THE ROUGH OPENING
 SUBTRATE.
  
 25B) DETAIL# 4 IS A HEAD DETAIL INDICATING A FIN TYPE
 WINDOW APPLICATION, NOTE THE CLOSENESS OF THE WINDOW
 FIN AND EDGE OF BLOCKWORK OR BEAM AND DERATING THAT
 WILL NEED TO TAKE PLACE FOR TAPCONS! PROVIDE THE
 MANUFACTURER OF TAPCON TO SEE IF DERATING OF TAPCON IS
 ALSO NEEDED IF INSPECTIONS ARE NOR PREFORMED!
  
 25C) DETAIL# 5 IT APPEARS THAT LESS THAN 3/4" OF THE
 WINDOW FIN IS OVER THE WINDOW BUCK NOTE ON THE PRODUCT
 APPROVAL EDGE DISTANCE WHEN SUBMITTED.
  
 25D) NOTE AGAIN EFIS OR EPS SYSTEMS OVER THE 40'
 ELEVATION NOT ALLOWED IF COMBUSTIBLE PROVIDE
 DOCUMENTATION!!!!!!
  
 26) COMPLIED.
  
 27) COMPLIED.
  
 28A) SHEET A-702 PLEASE PROVIDE ELEVATOR DETAIL FOER
 VENTING.EXCEPT AS PROVIDED FOR IN SECTION 3004.3.1 ,
 THE AREA OF THE VENTS SHALL NOT BE LESS THAN 3? PERCENT
 OF THE AREA OF THE HOISTWAY NOR LESS THAN 3 SQUARE FEET
 (0.28 M 2 ) FOR EACH ELEVATOR CAR, AND NOT LESS THAN 3?
 PERCENT NOR LESS THAN 0.5 SQUARE FOOT (0.047 M 2 ) FOR
 EACH DUMBWAITER CAR IN THE HOISTWAY, WHICHEVER IS
 GREATER. OF THE TOTAL REQUIRED VENT AREA, NOT LESS THAN
 ONE-THIRD SHALL BE OF THE PERMANENTLY OPEN TYPE UNLESS
 ALL VENTS ACTIVATE UPON DETECTION OF SMOKE FROM ANY OF
 THE ELEVATOR LOBBY SMOKE DETECTORS.
  
 28B) COMPLIED.
  
 29A) COMPLIED.
  
 29B) 2ND REQUESTPRODUCT APPROVALS SUBMITTED
 WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 29C) 2ND REQUEST,WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 29D)2ND REQUEST,FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOW
 FIXED
 SINGLE HUNG
 MULLION
 B) GLAZED DOORS
 AUTOMATIC HORIZONTAL SLIDING DOORS
 EXTERIOR HOLLOW METAL DOORS
 C) LOUVERS
 D) PANEL WALL SYSTEMS-STOREFRONT,
 SOFFITS- HARDI SOFFIT BOARD
 E) STRUCTURAL COMPONENTS- TRUSS ANCHORS
 F) ROOF ASSEMBLIES
 FLAT ROOFS- MODIFIED/ BITUMEN,EPDM ROOFING
 SLOPED:UNDERLAYMENTS, METAL ROOFS
  
 30) THIS ROOF IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
  
 ___ CONTRACTOR DID NOT PROVIDE THE MEAN
  
 ROOF HEIGHT.
  
 ___ CONTRACTOR DID NOT INDICATE THE ROOF
 PITCH.
  
 ___ CONTRACTOR FAILED TO INDICATE WHICH
 SYSTEM TO BE USED.
  
 ___ THE SYSTEM PROVIDED HAS A LOW
 PRESSURE FOR ZONE ___ .
  
 ___ THE SYSTEM PROVIDED STATES
 LIMITATION# 7, SHOULD THE FASTENER
 RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE
 BUILDING OFFICIAL, A REVISED
 FASTENER SPACING, PREPARED , SIGNED
 AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
  
 ___THE SYSTEM PROVIDED INDICATES
 LIMITATION# 9, NO ENHANCED
 FASTENING ALLOWED.
  
 31) S-101
 31A) PLANS INDICATE PLANS WERE CALCULATED TO ASCE 7-98
 SEE CHAPTER35REFERENCE STANDARDS FOR CORRECTION.
  
 32) 2ND REQUEST, PLEASE PROVIDE POSITIVE AND NEGATIVE
 WIND PRESSURES FOR THE INTERIOR ZONE AND THE END ZONES
 FOR THE OPENING SIZES 10'-100'WITH THE HEIGHT AND
 EXPOSURE ADJUSTMENT COEFFICIENTS. S-101SHOWS THE MAIN
 WIND FORCE RESISTING SYSTEM PRESSURES,NOT THE DESIGN
 WIND PRESSURES LISTED UNDER COMPONENTS AND CLADDING
 INCLUDE HEIGTH AND EXPOSURE
 COEFFICIENTS TABLE1609.6.2.1(4). PLEASE SHOW ON THE
 ELEVATIONS.
  
 33) COMPLIED AS NOTED.
  
 34) 2ND REQUEST,BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-02-01 Cont ID  
Sent By jwitmer Date 2007-02-01 Time 06:42 Rev Time 9.99
Received By jwitmer Date 2007-02-01 Time 06:41 Sent To  
Notes
2007-02-01 06:58:03 
  
 BUILDING PLAN REVIEW
 PERMIT: 06111067
 ADD: 2437 METROCENTRE BLVD
 CONT: AUTOBUILDERS
 TEL: (561)310-7735
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SPRINGHILL SUITES BY MARIOTT
 FIVE STORY/ 130 UNITS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) --- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS
 NULL & VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE
 OF COMMENCEMENT
 AT THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) FBC 1802.2.1 QUESTIONABLE SOILS,
 1802.2.1 QUESTIONABLE SOIL.
 WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN
 DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED,
 THE BUILDING OFFICIAL SHALL REQUIRE THAT THE NECESSARY
 INVESTIGATION BE MADE.
 SUCH INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS
 1802.4 THROUGH 1802.6 .
  
 4) WEST PALM BCH ADMINISTRATIVE CODE109.3.6
 THIS BUILDING IS CONSIDERED A THRESHOLD BUILDING,
 REQUIRING THREE SETS
 OF ALL DOCUMENTS TO BE SUBMITTED TO THE BUILDING
 DEPARTMENT, PLANS,
 REPORTS, SUBMITTALS AND OR PRODUCT APPROVALS.
  
 5) FL S. S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN
 CY CLASSIFICATION AS DEINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 STRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE
 ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE
 OF A BUILDING PERMIT FOR THE
 CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURL INSPECTION
 PLAN IS TO PROVIDE SPECIFIC INSPECTION
 PROCEDURES AND SCHEDULES SO THAT THE
 BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 6) WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 7) W.P.B. AMENDMENT 105.13.4.4 ALL
 PLANS FOR THE BUILDING WHICH ARE
 REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CON-
 TAIN A STATEMENT THAT, TO THE BEST OF
 THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE,
 THE PLANS AND SPECIFICATIONS COMPLY WITH
 THE APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 8) PLEASE NOTE:
 109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PERMORMED IN A MANNER
 SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS
 SUCH ACTIVITY IS PERMITTED TO AFFECT
 SAID PROPERTY PURSUANT TO A CONSENT BY
 THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE
 APPLICABLE PROPERTY OWNER.THIS INCLUDES
 BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF,
 DEBRIS, AND THE STORAGE OF CONSTRUCTION
 MATERIALS. NEW CONSTRUCTION ACTIVITY
 SHALL NOT ADVERSELY IMPACT HISTORIC
 SURFACE WATER DRAINAGE FLOWS SERVING
 ADJACENT PROPERTIES, & MAY REQUIRE
 SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS,
 AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR
 ITEMS, ON EXISTING PROPERTIES RESULTING
 IN A DECREASE IN EXCESS OF 800SQ FT OF
 PERMEABLE LAND AREA ON ANY PARCELL SHALL
 AS A PERMIT CONDITION, PROVIDE A
 PROFESSIONALLY PREPARED DRAINAGE PLAN
 CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 9) 109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 10) PFVS ARCHITECTURE PLANNING AND INTERIORS
 IS MISSING THE FIRMS CERTIFICATE OF AUTHORIZATION.
 481.219 F.S. CERTIFICATE OF AUTHORIZATION. THE TITLE
 BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL
 SERVICES, SHALL INCLUDE
 THE CERTIFICATE OF AUTHORIZATION
 NUMBER. ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 11) MISSING INFORMATION ON THE ARCHITECTS (PFVS)
 TITLEBLOCK,
 61G1-16.004 FL. ADMIN. CODE. PLANS
 PREPARED BY A REGISTERED ARCHITECT SHALL
 INCLUDE A TITLE BLOCK WHICH MUST:
 - STATE THE FIRM NAME, ADDRESS AND
 TELEPHONE NUMBER
 - STATE THE FIRM LICENSE NUMBER
 - STATE PROJECT NAME OR IDENTIFICATION
 - STATE DATE PREPARED
 - INCLUDE AN ORIGINAL SIGNATURE AND
 DATED SEAL
 - INCLUDE THE PRINTED NAME OF THE
 ARCHITECT SEALING THE PLANS
  
 12) SHEET G.000 THIS SHEET INDICATES NIELSEN STRUCTURAL
 ENGINEERING
 AS ONE OF THE FIRMS WORKING ON THIS PROJECT BUT THEY
 ARE NOT NOTED ON
 THE STRUCTURAL SHEETS? 106.1.2*
  
 13) SHEET G-000
 13A) THE PROJECT INDICATES THIS TO BE A (5) STORY, TYPE
 I-B SPRINKLERED BUILDING, THERE ARE NO PLANS FOR FIRE
 SPRINKLERS IN THE PLANS. FL S S 553.895(2) REQUIRES
 BUILDINGS 3 STORIES OR MORE TO HAVE FIRE SPINKLERS,
 SUBMIT PLANS FOR REVIEW BEFORE A PERMIT CAN BE ISSUED.
  
 14) SHEET A-401, PLEASE PROVIDE THE ELEVATIONS, CHANGE
 IN GRADE FROM UNDER THE PORTICO TO THE LOBBY, (DROP OFF
 AREA) PLANS ARE NOT CLEAR AS TO IF THERE IS A CURB OR
 ALL AT GRADE LEVEL. 11-4.5.2 CHANGES IN LEVEL.
  
 15) SHEET A-401, THE FRONT ENTRY DOORS (VESTIBULE)
 APPEAR TO BE HORIZONTAL SLIDING DOORS, PLEASE PROVIDE
 INFORMATION FOR MANUAL LY OPERATED (BREAK AWAY) IF LOSS
 OF POWER. SECTION 1008.1.3.3.
  
 16) SHEET A-101:
 16A) PLANS INDICATE 2 - 5 STORY STAIRWELLS THE DOOR
 SCHEDULE DOESN'T INDICATE 1 1/2 HR PROTECTIVES. PLEASE
 INDICATE IN HRS AND IN MINUTES THE OPENING PROTECTIVE
 RATING.707.4/ TABLE 715.3.
  
 16B) FIRE PUMP ROOM 132 ALSO REQUIRES 2 HR RATED WALLS
 SEE NFPA 20:5.1.12.1.1. OPENING PROTECTIVE FOR DOOR 1
 1/2 HR .TABLE 715.3.
  
 16C) ROOM # 160 DOMESTIC WATER HEATER ROOM INDICATES A
 SHAFT BUT NO WALL RATINGS ARE PROVIDED. 707.4
  
 16D) ROOM 136C LAUNDRY TERMINATION ROOM, THE ROOM
 REQUIRES A 1 HR FIRE RATING SHEET A-401 ENLARGED PLAN
 IS MISSING RATED WALLS.707.13.4.
 707.13.2 MATERIALS.
 A SHAFT ENCLOSURE CONTAINING A REFUSE OR LAUNDRY CHUTE
 SHALL BE CONSTRUCTED OF MATERIALS AS PERMITTED BY THE
 BUILDING TYPE OF CONSTRUCTION.
  
 16E) ROOM 136C LAUNDRY ROOM TERMINATION ROOM DOOR
 REQUIRES 3/4HR RATING SEE DOOR SCHEDULETABLE
 715.3/.707.13.4 TERMINATION ROOM.
 REFUSE AND LAUNDRY CHUTES SHALL DISCHARGE INTO AN
 ENCLOSED ROOM COMPLETELY SEPARATED FROM THE REMAINDER
 OF THE BUILDING BY CONSTRUCTION THAT HAS A
 FIRE-RESISTANCE RATING OF NOT LESS THAN 1 HOUR AND
 OPENINGS INTO THE TERMINATION ROOM SHALL BE PROTECTED
 BY OPENING PROTECTIVES HAVING A FIRE PROTECTION RATING
 OF NOT LESS THAN ? HOUR AND SHALL BE SELF-CLOSING OR
 AUTOMATIC-CLOSING UPON THE DETECTION OF SMOKE. REFUSE
 CHUTES SHALL NOT TERMINATE IN AN INCINERATOR ROOM.
 REFUSE AND LAUNDRY ROOMS THAT ARE NOT PROVIDED WITH
 CHUTES NEED ONLY COMPLY WITH TABLE 302.1.1 .
  
 16F) PLANS INDICATE THE USE OF BLOCK WALLS SEPERATING
 THE CORRIDORS FROM THE INDIVIDUAL SUITES SECTION 3A OR
 3B PLEASE PROVIDE THE STC RATING FOR WALLS.
 SEE A-401 ENLARGED PLAN. 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION ASSEMBLIES
 FOR PIPING; ELECTRICAL DEVICES; RECESSED CABINETS;
 BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR EXHAUST
 DUCTS SHALL BE SEALED, LINED, INSULATED OR OTHERWISE
 TREATED TO MAINTAIN THE REQUIRED RATINGS. THIS
 REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT ENTRANCE
 DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT FITTING TO
 THE FRAME AND SILL.
  
 16G) LAUNDRY CHUTE:707.13.6 AUTOMATIC FIRE SPRINKLER
 SYSTEM.
 AN APPROVED AUTOMATIC FIRE SPRINKLER SYSTEM SHALL BE
 INSTALLED IN ACCORDANCE WITH SECTION 903.2.10.2 .
 903.2.10.2 RUBBISH AND LINEN CHUTES.
 AN AUTOMATIC SPRINKLER SYSTEM SHALL BE INSTALLED AT THE
 TOP OF RUBBISH AND LINEN CHUTES AND IN THEIR TERMINAL
 ROOMS. CHUTES EXTENDING THROUGH THREE OR MORE FLOORS
 SHALL HAVE ADDITIONAL SPRINKLER HEADS INSTALLED WITHIN
 SUCH CHUTES AT ALTERNATE FLOORS. CHUTE SPRINKLERS SHALL
 BE ACCESSIBLE FOR SERVICING.
  
 16H) THE PLANS (A-401 ENLARGED) ALSO INDICATE SUITES
 104 & 106, THERE IS NO WALL TYPE IDENTIFICATION.
 PROVIDE THE STC RATING BETWEEN ROOM.
 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION
 ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; RECESSED
 CABINETS; BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR
 EXHAUST DUCTS SHALL BE SEALED, LINED, INSULATED OR
 OTHERWISE TREATED TO MAINTAIN THE REQUIRED RATINGS.
 THIS REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT
 ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT
 FITTING TO THE FRAME AND SILL.
  
 16I) THIS SAME SITUATION SHALL OCCUR BETWEEN SUITES
 BETWEEN FLOORS, SHOW COMPLIANCE WITH:
 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 16J) ENLARGED PLAN A-401 ELECTRIC ROOM 147 INDICATES
 THE USE OF SPANDRIAL GLASS THIS LOCATION? 106.1.2.
 ADDITIONAL INFORMATION.
  
 16K) PLEASE PROVIDE LAUNDRY SHUTE DETAILS: 707.13.2
 MATERIALS.
 A SHAFT ENCLOSURE CONTAINING A REFUSE OR LAUNDRY CHUTE
 SHALL BE CONSTRUCTED OF MATERIALS AS PERMITTED BY THE
 BUILDING TYPE OF CONSTRUCTION.
  
 16L) BOTH A-101 & A-401 SHOW A VENDING ROOM # 157 AND
 NO ACCESS. 106.1.2* ADDITIONAL INFO REQUIRED.
  
 16M) PLEASE PROVIDE CODE COMPLIANCE FOR HEADROOM
 CLEARENCE UNDER STAIRWELLS, 11-4.4.2 HEADROOM. WALKS,
 HALLS, CORRIDORS, PASSAGEWAYS, AISLES, OR OTHER
 CIRCULATION SPACES SHALL HAVE 80 INCHES (2030 MM)
 MINIMUM CLEAR HEAD ROOM [SEE FIGURE 11-8 (A)]. IF
 VERTICAL CLEARANCE OF AN AREA ADJOINING AN ACCESSIBLE
 ROUTE IS REDUCED TO LESS THAN 80 INCHES (2032 MM)
 (NOMINAL DIMENSION), A BARRIER TO WARN BLIND OR
 VISUALLY-IMPAIRED PERSONS SHALL BE PROVIDED [SEE FIGURE
 11-8 (C-1)].
  
 16N) SHEET A-101- A-105 ALL CORRIDORS WITH OCCUPANT
 LOAD GREATER THAN 10 (R-1) REQUIRES 1-HR RATED
 CORRIDORS WITH OPENING PROTECTIVES. PROVIDE
 DOOR IDENTIFICATION AND FIRE RATING. SEE SECTION
 715.3.
  
  
 16O) STAIRWELLS ARE MISSING STANDPIPES,905.1 GENERAL.
 STANDPIPE SYSTEMS SHALL BE PROVIDED IN ALL NEW
 BUILDINGS IN WHICH:
 1. THE HIGHEST FLOOR IS GREATER THAN 30 FEET (9144 MM)
 ABOVE THE LOWEST LEVEL OF FIRE DEPARTMENT VEHICLE
 ACCESS; OR
 2. THE HIGHEST FLOOR IS MORE THAN THREE STORIES ABOVE
 GRADE.
  
 16P) PLEASE PROVIDE INFORMATION FOR ELEVATOR CARS TO
 ACCOMMODATE AMBULANCE STRETCHER.
 3002.4 ELEVATOR CAR TO ACCOMMODATE AMBULANCE
 STRETCHER.
  
 16R) PLEASE PROVIDE INFORMATION FOR THE FIRE PUMP, SIZE
 OF PUMP, TYPE OF PUMP FUEL LOADS IF NOT ELECTRIC.
  
 IN BUILDINGS FOUR STORIES IN HEIGHT OR MORE, AT LEAST
 ONE ELEVATOR SHALL BE PROVIDED FOR FIRE DEPARTMENT
 EMERGENCY ACCESS TO ALL FLOORS. SUCH ELEVATOR CAR SHALL
 BE OF SUCH A SIZE AND ARRANGEMENT TO ACCOMMODATE A
 24-INCH BY 76-INCH (610 MM BY 1930 MM) AMBULANCE
 STRETCHER IN THE HORIZONTAL, OPEN POSITION AND SHALL BE
 IDENTIFIED BY THE INTERNATIONAL SYMBOL FOR EMERGENCY
 MEDICAL SERVICES (STAR OF LIFE). THE SYMBOL SHALL NOT
 BE LESS THAN 3 INCHES (76 MM) HIGH AND SHALL BE PLACED
 INSIDE ON BOTH SIDES OF THE HOISTWAY DOOR FRAME.
  
 176Q) STAIRWELL# 2 IS MISSING THE STANDPIPE:
 905.1 GENERAL.
 STANDPIPE SYSTEMS SHALL BE PROVIDED IN ALL NEW
 BUILDINGS IN WHICH:
 1. THE HIGHEST FLOOR IS GREATER THAN 30 FEET (9144 MM)
 ABOVE THE LOWEST LEVEL OF FIRE DEPARTMENT VEHICLE
 ACCESS; OR
 2. THE HIGHEST FLOOR IS MORE THAN THREE STORIES ABOVE
 GRADE
  
 17) SHEET A-402:
 17A) DETAIL# 7 LAUNDRY ACCESS ROOM INDICATES THE USE OF
 A 2 HR RATED WALL BUT NO SOUND TRANSMITION RATING IS
 PROVIDED? 1207.2.
  
 17B) SHEET A-402 DETAIL# 7 ALSO INDICATES A RECESSED
 FIRE EXTINGUISHER CABINET, HOW IS THE 2 HR RATING BEING
 MAINTAINED? 106.1.2*
  
 17C) SHEET A-402 DETAIL# 7 LAUNDRY ROOM ACCESS DOOR,
 THE SCHEDULE NEEDS TO BE IN MINUTES AND HRS. TABLE
 715.3.
  
 17D) SHEET A-402 DETAIL# 1, ELEVATOR LOBBY DOORS ARE
 NOT IDENTIFIED, FLOORS 2-5 INDICATE AS DOOR *34, DOOR
 SCHEDULE INDICATES "C" LABEL REQUIRES
 RATING ACCORDING TO TABLE 715.3. THESE DOORS ALSO
 INDICATE HOLD OPEN DEVICES, PLANS DO NOT INDICATE IF
 TIED TO SMOKE ALARM, SPRINKLER, ETC
  
 17E) SHEET A-402 DETAILS 3,4& 5 ALL INDICATE SHAFTS
 WITH WALLS NOT RATED (AO). 707.4.
  
 18) A-201- A-202 ELEVATIONS INDICATE THE USE OF EFIS
 TRIM ABOVE 40' ABOVE GRADE. BUILDING TYPE I-B.SHEETS
 A-301, A-302 & A-303.
 1406.2.2 ARCHITECTURAL TRIM.
 IN BUILDINGS OF TYPE I, II, III AND IV CONSTRUCTION
 THAT DO NOT EXCEED THREE STORIES OR 40 FEET (12 192 MM)
 IN HEIGHT ABOVE GRADE PLANE, EXTERIOR WALL COVERINGS
 SHALL BE PERMITTED TO BE CONSTRUCTED OF WOOD WHERE
 PERMITTED BY SECTION 1405.4 OR OTHER EQUIVALENT
 COMBUSTIBLE MATERIAL. COMBUSTIBLE EXTERIOR WALL
 COVERINGS, OTHER THAN FIRE-RETARDANT-TREATED WOOD
 COMPLYING WITH SECTION 2303.2 FOR EXTERIOR
 INSTALLATION, SHALL NOT EXCEED 10 PERCENT OF AN
 EXTERIOR WALL SURFACE AREA WHERE THE FIRE SEPARATION
 DISTANCE IS 5 FEET (1524 MM) OR LESS. ARCHITECTURAL
 TRIM THAT EXCEEDS 40 FEET (12 192 MM) IN HEIGHT ABOVE
 GRADE PLANE SHALL BE CONSTRUCTED OF APPROVED
 NONCOMBUSTIBLE MATERIALS AND SHALL BE SECURED TO THE
 WALL WITH METAL OR OTHER APPROVED NONCOMBUSTIBLE
 BRACKETS
  
 19) A-303 PARAPET DETAIL DOESN'T INDICATE ANY FASTENING
 SYSTEM NOR STRUCTURAL INFORMATION NOR REFRENCE ANY
 STRUCTURAL SHEETS? 106.1.2 ADD INFO REQUIRED.
  
 20) A-501 & A-502, PARAPET DETAIL DOESN'T INDICATE ANY
 FASTENING SYSTEM NOR STRUCTURAL INFORMATION NOR
 REFRENCE ANY STRUCTURAL SHEETS? 106.1.2 ADD INFO
 REQUIRED.
  
 21) SHEET A-106 ROOF PLAN LEFT SIDE OF THE SHEET
 INDICATES A DOORWAY ONTO THE FLAT ROOF, SHEET A-105
 STORAGE ROOM BELOW DOESN'T INDICATE STAIRS TO THE ROOF
 LEVEL.SHEET A-105,NOTE 6 INDICATES A STEEL LADDER.
 1009.12 ACCESS TO ROOF.
 BUILDINGS FOUR STORIES OR MORE IN HEIGHT, EXCEPT THOSE
 WITH A ROOF SLOPE GREATER THAN 4:12, SHALL BE PROVIDED
 WITH A STAIRWAY TO THE ROOF. SUCH STAIRWAY SHALL BE
 MARKED AT STREET AND FLOOR LEVELS WITH A SIGN
 INDICATING THAT IT CONTINUES TO THE ROOF. WHERE ROOFS
 ARE USED FOR ROOF GARDENS OR FOR OTHER PURPOSES,
 STAIRWAYS SHALL BE PROVIDED AS REQUIRED FOR SUCH USE OR
 OCCUPANCY.
 CODE COMMENTARY: IN BUILDINGS FOUR OR MORE STORIES
 HIGH, ROOF THAT ARE NOT USED FOR HABITABLE PURPOSES
 MUST BE MADE ACCESSIBLE BY CONVENTIONALSTAIRWAYS. TWO
 REASONS FOR THIS ARE ACCESS FOR ROOF OR EQUIPMENT
 REPAIR AND FIRE DEPARTMENT ACCESS DURING A FIRE EVENT.
  
 22) A-105 THIS SAME NOTE INDICATES 2'X2' ACCESS PANELS
 2ND, 3RD & 4TH FLOORS, FOR WHAT PURPOSE? 106.1.2
 ADDITIONAL INFO REQUIRED.
  
 23) SHEET A-106 ROOF DRAINS AND OVERFLOW DRAINS: WHERE
 IS THE OUTLET FOR THE OVERFLOW ROOF DRAINS? 106.1.2.ADD
 INFO.
  
 24) A-402 WATER HEATER ROOMS VS THE END ELEVATIONS
 A-201 & A-202 THE END VIEWS INDICATE (2) LOUVERS ONE
 WILL END UP IN THE 2 HR FIRE RATED STAIRWAY,
 ARE THESE FOR THE GAS FIRED WATERHEATERS? IF SO HOW
 WILL THE LOUVER LOCATED IN THE STAIRWELL BE SEPERATED
 FROM THE STAIRWELL?
  
 25) A-604 & A-605 BOTH INDICATE THE USE OF WOOD BUCKS
 FOR WINDOWS AND DOORS. PLANS DO NOT INDICATE HOW THE
 BUCKS ARE TO BE FASTENED,
 1714.5.4.1 ANCHORING REQUIREMENTS.
 WINDOW AND DOOR ASSEMBLIES SHALL BE ANCHORED IN
 ACCORDANCE WITH THE PUBLISHED MANUFACTURER?S
 RECOMMENDATIONS TO ACHIEVE THE DESIGN PRESSURE
 SPECIFIED. SUBSTITUTE ANCHORING SYSTEMS USED FOR
 SUBSTRATES NOT SPECIFIED BY THE FENESTRATION
 MANUFACTURER SHALL PROVIDE EQUAL OR GREATER ANCHORING
 PERFORMANCE AS DEMONSTRATED BY ACCEPTED ENGINEERING
 PRACTICE.
  
 1714.5.4.2 MASONRY, CONCRETE OR OTHER STRUCTURAL
 SUBSTRATE.
 WHERE THE WOOD SHIM OR BUCK THICKNESS IS LESS THAN 1 1
 / 2 INCHES (38 MM), WINDOW AND DOOR ASSEMBLIES SHALL BE
 ANCHORED THROUGH THE MAIN FRAME OR BY JAMB CLIP OR
 SUBFRAME SYSTEM, IN ACCORDANCE WITH THE MANUFACTURER?S
 PUBLISHED INSTALLATION INSTRUCTIONS. ANCHORS SHALL BE
 SECURELY FASTENED DIRECTLY INTO THE MASONRY, CONCRETE
 OR OTHER STRUCTURAL SUBSTRATE MATERIAL. UNLESS
 OTHERWISE TESTED, BUCKS SHALL EXTEND BEYOND THE
 INTERIOR FACE OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS PROVIDED. SHIMS SHALL BE
 MADE FROM MATERIALS CAPABLE OF SUSTAINING APPLICABLE
 LOADS, LOCATED AND APPLIED IN A THICKNESS CAPABLE OF
 SUSTAINING APPLICABLE LOADS. ANCHORS SHALL BE PROVIDED
 TO TRANSFER LOAD FROM THE WINDOW OR DOOR FRAME TO THE
 ROUGH OPENING SUBSTRATE.
 WHERE THE WOOD BUCK THICKNESS IS 1 1 / 2 INCHES (38 MM)
 OR GREATER, THE BUCK SHALL BE SECURELY FASTENED TO
 TRANSFER LOAD TO THE MASONRY, CONCRETE OR OTHER
 STRUCTURAL SUBTRATE AND THE BUCK SHALL EXTEND BEYOND
 THE INTERIOR FACE OF THE WINDOW OR DOOR FRAME. WINDOW
 AND DOOR ASSEMBLIES SHALL BE ANCHORED THROUGH THE MAIN
 FRAME OR BY JAMB CLIP OR SUBFRAME SYSTEM OR THROUGH THE
 FLANGE TO THE SECURED WOOD BUCK IN ACCORDANCE WITH THE
 MANUFACTURER?S PUBLISHED INSTALLATION INSTRUCTIONS.
 UNLESS OTHERWISE TESTED, BUCKS SHALL EXTEND BEYOND THE
 INTERIOR FACE OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS PROVIDED. SHIMS SHALL BE
 MADE FROM MATERIALS CAPABLE OF SUSTAINING APPLICABLE
 LOADS, LOCATED AND APPLIED IN A THICKNESS CAPABLE OF
 SUSTAINING APPLICABLE LOADS. ANCHORS SHALL BE PROVIDED
 TO TRANSFER LOAD FROM THE WINDOW OR DOOR FRAME ASSEMBLY
 TO THE SECURED WOOD BUCK.
  
 26) SHEET A-606 PUBLIC RESTROOMS INDICATE THE USE OF
 V.W.C. ? 1210.2 WALLS.
 WALLS WITHIN 2 FEET (610 MM) OF URINALS AND WATER
 CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 SURFACE, TO A HEIGHT OF 4 FEET (1219 MM) ABOVE THE
 FLOOR, AND EXCEPT FOR STRUCTURAL ELEMENTS, THE
 MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE THAT IS
 NOT ADVERSELY AFFECTED BY MOISTURE.
  
 27) A-701 THE STAIRWELL PLAN DOESN'T INDICATE THE
 HANDRAIL EXTENDING PAST THE FIRST RISER ON THE FIRST
 FLOOR.
 11-4.9.4(2) AT THE BOTTOM, THE HANDRAIL SHALL CONTINUE
 TO SLOPE FOR A DISTANCE OF THE WIDTH OF ONE TREAD FROM
 THE BOTTOM RISER; THE REMAINDER OF THE EXTENSION SHALL
 BE HORIZONTAL [SEE FIGURE 11-19 (C) AND FIGURE 11-19
 (D)]. HANDRAIL EXTENSIONS SHALL COMPLY WITH SECTION
 11-4.4 .
  
 28A) SHEET A-702 DETAIL# 1,PLEASE PROVIDE VENTING FOR
 ELEVATORS:
 3004.1 VENTS REQUIRED.
 HOISTWAYS OF ELEVATORS AND DUMBWAITERS PENETRATING MORE
 THAN THREE STORIES SHALL BE PROVIDED WITH A MEANS FOR
 VENTING SMOKE AND HOT GASES TO THE OUTER AIR IN CASE OF
 FIRE.
 3004.2 LOCATION OF VENTS.
 VENTS SHALL BE LOCATED BELOW THE FLOOR OR FLOORS AT THE
 TOP OF THE HOISTWAY, AND SHALL OPEN EITHER DIRECTLY TO
 THE OUTER AIR OR THROUGH NONCOMBUSTIBLE DUCTS TO THE
 OUTER AIR. NONCOMBUSTIBLE DUCTS SHALL BE PERMITTED TO
 PASS THROUGH THE ELEVATOR MACHINE ROOM PROVIDED THAT
 PORTIONS OF THE DUCTS LOCATED OUTSIDE THE HOISTWAY OR
 MACHINE ROOM ARE ENCLOSED BY CONSTRUCTION HAVING NOT
 LESS THAN THE FIRE PROTECTION RATING REQUIRED FOR THE
 HOISTWAY. HOLES IN THE MACHINE ROOM FLOORS FOR THE
 PASSAGE OF ROPES, CABLES OR OTHER MOVING ELEVATOR
 EQUIPMENT SHALL BE LIMITED SO AS NOT TO PROVIDE GREATER
 THAN 2 INCHES (51 MM) OF CLEARANCE ON ALL SIDES.
  
 28B) A-702 PLANS DO NOT INDICATE REQUIREMENTS FOR
 BRAILLE CHARACTERS AT HOISTWAY ENTRANCES. 11-4.10.5
 RAISED AND BRAILLE CHARACTERS ON HOISTWAY ENTRANCES.
 ALL ELEVATOR HOIST WAY ENTRANCES SHALL HAVE RAISED AND
 BRAILLE FLOOR DESIGNATIONS PROVIDED ON BOTH JAMBS. THE
 CENTERLINE OF THE CHARACTERS SHALL BE 60 INCHES (1525
 MM) ABOVE FINISH FLOOR. SUCH CHARACTERS SHALL BE 2
 INCHES (50 MM) HIGH AND SHALL COMPLY WITH SECTION
 11-4.30.4 . PERMANENTLY APPLIED PLATES ARE ACCEPTABLE
 IF THEY ARE PERMANENTLY FIXED TO THE JAMBS (SEE FIGURE
 11-20 ).
  
 29A) 1609.1.4 PROTECTION OF OPENINGS.
 IN WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IN THE LOWER 60 FEET (18.3 M) IN
 BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED
 OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IS IMPACT RESISTANT OR PROTECTED WITH AN
 IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND
 ASTM E 1996, OR MIAMI-DADE TAS 201, 202
 AND 203 REFERENCED THEREIN AS FOLLOWS:
 1. GLAZED OPENINGS LOCATED WITHIN 30
 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST.
 2. GLAZED OPENINGS LOCATED MORE THAN
 30 FEET (9.1 M) ABOVE GRADE SHALL MEET
 THE PROVISIONS OF THE SMALL MISSILE
  
 29B) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
 29C) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.]
  
 29D) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOW
 FIXED
 SINGLE HUNG
 MULLION
 B) GLAZED DOORS
 AUTOMATIC HORIZONTAL SLIDING DOORS
 EXTERIOR HOLLOW METAL DOORS
 C) LOUVERS
 D) PANEL WALL SYSTEMS-STOREFRONT,
 SOFFITS- HARDI SOFFIT BOARD
 E) STRUCTURAL COMPONENTS- TRUSS ANCHORS
 F) ROOF ASSEMBLIES
 FLAT ROOFS- MODIFIED/ BITUMEN, EPDM ROOFING
 SLOPED:UNDERLAYMENTS, METAL ROOFS
 G) THIS ROOF IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
  
 ___ CONTRACTOR DID NOT PROVIDE THE MEAN
  
 ROOF HEIGHT.
  
 ___ CONTRACTOR DID NOT INDICATE THE ROOF
 PITCH.
  
 ___ CONTRACTOR FAILED TO INDICATE WHICH
 SYSTEM TO BE USED.
  
 ___ THE SYSTEM PROVIDED HAS A LOW
 PRESSURE FOR ZONE ___ .
  
 ___ THE SYSTEM PROVIDED STATES
 LIMITATION# 7, SHOULD THE FASTENER
 RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE
 BUILDING OFFICIAL, A REVISED
 FASTENER SPACING, PREPARED , SIGNED
 AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
  
 ___ THE SYSTEM PROVIDED INDICATES
 LIMITATION# 9, NO ENHANCED
 FASTENING ALLOWED.
  
 31) S-101
 31A) PLANS INDICATE PLANS WERE CALCULATED TO ASCE 7-98
 SEE CHAPTER35 REFERENCE STANDARDS FOR CORRECTION.
  
 32) PLEASE PROVIDE POSITIVE AND NEGATIVE PRESSURES FOR
 THE INTERIOR ZONES AND END ZONES FOR OPENING SIZES 10'
 -100'
 WITH HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENTS.
 1606.2D.
  
 33) ASEPERATE PERMIT IS REQUIRED FOR THE POOL, POOL
 EQUIPMENT BUILDING , POOL FENCING AND SIGNAGE.
  
 34) BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 17 Status P Date 2009-10-30 Cont ID  
Sent By dpalmer Date 2009-10-30 Time 12:58 Rev Time 0.00
Received By dpalmer Date 2009-10-30 Time 12:58 Sent To PC
Notes
2009-10-30 12:58:59REDLINED PLANS:
  
 ACCESS CONTROLS ARE STILL REQUIRED TO BE UNDER SEPARATE
 PERMIT. NFPA-101 CHPATER 7.

Review Stop E ELECTRICAL
Rev No 16 Status F Date 2009-09-20 Cont ID  
Sent By dpalmer Date 2009-09-20 Time 12:25 Rev Time 0.00
Received By dpalmer Date 2009-09-20 Time 12:25 Sent To  
Notes
2009-09-20 12:25:46 
  
 ** DENIED **
  
 ** NOTES FROM PREVIOUS REVIEW ARE STILL IN NEED OF
 REVISING.
  
 1) NOTE: SEE COMMENT #2 FROM PREVIOUS REVIEW. NO ACCESS
 CONTROL SYSTEM PERMIT AND PLANS HAVE BEEN SUBMITTED TO
 DATE. IF A SYSTEM HAS BEEN INSTALLED IT WAS DONE
 WITHOUT REVIEW FOR CODE COMPLIANCE AND PERMIT.
 PLANS DO NOT SHOW COMPLIANCE FOR ANY SUCH SYSTEM ONLY
 NOTES FOR FUTURE.
 **ON PREVIOUS REVIEW IT WAS NOTED THAT REVIEW FOR
 NFPA-101 CHAPTER 7 AND OTHER APPLICABLE CODES HAVE NOT
 BEEN DONE.
 ONE EXAMPLE OF NON-CODE COMPLIANCE IS THE FACT THAT A
 JUNCTION BOX FOR FUTURE SYSTEM IS SHOWN IN STAIRS WHICH
 IS NOT PERMITTED PER FBC 1019.1.2
 ACCESS CONTROLS INSIDE STAIRS IS NOT PART OF THE
 STAIRS. PLEASE ADDRESS WITH BUILDING REVIEWER AND FIRE
 MARSHAL CHIEF CARSILLO.
  
 2) NOTE: IT WAS REQUESTED ON PREVIOUS REVIEW TO SUBMIT
 A COMPLETE REVISED PLAN WITH ALL CIRCUITING ON PLANS TO
 BE REVISED AND COORDINATED WITH REVISED SUBMITTED PANEL
 SCHEDULES. SOME REVISED PLANS WERE SUBMITTED ALONG WITH
 RESPONSE SHEETS FROM DESIGN TEAM. THE RESPONSE SHEETS
 DO NOT ACTUALLY RESPOND TO PREVIOUS COMMENTS THEY ONLY
 STATE CHANGES WHICH WERE MADE ON SPECIFIC SHEETS. THE
 RESPONSE ONLY INDICATES CHANGES TO THE FOLLOWING
 SHEETS:
 E001,
 E102,
 E105,
 E401,
 E402,
 E501,
 E504, AND 504A
  
 ** IT SHOULD BE NOTED THAT SOME OF THE PREVIOUS
 COMMENTS WERE NOT ACTUALLY RESPONDED TO BY DESIGN TEAM
 AND PLANS WERE NOT REVISED/CORRECTED EITHER. PLEASE SEE
 PREVIOUS NOTES #16 AND #18 FOR EXAMPLE; SEE NOTES
 BELOW.
  
  
 WHAT ABOUT SHEETS E103, E 411, 412 ??
 PREVIOUS NOTES MENTIONED TO REVISE PLANS FOR ALL
 CIRCUITING. REVIEW FOR LOAD CALCULATIONS FOR EXAMPLE
 CAN NOT BE DONE UNTIL ALL CIRCUITING IS REVISED AND
 COORDINATED WITH PLANS SUBMITTED.
  
 A) SEE LATEST REVISED SHEET E-103 WHICH WAS NOT
 SUBMITTED OR IN NOTED IN LETTER FROM DESIGN TEAM. THIS
 SHEET HOWEVER IS ON FILE.
 PLANS INDICATE CIRCUIT R-151 SHOWN FOR CORRIDOR
 LIGHTING HOWEVER REVISED PANEL SCHEDULE FOR PANEL R1
 INDICATES CIRCUIT 151 AS THE BREAK ROOM RECEPTACLE.
 REVISED SHEET 401 DOES INDICATE THIS HOWEVER BASED ON
 E103, THIS CIRCUIT IS SHOWN FOR BOTH LOCATIONS. THIS IS
 NOT POSSIBLE.
  
 B) SEE LATEST REVISED SHEET E-103 WHICH WAS NOT
 SUBMITTED OR IN NOTED IN LETTER FROM DESIGN TEAM. THIS
 SHEET HOWEVER IS ON FILE.
 PLEASE SEE CIRCUIT R1-149 WHICH PER E103 INDICATES THIS
 AS LIGHTING FOR STAIRS. HOWEVER BASED ON REVISED R1
 PANEL SCHEDULE R149 IS SHOWN FOR DISPOSAL.
  
 C) SEE LATEST REVISED SHEET E-103 WHICH WAS NOT
 SUBMITTED OR IN NOTED IN LETTER FROM DESIGN TEAM. THIS
 SHEET HOWEVER IS ON FILE. PLEASE SEE CIRCUIT M1-48
 SHOWN ON PLANS AS EXTERIOR LIGHTS. AS NOTED ON PREVIOUS
 REVIEW PANEL M1 IS A 42 CIRCUIT PANEL AND THERE ARE NO
 CIRCUITS ABOVE 42 LISTED.
  
 D) PLEASE REVISE THE LATEST ROOM PLANS FOR ALL
 RECEPTACLES AND LOCATIONS. REVISED CIRCUITING FOR
 ELECTRICAL NEEDS BE REVIEWED FOR CODE COMPLIANCE. IT
 SHOULD BE NOTED THAT CIRCUITS SUCH AS R*147 ON LATEST
 REVISED FILE SET OF PLANS ON SHEET E104 IS FOR CORRIDOR
 LIGHTS ON MULTIPLE FLOORS HOWEVER PER LATEST REVISED R*
 SCHEDULES, THIS IS ACTUALLY NOTED FOR ROOM MICROWAVES.
  
 E) PLEASE SEE LATEST REVISED PANELS R* R1-R5 INDICATE
 CIRCUIT R*164 AS MULTIPLE DIFFERENT CIRCUITS YET THE
 LATEST REVISED PLANS ON FILE FOR SHEET E104 INDICATES
 ALL R* 164 BEING TYPICAL TO ELEVATOR LOBBY LIGHTS.
 OTHERS LISTED ARE * VENDING MACHINE*, EXERCISE ROOM
 RECEPTACLES*, * HALL RECEPTACLE, * ENG/MAIN RECEPTACLE.
 ETC.
  
 *** BASED ON NO REVISED SHEETS SUBMITTED FOR THE ABOVE
 LISTED, REVIEW FOR MINIMUM CODE COMPLIANCE FOR MANY
 OTHER CIRCUITS, LOAD CALCULATIONS, PANELS BEING ETC CAN
 NOT BE DONE AT THIS TIME. PLEASE SUBMIT A COMPLETE SET
 OF REVISED PLANS SO THAT REVISED PLANS CAN BE REVIEWED.
 THE ABOVE ARE SOME EXAMPLES AND ARE NOT ALL AS PLANS ON
 FILE ARE SUBSTANTIALLY DIFFERENT FROM REVISED PANELS
 AND LOAD CALCULATIONS SUBMITTED.
  
 ** 408.4, 220 UNDER 2002 NEC 220.3, 220.11, 220.12,
 220.14 ETC
  
 3) NOTE: NEW COMMENT EVEN THOUGH FBC CHAPTER 11 WAS
 NOTED ON ORIGINAL REVIEWS. ALL AREAS WHICH ARE ADA
 ACCESSIBLE NEED TO MEET FBC 11-4.27.4 FOR CONTROL
 DEVICES. THE ORIGINAL PLANS MENTION TWIST TIMERS IN
 GUEST LAUNDRY ROOMS. ARE ALL OF THESE ROOMS ADA?
 GUEST LAUNDRY AREAS WHICH ARE ADA NEED TO MEET SECTION
 ABOVE. IT SHOULD BE VERIFIED AS IT IS UNDERSTOOD BY
 THIS REVIEWER, WHAT IS SHOWN ON PLANS AND INSTALLED MAY
 NOT MEET SECTION. TYPE OF DEVICE AND ACCESSIBILITY IS
 KEY TO MEETING MINIMUM COMPLIANCE.
  
 4) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENT #16. NO
 RESPONSE FROM DESIGN TEAM AND RISER SHEET WAS NOT
 REVISED.
 PLEASE REVISE VOLTAGE DROP CALCULATIONS TO COORDINATE
 WITH THE REVISED FEEDERS FOR ALL PANELS. SEVERAL WERE
 REVISED TO ALUMINUM YET THE CALCULATIONS STILL INDICATE
 12.9 FOR CONSTANT IN CALCULATIONS.
 ANOTHER WOULD BE FEEDER SIZES. EXAMPLE WOULD BE M-5.
 PER MDP THE CONDUCTORS ARE 4/0 ALUMINUM YET THE VOLTAGE
 DROP CALCULATIONS INDICATE 1/0 COPPER.
 ANOTHER WOULD BE PANEL H-5 AS SPECIFICALLY NOTED ON
 PREVIOUS REVIEW. MDP STILL INDICATES 300MCM ALUMINUM
 YET CALCULATIONS CLEARLY STILL INDICATE 500MCM COPPER.
 13-413.1ABC.1,13-413.1.ABC.1.1,13-413.1.ABC.1.2, NEC
 310.16, TABLES IN CHAPTER 9
  
 5) NOTE: PLEASE SEE THAT NO RESPONSE TO PREVIOUS REVIEW
 COMMENT #18 WAS SUBMITTED AND NO REVISED SHEET E503 WAS
 SUBMITTED.
  
 6) NOTE: PLEASE SEE THAT NO RESPONSE WAS MADE TO
 PREVIOUS COMMENT #17. SOME SHEETS WERE SUBMITTED AND
 REVISED HOWEVER BASED ON COMMENTS ABOVE THIS WAS NOT
 ADDRESSED. HOUSE LOADS ON PANEL SCHEDULES CAN NOT BE
 CONFIRMED AS MEETING MINIMUM CODE IF THE PLANS DO NOT
 COORDINATE.
 PLEASE RESPOND, REVISE AND SUBMIT COMPLETED PLANS.
 220,310,240, 408.4ETC
  
 7) NOTE: AS STATED IN PREVIOUS REVIEW, SHEET E501
 STATES HOUSE PANEL M1 HAS *0* AS THE LOAD FOR LIGHTING.
 THIS IS NOT POSSIBLE WHEN THE LIGHTING PLANS SUCH AS
 E103 STILL INDICATE HOUSE LIGHTING CIRCUITS TO M1
 PANEL.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 15 Status F Date 2009-08-02 Cont ID  
Sent By dpalmer Date 2009-08-02 Time 12:01 Rev Time 0.00
Received By dpalmer Date 2009-08-02 Time 08:14 Sent To PC
Notes
2009-08-02 12:02:17** DENIED REVIEW OF REVISIONS FOR FINAL **
  
 FINAL REVISIONS SUBMITTED FOR SPRING HILL SUITES.
  
 1) NOTE: IN THE INITIAL AND SUBSEQUENT REVIEWS
 SUBMITTED CIRCUITING ON PLANS FOR LIGHTING, RECEPTACLES
 AND OTHER ITEMS ARE GONE OVER FOR GENERAL MINIMUM CODE
 COMPLIANCE FOR LOADS, SIZING OF BRANCH CIRCUITS ETC.
 THE ACTUAL CIRCUITING IS ALWAYS KNOWN AS AN ITEM WHICH
 WILL BE REVISED DURING THE PROJECT BY THE ELECTRICAL
 CONTRACTOR. ALL FINAL PLANS SUBMITTED AS RECORD
 DOCUMENTS NEED TO HAVE ALL CIRCUITING UPDATED AND
 COORDINATED. THE LOADS NEED TO BE REVISED AS WELL AS
 OVER CURRENT PROTECTION ETC AS NEEDED. THE FOLLOWING
 NOTES ARE BASED ON MANY ITEMS ON PLANS WHICH DO NOT
 COORDINATE.
  
 ** PLEASE SEE 408.4 IN THE NEC. THIS IS THE SECTION FOR
 MANY OF THE NOTES BELOW WITH RESPECT TO CIRCUITING AND
 PANEL SCHEDULE INCONSISTENCIES.
 ALL CIRCUITING IS TO BE SPECIFIC TO ROOMS AND AREAS IN
 WHICH THEY FEED. THE USE OF *RECEPTACLES* OR *LIGHTING*
 IS NOT ACCEPTABLE. ALPHA AND/OR NUMERIC DESIGNATIONS
 MAY BE USED FOR LOCATIONS. A DESCRIPTION SUCH AS *
 LOBBY RECEPTS EAST* OR ROOM 101 LIGHTS, ROOM 117
 RECEPTS OR OTHER TYPES OF DESIGNATIONS IS ACCEPTABLE.
 STATING *RECEPTACLES*, *LIGHTING* COULD MEAN ANY
 RECEPTACLES OR LIGHTING ANYWHERE IN THE BUILDING.
  
 THERE ARE ALSO ITEMS WHICH WERE REVISED DURING THE
 PROJECT WHICH WERE NOT INDICATED AS BEING A REVISION.
 SOME ARE NOW SHOWN NOT MEETING MINIMUM CODE COMPLIANCE.
 THERE ARE ALSO NOTES BELOW FOR THESE ITEMS.
  
 ***** IMPORTANT ******
 PLEASE BE AWARE THAT MANY EXAMPLES WILL BE GIVEN BELOW
 HOWEVER IT SHOULD BE KNOWN THAT THESE ARE ONLY EXAMPLES
 AND NOT *ALL* ITEMS WHICH DO NOT COORDINATE. THERE ARE
 MANY OTHER ITEMS/CIRCUITS NOT NOTED. REVIEW IS NOT
 BASED ON A COMPLETE *PUNCH-LIST* OF ALL CIRCUITING
 WHICH NEEDS TO BE ADDRESSED.
  
 2) NOTE: ORIGINAL PLANS INCLUDING THIS SET OF PLANS
 INDICATES J-BOXES AT MANY LOCATIONS SUCH AS EXTERIOR
 DOORS, STAIRS, AND OTHER LOCATIONS FOR *ACCESS CONTROL
 SYSTEM* ALSO KNOWN AS CARD READER SYSTEM TO BE BY
 OTHERS. KEY NOTES #8 ON E001 AND KEYNOTE #1 ON E401 ARE
 EXAMPLES OF TWO LOCATIONS OF THESE NOTES.
 TO DATE OF THIS REVIEW NO PERMIT APPLICATION, PLANS OR
 REVIEW FOR CARD READER ACCESS CONTROLS SYSTEM FOR THIS
 LOCATION AS BEEN SUBMITTED FOR REVIEW. THERE ARE NOTES
 ON PLANS WHICH MENTION ACCESS CONTROLS AND SOME
 CONNECTIONS TO THE FIRE ALARM SYSTEM HOWEVER IT IS ALSO
 NOTED TO BE DONE BY OTHERS.
 REVIEW FOR LIFE SAFETY REQUIREMENTS PER NFPA-101
 CHAPTER 7 AND OTHER APPLICABLE CODES HAS NOT BEEN DONE.
  
  
 3) NOTE: PLEASE SEE E-401. PLEASE SEE BREAK ROOM WHICH
 INDICATES TWU-1 CIRCUITED TO H1 1,3, HOWEVER PANEL
 SCHEDULE FOR THIS IS SHOWN AS SPARE.
  
 4) NOTE: PLEASE SEE H1 SCHEDULE AS ALL TWU1 AND TWU2
 UNITS NOTED ON CIRCUITS 2-32 NEED TO BE SPECIFIC TO
 ROOMS/LOCATIONS.
  
 5) NOTE: PLEASE SEE E-401. PLEASE SEE OTHER EQUIPMENT
 IN THIS AREA SUCH AS CONDENSER PUMP FOR FCU#4 WHICH IS
 NOTED TO CIRCUIT M1-7, YET THE PANEL SCHEDULE FOR THIS
 SAME CIRCUIT IS FOR FCU#5.
  
 6) NOTE: PLEASE SEE E-401. FCU#4 SHOWN AS M1-1,3,5 YET
 PANEL SCHEDULE INDICATES THIS AS ONLY CIRCUIT 1,3. IS
 THIS A 2-POLE OR 3-POLE UNIT? THIS MAY ALSO AFFECT LOAD
 CALCULATIONS DEPENDING ON UNIT.
  
 7) NOTE: THE PANEL SCHEDULE FOR POOL PANEL *P* STATES
 MANY ITEMS AS *FUTURE* AND WHEN PERMITTING FOR BUILDING
 THIS WAS THE CASE. HOWEVER AT THIS TIME THE POOL PERMIT
 HAS BEEN DONE AND CIRCUITING SHOULD BE KNOWN. SEE NEXT
 COMMENT.
 WHAT ABOUT ACTUAL POOL LIGHT FIXTURES?
  
  
 8) NOTE: PLEASE SEE SITE LIGHTING PLAN E-001 WHICH
 INDICATES POOL LIGHTS AS CIRCUITS 1,3, YET THE PANEL
 SCHEDULE SHOWS THIS AS BEING A PUMP AND NOT LIGHTS.
  
 9) NOTE: PLEASE SEE SHEET E102 AND PANEL SCHEDULE
 SHEETS AS THERE ARE SEVERAL ITEMS WHICH NEED TO BE
 UPDATED. SHEET E102 SHOWS TYPICAL HOWEVER MANY OF THE
 ROOMS AND LOCATIONS ARE NOT SHOWN ACCURATE ON PANEL
 SCHEDULE. 408.4, 310.16, 220 ETC
  
 A) SHEET 102, ROOM *28, INDICATES H*55, 57 YET THE
 PANEL SCHEDULE FOR H5 55,57 INDICATES ROOM 527.
  
 B) SHEET 102, ROOM *11 INDICATES H* 22,24, YET THE
 PANEL SCHEDULE FOR H5 22,24 IS FOR ROOM 512.
  
 **THIS IS THE SAME FOR ALL ROOMS AND ALL LOCATIONS. THE
 TYPICAL ROOM DESIGNATIONS ARE NOT ACCURATE.
  
 C) SHEET E102, ROOM *24, INDICATES R*-127, 12. YET THE
 PANEL SCHEDULE FOR R5, CIRCUIT #12 FOR EXAMPLE
 INDICATES COFFEE RECEPTACLE IN ROOM 504. THIS IS THE
 OTHER END OF THE FLOOR.
 ROOM #504 DOES NOT SHOW ANY OF THESE CIRCUITS.
  
 D) SHEET E102, CIRCUIT R5-122, 124 ON PLANS ROOM *523,
 YET PANEL SCHEDULE FOR R5-122,124 IS FOR ROOM 524.
  
 10) NOTE: SHEET E 105. THERE ARE SEVERAL CIRCUITS NOTED
 TO A PANEL M-4, HOWEVER NOT PANEL M-4 WAS SUBMITTED.
  
 A) PLEASE SEE M5-24 ON PLANS WHICH ARE FOR A RECEPTACLE
 AT RTU YET THE PANEL SCHEDULE FOR M5-24 MENTIONS A/C
 #7.
  
 B) PLEASE SEE NUMEROUS CIRCUITS ON THESE SAME SHEETS
 FOR SIGNAGE ALL SHOWN TO A PANEL M-4 YET NONE OF THESE
 CAN BE CONFIRMED. CIRCUITING FOR LOADS, OVER CURRENT
 PROTECTION ETC CAN NOT BE CONFIRMED MEETING MINIMUM
 CODE COMPLIANCE. **PLEASE BE AWARE OF THE SIGN PERMIT
 APPLICATIONS ARE SPECIFIC LOADS CAN BE LOCATED AND NEED
 TO BE PLACED INTO LOAD CALCULATIONS AS WELL AS PANEL
 SCHEDULES.
  
 11) NOTE: PLEASE SEE E401, LOBBY RECEPTACLE CIRCUITS
 R-152, R-150 STATED AS * RECEPTACLES*. THIS IS ONE
 EXAMPLE OF ITEMS WHICH NEED TO BE SPECIFIC. THERE ARE
 DOZENS OF OTHERS.
  
 12) NOTE: PLEASE SEE SAME SHEET E401, FOR CIRCUIT R-101
 WHICH IS IN THE *MARKET AREA* ON PLANS. HOWEVER PLEASE
 SEE PANEL SCHEDULE FOR THIS SAME CIRCUIT, IT IS SHOWN
 AS A *SPARE CIRCUIT*?
  
 13) NOTE: PLEASE SEE ELEVATOR MACHINE ROOM LIGHTING ON
 CIRCUIT R1-7. THIS CIRCUIT IS NOW CONNECTED TO OTHER
 LIGHTING FEEDING OTHER ROOMS SUCH AS STORAGE ROOMS,
 CORRIDOR, AND OTHER LOCATIONS. IN FACT THE OTHER
 LIGHTING CIRCUIT R-128 IS CONNECTED?
 IN ORIGINAL REVIEWS DATED 1/7/07 REVIEW NOTE #17 AND
 REVIEW DATED 4/5/2007 NOTE #19 GAVE CODE SECTIONS
 REQUIRING DEDICATED BRANCH CIRCUITS FOR ELEVATOR
 MACHINE ROOM. THE PLANS WERE REVISED TO SHOW THE
 LIGHTING IN THIS ROOM AS BEING CONNECTED TO THE
 DEDICATED CIRCUIT. A REVISION SUBMITTED IN MARCH OF
 2008 DID NOT INDICATE ANY REVISION FOR THIS SAME ROOM
 YET THE LIGHTING WAS REVISED TO SHOW IT BEING CONNECTED
 TO OTHER LIGHTING. AS THE REVISION WAS NOT INDICATED IT
 WAS NOT PICKED UP BY THIS REVIEWER UNTIL THIS REVIEW.
 PLEASE CORRECT AND UPDATE CIRCUITING FOR THESE ITEMS
 PER 620. 22,23,24,25. ETC
 ** PLEASE BE AWARE OF ANY ITEMS NOT UNDER THE REVIEW OF
 THIS JURISDICTION WHICH IS UNDER THE INSPECTION OF THE
 STATE OF FLORIDA. ASME-17 CODE REQUIREMENTS.
  
 ** ELEVATOR PITS, ELEVATOR LANDINGS, ELEVATOR MACHINE
 ROOMS. CALL TO GO OVER AS THIS IS GIVEN FOR INFORMATION
 ONLY AND NOT PART OF THIS AHJ REVIEW.
 ASME-17 IS HOWEVER ADOPTED BY THE FLORIDA BUILDING CODE
 AS A REFERENCED STANDARD/CODE.
 THIS MAY OR MAY AFFECT FINAL ELEVATOR INSPECTION.
  
 14) NOTE: PLEASE SEE SHEET E402, WALL PACK LIGHT
 FIXTURE. SHOWN TO M-48, HOWEVER M PANEL SCHEDULE ONLY
 GOES UP TO 42.
 THIS IS THE SAME AS LATEST REVISED E102
  
 15) NOTE: PLEASE SEE E402 IN THIS SAME AREA AS NOTED IN
 #14 ABOVE. HALLWAY LIGHTING NOTED TO R-145, HOWEVER
 PANEL SCHEDULE FOR R-145 INDICATES THIS CIRCUIT FOR
 PYLON SIGN.
  
 16) NOTE: PLEASE REVISE VOLTAGE DROP CALCULATIONS. THE
 ACTUAL KNOWN VOLTAGE DROP SHOULD BE COMPLETE AT THIS
 TIME. THE CALCULATIONS ON SHEETE501 WERE NEVER UPDATED
 WHEN MOST OF THE FEEDERS WERE UPDATED TO ALUMINUM.
 FOR EXAMPLE:
 RTU-1, SHOWN AS 2/0 COPPER ON CALCULATIONS YET THE MDP
 SHOWS 4/0 ALUM.
 M-5 SHOWS 1/0 ON CALCULATIONS YET THE MDP SHOWS 3/0
 ALUM.
 H-5 SHOWS 500MCM ON CALCULATIONS AS THERE WAS A
 SUBSTANTIAL DISTANCE HOWEVER THE MDP SCHEDULE HAS THESE
 AS 300MCM ALUM. THIS IS OF CONCERN BASED ON THE
 DISTANCE. PLEASE PROVIDE CALCULATION FOR FEEDER AS WELL
 AS FARTHEST BRANCH CIRCUIT ON THIS PANEL.
 FBC 13-413.1ABC.1, 13-413.1.ABC.1.1, 13-413.1.ABC.1.2
  
 17) NOTE: PLEASE UPDATE ALL LOADS ON E501 FOR HOUSE
 LOADS. THERE ARE SEVERAL WHICH ARE NOT ACCURATE. THE
 FOLLOWING ARE SOME EXAMPLES IN WHICH LOADS ARE MUCH
 MORE THAN SHOWN.
  
 FOR EXAMPLE: HOUSE LIGHTING LOADS FOR R5 IS SHOWN AS
 1.4KW TOTAL. HOWEVER PLEASE SEE R-5 SCHEDULE AS
 CIRCUITS 157,158,159 ARE ALL GREATER THAN THE 1.4.
  
 FOR EXAMPLE: PLEASE SEE HOUSE LIGHTING LOADS ON PANEL
 R-4 WHICH INDICATES A TOTAL OF 1.4KW ONCE AGAIN. PLEASE
 SEE R-4 PANEL SCHEDULE AS CIRCUITS 148,150,152,163 AND
 165 ARE MUCH HIGHER. IN FACT JUST THESE ALONE ARE
 5.4KW.
  
 THE ABOVE MAY NOT SEEM TO BE MUCH HOWEVER PLEASE SEE
 R3, R2, R1. THESE ARE ALSO HIGHER ON PANEL SCHEDULES.
  
 FOR EXAMPLE: PLEASE SEE M1 HOUSE LIGHTING LOADS. THIS
 IS SHOWN AS *0*. THIS IS NOT POSSIBLE WHEN SHEET E 402
 AS NOTED ABOVE HAS LIGHTING BEING SHOWN ON PLANS TO M-1
 PANEL FOR EXTERIOR LIGHTS.
  
 18) NOTE: PLEASE UPDATE ANY FIXTURE SCHEDULES SUCH AS
 LIGHTING WHICH HAS BEEN REVISED DURING THE PROJECT. ANY
 DECREASES IN WATTAGE DESIGN WOULD NOT REQUIRE UPDATED
 LIGHTING PERFORMANCE CALCULATIONS. ANY INCREASES WOULD
 REQUIRE UPDATED CALCULATIONS.
 FOR EXAMPLE: SITE LIGHTING FIXTURES ON OTHER LOCATION
 *HOMEWOOD SUITES * HAD FIXTURES INCREASE FROM 450WATT
 TO 1000WATT. THIS WOULD REQUIRE UPDATED CALCULATIONS.
  
  
 *** PER DIRECTOR PLANS ARE NO LONGER RELEASED. ONLY ONE
 SET MAY BE SIGNED OUT IF NEEDED.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 14 Status F Date 2009-08-02 Cont ID  
Sent By dpalmer Date 2009-08-02 Time 08:12 Rev Time 0.00
Received By dpalmer Date 2009-07-31 Time 19:07 Sent To PC
Notes
2009-08-02 08:14:29** PREVIOUS REVISIONS FOR SITE LIGHTING SIGNED, AND
 SEALED DATE OF 7/09/09 HAS BEEN VOIDED. FIXTURE P1 ARE
 SHOWN IN VIOLATION OF 680.22. THE PLANS SHOW THE POLE
 LIGHT FIXTURES RIGHT AT THE EDGE OF THE WATER'S EDGE ON
 THE SWIMMING POOL. THIS MAY HAVE BEEN A SHIFT IN THE
 PLANS. IN EITHER CASE THIS SITE LIGHTING SHEET IS
 REVISED BY NEW PLANS SUBMITTED.
2009-08-02 07:53:31REVIEW IN PROGRESS

Review Stop E ELECTRICAL
Rev No 13 Status P Date 2009-07-20 Cont ID  
Sent By btrobaug Date 2009-07-20 Time 16:29 Rev Time 0.00
Received By btrobaug Date 2009-07-20 Time 16:25 Sent To Z
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 12 Status F Date 2009-07-16 Cont ID  
Sent By dpalmer Date 2009-07-16 Time 13:05 Rev Time 0.00
Received By dpalmer Date 2009-07-16 Time 13:05 Sent To PC
Notes
2009-07-16 13:06:17** DENIED REVISIONS **
  
 1) NOTE: THE SUBMITTED SHEET E-501 WAS NOT ACTUALLY
 REVISED. THE SAME REVISION #7 ON THE TITLE BLOCKS WAS
 SUBMITTED PREVIOUSLY. KEEP IN MIND THE PREVIOUS RISER
 WAS REDLINED ON REV #7 AS ONE MDP SCHEDULE INDICATES
 3200 AND THE OTHER 3500AMP BREAKER. BASED ON THE
 SERVICE ENTRANCE CONDUCTORS, IT SHOULD BE THE 3200 AS
 GONE OVER ON THE PREVIOUS CONVERSATIONS AND E-MAILS
 WITH THE ENGINEER.
 ** THIS WAS REDLINED ON PREVIOUS REVISION HOWEVER IF
 MAKING CHANGES PLEASE REVISE AND COORDINATE.
  
 230.70, FBC 106.1.1
  
 2) NOTE: PLEASE SUBMIT REVISED PANEL SCHEDULES AND LOAD
 CALCULATIONS FOR ALL PANELS AND EQUIPMENT AFFECT BY THE
 NEW CIRCUITING AND EQUIPMENT ON THE REVISED E401. ONE
 EXAMPLE WOULD BE M1- 20,22, 24. THIS EQUIPMENT AND
 CIRCUIT IS SHOWN AS A *SPARE* ON THE LATEST M1 SCHEDULE
 AND CALCULATIONS. THIS IS ONE EXAMPLE ONLY AS THERE ARE
 OTHER ITEMS WHICH WERE ALSO NOT UPDATED.
 408.4, FBC 106.1.1,106.5
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 11 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By dpalmer Date 2009-06-25 Time 09:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 10 Status P Date 2009-04-20 Cont ID  
Sent By dpalmer Date 2009-04-17 Time 16:57 Rev Time 0.00
Received By dpalmer Date 2009-04-17 Time 16:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 9 Status P Date 2009-03-27 Cont ID  
Sent By dpalmer Date 2009-03-27 Time 13:59 Rev Time 0.00
Received By dpalmer Date 2009-03-27 Time 13:59 Sent To  
Notes
2009-03-27 14:00:15REV 401 AND 402.
 NOT PART OF PREVIOUS REVIEW

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2008-10-29 Cont ID  
Sent By dpalmer Date 2008-10-29 Time 14:06 Rev Time 0.00
Received By dpalmer Date 2008-10-29 Time 14:06 Sent To  
Notes
2008-10-29 14:08:37 
  
 1) NOTE:** NOTES, ELECTRICAL SITE OK, HOWEVER NO STAMPS
 OR REVIEW STAMPS BY PALM BEACH COUNTY HEALTH
 DEPARTMENT. NO NIGHT TIME (AFTER DUSK) SWIMMING IS
 PERMITTED.
  
 2) NOTE: ELECTRICAL SITE ARE OK, HOWEVER BASED ON
 ZONING COMMENTS THE BACKGROUND FO THE ELECTRICAL SITE
 PLANS WILL BE REVISED.
  

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2008-10-03 Cont ID  
Sent By dpalmer Date 2008-10-03 Time 11:55 Rev Time 2.00
Received By dpalmer Date 2008-10-03 Time 11:55 Sent To PC
Notes
2008-10-03 11:55:52 
 ** DENIED **
  
  
  
  
 1) NOTE: PLEASE PROVIDE INFORMATION ON THE COMPACT
 CONDUCTORS AS NOTED ON THE RISER FOR THE NEW 800MCC
 ALUMINUM. PLEASE SEE TABLE 5A IN NEC CHAPTER 9 AS
 800MCM IS NOT A SIZE SHOWN. AREA FOR SQ INCHES NEEDS TO
 BE VERIFIED. PLEASE ALSO VERIFY TYPE OF CONDUIT. PLEASE
 KEEP IN MIND IF PVC AND ANY AREAS ARE SUBJECT TO
 PHYSICAL DAMAGE SCHEDULE 80 MAY BE REQUIRED.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2008-09-02 Cont ID  
Sent By dpalmer Date 2008-09-02 Time 15:16 Rev Time 0.00
Received By dpalmer Date 2008-09-02 Time 15:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2008-05-14 Cont ID  
Sent By dpalmer Date 2008-05-14 Time 11:20 Rev Time 0.00
Received By dpalmer Date 2008-05-14 Time 11:20 Sent To  
Notes
2008-05-14 11:20:57** DENIED/TEMPORARY**
  
 1) NOTE: PLEASE SEE THE THIRD SET OF REVISED ENERGY
 CALCULATIONS COULD NOT BE LOCATED ATTACHED TO PLANS.
 ONLY TWO COMPLETE SETS OF DOCUMENTS WERE ATTACHED TO
 TWO OF THE SETS.
 PLANS ARE IN A FAILED STATUS UNTIL THIRD SET IS
 SUBMITTED. THE THIRD COPY MAY BE BROUGHT IN AT ANY TIME
 BEFORE ALL REVIEWS ARE DONE. IF THESE ARE OK REVIEW
 STOP WILL BE UPDATED TO A *P* STATUS.
 ** ONCE FIRE REVIEW IS DONE AND IF OK, WILL NEED TO
 RETAIN ONE COPY OF REVISED ELECTRICAL PLANS FOR FILE.
  
 2) NOTE: REDLINED PLANS FOR MAIN ELECTRICAL ROOM DOOR
 AS THE SWING DIRECTION NEEDS TO SWING OUT. ONE DOOR OK,
 THE OTHER SHOWS IN-SWING.
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-01-04 Cont ID  
Sent By dpalmer Date 2008-01-04 Time 15:05 Rev Time 0.00
Received By dpalmer Date 2008-01-04 Time 15:05 Sent To  
Notes
2008-01-04 15:06:02*** REDLINED PLANS ***
  
 1) PLEASE SEE SOME CANDELA LEVELS ARE STILL SHOWN BELOW
 MINIMUM PER FBC 11-4.28.3.(4).
 THESE WERE REDLINED ON PLANS AND WILL NOT AFFECT
 ISSUANCE OF ELECTRICAL.
 PLEASE SEE FOR EXAMPLE: E-101 GUEST LAUNDRY, E-102
 ELEVATOR LOBBY ETC.
  
 2) NOTE: PLEASE SEE E-412, KEYED NOTES FLAG #2 REMOVED
 FROM BLOCK OF NOTES YET THIS #2 FLAG STILL ON PLANS IN
 ROOMS.
  
 *** ALL REVISIONS SHALL BE SUBMITTED BEFORE ROUGH
 INSPECTIONS. PLEASE CORRECT THE ABOVE ITEMS ALONG WITH
 ANY OTHER CHANGES.
 ** REVISED, REVIEWED AND STAMPED PLANS ARE REQUIRED TO
 BE ON JOB-SITE FOR INSPECTIONS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CONTACT REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-09-30 Cont ID  
Sent By dpalmer Date 2007-09-30 Time 11:15 Rev Time 0.00
Received By dpalmer Date 2007-09-27 Time 20:00 Sent To  
Notes
2007-09-30 11:15:202007-09-30 11:15:20
  
 ** DENIED 3RD REVIEW ***
 SPRINGHILLSUITES
 5-STORY 130 UNITS.
  
 ** PLEASE SEE THERE ARE COMMENTS FROM PREVIOUS REVIEW
 WHICH ARE STILL IN NEED OF ADDRESSING.
  
 ** PLEASE SEE THERE ARE SOME NEW COMMENTS BASED ON
 PLANS AND/OR REVISIONS TO PLANS WHICH INFORMATION IS
 ONLY NOW BEING SUBMITTED. DUE TO CHANGES AND
 INFORMATION WHICH WAS NOT ON PREVIOUS PLANS OR REVIEW,
 THESE ITEMS COULD NOT HAVE COMMENTED ON AS SOME ITEMS
 AND INFORMATION IS NEW TO PLANS AND/OR DESIGN. THESE
 ITEMS WILL BE CLEARLY NOTED.
  
 1) NOTE: PLEASE SEE PREVIOUS NOTE #1 WHICH REQUESTED
 FOR THE PRODUCT APPROVALS ETC NOT TO BE ATTACHED TO
 ROLLS. THIS WAS OK, AND THESE WERE NOT ATTACHED HOWEVER
 OF THE TWO ROLLS OF PLANS THIS REVIEWER REVIEWED, ALL
 SHEETS IN BOTH ROLLS WERE LOOSE AND NOT ATTACHED INTO
 SECURED ROLLS.
 PLEASE DO NOT SUBMIT ROLLS OF PLANS IN WHICH THE SHEETS
 ARE LOOSE AND NOT ATTACHED.THESE TWO ROLLS WERE
 SECURED BY THIS OFFICE.
 PLEASE SEE SOME SHEETS IN SETS ARE ACTUALLY INSERTED
 BACKWARDS AND UPSIDE DOWN. (S-SHEETS).
 FBC ADMIN SECTION 106.1, 106.5 ETC.
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #2 WITH
 RESPECT TO SIGNATURE VERIFICATION LETTER(S). THIS WAS
 SUBMITTED HOWEVER WAS NOT SEALED AS PREVIOUSLY
 REQUESTED.
 THIS CAN BE SUBMITTED AT ANY TIME.
 FS 471.025, 481.025 AND FAC 61G15-23.002, 61G1-16.004
  
 THIS WAS COMPLETELY STATED ON PREVIOUS NOTE #2.
  
 3) NOTE: PLEASE SEE PREVIOUS NOTE #4 WHICH MENTIONED
 THE MISSING CERTIFICATE OF AUTHORIZATION NUMBER. AS
 PLANS WERE REVISED REMOVING ARCHITECTURAL FIRM MOST
 SHEETS ARE CORRECT HOWEVER PLEASE SEE THAT SOME SHEETS
 IN SOME SETS STILL CONTAIN PFVS (HOMEWOOD) AND COVER
 SHEETS (SPRINGHILL) STILL CALL FOR PFVS ARCHITECTS
 INC.
  
 THIS REVIEWER HAS SPOKEN WITH MR. KEY AND IT IS THE
 UNDERSTANDING THE FIRM NOW HAS OBTAINED THE REQUIRED
 LICENSING THROUGH THE STATE. PLEASE KNOW THAT ALL
 INFORMATION ON TITLE BLOCKS MAY BE REVISED AND
 CORRECTED ONCE ALL REVIEWS ARE COMPLETED AND PLANS ARE
 PICKED UP FOR CORRECTIONS.
 PLEASE SEE FS481.219, FAC 61G1-16.004
  
 4) NOTE: THIS IS A NEW COMMENT: PLEASE SEE THE SEAL
 WHICH IS NOW BEING USED ON ALL THREE SETS FOR BOTH
 HOTELS FOR THE ARCHITECT OF RECORD MR. GREG PORTMAN IS
 NO LONGER ACCEPTED IN THE STATE OF FLORIDA.
 PLEASE SEE RULING FAC61G1-16.002 WHICH CHANGED SEVERAL
 YEARS AGO, WHICH NOW REQUIRES A MINIMUM SEAL SIZE OF
 2INCHES. PLEASE SEE THE NEW SHEETS NOW SUBMITTED
 CONTAINS AN OLD SEAL.
 IF THIS WAS THE ONLY COMMENT ON PLANS, THE ARCHITECT OF
 RECORD WOULD BE ABLE TO COME INTO THIS OFFICE AND
 RE-SIGN, DATE AND SEAL PLANS.
  
 5) NOTE: PLEASE SEE PREVIOUS NOTE #12 WITH RESPECT TO
 FBC CHAPTER 13.
  
 A) PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED
 STILL NEED SOME COORDINATION WITH ELECTRICAL LIGHTING
 ON PLANS. PLEASE THE INPUT DATA REPORT WHICH WILL BE
 NOTED AS IDR ON THE FOLLOWING DOES NOT CORRELATE WITH
 ALL LIGHTING ON PLANS AND FIXTURE LIGHTING LEGEND.
 PLEASE SEE SOME OF THE FOLLOWING EXAMPLES: EXTERIOR
 LIGHTING WHICH IS ON PLANS DOES NOT MATCH WITH THE IDR
 FOR THE SAME NUMBER OF FIXTURES, TYPE(S) AND WATTAGE.
 PLEASE SEE FRONT ENTRANCE AREA Z-21, 32WATT ON IDR AND
 100WATTS ON FIXTURE LEGEND.
 PLEASE SEE FOR EXAMPLE THE WATTAGE WHICH IS REQUIRED
 FOR THE IDR FOR TRACK LIGHT IF LINE VOLTAGE OR LOW
 VOLTAGE IS REQUIRED TO MEET 13-415.2.ABC .1.2. THIS
 INFORMATION ON THE IDR DOES NOT COORDINATE WITH THE
 NOTES ON E-402 AS THE WATTAGE BEING LISTED FOR MAXIMUM
 IS NOT THAT WHICH IS LISTED ON THE IDR FOR THE GREAT
 ROOM. D-58 ETC.
 PLEASE ALSO SEE OTHER FIXTURES WHICH DOE NOT MATCH FOR
 THE GREAT ROOM ALONE: W, W-2, S, WHERE ARE THESE?
 PLEASE SE ANOTHER EXAMPLE IS THE FIXTURE WATTAGES FOR
 MEETING ROOM. THE FIXTURE COUNTS ARE OK, HOWEVER THE
 WATTAGE FOR R22 IS 32WATTS ON THE IDR AND 75WATTS ON
 FIXTURE LEGEND.
 PLEASE ALSO SEE R22D WHICH THE WATTAGE ON FIXTURE
 LEGEND ALONE INDICATES 32 AND 75.?
 PLEASE SEE MISSING 5TH FLOOR LINEN CLOSET.
 PLEASE SEE THE TYPICAL FLOOR LIGHTING PLANS WHICH
 INDICATES 3-FIXTURES FOR STORAGE ROOMS, YET THIS SAME
 ROOM DETAIL ON THE SAME PAGE E-104 INDICATES 2-FIXTURES
 IN ROOMS FOR 3RD, 4TH AND 5TH FLOORS? PLEASE SEE THE
 IDR WHICH INDICATES THREE FIXTURES?
 PLEASE SEE ELECTRICAL ROOMS/CLOSETS FOR EACH FLOOR ARE
 SHOWN AS TYPICAL ON PLANS, YET THE WATTAGE 7SHOWN FOR
 WHAT SHOULD BE THE SAME F7 FIXTURE IS SHOWN AS TWO
 DIFFERENT WATTAGES ON THE IDR. (SEE DIFFERENCES IN 233,
 333 AND THEN BACK TO 433_
 WHERE IS ELECTRICAL ROOM/CLOSET FOR 5TH FLOOR ON THE
 IDR?
 PLEASE BE SURE TO VERIFY METHOD OF CONTROLS LISTED ON
 THE IDR, AS DEVICES SUCH AS TIMERS ETC ARE NOT
 CONSIDERED *MANUAL ON/OFF*. PLEASE CORRELATE ALL
 METHODS OF CONTROLS.
 ** PLEASE SEE THAT THE ABOVE IS SOME EXAMPLES OF
 COORDINATION WHICH NEEDS TO TAKE PLACE BETWEEN THE
 ELECTRICAL LIGHTING ON PLANS AND THE LIGHTING WHICH IS
 PLACE IN THE INPUT DATA REPORT. THIS OFFICE CAN NOT
 EMPHASIZE ENOUGH THE NEED FOR COORDINATION.
  
 B) PLEASE CLARIFY RECEPTACLES WHICH ARE SHOWN FOR ROOMS
 ARE SWITCHED OR PROVIDE POWER TO LIGHTING SUCH AS TABLE
 LAMPS/FLOOR LAMPS ETC. AS PLANS DO INDICATE WHAT
 APPEARS TO BE LAMPS ETC IN ROOMS THEN ANY OF THESE
 WHICH ARE PLUGGED INTO THESE RECEPTACLES WOULD BE
 REQUIRED TO BE PART OF THE ROOM LIGHTING CONTROLS. THIS
 WOULD REQUIRE THE SAME CIRCUITS FOR RECEPTACLES OR
 CONTROLS INSTALLED AND PROVIDING HALF SWITCHED
 RECEPTACLES.
 PLEASE SEE 13-415.1.ABC .1.1, .1.2 AND .1.3
  
 C) PLEASE SEE NOT ALL THREE SETS OF THE REQUIRED ENERGY
 CALCULATIONS ARE SIGNED, DATED AND SEALED BY TEH
 DESIGNERS. IN FACT PLEASE SEE SOME ARE PHOTO-COPIED
 SIGNATURES AND SEALS. PLEASE ALSO SEE THE OWNER/AGENT
 ON TEH CERTIFICAITON SHEET(S) IS ALSO NOT DONE. FBC
 13-103.1.1.1, FS 471.025, FAC 61G15-23.002
  
 6) NOTE: PLEASE SEE PREVIOUS NOTE #15 AS THIS REQUESTED
 ALL HORN, STROBE OR HORN/STROBE DEVICESTO INDICATE
 THE MINIMUM LEVELS FOR ADA PER FBC 11-4.28.1, .2 AND
 .3(4). THE RESPONSE LETTER MENTIONS THIS WAS DONE AT
 ALL LOCATIONS ON PLANS HOWEVER PLEASE CLARIFY WHERE
 THESE LEVELS ARE FOR THE DEVICES LOCATED IN THE ROOMS
 WHICH ARE ON E-411 AND E-412?
 PLEASE SEE THE NOTES ON E-502 WHICH WERE CORRECTED FOR
 THE CANADIAN CODE HOWEVER REFERENCES TO THE REQUIRED
 FLORIDA BUILDING CODE COULD NOT BE FOUND. PLEASE SEE
 CHAPTER 11 OF THE FBC IS SUBSTANTIALLY MORE RESTRICTIVE
 THAN THE NFPA-72 AS NOTED.
  
 7) NOTE: PLEASE SEE PREVIOUS NOTE #22 WHICH REQUESTED
 FOR ALL MANUFACTURES SPECS/CUT SHEETS TO BE SUBMITTED
 FOR THE FIRE PUMP, FIRE PUMP CONTROLLER ETC.
 CODES AND SECTIONS WERE GIVEN FOR THESE ITEMS WHICH AT
 THAT POINT COULD NOT BE REVIEWED AS NO INFORMATION WAS
 SUBMITTED.
 PLEASE SEE THE SPECS/CUT SHEETS WERE SUBMITTED HOWEVER
 COORDINATION WITH PLANS FROM E-401, ELECTRICAL RISER
 E-501, FP SHEETS AND SPECS/CUT SHEETS NEED MUCH
 COORDINATION.
 PLEASE SEE SHEET E-401 WHICH INDICATES THE FP AS 208V,
 60HP AND BEING OF CERTAIN MANUFACTURE. THIS INFORMATION
 ON THE E-501AND MANUFACTURES SPECS/CUT SHEETS SUBMITTED
 DO NOT MATCH. PLEASE SEE THE SPECS INCLUDE A 480V MOTOR
 WHICH IS NOT POSSIBLE WHEN THE SERVICE IS BEING SHOWN
 AS 208V ON RISER.
 PLEASE SEE THE SPECS INDICATE A 75HP WHICH IS ALSO NOT
 THE SAME AS ON RISER AND SHEET 401. THIS WOULD CHANGE
 CONDUCTORS, OVER CURRENT PROTECTION ETC AT 480V AND
 75HP.
 PLEASE SEE THE MANUFACTURES SPECS/CUT SHEETS ARE FOR
 DIFFERENT MANUFACTURES THAN THAT LISTED ON E401 AND
 THIS IS THE SAME FOR JOCKEY PUMP AND JP CONTROLLER.
 PLEASE KNOW THAT AS THE SPECIFIC SIZE MOTOR AND VOLTAGE
 HAS NOT YET BEEN DETERMINED, COMPLETE REVIEW FOR CODE
 COMPLIANCE CAN NOT BE DONE AT THIS TIME. PLEASE BE SURE
 TO SEE NEC 695, NFPA-20 2003 AS NO SPECIFIC SECTIONS
 WILL BE GIVEN WHICH WAS NOT PREVIOUSLY NOTED. PLEASE
 SEE THE FPC IS LISTED WITH A DIFFERENT MANUFACTURE THAN
 THE PUMPS, PLEASE BE SURE ALL ITEMS ARE LISTED
 ASSEMBLIES AS REQUIRED. NEC 110.3, 90.7. PLEASE BE SURE
 TO COORDINATE WITH INFORMATION TO BE PROVIDED ON FIRE
 SPRINKLER PLANS AND ANY REVIEW COMMENTS FROM THE FIRE
 MARSHAL.
 NOTE #22 FROM PREVIOUS REVIEW IS BEING LEFT BELOW.
  
 ********PREVIOUS NOTE *********
 22) NOTE: PLEASE SUBMIT ALL MANUFACTURE SPEC/CUTS
 SHEETS FOR THE FIRE PUMP AND FIRE PUMP CONTROLLER.
 PLEASE SEE NO INFORMATION FOR LOCKED ROTOR CURRENT
 SETTING IS STATED ON PLANS BY NOTE OR ANY OTHER MEANS.
 PLEASE SEE AS NO INFORMATION WAS SUBMITTED OF EQUIPMENT
 AS STATED ABOVE REVIEW FOR NUMEROUS ITEMS FOR CODE
 COMPLIANCE CAN NOT BE DONE AT THIS TIME. NO INFORMATION
 WAS SUBMITTED FOR REVIEW.
 PLEASE SEE NFPA-20 2003 CHAPTER 9 AND CHAPTER 10.
 PLEASE ALSO SEE NEC 695.4
 ** PLEASE KNOW REFERENCES TO THE CHAPTERS ARE GIVEN AND
 NOT SPECIFIC SECTIONS AS THERE ARE TOO MANY TO LIST.
 DISCONNECTING MEANS, ISOLATION SWITCH, LOCKED ROTOR,
 ETC.
 PLEASE BE SURE EQUIPMENT SHEETS CONTAIN THE LISTING
 FROM A NRTL PER 695.10 AND NFPA-20 10.1.2.1.
 NEC 110.3, 90.7
 FBC 106.1.2 **************************************
  
 8) NOTE: PLEASE SEE THERE IS CLARIFICATION NEEDED FOR
 ROOM PTAC UNITS. PLEASE SEE THE PLANS CONTAINS A *FLAG*
 NOTE WHICH MENTIONS THESE UNITS ARE GOING TO BE
 HARDWIRED YET THE SAME PLANS AT THE SAME LOCATION ON
 SHEET E-411 ALSO CONTAINS AN OCTAGONAL NOTE #6 WHICH
 MENTIONS THESE ARE GOING TO BE 30AMP RECEPTACLE FOR
 THIS SAME UNIT? (6-30R).
 ADMIN SECTION 106.1.2, 106.3.5.1.2 FOR COORDINATION.
  
  
 9) NOTE: PLEASE SEE PREVIOUS NOTE #34 WITH RESPECT TO
 THE GROUNDING ELECTRODE FOR THE FIRE PUMP SERVICE. AS
 THE SIZE, VOLTAGE AND RATING OF SERVICE IS NOT CLEAR
 THIS NOTE WILL REMAIN. THE RISER SHOWS *2G*, WHAT IS
 THIS?
 PLEASE SEE MISSING SIZE OF THE GROUNDING ELECTRODE
 CONDUCTOR TO THE FIRE PUMP SERVICE. 250.50, 250.66
  
 10) NOTE: PLEASE SEE PREVIOUS NOTE #35 WHICH REQUESTED
 TO CLARIFY AND SHOW ALL CONTINUOUS LOADS AT 125% FOR
 POOL PANEL (PANEL P). PLEASE SEE PANEL P AS SHOWN ON
 E501, WHERE IS THIS IDENTIFIED?
 **PREVIOUS REVIEW NOTE **
 ** PLEASE SEE LOADS FOR CONTINUOUS LOADS IN PANEL "P"
 NEED TO BE SHOWN..
 PLEASE SUBMIT AND COMPLETE EVEN FOR FUTURE LOAD ETC.
 PLEASE ADJUST LOAD CALCULATIONS AND MDP. PREVIOUSLY
 NOTED FOR CONTINUOUS LOADS.
 220, 215.3, 230.42.
 FBC 106.1.2
  
 11) NOTE: PLEASE SEE PREVIOUS NOTE #44, WHERE IS THE
 TRACK LIGHTING LOADS SHOWN IN THE LOAD CALCULATIONS?
 PLEASE SHOW AND COMPLETE LOAD CALCULATIONS FOR TRACK
 LIGHTING PER 220.12B
  
 ** PLEASE KNOW ONCE ALL REVIEWS ARE DONE, ONE ROLL MAY
 BE RETAINED BY THIS OFFICE DUE TO REPEAT COMMENTS FOR
 CODE COMPLIANCE AND PREVIOUS NOTE TO FS 553.80(2)(B).
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-09-30 08:40:192007-09-30 08:40:19
  
 REVIEW IN PROGRESS
2007-09-28 21:24:582007-09-28 21:24:58
  
 REVIEW IN PROGRESS, NOTES TO FOLLOW ONCE REVIEW IS
 COMPLETED.
2007-09-27 20:01:152007-09-27 20:01:15
  
 ONE SET IN ELECTRICAL FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-04-06 Cont ID  
Sent By dpalmer Date 2007-04-06 Time 16:03 Rev Time 0.00
Received By dpalmer Date 2007-04-05 Time 14:14 Sent To  
Notes
2007-04-06 16:04:21*** UNSAT2ND REVIEW ***
  
 SPRINGHILLSUITES
 5-STORY 130 UNITS.
  
 ** PLEASE SEE MANY ITEMS FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
  
  
 ** PLEASE SEE MANY OF THE NOTES WILL CONTAIN
 ABBREVIATIONS FOR REQUIRED ITEMS.
 PLEASE SEE SOME OF THE FOLLOWING WHICH WILL BE COMMON *
 ANY REFERENCE TO THE FBC CHAPTER 1, ARE SECTIONS TO THE
 ADMINISTRATIVE SECTION OF THE FBC 2004 AS ADOPTED BY
 THE CITY OF WEST PALM BEACH.
 * PLEASE SEE MANY REFERENCE TO THE FLORIDA STATUTES
 WILL BE DONE AS FS.
 * PLEASE SEE MANY REFERENCES TO THE FLORIDA
 ADMINISTRATIVE CODE WILL BE FAC.
  
 1) NOTE: PLEASE KNOW THAT A WRITTEN RESPONSE FROM THE
 DESIGN TEAM WILL HELP IN THE REVIEW PROCESS.THE
 RESPONSES WHICH WERE ATTACHED TO THE SPRING HILL SUITES
 PLANS WERE THAT OF THE SAME RESPONSES WHICH WERE
 ATTACHED TO THE HOMEWOOD SUITES PLANS. THEY ARE IN FACT
 THE SAME RESPONSE WITH THE SAME PERMIT NUMBER.
 ** ALL ADDITIONAL INFORMATION BY WAY OF PRODUCT
 APPROVALS, DATA, REPORTS, RESPONSES ETC SHOULD NOT BE
 ATTACHED/STAPLED TO ROLLS OF PLANS. PLEASE PLACE IN
 FOLDERS/BINDERS OF SOME SORT AND LABEL ACCORDINGLY.
  
 2) NOTE: PLEASE SEE FS 471.025, 481.025 AND FAC
 61G15-23.002, 61G1-16.004 AS ALL PLANS SHALL BEAR THE
 ORIGINAL AND LEGAL SIGNATURE OF ALL DESIGNERS OF
 RECORD. PLEASE SEE THE ARCHITECTURAL SHEETS WHICH
 CONTAIN A RAISED SEAL OVER A *PRINTED* OR
 *PHOTO-COPIED* SIGNATURE. THIS SIGNATURE AND DATE IS
 NOT ORIGINAL AS REQUIRED.
 **PLEASE ALSO KNOW ONE SET WILL BE RETAINED BY THIS
 OFFICE.
 ** PLEASE SEE THE ELECTRICAL SHEETS SEEMED TO BE SIGNED
 WITH WHAT APPEARS TO BE *INITIALS*? IF THIS IS INDEED
 THE LEGAL SIGNATURE OF THE DESIGNER, PLEASE SUBMIT AN
 ORIGINAL SIGNED, DATED AND SEALED LETTER FROM THE
 ENGINEER ATTESTING TO THE LEGAL SIGNATURE. THIS WILL BE
 PLACED IN OUR SIGNATURE FILE FOR FUTURE REFERENCE. **
 PLEASE KNOW THAT THE LETTER WILL BE REQUIRED TO BE
 NOTARIZED. PLEASE SEE FS 117.05 FOR CORRECT NOTARY
 REQUIRED STATEMENTSETC.
  
 3) NOTE: PLEASE SEE THE NEW LICENSE INFORMATIONKNOWN
 AS THE CERTIFICATE OF AUTHORIZATION NUMBER WHICH HAS
 NOW BEEN ADDED TO THE TITLE BLOCKS ON ALL ENGINEERING
 SHEETS IS CURRENTLY *DELINQUENT* WITH THE DEPARTMENT OF
 BUSINESS AND PROFESSIONAL REGULATION. PLEASE SEE A
 PRINT OUT FROM THE STATE OF FLORIDA WEBSITE WHICH IS
 BEING ATTACHED TO THE NOTES WHICH WAS PRINTED ON 4/5/07
 SHOWS THE LICENSE FOR FIRM AS BEING DELINQUENT SINCE
 2/28/07.
 PLEASE SEE FAC 61G15-23.002 AND FS 471.023 WHICH
 REQUIRES THIS NUMBER TO BE CURRENT AND IN FULL EFFECT
 FOR SAID FIRM.
 PLEASE KNOW THIS IS REQUIRED ON ALL SHEETS AND FOR ALL
 TRADES WHETHER OR NOT COMMENT IS MADE BY OTHER
 TRADE(S).
  
 4) NOTE: PLEASE SEE MISSING THE COMPLETE INFORMATION OF
 THE TITLE BLOCKS FOR THE ARCHITECTURAL FIRM. FAC
 61G1-16.004, FS 481.219
 PLEASE SEE THE ARCHITECTURAL FIRM TITLE BLOCKS ARE NOT
 COMPLETE AT THIS TIME. PLEASE SEE THAT THIS IS REQUIRED
 FOR ALL SHEETS WHICH CONTAIN THE TITLE BLOCK FOR SAID
 FIR, *PFVS*
 PLEASE SEE MISSING THE PRINTED NAME AND LICENSE NUMBER
 OF THE ARCHITECT.
 PLEASE SEE THE MISSING CERTIFICATE OF AUTHORIZATION
 NUMBER. THIS MAY ALSO BE KNOWN AS THE FIRM LICENSE
 NUMBER.
 THIS IS REQUIRED ON ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADES.
  
 5) NOTE:PLEASE SEE THE PREVIOUS NOTES AS FOR THE
 REQUIRED STATEMENT FOR ALL DESIGNERS. PLEASE SEE THAT
 SOME SHEETS CONTAIN THIS STATEMENT HOWEVER NOT ALL.
 PLEASE SEE FBC ADMIN SECTION 109.3.6, 109.3.6.4.4 WHICH
 REQUIRES THE STATEMENT FOR THRESHOLD PROJECTS ON ALL
 ARCH AND ENG SHEETS.
 " TO THE BEST OF THE ARCHITECT'S /OR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND CHAPTER
 633 OF THE FLORIDA STATUTES".
 THIS IS REQUIRED FOR EACH DESIGN PROFESSIONAL ON
 PLANS.
  
 6) NOTE: PLEASE SEE THE *S* SHEETS WHICH DO NOT CONTAIN
 THE REQUIRED LICENSE INFORMATION FOR THE ENGINEERING
 FIRM AS REQUIRED PER FAC 61G15-23.002, FS 471.023.
 REQUIRED WHETHER OR NOT COMMENT IS MADE BY OTHER
 TRADES.
  
 7) NOTE: PLEASE SEE THE ADDRESS OF THE PROJECT HAS NOT
 BEEN INCLUDE IN THE TITLE BLOCKS AS PREVIOUSLY
 REQUESTED. PLEASE SEE BY SIMPLY STATING THE CLOSEST
 MAIN INTERSECTION DOES NOT PROVIDE THE REQUIRED
 INFORMATION.
 PLEASE SEE THAT ONCE THE ADDRESS FOR SAID PROJECT IS
 FINALIZED; PLEASE BE SURE THE TITLE BLOCKS FOR ALL
 SHEETS CONTAIN THE CORRECT ADDRESS. THE ADDRESS GIVEN
 BY THE ADDRESSING REVIEWER ON THE PREVIOUS REVIEW IS
 THAT AS NOTED BELOW.
 PLEASE SEE A PRELIMINARY ADDRESS OF 2437 METROCENTRE
 BLVD IS CURRENTLY IN OUR SYSTEM FOR THE PCN/ PARCEL
 CONTROL NUMBER APPLIED WITH APPLICATION HOWEVER THIS
 ADDRESS MAY CHANGE AS DETERMINED BY THE ADDRESSING
 REVIEWER AND THE FIRE MARSHAL?S OFFICE. AT THIS TIME
 THE ADDRESSING REVIEW HAS ASSIGNED THE ABOVE 2437. FAC
 61G1-16.004, FAC 61G15-23.002
 * THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES.
  
 8) NOTE: PLEASE SEE ALL SEALS SHALL BE CLEAR AND
 VISIBLE WITH ALL INFORMATION ON SAID SEAL EASILY
 READABLE. PLEASE SEE FAC 61G15-23.001, AND 61G1-16.003
 PLEASE SEE SOME SHEETS THE SEALS ARE NOT CLEAR EVEN IF
 SHADOWING WITH LEAD/DUST RUB.
 PLEASE SEE SOME SHEETS ARE STILL LIKE THIS IN SETS,
 PLEASE SEE THE *A* SHEETS AS THESE WERE SEALED ON THE
 BACK OF EACH SHEET. THE SHEET FACING WITH INFORMATION,
 DESIGNS ETC SHALL BEAR THE SEAL FACING THE FRONT FOR
 READING, SCANNING ETC OF DOCUMENTS.
  
 9) NOTE: PLEASE SEE SOME OF THE SP SHEETS ARE MISSING
 INFORMATION ON THE TITLE BLOCKS FOR THE PRINTED NAME
 AND LICENSE INFORMATION AS REQUIRED PER FAC 61G1-16.004
 AND FS 481.219
  
 10) NOTE: PLEASE SEE THE SURVEY SHEETS WHICH DO NOT
 CONTAIN AN ORIGINAL SIGNATURE AS REQUIRED PER FAC
 61G17-7.002, AND FS 472.025
  
 11) NOTE: PLEASE SEE THE PHOTO-METRICS PROVIDED ARE NOT
 CLEAR OR READABLE WITH MINIMUM LEVELS AS REQUIRED.
 PLEASE ALSO SEE THAT THE PLANS DO NOT CONTAIN ANY
 STAMPS FROM THE PALM BEACH COUNTY HEALTH DEPARTMENT. **
 PLEASE KNOW AS THE PLANS SUBMITTED CONTAIN A POOL,
 PLEASE KNOW THIS WILL BE UNDER A SEPARATE PERMIT WITH
 PLANS, FEES AND PERMIT APPLICATION.
 PLEASE KNOW THAT ALL PLANS FOR THIS TYPE OF PUBLIC
 SWIMMING POOL WILL BE REQUIRED TO BE SUBMITTED TO THE
 PALM BEACH COUNTY HEALTH DEPARTMENT FOR ANY REVIEW OF
 COMPLETED PHOTO-METRICS FOR ANY AFTER DUSK SWIMMING.
 PLEASE ALSO SEE ANY PLUMBING REVIEW COMMENTS WHICH MAY
 ALSO REQUIRED THESE PLANS WHEN SUBMITTING FOR SEPARATE
 PERMIT TO ALSO BE STAMPED FOR REVIEW BY THE SAME.
  
 12) NOTE: PLEASE SEE THAT MUCH OF THE INFORMATION
 NEEDED FOR REVIEW FOR CODE COMPLIANCE FOR CHAPTER 13
 HAS NOT YET BEEN SUBMITTED. PLEASE SEE THE ENERGY
 CALCULATIONS PER FBC 2004 CHAPTER 13 THAT WERE
 SUBMITTED FOR REVIEW. 13-415.1.AB.1 DO NOT FULLY
 CORRELATE WITH THE FIXTURES, TYPES, NUMBERS, WATTAGES
 AS SHOWN ON PLANS AND FIXTURE LEGENDS. PLEASE BE SURE
 TO GO THROUGH PLANS AND ENERGY CALCULATIONS AND
 COORDINATE ALL INFORMATION.
 **PLEASE SEE THE 2004 FBC CHAPTER 13.
 **PLEASE SEE 13-413.1ABC.1 WHICH REQUIRES WORST CASE
 VOLTAGE DROP TO BE SHOWN ON PLANS FOR FEEDERS AND
 BRANCH CIRCUITS. THE NOTE FOR CONDUCTOR LENGTH INCREASE
 IS NOTED, HOWEVER PLEASE PROVIDE ABOVE AS REQUIRED.
 PLEASE SEE THIS VOLTAGE DROP INFORMATION COULD NOT BE
 LOCATED FOR THE FEEDERS.
 **PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE
 SEE A COMPLETE LIGHTING CONTROL SYSTEM AND/OR OTHER
 METHODS FOR AUTOMATIC LIGHTING CONTROLS ARE REQUIRED.
 PLEASE SEE AS NO SYSTEM OR DEVICES WERE SUBMITTED,
 REVIEW FOR CODE COMPLIANCE OF SUCH ITEMS COULD NOT BE
 DONE AT THIS TIME.
 A RESPONSE IN THE PLAN REVIEW NOTES FOR THE OTHER HOTEL
 CONTAIN A NOTE THAT THIS IS A 24/7/365 OPERATION AND
 DOES NOT NEED TO MEET ANY AUTOMATED LIGHTING CONTROLS.
 PLEASE SEE THERE ARE SOME AREAS IN WHICH CAN BE
 CONSIDERED 24HR OPERATION HOWEVER PLEASE SEE .1.3 (3)
 AS THE ROOMS MUST CONTAIN AUTOMATED SHUT OFF FOR ALL
 LIGHTING CIRCUITS IN THESE ROOMS INCLUDING ANY SWITCHED
 RECEPTACLES CIRCUITS.
 PLEASE SEE ALL OTHER LOCATIONS SUCH AS STORAGE ROOMS
 ETC WHICH CONTAIN FLOOR TO CEILING HEIGHT PARTITIONS
 WILL BE REQUIRED TO CONTAIN AUTOMATED DEVICES. PLEASE
 KNOW THAT THIS WAS FEDERALLY MANDATED IN JULY 04 WHICH
 REQUIRED FOR ALL STATES BY THE NEXT CODE CYCLE TO ADOPT
 THE 1999 ASHAE 90.1 STANDARDS OR BETTER. THE STATE OF
 FLORIDA ADOPTED THE FBC ENERGY CODE ON OCT 1ST, 2005.
 THIS IS REQUIRED STATEWIDE.
 PLEASE KNOW THAT SOME OF THE LOCATIONS WHICH WOULD BE
 CONSIDERED FOR 24HR OPERATION MAY BE THE LOBBY, FRONT
 DESK, RECEPTION OFFICE LOCATIONS ALONG WITH HALLWAYS.
 ** PLEASE SEE 13-415.2, 13-415.2.ABC.1 FOR PERFORMANCE
 CALCULATIONS REQUIRED.
 ** PLEASE SEE TRACK LIGHTING REQUIREMENTS PER
 13-415.2.ABC.1.2
 ** PLEASE SEE NOTE #16 WITH RESPECT TO STAIRWELLS AND
 FAILURE OF DEVICES AS PER NFPA-101.
 ** PLEASE BE SURE WITH SYSTEM AND/OR DEVICE WHICH ARE
 GOING TO BE PART OF THE DESIGN SHALL CORRELATE WITH THE
 SYMBOL LEGEND. PLEASE BE SURE ALL OVER RIDE DEVICES
 STATE THE MAXIMUM OVER RIDE TIMES AS PERMITTED BY CODE.
 PLEASE SEE 30MINS MAXIMUM FOR OCCUPANCY TYPE AND 4HRS
 MAXIMUM FOR TIMER TYPE DEVICES.
 PLEASE SEE 13-415.1.ABC.1.4 AND 13-415.1.ABC.2 FOR
 EXTERIOR BUILDING LIGHTING ALLOWANCES.
  
 ** PLEASE SEE ALL OF FBC CHAPTER 13 AS ALL SECTIONS AS
 REQUIRED CAN NOT BY TYPED IN NOTES AS GIVEN. PLEASE SEE
 SOME OF THE KEY ITEMS AND SECTIONS HAVE BEEN GIVEN TO
 COMPLY.
  
 13) NOTE: PLEASE SUBMIT WIND LOAD INFORMATION FOR ALL
 SITE LIGHTING. PLEASE SEE THE FBC IN THE WIND REGION IS
 140 MPH 3 SECOND GUSTS. PLEASE KNOW THIS WILL BE
 REQUIRED TO BE STATED ON PLANS AND STRUCTURAL
 CALCULATIONS FOR ALL POLES WITH THE EPA (EFFECTIVE
 PROJECTED AREA) OF LIGHT FIXTURE WILL BE CONFIRMED
 BASED ON THE FIXTURES AS NOTED ON PLANS.
 NO RESPONSE WAS SUBMITTED FOR THIS. PLEASE SEE THE
 INFORMATION ON PLANS MENTIONS THE MINIMUM RATING AND
 MENTIONS INFORMATION TO THE ELECTRICAL INSPECTOR.
 PLEASE KNOW THAT THIS INFORMATION IS AND WILL BE
 REQUIRED BE DONE ON PLANS AND SUBMITTED FOR REVIEW
 BEFORE ANY INSTALLATION. PLEASE KNOW THAT IF THE WIND
 LOAD CALCULATIONS AND INFORMATION IS NOT SUBMITTED AT
 THIS TIME, THIS WILL BE PART OF THE CONDITIONS OF
 ISSUANCE WHICH MAY BE DONE..
  
 14) NOTE: PLEASE SEE THE ONLY SOME INFORMATION WAS
 SHOWN FOR THE FIRE ALARM INFORMATION AND NO FIRE
 SPRINKLER INFORMATION WAS SUBMITTED.PLEASE SEE THE
 BASE PLANS FOR THIS BUILDING SHALL CONTAIN THE COMPLETE
 FIRE SPRINKLER LAYOUT AND BASE FIRE ALARM SYSTEM PLEASE
 KNOW THAT BOTH OF THESE WILL STILL BE SUBMITTED FOR
 SEPARATE PERMITS PLANS AND FEES AT A LATER DATE ONCE
 THE BUILDING PERMIT IS ISSUED. BASE SYSTEM FOR FIRE
 ALARM IS SHOWN; HOWEVER PLEASE SEE COMMENTS WITH
 RESPECT TO PLANS SUBMITTED FOR THIS AND DEVICES MISSING
 ETC.
 PLEASE KNOW THAT EVEN THOUGH THESE WILL BE UNDER
 SEPARATE PERMIT, THE MINIMUM REQUIREMENTS FOR THE CODE
 SHALL BE SHOWN ON PLANS.
 FBC ADMIN SECTION 106.3.5.1.1 (5).
  
 15) NOTE: PLANS DID NOT CHANGE. COMPLIANCE FOR ADA
 DEVICES, LOCATIONS, LEVELS ETC HAVE NOT BEEN MET.
 PLEASE SEE PLANS STILL INDICATE BEING DONE UNDER THE
 CANADIAN NATIONAL BUILDING CODE.
 PLEASE SEE FBC 2004 11-4.28.2, .3(4). PLEASE STATE ALL
 MINIMUM LEVELS AS REQUIRED FOR ALL AREAS. PLEASE KNOW
 IS NOTED THAT THE LEVELS FOR ACCESSIBLE UNITS ARE NOTED
 ON PLANS, HOWEVER THIS IS REQUIRED FOR ALL OTHER AREAS
 AS STATED IN 11-4.28.1
 PLEASE SEE PLANS CURRENTLY STATE THE 1995 CANADA
 NATIONAL BUILDING CODE. PLEASE SEE THAT THESE PLANS ARE
 BEING SUBMITTED IN THE STATE OF FLORIDA IN THE US.
 PLEASE ADJUST PLANS AND ALL CODE REFERENCES. PLEASE BE
 SURE TO SEE SECTIONS GIVEN FOR STROBE AND HORN DEVICES
 FROM THE FBC AND PLEASE ALSO SEE NFPA-72. PLEASE KNOW
 THAT THE FBC CHAPTER 11 REQUIREMENTS ARE MORE STRINGENT
 AND THE MORE STRINGENT SHALL APPLY.
 THIS IS THE SAME COMMENT AS NO CHANGES HAVE BEEN MADE.
  
  
 16) NOTE: THIS COMMENT WILL REMAIN AS THE LOCATIONS OF
 ALL DEVICES WHICH MAY BE STATED BY THE FIRE REVIEW MAY
 ALSO AFFECT THE ELECTRICAL PLANS.
 *PREVIOUS REVIEW NOTE * PLEASE SEE FIRE REVIEW COMMENTS
 AS THERE SEEMS FOR MANY LOCATIONS WHICH SMOKE DETECTORS
 ARE MISSING AND WILL BE REQUIRED.
 PLEASE SEE THESE WILL BE STATED BY FIRE REVIEW AND IS
 ONLY GIVEN AS A NOTE AT THIS TIME AS SOME AREAS WHICH
 DO NOT CONTAIN ANY NOTATION FOR THESE DEVICES WILL
 REQUIRE THESE.(PUMP ROOM, ELEVATOR MACHINE ROOM ) ETC
 PLEASE SEE NFPA-72 AND NFPA-101 AND FBC 905
  
 17) NOTE:PLEASE BE SURE THESE CODES AS PREVIOUSLY
 NOTED ARE ON THE ARCHITECTURAL PLANS TITLE SHEETS FOR
 CODES AND THE ELECTRICAL PLANS AT A MINIMUM. PLEASE SEE
 SOME OF THE CODES REFLECTED ON PLANS ARE NO LONGER IN
 USE IN THE STATE OF FLORIDA. PLEASE SEE THE FOLLOWING
 CODES SHALL BE LISTED ON ALL PLANS AND ANY CODES
 RELEVANT TO THE SPECIFIC TRADES SHEETS SHALL BE STATED
 ON THOSE SHEETS. (ELECTRICAL) PLEASE LIST THE FOLLOWING
 AT A MINIMUM AS REQUIRED FOR ELECTRICAL REVIEW. 2002
 NFPA-70 (NEC) STATED ON COVER SHEET HOWEVER SHOULD ALSO
 BE STATED ON E-TITLE SHEET.
 2002-NFPA-72 NATIONAL FIRE ALARM CODE, 2003 NFPA-20
 NATIONAL FIRE PUMP CODE, AND 2003 NFPA-101 LIFE SAFETY
 CODE.
  
 18) NOTE:PLEASE SEE THAT SOME OF THE PHOTO-METRICS
 SUBMITTED DO NOT COMPLY WITH THE MINIMUM LEVELS
 REQUIRED FOR LIFE SAFETY. PLEASE SEE THE LEVELS AS
 STATED IN PREVIOUS REVIEW. (SEE STAIRS WHICH SHOW ONLY
 2.9FC WHEN A MINIMUM OF 10FC IS REQUIRED.).
 PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR ALL EGRESS
 PATHS UNDER NORMAL LIGHTING LEVELS AND UNDER EMERGENCY
 LIGHTING LEVELS TO THE PUBLIC RIGHT OF WAY OUT AND AWAY
 FROM BUILDING.
 PLEASE SEE NFPA-101 7.8 AND 7.9.
 PLEASE ALSO SEE 7.8.1.3 AND 7.9.2.2 AS ALL STAIRS SHALL
 INDICATE THE 10FT CANDLES MINIMUM UNDER NORMAL AND THE
 ALLOWED DE-RATED LEVELS UNDER EMERGENCY CONDITIONS TO
 1FT CANDLE.
 FBC 106.1.2 ADMIN SECTION.
 REVIEW FOR COMPLIANCE OF THIS CAN NOT BE DONE AT THIS
 TIME.
  
 19) NOTE: PLEASE SEE THIS COMMENT WILL REMAIN AS THE
 DISCONNECTING MEANS FOR EQUIPMENT AND LOCATIONS IN THE
 ELEVATOR EQUIPMENT ROOM NEEDS TO BE MORE DETAILED.
 PLEASE SEE NEC 620.22, 620.23 AND 620.24 FOR ALL THE
 REQUIRED DEDICATED BRANCH CIRCUITS FOR ELEVATOR
 EQUIPMENT ROOMS. PLEASE 620.23 AND .24 WHICH MORE
 SPECIFICALLY SHOWS THE LIGHTING AND RECEPTACLES ALSO
 BEING SHOWN CIRCUITED TO OTHER AREAS AND ROOMS WHICH
 ARE NOT PERMITTED.
 PLEASE ALSO SEE 620.51 FOR REQUIRED DISCONNECTING MEANS
 FOR ALL AS NOTED AND LOCATIONS REQUIRED.
  
 20) NOTE:SEE NOTE ABOVE, LABEL EQUIPMENT,
 DISCONNECTS, CIRCUITING.
 PLEASE SEE PLANS INDICATE DISCONNECTS FOR THE ELEVATOR
 EQUIPMENT A NOT COMPLETE ON PLANS AT THIS TIME. PLEASE
 SEE KNOW THAT REVIEW OF THIS CAN NOT BE DONE AT THIS
 TIME. PLEASE SEE THE FOLLOWING COMMENT.
 FBC 106.1.2, NEC 408.4, 310.16 ETC
  
 21) NOTE:SAME AS PREVIOUSLY NOTED.
 PLEASE LIST THE CIRCUITING ON THE MDP WITH THE
 RESPECTIVE CIRCUITS AS WOULD BE LOCATED ON A PANEL
 SCHEDULE. PLEASE SEE THE CIRCUITING FOR OTHER PANELS
 SUBMITTED.
 1,3,5,7,9 / 2,4,6,8, ETC.
 PLEASE SEE THE CIRCUITING ON PLANS FOR ALL OF THESE
 ITEMS SHALL CORRELATE.
 FBC 106.1.2, NEC, 408.4, 310.16, 240.4 ETC
  
  
 22) NOTE: PLEASE SUBMIT ALL MANUFACTURE SPEC/CUTS
 SHEETS FOR THE FIRE PUMP AND FIRE PUMP CONTROLLER.
 PLEASE SEE NO INFORMATION FOR LOCKED ROTOR CURRENT
 SETTING IS STATED ON PLANS BY NOTE OR ANY OTHER MEANS.
 PLEASE SEE AS NO INFORMATION WAS SUBMITTED OF EQUIPMENT
 AS STATED ABOVE REVIEW FOR NUMEROUS ITEMS FOR CODE
 COMPLIANCE CAN NOT BE DONE AT THIS TIME. NO INFORMATION
 WAS SUBMITTED FOR REVIEW.
 PLEASE SEE NFPA-20 2003 CHAPTER 9 AND CHAPTER 10.
 PLEASE ALSO SEE NEC 695.4
 ** PLEASE KNOW REFERENCES TO THE CHAPTERS ARE GIVEN AND
 NOT SPECIFIC SECTIONS AS THERE ARE TOO MANY TO LIST.
 DISCONNECTING MEANS, ISOLATION SWITCH, LOCKED ROTOR,
 ETC.
 PLEASE BE SURE EQUIPMENT SHEETS CONTAIN THE LISTING
 FROM A NRTL PER 695.10 AND NFPA-20 10.1.2.1.
 NEC 110.3, 90.7
 FBC 106.1.2
  
  
 23) NOTE:SAME NOTE TO REMAIN AS THE SYMBOLS ON PLANS
 WILL CHANGE AND SOME ARE NOT CLEAR AT THIS TIME. SEE
 PLANS.
 PLEASE SEE SOME DEVICES SHOWN ON PLANS COULD NOT BE
 LOCATED ON THE DEVICE SYMBOL LEGEND. PLEASE COMPLETE
 FOR REVIEW OF THESE ITEMS.
 FBC ADMIN SECTION 106.1.2, 106.3.5.1.2
  
 24) NOTE:SAME NOTE TO REMAIN AS SYMBOL AND LEGEND
 WILL CHANGE.
 PLEASE KNOW BASED ON THE REQUIREMENTS OF MANY OF THE
 REVIEW COMMENTS AND FBC CHAPTER 13, THE PLAN KEYNOTES
 WILL MOST LIKELY BE ADJUSTED.
 PLEASE BE SURE TO CORRELATE.
  
 25) NOTE: PLEASE CORRELATE ARCHITECTURAL PLANS WITH
 THAT OF THE ELECTRICAL PLANS FOR ALL ROOM LAYOUTS AND
 FOOT PRINTS OF ROOMS/BUILDING. PLEASE SEE THE MAIN
 ELECTRICAL ROOM FOR ONE EXAMPLE. PLEASE SEE THE FLOOR
 LAYOUTS DO NOT CORRELATE AND REVIEW FOR SOME ITEMS FOR
 CODE COMPLIANCE CAN NOT BE DONE AT THIS TIME. PLEASE
 SEE THE ELECTRICAL PLANS DO NOT SHOW ANY ELECTRICAL
 ROOMS FOR THE TYPICAL LAYOUTS AND THE ELECTRICAL
 PANELS. PLEASE SEE NO DOORS ARE BEING SHOWN TO ACCESS
 ANY PANELS? PLEASE SEE ARCHITECTURAL SHEETS AND
 CORRELATE.
 PLEASE SEE 240.24, 110.26 ETC
 ** PLEASE SEE THE ELECTRICAL ROOM WHICH ALSO CONTAINS
 BATHROOM FIXTURES ON PLANS.
 ** PLEASE SEE THE DOOR SWING IN THE MAIN ELECTRICAL
 ROOM SHALL FACE OUTWARD, ALONG WITH PANIC HARDWARE
 ETC.
 PLEASE ADJUST PLANS AND BEAR IN MIND THE REQUIREMENTS
 FOR THE DOOR SWINGS IN THE EGRESS CORRIDOR FOR BUILDING
 CODE.
 PLEASE SEE THE PLANS SHALL ALSO CONTAIN A NOTE FOR DOOR
 HARDWARE.
  
  
  
 26) NOTE: **THIS NOTE WILL REMAIN AS USE AS SUITES AND
 PERMANENT MEANS OF COOKING IS NOT CLEAR.
 PLEASE SEE 210.60 WHICH REFERENCES TO 210.52 FOR ITEMS
 REQUIRED.
 PLEASE SEE THERE ARE SEVERAL ITEMS FOR THIS. PLEASE
 KNOW AT THIS TIME IT SEEMS THESE MICROWAVE UNITS ARE
 BEING PERMANENTLY INSTALLED AT AN UPPER LEVEL. PLEASE
 SEE SOME OF THE FOLLOWING COMMENTS WHICH MAY VERY WELL
 APPLY.
 PLEASE ALSO SEE COMMENT WITH RESPECT TO THE HEIGHT OF
 THE MICROWAVE IN ACCESSIBLE UNITS.
  
 27) NOTE: **THIS NOTE WILL REMAIN AS USE AS SUITES AND
 PERMANENT MEANS OF COOKING IS NOT CLEAR.
 PLEASE SEE MISSING THE SMALL APPLIANCE CIRCUITS AS
 REQUIRED PER 210.52B1, 210.11C1 AND 220.16. PLEASE KNOW
 THAT NO OTHER OUTLETS MAY BE FED FROM THESE CIRCUITS.
 (IF APPLICABLE)
  
 28) NOTE: **THIS NOTE WILL REMAIN AS USE AS SUITES AND
 PERMANENT MEANS OF COOKING IS NOT CLEAR.
 PLEASE SEE 210.52B1 AS THERE ARE RECEPTACLES LOCATED IN
 THE KITCHEN/BREAKFAST/DINING AREAS WHICH ARE FED FROM
 THE LIGHTING CIRCUITS WHICH ARE NOT PERMITTED. PLEASE
 SEE 210.11C1, 220.16 AS NOTED IN NOTE #31
 (WHERE APPLICABLE AS NOTE IN NOTE #30)
  
 29) NOTE: **THIS NOTE WILL REMAIN AS USE AS SUITES AND
 PERMANENT MEANS OF COOKING IS NOT CLEAR. PLEASE ALSO
 SEE THERE ARE SOME WALL AREAS WHICH ARE MISSING
 RECEPTACLES AS NOTED.
  
 PLEASE SEE MISSING RECEPTSPER 210.52 FOR 2FT OF WALL
 , KITCHEN AREA, KITCHEN WALL OVER 2FT, WITHIN 6FT OF
 DOORS ETC.
 PLEASE KNOW AS THE CODE DOES PERMIT THE SPACING FOR
 HOTEL/MOTELS AND GUEST SUITES TO BE SPACE FOR FURNITURE
 LAYOUTS, IT ALSO STILL REQUIRES THE SAME NUMBER OF
 RECEPTS WHICH WOULD BE REQUIRED IN A DWELLING TO BE
 INSTALLED.
 PLEASE SEE MOST UNITS SEEM TO BE OK, HOWEVER THERE ARE
 SOME UNITS WHICH DO NOT HAVE ANY RECEPTS LOCATE DON
 WALLS. PLEASE KNOW IF THIS IS NOT A UNIT WITH PERMANENT
 COOKING WHICH IS NOT YET DETERMINED THEN, SPACING MAY
 FALL UNDER GUEST ROOMS/SUITES AND NOT DWELLING. 210.60
  
 30) NOTE: **THIS NOTE WILL REMAIN AS USE AS SUITES AND
 PERMANENT MEANS OF COOKING IS NOT CLEAR.
 HEIGHTS, AND USE IS NOT CLEAR AT THIS TIME.
 PLEASE SEE THE HEIGHTS FOR THE MICROWAVES IN ACCESSIBLE
 UNITS ARE AT 62INCHES, WHERE ARE THESE UNITS GOING TO
 BE MOUNTED? AND SHOW DETAIL.
 FBC CHAPTER 11, FHAR 24CFR100.205
  
 31) NOTE: **THIS NOTE WILL REMAIN AS USE AS SUITES AND
 PERMANENT MEANS OF COOKING IS NOT CLEAR.
 PLEASE KNOW THAT IN EITHER CASE WHETHER OR NOT THE
 FACILITY CONTAINS PERMANENT MEANS FOR COOKING THE
 RECEPTACLES SERVING KITCHEN COUNTER SPACE SHALL BE
 GFI/GFI PROTECTED.
 PLEASE SEE 210.8A6 AS ALL RECEPTS SERVING KITCHEN
 COUNTER SPACES AND THE LIKE SHALL BE GFI/GFI
 PROTECTED.
  
  
 32) NOTE:PLEASE SEE THE 2002 NEC AS ARC FAULT
 PROTECTION IS NO LONGER ONLY FOR RECEPTACLES IN
 SLEEPING ROOMS. PLEASE SEE THE NOTES ON PLANS WHICH
 MENTION AFCI PROTECTION ONLY FOR RECEPTACLES.
 * PREVIOUS NOTE.
 PLEASE CLARIFY THE ARC FAULT PROTECTION WHICH IS NOT
 CURRENTLY BEING SHOWN. PLEASE SEE NOTE #30 AND IF UNITS
 CONTAIN PERMANENT COOKING MOUNTED EQUIPMENT THEN THESE
 WILL BE REQUIRED FOR PROTECTION IN SLEEPING ROOMS.
 210.12
  
 33) NOTE:SAME NOTE.
 PLEASE EITHER PROVIDE SCHEDULE FOR OCP AND AWG RATINGS,
 OR COMPLETE PANEL SCHEDULES AS PREVIOUSLY NOTED. PLEASE
 COMPLETE ALL PANEL BOARDS WITH THE CONDUCTOR SIZES FOR
 ALL BRANCH CIRCUITS.
 PLEASE SEE 310.16, 240.4, FBC 106.1.2, 106.3.5.1.2
 REVIEW FOR CONDUCTORS CAN NOT BE DONE AT THIS TIME.
  
 34) NOTE: PLEASE SEE MISSING SIZE OF THE GROUNDING
 ELECTRODE CONDUCTOR TO THE FIRE PUMP SERVICE. 250.50
  
 35) NOTE: PLEASE SEE LOADS FOR CONTINUOUS LOADS IN
 PANEL "P" NEED TO BE SHOWN..
 PLEASE SUBMIT AND COMPLETE EVEN FOR FUTURE LOAD ETC.
 PLEASE ADJUST LOAD CALCULATIONS AND MDP. PREVIOUSLY
 NOTED FOR CONTINUOUS LOADS.
 220, 215.3, 230.42.
 FBC 106.1.2
  
 36) NOTE: THIS NOTE WILL REMAIN AND THERE WILL BE
 CHANGES ON PLANS.
 * PREVIOUS NOTE * PLEASE SUBMIT COMPLETE LOAD
 CALCULATIONS AND SUMMARY FOR ALL LOADS AND SHOW ALL
 CONTINUOUS/LARGEST MOTOR LOADS AT 125%.
 220.3,220.10,220.11,220.13, 230.42, 215.3 ETC.
  
 37) NOTE: PLEASE ALSO CORRELATE ALL PLANS AND SHEETS AS
 THE PANEL P IS BEING SHOWN IN MULTIPLE LOCATIONS. ONE
 SHEET PANEL IS SHOWN IN ONE ROOM AND ANOTHER SHEET
 SHOWS THIS SAME PANEL LOCATED AT ANOTHER ROOM. PLEASE
 CORRELATE.
 FBC 106.1.2 ADMIN SECTION FOR ADDITIONAL
 INFORMATION/CLARIFICATION.
  
 38) NOTE:PLEASE SEE ROOF TOP PLANS WHICH INDICATE A
 RTU HOWEVER NO CIRCUITING IS BEING SHOWN ETC. PLEASE
 SEE 440.11 AND 210.63 FOR OTHER REQUIRED DISCONNECTS
 AND WP GFI REQUIRED.
 THIS WAS NOTED ON PREVIOUS PLANS AND SOME INFORMATION
 ON THE MDP WAS PROVIDED HOWEVER DISCONNECTING MEANS AND
 GFI CAN NOT BE DETERMINED AT THIS TIME. PLEASE SEE THE
 NOTES ON PLANS MENTION THE EQUIPMENT CONTAINS INTERNAL
 DISCONNECTING MEANS YET THIS CAN NOT BE VERIFIED.
 PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS WHICH SHOWS
 THIS AS REQUIRED PER 440.11.
 PLEASE SEE THE NOTE ALSO MENTIONS THE GFI REQUIRED WILL
 BE FED FROM THE RTU. HOW IS THIS POSSIBLE WHEN THE
 CIRCUITING DOES NOT INDICATE ANY NEUTRAL CONDUCTOR
 BEING FED FROM THE MDP TO UNIT. THE LOAD FOR THE GFI
 CAN NOT BE FED FROM THE UNIT.
 THE FOLLOWING SCENARIO IS AN EXAMPLE, THE UNIT NEEDS TO
 BE SERVICED AND THE POWER TO THE UNIT IS SHUT DOWN, HOW
 WILL A RECEPTACLE WHICH IS FED FROM THIS UNIT STILL
 CONTAIN POWER FOR SERVICING OR ANY OTHER NEEDS WHEN
 THERE IS NO POWER?
 PLEASE ALSO EXPLAIN WHO THE NEUTRAL IS BEING DERIVED?
 THERE ARE SEVERAL UNANSWERED QUESTIONS AT THIS TIME.
 PLEAS COORDINATE AND ADJUST PLANS.
  
 39) NOTE: PLEASE EXPLAIN WHERE NOTES AND INFORMATION
 FOR THE BELOW AS PREVIOUSLY NOTED IS MET.
 PLEASE SEE NFPA-72 FOR REQUIREMENTS OF THE FACP
 CIRCUIT(S).
 4.4.1.4.2.1 THE DEDICATED BRANCH CIRCUIT(S) AND
 CONNECTIONS SHALL BE MECHANICALLY PROTECTED.
 4.4.1.4.2.2 CIRCUIT DISCONNECTING MEANS SHALL HAVE A
 RED MARKING SHALL BE ACCESSIBLE ONLY TO AUTHORIZED
 PERSONNEL, AND SHALL BE IDENTIFIED AS ?FIRE ALARM
 CIRCUIT.?
 4.4.1.4.2.3 THE LOCATION OF THE CIRCUIT DISCONNECTING
 MEANS SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM
 CONTROL UNIT
 PLEASE KNOW ANY NOTATION FOR THE REQUIRED LOCK OFF TYPE
 BREAKER SHALL STATE "ANY LOCK-OFF DEVICE SHALL HAVE THE
 HANDLE/LOCK AN INTEGRAL PART OF THE BREAKER" OR WORDS
 TO THAT AFFECT. PLEASE KNOW DEVICES SUCH AS THE
 SNAP/CLIP ON TYPE ARE NOT PERMITTED AS THEY ARE EASILY
 REMOVED OR FALL OFF WHEN A PANEL COVER IS REMOVED WHICH
 THEN NO LONGER PROVIDES THE NEEDED PROTECTION OF THE
 CIRCUITS(S).
  
  
 40) NOTE:PLEASE SEE MISSING NEUTRAL CONDUCTOR TO THE
 FIRE PUMP/FIRST MEANS OF DISCONNECT. PLEASE SEE
 250.24B, 250.24, 250.6. EVEN AS A MOTOR LOAD, THIS IS
 REQUIRED.
 PLEASE SEE AS NOTED, (250.6) NO EQUIPMENT GROUNDING
 CONDUCTOR IS INSTALLED BEFORE THE FIRST MEANS OF
 DISCONNECT.
 THIS WOULD CREATE OBJECTIONABLE CURRENTS.
 THIS IS THE SAME COMMENT AS THE RISER SHOWS TWO
 DIFFERENT SETS OF SERVICE ENTRANCE CONDUCTORS??
  
 41) NOTE: PLEASE PROVIDE INFORMATION FOR KEY CARD
 ACCESS CONTROL SYSTEM. PLEASE SEE NFPA-1017 7.2.1,
 7.1.9, 7.2.1.5 WHICH REQUIRES THAT ANY ACCESS CONTROL
 OR DOOR LOCK SYSTEM NOT TO IMPEDED EGRESS IN ANY
 FASHION UNDER NORMAL OR EMERGENCY CONDITIONS. PLEASE
 ALSO SEE FIRE REVIEW'S POSSIBLE COMMENTS.
  
 42) NOTE: THIS NOTE REMAINS AS ALL LOCATIONS HAVE NOT
 YET BEEN CONFIRMED AND LOCATIONS ON CEILINGS NEED TO BE
 VERIFIED.
 * PREVIOUS REVIEW NOTE*
 PLEASE SEE NFPA-72 11.8.3 WHICH REQUIRES LOCATIONS OF
 SMOKE DETECTORS TO BE INSTALLED WITH MINIMUM CRITERIA.
 PLEASE SEE AREAS WHERE THERE ARE SLOPED CEILINGS AS
 SHOWN ON THE ARCHITECTURAL SHEETS, THE SD SHALL BE
 INSTALLED WITHIN 3FT OF THE PEAK OF THAT SLOPE.
 (LOUNGE) ETC OR WITHIN 12 INCHES OF THE HIGHEST POINT
 ON A FLAT CEILING. PLEASE NOTE THE REQUIREMENTS AS
 LISTED. (3FT FROM BATH ROOM AND KITCHEN DOORS/OPENINGS
 ETC. PLANS DO ALREADY CONTAIN A NOTE FOR THE SMOKE
 DEVICE BEING PHOTO-ELECTRIC IN SOME AREAS. THIS COMMENT
 MAYBE EXPANDED UPON.
 PLEASE SE PREVIOUS NOTE WITH RESPECT TO LOCATION
 MISSING WHICH WILL REQUIRE ADDITIONAL.
  
 43) NOTE: PLEASE PLACE ALL ROOM AND AREA DESIGNATIONS
 ON PLANS. THIS IS REQUIRED FOR ALL ENLARGED LAYOUT
 SHEETS AS WELL.
 FBC 106.1.2, 106.3.5.1.2
  
 44) NOTE: PLEASE SHOW AND COMPLETE LOAD CALCULATIONS
 FOR TRACK LIGHTING PER 220.12B
  
 45) NOTE: NOTE FROM PREVIOUS REVIEW TO REMAIN AS NOTES
 ABOVE MENTION THIS. PLEASE KNOW DOORS SHALL BE SHOWN
 FOR ALL ROOMS, MORE SPECIFICALLY THE MAIN ELECTRICAL
 ROOM(S), ELEVATOR ROOMS ETC. PLEASE KNOW THE LAYOUTS
 FROM THE ARCHITECTURAL SHEETS AND THE ELECTRICAL SHEETS
 DO NOT CORRELATE, THE DOOR SWINGS MAY BE AN ISSUE IF
 THE DOORS ARE ACTUALLY ON THE INSIDE AND LOCATED IN AN
 EGRESS CORRIDOR. PLEASE SEE FBC AND LS101 FOR DOOR
 SWINGS IN EGRESS PATHS.7.2.1.4 ETC
  
 46) NOTE:SAME NOTE, SEE KITCHEN AREAS AND THE LIKE.
 PLEASE SEE 210.8B3 FOR BRANCH CIRCUITS IN KITCHEN AREAS
 AND THE LIKE WHICH REQUIRES PROTECTION FOR ALL 15/20
 AMP 120 CIRCUITS.
  
 47) NOTE: PLEASE SEE ATTACHED COPY OF FLORIDA STATUTES
 553.80(2)(B) WITH RESPECT TO DESIGN PROFESSIONALS AND
 REPEAT COMMENTS FOR CODE COMPLIANCE.
 ** ONE COMPLETE SET OF PLANS ARE BEING RETAINED BY THIS
 OFFICE.
  
 48) NOTE: PLEASE SEE THE LOADS ON THE MDP'S AS NOTED ON
 PLANS DO NOT CORRELATE. PLEASE SEE ONE MDP SHOWS ONE
 LOAD AND THE LOAD SHOWN FOR TEH SAME MDP IN OTHER
 LOCATIONS IS YET ANOTHER LOAD?
 PLEASE CORRDINATE ONCE ALL LOADS ARE DONE.
 FBC 106.1.3.5.1.2, 106.1.2
 NEC 220
  
 49) NOTE:PLEASE PROVIDE THE UL DETAILS FOR ANY AND
 ALL FIRE RATED PENETRATIONS.
 NEC 300.21, NFPA-221, 4.2 ETC.
 PLEASE PROVIDE DETAIL SHEET.
  
  
  
 *** PLEASE KNOW AS THERE ARE MANY ITEMS NOT SUBMITTED
 FOR REVIEW, PLANS NOT DESIGNED TO FBC CHAPTER 13 ETC,
 THERE MAY BE FUTURE REVIEW COMMENTS ON THE FOLLOW UP
 REVIEW.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-04-06 11:23:501-ROLL IN ELEC FOR REVIEW.
 NOTES TO FOLLOW

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-01-07 Cont ID  
Sent By dpalmer Date 2007-01-07 Time 13:41 Rev Time 0.00
Received By dpalmer Date 2007-01-07 Time 07:33 Sent To  
Notes
2007-01-07 13:45:53** UNSAT ***
  
 SPRINGHILL SUITES
 5-STORY 130 UNITS.
  
 ** PLEASE SEE MANY OF THE NOTES WILL CONTAIN
 ABBREVIATIONS FOR REQUIRED ITEMS.
 PLEASE SEE SOME OF THE FOLLOWING WHICH WILL BE COMMON *
 ANY REFERENCE TO THE FBC CHAPTER 1, ARE SECTIONS TO THE
 ADMINISTRATIVE SECTION OF THE FBC 2004 AS ADOPTED BY
 THE CITY OF WEST PALM BEACH.
 * PLEASE SEE MANY REFERENCE TO THE FLORIDA STATUTES
 WILL BE DONE AS FS.
 * PLEASE SEE MANY REFERENCES TO THE FLORIDA
 ADMINISTRATIVE CODE WILL BE FAC.
  
 1) NOTE: PLEASE KNOW AS THIS WILL BE A THRESHOLD
 PROJECT AND THREE SETS OF ALL PLANS AND ALL DOCUMENTS
 SHALL BE SUBMITTED FOR REVIEW AND STAMPING.
 PLEASE SEE BUILDING REVIEW NOTES ALSO.
 FBC ADMIN SECTIONS 109.3.6, 106.1.2
  
 2) NOTE: PLEASE SEE FS 471.025 AND FAC 61G15-23.002 AS
 ALL PLANS SHALL BEAR THE ORIGINAL AND LEGAL SIGNATURE
 FOR THE ENGINEER OF RECORD ON ALL DOCUMENTS. PLEASE SEE
 BOTH SETS OF PLANS SUBMITTED IN FACT CONTAIN A RAISED
 SEAL OVER A PHOTO-COPIED SIGNATURES AND DATE ON MOST OF
 THE MP AND E SHEETS. PLEASE SEE ONLY SOME OF THE SHEETS
 ACTUALLY CONTAINED AN ORIGINAL WET INK SIGNATURE.
 PLEASE KNOW THE COMMENT IS FOR ALL MEP PLANS WHETHER OR
 NOT COMMENT IS MADE BY OTHER TRADE(S).
 PLEASE ALSO KNOW ONE SET WILL BE RETAINED BY THIS
 OFFICE.
  
 3) NOTE: PLEASE SEE MISSING TITLE BLOCKS ON ALL
 ENGINEERING SHEETS WHICH ARE REQUIRED PER FAC
 61G15-23.002 AND FS 471.023
 THIS IS FOR M,E,P AND S SHEETS.
 PLEASE ALSO SEE MISSING THE FOLLOWING.
 THE PRINTED NAME AND LICENSE NUMBER OF THE ENGINEER.
 THE CERTIFICATE OF AUTHORIZATION NUMBER/ALSO KNOWN AS
 THE ENGINEERING BUSINESS #.
 PLEASE KNOW THIS IS REQUIRED ON ALL SHEETS AND FOR ALL
 TRADES WHETHER OR NOT COMMENT IS MADE BY OTHER
 TRADE(S).
  
 4) NOTE: PLEASE SEE MISSING THE COMPLETE INFORMATION OF
 THE TITLE BLOCKS FOR THE ARCHITECTURAL FIRM. FAC
 61G1-16.004, FS 481.219
 PLEASE SEE MISSING THE PRINTED NAME AND LICENSE NUMBER
 OF THE ARCHITECT.
 PLEASE SEE THE MISSING CERTIFICATE OF AUTHORIZATION
 NUMBER. THIS MAY ALSO BE KNOWN AS THE FIRM LICENSE
 NUMBER.
 THIS IS REQUIRED ON ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADES.
  
 5) NOTE: PLEASE SEE FBC ADMIN SECTION 109.3.6,
 109.3.6.4.4 WHICH REQUIRES THE STATEMENT FOR THRESHOLD
 PROJECTS ON ALL ARCH AND ENG SHEETS.
 " TO THE BEST OF THE ARCHITECT'S /OR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND CHAPTER
 633 OF THE FLORIDA STATUTES".
 THIS IS REQUIRED FOR EACH DESIGN PROFESSIONAL ON
 PLANS.
  
 6) NOTE: PLEASE SEE THE MECHANICAL AND PLUMBING SHEETS
 WHICH ARE SEALED WITH A RAISED SEAL WHICH IS NO LONGER
 VALID FOR USE IN THE STATE OF FLORIDA. PLEASE SEE THE
 FAC 61G1-16.001 WHICH RULED IN FEBRUARY OF 2004 THAT
 ALL SEALS SHALL BEAR THE WORDING OF "LICENSE" AND THE
 PREVIOUS WORDING OF "CERTIFICATE" WOULD NO LONGER BE
 PERMITTED IN THE STATE OF FLORIDA. PLEASE KNOW AN
 EXTENSION WAS GRANTED TO THE DATE OF DECEMBER 31ST,
 2005 HOWEVER ALL PLANS AFTER THIS DATE SHALL CONTAIN
 THE NEW WORDING OF LICENSE. PLEASE OBTAIN NEW SEAL.
 THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADE(S).
  
 7) NOTE: PLEASE SEE THAT ONCE THE ADDRESS FOR SAID
 PROJECT IS FINALIZED; PLEASE BE SURE THE TITLE BLOCKS
 FOR ALL SHEETS CONTAIN THE CORRECT ADDRESS.
 PLEASE SEE A PRELIMINARY ADDRESS OF 2437 METROCENTRE
 BLVD IS CURRENTLY IN OUR SYSTEM FOR THE PCN/ PARCEL
 CONTROL NUMBER APPLIED WITH APPLICATION HOWEVER THIS
 ADDRESS MAY CHANGE AS DETERMINED BY THE ADDRESSING
 REVIEWER AND THE FIRE MARSHAL'S OFFICE. AT THIS TIME
 THE ADDRESSING REVIEW HAS ASSIGNED THE ABOVE 2437. FAC
 61G1-16.004, FAC 61G15-23.002
 * THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES.
  
 8) NOTE: PLEASE SEE ALL SEALS SHALL BE CLEAR AND
 VISIBLE WITH ALL INFORMATION ON SAID SEAL EASILY
 READABLE. PLEASE SEE FAC 61G15-23.001, AND 61G1-16.003
 PLEASE SEE SOME SHEETS THE SEALS ARE NOT CLEAR EVEN IF
 SHADOWING WITH LEAD/DUST RUB.
  
 9) NOTE: PLEASE KNOW AS THE PLANS SUBMITTED CONTAIN A
 POOL, PLEASE KNOW THIS WILL BE UNDER A SEPARATE PERMIT
 WITH PLANS, FEES AND PERMIT APPLICATION.
 PLEASE KNOW THAT ALL PLANS FOR THIS TYPE OF PUBLIC
 SWIMMING POOL WILL BE REQUIRED TO BE SUBMITTED TO THE
 PALM BEACH COUNTY HEALTH DEPARTMENT FOR ANY REVIEW OF
 COMPLETED PHOTO-METRICS FOR ANY AFTER DUSK SWIMMING.
 PLEASE ALSO SEE ANY PLUMBING REVIEW COMMENTS WHICH MAY
 ALSO REQUIRED THESE PLANS WHEN SUBMITTING FOR SEPARATE
 PERMIT TO ALSO BE STAMPED FOR REVIEW BY THE SAME.
  
 10) NOTE: PLEASE SEE NO ENERGY CALCULATIONS PER FBC
 2004 CHAPTER 13 WERE SUBMITTED FOR REVIEW.
 13-415.1.AB.1
 **PLEASE SEE THE 2004 FBC CHAPTER 13.
 **PLEASE SEE 13-413.1ABC.1 WHICH REQUIRES WORST CASE
 VOLTAGE DROP TO BE SHOWN ON PLANS FOR FEEDERS AND
 BRANCH CIRCUITS. THE NOTE FOR CONDUCTOR LENGTH INCREASE
 IS NOTED, HOWEVER PLEASE PROVIDE ABOVE AS REQUIRED.
 **PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE
 SEE A COMPLETE LIGHTING CONTROL SYSTEM AND/OR OTHER
 METHODS FOR AUTOMATIC LIGHTING CONTROLS ARE REQUIRED.
 PLEASE SEE AS NO SYSTEM OR DEVICES WERE SUBMITTED,
 REVIEW FOR CODE COMPLIANCE OF SUCH ITEMS COULD NOT BE
 DONE AT THIS TIME.
 ** PLEASE SEE 13-415.2, 13-415.2.ABC.1 FOR PERFORMANCE
 CALCULATIONS REQUIRED.
 ** PLEASE BE SURE WITH SYSTEM AND/OR DEVICE WHICH ARE
 GOING TO BE PART OF THE DESIGN SHALL CORRELATE WITH THE
 SYMBOL LEGEND. PLEASE BE SURE ALL OVER RIDE DEVICES
 STATE THE MAXIMUM OVER RIDE TIMES AS PERMITTED BY CODE.
 PLEASE SEE 30MINS MAXIMUM FOR OCCUPANCY TYPE AND 4HRS
 MAXIMUM FOR TIMER TYPE DEVICES.
 PLEASE SEE 13-415.1.ABC.1.4 AND 13-415.1.ABC.2 FOR
 EXTERIOR BUILDING LIGHTING ALLOWANCES.
  
 ** PLEASE SEE ALL OF FBC CHAPTER 13 AS ALL SECTIONS AS
 REQUIRED CAN NOT BY TYPED IN NOTES AS GIVEN. PLEASE SEE
 SOME OF THE KEY ITEMS AND SECTIONS HAVE BEEN GIVEN TO
 COMPLY.
  
 11) NOTE: PLEASE SUBMIT WIND LOAD INFORMATION FOR ALL
 SITE LIGHTING. PLEASE SEE THE FBC IN THE WIND REGION IS
 140 MPH 3 SECOND GUSTS. PLEASE KNOW THIS WILL BE
 REQUIRED TO BE STATED ON PLANS AND STRUCTURAL
 CALCULATIONS FOR ALL POLES WITH THE EPA (EFFECTIVE
 PROJECTED AREA) OF LIGHT FIXTURE WILL BE CONFIRMED
 BASED ON THE FIXTURES AS NOTED ON PLANS.
  
 12) NOTE: PLEASE SEE THE BASE PLANS FOR THIS BUILDING
 SHALL CONTAIN THE COMPLETE FIRE SPRINKLER LAYOUT AND
 BASE FIRE ALARM SYSTEM PLEASE KNOW THAT BOTH OF THESE
 WILL STILL BE SUBMITTED FOR SEPARATE PERMITS PLANS AND
 FEES AT A LATER DATE ONCE THE BUILDING PERMIT IS
 ISSUED. BASE SYSTEM FOR FIRE ALARM IS SHOWN, HOWEVER
 PLEASE SEE COMMENTS WITH RESPECT TO PLANS SUBMITTED FOR
 THIS AND DEVICES MISSING ETC.
 FBC ADMIN SECTION 106.3.5.1.1 (5).
  
 13) NOTE: PLEASE SEE FBC 2004 11-4.28.2, .3(4). PLEASE
 STATE ALL MINIMUM LEVELS AS REQUIRED FOR ALL AREAS.
 PLEASE KNOW IS NOTED THAT THE LEVELS FOR ACCESSIBLE
 UNITS ARE NOTED ON PLANS, HOWEVER THIS IS REQUIRED FOR
 ALL OTHER AREAS AS STATED IN 11-4.28.1
 PLEASE SEE PLANS CURRENTLY STATE THE 1995 CANADA
 NATIONAL BUILDING CODE. PLEASE SEE THAT THESE PLANS ARE
 BEING SUBMITTED IN THE STATE OF FLORIDA IN THE US.
 PLEASE ADJUST PLANS AND ALL CODE REFERENCES. PLEASE BE
 SURE TO SEE SECTIONS GIVEN FOR STROBE AND HORN DEVICES
 FROM THE FBC AND PLEASE ALSO SEE NFPA-72. PLEASE KNOW
 THAT THE FBC CHAPTER 11 REQUIREMENTS ARE MORE STRINGENT
 AND THE MORE STRINGENT SHALL APPLY.
  
 14) NOTE: PLEASE SEE FIRE REVIEW COMMENTS AS THERE
 SEEMS FOR MANY LOCATIONS WHICH SMOKE DETECTORS ARE
 MISSING AND WILL BE REQUIRED.
 PLEASE SEE THESE WILL BE STATED BY FIRE REVIEW AND IS
 ONLY GIVEN AS A NOTE AT THIS TIME AS SOME AREAS WHICH
 DO NOT CONTAIN ANY NOTATION FOR THESE DEVICES WILL
 REQUIRE THESE.(PUMP ROOM, ELEVATOR MACHINE ROOM ) ETC
 PLEASE SEE NFPA-72 AND NFPA-101 AND FBC 905
  
 15) NOTE: PLEASE SEE SOME OF THE CODES REFLECTED ON
 PLANS ARE NO LONGER IN USE IN THE STATE OF FLORIDA.
 PLEASE SEE THE FOLLOWING CODES SHALL BE LISTED ON ALL
 PLANS AND ANY CODES RELEVANT TO THE SPECIFIC TRADES
 SHEETS SHALL BE STATED ON THOSE SHEETS. (ELECTRICAL)
 PLEASE LIST THE FOLLOWING AT A MINIMUM AS REQUIRED FOR
 ELECTRICAL REVIEW.
 2002 NFPA-70 (NEC) STATED ON COVER SHEET HOWEVER SHOULD
 ALSO BE STATED ON E-TITLE SHEET.
 2002-NFPA-72 NATIONAL FIRE ALARM CODE, 2003 NFPA-20
 NATIONAL FIRE PUMP CODE, AND 2003 NFPA-101 LIFE SAFETY
 CODE.
  
 16) NOTE: PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR ALL
 EGRESS PATHS UNDER NORMAL LIGHTING LEVELS AND UNDER
 EMERGENCY LIGHTING LEVELS TO THE PUBLIC RIGHT OF WAY
 OUT AND AWAY FROM BUILDING.
 PLEASE SEE NFPA-101 7.8 AND 7.9.
 PLEASE ALSO SEE 7.8.1.3 AND 7.9.2.2 AS ALL STAIRS SHALL
 INDICATE THE 10FT CANDLES MINIMUM UNDER NORMAL AND THE
 ALLOWED DE-RATED LEVELS UNDER EMERGENCY CONDITIONS TO
 1FT CANDLE.
 FBC 106.1.2 ADMIN SECTION.
 REVIEW FOR COMPLIANCE OF THIS CAN NOT BE DONE AT THIS
 TIME.
  
 17) NOTE: PLEASE SEE NEC 620.22, 620.23 AND 620.24 FOR
 ALL THE REQUIRED DEDICATED BRANCH CIRCUITS FOR ELEVATOR
 EQUIPMENT ROOMS. PLEASE 620.23 AND .24 WHICH MORE
 SPECIFICALLY SHOWS THE LIGHTING AND RECEPTACLES ALSO
 BEING SHOWN CIRCUITED TO OTHER AREAS AND ROOMS WHICH
 ARE NOT PERMITTED.
 PLEASE ALSO SEE 620.51 FOR REQUIRED DISCONNECTING MEANS
 FOR ALL AS NOTED AND LOCATIONS REQUIRED.
  
 18) NOTE: PLEASE SEE PLANS INDICATE DISCONNECTS FOR THE
 ELEVATOR EQUIPMENT A NOT COMPLETE ON PLANS AT THIS
 TIME. PLEASE SEE KNOW THAT REVIEW OF THIS CAN NOT BE
 DONE AT THIS TIME. PLEASE SEE THE FOLLOWING COMMENT.
 FBC 106.1.2, NEC 408.4, 310.16 ETC
  
 19) NOTE: PLEASE LIST THE CIRCUITING ON THE MDP WITH
 THE RESPECTIVE CIRCUITS AS WOULD BE LOCATED ON A PANEL
 SCHEDULE. PLEASE SEE THE CIRCUITING FOR OTHER PANELS
 SUBMITTED.
 1,3,5,7,9 / 2,4,6,8, ETC.
 PLEASE SEE THE CIRCUITING ON PLANS FOR ALL OF THESE
 ITEMS SHALL CORRELATE.
 FBC 106.1.2, NEC, 408.4, 310.16, 240.4 ETC
  
 20) NOTE: PLEASE SEE THAT ALL OF THE FOLLOWING ROOMS
 WILL BE REQUIRED TO CONTAIN AN EMERGENCY BATTERY BACK
 UP LIGHT OF SOME KIND.
 MAIN ELECTRICAL ROOM, FIRE PUMP ROOM, BOTH ELEVATOR
 CONTROL/MACHINE ROOMS.
 90.4, LS 101 7.8, 7.9, 700.12E, 700.16.
  
 21) NOTE: PLEASE CLARIFY THE AIC RATINGS FOR ALL
 SERVICE EQUIPMENT AND PANELS. PLEASE SEE THE RISER AND
 SOME PANELS SHOW SOME PANELS AND THEIR RATINGS, HOWEVER
 NOT ALL.
 PLEASE COMPLETE.
 PLEASE SEE 110.9, 110.10, 240.12 ETC.
 PLEASE ALSO SEE THE NOTES WITH RESPECT TO THE FIRE PUMP
 CONTROLLER WHICH SHALL ALSO STATE THE MINIMUM RATINGS.
  
 22) NOTE: PLEASE SUBMIT ALL MANUFACTURE SPEC/CUTS
 SHEETS FOR THE FIRE PUMP AND FIRE PUMP CONTROLLER.
 PLEASE SEE NO INFORMATION FOR LOCKED ROTOR CURRENT
 SETTING IS STATED ON PLANS BY NOTE OR ANY OTHER MEANS.
 PLEASE SEE AS NO INFORMATION WAS SUBMITTED OF EQUIPMENT
 AS STATED ABOVE REVIEW FOR NUMEROUS ITEMS FOR CODE
 COMPLIANCE CAN NOT BE DONE AT THIS TIME.
 PLEASE SEE NFPA-20 2003 CHAPTER 9 AND CHAPTER 10.
 PLEASE ALSO SEE NEC 695.4
 ** PLEASE KNOW REFERENCES TO THE CHAPTERS ARE GIVEN AND
 NOT SPECIFIC SECTIONS AS THERE ARE TOO MANY TO LIST.
 DISCONNECTING MEANS, ISOLATION SWITCH, LOCKED ROTOR,
 ETC.
 PLEASE BE SURE EQUIPMENT SHEETS CONTAIN THE LISTING
 FROM A NRTL PER 695.10 AND NFPA-20 10.1.2.1.
  
 ** PLEASE KNOW DETERMINATION FOR WHETHER OR NOT ON-SITE
 GENERATOR BACK UP FOR THE FIRE PUMP HAS NOT YET BEEN
 CONFIRMED WITH THE FIRE MARSHAL'S OFFICE.
 PLEASE KNOW AS FLORIDA HAS BECOME PRONE TO HURRICANES
 AND TROPICAL STORMS ON MORE OF A SUBSTANTIAL TIME FRAME
 FROM YEARS PAST AND THE POWER NOT BEING AVAILABLE FOR
 THE FIRE PUMP IN AN EMERGENCY HAS BECOME A CONCERN OF
 THIS OFFICE AND THE FIRE MARSHAL'S OFFICE. PLEASE KNOW
 THIS MAY BE CONSIDERED AS REQUIRED PER 695.3, NFPA-20
 9.2.1.1 THAT A ON-SITE POWER MAY BE REQUIRED. PLEASE
 SEE THE NEXT COMMENT.
  
 23) NOTE: PLEASE BE SURE TO PLACE NOTE(S) ON PLANS FOR
 ALL SIGNAGE REQUIRED FOR SERVICE LOCATIONS AND FIRE
 PUMP LOCATION. 230.2E
 PLEASE ALSO SEE 9.3.2.2.3.2 WHICH STATES A PLACARD
 SHALL BE PLACED ADJACENT TO THE FIRE PUMP CONTROLLER
 STATING THE LOCATION OF THIS DISCONNECTING MEANS AND
 THE LOCATION OF THE KEY (IF THE DISCONNECTING MEANS IS
 LOCKED).
 FBC 106.1.2 ADMIN SECTION.
  
 24) NOTE: PLEASE SEE FIXTURE LEGEND SHALL STATE THE
 MINIMUM TIMES ON THE EMERGENCY AND EXIT LIGHTS AS
 REQUIRED PER LS 101 7.9.2.1
  
 25) NOTE: PLEASE SEE SOME DEVICES SHOWN ON PLANS COULD
 NOT BE LOCATED ON THE DEVICE SYMBOL LEGEND. PLEASE
 COMPLETE FOR REVIEW OF THESE ITEMS.
 FBC ADMIN SECTION 106.1.2, 106.3.5.1.2
  
 26) NOTE: PLEASE KNOW BASED ON THE REQUIREMENTS OF MANY
 OF THE REVIEW COMMENTS AND FBC CHAPTER 13, THE PLAN
 KEYNOTES WILL MOST LIKELY BE ADJUSTED.
 PLEASE BE SURE TO CORRELATE.
  
 27) NOTE: PLEASE CORRELATE ARCHITECTURAL PLANS WITH
 THAT OF THE ELECTRICAL PLANS FOR ALL ROOM LAYOUTS AND
 FOOT PRINTS OF ROOMS/BUILDING. PLEASE SEE THE MAIN
 ELECTRICAL ROOM FOR ONE EXAMPLE. PLEASE SEE THE FLOOR
 LAYOUTS DO NOT CORRELATE AND REVIEW FOR SOME ITEMS FOR
 CODE COMPLIANCE CAN NOT BE DONE AT THIS TIME. PLEASE
 SEE THE ELECTRICAL PLANS DO NOT SHOW ANY ELECTRICAL
 ROOMS FOR THE TYPICAL LAYOUTS AND THE ELECTRICAL
 PANELS. PLEASE SEE NOT DOORS ARE BEING SHOWN TO ACCESS
 ANY PANELS? PLEASE SEE ARCHITECTURAL SHEETS AND
 CORRELATE.
 PLEASE SEE 240.24, 110.26 ETC
  
 28) NOTE: PLEASE SEE THE MAIN FLOOR AND TYPICAL FLOOR
 PLANS SHALL MEET A MINIMUM OF 1/8INCH SCALE. PLEASE
 SUBMIT FOR REVIEW AS MANY ITEMS ARE VERY SMALL FOR
 VERIFICATION.
 PLEASE SEE FBC ADMIN SECTION 106.1.2, 106..1.3.
  
 29) NOTE: PLEASE SEE PANEL MDP SHOWS THE MAIN OVER
 CURRENT DEVICE FOR PANEL R! AT 400AMPS, YET THIS PANEL
 R1 IS SHOWN AS 200AMP MLO?
 PLEASE SEE THERE ARE SEVERAL OTHER PANELS WHICH DO NOT
 CORRELATE WITH THE RISER OR ARE NOT SUBMITTED FOR PANEL
 SCHEDULES OR ARE LOCATED ON RISER DIAGRAM.
 PLEASE SEE SOME FOR EXAMPLE. PANEL RT, HT ETC. PLEASE
 CORRELATE ALL PANELS ON RISER, MDP AND PANEL SCHEDULES
 TO BE SUBMITTED.
 FBC ADMIN SECTION. 106.1.2, 106.3.5.1.2
 NEC 215.5, 408.4, 310.16, 240.4 ARE ONLY SOME SECTIONS
 WHICH CAN NOT BE VIEWED FOR CODE COMPLIANCE AS MANY OF
 THESE WERE NOT SUBMITTED ETC.
  
 30) NOTE: PLEASE SEE 210.60 WHICH REFERENCES TO 210.52
 FOR ITEMS REQUIRED.
 PLEASE SEE THERE ARE SEVERAL ITEMS FOR THIS. PLEASE
 KNOW AT THIS TIME IT SEEMS THESE MICROWAVE UNITS ARE
 BEING PERMANENTLY INSTALLED AT AN UPPER LEVEL. PLEASE
 SEE SOME OF THE FOLLOWING COMMENTS WHICH MAY VERY WELL
 APPLY.
 PLEASE ALSO SEE COMMENT WITH RESPECT TO THE HEIGHT OF
 THE MICROWAVE IN ACCESSIBLE UNITS.
  
 31) NOTE: PLEASE SEE MISSING THE SMALL APPLIANCE
 CIRCUITS AS REQUIRED PER 210.52B1, 210.11C1 AND 220.16.
 PLEASE KNOW THAT NO OTHER OUTLETS MAY BE FED FROM THESE
 CIRCUITS.
 (IF APPLICABLE)
  
 32) NOTE: PLEASE SEE 210.52B1 AS THERE ARE RECEPTACLES
 LOCATED IN THE KITCHEN/BREAKFAST/DINING AREAS WHICH ARE
 FED FROM THE LIGHTING CIRCUITS WHICH ARE NOT PERMITTED.
 PLEASE SEE 210.11C1, 220.16 AS NOTED IN NOTE #31 (WHERE
 APPLICABLE AS NOTE IN NOTE #30)
  
 33) NOTE: PLEASE SEE MISSING RECEPTS PER 210.52 FOR 2FT
 OF WALL , KITCHEN AREA, KITCHEN WALL OVER 2FT, WITHIN
 6FT OF DOORS ETC.
 PLEASE KNOW AS THE CODE DOES PERMIT THE SPACING FOR
 HOTEL/MOTELS AND GUEST SUITES TO BE SPACE FOR FURNITURE
 LAYOUTS, IT ALSO STILL REQUIRES THE SAME NUMBER OF
 RECEPTS WHICH WOULD BE REQUIRED IN A DWELLING TO BE
 INSTALLED.
 PLEASE SEE MOST UNITS SEEM TO BE OK, HOWEVER THERE ARE
 SOME UNITS WHICH DO NOT HAVE ANY RECEPTS LOCATE DON
 WALLS. PLEASE KNOW IF THIS IS NOT A UNIT WITH PERMANENT
 COOKING WHICH IS NOT YET DETERMINED THEN, SPACING MAY
 FALL UNDER GUEST ROOMS/SUITES AND NOT DWELLING. 210.60
  
 34) NOTE: PLEASE SEE THE HEIGHTS FOR THE MICROWAVES IN
 ACCESSIBLE UNITS ARE AT 62INCHES, WHERE ARE THESE UNITS
 GOING TO BE MOUNTED? AND SHOW DETAIL.
 FBC CHAPTER 11, FHAR 24CFR100.205
  
 35) NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTS SERVING
 KITCHEN COUNTER SPACES AND THE LIKE SHALL BE GFI/GFI
 PROTECTED.
  
 36) NOTE: PLEASE CLARIFY THE ARC FAULT PROTECTION WHICH
 IS NOT CURRENTLY BEING SHOWN. PLEASE SEE NOTE #30 AND
 IF UNITS CONTAIN PERMANENT COOKING MOUNTED EQUIPMENT
 THEN THESE WILL BE REQUIRED FOR PROTECTION IN SLEEPING
 ROOMS. 210.12
  
 37) NOTE: PLEASE COMPLETE ALL PANEL BOARDS WITH THE
 CONDUCTOR SIZES FOR ALL BRANCH CIRCUITS.
 PLEASE SEE 310.16, 240.4, FBC 106.1.2, 106.3.5.1.2
 REVIEW FOR CONDUCTORS CAN NOT BE DONE AT THIS TIME.
  
 38) NOTE: PLEASE SEE THE LOAD ON R1 EXCEEDS THAT OF THE
 RATING OF THE PANELS(S). SHOWN AT 200 AMPS. 240, 408
 ETC.
  
 39) NOTE: PLEASE SEE MISSING GROUNDING ELECTRODE SYSTEM
 AT THE FIRE PUMP SERVICE.
 250.50
  
 40) NOTE: PLEASE SUBMIT A COMPLETED GROUNDING ELECTRODE
 SYSTEM. PLEASE SEE PLANS DID NOT SHOW AS REQUIRED PER
 250.50. PLEASE SEE MISSING FOOTER STEEL.
 PLEASE ALSO SEE 250.104 FOR ANY WATER AND OTHER TYPES
 OF METAL PIPING. (SPRINKLER ETC)
  
 41) NOTE: PLEASE SEE MISSING GROUNDING ELECTRODE SYSTEM
 AT DETACHED BUILDINGS/STRUCTURES PER 250.32
  
 42) NOTE: PLEASE SEE MISSING PANEL SCHEDULE FOR PANEL
 "P".
 PLEASE SUBMIT AND COMPLETE EVEN FOR FUTURE LOAD ETC.
 THE MDP DOES LIST THE PANEL, YET LOADS CAN NOT BE
 VERIFIED FOR PANEL SCHEDULE.
 CONTINUOUS LOADS ETC.
 220, 215.3, 230.42.
 FBC 106.1.2
  
 43) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS AND
 SUMMARY FOR ALL LOADS AND SHOW ALL CONTINUOUS/LARGEST
 MOTOR LOADS AT 125%.
 220.3,220.10,220.11,220.13, 230.42, 215.3 ETC.
  
 44) NOTE: PLEASE SEE THAT ALL CIRCUITING AT THE POOL
 HOUSE STRUCTURE SHALL EITHER COME FROM PANEL P OR SHALL
 CONTAIN DISCONNECTING MEANS AND ALL SHALL BE GROUPED
 AND GROUNDED PER 225.31-225.39, 250.32.
  
 45) NOTE: PLEASE SEE SOME CIRCUITS ARE SHOWN FROM R
 PANEL(S).
 PLEASE ALSO CORRELATE ALL PLANS AND SHEETS AS THE PANEL
 P IS BEING SHOWN IN MULTIPLE LOCATIONS. ONE SHEET PANEL
 IS SHOWN IN ONE ROOM AND ANOTHER SHEET SHOWS THIS SAME
 PANEL LOCATED AT ANOTHER ROOM. PLEASE CORRELATE. FBC
 106.1.2 ADMIN SECTION FOR ADDITIONAL
 INFORMATION/CLARIFICATION.
  
 46) NOTE: PLEASE SEE ROOF TOP PLANS WHICH INDICATE A
 RTU HOWEVER NOT CIRCUITING IS BEING SHOWN ETC. PLEASE
 SEE 440.11 AND 210.63 FOR OTHER REQUIRED DISCONNECTS
 AND WP GFI REQUIRED.
  
 47) NOTE: PLEASE SEE NFPA-72 FOR REQUIREMENTS OF THE
 FACP CIRCUIT(S).
 4.4.1.4.2.1 THE DEDICATED BRANCH CIRCUIT(S) AND
 CONNECTIONS SHALL BE MECHANICALLY PROTECTED.
 4.4.1.4.2.2 CIRCUIT DISCONNECTING MEANS SHALL HAVE A
 RED MARKING SHALL BE ACCESSIBLE ONLY TO AUTHORIZED
 PERSONNEL, AND SHALL BE IDENTIFIED AS "FIRE ALARM
 CIRCUIT."
 4.4.1.4.2.3 THE LOCATION OF THE CIRCUIT DISCONNECTING
 MEANS SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM
 CONTROL UNIT
 PLEASE KNOW ANY NOTATION FOR THE REQUIRED LOCK OFF TYPE
 BREAKER SHALL STATE "ANY LOCK-OFF DEVICE SHALL HAVE THE
 HANDLE/LOCK AN INTEGRAL PART OF THE BREAKER" OR WORDS
 TO THAT AFFECT. PLEASE KNOW DEVICES SUCH AS THE
 SNAP/CLIP ON TYPE ARE NOT PERMITTED AS THEY ARE EASILY
 REMOVED OR FALL OFF WHEN A PANEL COVER IS REMOVED WHICH
 THEN NO LONGER PROVIDES THE NEEDED PROTECTION OF THE
 CIRCUITS(S).
  
  
 48) NOTE: PLEASE SEE MISSING NEUTRAL CONDUCTOR TO THE
 FIRE PUMP/FIRST MEANS OF DISCONNECT. PLEASE SEE
 250.24B, 250.24, 250.6. EVEN AS A MOTOR LOAD, THIS IS
 REQUIRED.
 PLEASE SEE AS NOTED, (250.6) NO EQUIPMENT GROUNDING
 CONDUCTOR IS INSTALLED BEFORE THE FIRST MEANS OF
 DISCONNECT.
 THIS WOULD CREATE OBJECTIONABLE CURRENTS.
  
 49) NOTE: PLEASE PROVIDE INFORMATION FOR KEY CARD
 ACCESS CONTROL SYSTEM. PLEASE SEE NFPA-1017 7.2.1,
 7.1.9, 7.2.1.5 WHICH REQUIRES THAT ANY ACCESS CONTROL
 OR DOOR LOCK SYSTEM NOT TO IMPEDED EGRESS IN ANY
 FASHION UNDER NORMAL OR EMERGENCY CONDITIONS. PLEASE
 ALSO SEE FIRE REVIEW'S POSSIBLE COMMENTS.
  
 50) NOTE: PLEASE SEE NFPA-72 11.8.3 WHICH REQUIRES
 LOCATIONS OF SMOKE DETECTORS TO BE INSTALLED WITH
 MINIMUM CRITERIA. PLEASE SEE AREAS WHERE THERE ARE
 SLOPED CEILINGS AS SHOWN ON THE ARCHITECTURAL SHEETS,
 THE SD SHALL BE INSTALLED WITHIN 3FT OF THE PEAK OF
 THAT SLOPE. (LOUNGE) ETC OR WITHIN 12 INCHES OF THE
 HIGHEST POINT ON A FLAT CEILING. PLEASE NOTE THE
 REQUIREMENTS AS LISTED. (3FT FROM BATH ROOM AND KITCHEN
 DOORS/OPENINGS ETC. PLANS DO ALREADY CONTAIN A NOTE FOR
 THE SMOKE DEVICE BEING PHOTO-ELECTRIC IN SOME AREAS.
 THIS COMMENT MAYBE EXPANDED UPON.
 PLEASE SE PREVIOUS NOTE WITH RESPECT TO LOCATION
 MISSING WHICH WILL REQUIRE ADDITIONAL.
  
 50) NOTE: PLEASE CLARIFY THE CIRCUIT ON M1 WHICH SHOWS
 A CIRCUIT TO THE FIRE PUMP CONTROLLER? PLEASE SEE THIS
 FPC IS BEING FED FROM A SEPARATE SERVICE AND SERVICE
 ENTRANCE WHICH MAY NOT CONTAIN CIRCUITS FROM OTHER
 SERVICE EQUIPMENT TO THE SAME EQUIPMENT.
 230
  
 51) NOTE: PLEASE SEE NOTE ON RISER WHICH STATES THE
 FIRE PUMP SHALL MEET THE LATEST EDITION OF THE NEC.
 PLEASE KNOW THE CODE IN GENERAL OR SECTIONS OF THE CODE
 SHALL NOT BE QUOTED ON PLANS IN LIEU OF THE REQUIRED
 INFORMATION, DETAILS OR DESIGN CRITERIA.
 PLEASE KNOW AS NOTED ABOVE WHERE REQUIRED CODES
 RELEVANT TO THIS PROJECT SHALL BE ON PLANS, THE STATE
 OF FLORIDA ADOPTED THE 2005 NEC /NFPA-70 ON DECEMBER
 8TH, 2006 WHICH WOULD BE "LATEST EDITION", HOWEVER THIS
 PROJECT AS IT WAS SUBMITTED FOR PERMITTING BEFORE SUCH
 DATE WILL BE UNDER THE PREVIOUS CODE AND NOT THE LATEST
 EDITION.
  
 52) NOTE: PLEASE PLACE ALL ROOM AND AREA DESIGNATIONS
 ON PLANS. THIS IS REQUIRED FOR ALL ENLARGED LAYOUT
 SHEETS AS WELL.
 FBC 106.1.2, 106.3.5.1.2
  
 53) NOTE: PLEASE SHOW AND COMPLETE LOAD CALCULATIONS
 FOR TRACK LIGHTING PER 220.12B
  
 54) NOTE: PLEASE SEE 240.4C WHICH REQUIRES ALL SERVICE
 ENTRANCE CONDUCTOR AMPERAGE FOR DEVICES RATED 800AMPS
 OR MORE TO MEET OR EXCEED THE RATED DEVICE. PLEASE SEE
 310.16, 110.14
  
 55) NOTE: PLEASE SEE SOME ROOMS ON PLANS ARE MISSING
 LIGHTING. PLEASE SEE EXAMPLE OF THE ELEVATOR MACHINE
 ROOM.
 PLEASE COMPLETE PLANS. LS 101 7.8, 7.9
 FBC ADMIN SECTION 106.3.5.1.2
  
 56) NOTE: PLEASE KNOW DOORS SHALL BE SHOWN FOR ALL
 ROOMS, MORE SPECIFICALLY THE MAIN ELECTRICAL ROOM(S),
 ELEVATOR ROOMS ETC. PLEASE KNOW THE LAYOUTS FROM THE
 ARCHITECTURAL SHEETS AND THE ELECTRICAL SHEETS DO NOT
 CORRELATE, THE DOOR SWINGS MAY BE AN ISSUE IF THE DOORS
 ARE ACTUALLY ON THE INSIDE AND LOCATED IN AN EGRESS
 CORRIDOR. PLEASE SEE FBC AND LS101 FOR DOOR SWINGS IN
 EGRESS PATHS.7.2.1.4 ETC
  
 57) NOTE: PLEASE SEE 210.8B3 FOR BRANCH CIRCUITS IN
 KITCHEN AREAS AND THE LIKE WHICH REQUIRES PROTECTION
 FOR ALL 15/20 AMP 120 CIRCUITS.
  
 58) NOTE: PLEASE SEE SITE PLAN SHEET SHOWS THE NOTES
 FOR THE MAIN ELECTRICAL ROOM SERVICE AND OTHER SITE
 ELECTRICAL, HOWEVER PLEASE SEE THE SERVICE FOR THE FIRE
 PUMP IS NOT SHOWN? PLEASE SEE RISER SHOWS THIS COMING
 FROM THE SAME TRANSFORMER.
 PLEASE SHOW. FBC 106.1.2 FOR ADDITIONAL INFORMATION
 REQUIRED.
  
  
 *** PLEASE KNOW AS THERE ARE MANY ITEMS NOT SUBMITTED
 FOR REVIEW, PLANS NOT DESIGNED TO FBC CHAPTER 13 ETC,
 THERE MAY BE FUTURE REVIEW COMMENTS ON THE FOLLOW UP
 REVIEW.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-01-07 11:11:522007-01-07 11:11:52
 REVIEW COMMENCED
2007-01-03 07:33:362007-01-03 07:33:36
 IN ELECTRIC FOR REVIEW

Review Stop ENG ENGINEERING CSD
Rev No 9 Status P Date 2009-06-16 Cont ID  
Sent By dlauderm Date 2009-06-16 Time 12:18 Rev Time 0.00
Received By dlauderm Date 2009-06-16 Time 12:13 Sent To  
Notes
2009-06-16 12:18:33APPROVED WITH PROVISOS:
 1. ALL POLLUTION CONTROL SHALL BE KEPT IN PLACE UNTIL
 CO OF PHASE II BUILDING.
 2. ALL PROTECTIVE DEVICES AROUND AND IN CATCH BASINS
 WILL BE KEPT IN PLACE IN PHASE I UNTIL PHASE II HAS
 BEEN COED.
 3. SILT FENCE SHALL BE INSTALLED WITH TEMPORARY
 CONSTRUCTION FENCE MENTIONED IN THE NOTES ON PHASING
 (SHEET 2 OF 9).

Review Stop ENG ENGINEERING CSD
Rev No 8 Status P Date 2009-04-13 Cont ID  
Sent By dlauderm Date 2009-04-13 Time 10:25 Rev Time 0.00
Received By dlauderm Date 2009-04-13 Time 10:15 Sent To  
Notes
2009-04-13 10:24:28PASSED WITH PROVISOS:
 1) IN PAST REVIEWS R, CHOSKI HAD ASKED THAT OUR
 STANDRADS BE FOLLWED FOR DUMPSTERS. THEY HAVE NOT. THE
 MINIMUM DOOR OPENING IN A DUMPSTER ENCLOSER MUST BE
 12.5' WIDE. THE OPENING SHOWED FOR THE ENCLOSURE IS
 13.0' WIDE WITH THE 6" STEEL PIPE USED TO HOLD THE GATE
 OPEN ON SHEET C4. THIS WOULD MEAN THERE WOULD BE A
 MINIMUM OPENING OF LESS THAN 12.0', SINCE THE GATES ARE
 SHOWN INSIDE THE POSTS. WHILE ON SHEET SP-1 THEY ARE
 SHOWN TO BE SQUARE WITH THE GATES ON THE INSIDE,
 LEADING ME TO ASSUME THAT THE GATE OPENING WILL BE LESS
 THAN 12.5' WIDE. THE GATES NEED TO BE INSTALLED WITH AN
 INTERNAL OPENING OF 12.5' AS STATED IN OUR STANDARDS
 AND AS ASKED FOR IN THE PREVIOUS REVIEWS.

Review Stop ENG ENGINEERING CSD
Rev No 7 Status P Date 2008-10-22 Cont ID  
Sent By dlauderm Date 2008-10-22 Time 11:53 Rev Time 0.00
Received By dlauderm Date 2008-10-22 Time 11:53 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 6 Status F Date 2008-09-09 Cont ID  
Sent By shill Date 2008-09-09 Time 16:24 Rev Time 0.00
Received By shill Date 2008-09-09 Time 16:24 Sent To  
Notes
2008-09-09 16:26:31***CORRECTIONS**
  
 JONATHAN BRAMLEY
 561-494-1040
  
 **NOTE - CIVIL SHEETS SUBMITTED DO NOT MATCH SHEETS
 SUBMITTED FOR THE ISSUED SITEWORK PERMIT**
  
 1. THE ISSUED PERMIT WAS SIGNED AND SEALED BY MICHAEL
 W. HAGERTY, PE; NEW SHEETS SUBMITTED WITH 06111067 ARE
 SIGNED AND SEALED BY PHILIP ROWE, JR., PE. THE PLANS
 ARE TO BE SIGNED AND SEALED BY THE PROFESSIONAL
 ENGINEER IN RESPONSIBLE CHARGE, FAC61G15-23.002(2). IF
 THIS IS A SUCCESSOR ENGINEER, PLEASE PROVIDE A LETTER
 STATING THAT THE PROCEDURES OF FAC61G15-27.001 HAVE
 BEEN FOLLOWED.
  
 2. THE NEW CIVIL SHEETS SUBMITTED WITH 06111067 DO NOT
 MATCH THE SITEWORK PERMIT RECORD SET. SHEETS 6 AND 7-9
 WERE REMOVED FROM THE SITEWORK PERMIT (SHEETS REMOVED
 AND STRUCK OUT ON THE INDEX SHEET). PLEASE REVISE THE
 SITEWORK PERMIT AS NECESSARY. AS THE SITEWORK PERMIT
 HAS ALREADY ISSUED, THE PAGES SUBMITTED WITH THE
 BUILDING PERMIT SHOULD MATCH THE RECORD SET.
  
 3. THE SHEETS SUBMITTED WITH 06111067 DO NOT INDICATE
 ANY CHANGES; NO CLOUDS OR REVISION NUMBERS, ALTHOUGH
 REVISIONS WERE MADE (INDEX SHEET, ADDITION OF SHEETS 6
 THROUGH 9). CHANGES TO THE PLAN ARE TO BE CLEARLY
 INDICATED WITH CLOUDS AND REVISION DATES/NUMBERS.
  
 4. IF THESE SHEETS ARE NOT REQUIRED TO SHOW CODE
 COMPLIANCE FOR THE BUILDING (FOR EXAMPLE, PARKING OR A
 SITE PLAN), AND ALL REQUIRED INFORMATION FOR BUILDING,
 ZONING, ETC. ARE SHOWN ON OTHER SHEETS (ARCHITECTURAL
 OR ENGINEERING SHEETS), THEY CAN BE REMOVED FROM THE
 PLAN. AS THE SITEWORK PERMIT HAS BEEN ISSUED, THEY
 MIGHT NOT BE NECESSARY FOR THE BUILDING PERMIT. PLEASE
 CONFIRM INFORMATION REQUIRED. IF THESE SHEETS ARE
 REQUIRED, PLEASE REVISE THE SITEWORK PERMIT SO THAT THE
 TWO ARE THE SAME.
  
  

Review Stop ENG ENGINEERING CSD
Rev No 5 Status P Date 2008-03-03 Cont ID  
Sent By rchokshi Date 2008-03-03 Time 11:11 Rev Time 0.00
Received By rchokshi Date 2008-03-03 Time 11:11 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 4 Status F Date 2008-01-18 Cont ID  
Sent By rchokshi Date 2008-01-18 Time 11:30 Rev Time 0.00
Received By rchokshi Date 2008-01-18 Time 11:04 Sent To  
Notes
2008-01-18 11:29:52****FAILED******
  
 1. TWO OF THE THREE DRAWING SETS NOT SEALED & SIGNED BY
 P.E. OF SIMMONS & WHITE, INC
 2. ONE SEALED & SIGNEDOF THE THREE SETS NOT REVISED
 PER LATEST NOTE,FOR EXAMPLE SHEET 4 0F 9 DUMPSTER
 DETAIL REVISED PER YOUR NOTE AND SHEET 5 OF 9
 UNREVISED 2 NOTESSAYS IN ONE SET & DOES NOT SAY THAT
 IN OTHER SET, AND SO FORTH, ALLDRAWINGS IN EACH SET
 MUST BE CONSISTENT TO THE LATEST REVISION.
 3.PLEASE RESUBMIT WITH THE LASTESTREVISIONIN ALL
 3 SETS IDENTICALAT TIME WHEN YOU RESUBMIT THE WHOLE
 PROJECT OF THIS PERMIT #.I THOUGHTI SAW YOUR
 DRAWING SET IN SOMETIME INDEC 07HAD ALL REVISIONS,
 BUT IF YOU REVISED AGAIN PLEASE INCLUDE THEM.
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2007-10-11 Cont ID  
Sent By rchokshi Date 2007-10-11 Time 11:48 Rev Time 0.00
Received By rchokshi Date 2007-10-11 Time 11:48 Sent To  
Notes
2007-10-11 11:48:35PASSED
  
 NEED 3 SETS OF LAST REVISED CIVIL PAVINGS & DRAINAGE
 DRAWINGS FOR STAMPS & SIGN.READY FOR PASS & SIGNATURE
 & STAMP.
  
 RASIK CHOKSHI805-6723
  
  
 RECEIVED 3 SETS, SIGNED & STAMPED PUT TOGETHER3 SETS
 WITH WHOLE FILE.10/17/07 RASIK

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2007-04-13 Cont ID  
Sent By rchokshi Date 2007-04-13 Time 15:32 Rev Time 0.00
Received By rchokshi Date 2007-04-13 Time 15:33 Sent To  
Notes
2007-04-13 15:32:47PLEASE PROVIDE FOLLOWING INFO:
  
 1. PLEASE SHOW ON DRAWINGS STANDARDS NOTES OF CITY OF
 WPB(WHICH YOU CAN GET IN A CD FROM 45TH STREET ENG) FOR
 SIDEWALK WIDTH , ITS SLOPE, DRIVEWAY, PARKING, HANDICAP
 PARKING, PAINTPER CITY CODES ETC.,, MUST MEET PER
 ADA,,ETC.,
 2. PLEASE SHOW ON DRAWINGS STANDARDS NOTES OF CITY OF
 WPB(WHICH YOU CAN GET FROM 45TH STREET ENG) FOR
 DUMPSTER & ITS ENCLOSURE PER CITY OF WPB, &LOCATION
 ON DWG, LOCATION MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 3. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD ,
 SIDEWALK ELEVATION MUST MEET FLOOD ZONE AREA & FLORIDA
 BLDG CODE, PLEASE SHOW ON THE DRAWINGS.
 4. PLEASE SHOW CALCULATION FOR EXFILTRATION TRENCH
 LENGTH. WHAT SAFETY FACTOR YOU USED IN LENGTH?
 5.PLEASE SHOW STORM WATER CALCULATIONS, WHAT CRITERIA
 YOU ASSUMEDFOR RUNOFF CAL.,, LIKE 1" OVER ENTIRE SITE
 OR2.5"CRITERIA, ?PERVIOUS AREA, LIKE GREEN,
 LAKES, ETC,IMPERVIOUS AREA CAL.,
 6. WHAT IS THE SITE AREA, YOU ARE DEVELOPING FOR THIS
 PROJECT ? PLEASE SHOW TOTAL PERVIOUS, IMPERVIOUS AREA
 ON SEPARATE SHEET.
 7. HOW YOU CONNECT TO THE STORM WATER PIPES IN YOUR
 SITE? ITS DETAILS.PLEASE SHOW ALL STORM WATER PIPES
 AROUND YOUR SITE SO, WE CANSEE THE BEST PIPE TO
 CONNECT WITH THE STORM WATERFROM ALL OTHER STORM
 WATER PIPES. PLEASE SHOW DETAIL OF THE CONTROL
 STRUCTURES WITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC PLEASE SHOW CALCULATIONS FOR
 EXFILTRATION TRENCH.
 8.PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND YOUR
 SITE FOR STORM WATER DRAIN.
 9. PLEASE GET UTILITY APPROVAL FROM MANNY G. 45TH
 STREET ENG DEPT.
  
 PLEASE RESPOND EACHITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2007-01-11 Cont ID  
Sent By rchokshi Date 2007-01-11 Time 14:08 Rev Time 0.00
Received By rchokshi Date 2007-01-11 Time 13:50 Sent To  
Notes
2007-01-11 14:19:20PLEASE PROVIDE FOLLOWING INFO:
  
 1. PLEASE SHOW ON DRAWINGS STANDARDS NOTES OF CITY OF
 WPB FOR SIDEWALK WIDTH , ITS SLOPE, DRIVEWAY, PARKING,
 HANDICAP PARKING, PAINTPER CITY CODES ETC.,, MUST
 MEET PER ADA,,ETC.,
 2. PLEASE SHOW ON DRAWINGS STANDARDS NOTES FOR
 DUMPSTER & ITS ENCLOSURE PER CITY OF WPB, &LOCATION
 ON DWG, LOCATION MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 3. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD ,
 SIDEWALK ELEVATION MUST MEET FL BLDG CODE, PLEASE SHOW
 ON THE DRAWINGS.
 4. PLEASE PROVIDE A COPY OF SFWMD PERMIT, & GEOTECH
 REPORT
 5.PLEASE SHOW STORM WATER CALCULATIONS, WHAT CRITERIA
 YOU ASSUMEDFOR RUNOFF CAL.,, LIKE 1" OVER ENTIRE SITE
 OR2.5"CRITERIA, ?PERVIOUS AREA, LIKE GREEN,
 LAKES, ETC,IMPERVIOUS AREA CAL.,
 6. WHAT IS THE SITE AREA, YOU ARE DEVELOPING FOR THIS
 PROJECT ONLY ? PLEASE SHOW TOTAL PERVIOUS, IMPERVIOUS
 AREA ON SEPARATE SHEET.
 7. HOW YOU CONNECT TO THE STORM WATER PIPES IN YOUR
 SITE? ITS DETAILS.PLEASE SHOW ALL STORM WATER PIPES
 AROUND YOUR SITE SO, WE CANSEE THE BEST PIPE TO
 CONNECT WITH THE STORM WATERFROM ALL OTHER STORM
 WATER PIPES. PLEASE SHOW DETAIL OF THE CONTROL
 STRUCTURES WITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC PLEASE SHOW CALCULATIONS FOR
 EXFILTRATION TRENCH.
 8.PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND YOUR
 SITE FOR STORM WATER DRAIN.
 9. PLEASE GET UTILITY APPROVAL FROM MANNY G. 45TH
 STREET ENG DEPT.
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 12 Status P Date 2009-06-19 Cont ID  
Sent By mawillia Date 2009-06-19 Time 13:28 Rev Time 0.00
Received By mawillia Date 2009-06-19 Time 13:01 Sent To  
Notes
2009-06-19 13:28:39*****REVISION, FOR PROJECT PHASING, APPROVED*****
  
 PLAN SHEET SP-1 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 11 Status P Date 2009-05-06 Cont ID  
Sent By mawillia Date 2009-05-06 Time 11:37 Rev Time 0.00
Received By mawillia Date 2009-05-06 Time 11:09 Sent To  
Notes
2009-05-06 11:36:59*****REVISION APPROVED*****
  
  
 REVISED PLAN SHEETS A-101 AND A-401 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 10 Status F Date 2009-04-24 Cont ID  
Sent By mawillia Date 2009-04-24 Time 11:08 Rev Time 0.00
Received By mawillia Date 2009-04-24 Time 09:38 Sent To  
Notes
2009-04-24 11:08:24*****DENIED*****
  
 1. THE PROJECT SITE ADDRESS SHALL BE IN THE TITLE BLOCK
 OF EACH SUBMITTED PLAN SHEET.
  
 2. NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 3. SPECIFY INTERIOR WALL AND CEILING FINISH MATERIALS
 IN TERMS OF CLASS A, CLASS B, OR CLASS C AS PER
 28.3.3.2 OF NFPA 101.
  
 4. SPECIFY INTERIOR FLOOR FINISH IN TERMS OF CLASS I OR
 CLASS II AS PER 28.3.3.3 OF NFPA 101.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 9 Status N Date 2009-04-10 Cont ID  
Sent By adarroug Date 2009-04-10 Time 08:51 Rev Time 0.00
Received By adarroug Date 2009-04-08 Time 13:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 8 Status P Date 2009-04-03 Cont ID  
Sent By mwennerg Date 2009-04-03 Time 10:20 Rev Time 0.00
Received By mwennerg Date 2009-04-03 Time 10:20 Sent To  
Notes
2009-04-03 10:21:44REVISION DATED 10/30/08

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status P Date 2008-09-05 Cont ID  
Sent By mawillia Date 2008-09-05 Time 13:23 Rev Time 0.00
Received By mawillia Date 2008-09-05 Time 12:38 Sent To E
Notes
2008-09-05 12:42:14*****REVISIONS APPROVED*****
  
 REVISED PLAN SHEETS A-604, E-101, E-401, AND E-402 WERE
 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2008-05-29 Cont ID  
Sent By mawillia Date 2008-05-29 Time 11:57 Rev Time 0.00
Received By mawillia Date 2008-05-29 Time 11:19 Sent To  
Notes
2008-05-29 11:57:28*****REVISION, DATED 3/03/2008, APPROVED*****
  
  
 PLAN SHEETS G-003, FS1, AND E-101 THRU E-104 WERE
 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2008-03-18 Cont ID  
Sent By mawillia Date 2008-03-18 Time 15:41 Rev Time 0.00
Received By mawillia Date 2008-05-29 Time 11:18 Sent To  
Notes
2008-03-18 14:55:16*****APPROVED*****
  
  
 PLAN SHEETS G-003, A-202, FS1, E-101 THRU E-104, AND
 FP1 THRU FP6 WERE STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-02-11 Cont ID  
Sent By mawillia Date 2008-02-11 Time 18:24 Rev Time 0.00
Received By mawillia Date 2008-02-11 Time 16:05 Sent To  
Notes
2008-02-11 16:29:03*****PROVISO*****
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN SATISFIED;HOWEVER THE APPROPIATE PLAN SHEETS TO
 BE FIRE-STAMPED WHEN THE OTHER REVIEWERS HAVE BEEN
 SATISFIED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2007-10-24 Cont ID  
Sent By mawillia Date 2007-10-24 Time 18:17 Rev Time 0.00
Received By mawillia Date 2007-10-24 Time 16:51 Sent To  
Notes
2007-10-24 17:18:59*****DENIED*****
  
 THE FOLLOWING COMMENTS OF THE PREVIOUS 29 STILL NEED TO
 BE ADDRESSED:
  
  
 01.THE COMPLETE ADDRESS OR ACTUAL ADDRESS OF WHERE
 THE SCOPE OF WORK WILL BE CONDUCTED SHALL BE IN THE
 TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.NO ADDRESS
 SHOWN ON THE NEW SUBMITTED FIRE SPRINKLER SHEETS
  
 05.KNOX-BOX WILL BE REQUIRED FOR THE BUILDING.FOR
 KNOX APPLICATIONS, CONTACT WEST PALM BEACH FIRE
 PREVENTION BUREAU AT 561-804-4724.KNOX BOX AS SHOWN
 ON SHEET A-101 APPEARS TO BE INSIDE THE GENERAL
 MANAGER'S OFFICE. THIS DEVICE SHALL BE INSTALLED IN AN
 ACCESSIBLE LOCATION AT THE FRONT ENTRANCE AREA.
  
 06. ON THE APPROPIATE EXTERIOR ELEVATION FRONTING
 METROCENTRE BOULEVARD EAST,POST THE NUMERICAL ADDRESS
 ON THE BUILDING.AS PER WEST PALM BEACH CODE, THOSE
 NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS
 THAN 1" IN WIDTH.ONCE THIS PERMIT HAS BEEN ISSUED,
 THE NUMERICAL ADDRESS SHALL BE TEMPORARILY POSTED
 BEFORE & DURING CONSTRUCTION OPERATIONS, AND PERMANENLY
 POSTED AFTER CONSTRUCTION PRIOR TO ATTAINING A
 CERTIFICATE OF OCCUPANCY.IF THE BUILDING IS SET-BACK
 FROM THE STREET OR ROADSIDE, A NUMERICAL ADDRESS ( THE
 SAME DIMENSIONS AS PER WPB CODE) SHALL BE REQUIRED ON
 THE MONUMENT SIGN OR MARQUEE IN ADDITION TO THOSE ON
 THE BUILDING.ADDRESS NOT SHOWN ON SHEET AC-101 AS
 PER YOUR RESPONSE LETTER;PLEASE COMPLY
  
 25.KNOX LOCKING CAPS WILL BE REQUIRED ON FIRE
 DEPARTMENT CONNECTIONS (FDC). CONTACT WEST PALM BEACH
 FIRE PREVENTION AT 561-804-4724 FOR KNOX APPLICATIONS.
 ADD TO FIRE SPRINKLER PLAN SHEET; PLEASE COMPLY
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-04-26 Cont ID  
Sent By mawillia Date 2007-04-26 Time 14:00 Rev Time 0.00
Received By mawillia Date 2007-04-25 Time 16:28 Sent To  
Notes
2007-04-25 16:38:52*****DENIED*****
  
 NOTICE:THE INFORMATION ON THE SUBMITTED PLAN SHEETS
 ARE INCONSISTENT WHICH MAKE THE PLAN REVIEW PROCESS
 MORE TEDIOUS, TIME CONSUMING , AND CONFUSING FOR THE
 REVIEWERS.FOR EXAMPLE -THE FIRE PUMP ROOM MAY BE
 INDICATED AS FIRST FLOOR EAST END OF THE BUILDING ON A
 PLAN SHEET, BUT ON ANOTHER SHEET FOR THE SAME LOCATION
 AN ELECTRICAL ROOM IS OUTLINED.SEE COMMENTS #16 AND
 #18 FOR OTHER EXAMPLES OF THIS OCCURRING.
  
 01.THE COMPLETE ADDRESS OR ACTUAL ADDRESS OF WHERE
 THE SCOPE OF WORK WILL BE CONDUCTED SHALL BE IN THE
 TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.PLEASE
 COMPLY
  
 03.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD
 TO THE APPROPIATE PLAN(S)
  
 04.EXIT STAIRS ARE TO BE KEPT UP WITH CONSTRUCTION.
 ADD TO THE APPROPIATE PLAN SHEET(S)
  
 05.KNOX-BOX WILL BE REQUIRED FOR THE BUILDING.FOR
 KNOX APPLICATIONS, CONTACT WEST PALM BEACH FIRE
 PREVENTION BUREAU AT 561-804-4724.ACCESS(KNOX) BOXIS
 TO BE INSTALLED IN AN ACCESSIBLE LOCATION SHERE ACCESS
 TO OR WITHIN THE STRUCTURE MAY BE GAINED
  
 06. ON THE APPROPIATE EXTERIOR ELEVATION FRONTING
 METROCENTRE BOULEVARD EAST,POST THE NUMERICAL ADDRESS
 ON THE BUILDING.AS PER WEST PALM BEACH CODE, THOSE
 NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS
 THAN 1" IN WIDTH.ONCE THIS PERMIT HAS BEEN ISSUED,
 THE NUMERICAL ADDRESS SHALL BE TEMPORARILY POSTED
 BEFORE & DURING CONSTRUCTION OPERATIONS, AND PERMANENLY
 POSTED AFTER CONSTRUCTION PRIOR TO ATTAINING A
 CERTIFICATE OF OCCUPANCY.IF THE BUILDING IS SET-BACK
 FROM THE STREET OR ROADSIDE, A NUMERICAL ADDRESS ( THE
 SAME DIMENSIONS AS PER WPB CODE) SHALL BE REQUIRED ON
 THE MONUMENT SIGN OR MARQUEE IN ADDITION TO THOSE ON
 THE BUILDING.PLEASE COMPLY
  
 07.TEMPORARY STANDPIPES ARE REQUIRED WHEN THE
 BUILDING REACHES THREE STORIES OR 30 FEET IN HEIGHT.
 ADD TO AN APPROPIATE PLAN SHEET
  
 08.FIRE DOORS AND WINDOWS SHALL COMPLY WITH NFPA 80.
 ADD TO SHEET A-604
  
 09.DOORS THAT OPEN ONTO EXIT ACCESS CORRIDORS SHALL
 NOT HAVE LESS THAN A 20-MINUTE FIRE PROTECTION RATING.
 THOSE DOORS SHALL BE SELF-CLOSING AND SELF-LATCHING.
 ADD TO SHEET A-604
  
 10.HORIZONTAL-SLIDING DOORS THAT ARE PART OF THE
 REQUIRED MEANS OF EGRESS SHALL COMPLY WITH 7.2.1.4.1.4
 OF NFPA 101.ADD TO SHEET A-604
  
 11.THE INTERIOR FINISH CLASSIFICATION FOR WALLS AND
 CEILING SHALL BE CLASS A FOR EXIT ENCLOSURES, CLASS A
 OR B FOR LOBBIES AND CORRIDORS, AND CLASS A, B, OR C
 FOR OTHER SPACES.ADD TO SHEET A-606;BE SPECIFIC AS
 WHATTHESE AREAS WILL BE CLASSIFIED
  
 12.PROVIDE PRESCRIPTIVE DETAIL STRENGHTS FOR ALL
 HANDRAILS AND GUARDRAILS. ADD TO SHEET A-701
  
 13.ELEVATOR WARNING SIGNS WILL BE REQUIRED IN THE
 LOBBIES. ADD TO SHEET A-702
  
 14.AT LEAST ONE IDENTIFIBLE ELEVATOR SHALL BE
 AVAILABLE FOR USE BY THE FIRE DEPARTMENT IN CASE OF
 EMERGENCY. ADD TO SHEET A-702
  
 16.THERE IS NO INDICATION OF THE LOCATION FOR THE
 HEARING IMPAIRED ROOM ON THE FIFTH FLOOR (SHEET A-105)
 , BUT IS INDICATED AS ROOM 503 ON SHEET AR-105.SHOW
 CONSISTENCY OF PLAN SHEETS
  
 17.A FLOOR DIAGRAM REFLECTING THE ACTUAL FLOOR
 ARRANGEMENT, EXIT LOCATIONS AND ROOM IDENTIFICATION
 SHALL BE POSTED IN A LOCATION AND MANNER ACCEPTABLE TO
 THE AHJ ON, OR IMMEDIATELY ADJACENT TO, EVERY GUEST
 ROOM IN THE HOTEL.ADD TO SHEET A-411AND A-412
  
 18.SMOKE DETECTORS ARE NOT SHOWN FOR THE ELEVATOR
 LOBBY, ICE ROOM, OR ELECTRIC ROOM ON SHEETS E-101,
 E-102, E-103; HOWEVER THEY ARE CORRECTLY SHOWN ON
 SHEETS E-203 AND E-204.SHOW CONSISTENCY OF PLAN
 SHEETS
  
 19.PLEASE PROVIDE A LAYOUT OF THE FIRE ALARM SYSTEM
 INDEPENDENT OF THE ELECTRICAL SHEETS.PLEASE COMPLY;
 SEE ELECTRICAL PLAN NOTE #14
  
 20.THE FIRE ALARM SYSTEM SHALL BE FULLY ADDRESSABLE
 AND U.L. CETIFICATED FOR CENTRAL STATION SERVICE.ADD
 TO THE FIRE ALARM PLAN SHEET
  
 21.ALL GUESTROOMS FOR HEARING IMPAIRED SHALL BE
 PROVIDED WITH FIRE ALARM VISUAL DEVICES.
  
 22.DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM AS PER WEST PALM BEACH FIRE PREVENTION.ADD
 TO THE FIRE ALARM PLAN SHEET
  
 23.PLEASE PROVIDE A LAYOUT OF THE FIRE SPRINKLER
 SYSTEM INDEPENDENT OF THE PLUMBING SHEETS.INCLUDE THE
 LOCATION OF THE FIRE DEPARTMENT CONNECTION(S) AND THE
 DOUBLE DETECTOR CHECK VALVE ASSEMBLY.PLEASE COMPLY;
 SEE ELECTRICAL NOTE #14
  
 24.ELECTRONIC SWITCHES IN ADDITION TO CHAIN AND LOCK
 IS REQUIRED FOR THE DOUBLE DETECTOR CHECK VALVE
 ASSEMBLY.ADD COMMENT TO CIVIL SHEET (8 OF 9) OR TO
 THE FIRE SPRINKLER PLAN SHEET
  
 25.KNOX LOCKING CAPS WILL BE REQUIRED ON FIRE
 DEPARTMENT CONNECTIONS (FDC). CONTACT WEST PALM BEACH
 FIRE PREVENTION AT 561-804-4724 FOR KNOX APPLICATIONS.
 ADD TO FIRE SPRINKLER PLAN SHEET
  
 26.PROVIDE SPECIFICATIONS FOR THE FIRE PUMP AND
 ASSOCIATED EQUIPMENT.PLEASE COMPLY
  
 27.SIGNS REQUIRED IN STAIRWELLS INDICATING FLOOR
 IDENTITY.ADD TO SHEET A-701
  
 28.FIRE EXTINGUISHERS ARE TO BE 2A:10 BC.ADDITIONAL
 EXTINGUISHERS MAY BE NEEDED IF THE TRAVEL DISTANCE TO
 THIS EQUIPMENT IS GREATER THAN 75 FEET FROM A ROOM IN
 THE BUILDING OR ON THE FLOOR OF THE BUILDING.
  
 29.SEPARATE PLAN AND PERMITS WILL BEREQUIRED FOR
 ANY COOKING HOOD INSTALLATION ANDASSOCIATED FIRE
 SUPPRESSION SYSTEM PLANNED.PLEASE ACKNOWLEDGE
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-02-17 Cont ID  
Sent By mawillia Date 2007-02-17 Time 22:48 Rev Time 0.00
Received By mawillia Date 2007-02-17 Time 17:27 Sent To  
Notes
2007-02-18 01:27:20*****DENIED*****
  
 NOTICE:THE INFORMATION ON THE SUBMITTED PLAN SHEETS
 ARE INCONSISTENT WHICH MAKE THE PLAN REVIEW PROCESS
 MORE TEDIOUS, TIME CONSUMING , AND CONFUSING FOR THE
 REVIEWERS.FOR EXAMPLE -THE FIRE PUMP ROOM MAY BE
 INDICATED AS FIRST FLOOR EAST END OF THE BUILDING ON A
 PLAN SHEET, BUT ON ANOTHER SHEET FOR THE SAME LOCATION
 AN ELECTRICAL ROOM IS OUTLINED.SEE COMMENTS #16 AND
 #18 FOR OTHER EXAMPLES OF THIS OCCURRING.
  
 01.THE COMPLETE ADDRESS OR ACTUAL ADDRESS OF WHERE
 THE SCOPE OF WORK WILL BE CONDUCTED SHALL BE IN THE
 TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 02.ON SHEET G-000, INCLUDE COMPLETE ADDRESS UNDER
 BUILDING INFOMATION.UNDER GOVERNING CODES, THE 2003
 EDITION OF NFPA 101 SHALL BE REFERENCED.
  
 03.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 04.EXIT STAIRS ARE TO BE KEPT UP WITH CONSTRUCTION.
  
 05.KNOX-BOX WILL BE REQUIRED FOR THE BUILDING.FOR
 KNOX APPLICATIONS, CONTACT WEST PALM BEACH FIRE
 PREVENTION BUREAU AT 561-804-4724.
  
 06. ON THE APPROPIATE EXTERIOR ELEVATION FRONTING
 METROCENTRE BOULEVARD EAST,POST THE NUMERICAL ADDRESS
 ON THE BUILDING.AS PER WEST PALM BEACH CODE, THOSE
 NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS
 THAN 1" IN WIDTH.ONCE THIS PERMIT HAS BEEN ISSUED,
 THE NUMERICAL ADDRESS SHALL BE TEMPORARILY POSTED
 BEFORE & DURING CONSTRUCTION OPERATIONS, AND PERMANENLY
 POSTED AFTER CONSTRUCTION PRIOR TO ATTAINING A
 CERTIFICATE OF OCCUPANCY.IF THE BUILDING IS SET-BACK
 FROM THE STREET OR ROADSIDE, A NUMERICAL ADDRESS ( THE
 SAME DIMENSIONS AS PER WPB CODE) SHALL BE REQUIRED ON
 THE MONUMENT SIGN OR MARQUEE IN ADDITION TO THOSE ON
 THE BUILDING.
  
 07.TEMPORARY STANDPIPES ARE REQUIRED WHEN THE
 BUILDING REACHES THREE STORIES OR 30 FEET IN HEIGHT.
  
 08.FIRE DOORS AND WINDOWS SHALL COMPLY WITH NFPA
 80.
  
 09.DOORS THAT OPEN ONTO EXIT ACCESS CORRIDORS SHALL
 NOT HAVE LESS THAN A 20-MINUTE FIRE PROTECTION RATING.
 THOSE DOORS SHALL BE SELF-CLOSING AND SELF-LATCHING.
  
 10.HORIZONTAL-SLIDING DOORS THAT ARE PART OF THE
 REQUIRED MEANS OF EGRESS SHALL COMPLY WITH 7.2.1.4.1.4
 OF NFPA 101.
  
 11.THE INTERIOR FINISH CLASSIFICATION FOR WALLS AND
 CEILING SHALL BE CLASS A FOR EXIT ENCLOSURES, CLASS A
 OR B FOR LOBBIES AND CORRIDORS, AND CLASS A, B, OR C
 FOR OTHER SPACES.
  
 12.PROVIDE PRESCRIPTIVE DETAIL STRENGHTS FOR ALL
 HANDRAILS AND GUARDRAILS.
  
 13.ELEVATOR WARNING SIGNS WILL BE REQUIRED IN THE
 LOBBIES.
  
 14.AT LEAST ONE ELEVATOR SHALL BE PROVIDED WITH A
 PROTECTED POWER SUPPLY AND SHALL BE AVAILABLE FOR USE
 BY THE FIRE DEPARTMENT IN CASE OF EMERGENCY.
  
 15.WHAT IS THE RATIONALE FOR THE NON USAGE OF ROOM
 311 (SHEET A-103) AND ROOM 411 (SHEET A-104) ?
  
 16.THERE IS NO INDICATION OF THE LOCATION FOR THE
 HEARING IMPAIRED ROOM ON THE FIFTH FLOOR (SHEET A-105)
 , BUT IS INDICATED AS ROOM 503 ON SHEET AR-105.
  
 17.A FLOOR DIAGRAM REFLECTING THE ACTUAL FLOOR
 ARRANGEMENT, EXIT LOCATIONS AND ROOM IDENTIFICATION
 SHALL BE POSTED IN A LOCATION AND MANNER ACCEPTABLE TO
 THE AHJ ON, OR IMMEDIATELY ADJACENT TO, EVERY GUEST
 ROOM IN THE HOTEL.
  
 18.SMOKE DETECTORS ARE NOT SHOWN FOR THE ELEVATOR
 LOBBY, ICE ROOM, OR ELECTRIC ROOM ON SHEETS E-101,
 E-102, E-103; HOWEVER THEY ARE CORRECTLY SHOWN ON
 SHEETS E-203 AND E-204.
  
 19.PLEASE PROVIDE A LAYOUT OF THE FIRE ALARM SYSTEM
 INDEPENDENT OF THE ELECTRICAL SHEETS
  
 20.THE FIRE ALARM SYSTEM SHALL BE FULLY ADDRESSABLE
 AND U.L. CETIFICATED FOR CENTRAL STATION SERVICE.
  
 21.ALL GUESTROOMS FOR HEARING IMPAIRED SHALL BE
 PROVIDED WITH FIRE ALARM VISUAL DEVICES.
  
 22.DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM AS PER WEST PALM BEACH FIRE PREVENTION.
  
 23.PLEASE PROVIDE A LAYOUT OF THE FIRE SPRINKLER
 SYSTEM INDEPENDENT OF THE PLUMBING SHEETS.INCLUDE THE
 LOCATION OF THE FIRE DEPARTMENT CONNECTION(S) AND THE
 DOUBLE DETECTOR CHECK VALVE ASSEMBLY.
  
 24.ELECTRONIC SWITCHES IN ADDITION TO CHAIN AND LOCK
 IS REQUIRED FOR THE DOUBLE DETECTOR CHECK VALVE
 ASSEMBLY.
  
 25.KNOX LOCKING CAPS WILL BE REQUIRED ON FIRE
 DEPARTMENT CONNECTIONS (FDC). CONTACT WEST PALM BEACH
 FIRE PREVENTION AT 561-804-4724 FOR KNOX APPLICATIONS.
  
 26.PROVIDE SPECIFICATIONS FOR THE FIRE PUMP AND
 ASSOCIATED EQUIPMENT.
  
 27.SIGNS REQUIRED IN STAIRWELLS INDICATING FLOOR
 IDENTITY.
  
 28.FIRE EXTINGUISHERS ARE TO BE 2A:10 BC.ADDITIONAL
 EXTINGUISHERS MAY BE NEEDED IF THE TRAVEL DISTANCE TO
 THIS EQUIPMENT IS GREATER THAN 75 FEET FROM A ROOM IN
 THE BUILDING OR ON THE FLOOR OF THE BUILDING.
  
 29.SEPARATE PLAN AND PERMITS WILL BEREQUIRED FOR
 ANY COOKING HOOD INSTALLATION ANDASSOCIATED FIRE
 SUPPRESSION SYSTEM PLANNED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 9 Status P Date 2009-04-07 Cont ID  
Sent By lwagner Date 2009-04-07 Time 11:11 Rev Time 0.00
Received By lwagner Date 2009-04-07 Time 10:10 Sent To  
Notes
2009-04-07 11:11:44REVISION OK

Review Stop G GAS REVIEW
Rev No 8 Status F Date 2009-03-09 Cont ID  
Sent By lwagner Date 2009-03-09 Time 14:08 Rev Time 0.00
Received By lwagner Date 2009-03-09 Time 11:01 Sent To  
Notes
2009-03-09 13:03:31PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS/PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. THE NOTE AT GAS METER & REGULATOR ASSEMBLY SHOULD BE
 CHANGED TO 1950 CFH
  
 2. THE CFH AFTER THE FIRST TEE SHOULD BE 1550
  
 3. THE NOTE 3/4" @ 600 CFH SHOULD BE 750 CFH
  
 4. THE PIPE SECTION FROM THE METER, BEFORE THE FIRST
 TEE SHOULD BE LABELED AS 1 1/4" (FROM TABLE 402.4 (3)
 ).
  
 5. THE 350 CFH DROP AT THE END IS NOT LABELED AS TO
 WHICH APPLIANCE OR WHICH REGULATOR IS BEING USED.
  
 6. ***NOTE*** THE PIPE SIZES ARE NOT CONSISTENT, SUCH
 AS, 1" PIPE ENTERING THE BUILDING YET 3" PIPE OVERHEAD
 AND A 3/4" DROP WITH 2" PIPE FEEDING THE FOUR WATER
 HEATERS.
  
 REVIEW BY LARRY WAGNER
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop G GAS REVIEW
Rev No 7 Status P Date 2008-05-05 Cont ID  
Sent By kstevens Date 2008-05-05 Time 10:23 Rev Time 0.00
Received By kstevens Date 2008-05-05 Time 10:23 Sent To  
Notes
2008-05-05 10:24:50REVISION OK--SHT P510--SEE PROVISO SECTIONS 2 &
 3 AT TIME OF GAS PERMIT APPLICATION.

Review Stop G GAS REVIEW
Rev No 6 Status P Date 2008-03-19 Cont ID  
Sent By kstevens Date 2008-03-19 Time 08:23 Rev Time 0.00
Received By kstevens Date 2008-03-18 Time 18:55 Sent To  
Notes
2008-03-19 08:31:06 
  
  
  
 PASSED/PROVISO
  
 THE PIPE SIZING FOR THE SUPPLY LINES AND SHUT OFF
 VALVES TO EACH 200 CFH UNIT SHALL BE 1-1/4" AND THE
 INLET PRESSURE SHALL BE INDICATED AS 1/2 PSI. REVISION
 REQUIRED AT THE TIME OF APPLICATION FOR THE GAS
 PERMIT.
  
 MANUF. SPECIFICATION SHEETS REQUIRED SHOWING LISTING
 AND BTU LOAD FOR FIXTURES REQUIRED AT THE TIME OF
 APPLICATION FOR THE GAS PERMIT.
  
 WELDING CERTIFICATIONS REQUIRED FOR WELDER AS WELL AS
 THE WELDING PROCEDURE AT THE TIME OF APPLICATION FOR
 THE GAS PERMIT.
  
  
  
  
  
 .

Review Stop G GAS REVIEW
Rev No 5 Status F Date 2008-03-13 Cont ID  
Sent By kstevens Date 2008-03-13 Time 12:39 Rev Time 0.00
Received By kstevens Date 2008-03-12 Time 18:55 Sent To  
Notes
2008-03-13 12:43:22DENIED
 REFERENCE: FBC-2004 FUEL GAS
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ***FROM PREVIOUS REVIEW:
  
 ******FROM PREVIOUS REVIEWS: 3RD REVIEW
  
 ********FROM PREVIOUS REVIEWS: 4TH REVIEW:
  
 **********FROM PREVIOUS REVIEWS: 5TH REVIEW:
  
 A. THE FOLLOWING INFORMATION IS REQUIRED FOR THE GAS
 PERMIT. PLEASE SUBMIT THE FOLLOWING:
  
 1. OK
 2. OK
 3. OK - NATURAL
 4. OK
 5. OK
 6. OK
 7. OK
 8. OK
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED. GAS REVIEW WILL STAY IN FAILED
 STATUS UNTIL MANUF. SPECIFICATION SHEETS WITH LISTING
 AND BTU'S THAT REFLECT THE RISER DIAGRAM ARE
 SUBMITTED.
 ********RESPONSE NOTED, BUT THE ONLY GAS MANUF.
 SPECIFICATION SHEET SUBMITTED ARE FOR THE WATER
 HEATERS. THE MANUF. SPECIFICATION SHEETS FOR THE DRYERS
 AND THE POOL HEATER ARE REQUIRED.
 **********RESPONSE NOTED, BUT THE MANUF. SHEETS FOR THE
 DRYERS AND THE POOL HEATER DO NOT SHOW A LISTING, NOR
 DO THE BUT LOADS REFLECT THE RISER DIAGRAM. PLEASE
 INDICATE MODEL NUMBER.
  
 10. N/A (NATURAL GAS)
 11. N/A (NATURAL GAS)
  
 **********NEW COMMENTS**********
  
 1B. OK
 2B. OK
 3B. OK
 4B. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2008-02-01 Cont ID  
Sent By kstevens Date 2008-02-01 Time 14:41 Rev Time 0.00
Received By kstevens Date 2008-02-01 Time 14:41 Sent To  
Notes
2008-02-01 14:44:40DENIED
 REFERENCE: FBC-2004 FUEL GAS
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ***FROM PREVIOUS REVIEW:
  
 ******FROM PREVIOUS REVIEWS: 3RD REVIEW
  
 ********FROM PREVIOUS REVIEWS: 4TH REVIEW:
  
 A. THE FOLLOWING INFORMATION IS REQUIRED FOR THE GAS
 PERMIT. PLEASE SUBMIT THE FOLLOWING:
  
 1. OK
 2. OK
 3. OK - NATURAL
 4. OK
 5. OK
 6. OK
 7. OK
 8. OK
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED. GAS REVIEW WILL STAY IN FAILED
 STATUS UNTIL MANUF. SPECIFICATION SHEETS WITH LISTING
 AND BTU'S THAT REFLECT THE RISER DIAGRAM ARE
 SUBMITTED.
 ********RESPONSE NOTED, BUT THE ONLY GAS MANUF.
 SPECIFICATION SHEET SUBMITTED ARE FOR THE WATER
 HEATERS. THE MANUF. SPECIFICATION SHEETS FOR THE DRYERS
 AND THE POOL HEATER ARE REQUIRED.
  
 10. N/A (NATURAL GAS)
 11. N/A (NATURAL GAS)
  
 **********NEW COMMENTS**********
  
 1B. OK
 2B. OK
 3B. OK
 4B. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2007-11-24 Cont ID  
Sent By kstevens Date 2007-11-24 Time 12:37 Rev Time 0.00
Received By kstevens Date 2007-11-24 Time 12:37 Sent To  
Notes
2007-11-24 12:42:09DENIED
 REFERENCE: FBC-2004 FUEL GAS
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ***FROM PREVIOUS REVIEW:
  
 ******FROM PREVIOUS REVIEWS: 3RD REVIEW
  
 A. THE FOLLOWING INFORMATION IS REQUIRED FOR THE GAS
 PERMIT. PLEASE SUBMIT THE FOLLOWING:
  
 1. OK
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 ****NO RESPONSE, NOT ADDRSSED. PIPE SIZES SHALL BE
 SHOWN FOR ALL SECTIONS OF PIPE AND VALVES SHALL BE FULL
 SIZE FOR THE PIPE SIZE INDICATED TO THE GAS EQUIPMENT.
 ******RESPONSE NOTED, BUT 1-1/4" SUPPLY AND SHUT OFF
 VALVE IS REQUIRED FOR THE DRYERS, 1-1/4" SUPPLY AND
 SHUT OFF VALVE IS REQUIRED FOR THE POOL HEATER, 2" IS
 REQUIRED FOR THE SUPPLY TO THE FIRST WATER HEATER, AND
 1" SUPPLY AND SHUT OFF VALVE IS REQUIRED TO EACH WATER
 HEATER. TABLE 402.4(2). PLEASE CORRECT PIPE SIZING AND
 SHUT OFF VALVE SIZE.
  
 3. OK - NATURAL
 4. OK
 5. OK
 6. OK
 7. OK
 8. OK
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED. GAS REVIEW WILL STAY IN FAILED
 STATUS UNTIL MANUF. SPECIFICATION SHEETS WITH LISTING
 AND BTU'S THAT REFLECT THE RISER DIAGRAM ARE
 SUBMITTED.
  
 10. N/A (NATURAL GAS)
 11. N/A (NATURAL GAS)
  
 **********NEW COMMENTS**********
  
 1B. OK
 2B. OK
 3B. OK
 4B. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2007-04-16 Cont ID  
Sent By kstevens Date 2007-04-16 Time 17:47 Rev Time 0.00
Received By kstevens Date 2007-04-09 Time 18:57 Sent To  
Notes
2007-04-16 18:23:21DENIED
 REFERENCE: FBC-2004 FUEL GAS
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ***FROM PREVIOUS REVIEW:
  
 A. THE FOLLOWING INFORMATION IS REQUIRED FOR THE GAS
 PERMIT. PLEASE SUBMIT THE FOLLOWING:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ****RESPONSE NOTED, BUT THE FIRST THREE CUT SECTIONS
 DOWNSTREAM OF THE METER, AND TWO SECTIONS OF PIPE IN
 THE CEILING DO NOT SHOW THE LENGHTS OF PIPES.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 ****NO RESPONSE, NOT ADDRSSED. PIPE SIZES SHALL BE
 SHOWN FOR ALL SECTIONS OF PIPE AND VALVES SHALL BE FULL
 SIZE FOR THE PIPE SIZE INDICATED TO THE GAS EQUIPMENT.
  
 3. OK - NATURAL
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 ****RESPONSE NOTED, BUT THE TOTAL BTU'S ADDS UP TO
 1,785,000, BUT IS SHOWN AS TOTAL OF 2,100,000 BTU'S.
 PLEASE CLARIFY. - PLEASE IDENTIFY ALL APPLIANCES ON THE
 ISOMETRIC.
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ****NO RESPONSE, NOT ADDRESSED.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304. (CLOTHS DRYERS).
 ****NO RESPONSE, NOT ADDRESSED.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 ****RESPONSE NOTED, BUT THE UTILITY COMPANY DOES NOT
 DELEVER 1PSI. PLANS SHOW 7" TO 14" WC. AND 1PSI. PLEASE
 CHECK WITH GAS PROVIDER.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
 ****NO RESPONSE, NOT ADDRESSED.
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****NO RESPONSE, NOT ADDRESSED.
  
 10. N/A (NATURAL GAS)
 11. N/A (NATURAL GAS)
  
 **********NEW COMMENTS**********
  
 1B. SHT P502 RISER SHOWS VALVES IN THE CEILING. THESE
 VALVES ARE NOT REQUIRED, BUT IF THE VALVES ARE LEFT IN,
 A UNION IS REQUIRED FOR EACH VALVE, AND THE VALVE AND
 UNION ARE NOT APPROVED IN THE CEILING.--A NOTE
 INDICATES "SOLENOID VALVE TYPICAL" PLEASE CLARIFY.
 SECTION 106.1.1.
  
 2B. SHT P502 DETAIL 7 INDICATES "DESIGNED ACCORDING TO
 THE 2000 IFGC" & "DESIGNED ACCORDING TO THE 2003 IFGC".
 THE CODE ADOPTED AND IN EFFECT IS THE FBC-2004. PLEASE
 CHANGE CODE REFERENCES. SECTION 106.1.1.
  
 3B. PER ELECTRICAL REVIEW COMMENT #47 SEE ATTACHED
 SHEET CONCERNING THE DESIGN PROFESSIONAL AND FS
 533.80(2)(B). THIS IS GIVEN AS A NOTICE ONLY & ONE TIME
 ONLY.
  
 4B. ALL MEP SHEETS. THE ENGINEERING COMPANY'S
 CERTIFICATE OF AUTHORIZATION NUMBER SHOWS DELINQUENT ON
 THE FLORIDA DBPR WEBSITE. SEE SHEET ATTACHED TO
 ELECTRICAL PLAN REVIEW NOTES. THIS SHALL BE TAKEN CARE
 OF PRIOR TO ISSUING THE PERMIT.FAC 61G15-23.002 & FS
 471.023
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-01-20 Cont ID  
Sent By kstevens Date 2007-01-20 Time 16:44 Rev Time 0.00
Received By kstevens Date 2007-01-20 Time 16:44 Sent To  
Notes
2007-01-20 16:49:37DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 A. THE FOLLOWING INFORMATION IS REQUIRED FOR THE GAS
 PERMIT. PLEASE SUBMIT THE FOLLOWING:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304. (CLOTHS DRYERS).
  
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 10. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 11. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 30 Status N Date 2009-10-27 Cont ID  
Sent By cjordan Date 2009-10-26 Time 10:42 Rev Time 0.00
Received By cjordan Date 2009-10-27 Time 10:42 Sent To  
Notes
2009-10-27 10:44:33***************** EXPEDITED ******************
 GAVE TO DEWEY

Review Stop I INCOMING/PROCESSING
Rev No 29 Status N Date 2009-09-14 Cont ID  
Sent By lmartine Date 2009-09-14 Time 16:21 Rev Time 0.00
Received By lmartine Date 2009-09-14 Time 16:21 Sent To  
Notes
2009-09-14 16:23:20SITE LIGHTING
2009-09-14 16:22:42***************EXPEDITED**************** GAVE TO DEWEY

Review Stop I INCOMING/PROCESSING
Rev No 28 Status N Date 2009-08-11 Cont ID  
Sent By lmartine Date 2009-08-11 Time 08:48 Rev Time 0.00
Received By lmartine Date 2009-08-11 Time 08:48 Sent To  
Notes
2009-08-11 08:49:41$$$ EXPEDITED $$$, GAVE TO DEWEY

Review Stop I INCOMING/PROCESSING
Rev No 27 Status N Date 2009-07-09 Cont ID  
Sent By jgomez Date 2009-07-09 Time 16:43 Rev Time 0.00
Received By jgomez Date 2009-07-09 Time 16:42 Sent To  
Notes
2009-07-09 16:43:56SENT TO COMMERCIAL BOX # 35 ALONG WITH PERMIT NUMBER
 06111071.

Review Stop I INCOMING/PROCESSING
Rev No 26 Status N Date 2009-06-03 Cont ID  
Sent By jgomez Date 2009-06-03 Time 15:13 Rev Time 0.00
Received By jgomez Date 2009-06-03 Time 15:13 Sent To  
Notes
2009-06-03 15:14:20SENT TO COMMERCIAL BOX C26.

Review Stop I INCOMING/PROCESSING
Rev No 25 Status N Date 2009-04-29 Cont ID  
Sent By dpalmer Date 2009-04-29 Time 12:09 Rev Time 0.00
Received By dpalmer Date 2009-04-29 Time 12:09 Sent To B
Notes
2009-04-29 12:09:56TO JW'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 24 Status N Date 2009-04-10 Cont ID  
Sent By adarroug Date 2009-04-10 Time 09:46 Rev Time 0.00
Received By adarroug Date 2009-04-10 Time 09:46 Sent To  
Notes
2009-04-10 09:46:35TO "C26"

Review Stop I INCOMING/PROCESSING
Rev No 23 Status N Date 2009-04-07 Cont ID  
Sent By adarroug Date 2009-04-07 Time 13:52 Rev Time 0.00
Received By adarroug Date 2009-04-07 Time 13:52 Sent To  
Notes
2009-04-07 14:00:00TO "C36"

Review Stop I INCOMING/PROCESSING
Rev No 22 Status N Date 2009-04-06 Cont ID  
Sent By adarroug Date 2009-04-06 Time 16:40 Rev Time 0.00
Received By adarroug Date 2009-04-06 Time 16:40 Sent To FIRE
Notes
2009-04-06 16:41:19TO "MAW" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 21 Status N Date 2009-04-06 Cont ID  
Sent By adarroug Date 2009-04-06 Time 13:19 Rev Time 0.00
Received By adarroug Date 2009-04-06 Time 13:19 Sent To G
Notes
2009-04-06 13:19:21TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 20 Status N Date 2009-03-27 Cont ID  
Sent By adarroug Date 2009-03-27 Time 16:54 Rev Time 0.00
Received By adarroug Date 2009-03-27 Time 16:54 Sent To  
Notes
2009-03-27 16:55:26TO IN-BOX "C23"

Review Stop I INCOMING/PROCESSING
Rev No 19 Status N Date 2009-03-02 Cont ID  
Sent By adarroug Date 2009-03-02 Time 10:41 Rev Time 0.00
Received By adarroug Date 2009-03-02 Time 10:41 Sent To B
Notes
2009-03-02 10:41:31TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2009-02-27 Cont ID  
Sent By adarroug Date 2009-02-27 Time 16:39 Rev Time 0.00
Received By adarroug Date 2009-02-27 Time 16:39 Sent To P
Notes
2009-02-27 16:39:44TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2009-02-24 Cont ID  
Sent By adarroug Date 2009-02-24 Time 14:35 Rev Time 0.00
Received By adarroug Date 2009-02-24 Time 14:35 Sent To  
Notes
2009-02-24 14:38:08TO "COMM" BD#15

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2009-02-09 Cont ID  
Sent By adarroug Date 2009-02-09 Time 16:32 Rev Time 0.00
Received By adarroug Date 2009-02-09 Time 16:32 Sent To  
Notes
2009-02-09 16:34:20TO "COMM" BD#20

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2008-11-06 Cont ID  
Sent By adarroug Date 2008-11-06 Time 10:27 Rev Time 0.00
Received By adarroug Date 2008-11-06 Time 10:27 Sent To  
Notes
2008-11-06 10:32:45TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2008-10-14 Cont ID  
Sent By adarroug Date 2008-10-14 Time 08:52 Rev Time 0.00
Received By adarroug Date 2008-10-14 Time 08:52 Sent To  
Notes
2008-10-14 08:58:38TO "COMM" BD#8/PLANS ON RACK/ LARGE FOLDED PLANS

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2008-09-26 Cont ID  
Sent By adarroug Date 2008-09-26 Time 15:02 Rev Time 0.00
Received By adarroug Date 2008-09-26 Time 15:02 Sent To E
Notes
2008-09-26 15:03:08TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2008-09-24 Cont ID  
Sent By adarroug Date 2008-09-24 Time 12:26 Rev Time 0.00
Received By adarroug Date 2008-09-24 Time 12:26 Sent To B
Notes
2008-09-24 12:26:48TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2008-08-08 Cont ID  
Sent By adarroug Date 2008-08-08 Time 09:05 Rev Time 0.00
Received By adarroug Date 2008-08-08 Time 09:05 Sent To B
Notes
2008-08-08 09:05:45TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-08-06 Cont ID  
Sent By adarroug Date 2008-08-06 Time 11:49 Rev Time 0.00
Received By adarroug Date 2008-08-06 Time 11:49 Sent To  
Notes
2008-08-06 11:50:08TO "COMM" BD#59

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-07-15 Cont ID  
Sent By adarroug Date 2008-07-15 Time 16:36 Rev Time 0.00
Received By adarroug Date 2008-07-15 Time 16:36 Sent To B
Notes
2008-07-15 16:36:56TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-07-03 Cont ID  
Sent By adarroug Date 2008-07-03 Time 10:36 Rev Time 0.00
Received By adarroug Date 2008-07-03 Time 10:36 Sent To B
Notes
2008-07-03 10:37:17TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-05-22 Cont ID  
Sent By adarroug Date 2008-05-22 Time 15:55 Rev Time 0.00
Received By adarroug Date 2008-05-22 Time 15:54 Sent To B
Notes
2008-05-22 15:55:17TO "JWITMER" DESK/ 3 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-04-24 Cont ID  
Sent By adarroug Date 2008-04-24 Time 09:44 Rev Time 0.00
Received By adarroug Date 2008-04-24 Time 09:44 Sent To  
Notes
2008-04-24 09:46:21TO "COMM" BD#4--PLANS ON RACK/LARGE FOLDED PLANS

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-02-15 Cont ID  
Sent By adarroug Date 2008-02-15 Time 16:39 Rev Time 0.00
Received By adarroug Date 2008-02-15 Time 16:39 Sent To  
Notes
2008-02-15 16:44:10TO "COMM" BD#31/PLANS ON INCOMING TABLE

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-01-03 Cont ID  
Sent By adarroug Date 2008-01-03 Time 16:36 Rev Time 0.00
Received By adarroug Date 2008-01-03 Time 16:36 Sent To  
Notes
2008-01-03 16:36:56TO "COMM" BD#4/4 ROLLS/BINDERS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-09-05 Cont ID  
Sent By adarroug Date 2007-09-05 Time 16:30 Rev Time 0.00
Received By adarroug Date 2007-09-05 Time 16:30 Sent To  
Notes
2007-09-24 16:21:10TO "COMM" BD#57--PLANS ON RACK/2 APPL'S AND 8 ROLLS
2007-09-05 16:31:07WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-24 Cont ID  
Sent By adarroug Date 2007-03-24 Time 17:23 Rev Time 0.00
Received By adarroug Date 2007-03-24 Time 17:23 Sent To  
Notes
2007-03-24 17:23:40TO "COMM" BD#31/PLANS ON RACK--3 ROLLS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-02-19 Cont ID  
Sent By   Date 2007-02-19 Time   Rev Time 0.00
Received By adarroug Date 2006-12-05 Time 11:09 Sent To  
Notes
2006-12-21 16:39:36TO "COMM" BD#60
2006-12-05 11:09:33WAITING FOR "COMM" BD

Review Stop L LANDSCAPING
Rev No 8 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By rkussner Date 2009-07-29 Time 17:36 Sent To  
Notes
2009-07-29 17:42:36***LANDSCAPE ELECTRICAL REVIEW APPROVED***
  
 LANDSCAPE ELECTRICAL REVIEW IS BASED UPON SHEET E-001.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop L LANDSCAPING
Rev No 7 Status P Date 2009-07-13 Cont ID  
Sent By rkussner Date 2009-07-13 Time 15:57 Rev Time 0.00
Received By rkussner Date 2009-07-13 Time 15:57 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 6 Status F Date 2009-06-11 Cont ID  
Sent By rkussner Date 2009-06-11 Time 13:57 Rev Time 0.00
Received By rkussner Date 2009-06-11 Time 13:57 Sent To  
Notes
2009-06-11 14:11:44***LANDSCAPE REVIEW FAILED***
  
 1. THE SIDEWALK JUST NORTH OF THE SPRINGHILL SUITES
 MAIN ENTRANCE SHALL BE REVISED TO DUPLICATE WHAT WAS
 PROPOSED ON THE SOUTH SIDE OF THE ENTRANCE. THE WALKWAY
 SHALL BE MOVED TO THE EAST SIDE OF THE LANDSCAPE ISLAND
 AND TYPE D CURBING SHALL BE ADDED ON TWO SIDES TO
 SEPARATE THE LANDSCAPE AREA FROM THE VEHICULAR USE
 AREA. THE TREE SHALL BE SHIFTED TO THE WEST TO BE IN
 LINE WITH THE ONE ON THE SOUTH SIDE OF THE ENTRANCE.
  
 2. THE THREE ROYAL PALMS ADJACENT TO THE TRAVEL AISLE
 THAT SEPARATES THE TWO HOTELS SHALL BE IN LINE. THE
 PALM THAT IS CENTERED IN THE ISLAND SHALL BE SHIFTED TO
 THE WEST TO LINE UP WITH THE OTHERS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop L LANDSCAPING
Rev No 5 Status P Date 2009-04-15 Cont ID  
Sent By rkussner Date 2009-04-15 Time 18:08 Rev Time 0.00
Received By rkussner Date 2009-04-15 Time 18:08 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 4 Status F Date 2008-10-24 Cont ID  
Sent By rkussner Date 2008-10-24 Time 10:55 Rev Time 0.00
Received By rkussner Date 2008-10-24 Time 10:55 Sent To  
Notes
2008-10-24 10:55:32***LANDSCAPE REVIEW FAILED***
  
 1. PLEASE PROVIDE A DETAIL OF FENCE. IF THE FENCE WILL
 BE VINYL CLAD CHAIN LINK, ALLAMANDA VINE WILL ATTACH
 BETTER THAN FICUS REPENS. IF THE FENCE IS WOOD THE
 FICUS WILL DO FINE. AN ALUMINUM RAIL FENCE WOULD BE THE
 MOST ATTRACTIVE FENCE AND THE ALAMANDA COULD BE
 ATTACHED TO IT. .
  
 2. THERE ARE NUMEROUS CONFLICTS BETWEEN PROPOSED STREET
 LIGHTS AND TREES. THE STREET LIGHTS SHALL NOT BE PLACED
 IN THE LANDSCAPE ISLANDS OR CENTERED IN THE MIDDLE OF
 TWO INTERIOR ISLANDS AND THE LANDSCAPE SEPARATOR
 BETWEEN PARKING ROWS. THEY SHALL BE CENTERED BETWEEN
 TREES AND THE HEADS OF THE LIGHTS SHALL BE DIRECTED
 AWAY FROM THE TREE CANOPIES--NOT INTO THEM.
  
 3. THERE ARE OTHER CONFLICTS BETWEEN PROPOSED UTILITIES
 AND VARIOUS LANDSCAPED AREAS. IN ORDER TO ELIMINATE ALL
 POTENTIAL PROBLEMS IN THE FIELD, PLEASE SHOW ALL
 UTILITIES, EASEMENTS AND STREET LIGHTS ON THE LANDSCAPE
 PLAN.
  
 4. REPEAT COMMENT: THE SIDEWALK IN THE NORTHEAST CORNER
 OF THE BUILDING SHALL BE ELIMINATED AND THE LANDSCAPING
 SHALL BE INSTALLED AS PREVIOUSLY APPROVED.
  
 5. THE TYPICAL PARKING DETAIL ON CIVIL SHEET 3 OF 9,
 SHALL MEET THE PARKING STRIPING REQUIREMENTS PURSUANT
 TO SECTION 94-485 (J) (2) (I.E. THE STRIPPING SHALL BE
 4" LINE, 1'-4" , 4" LINE).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME AT THE
 NUMBER BELOW.
  
 ROBERT KUSSNER
 LANDSCAPE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1462
 EMAIL: [email protected]
  

Review Stop L LANDSCAPING
Rev No 3 Status F Date 2008-08-18 Cont ID  
Sent By rkussner Date 2008-08-18 Time 12:04 Rev Time 0.00
Received By rkussner Date 2008-08-18 Time 12:04 Sent To  
Notes
2008-08-18 12:12:07LANDSCAPE:***FAILED***
  
  
 1.SHEETS E-001 AND E-002 WERE MISSING FROM THE PERMIT
 SETS.PLEASE ADD THESE SHEETS.IN ADDITION, THE SITE
 LIGHING LOCATIONS SHALL BE SHOWN ON THE LANDSCAPE
 PLAN.
  
 2.THE SPECIES OF HEDGE TO BE PLANTED ALONG 45TH
 STREET SHALL BE CHANGED FROM VIBURNUM SUSPENSUM TO
 VIBURNUM ODORATISSIMUM TO BE CONSISTENT WITH THE
 REMAINDER OF THE EXISTING PERIMETER HEDGE.PROVIDE A
 CROSS SECTION AND SHOW THE CONTOUR LINES OF
 THE BERM THAT RUNS ALONG 45TH SREET.
  
 3.STAFF RECOMMENDS THAT TREES BE ADDED ALONG THE
 LANDSCAPE STRIP (EAST SIDE OF THE TRAVEL LANE THAT
 SEPARATES THE TWO HOTELS)WITHIN THE IXORA HEDGEROW.
  
  
 IF YOU HAVE ANY QUESTIONS REGARDING THE LANDSCAPE
 COMMENT, PLEASE CONTACT: ROBERT KUSSNER, LANDSCAPE
 PLANNER @ (561) 822-1462.

Review Stop L LANDSCAPING
Rev No 2 Status F Date 2008-05-02 Cont ID  
Sent By rkussner Date 2008-05-02 Time 18:15 Rev Time 0.00
Received By rkussner Date 2008-05-02 Time 18:15 Sent To  
Notes
2008-05-02 19:07:59LANDSCAPING COMMENTS:**** FAILED, THE PREVIOUS PLANS
 WERE PASSED WITH PROVISO, THIS PROVISO HAS NOT BEEN
 ADDRESSED, ( PROVISO READS AS FOLLOWS, IF PROVISO HAS
 NOT BEEN ADDRESSED WITHIN 60-DAYS OF PERMIT ISSUANCE,
 THE PERMIT WILL BE REVOKED. ****
  
  
 1. THE LANDSCAPE ISLANDS SHALL HAVE A MINIMUM DIMENSION
 OF 5 FEET, EXCLUDING THE REQUIRED CURBING.CURBING
 CANNOT BE INCLUDED AS PART OF THE LANDSCAPE ISLAND
 SINCE IT IS NOT LANDSCAPING.
  
 2. ELIMINATE THE CURBING AT THE HEAD OF THE PARKING
 STALLS.WHEEL STOPS SHALL BE SET BACK 24" FROM THE
 EDGE-OF-PAVEMENT TO ELIMINATE ANYVEHICULAR
 ENCROACHMENT INTO THE DIVIDER LANDSCAPE STRIPS.
 LANDSCAPE STRIPS MUST BE AT LEAST FIVE (5) FEET IN
 WIDTH WITHOUT ANY VEHICULAR ENCROACHMENT (REVISE, CIVIL
 SHEET 2 OF 9 [DETAIL "A"], LANDSCAPING LP-2 AND SITE
 SP-1 [PARKING AND STRIPPING]).
 RESPONSE TO RE-SUBMITTAL:SEE COMMENT NUMBER 2
 REGARDING THE REQUIREMENTS FOR THE WHEEL STOPS. IN
 ADDITION, ALL CURBING AND WHEEL STOPS SHALL BE SHOWN ON
 PLANS (I.E. LANDSCAPING LP-2). IN REFERENCE TO THE
 7-FOOT WIDE LANDSCAPE SEPARATOR STRIPS, THE WHEEL STOPS
 ARE SHOWN AT LESS THAN THE 2 FEET THAT ARE REQUIRED.
 IF THE WHEEL STOPS ARE REMOVED AND CURBING IS USED AT
 THE EDGE THEN THE WIDTH OF THE STRIP BETWEEN TWO
 PARKING ROWS HAS TO BE AT LEAST 9 FEET.
  
 3. IRRIGATION WITHIN THE RIGHTS-OF-WAY SHALL BE SHOWN
 ON THE IRRIGATION PLAN.
 RESPONSE TO RE-SUBMITTAL: AN IRRIGATION PLAN AND PERMIT
 SHALL BE SUBMITTED.
  
 4. THE HEDGE ADJACENT TO 45TH STREET SHALL BE PLANTED
 ALONG THE INTERIOR PERIMETER OF THE LANDSCAPE SETBACK
 TO IMPROVE THE VISTA FROM THE STREET. STAFF RECOMMENDS
 THAT ADDITIONAL PLANTING OF SHRUBS AND GROUND COVERS
 SHOULD BE PROVIDED ON THE STREET SIDE OF THE HEDGE
 ADJACENT TO 45TH STREET.THESE PLANTINGS SHOULD BE
 TIERED WITH THE HIGHER PLANTING TO THE REAR AND
 GRADUALLY DESCENDING TO A LOWER LEVEL ON THE STREET
 SIDE.
 RESPONSE TO RE-SUBMITTAL: COMMENT NOT ADDRESSED.
  
 A. SHEET LP-1 SHOWS A NEW HEDGE IS BEING PLANTED, THAT
 HEDGE NEEDS ACCORDING TO THIS COMMENT AND THE EXISTING
 HEDGE SHOWN ON SHEET LP-2 SHALL BE REPLACED WITH
 COCOPLUM TO BE CONSISTENT WITH THE REMAINDER OF THE
 LANDSCAPE BUFFER.IN ADDITION:
 B. MOVE THE PROPOSED HEDGE ON THE EAST PERIMITER TO THE
 PROPERTY LINE TO AVOID CREATING A "DOG-RUN", BUT OBTAIN
 AUTHORIZATION FROM THE UTILITY EASEMENT HOLDER AND MOVE
 TREES OUT OF UTILITY EASEMENT.
  
  
 5. YOU SHALL ABIDE BY THE FPL GUIDELINES LISTED IN
 THEIR ON LINE PUBLICATION "PLANT THE RIGHT TREE IN THE
 RIGHT PLACE".LIVE OAK TREES CANNOT BE PLANTED WITHIN
 30 FEET OF OVERHEAD POWER LINES.THE TREES ALONG THE
 NORTH PERIMETER OF THE SITE SHALLBE CHANGED TO
 ANOTHER APPROVED SPECIES TO COMPLY WITH THIS
 REQUIREMENT.
 RESPONSE TO RE-SUBMITTAL: COMMENTS NOT ADDRESSED.
  
 A. THE LIVE OAK ARE STILL SHOWN ON LP-2.IN ADDITION,
 THE SPACING BETWEEN THE TREES CANNOT EXCEED 30 FEET.
 B. PALMS SHALL BE PLANTED IN GROUPS OF 3 WITH THE
 SPACING BETWEEN THE GROUPINGS MEASURED FROM THE MIDDLE
 PALM.
 C. THE ENTIRE LANDSCAPE BUFFER STRIP ADJACENT TO 45TH
 STREET SHALL BE UNIFORM.IN ADDITION, SHOW ALL SITE
 LIGHTING ON LANDSCAPE PLAN TO AVOID CONFLICT WITH
 PROPOSED TREES.
  
  
 FOR ANY QUESTIONS CONCERNING THESE COMMENTS, PLEASE
 CONTACT ROBERT KUSSNER, LANDSCAPE PLANNER AT (561)
 822-1462.

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2008-02-27 Cont ID  
Sent By rkussner Date 2008-02-25 Time   Rev Time 0.00
Received By rkussner Date 2008-02-25 Time 13:03 Sent To  
Notes
2008-02-25 13:52:07LANDSCAPING COMMENTS: **** PASSED WITH PROVISO - IF
 PROVISO IS NOT ADDRESSED WITHIN 60-DAYS OF PERMIT
 ISSUANCE, THE PERMIT WILL BE REVOKED. ****
  
 1. THE DUMPSTER ENCLOSURE/EXTERIOR STORAGE BUILDING
 CANNOT ENCROACH INTO THE PARKING STALLS. IT SHALL BE
 SHIFTED TO THE SOUTH. IN ADDITION, THE GATE INTO THE
 ENCLOSURE SHALL OPEN TO THE SIDEWALK.
  
 2. BOTH ENDS OF THE LOADING ZONE SHOULD TERMINATE AT A
 45 DEGREE ANGLE TO ALLOW EASIER VEHICULAR ACCESS.
  
 3. THE LANDSCAPE ISLANDS SHALL HAVE A MINIMUM DIMENSION
 OF 5 FEET, EXCLUDING THE REQUIRED CURBING.
  
 4. ELIMINATE THE CURBING AT THE HEAD OF THE PARKING
 STALLS. WHEEL STOPS SHALL BE SET BACK 24" FROM THE
 EDGE-OF--PAVEMENT TO ELIMINATE ANY VEHICULAR
 ENCROACHMENT INTO THE DIVIDER LANDSCAPE STRIPS.
 LANDSCAPE STRIPS MUST BE AT LEAST FIVE (5) FEET IN
 WIDTH WITHOUT ANY VEHICULAR ENCROACHMENT.
  
 5. A NOTE SHALL BE PLACED ON THE LANDSCAPE PLAN
 INDICATING THAT SOD AND IRRIGATION WILL BE PROVIDED IN
 THE ADJACENT RIGHTS-OF-WAY. IRRIGATION WITHIN THE
 RIGHTS-OF-WAY SHALL BE SHOWN ON THE IRRIGATION PLAN.
  
 6. THE HEDGE ADJACENT TO 45TH STREET SHALL BE PLANTED
 ALONG THE INTERIOR PERIMETER OF THE LANDSCAPE SETBACK
 TO IMPROVE THE VISTA FROM THE STREET. STAFF RECOMMENDS
 THAT ADDITIONAL PLANTING OF SHRUBS AND GROUND COVERS
 SHOULD BE PROVIDED ON THE STREET SIDE OF THE HEDGE
 ADJACENT TO 45TH STREET. THESE PLANTINGS SHOULD BE
 TIERED WITH THE HIGHER PLANTING TO THE REAR AND
 GRADUALLY DESCENDING TO A LOWER LEVEL ON THE STREET
 SIDE.
  
 7. THE SYMBOL 'GU' WAS USED ON THE PLAN WITH NO
 REFERENCE TO THAT SYMBOL ON THE PLANT LIST.
  
 8. YOU SHALL ABIDE BY THE FPL GUIDELINES LISTED IN
 THEIR ON LINE PUBLICATION "PLANT THE RIGHT TREE IN THE
 RIGHT PLACE". LIVE OAK TREES CANNOT BE PLANTED WITHIN
 30 FEET OF OVERHEAD POWER LINES. THE TREES ALONG THE
 NORTH PERIMETER OF THE SITE SHALL BE CHANGED TO ANOTHER
 APPROVED SPECIES TO COMPLY WITH THIS REQUIREMENT.
  
 FOR ANY QUESTIONS CONCERNING THESE COMMENTS, PLEASE
 CONTACT ROBERT KUSSNER, LANDSCAPE PLANNER AT (561)
 822-1462.

Review Stop M MECHANICAL (A/C)
Rev No 9 Status P Date 2009-03-27 Cont ID  
Sent By rregueir Date 2009-03-27 Time 14:29 Rev Time 0.00
Received By rregueir Date 2009-03-27 Time 14:12 Sent To  
Notes
2009-03-27 14:28:19REVISED M101

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2008-12-20 Cont ID  
Sent By rregueir Date 2008-12-20 Time 10:40 Rev Time 0.00
Received By rregueir Date 2008-12-20 Time 10:30 Sent To B
Notes
2008-12-20 10:31:14REVISED ENERGY CALCS, MECHANIAL ONLY OK

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2008-08-07 Cont ID  
Sent By tgordon Date 2008-08-07 Time 11:10 Rev Time 2.00
Received By tgordon Date 2008-08-07 Time 11:09 Sent To  
Notes
2008-08-07 11:10:55REVISION TO MECH. PLAN M-101 AND ENERGY CAL'S.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2008-04-24 Cont ID  
Sent By tgordon Date 2008-04-24 Time 14:48 Rev Time 1.30
Received By tgordon Date 2008-04-24 Time 14:48 Sent To  
Notes
2008-04-24 14:58:13PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 ** REVISION TO MECHANICAL PLAN PAGE M-101 **
 *** DENIED ***
  
 1)PAGE M-101 SEE YELLOW HIGH LIGHTED WALLS THAT ARE
 SHOWN AS RATED WALLS ON PAGE A-401, IF SO SEE RED LINE
 SHOWING WERE FIRE DAMPERS WILL BE NEEDED. IF NOT RATED
 CORRECT ARCHITECTURAL PLANS, SEE 2004 FBC/M 607.5.1.
  
 2) PLEASE COORDINATE ALL FIRE RESISTANCE RATED WALL
 LOCATION CHANGES WITH ARCHITECT AND MECHANICAL
 ENGINEER.
  
 *** REVISION TO MECHANICAL PLANS M-001, M-102, M-103,
 M-104, M-105, AND M-106 WERE REVIEWED AND STAMPED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2008-01-16 Cont ID  
Sent By tgordon Date 2008-01-16 Time 11:54 Rev Time 0.45
Received By tgordon Date 2008-01-16 Time 11:54 Sent To  
Notes
2008-01-16 11:59:02*** PROVISO ***
 1) PER 2004 FBC/M 607.5.3 DUCT PENETRATIONS IN FIRE
 PARTITIONS SHALL BE PROTECTED WITH APPROVED FIRE
 DAMPERS INSTALLED IN ACCORDANCE WITH THEIR LISTING OR
 MEET THE EXCEPTIONS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2008-01-08 Cont ID  
Sent By tgordon Date 2008-01-08 Time 14:12 Rev Time 2.00
Received By tgordon Date 2008-01-08 Time 14:12 Sent To  
Notes
2008-01-08 14:13:26PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) AS NOTED IN LAST REVIEW 10-15-07 NOTE #3. SEE
 MECHANICAL PLAN PAGE M101, THE YELLOW HIGH LIGHTS THAT
 ARE SHOWINGING THE RATED WALLS WERE THE DUCTS PENETRATE
 THEM FIRE DAMPERS WILL BE REQUIRED (SEE RED LINE ON
 PLAN) OR STATE HOW THEY ARE COMPLYING WITH 2004 FBC/M
 607.5.1. ALSO SEE WALL ASSEMBLY TYPES PLAN PAGES A-401
 AND A-601.
  
 2)PLEASE COORDINATE ALL FIRE RESISTANCE RATED WALL
 LOCATION CHANGES WITH ARCHITECT AND MECHANICAL
 ENGINEER.
  
 3)SEE ATTACHED NOTICE FS 553.80 (2) (B) REGARDING
 FOUR TIMES THE FEE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-10-15 Cont ID  
Sent By tgordon Date 2007-10-15 Time 16:04 Rev Time 3.30
Received By tgordon Date 2007-10-15 Time 16:04 Sent To  
Notes
2007-10-15 16:18:47PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PAGE G-003 LEGEND MAY BE BACKWARDS FROM ONE AND TWO
 HOUR RATING, PLEASE CHECK AND CORRECT IF NEEDED.
  
 2) PAGE A-401 AND G-003 DO NOT SHOW THE SAME RATED
 WALLS. SEE YELLOW HIGH LIGHTS ON PAGE A-401 AT SALES
 OFFICE, REGISTRATION, AND ENG./MAINT. PLEASE CHECK AND
 CORRECT IF NEEDED.
  
 3) PAGE M-101 SEE YELLOW HIGH LIGHTED WALLS THAT I
 THINK ARE RATED, IF SO SEE RED LINE SHOWING WERE FIRE
 DAMPERS WILL BE NEEDED, SEE 2004 FBC/M 607.5.1.
  
 4) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-04-09 Cont ID  
Sent By tgordon Date 2007-04-09 Time 14:16 Rev Time 1.30
Received By tgordon Date 2007-04-09 Time 14:16 Sent To  
Notes
2007-04-09 14:19:11*** DENIED ***
 1) MINICK ENGINEERING INC. CERTIFICATE OF AUTHORIZATION
 NUMBER EXPIRED 2-28-07, PLEASE CORRECT.
  
 2) ARCHITECT FIRM'S LICENSE NUMBER IS MISSING FROM THE
 TITLE BLOCK, SEE FAC 61G1-16.004. PLEASE CORRECT.
  
 3) PLEASE ADD A NOTE TO PAGE M-106 MECH. ROOF PLAN. NO
 PLUMBING VENT PIPES OR OTHER EXHAUST VENTS WITH IN 10
 FEET OF THE OUTSIDE AIR INTAKE OF THE A/C PACKAGE
 UNITS. SEE 2004 FBC/M 401.5.1.
  
 4) PLEASE SUBMIT THREE SETS OF THE ENERGY
 CALCULATIONS.
  
 5) THE SUBMITTAL FOR THE RUSKIN WALL LOUVERS NOTICE OF
 ACCEPTANCE EXPIRED ON 7-9-01, PLEASE CORRECT.
  
 6) AS REQUESTED IN LAST REVIEW 1-26-07 NOTE #5 PLEASE
 PROVIDE PRODUCT APPROVALS FOR 18"X18" HURRICANE LOUVER
 VENTS ON POOL EQUIPMENT ROOM #166, AND FOR THE
 PER-ENGINEERED A/CCONDENSER STANDS.
 PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-01-26 Cont ID  
Sent By tgordon Date 2007-01-26 Time 16:30 Rev Time 3.50
Received By tgordon Date 2007-01-26 Time 16:30 Sent To  
Notes
2007-01-26 16:49:33SPRINGHILL SUITES HOTEL
  
 *** DENIED ***
 1) SEE ELECTRICAL REVIEW NOTES 1 THROUGH 10, PLEASE
 CORRECT.
  
 2) SEE PAGE M-101 PLANS SHOW GUEST LAUNDRY ROOM, NEEDS
 TO SHOW FIRE PUMP ROOM, PLEASE CORRECT.
  
 3) SEE PAGE M-102 PLANS SHOW ENG. & MAINT. NEEDS TO
 SHOW JAN./GUEST LAUNDRY, PLEASE CORRECT.
  
 4) NEED DETAIL ON PLANS SHOWING HOW CONDENSER UNIT (CU)
 STANDS ARE TO BE SECURED TO THE ROOF AND HOW THE
 CONDENSER UNITS ARE TO BE SECURED TO THE STANDS TO
 WITHSTAND 140 MPH WINDS, PER 2004 FBC 1609.
  
 5) PLEASE PROVIDE PRODUCT APPROVALS FOR LOUVER VENTS ON
 POOL HOUSE AND CONDENSER UNIT STANDS.
 PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 8 Status P Date 2008-09-03 Cont ID  
Sent By kstevens Date 2008-09-03 Time 09:50 Rev Time 0.00
Received By kstevens Date 2008-09-03 Time 09:50 Sent To  
Notes
2008-09-03 09:51:15RESTAMP OF REVISIONS APPROVED 5-5-2008. -- REVISIONS OK
 -- SHTS P101A, P101B, P403, P502, P505, P507 & P508.

Review Stop P PLUMBING
Rev No 7 Status P Date 2008-05-05 Cont ID  
Sent By kstevens Date 2008-05-05 Time 10:21 Rev Time 0.00
Received By kstevens Date 2008-05-03 Time 17:54 Sent To  
Notes
2008-05-05 10:22:47REVISIONS OK -- SHTS P101A, P101B, P403, P502, P505,
 P507 & P508.

Review Stop P PLUMBING
Rev No 6 Status P Date 2008-03-19 Cont ID  
Sent By kstevens Date 2008-03-19 Time 08:54 Rev Time 0.00
Received By kstevens Date 2008-03-18 Time 18:54 Sent To  
Notes
2008-03-19 09:06:14 
  
  
  
 PASSED/PROVISO
  
 SHTS P101A & P101B INDICATES THE LAV AS FIXTURE MARK
 P-3B AND THE URINAL AS FIXTURE MARK P-2. THIS DOES NOT
 RELFECT THE FIXTURE SCHEDULE ON P601. REVISION
 REQUIRED.
  
 SHT P101B SHOWS RISER CW/52 - HW/52. RISER CW/52 -
 HW/52 NOT SUBMITTED. REVISION REQUIRED.
  
 SHT P403 SHOWS FIXTURE MARK P-8 FOR THE TUB IN DETAIL
 #4. P-8 IN THE FIXTURE SCHEDULE IS INDICATED AS A
 LAUNDRY ROOM SINK. REVISION REQUIRED.
  
 SHT P502 SAN/47 SHOWS FIXTURE MARK P-7, (INDICATED AS A
 BREAK ROOM SINK ON FIXTURE SCHEDULE), AND P-8,
 (INDICATED AS A LAUNDRY ROOM SINK ON THE FIXTURE
 SCHEDULE), BUT ARE SHOWN AS SHOWER & TUB ON THE FLOOR
 PLAN. REVISION REQUIRED.
  
 SHT P502 SAN/48 SHOWS FIXTURES IN THE CEILING. NO
 FIXTURES ARE SHOWN ON THE FLOOR PLAN FOR THIS RISER.
 REVISION REQUIRED.
  
 SHT P505 RISERS 40, 41, 42, 45, 46, 47 & 63 STILL SHOW
 WATER SUPPLY UNDER THE SLAB. REVISION REQUIRED.
  
 SHT P507 WATER HAMMER ARRESTORS ARE REQUIRED AT THE
 DISH SANITIZER. SECTION 604.9. REVISION REQUIRED.
  
  
  
  
 .

Review Stop P PLUMBING
Rev No 5 Status F Date 2008-03-13 Cont ID  
Sent By kstevens Date 2008-03-13 Time 10:46 Rev Time 0.00
Received By kstevens Date 2008-03-12 Time 18:55 Sent To  
Notes
2008-03-13 12:12:09 
 DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2001 BUILDING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
 ******FROM PREVIOUS REVIEW: 3RD REVIEW:
 ********FROM PREVIOUS REVIEWS: 4TH REVIEW:
 **********FROM PREVIOUS REVIEWS: 5TH REVIEW:
  
 1. OK
 2. OK
 3. OK
 4. OK
 5. OK
 6. OK
 7. OK
 8. OK
 9. OK
 10. OK
 11. OK
 12. OK
  
 13. SHTS A-802 APPLICABLE ELEVATIONS 1 THRU 13,A-803
 APPLICABLE ELEVATIONS 1- THRU 14, A-804 APPLICABLE
 ELEVATIONS 1 THRU 15, SHALL COMPLY WITH SECTIONS
 11-4.16, 11-4.18, 11-4.19, 11-4.20, 11-4.21 & 11-4.22
 AND ALL SUBSECTIONS. PLEASE INDICATE ON ELEVATIONS.
 ALSO SHOW ALL W/C'S TO BE 18" OFF THE WALL TO THE
 CENTERLINE OF THE FIXTURE, & SHOW ALL LAVS TO BE MIN.
 15" OFF THE WALL TO THE CENTERLINE OF THE FIXTURE WHERE
 THE FIXTURES ARE ADJACENT TO THE WALLS. FIGURES 11-28
 AND 11-32.
 ****NO RESPONSE. SHOW THE FOLLOWING:
 SHT A-802..
 ___FOR W/C'S:
 A. OK
 ___FOR URINALS:
 A. 11-4.18.3 CLEAR FLOOR SPACE
 ******NOT ADDRESSED
 ********NOT ADDRESSED
 **********RESPONSE NOTED, BUT NOT ADDRESSED
 B. OK
 ____FOR LAVS:
 A. OK
 B. OK
 C. OK
 SHT A-803
 ___FOR W/C'S:
 A. OK
 ___FOR LAVS:
 A. OK
 B. OK
 ___FOR TUBS:
 A. 11-4.20.2 CLEAR FLOOR SPACE
 ******NOT ADDRESSED
 ********NOT ADDRESSED
 **********NO RESPONSE, NOT ADDRESSED
 B. 11-4.20.5 CONTROLS
 ******NOT ADDRESSED
 ********NOT ADDRESSED
 **********NO RESPONSE, NOT ADDRESSED
 ___FOR TOILET ROOMS
 A. OK
  
 14. OK
 15. N/A
 16. OK
 17. OK
 18. OK
 19. OK
 20. OK
 21. OK
 22. OK
 23. OK
 24. OK
 25. OK
 26. OK
 27. OK
 28. OK
 29. OK
 30. OK
 31. OK
  
 32. SUBMIT A SANITARY HORIZONTAL BUILDING DRAIN
 ISOMETRIC RISER DIAGRAM THAT REFLECT THE FLOOR PLAN.
 SHOW ALL PIPE SIZES, RISER LOCATIONS, TRAPS AND DFU'S
 AS THEY ACCUMULATE IN THE SYSTEM. SECTION 106.3.5.1.3.
 -SHOW ALL THE FIRST FLOOR FIXTURES NOT CONNECTED TO A
 VERTICAL RISER ON THE HORIZONTAL RISER DIAGRAM. (SEE
 BREAK ROOM, FOOD PREP, LAUNDRY ROOM, TOILET ROOMS, PUMP
 ROOM ETC.).
 ****RESPONSE NOTED, BUT NOT ALL FIXTURES OR FIXTURES
 GROUPS FOR THE FIRST FLOOR ARE SHOWN ON THE HORIZONTAL
 SANITARY RISER ISOMETRIC DIAGRAM. THE 1ST FLOOR IS
 WHERE THE BRANCH LINE CONNECTS ALL RISERS, TOILET
 ROOMS, PUMP ROOMS, LAUNDRY, FOOD PREP ROOM, BREAK ROOM,
 VENDING, VENTING ETC. AND ALL THIS PIPING SHALL BE
 SHOWN CONNECTING TO THE HORIZONTAL ISOMETRIC.
 ******RESPONSE NOTED, BUT THE COMMENT IS STILL NOT
 ADDRESSED.
 ********RESPONSE NOTED, BUT THE PIPE SIZES ARE NOT
 SHOWN FOR MUCH OF THE PIPING, DFU'S ARE NOT INDICATED
 AS THEY ACCUMULATE IN THE SYSTEM, NOT ALL PIPING FOR
 THE FOOD PREP AREA PER SHT P-401 DETAIL 5,THE
 DOWNSTREAM VENT FOR THE DOMESTIC PUMP ROOM OFFSETS
 HORIZONTALLY PRIOR TO 6" ABOVE THE FLOOD RIM LEVEL.
 (SECTION 905.4). THE PIPING FOR THE GREASE INTERCEPTOR
 IS NOT SHOWN ON THE RISER DIAGRAM. THE BRANCH LINE FOR
 KEY NOTE 48, (WATER WALL), SHOWN ON THE FLOOR PLAN IS
 NOT SHOWN ON THE RISER DIAGRAM. VENTING DOES NOT
 REFLECT THE FLOOR PLAN IN SOME AREAS AND NOT SHOWN IN
 OTHERS. PIPING DOES NOT REFLECT THE FLOOR PLAN AT THE
 FOLLOWING RISERS: 5, 6, 7, 8, 9, 10, 18, 19, 22 & 60.
 THE CLEANOUT DOWNSTREAM OF SANT. RISER 63 SHOWN ON THE
 FLOOR PLAN IS NOT SHOWN ON THE RISER DIAGRAM. THE
 BRANCH LINE FOR THE ICE MACHINE, (9), IS SHOWN UPSTREAM
 OF THE DOUBLE WYE FITTING ON THE FLOOR PLAN, BUT
 DOWNSTREAM OF THE DOUBLE WYE ON THE RISER DIAGRAM. THE
 RISER DIAGRAM FOR THE PUBLIC TOILET ROOMS DOES NOT
 REFLECT THE FLOOR PLAN. THE FLOOR DRAIN LINES ARE SHOWN
 ON THE BRANCH LINE TO THE LAVS ON THE RISER DIAGRAM,
 BUT OFF THE BRANCH LINE TO THE WATER CLOSETS, URINAL ON
 THE FLOOR PLAN. PLEASE CORRELATE THE RISER DIAGRAMS AND
 THE FLOOR PLAN.
 **********RESPONSE NOTED, BUT THE PIPING FOR THE FOOD
 PREP AREA, (3 COMP. SINK, HAND SINK, AND FLOOR DRAIN),
 IS NOT SHOWN ON THE RISER DIAGRAM AS WELL AS THE
 ISOMETRIC PIPING FOR THE GREASE INTERCEPTOR AS
 INDICATED. PIPING DOES NOT REFLECT THE FLOOR PLAN AT
 THE FOLLOWING RISERS: 5, 6, 7, 8, 9, 10, 18, 19, 22 &
 60. THE CLEANOUT DOWNSTREAM OF SANT. RISER 63 SHOWN ON
 THE FLOOR PLAN IS NOT SHOWN ON THE RISER DIAGRAM. AFTER
 CHECKING THE DRAINAGE FIXTURE UNITS FOR ALL RISERS AND
 BRANCH LINES IT APPEARS THAT THE DFU'S INDICATED ARE
 NOT CORRECT IN MANY AREAS. ALSO THE PIPE SIZE FOR THE
 BUILDING DRAIN SHALL BE INCREASED TO 8" DOWNSTREAM OF
 RISERS 24 THRU 27 AND 44 THRU 47 AS THE DFU'S ADD UP TO
 742. 6" IS SHOWN.
  
 32A. SUBMIT A HORIZONTAL BUILDING WATER ISOMETRIC RISER
 DIAGRAM. SHOW ALL PIPE SIZES, VALVES, WATER HAMMER
 ARRESTORS, (REQUIRED BY SECTION 604.9 FOR ICE MAKERS,
 WASH MACHINES, AND DISHWASHERS).
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THERE IS STILL NO WATER
 ISOMETRICS FOR THE EMPLOYEE TOILET ROOM, THE WASH
 MACHINE ROOM, THE FOOD PREP AREA, THE WATER HEATER
 ROOM, GUEST LAUNDRY, MOP SINK/WASH MACHINE. RISER SHALL
 INDICATE THE PIPING AS IT ENTERS THE BUILDING SHOWING
 THE FULL OPEN VALVE REQUIRED BY SECTION 606.1(2) AND AT
 THE BASE OF EACH RISER DIAGRAM REQUIRED BY SECTION
 606.1(3).
 ********RESPONSE NOTED, BUT THE RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN IN MANY AREAS WHERE THE BRANCH
 LINES CONNECT TO THE MAIN WATER LINES, (SEE RISER
 BRANCH TO RISERS 53, 54, 55,45, 46, 47 & THEDISH
 SANITIZER,AT THE PUBLIC TOILET ROOMS, RISER NUMBERS
 DO NOT REFLECT THE FLOOR PLAN FOR RISERS 28, 29 & 30,
 (TWO SETS). THE REQUIRED WATER HAMMER ARRESTORS SHALL
 BE INDICATED PER SECTION 604.9, (ICE MAKERS, DISH
 WASHER, WASH MACHINES OR ANY OTHER QUICK CLOSING
 VALVE). SOME LINES HAVE THE HOT WATER LINES LABELED AS
 COLD WATER AND SOME LINES HAVE THE COLD WATER LINES
 LABELED AS HOT WATER LINES. IN THE PUBLIC TOILETS
 FIXTURES 3B HAVE THE COLD ON THE LEFT AND THE HOT ON
 THE RIGHT. (SECTION 607.4). SHOW ALL VALVES REQUIRED
 PER SECTIONS 606.1 & 606.2 ON THE RISER DIAGRAM. SHOW
 ALL PIPE SIZES PER SECTION 604. SHT P507 DETAIL 2 THE
 STANDARD TOILET AND THE URINAL ARE MISLABELED AND THE
 FIXTURE INDICATED AS P5A, (SHOWER?), IS NOT INDICATED
 ON THE WATER RISER DIAGRAM. PLEASE CLARIFY.
 **********RESPONSE NOTED, BUT THE PIPING TO THE DISH
 SANITIZER AND THE PUBLIC TOILETS STILL DOES NOT REFLECT
 THE FLOOR PLAN.--THE REQUIRED WATER HAMMER
 ARRESTORS SHALL BE INDICATED PER SECTION 604.9, (ICE
 MAKERS, DISH WASHER, WASH MACHINES OR ANY OTHER QUICK
 CLOSING VALVE). THIS IS A REQUIREMENT FOR THE WATER
 SYSTEM AND SHALL BE SHOWN ON THE WATER SYSTEM.
  
 33 OK
 34. OK
 35. OK
 36. OK
 37. OK
  
 **********NEW COMMENTS**********
  
 1B. OK
 2B. OK
  
 3B. SUBMIT ISOMETRIC STORM RISER DIAGRAMS FOR EACH RWL.
 SHOW ALL PIPE SIZES, OFFSETS, SQUARE FOOTAGE & INDICATE
 THE TERMINATION POINT FOR EACH ROOF DRAIN. IF THERE ARE
 TYPICAL RWL'S, INDICATE THE ROOF DRAINS THAT ARE
 TYPICAL OF WHICH RWL. EACH RWL AND ROOF DRAIN SHALL BE
 NUMBERED SUCH AS RWL-1, RWL-2 AND RD-1, RD-2 AND SHALL
 BE INDICATED ON EACH FLOOR PLAN SO AS TO TRACK EACH
 RWL/RD THROUGH THE BUILDING. TABLE 1106.3 AND SECTION
 106.1.3.5.1.3(7)(13).
 ******RESPONSE NOTED, BUT THE RISERS ARE NOT COMPLETE.
 SHOW THE RISERS FROM THE ROOF DRAIN THRU THE BUILDING
 STORM DRAIN PIPING AND EXITING THE BUILDING SHOWING ALL
 PIPE SIZE, CLEANOUTS REQUIRED BY SECTION 1101.8,
 OFFSETS AND IF RISERS COMBINE IN THE BUILDING SHOW THIS
 ON THE RISER ALSO. THE SQUARE FOOTAGE AND PIPE SIZE
 WILL BE VERIFIDE WHEN THE ROOF DRAINAGE CALCULATIONS
 HAVE BEEN SUBMITTED AND VERIFIED.
 ********RESPONSE NOTED, BUT THE RISER DIAGRAM AND THE
 FLOOR PLAN STATE "FOR CONT. SEE P101C". THE SHT P101C
 SUBMITTED IS FOR HOMEWOOD SUITES, NOT SPRINGHILL
 SUITES. RISER DIAGRAM DOES NOT REFLECT THE FLOOR PLAN.
 NO PIPING TO THE RISERS FOR THE STORM DRAINAGE AT THE
 "PORTE COCHERE" AS WELL AS THE PIPING FOR THE DRAINAGE
 TO THE EAST SIDE OF THE BUILDING. (NO SHT A101C
 SUBMITTED FOR THE SPRINGHILL SUITES). SOME PIPE SIZING
 IS INCORRECT. (SEE 4" HORIZONTAL INDICATED FOR 2068SF).
 SHOW ALL PIPE SIZES, AND INDICATED THE SQUARE FOOTAGE
 AS IT ACCUMULATES IN THE SYSTEM.
 **********RESPONSE NOTED BUT THE PIPE SIZING IS STILL
 INCORRECT FOR THE PIPING FOR THE 4" 2371SF 1/8"-FT,
 ZONES 1 & 2. ALSO THE PIPING SHALL BE UNIFORM IN SLOPE.
 THE PIPING SHOWS 1/4"-FT TO 1/2"-FT IN ONE AREA AND
 1/8"-FT TO 1/2"-FT IN TWO OTHER AREAS. (SEE ZONES 7 &
 1). SECTION 704.1. ONE LINE DOES NOT INDICATE THE SLOPE
 OR PIPE SIZE ON THE HORIZONTAL 2344SF. (ZONE 6 OFD).
 SECTION 106.1.2.
  
 4B. OK
  
 *****NEW COMMENTS 3RD REVIEW*****
  
 1C. OK
  
 2C. SHT P401 PLEASE SUBMIT RISER DIAGRAMS FOR THE
 SANITARY AND WATER PIPING IN DETAILS 1, 4, 5 & 6. FOR
 THE SANITARY SHOW ALL PIPE SIZES, TRAPS, & VENTS. FOR
 THE WATER SHOW ALL PIPE SIZES, VALVES, WATER HAMMER
 ARRESTORS ECT. SECTION 106.3.5.1.3. ********RESPONSE
 NOTED, BUT THE RISER DIAGRAMS FOR DETAILS 5 & 6 ARE NOT
 SHOWN ON SHTS P507 OR P508. NO WATER TO THE HAND SINK
 NOR TO THE 3 COMPARTMENT SINK. NO SANITARY SHOWN TO THE
 HAND SINK, THE 3 COMPARTMENT SINK OR THE FLOOR DRAIN
 SHOWN IN DETAIL 5 SHT P401. THE FLOOR DRAIN SHALL
 CONNECT TO THE GREASE LINE, NOT THE SANITARY LINE.
 **********RESPONSE NOTED, BUT ISOMETRICS FOR DETAILS 5
 & 6 NOT ADDRESSED AS THEY ARE NOT ON SHTS P507 OR
 P508.
  
 3C. OK
 4C. OK
 5C. OK
  
 6C. SHT P502 PLEASE INDICATE THE LOCATION OF THE WATER
 RISER DIAGRAMS FOR THE KITCHEN AREA, THE WATER HEATER
 ROOM, THE GUEST LAUNDRY ROOMS, THE LAUNDRY ROOM, THE
 EMPLOYEE TOILET ROOM AND ANY OTHER COMMON AREA NOT
 SUBMITTED. SHOW ALL PIPE SIZES, VALVES, WATER HAMMER
 ARRESTORS ETC. SECTION 106.3.5.1.3.--RISER 1/502
 INDICATES A MOP SINK AND A SHOWER ON ONE PORTION AND A
 WASH MACHINE AND WATER CLOSET ON THE OTHER PORTION.
 ALSO IT SHOWS FIXTURES ON ALL 5 FLOORS. PLEASE CLARIFY
 AS THERE ARE NOT FIXTURES ON THE FIRST FLOOR AND THESE
 FIXTURES ARE NOT SHOWN ON THE FLOOR PLAN.--RISER
 2/502 SHOWS WASH MACHINES AND WATER CLOSETS ON ALL 5
 FLOORS. PLEASE CLARIFY.--RISER 3/502 SHOWS MOP
 SINKS ON THE LAV RISER. PLEASE CLARIFY.--RISER
 4/502 SHOWS SHOWERS ON THE SINK RISER. PLEASE CLARIFY.
 --RISER 4/502 SHOW FIXTURE 4A WHICH IS NOT SHOWN ON
 THE FIXTURE SCHEDULE. PLEASE CLARIFY.--RISER 5/502
 SHOWS FIXTURE 9A WHICH IS NOT INDICATED ON THE FIXTURE
 SCHEDULE. PLEASE CLARIFY.--RISER 6/502 NONE OF THE
 FIXTURES ON THE RISE REFLECT WHAT IS SHOWN ON THE FLOOR
 PLAN. PLEASE CLARIFY.--PLEASE MAKE SURE ALL RISERS
 REFLECT THE FLOOR PLAN AND REFLECT THE FIXTURES SHOWN
 ON THE FLOOR PLAN. SECTION 106.1.1.--TYPICAL WATER
 RISER DIAGRAMS ARE NOT TYPICAL ON THE FLOOR PLAN.
 DIFFERENT FIXTURES ON THE FLOOR REQUIRE DIFFERENT RISER
 DIAGRAMS THAT REFLECT THE FLOOR PLAN. PLEASE SUBMIT
 RISER DIAGRAMS THAT REFLECT THE FLOOR PLAN.
 ********RESPONSE NOTED, BUT THE WATER HAMMER ARRESTORS
 ARE NOT SHOWN ON THE WATER RISER DIAGRAMS. RISER 5/502
 NOW SHOWS P-7, (BREAK SINK), AND P-8, (LAUNDRY ROOM
 SINK), WHERE AS THE FLOOR PLAN SHOWS SHOWER/TUB.ALSO
 ON SANITARY RISER 48 FIRST FLOOR SHOWS TWO FIXTURES, P4
 & P-13, BUT ON THE FLOOR PLAN NO FIXTURES ARE SHOWN.
 PLEASE CORRELATE. SANITARY RISER 48 APPEARS TO RUN
 THROUGH THE BASE CABINET ON THE FIRST FLOOR. PLEASE
 CLARIFY.
 **********RESPONSE NOTED, BUT THE WATER HAMMER
 ARRESTORS ARE A WATER SUPPLY PIPING REQUIREMENT AND
 SHALL BE SHOWN ON THE PIPING FOR THE FIXTURES
 INDICATED. THE WATER RISER DIAGRAMS INDICATED IN
 COMMENT RESPONSE ARE NOT SHOWN ON SHEETS P507 OR P508.
  
 7C. OK
 8C. OK
 9C. OK
 10C. OK
  
 **********NEW COMMENT**********
  
 1D. SHTS P504 & P505 THE WATER RISER DIAGRAMS DO NOT
 REFLECT THE FLOOR PLAN. THE FLOOR PLAN SHOWS THE WATER
 PIPING FOR THE MAINS IN THE CEILING OF THE FIRST FLOOR,
 BUT THE RISER DIAGRAMS SHOW THE WATER RISERS CONNECTING
 TO THE MAIN UNDERGROUND. PLEASE CORRELATE. SECTIONS
 106.1.1 & 604.
 **********RESPONSE NOTED, BUT COMMENT NOT ADDRESSED.
  
 2D. N/A PER R. BROWN.
  
 **********NEW COMMENT**********
  
 1E. MANY OF THE MARKS FOR FIXTURES ON THE FLOOR PLANS &
 WATER RISER DIAGRAMS DO NOT REFLECT THE FIXTURE MARKS
 CALLED OUT ON THE FIXTURE SCHEDULE ON SHT P601. PLEASE
 CORRELATE. (EXAMPLE ON ONE IS THE DRINKING FOUNTAIN AT
 THE PUBLIC TOILETS SHTS P101B & P508 INDICATED AS
 FIXTURE P5A, (ROLL IN SHOWER), AND IS NOT SHOWN ON SHT
 P507.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 4 Status F Date 2008-01-31 Cont ID  
Sent By kstevens Date 2008-01-31 Time 11:17 Rev Time 0.00
Received By kstevens Date 2008-01-23 Time 16:54 Sent To  
Notes
2008-01-31 16:55:25 
 DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2001 BUILDING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
 ******FROM PREVIOUS REVIEW: 3RD REVIEW: ********FROM
 PREVIOUS REVIEWS: 4TH REVIEW:
  
 1. OK
 2. OK
 3. OK
 4. OK
 5. OK
 6. OK
 7. OK
  
 8. SHT A-106 SUBMIT CALCULATIONS FOR THE PRIMARY AND
 SECONDARY ROOF DRAINS. SHOW THE AREA TO BE DRAINED FOR
 EACH ROOF DRAIN, AND INDICATE 1/2 THE AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS ADDED TO THAT AREA.
 ALSO INDICATE ALL AREAS FROM ROOF AREAS THAT DRAIN ONTO
 THE ROOF FROM ABOVE. SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS AND TABLES. INDICATE TOTAL AREA BEING
 DRAINED BY EACH DRAIN.
 ****RESPONSE NOTED, BUT NO CALCULATION WERE FOUND.
 PLEASE SUBMIT THE CALCULATIONS REQUESTED.
 ******RESPONSE NOTED, BUT THE CALCULATIONS WERE NOT
 SUBMITTED. IS THE AREA FOR EACH ROOF DRAIN EXACTLY THE
 SAME? ARE THE VERTICAL WALLS & PARAPETS THE SAME FOR
 EACH AREA? PLEASE SUBMIT THE CALCULATIONS FOR EACH AREA
 SHOWING THE INFORMATION REQUESTED. ********RESPONSE
 NOTED, BUT CALCULATIONS WERE NOT SUBMITTED. HAVING DONE
 THE CALCULATIONS FOR ONE AREA, IT APPEARS THAT THE AREA
 DRAINS APPROXIMATELY 2784SF. THIS IS THE NORTHWEST
 CORNER. OTHER AREAS HAVE A MUCH SMALLER AREA, (TWO
 AREAS BETWEEN COL. LINES 4 & 8 ON THE EAST SIDE OF THE
 ROOF). SUBMIT THE CALCULATIONS FOR EACH AREA SHOWING
 THE SQUARE FOOTAGE OF EACH AREA, WITH 1/2 THE AREA OF
 ALL VERTICAL WALLS, AS WELL AS ALL ROOF AREAS THAT
 DRAIN ONTO THE ROOF FROM ABOVE. ALSO THE ROOF FOR THE
 STAIRWELL IS NOT INDICATED ON THE PLUMBING SHEET AND NO
 INDICATION OF HOW THE ROOF WILL BE DRAINED. PRIMARY AND
 SECONDARY ROOF DRAINS ARE REQUIRED FOR THE ROOF OVER
 THE STAIRWELL. (INFORMATIONAL, THE STAIRWELL IS NOT
 INDICATED ON SHT A-201 DETAIL 1, SHT A-301 DETAIL 2,
 NOR IS IT SHOWN ON THE ROOF PLAN SHT P105).
  
 9. OK
  
 10. SHTS A-411, & A-412 SHOW THE CLEAR FLOOR SPACE FOR
 EACH FIXTURE AND SHOW EACH FIXTURE IN THE ACCESSIBLE
 UNITS. SECTIONS 11-4.16.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE CLEAR FLOOR SPACE IS NOT
 SHOWN FOR THE SHOWER, THE TUB, NOR THE SINK.
 ********RESPONSE NOTED, BUT NOT ADDRESSED FOR THE
 SHOWER, TUB, SINK.
  
 11. OK
  
 12 SHT A-801 ELEVATION 15. THE SINK SHALL COMPLY WITH
 SECTION 11-4.24 AND ALL SUBSECTIONS. A FORWARD APPROACH
 CLEAR FLOOR SPACE IS REQUIRED AND SHALL EXTEND A
 MAXIMUM OF 19" UNDERNEATH THE SINK. CABINET DOORS ARE
 NOT APPROVED IN THE CLEAR FLOORSPACE AND ARE NOT TO
 BE INSTALLED.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT COMPLIANCE FOR THE FOLLOWING
 IS NOT SHOWN:
 A. OK
 B. OK
 C. 11-4.24.5 CLEAR FLOOR SPACE
 ********RESPONSE NOTED, BUT THE CLEAR FLOOR SPACE IS
 NOT SHOWN ON SHT A-401.
 D. OK
  
 13. SHTS A-802 APPLICABLE ELEVATIONS 1 THRU 13,A-803
 APPLICABLE ELEVATIONS 1- THRU 14, A-804 APPLICABLE
 ELEVATIONS 1 THRU 15, SHALL COMPLY WITH SECTIONS
 11-4.16, 11-4.18, 11-4.19, 11-4.20, 11-4.21 & 11-4.22
 AND ALL SUBSECTIONS. PLEASE INDICATE ON ELEVATIONS.
 ALSO SHOW ALL W/C'S TO BE 18" OFF THE WALL TO THE
 CENTERLINE OF THE FIXTURE, & SHOW ALL LAVS TO BE MIN.
 15" OFF THE WALL TO THE CENTERLINE OF THE FIXTURE WHERE
 THE FIXTURES ARE ADJACENT TO THE WALLS. FIGURES 11-28
 AND 11-32.
 ****NO RESPONSE. SHOW THE FOLLOWING:
 SHT A-802..
 ___FOR W/C'S:
 A. 11-4.16.2 OK
 ___FOR URINALS:
 A. 11-4.18.3 CLEAR FLOOR SPACE
 ******NOT ADDRESSED
 ********NOT ADDRESSED
 B. 11-4.18.4 FLUSH CONTROLS
 ******NOT ADDRESSED
 ********NOT ADDRESSED (HEIGHT)
 ____FOR LAVS:
 A. OK
 B. OK
 C. OK
 SHT A-803
 ___FOR W/C'S:
 A. OK
 ___FOR LAVS:
 A. OK
 B. OK
 ___FOR TUBS:
 A. 11-4.20.2 CLEAR FLOOR SPACE
 ******NOT ADDRESSED
 ********NOT ADDRESSED
 B. 11-4.20.5 CONTROLS
 ******NOT ADDRESSED
 ********NOT ADDRESSED
 ___FOR TOILET ROOMS
 A. OK
  
 14. SHT A-806 DETAIL 5 INDICATE THE FOLLOWING:
 A. 11-4.24.4 OK
 B. 11-4.24.5 CLEAR FLOOR SPACE
 ******NOT ADDRESSED
 ********NOT ADDRESSED
 C. 11-4.24.7 FAUCETS (TYPE)
 ******NOT ADDRESSED
 ****NO RESPONSE, NOT ADDRESSED
 ******RESPONSE NOTED, NOT COMPLETLY ADDRESSED
 ********RESPONSE NOTED, BUT NOT FAUCET NOT APPROVED.
 (SEE ATTACHED SHEET)
  
  
 15. N/A
  
 16. SHT A-812 DETAIL 1, INDICATES A WATER WALL FEATURE.
 MORE INFORMATION IS REQUIRED. WILL THERE BE A WATER
 SUPPLY LINE CONNECTED TO THE WATER FEATURE? WILL THE
 WATER FEATURE CONNECT TO THE SANITARY DRAINAGE SYSTEM.
 PLEASE CLARIFY.SECTION 106.1.1.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT PLEASE EXPLAIN KEYNOTES #47 &
 #48 ON SHT P101 AND RELATED WATER PIPING THAT INDICATES
 WATER TO THE WATER WALL FEATURE? BACKFLOW PREVENTION IS
 REQUIRED FOR THE WATER SUPPLY. PLEASE INDICATE METHOD.
 SECTION 608.--PLEASE INDICATE THE DRAINAGE PIPING
 ON THE FLOOR PLAN AND MAKE SURE IT IS REFLECTED IN AN
 ISOMETRIC RISER DIAGRAM.
 ********RESPONSE NOTED, BUT THE WATTS 709 IS A DOUBLE
 CHECK VALVE ASSEMBLIES AND IS NOT APPROVED FOR THIS
 APPLICATION. (THE MINIMUM SIZE IS 2-1/2"). A WATTS N36
 VACUUM BREAKER, (OR EQUIVALENT), INSTALLED AT THE TOP
 OF THE DROP WILL BE SUFFICIENT. PLEASE CORRECT KEYNOTE
 21 ON SHT P101B
  
 17. OK
 18. OK
 19. OK
 20. OK
 21. OK
  
 22. SHT P101 SOME RISERS AND SOME FIRST FLOOR FIXTURES
 SHOW NO PIPING OR BRANCH LINES CONNECTING THE
 RISERS/FIXTURES TO THE BUILDING DRAIN. PLEASE CLARIFY.
 SECTION 106.1.1.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THERE IS STILL SANITARY
 PIPING NOT SHOWN. THE PIPING FOR ALL SYSTEMS IS NOT
 VERY LEGIBLE. THE PIPING IS NOT SHOWN TO MANY RISERS,
 AND IN MANY CASES THE PIPING IS HARD TO FOLLOW BECAUSE
 IS IS COVERED BY DARKER/BOLDER LINES OR OTHER SYSTEMS.
 IN SOME CASES IT IS NOT CLEAR WHAT SYSTEM CONNECTS TO
 WHAT RISER. SOME FIXTURES HAVE NO WATER PIPING SHOWN.
 SEE NEW COMMENTS FOR SHT P101 AT THE END OF THESE
 COMMENTS.
 ********RESPONSE NOTED, BUT THE BRANCH PIPING TO SANT.
 RISERS 13, 14, 16, 17 & 18 IS STILL NOT SHOWN ON THE
 FLOOR PLAN.
  
 23. OK
 24. OK
 25. OK
 26. OK
 27. OK
 28. OK
 29. OK
 30. OK
 31. OK
  
 32. SUBMIT A SANITARY HORIZONTAL BUILDING DRAIN
 ISOMETRIC RISER DIAGRAM THAT REFLECT THE FLOOR PLAN.
 SHOW ALL PIPE SIZES, RISER LOCATIONS, TRAPS AND DFU'S
 AS THEY ACCUMULATE IN THE SYSTEM. SECTION 106.3.5.1.3.
 -SHOW ALL THE FIRST FLOOR FIXTURES NOT CONNECTED TO A
 VERTICAL RISER ON THE HORIZONTAL RISER DIAGRAM. (SEE
 BREAK ROOM, FOOD PREP, LAUNDRY ROOM, TOILET ROOMS, PUMP
 ROOM ETC.).
 ****RESPONSE NOTED, BUT NOT ALL FIXTURES OR FIXTURES
 GROUPS FOR THE FIRST FLOOR ARE SHOWN ON THE HORIZONTAL
 SANITARY RISER ISOMETRIC DIAGRAM. THE 1ST FLOOR IS
 WHERE THE BRANCH LINE CONNECTS ALL RISERS, TOILET
 ROOMS, PUMP ROOMS, LAUNDRY, FOOD PREP ROOM, BREAK ROOM,
 VENDING, VENTING ETC. AND ALL THIS PIPING SHALL BE
 SHOWN CONNECTING TO THE HORIZONTAL ISOMETRIC.
 ******RESPONSE NOTED, BUT THE COMMENT IS STILL NOT
 ADDRESSED.
 ********RESPONSE NOTED, BUT THE PIPE SIZES ARE NOT
 SHOWN FOR MUCH OF THE PIPING, DFU'S ARE NOT INDICATED
 AS THEY ACCUMULATE IN THE SYSTEM, NOT ALL PIPING FOR
 THE FOOD PREP AREA PER SHT P-401 DETAIL 5,THE
 DOWNSTREAM VENT FOR THE DOMESTIC PUMP ROOM OFFSETS
 HORIZONTALLY PRIOR TO 6" ABOVE THE FLOOD RIM LEVEL.
 (SECTION 905.4). THE PIPING FOR THE GREASE INTERCEPTOR
 IS NOT SHOWN ON THE RISER DIAGRAM. THE BRANCH LINE FOR
 KEY NOTE 48, (WATER WALL), SHOWN ON THE FLOOR PLAN IS
 NOT SHOWN ON THE RISER DIAGRAM. VENTING DOES NOT
 REFLECT THE FLOOR PLAN IN SOME AREAS AND NOT SHOWN IN
 OTHERS. PIPING DOES NOT REFLECT THE FLOOR PLAN AT THE
 FOLLOWING RISERS: 5, 6, 7, 8, 9, 10, 18, 19, 22 & 60.
 THE CLEANOUT DOWNSTREAM OF SANT. RISER 63 SHOWN ON THE
 FLOOR PLAN IS NOT SHOWN ON THE RISER DIAGRAM. THE
 BRANCH LINE FOR THE ICE MACHINE, (9), IS SHOWN UPSTREAM
 OF THE DOUBLE WYE FITTING ON THE FLOOR PLAN, BUT
 DOWNSTREAM OF THE DOUBLE WYE ON THE RISER DIAGRAM. THE
 RISER DIAGRAM FOR THE PUBLIC TOILET ROOMS DOES NOT
 REFLECT THE FLOOR PLAN. THE FLOOR DRAIN LINES ARE SHOWN
 ON THE BRANCH LINE TO THE LAVS ON THE RISER DIAGRAM,
 BUT OFF THE BRANCH LINE TO THE WATER CLOSETS, URINAL ON
 THE FLOOR PLAN. PLEASE CORRELATE THE RISER DIAGRAMS AND
 THE FLOOR PLAN.
  
 32A. SUBMIT A HORIZONTAL BUILDING WATER ISOMETRIC RISER
 DIAGRAM. SHOW ALL PIPE SIZES, VALVES, WATER HAMMER
 ARRESTORS, (REQUIRED BY SECTION 604.9 FOR ICE MAKERS,
 WASH MACHINES, AND DISHWASHERS).
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THERE IS STILL NO WATER
 ISOMETRICS FOR THE EMPLOYEE TOILET ROOM, THE WASH
 MACHINE ROOM, THE FOOD PREP AREA, THE WATER HEATER
 ROOM, GUEST LAUNDRY, MOP SINK/WASH MACHINE. RISER SHALL
 INDICATE THE PIPING AS IT ENTERS THE BUILDING SHOWING
 THE FULL OPEN VALVE REQUIRED BY SECTION 606.1(2) AND AT
 THE BASE OF EACH RISER DIAGRAM REQUIRED BY SECTION
 606.1(3).
 ********RESPONSE NOTED, BUT THE RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN IN MANY AREAS WHERE THE BRANCH
 LINES CONNECT TO THE MAIN WATER LINES, (SEE RISER
 BRANCH TO RISERS 53, 54, 55,45, 46, 47 & THEDISH
 SANITIZER,AT THE PUBLIC TOILET ROOMS, RISER NUMBERS
 DO NOT REFLECT THE FLOOR PLAN FOR RISERS 28, 29 & 30,
 (TWO SETS). THE REQUIRED WATER HAMMER ARRESTORS SHALL
 BE INDICATED PER SECTION 604.9, (ICE MAKERS, DISH
 WASHER, WASH MACHINES OR ANY OTHE QUICK CLOSING VALVE).
 SOME LINES HAVE THE HOT WATER LINES LABELED AS COLD
 WATER AND SOME LINES HAVE THE COLD WATER LINES LABELED
 AS HOT WATER LINES. IN THE PUBLIC TOILETS FIXTURES 3B
 HAVE THE COLD ON THE LEFT AND THE HOT ON THE RIGHT.
 (SECTION 607.4). SHOW ALL VALVES REQUIRED PER SECTIONS
 606.1 & 606.2 ON THE RISER DIAGRAM. SHOW ALL PIPE SIZES
 PER SECTION 604. SHT P507 DETAIL 2 THE STANDARD TOILET
 AND THE URINAL ARE MISLABELED AND THE FIXTURE INDICATED
 AS P5A, (SHOWER?), IS NOT INDICATED ON THE WATER RISER
 DIAGRAM. PLEASE CLARIFY.
  
 33 OK
 34. OK
 35. OK
 36. OK
 37. OK
  
 **********NEW COMMENTS**********
  
 1B. OK
 2B. OK
  
 3B. SUBMIT ISOMETRIC STORM RISER DIAGRAMS FOR EACH RWL.
 SHOW ALL PIPE SIZES, OFFSETS, SQUARE FOOTAGE & INDICATE
 THE TERMINATION POINT FOR EACH ROOF DRAIN. IF THERE ARE
 TYPICAL RWL'S, INDICATE THE ROOF DRAINS THAT ARE
 TYPICAL OF WHICH RWL. EACH RWL AND ROOF DRAIN SHALL BE
 NUMBERED SUCH AS RWL-1, RWL-2 AND RD-1, RD-2 AND SHALL
 BE INDICATED ON EACH FLOOR PLAN SO AS TO TRACK EACH
 RWL/RD THROUGH THE BUILDING. TABLE 1106.3 AND SECTION
 106.1.3.5.1.3(7)(13).
 ******RESPONSE NOTED, BUT THE RISERS ARE NOT COMPLETE.
 SHOW THE RISERS FROM THE ROOF DRAIN THRU THE BUILDING
 STORM DRAIN PIPING AND EXITING THE BUILDING SHOWING ALL
 PIPE SIZE, CLEANOUTS REQUIRED BY SECTION 1101.8,
 OFFSETS AND IF RISERS COMBINE IN THE BUILDING SHOW THIS
 ON THE RISER ALSO. THE SQUARE FOOTAGE AND PIPE SIZE
 WILL BE VERIFIDE WHEN THE ROOF DRAINAGE CALCULATIONS
 HAVE BEEN SUBMITTED AND VERIFIED.
 ********RESPONSE NOTED, BUT THE RISER DIAGRAM AND THE
 FLOOR PLAN STATE "FOR CONT. SEE P101C". THE SHT P101C
 SUBMITTED IS FOR HOMEWOOD SUITES, NOT SPRINGHILL
 SUITES. RISER DIAGRAM DOES NOT REFLECT THE FLOOR PLAN.
 NO PIPING TO THE RISERS FOR THE STORM DRAINAGE AT THE
 "PORTE COCHERE" AS WELL AS THE PIPING FOR THE DRAINAGE
 TO THE EAST SIDE OF THE BUILDING. (NO SHT A101C
 SUBMITTED FOR THE SPRINGHILL SUITES). SOME PIPE SIZING
 IS INCORRECT. (SEE 4" HORIZONTAL INDICATED FOR 2068SF).
 SHOW ALL PIPE SIZES, AND INDICATED THE SQUARE FOOTAGE
 AS IT ACCUMULATES IN THE SYSTEM.
  
 4B. OK
  
 *****NEW COMMENTS 3RD REVIEW*****
  
 1C. SHT P101 PLUMBING KEYNOTES, 18, 30 & 31 WERE NOT
 FOUND. PLEASE CLARIFY.--KEYNOTES 41 & 43 STATE "NOT
 USED" BUT WERE FOUND ON THE FLOOR PLAN. PLEASE CLARIFY.
 --KEYNOTE 14 IS SHOWN CONNECTING TO THE BUILDING
 SANT. DRAIN. PLEASE CLARIFY.--KEYNOTE 20, ONE
 APPEARS TO BE CONNECTING TO STORM DRAIN LINE AND ONE
 APPEARS TO BE SHOWN TO A HOT WATER LINE. PLEASE
 CLARIFY.--KEYNOTE 25 STILL SHOWS 7" W.C. FOR THE
 GAS PRESSURE. RISER CHANGED TO 12" - 14" W.C. PLEASE
 CORRELATE.--KEYNOTE 47 INDICATES WATER SUPPLY TO
 WATER WALL. BACKFLOW PREVENTION IS REQUIRED. PLEASE
 INDICATE METHOD. (A VACUUM BREAKER AT THE HIGHES POINT
 WILL SUFFICE).SECTION 608.--KEYNOTE 1 INDICATES
 SANT./HOT/COLD BUT MOST KEYNOTES ON THE FLOOR PLAN ONLY
 SHOW THE HOT & COLD WATER BUT NO SANITARY. CLARIFY. --
 KEYNOTE 9 IS SHOWING THE WATER SUPPLY TO AN ICE MACHINE
 CONNECTING TO A 2-1/2" FIRE LINE IN THE STAILWELL. THE
 FIRE LINE IS NOT CONSIDERED A POTABLE WATER LINE, AND
 ONLY THE PIPING REQUIRED FOR THE FIGHTING OF FIRES
 SHALL BE LOCATED IN THE STAIRWELLS. NFPA-101 SECTION
 7.1.3.2.1(6). PLEASE DELETE THE CONNECTION AND SHOW THE
 ICE MAKER CONNECTING TO THE POTABLE WATER SYSTEM.--
 REFERENCES TO SHT P402 & P403 ARE SHOWN WHEN CALLING
 OUT ENLARGED SECTIONS. SHEETS P402 & P403 HAVE NOT BEEN
 SUBMITTED. PLEASE CLARIFY.--KEYNOTE 48 DOES NOT
 SHOW SANITARY PIPING.PLEASE CLARIFY.--KEYNOTE 40
 & 26 IN THE GAS SYSTEM. PLEASE INDICATE WHERE THE
 CONTINUANCE OF THE GAS LINE AFTER KEYNOTES IS LOCATED.
 --KEYNOTE 21, (SANT.),APPEARS TO CONNECT TO THE GAS
 SYSTEM. PLEASE CLARIFY.--KEYNOTE 22 SHOWS NO
 SANITARY. PLEASE CLARIFY.--KEYNOTE 4 AT SOME SHOW
 NO HOT WATER SUPPLY. PLEASE CLARIFY.--KEYNOTE 3 AT
 ONE 1/P402 SHOWS NOT WATER SUPPLY LINES. PLEASE
 CLARIFY. --STORM DRAIN IS SHOWN ENTERING THE
 BUILDING ON THE EAST SIDE OF THE BUILDING AND EXITING
 BY THE PORTE COCHERE. PLEASE INDICATED WHERE THE STORM
 LINE CONTINUES EAST OF THE BUILDING AND INDICATE WHERE
 THE RISER DIAGRAM IS FOR THIS STORM PIPING.--A
 WATER LINE IS SHOWN CONNECTING TO A 3/4" NFWH. PLEASE
 INDICATE WHERE THIS LINE CONTIUES AND INDICATE WHERE ON
 THE RISER DIAGRAM THIS IS SHOWN.--KEYNOTES 20, 21 &
 22 EAST OF THE PUBLIC TOILET ROOMS DO NOT SHOW SANITARY
 CONNTECTING TO THE RISERS. PLEASE CLARIFY.--4" SAN
 A/C IS NOT INDICATED ON THE PLUMBING LEGEND ON SHT
 P601. PLEASE INDICATE WHAT THE A/C STANDS FOR. PLEASE
 SHOW ON THE PLUMBING LEGEND.--THE 4" SAN A/C ABOVE
 THE KITCHEN AREA DOES NOT APPEAR TO CONNECT TO THE
 SANITARY BUILDING DRAIN. PLEASE CLARIFY.--TWO WAY
 CLEANOUTS ARE REQUIRED AT THE ENTRANCE AND EXIT PIPING
 OF THE GREASE INTERCEPTOR AS WELL AS NEAR THE JUNCTION
 OF THE BUILDING DRAIN AND THE BUILDING SEWER AS THE
 PIPING EXITS THE BUILDING. WPB UTILITY STANDARD AND
 SECTION 708.3.5. (IF THE 2-WAY C/O'S ARE INSTALLED AT
 THE GREASE INTERCEPTOR THEY WILL SUFFICE FOR BOTH
 REQUIREMENTS). SECTION 106.1.1.
 ********RESPONSE NOTED, BUT NOW KEYNOTES 9 & 26 STATE
 "NOT USED" BUT ARE SHOWN ON THE FLOOR PLAN. ALSO
 KEYNOTE 40 HAS NOT BEEN FOUND ON THE FLOOR PLAN. PLEASE
 CLARIFY.
  
 2C. SHT P401 PLEASE SUBMIT RISER DIAGRAMS FOR THE
 SANITARY AND WATER PIPING IN DETAILS 1, 4, 5 & 6. FOR
 THE SANITARY SHOW ALL PIPE SIZES, TRAPS, & VENTS. FOR
 THE WATER SHOW ALL PIPE SIZES, VALVES, WATER HAMMER
 ARRESTORS ECT. SECTION 106.3.5.1.3. ********RESPONSE
 NOTED, BUT THE RISER DIAGRAMS FOR DETAILS 5 & 6 ARE NOT
 SHOWN ON SHTS P507 OR P508. NO WATER TO THE HAND SINK
 NOR TO THE 3 COMPARTMENT SINK. NO SANITARY SHOWN TO THE
 HAND SINK, THE 3 COMPARTMENT SINK OR THE FLOOR DRAIN
 SHOWN IN DETAIL 5 SHT P401. THE FLOOR DRAIN SHALL
 CONNECT TO THE GREASE LINE, NOT THE SANITARY LINE.
  
 3C. OK
 4C. OK
 5C. OK
  
 6C. SHT P502 PLEASE INDICATE THE LOCATION OF THE WATER
 RISER DIAGRAMS FOR THE KITCHEN AREA, THE WATER HEATER
 ROOM, THE GUEST LAUNDRY ROOMS, THE LAUNDRY ROOM, THE
 EMPLOYEE TOILET ROOM AND ANY OTHER COMMON AREA NOT
 SUBMITTED. SHOW ALL PIPE SIZES, VALVES, WATER HAMMER
 ARRESTORS ETC. SECTION 106.3.5.1.3.--RISER 1/502
 INDICATES A MOP SINK AND A SHOWER ON ONE PORTION AND A
 WASH MACHINE AND WATER CLOSET ON THE OTHER PORTION.
 ALSO IT SHOWS FIXTURES ON ALL 5 FLOORS. PLEASE CLARIFY
 AS THERE ARE NOT FIXTURES ON THE FIRST FLOOR AND THESE
 FIXTURES ARE NOT SHOWN ON THE FLOOR PLAN.--RISER
 2/502 SHOWS WASH MACHINES AND WATER CLOSETS ON ALL 5
 FLOORS. PLEASE CLARIFY.--RISER 3/502 SHOWS MOP
 SINKS ON THE LAV RISER. PLEASE CLARIFY.--RISER
 4/502 SHOWS SHOWERS ON THE SINK RISER. PLEASE CLARIFY.
 --RISER 4/502 SHOW FIXTURE 4A WHICH IS NOT SHOWN ON
 THE FIXTURE SCHEDULE. PLEASE CLARIFY.--RISER 5/502
 SHOWS FIXTURE 9A WHICH IS NOT INDICATED ON THE FIXTURE
 SCHEDULE. PLEASE CLARIFY.--RISER 6/502 NONE OF THE
 FIXTURES ON THE RISE REFLECT WHAT IS SHOWN ON THE FLOOR
 PLAN. PLEASE CLARIFY.--PLEASE MAKE SURE ALL RISERS
 REFLECT THE FLOOR PLAN AND REFLECT THE FIXTURES SHOWN
 ON THE FLOOR PLAN. SECTION 106.1.1.--TYPICAL WATER
 RISER DIAGRAMS ARE NOT TYPICAL ON THE FLOOR PLAN.
 DIFFERENT FIXTURES ON THE FLOOR REQUIRE DIFFERENT RISER
 DIAGRAMS THAT REFLECT THE FLOOR PLAN. PLEASE SUBMIT
 RISER DIAGRAMS THAT REFLECT THE FLOOR PLAN.
 ********RESPONSE NOTED, BUT THE WATER HAMMER ARRESTORS
 ARE NOT SHOWN ON THE WATER RISER DIAGRAMS. RISER 5/502
 NOW SHOWS P-7, (BREAK SINK), AND P-8, (LAUNDRY ROOM
 SINK), WHERE AS THE FLOOR PLAN SHOWS SHOWER/TUB.ALSO
 ON SANITARY RISER 48 FIRST FLOOR SHOWS TWO FIXTURES, P4
 & P-13, BUT ON THE FLOOR PLAN NO FIXTURES ARE SHOWN.
 PLEASE CORRELATE. SANITARY RISER 48 APPEARS TO RUN
 THROUGH THE BASE CABINET ON THE FIRST FLOOR. PLEASE
 CLARIFY.
  
 7C. SHT P503 SANITARY AND VENT RISER SHOWS NO VENT
 PIPING & DOES NOT RELFECT THE FLOOR PLAN WHERE MANY OF
 THE BRANCH LINES CONNECT TO THE BUILDING SANITARY DRAIN
 LINE. SHOW ALL PIPING ON THE RISER DIAGRAM THAT
 REFLECTS THE FLOOR PLAN. SHOW THE PIPING FROM THE
 BUILDING DRAIN TO THE RISER DIAGRAM SHOWING ALL OFFSETS
 AND SHOW ALL FIRST FLOOR FIXTURES ON THE RISER DIAGRAM
 INCLUDING ALL PIPING FROM THE BUILDING SANT. DRAIN TO
 THE FIXTURES. SHOW ALL CLEANOUTS REQUIRED BY SECTION
 708 & ALL SUBSECTIONS. SECTION 106.1.1.
 ********RESPONSE NOTED, BUT NO BRANCH LINE SHOWN FOR
 SANT. RISERS 13,14,16,17 & 18.
  
 8C. OK
 9C. OK
  
 10C. SHT P505 THE FLOOR PLAN SHOWS SOME ROOF DRAINS
 CONNECTING IN THE BUILDING STORM DRAIN PRIOR TO EXITING
 THE BUILDING. PLEASE SUBMIT STORM ISOMETRIC RISER
 DIAGRAMS FOR ALL RISER DIAGRAMS THAT ARE NOT TYPICAL.
 SHOW ALL PIPE SIZES, OFFSETS, CLEANOUTS REQUIRED BY
 SECTION 1101.8 AND INDICATE THE SQUARE FOOTAGE AS IT
 ACCUMULATES IN THE SYSTEM.
 ********RESPONSE NOTED, COMMENT NOT ADDRESSED.
  
 **********NEW COMMENT**********
  
 1D. SHTS P504 & P505 THE WATER RISER DIAGRAMS DO NOT
 REFLECT THE FLOOR PLAN. THE FLOOR PLAN SHOWS THE WATER
 PIPING FOR THE MAINS IN THE CEILING OF THE FIRST FLOOR,
 BUT THE RISER DIAGRAMS SHOW THE WATER RISERS CONNECTING
 TO THE MAIN UNDERGROUND. PLEASE CORRELATE. SECTIONS
 106.1.1 & 604.
  
 2D. PER FS 553.80(2)(B) WITH RESPECT TO THE DESIGN
 PROFESSIONAL AND WITH RESPECT TO REPEAT COMMENTS FOR
 CODE COMPLIANCE A FEE OF $99,000 IS DUE BEFORE
 RESUBMITTING THE PLANS FOR REVIEW. THIS IS NOT ACCESSED
 TO THE OWNER OR CONTRACTOR. ONE SET OF PLANS IS BEING
 RETAINED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-11-21 Cont ID  
Sent By kstevens Date 2007-11-21 Time 16:32 Rev Time 0.00
Received By kstevens Date 2007-11-21 Time 16:32 Sent To  
Notes
2007-11-21 17:25:59 
 DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2001 BUILDING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
  
 ******FROM PREVIOUS REVIEW: 3RD REVIEW:
  
 1. SHTS G-000 THRU G-003 THE FIRM LICENSE NUMBER AND
 THE PRINTED NAME OF THE PERSON SEALING THE DOCUMENT ARE
 REQUIRED ON EACH SHEET. FAC 61G1-16.004(2)(6) & FS
 481.219, 481.2055.-THE EMBOSSED SEAL SHALL IMPRESS
 ALL INFORMATION REQUIRED BY FAC 61G1-16.002 & FS
 481.2055. NOT ALL INFORMATION REQUIRED IS IMPRESSED ON
 EACH SHEET. PLEASE MAKE SURE THE REQUIRED INFORMATION
 IS IN THE TITLE BLOCK AND RESEAL THE PLANS MAKING SURE
 ALL INFORMATION IS IMPRESSED & LEGIBLE WHEN SEALING THE
 PLANS.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. FIRM
 LICENSE FOR PFVS ARCHITECTS INC. IS NOT INDICATED IN
 THE TITLE BLOCK NOR HAS THE INFORMATION REQUIRED WHEN
 SEALING THE SHEETS BEEN ADDRESSED.
 ******RESPONSE NOTED, BUT THE TITLE BLOCK STILL
 INDICATES PFVS ARCHITECTS. ALL REFERENCE TO THE
 ARCHITECTURAL COMPANY SHALL BE DELETED FROM THE TITLE
 BLOCK OR A FIRM LICENSE NUMBER, (CERTIFICATE OF
 AUTHORIZATION), WILL BE REQUIRED.--ALSO THE SEAL
 BEING USED IS NOT APPROVED. PER FAC 61G1-16.002 THE
 SEAL SHALL BE APPROX. 2" IN DIAMETER. FS 481.2055.
  
 2.OK
  
 3. ALL STRUCTURAL SHEETS. THE ENGINEERS SHALL LEGIBLY
 INDICATE THEIR NAME, ADDRESS, AND LICENSE NUMBER ON
 EACH SHEET. IF PRACTICING THROUGH A DULY AUTHORIZED
 ENGINEERING BUSINESS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME & LICENSE NUMBER, AS WELL AS, THE NAME,
 ADDRESS, AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS ON EACH SHEET. FAC 61G15-23.002(2)
 & FS 471.025. THE BUSINESS NUMBER, (CERTIFICATE OF
 AUTHORIZATION), FOR PFVS ARCHITECTURE IS REQUIRED IN
 THE TITLE BLOCK AS WELL. FAC 61G1-16.004(2) & FS
 481.219, 481.2055.
 ****RESPONSE NOTED, BUT ENGINEERING CA# NOT INDICATED
 AS WELL AS THE REQUIREMENT FOR THE ARCHITECTURE,
 (BUSINESS NUMBER), HAS NOT BEEN ADDRESSED.
 ******RESPONSE NOTED, BUT PFVS ARCHITECTS IS STILL
 INDICATED IN THE TITLE BLOCK OF EACH SHEET. ALL
 REFERENCE TO THE ARCHITECTURAL COMPANY SHALL BE DELETED
 FROM THE TITLE BLOCK OR A FIRM LICENSE NUMBER,
 (CERTIFICATE OF AUTHORIZATION), WILL BE REQUIRED.
  
 4. OK
 5. OK
 6. OK
 7. OK
  
 8. SHT A-106 SUBMIT CALCULATIONS FOR THE PRIMARY AND
 SECONDARY ROOF DRAINS. SHOW THE AREA TO BE DRAINED FOR
 EACH ROOF DRAIN, AND INDICATE 1/2 THE AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS ADDED TO THAT AREA.
 ALSO INDICATE ALL AREAS FROM ROOF AREAS THAT DRAIN ONTO
 THE ROOF FROM ABOVE. SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS AND TABLES. INDICATE TOTAL AREA BEING
 DRAINED BY EACH DRAIN.
 ****RESPONSE NOTED, BUT NO CALCULATION WERE FOUND.
 PLEASE SUBMIT THE CALCULATIONS REQUESTED.
 ******RESPONSE NOTED, BUT THE CALCULATIONS WERE NOT
 SUBMITTED. IS THE AREA FOR EACH ROOF DRAIN EXACTLY THE
 SAME? ARE THE VERTICAL WALLS & PARAPETS THE SAME FOR
 EACH AREA? PLEASE SUBMIT THE CALCULATIONS FOR EACH AREA
 SHOWING THE INFORMATION REQUESTED.
  
 9. SHT A-401 TOILET ROOM 134, NO FIXTURES ARE SHOWN.
 PLEASE CLARIFY. SECTION 1106.1.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE WATER CLOSET IS LOCATED
 ON A WALL OPPOSITE OF THE GRAB BARS AND DOES NOT
 REFLECT THE FIXTURE LAYONT ON SHT P101.--THE DOOR
 SHALL NOT SWING INTO THE CLEAR FLOOR SPACE REQUIRED FOR
 THE LAV PER SECTION 11-4.22.2(1). THE DOOR IS SHOWN
 SWINGING THRU THE CLEAR FLOOR SPACE.
  
 10. SHTS A-411, & A-412 SHOW THE CLEAR FLOOR SPACE FOR
 EACH FIXTURE AND SHOW EACH FIXTURE IN THE ACCESSIBLE
 UNITS. SECTIONS 11-4.16.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE CLEAR FLOOR SPACE IS NOT
 SHOWN FOR THE SHOWER, THE TUB, NOR THE SINK.
  
 11. OK
  
 12 SHT A-801 ELEVATION 15. THE SINK SHALL COMPLY WITH
 SECTION 11-4.24 AND ALL SUBSECTIONS. A FORWARD APPROACH
 CLEAR FLOOR SPACE IS REQUIRED AND SHALL EXTEND A
 MAXIMUM OF 19" UNDERNEATH THE SINK. CABINET DOORS ARE
 NOT APPROVED IN THE CLEAR FLOORSPACE AND ARE NOT TO
 BE INSTALLED.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT COMPLIANCE FOR THE FOLLOWING
 IS NOT SHOWN:
 A. 11-4.24.3 KNEE CLEARANCE
 B. 11-4.24.4 SINK DEPTH
 C. 11-4.24.5 CLEAR FLOOR SPACE
 D. 11-4.24.7 FAUCET TYPE
  
 13. SHTS A-802 APPLICABLE ELEVATIONS 1 THRU 13,A-803
 APPLICABLE ELEVATIONS 1- THRU 14, A-804 APPLICABLE
 ELEVATIONS 1 THRU 15, SHALL COMPLY WITH SECTIONS
 11-4.16, 11-4.18, 11-4.19, 11-4.20, 11-4.21 & 11-4.22
 AND ALL SUBSECTIONS. PLEASE INDICATE ON ELEVATIONS.
 ALSO SHOW ALL W/C'S TO BE 18" OFF THE WALL TO THE
 CENTERLINE OF THE FIXTURE, & SHOW ALL LAVS TO BE MIN.
 15" OFF THE WALL TO THE CENTERLINE OF THE FIXTURE WHERE
 THE FIXTURES ARE ADJACENT TO THE WALLS. FIGURES 11-28
 AND 11-32.
 ****NO RESPONSE. SHOW THE FOLLOWING:
 SHT A-802..
 ___FOR W/C'S:
 A. 11-4.16.2 OK
 ___FOR URINALS:
 A. 11-4.18.3 CLEAR FLOOR SPACE
 ******NOT ADDRESSED
 B. 11-4.18.4 FLUSH CONTROLS
 ******NOT ADDRESSED
 ____FOR LAVS:
 A. 11-4.19.2 HEIGHT & CLEARANCES (CLEARANCES)
 ******NOT ADDRESSED
 B. 11-4.19.4 OK
 C. 11-4.19.5 FAUCETS
 ******NOT ADDRESSED
 SHT A-803
 ___FOR W/C'S:
 A. 11-4.16.2 OK
 ___FOR LAVS:
 A. 11-4.19.3 OK
 B. 11-4.19.5 FAUCETS
 ******NOT ADDRESSED
 ___FOR TUBS:
 A. 11-4.20.2 CLEAR FLOOR SPACE
 ******NOT ADDRESSED
 B. 11-4.20.5 CONTROLS
 ******NOT ADDRESSED
 ___FOR TOILET ROOMS
 A. 11-4.22.3 OK
 OK
  
 14. SHT A-806 DETAIL 5 INDICATE THE FOLLOWING:
 A. 11-4.24.4 OK
 B. 11-4.24.5 CLEAR FLOOR SPACE
 ******NOT ADDRESSED
 C. 11-4.24.7 FAUCETS (TYPE)
 ******NOT ADDRESSED
 ****NO RESPONSE, NOT ADDRESSED
 ******RESPONSE NOTED, NOT COMPLETLY ADDRESSED
  
  
 15. N/A
 16. SHT A-812 DETAIL 1, INDICATES A WATER WALL FEATURE.
 MORE INFORMATION IS REQUIRED. WILL THERE BE A WATER
 SUPPLY LINE CONNECTED TO THE WATER FEATURE? WILL THE
 WATER FEATURE CONNECT TO THE SANITARY DRAINAGE SYSTEM.
 PLEASE CLARIFY.SECTION 106.1.1.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT PLEASE EXPLAIN KEYNOTES #47 &
 #48 ON SHT P101 AND RELATED WATER PIPING THAT INDICATES
 WATER TO THE WATER WALL FEATURE? BACKFLOW PREVENTION IS
 REQUIRED FOR THE WATER SUPPLY. PLEASE INDICATE METHOD.
 SECTION 608.--PLEASE INDICATE THE DRAINAGE PIPING
 ON THE FLOOR PLAN AND MAKE SURE IT IS REFLECTED IN AN
 ISOMETRIC RISER DIAGRAM.
  
 17. SHT A-813 DETAIL 4, SHOW THE FOLLOWING:
 A. 11-4.19.2 CLEARANCE
 ******RESPONSE NOTED, NOT CORRECT 29" REQUIRED
 B. 11-4.19.5 FAUCETS
 ******RESPONSE NOTED, FAUCET TYPE NOT ADDRESSED ****NO
 RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, COMMENTS NOT ADDRESSED
 CORRECTLY.
  
 18. OK
 19. OK
 20. OK
 21. OK
  
 22. SHT P101 SOME RISERS AND SOME FIRST FLOOR FIXTURES
 SHOW NO PIPING OR BRANCH LINES CONNECTING THE
 RISERS/FIXTURES TO THE BUILDING DRAIN. PLEASE CLARIFY.
 SECTION 106.1.1.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THERE IS STILL SANITARY
 PIPING NOT SHOWN. THE PIPING FOR ALL SYSTEMS IS NOT
 VERY LEGIBLE. THE PIPING IS NOT SHOWN TO MANY RISERS,
 AND IN MANY CASES THE PIPING IS HARD TO FOLLOW BECAUSE
 IS IS COVERED BY DARKER/BOLDER LINES OR OTHER SYSTEMS.
 IN SOME CASES IT IS NOT CLEAR WHAT SYSTEM CONNECTS TO
 WHAT RISER. SOME FIXTURES HAVE NO WATER PIPING SHOWN.
 SEE NEW COMMENTS FOR SHT P101 AT THE END OF THESE
 COMMENTS.
  
 23. OK
 24. OK
 25. OK
 26. OK
 27. OK
  
 28. SHT P401 FIRE PUMP ROOM, THE FLOOR DRAINS ARE NOT
 VENTED. SECTION 901.2.1. THE FLOOR PLAN DOES NOT
 REFLECT THE PIPING LAYOUT ON SHT P101. PLEASE CORRELATE
 THE FLOOR PLANS. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THE PLANS NOW SHOW A 3" VENT
 THAT APPEARS TO BE A DRY HORIZONTAL VENT. THIS IS NOT
 SHOWN ON THE SANITARY RISER DIAGRAM SO ITS NOT CLEAR.
 PLEASE INDICATE ALL PIPING ON THE HORIZONTAL PIPING
 ISOMETRIC FOR ALL PIPING UP TO ALL RISERS AND
 FIXTURES/FIXTURE GROUPS ON THE FIRST FLOOR TO REFLECT
 THE FLOOR PLAN.
 ******RESPONSE NOTED, BUT THIS SANITARY & VENT PIPING
 IS NOT SHOWN ON ANY ISOMETRIC RISE DIAGRAM SHOWING PIPE
 SIZES, ETC.
  
 29. OK
 30. OK
 31. OK
  
 32. SUBMIT A SANITARY HORIZONTAL BUILDING DRAIN
 ISOMETRIC RISER DIAGRAM THAT REFLECT THE FLOOR PLAN.
 SHOW ALL PIPE SIZES, RISER LOCATIONS, TRAPS AND DFU'S
 AS THEY ACCUMULATE IN THE SYSTEM. SECTION 106.3.5.1.3.
 -SHOW ALL THE FIRST FLOOR FIXTURES NOT CONNECTED TO A
 VERTICAL RISER ON THE HORIZONTAL RISER DIAGRAM. (SEE
 BREAK ROOM, FOOD PREP, LAUNDRY ROOM, TOILET ROOMS, PUMP
 ROOM ETC.).
 ****RESPONSE NOTED, BUT NOT ALL FIXTURES OR FIXTURES
 GROUPS FOR THE FIRST FLOOR ARE SHOWN ON THE HORIZONTAL
 SANITARY RISER ISOMETRIC DIAGRAM. THE 1ST FLOOR IS
 WHERE THE BRANCH LINE CONNECTS ALL RISERS, TOILET
 ROOMS, PUMP ROOMS, LAUNDRY, FOOD PREP ROOM, BREAK ROOM,
 VENDING, VENTING ETC. AND ALL THIS PIPING SHALL BE
 SHOWN CONNECTING TO THE HORIZONTAL ISOMETRIC.
 ******RESPONSE NOTED, BUT THE COMMENT IS STILL NOT
 ADDRESSED.
  
 32. SUBMIT A HORIZONTAL BUILDING WATER ISOMETRIC RISER
 DIAGRAM. SHOW ALL PIPE SIZES, VALVES, WATER HAMMER
 ARRESTORS, (REQUIRED BY SECTION 604.9 FOR ICE MAKERS,
 WASH MACHINES, AND DISHWASHERS).
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THERE IS STILL NO WATER
 ISOMETRICS FOR THE EMPLOYEE TOILET ROOM, THE WASH
 MACHINE ROOM, THE FOOD PREP AREA, THE WATER HEATER
 ROOM, GUEST LAUNDRY, MOP SINK/WASH MACHINE. RISER SHALL
 INDICATE THE PIPING AS IT ENTERS THE BUILDING SHOWING
 THE FULL OPEN VALVE REQUIRED BY SECTION 606.1(2) AND AT
 THE BASE OF EACH RISER DIAGRAM REQUIRED BY SECTION
 606.1(3).
  
 33 SUBMIT A HORIZONTAL BUILDING CONDENSATE ISOMETRIC
 RISER DIAGRAM AND VERTICAL RISER DIAGRAMS. SHOW ALL
 PIPE SIZES AND INDICATE THE TERMINATION POINT.
 ****RESPONSE NOTED, BUT IF THE CONDENSATE IS CONNECTING
 TO THE STORM LINE, A RELIEF VENT WILL BE REQUIRED AS
 THE CONDENSATE LINE EXITS THE BUILDING. PLEASE SHOW THE
 RELIEF VENT AND THE TERMINATION POINT ON THE RISER
 DIAGRAM.
 ******RESPONSE NOTED, BUT PLEASE EXPLAIN "TO SPILL TO
 GRADE". THE CONDENSATE SHALL NOT DRAIN ON TO THE
 SIDEWALK, PARKING LOT, STREET, ALLEY OR ANY PLACE WHERE
 IS CAN CREATE A HAZARD OR NUISANCE.SECTION M307.2.1.
  
 34. INDICATE A NUMBER DESIGNATION FOR EACH RISER
 INCLUDING ALL SANT., WATER, STORM, CONDENSATE. (EXAMPLE
 SANT-1, SANT-2, RWL-1, RWL-2, CON-1, CON-2, W-1, W-2
 ETC.). THIS WILL AID IN TRACKING ALL RISERS FROM THE
 UNDERGROUND PIPING THROUGH THE ROOF. SECTIONS
 106.3.5.1.3 & SECTION 106.1.1.--INDICATE WHICH
 RISER IS TYPICAL OF WHICH RISER ISOMETRIC DIAGRAM.
 (EXAMPLE SANT-1 SANT-4 TYPICAL OF DETAIL 4 SHT P401) --
 INDICATE ROOM NUMBER EACH RISER CAN BE LOCATED.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED BY HAVING
 MULTIPLE RISERS WITH THE SAME DESIGNATION, SUCH AS
 RISER 2 OR RISER 8. ALL RISER NUMBERS SHALL BE SHOWN ON
 THE HORIZONTAL ISOMETRIC AND THE FLOOR PLANS OF EACH
 FLOOR.
 ******RESPONSE NOTED, BUT THE RISERS ARE NOT TYPICAL IF
 THEY HAVE DIFFERENT FIXTURES. SOME FLOOR PLANS SHOW
 TUBS BACK TO BACK, OTHER FLOOR PLANS SHOW TUB & SHOWERS
 BACK TO BACK. WHERE AS OTHER FLOOR PLANS SHOW SHOWERS
 BACK TO BACK. OTHER RISERS SHOW FIXTURES ON ALL 5
 FLOORS BUT ONLY HAVE FIXTURES ON 4 FLOORS AS THE FIRST
 FLOOR DOES NOT HAVE A SUITE. EACH RISER SHALL REFLECT
 THE FIXTURES SHOWN ON THE FLOOR PLAN FOR EACH FLOOR.
  
 35. ROUTE PLANS TO THE DEPT. OF BUSINESS REGULATION,
 HOTEL & RESTURANT DIVISION FOR REVIEW PRIOR TO
 RESUBMITTING TO THE CITY FOR REVIEW. A MINIMUM OF TWO
 SETS OF PLANS, STAMPED BY DBPR AND TWO PAGE
 "WORKSHEETS" ATTACHED TO PLAN ARE REQUIRED. SECTION
 102.2.1.
 ****RESPONSE NOTED, BUT "REVIEWED, STAMPED" PLANS AND
 ATTACHED "TWO PAGE WORKSHEET" SHALL BE REQUIRED FOR
 EACH SET OF PLANS AT THE TIME OF RESUBMITTING FOR
 REVIEW TO THE CITY.
 ******RESPONSE NOTED, BUT THE TWO PAGE "SPECIFICATION
 WORKSHEETS" FOR SPRINGHILL HAS BEEN ATTACHED TO THE
 HOMEWOOD PLANS AND THE HOMEWOOD WORKSHEETS HAS BEEN
 ATTACHED TO THE SPRINGHILL PLANS.
  
 36. SHT 602 DETAIL 1 SHOWS A GREASE TRAP INSIDE THE
 FOOD PREP AREA. THIS IS NOT APPROVED PER SECTION
 90-124(7)(B) OF THE MUNICIPAL CODE. A MINIMUM 750 GAL.
 INTERCEPTOR IS REQUIRED. PLEASE CONTACT LMASSON,
 ENVIRONMENTAL COMPLIANCE MANAGER FOR SIZING OF THE
 GREASE INTERCEPTOR. CONTACT HER BY PHONE (561)
 822-2271, FAX (561) 822-2279, OR E-MAIL
 [email protected].
 ****RESPONSE NOTED, NO COMMENT FROM ENVIRONMENTAL AS OF
 YET.
 ******RESPONSE NOTED, BUT STILL AWAITING CONFIRMATION
 OF INTERCEPTOR SIZE FROM ENVIRONMENTAL COMPLIANCE. I
 HAVE SENT AN E-MAIL AND WILL PURSUE CONFIRMATION ON
 THIS END.
  
 37. OK
  
 **********NEW COMMENTS**********
  
 1B. OK
 2B. OK
  
 3B. SUBMIT ISOMETRIC STORM RISER DIAGRAMS FOR EACH RWL.
 SHOW ALL PIPE SIZES, OFFSETS, SQUARE FOOTAGE & INDICATE
 THE TERMINATION POINT FOR EACH ROOF DRAIN. IF THERE ARE
 TYPICAL RWL'S, INDICATE THE ROOF DRAINS THAT ARE
 TYPICAL OF WHICH RWL. EACH RWL AND ROOF DRAIN SHALL BE
 NUMBERED SUCH AS RWL-1, RWL-2 AND RD-1, RD-2 AND SHALL
 BE INDICATED ON EACH FLOOR PLAN SO AS TO TRACK EACH
 RWL/RD THROUGH THE BUILDING. TABLE 1106.3 AND SECTION
 106.1.3.5.1.3(7)(13).
 ******RESPONSE NOTED, BUT THE RISERS ARE NOT COMPLETE.
 SHOW THE RISERS FROM THE ROOF DRAIN THRU THE BUILDING
 STORM DRAIN PIPING AND EXITING THE BUILDING SHOWING ALL
 PIPE SIZE, CLEANOUTS REQUIRED BY SECTION 1101.8,
 OFFSETS AND IF RISERS COMBINE IN THE BUILDING SHOW THIS
 ON THE RISER ALSO. THE SQUARE FOOTAGE AND PIPE SIZE
 WILL BE VERIFIDE WHEN THE ROOF DRAINAGE CALCULATIONS
 HAVE BEEN SUBMITTED AND VERIFIED.
  
 4B. OK
  
 *****NEW COMMENTS 3RD REVIEW*****
  
 1C. SHT P101 PLUMBING KEYNOTES, 18, 30 & 31 WERE NOT
 FOUND. PLEASE CLARIFY.--KEYNOTES 41 & 43 STATE "NOT
 USED" BUT WERE FOUND ON THE FLOOR PLAN. PLEASE CLARIFY.
 --KEYNOTE 14 IS SHOWN CONNECTING TO THE BUILDING
 SANT. DRAIN. PLEASE CLARIFY.--KEYNOTE 20, ONE
 APPEARS TO BE CONNECTING TO STORM DRAIN LINE AND ONE
 APPEARS TO BE SHOWN TO A HOT WATER LINE. PLEASE
 CLARIFY.--KEYNOTE 25 STILL SHOWS 7" W.C. FOR THE
 GAS PRESSURE. RISER CHANGED TO 12" - 14" W.C. PLEASE
 CORRELATE.--KEYNOTE 47 INDICATES WATER SUPPLY TO
 WATER WALL. BACKFLOW PREVENTION IS REQUIRED. PLEASE
 INDICATE METHOD. (A VACUUM BREAKER AT THE HIGHES POINT
 WILL SUFFICE).SECTION 608.--KEYNOTE 1 INDICATES
 SANT./HOT/COLD BUT MOST KEYNOTES ON THE FLOOR PLAN ONLY
 SHOW THE HOT & COLD WATER BUT NO SANITARY. CLARIFY. --
 KEYNOTE 9 IS SHOWING THE WATER SUPPLY TO AN ICE MACHINE
 CONNECTING TO A 2-1/2" FIRE LINE IN THE STAILWELL. THE
 FIRE LINE IS NOT CONSIDERED A POTABLE WATER LINE, AND
 ONLY THE PIPING REQUIRED FOR THE FIGHTING OF FIRES
 SHALL BE LOCATED IN THE STAIRWELLS. NFPA-101 SECTION
 7.1.3.2.1(6). PLEASE DELETE THE CONNECTION AND SHOW THE
 ICE MAKER CONNECTING TO THE POTABLE WATER SYSTEM.--
 REFERENCES TO SHT P402 & P403 ARE SHOWN WHEN CALLING
 OUT ENLARGED SECTIONS. SHEETS P402 & P403 HAVE NOT BEEN
 SUBMITTED. PLEASE CLARIFY.--KEYNOTE 48 DOES NOT
 SHOW SANITARY PIPING.PLEASE CLARIFY.--KEYNOTE 40
 & 26 IN THE GAS SYSTEM. PLEASE INDICATE WHERE THE
 CONTINUANCE OF THE GAS LINE AFTER KEYNOTES IS LOCATED.
 --KEYNOTE 21, (SANT.),APPEARS TO CONNECT TO THE GAS
 SYSTEM. PLEASE CLARIFY.--KEYNOTE 22 SHOWS NO
 SANITARY. PLEASE CLARIFY.--KEYNOTE 4 AT SOME SHOW
 NO HOT WATER SUPPLY. PLEASE CLARIFY.--KEYNOTE 3 AT
 ONE 1/P402 SHOWS NOT WATER SUPPLY LINES. PLEASE
 CLARIFY. --STORM DRAIN IS SHOWN ENTERING THE
 BUILDING ON THE EAST SIDE OF THE BUILDING AND EXITING
 BY THE PORTE COCHERE. PLEASE INDICATED WHERE THE STORM
 LINE CONTINUES EAST OF THE BUILDING AND INDICATE WHERE
 THE RISER DIAGRAM IS FOR THIS STORM PIPING.--A
 WATER LINE IS SHOWN CONNECTING TO A 3/4" NFWH. PLEASE
 INDICATE WHERE THIS LINE CONTIUES AND INDICATE WHERE ON
 THE RISER DIAGRAM THIS IS SHOWN.--KEYNOTES 20, 21 &
 22 EAST OF THE PUBLIC TOILET ROOMS DO NOT SHOW SANITARY
 CONNTECTING TO THE RISERS. PLEASE CLARIFY.--4" SAN
 A/C IS NOT INDICATED ON THE PLUMBING LEGEND ON SHT
 P601. PLEASE INDICATE WHAT THE A/C STANDS FOR. PLEASE
 SHOW ON THE PLUMBING LEGEND.--THE 4" SAN A/C ABOVE
 THE KITCHEN AREA DOES NOT APPEAR TO CONNECT TO THE
 SANITARY BUILDING DRAIN. PLEASE CLARIFY.--TWO WAY
 CLEANOUTS ARE REQUIRED AT THE ENTRANCE AND EXIT PIPING
 OF THE GREASE INTERCEPTOR AS WELL AS NEAR THE JUNCTION
 OF THE BUILDING DRAIN AND THE BUILDING SEWER AS THE
 PIPING EXITS THE BUILDING. WPB UTILITY STANDARD AND
 SECTION 708.3.5. (IF THE 2-WAY C/O'S ARE INSTALLED AT
 THE GREASE INTERCEPTOR THEY WILL SUFFICE FOR BOTH
 REQUIREMENTS). SECTION 106.1.1.
  
 2C. SHT P401 PLEASE SUBMIT RISER DIAGRAMS FOR THE
 SANITARY AND WATER PIPING IN DETAILS 1, 4, 5 & 6. FOR
 THE SANITARY SHOW ALL PIPE SIZES, TRAPS, & VENTS. FOR
 THE WATER SHOW ALL PIPE SIZES, VALVES, WATER HAMMER
 ARRESTORS ECT. SECTION 106.3.5.1.3.
  
 3C. SHT P401 DETAILS 2 & 3 SHOW TYPICAL BACK TO BACK &
 SINGLE TOILET PLUMBING. NOT ALL UNITS ARE TYPICAL AS
 SOME BACK TO BACK HAVE TUB/TUB OR TUB/SHOWER OR
 SHOWER/SHOWER. PLEASE SHOW ALL TYPE FLOOR PLANS.
 SECTION 106.1.2.
  
 4C. SHT P501 SHOW TYPICAL RISER DIAGRAMS. NOT ALL UNITS
 ARE TYPICAL AND A RISER IS REQUIRED FOR EACH FLOOR
 PLAN. SECTION 106.3.5.1.3.
  
 5C. SHT P501 RISER DIAGRAM 9/501 IS NOT SHOWN ON THE
 FIRST FLOOR PLAN. PLEASE INDICATE WHERE THE VENDING
 MACHINE FLOOR DRAIN ARE LOCATED. PLEASE INDICATE IF
 THERE IS AN ICE MACHINE ON EACH FLOOR BY THE VENDING
 MACHINES. FLOOR DRAINS ARE NOT APPROVED INDIRECT WASTE
 RECPTORS AND FLOOR SINKS OR HUB WILL BE REQUIRED TO
 DRAIN THE ICE MACHINES. SECTIONS 802.3 & 802.3.2.
 PLEASE CLARIFY.
  
 6C. SHT P502 PLEASE INDICATE THE LOCATION OF THE WATER
 RISER DIAGRAMS FOR THE KITCHEN AREA, THE WATER HEATER
 ROOM, THE GUEST LAUNDRY ROOMS, THE LAUNDRY ROOM, THE
 EMPLOYEE TOILET ROOM AND ANY OTHER COMMON AREA NOT
 SUBMITTED. SHOW ALL PIPE SIZES, VALVES, WATER HAMMER
 ARRESTORS ETC. SECTION 106.3.5.1.3.--RISER 1/502
 INDICATES A MOP SINK AND A SHOWER ON ONE PORTION AND A
 WASH MACHINE AND WATER CLOSET ON THE OTHER PORTION.
 ALSO IT SHOWS FIXTURES ON ALL 5 FLOORS. PLEASE CLARIFY
 AS THERE ARE NOT FIXTURES ON THE FIRST FLOOR AND THESE
 FIXTURES ARE NOT SHOWN ON THE FLOOR PLAN.--RISER
 2/502 SHOWS WASH MACHINES AND WATER CLOSETS ON ALL 5
 FLOORS. PLEASE CLARIFY.--RISER 3/502 SHOWS MOP
 SINKS ON THE LAV RISER. PLEASE CLARIFY.--RISER
 4/502 SHOWS SHOWERS ON THE SINK RISER. PLEASE CLARIFY.
 --RISER 4/502 SHOW FIXTURE 4A WHICH IS NOT SHOWN ON
 THE FIXTURE SCHEDULE. PLEASE CLARIFY.--RISER 5/502
 SHOWS FIXTURE 9A WHICH IS NOT INDICATED ON THE FIXTURE
 SCHEDULE. PLEASE CLARIFY.--RISER 6/502 NONE OF THE
 FIXTURES ON THE RISE REFLECT WHAT IS SHOWN ON THE FLOOR
 PLAN. PLEASE CLARIFY.--PLEASE MAKE SURE ALL RISERS
 REFLECT THE FLOOR PLAN AND REFLECT THE FIXTURES SHOWN
 ON THE FLOOR PLAN. SECTION 106.1.1.--TYPICAL WATER
 RISER DIAGRAMS ARE NOT TYPICAL ON THE FLOOR PLAN.
 DIFFERENT FIXTURES ON THE FLOOR REQUIRE DIFFERENT RISER
 DIAGRAMS THAT REFLECT THE FLOOR PLAN. PLEASE SUBMIT
 RISER DIAGRAMS THAT REFLECT THE FLOOR PLAN.
  
 7C. SHT P503 SANITARY AND VENT RISER SHOWS NO VENT
 PIPING & DOES NOT RELFECT THE FLOOR PLAN WHERE MANY OF
 THE BRANCH LINES CONNECT TO THE BUILDING SANITARY DRAIN
 LINE. SHOW ALL PIPING ON THE RISER DIAGRAM THAT
 REFLECTS THE FLOOR PLAN. SHOW THE PIPING FROM THE
 BUILDING DRAIN TO THE RISER DIAGRAM SHOWING ALL OFFSETS
 AND SHOW ALL FIRST FLOOR FIXTURES ON THE RISER DIAGRAM
 INCLUDING ALL PIPING FROM THE BUILDING SANT. DRAIN TO
 THE FIXTURES. SHOW ALL CLEANOUTS REQUIRED BY SECTION
 708 & ALL SUBSECTIONS. SECTION 106.1.1.
  
 8C. SHT P504 HOT & COLD WATER RISER DIAGRAM. SHOW THE
 PIPING FROM THE WATER MAINS TO EACH FIXTURE ON THE
 FIRST FLOOR AND TO EACH RISER. SHOW ALL PIPE SIZES,
 OFFSETS, VALVES AND WATER HAMMER ARRESTORS. SECTIONS
 604.9, 606 & TABLES 603.1, 604.3 & 604.5.
  
 9C. SHT P504 REFERES TO SHT P501 FOR WATER RISERS. SHT
 P501 ONLY HAS WASTE AND VENT RISERS. PLEASE CLARIFY. --
 PLEASE INDICATE WHERE THE WATER ISOMETRIC RISER
 DIAGRAMS FOR THE EMPLOYEE TOILET ROOM, THE LAUNDRY
 ROOM, THE WATER HEATER ROOM, THE GUEST LAUNDRY ROOM,
 THE KITCHEN AND ANY OTHER AREA THAT HAS HOT & COLD
 WATER PIPING THAT IS NOT SHOWN BY THE WATER ISOMETRIC
 RISER DIAGRAMS. SECTION 106.3.5.1.3.
  
 10C. SHT P505 THE FLOOR PLAN SHOWS SOME ROOF DRAINS
 CONNECTING IN THE BUILDING STORM DRAIN PRIOR TO EXITING
 THE BUILDING. PLEASE SUBMIT STORM ISOMETRIC RISER
 DIAGRAMS FOR ALL RISER DIAGRAMS THAT ARE NOT TYPICAL.
 SHOW ALL PIPE SIZES, OFFSETS, CLEANOUTS REQUIRED BY
 SECTION 1101.8 AND INDICATE THE SQUARE FOOTAGE AS IT
 ACCUMULATES IN THE SYSTEM.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 -PLEASE RESUBMIT ONE SET OF OLD SHEETS
 FOR COMPARISON.
  
 OK
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-04-16 Cont ID  
Sent By kstevens Date 2007-04-16 Time 12:53 Rev Time 0.00
Received By kstevens Date 2007-04-09 Time 18:58 Sent To  
Notes
2007-04-16 16:51:07 
 DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2001 BUILDING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
  
 1. SHTS G-000 THRU G-003 THE FIRM LICENSE NUMBER AND
 THE PRINTED NAME OF THE PERSON SEALING THE DOCUMENT ARE
 REQUIRED ON EACH SHEET. FAC 61G1-16.004(2)(6) & FS
 481.219, 481.2055.-THE EMBOSSED SEAL SHALL IMPRESS
 ALL INFORMATION REQUIRED BY FAC 61G1-16.002 & FS
 481.2055. NOT ALL INFORMATION REQUIRED IS IMPRESSED ON
 EACH SHEET. PLEASE MAKE SURE THE REQUIRED INFORMATION
 IS IN THE TITLE BLOCK AND RESEAL THE PLANS MAKING SURE
 ALL INFORMATION IS IMPRESSED & LEGIBLE WHEN SEALING THE
 PLANS.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. FIRM
 LICENSE FOR PFVS ARCHITECTS INC. IS NOT INDICATED IN
 THE TITLE BLOCK NOR HAS THE INFORMATION REQUIRED WHEN
 SEALING THE SHEETS BEEN ADDRESSED.
  
 2.OK
  
 3. ALL STRUCTURAL SHEETS. THE ENGINEERS SHALL LEGIBLY
 INDICATE THEIR NAME, ADDRESS, AND LICENSE NUMBER ON
 EACH SHEET. IF PRACTICING THROUGH A DULY AUTHORIZED
 ENGINEERING BUSINESS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME & LICENSE NUMBER, AS WELL AS, THE NAME,
 ADDRESS, AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS ON EACH SHEET. FAC 61G15-23.002(2)
 & FS 471.025. THE BUSINESS NUMBER, (CERTIFICATE OF
 AUTHORIZATION), FOR PFVS ARCHITECTURE IS REQUIRED IN
 THE TITLE BLOCK AS WELL. FAC 61G1-16.004(2) & FS
 481.219, 481.2055.
 ****RESPONSE NOTED, BUT ENGINEERING CA# NOT INDICATED
 AS WELL AS THE REQUIREMENT FOR THE ARCHITECTURE,
 (BUSINESS NUMBER), HAS NOT BEEN ADDRESSED.
  
 4. OK
  
 5. SHT G-000 GUESTROOM MATRIX INDICATES 2 HEARING
 IMPAIRED UNITS, STANDARD DOUBLE/DOUBLE, BUT THE FLOOR
 PLANS SHTS A-101 THRU A-105 ONLY SHOW 1 ON THE 4TH
 FLOOR. PLEASE CLARIFY & CORRELATE INFORMATION BETWEEN
 THE FLOOR PLANS & MATRIX. SECTION 106.1.1 & SECTION
 11-9.1.3.-PLEASE INDICATE WHICH ROOMS COMPLY WITH
 SECTION 11-9.1.3.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 6. SHT G-000 PLEASE CLARIFY THE DIFFERENCE BETWEEN A
 KING STANDARD, A KING CONNECTOR, A KING SUITE, AND
 INDICATE HOW THE ACCESSIBLE UNITS ARE DISPERSED AMONG
 THE VARIOUS CLASSES. ALSO PLEASE CLARIFY DIFFERENCE
 BETWEEN THE KING TYPE A, KING ALTERNATE, THE KING & THE
 KING ALT B AND INDICATE HOW THE ACCESSIBLE UNITS ARE
 DIAPERSED AMONG THE VARIOUS CLASSES.--PLEASE
 CLARIFY THE DIFFERENCE BETWEEN THE DOUBLE/DOUBLE
 STANDARD, THE DOUBLE/DOUBLE CONNECTOR STANDARD, THE
 DOUBLE/DOUBLE TYPE "A", THE DOUBLE/DOUBLE TYPE "B", THE
 DOUBLE/DOUBLE TYPE "C", THE DOUBLE/DOUBLE SUITE TYPE
 "A", THE DOUBLE/DOUBLE SUITE TYPE "B", AND THE
 DOUBLE/DOUBLE ALTERNATE.--THE DIFFERENCES SHALL BE
 CALLED OUT ON THE PLANS.-- OF CONCERN ALSO IS THE
 MATRIX DOES NOT MENTION THE PRESIDENTIAL SUITE SHOWN ON
 SHT A-411, AND IS INDICATED AS A DOUBLE/DOUBLE ON SHTS
 A-103, A-104 & A-105. PLEASE INDICATE WHY AN ACCESSIBLE
 UNIT FOR THE PRESIDENTIAL SUIT IS NOT PROVIDED.--
 ALSO OF CONCERN IS THE GUESTROOM MATRIX SHOWS
 ACCESSIBLE KING UNITS UNDER THE SECTION OF THE MATRIX
 INDICATED AS "KING GUESTROOMS", BUT UNDER THE SECTION
 INDICATED AS "DOUBLE/DOUBLE GUESTROOMS" THE ACCESSIBLE
 UNITS ARE "KING ACCESSIBLE UNITS". PLEASE CLARIFY.
 PLEASE COMPLY WITH SECTION 11-9.1.2.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.- 4TH FLOOR
 SHOWS 2 ACCESSIBLE KINGS & KING CONN., BUT THE MATRIX
 SHOWS 2 KING'S WITH ROLL-IN SHOWERS. PLEASE CLARIFY.-
 THE MATRIX INDICATES A KING-SUITE ON THE 4TH FLOOR, BUT
 THE FLOOR PLAN DOES NOT SHOW A KING SUITE. PLEASE
 INDICATE THE ROOM NUMBER & INDICATE WHY IT IS NOT
 ACCESSIBLE.
  
 7. SHT G-000 GUESTROOM MATRIX DOES NOT REFLECT THE
 FLOOR PLANS ON SHTS A-101 THRU A-105. THE MATRIX
 INDICATES A TOTAL OF 7 ACCESSIBLE UNITS, BUT THE FLOOR
 PLANS INDICATE A TOTAL OF 12 UNITS. PLEASE CORRELATE
 THE INFORMATION ON THE MATRIX AND THE FLOOR PLANS.
 SECTIONS 106.1.1 AND 11-9.1.2.
 ****RESPONSE NOTED, BUT THE FLOOR PLAN SHOWS 12
 ACCESSIBLE UNITS, WITH 4 UNITS FOR THE HEARING
 IMPAIRED. THE MATRIX, (NOW ON SHT G-002), SHOWS ONLY 8
 ACCESSIBLE UNITS, AND 5 UNITS FOR THE HEARING IMPAIRED
 ARE REQUIRED.-SECTION 11-9.2.3 INDICATES 2 UNITS
 REQUIRED. PLEASE INDICATE WHICH UNITS MEET THIS
 REQUIREMENT. (GIVE ROOM NUMBERS).
  
 8. SHT A-106 SUBMIT CALCULATIONS FOR THE PRIMARY AND
 SECONDARY ROOF DRAINS. SHOW THE AREA TO BE DRAINED FOR
 EACH ROOF DRAIN, AND INDICATE 1/2 THE AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS ADDED TO THAT AREA.
 ALSO INDICATE ALL AREAS FROM ROOF AREAS THAT DRAIN ONTO
 THE ROOF FROM ABOVE. SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS AND TABLES. INDICATE TOTAL AREA BEING
 DRAINED BY EACH DRAIN.
 ****RESPONSE NOTED, BUT NO CALCULATION WERE FOUND.
 PLEASE SUBMIT THE CALCULATIONS REQUESTED.
  
 9. SHT A-401 TOILET ROOM 134, NO FIXTURES ARE SHOWN.
 PLEASE CLARIFY. SECTION 1106.1.
 ****NO RESPONSE, NOT ADDRESSED.
  
 10. SHTS A-411, & A-412 SHOW THE CLEAR FLOOR SPACE FOR
 EACH FIXTURE AND SHOW EACH FIXTURE IN THE ACCESSIBLE
 UNITS. SECTIONS 11-4.16.
 ****NO RESPONSE, NOT ADDRESSED.
  
 11. SHT A-600 FINISH SCHEDULE FOR ROOMS 134, 150, & 151
 SHOW PAINT OR V.W.C. FOR THE WALLS. SECTION 1210.2
 CALLS FOR "SMOOTH, HARD, NONABSORBENT" SURFACES. PAINT
 AND V.W.C. DO NOT COMPLY WITH THE "HARD" REQUIREMENT.
 PLEASE COMPLY.
 ****NO RESPONSE, SHEET DELETED. PLEASE SUBMIT FINISH
 SCHEDULE SHOWING REQUIRED INFORMATION.
  
 12 SHT A-801 ELEVATION 15. THE SINK SHALL COMPLY WITH
 SECTION 11-4.24 AND ALL SUBSECTIONS. A FORWARD APPROACH
 CLEAR FLOOR SPACE IS REQUIRED AND SHALL EXTEND A
 MAXIMUM OF 19" UNDERNEATH THE SINK. CABINET DOORS ARE
 NOT APPROVED IN THE CLEAR FLOORSPACE AND ARE NOT TO
 BE INSTALLED.
 ****NO RESPONSE, NOT ADDRESSED.
  
 13. SHTS A-802 APPLICABLE ELEVATIONS 1 THRU 13,A-803
 APPLICABLE ELEVATIONS 1- THRU 14, A-804 APPLICABLE
 ELEVATIONS 1 THRU 15, SHALL COMPLY WITH SECTIONS
 11-4.16, 11-4.18, 11-4.19, 11-4.20, 11-4.21 & 11-4.22
 AND ALL SUBSECTIONS. PLEASE INDICATE ON ELEVATIONS.
 ALSO SHOW ALL W/C'S TO BE 18" OFF THE WALL TO THE
 CENTERLINE OF THE FIXTURE, & SHOW ALL LAVS TO BE MIN.
 15" OFF THE WALL TO THE CENTERLINE OF THE FIXTURE WHERE
 THE FIXTURES ARE ADJACENT TO THE WALLS. FIGURES 11-28
 AND 11-32.
 ****NO RESPONSE. SHOW THE FOLLOWING:
 SHT A-802..
 ___FOR W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 ___FOR URINALS:
 A. 11-4.18.3 CLEAR FLOOR SPACE
 B. 11-4.18.4 FLUSH CONTROLS
 ____FOR LAVS:
 A. 11-4.19.2 HEIGHT & CLEARANCES (CLEARANCES)
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
 SHT A-803
 ___FOR W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 ___FOR LAVS:
 A. 11-4.19.3 CLEAR FLOOR SPACE
 B. 11-4.19.5 FAUCETS
 ___FOR TUBS:
 A. 11-4.20.2 CLEAR FLOOR SPACE
 B. 11-4.20.5 CONTROLS
 ___FOR TOILET ROOMS
 A. 11-4.22.3 TURNING AREA (ALL ACCESSIBLE
 BATHROOMS).
 W/C'S NOT SHOWN AT 18" TO THE CENTERLINE OF THE FIXTURE
 OFF THE WALLS.
  
  
 14. SHT A-806 DETAIL 5 INDICATE THE FOLLOWING:
 A. 11-4.24.4 SINK DEPTH
 B. 11-4.24.5 CLEAR FLOOR SPACE
 C. 11-4.24.7 FAUCETS
 ****NO RESPONSE, NOT ADDRESSED
  
  
 15. N/A
  
 16. SHT A-812 DETAIL 1, INDICATES A WATER WALL FEATURE.
 MORE INFORMATION IS REQUIRED. WILL THERE BE A WATER
 SUPPLY LINE CONNECTED TO THE WATER FEATURE? WILL THE
 WATER FEATURE CONNECT TO THE SANITARY DRAINAGE SYSTEM.
 PLEASE CLARIFY.SECTION 106.1.1.
 ****NO RESPONSE, NOT ADDRESSED.
  
 17. SHT A-813 DETAIL 4, SHOW THE FOLLOWING:
 A. 11-4.19.2 CLEARANCE
 B. 11-4.19.5 FAUCETS
 ****NO RESPONSE, NOT ADDRESSED.
  
 18. OK
 19. OK
 20. OK
 21. OK
  
 22. SHT P101 SOME RISERS AND SOME FIRST FLOOR FIXTURES
 SHOW NO PIPING OR BRANCH LINES CONNECTING THE
 RISERS/FIXTURES TO THE BUILDING DRAIN. PLEASE CLARIFY.
 SECTION 106.1.1.
 ****NO RESPONSE, NOT ADDRESSED.
  
 23. OK
 24. OK
 25. OK
 26. OK
 27. OK
  
 28. SHT P401 FIRE PUMP ROOM, THE FLOOR DRAINS ARE NOT
 VENTED. SECTION 901.2.1. THE FLOOR PLAN DOES NOT
 REFLECT THE PIPING LAYOUT ON SHT P101. PLEASE CORRELATE
 THE FLOOR PLANS. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THE PLANS NOW SHOW A 3" VENT
 THAT APPEARS TO BE A DRY HORIZONTAL VENT. THIS IS NOT
 SHOWN ON THE SANITARY RISER DIAGRAM SO ITS NOT CLEAR.
 PLEASE INDICATE ALL PIPING ON THE HORIZONTAL PIPING
 ISOMETRIC FOR ALL PIPING UP TO ALL RISERS AND
 FIXTURES/FIXTURE GROUPS ON THE FIRST FLOOR TO REFLECT
 THE FLOOR PLAN.
  
 29. OK
 30. OK
 31. OK
  
 32. SUBMIT A SANITARY HORIZONTAL BUILDING DRAIN
 ISOMETRIC RISER DIAGRAM THAT REFLECT THE FLOOR PLAN.
 SHOW ALL PIPE SIZES, RISER LOCATIONS, TRAPS AND DFU'S
 AS THEY ACCUMULATE IN THE SYSTEM. SECTION 106.3.5.1.3.
 -SHOW ALL THE FIRST FLOOR FIXTURES NOT CONNECTED TO A
 VERTICAL RISER ON THE HORIZONTAL RISER DIAGRAM. (SEE
 BREAK ROOM, FOOD PREP, LAUNDRY ROOM, TOILET ROOMS, PUMP
 ROOM ETC.).
 ****RESPONSE NOTED, BUT NOT ALL FIXTURES OR FIXTURES
 GROUPS FOR THE FIRST FLOOR ARE SHOWN ON THE HORIZONTAL
 SANITARY RISER ISOMETRIC DIAGRAM. THE 1ST FLOOR IS
 WHERE THE BRANCH LINE CONNECTS ALL RISERS, TOILET
 ROOMS, PUMP ROOMS, LAUNDRY, FOOD PREP ROOM, BREAK ROOM,
 VENDING, VENTING ETC. AND ALL THIS PIPING SHALL BE
 SHOWN CONNECTING TO THE HORIZONTAL ISOMETRIC.
  
 32. SUBMIT A HORIZONTAL BUILDING WATER ISOMETRIC RISER
 DIAGRAM. SHOW ALL PIPE SIZES, VALVES, WATER HAMMER
 ARRESTORS, (REQUIRED BY SECTION 604.9 FOR ICE MAKERS,
 WASH MACHINES, AND DISHWASHERS).
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED.
  
 33 SUBMIT A HORIZONTAL BUILDING CONDENSATE ISOMETRIC
 RISER DIAGRAM AND VERTICAL RISER DIAGRAMS. SHOW ALL
 PIPE SIZES AND INDICATE THE TERMINATION POINT.
 ****RESPONSE NOTED, BUT IF THE CONDENSATE IS CONNECTING
 TO THE STORM LINE, A RELIEF VENT WILL BE REQUIRED AS
 THE CONDENSATE LINE EXITS THE BUILDING. PLEASE SHOW THE
 RELIEF VENT AND THE TERMINATION POINT ON THE RISER
 DIAGRAM.
  
 34. INDICATE A NUMBER DESIGNATION FOR EACH RISER
 INCLUDING ALL SANT., WATER, STORM, CONDENSATE. (EXAMPLE
 SANT-1, SANT-2, RWL-1, RWL-2, CON-1, CON-2, W-1, W-2
 ETC.). THIS WILL AID IN TRACKING ALL RISERS FROM THE
 UNDERGROUND PIPING THROUGH THE ROOF. SECTIONS
 106.3.5.1.3 & SECTION 106.1.1.--INDICATE WHICH
 RISER IS TYPICAL OF WHICH RISER ISOMETRIC DIAGRAM.
 (EXAMPLE SANT-1 SANT-4 TYPICAL OF DETAIL 4 SHT P401) --
 INDICATE ROOM NUMBER EACH RISER CAN BE LOCATED.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED BY HAVING
 MULTIPLE RISERS WITH THE SAME DESIGNATION, SUCH AS
 RISER 2 OR RISER 8. ALL RISER NUMBERS SHALL BE SHOWN ON
 THE HORIZONTAL ISOMETRIC AND THE FLOOR PLANS OF EACH
 FLOOR.
  
 35. ROUTE PLANS TO THE DEPT. OF BUSINESS REGULATION,
 HOTEL & RESTURANT DIVISION FOR REVIEW PRIOR TO
 RESUBMITTING TO THE CITY FOR REVIEW. A MINIMUM OF TWO
 SETS OF PLANS, STAMPED BY DBPR AND TWO PAGE
 "WORKSHEETS" ATTACHED TO PLAN ARE REQUIRED. SECTION
 102.2.1.
 ****RESPONSE NOTED, BUT "REVIEWED, STAMPED" PLANS AND
 ATTACHED "TWO PAGE WORKSHEET" SHALL BE REQUIRED FOR
 EACH SET OF PLANS AT THE TIME OF RESUBMITTING FOR
 REVIEW TO THE CITY.
  
 36. SHT 602 DETAIL 1 SHOWS A GREASE TRAP INSIDE THE
 FOOD PREP AREA. THIS IS NOT APPROVED PER SECTION
 90-124(7)(B) OF THE MUNICIPAL CODE. A MINIMUM 750 GAL.
 INTERCEPTOR IS REQUIRED. PLEASE CONTACT LMASSON,
 ENVIRONMENTAL COMPLIANCE MANAGER FOR SIZING OF THE
 GREASE INTERCEPTOR. CONTACT HER BY PHONE (561)
 822-2271, FAX (561) 822-2279, OR E-MAIL
 [email protected].
 ****RESPONSE NOTED, NO COMMENT FROM ENVIRONMENTAL AS OF
 YET.
  
 37. PLANS DO NOT APPEAR TO BE 100% AT THIS TIME AND
 MORE OR DIFFERENT COMMENTS MAY BE FORTHCOMING DEPENDING
 ON THE REVISIONS OR COMMENT RESPONSES.
 ****MORE INFORMATION IS STILL REQUIRED. SEE COMMENTS.
  
 **********NEW COMMENTS**********
  
 1B. SHT A-101AIS MISLABELED AS 2ND FLOOR PLAN. PLEASE
 CORRECT. SECTION 106.1.1.
  
 2B. SHT A-401 THE TURNING AREA IS TO BE IN THE TOILET
 ROOM, NOT THE ACCESSIBLE STALL. SECTION 11-4.22.3. (SEE
 ROOMS 150 & 151).
  
 3B. SUBMIT ISOMETRIC STORM RISER DIAGRAMS FOR EACH RWL.
 SHOW ALL PIPE SIZES, OFFSETS, SQUARE FOOTAGE & INDICATE
 THE TERMINATION POINT FOR EACH ROOF DRAIN. IF THERE ARE
 TYPICAL RWL'S, INDICATE THE ROOF DRAINS THAT ARE
 TYPICAL OF WHICH RWL. EACH RWL AND ROOF DRAIN SHALL BE
 NUMBERED SUCH AS RWL-1, RWL-2 AND RD-1, RD-2 AND SHALL
 BE INDICATED ON EACH FLOOR PLAN SO AS TO TRACK EACH
 RWL/RD THROUGH THE BUILDING. TABLE 1106.3 AND SECTION
 106.1.3.5.1.3(7)(13).
  
 4B. RESPONSE SHEETS DO NOT REFLECT THE COMMENTS FROM
 THE PREVIOUS REVIEW. SOME COMMENT RESPONSES DO NO
 REFLECT ANY COMMENTS FROM THE PREVIOUS REVIEW, AND THE
 COMMENT RESPONSE NUMBERS DO NOT REFLECT ALL COMMENT
 NUMBERS FROM THE PREVIOUS REVIEW. PLEASE CLARIFY.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 -PLEASE RESUBMIT ONE SET OF OLD SHEETS
 FOR COMPARISON.
 ****NO RESPONSE, NOT ADDRESSED
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-01-20 Cont ID  
Sent By kstevens Date 2007-01-20 Time 06:45 Rev Time 0.00
Received By kstevens Date 2007-01-18 Time 18:54 Sent To  
Notes
2007-01-20 16:28:36 
 DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2001 BUILDING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHTS G-000 THRU G-003 THE FIRM LICENSE NUMBER AND
 THE PRINTED NAME OF THE PERSON SEALING THE DOCUMENT ARE
 REQUIRED ON EACH SHEET. FAC 61G1-16.004(2)(6) & FS
 481.219, 481.2055.-THE EMBOSSED SEAL SHALL IMPRESS
 ALL INFORMATION REQUIRED BY FAC G1G1-16.002 & FS
 481.2055. NOT ALL INFORMATION REQUIRED IS IMPRESSED ON
 EACH SHEET. PLEASE MAKE SURE THE REQUIRED INFORMATION
 IS IN THE TITLE BLOCK AND RESEAL THE PLANS MAKING SURE
 ALL INFORMATION IS IMPRESSED & LEGIBLE WHEN SEALING THE
 PLANS.
  
 2.SHTS SP-1, LP-1, LP-2 & LP-3. THE ADDRESS OF THE
 LANDSCAPE ARCHITECT DOES NOT REFLECT THE ADDRESS
 INDICATED ON THE DBPR WEBSITE. (SEE ATTACHED SHEET FROM
 THE STATE WEBSITE). PLEASE SHOW CORRECT ADDRESS IN THE
 TITLE BLOCK OR UPDATE THE ADDRESS WITH THE STATE DBPR
 WEBSITE. FAC 61G1-16.004(1) & FS 481.2055.
  
 3. ALL STRUCTURAL SHEETS. THE ENGINEERS SHALL LEGIBLY
 INDICATE THEIR NAME, ADDRESS, AND LICENSE NUMBER ON
 EACH SHEET. IF PRACTICING THROUGH A DULY AUTHORIZED
 ENGINEERING BUSINESS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME & LICENSE NUMBER, AS WELL AS, THE NAME,
 ADDRESS, AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS ON EACH SHEET. FAC 61G15-23.002(2)
 & FS 471.025. THE BUSINESS NUMBER, (CERTIFICATE OF
 AUTHORIZATION), FOR PFVS ARCHITECTURE IS REQUIRED IN
 THE TITLE BLOCK AS WELL. FAC 61G1-16.004(2) & FS
 481.219, 481.2055.
  
 4. SHT AC103 INFORMATIONAL: A SEPARATE POOL PERMIT IS
 REQUIRED. PLANS SHALL BE REVIEWED, APPROVED, AND
 STAMPED BY THE PALM BEACH COUNTY HEALTH DEPT. PRIOR TO
 SUBMITTAL FOR APPLICATION AND REVIEW BY WEST PALM BEACH
 PLAN REVIEW. SECTION 102.2.1.
  
 5. SHT G-000 GUESTROOM MATRIX INDICATES 2 HEARING
 IMPAIRED UNITS, STANDARD DOUBLE/DOUBLE, BUT THE FLOOR
 PLANS SHTS A-101 THRU A-105 ONLY SHOW 1 ON THE 4TH
 FLOOR. PLEASE CLARIFY & CORRELATE INFORMATION BETWEEN
 THE FLOOR PLANS & MATRIX. SECTION 106.1.1 & SECTION
 11-9.1.3.-PLEASE INDICATE WHICH ROOMS COMPLY WITH
 SECTION 11-9.1.3.
  
 6. SHT G-000 PLEASE CLARIFY THE DIFFERENCE BETWEEN A
 KING STANDARD, A KING CONNECTOR, A KING SUITE, AND
 INDICATE HOW THE ACCESSIBLE UNITS ARE DISPERSED AMONG
 THE VARIOUS CLASSES. ALSO PLEASE CLARIFY DIFFERENCE
 BETWEEN THE KING TYPE A, KING ALTERNATE, THE KING & THE
 KING ALT B AND INDICATE HOW THE ACCESSIBLE UNITS ARE
 DIAPERSED AMONG THE VARIOUS CLASSES.--PLEASE
 CLARIFY THE DIFFERENCE BETWEEN THE DOUBLE/DOUBLE
 STANDARD, THE DOUBLE/DOUBLE CONNECTOR STANDARD, THE
 DOUBLE/DOUBLE TYPE "A", THE DOUBLE/DOUBLE TYPE "B", THE
 DOUBLE/DOUBLE TYPE "C", THE DOUBLE/DOUBLE SUITE TYPE
 "A", THE DOUBLE/DOUBLE SUITE TYPE "B", AND THE
 DOUBLE/DOUBLE ALTERNATE.--THE DIFFERENCES SHALL BE
 CALLED OUT ON THE PLANS.-- OF CONCERN ALSO IS THE
 MATRIX DOES NOT MENTION THE PRESIDENTIAL SUITE SHOWN ON
 SHT A-411, AND IS INDICATED AS A DOUBLE/DOUBLE ON SHTS
 A-103, A-104 & A-105. PLEASE INDICATE WHY AN ACCESSIBLE
 UNIT FOR THE PRESIDENTIAL SUIT IS NOT PROVIDED.--
 ALSO OF CONCERN IS THE GUESTROOM MATRIX SHOWS
 ACCESSIBLE KING UNITS UNDER THE SECTION OF THE MATRIX
 INDICATED AS "KING GUESTROOMS", BUT UNDER THE SECTION
 INDICATED AS "DOUBLE/DOUBLE GUESTROOMS" THE ACCESSIBLE
 UNITS ARE "KING ACCESSIBLE UNITS". PLEASE CLARIFY.
 PLEASE COMPLY WITH SECTION 11-9.1.2.
  
 7. SHTS G-000 GUESTROOM MATRIX DOES NOT REFLECT THE
 FLOOR PLANS ON SHTS A-101 THRU A-105. THE MATRIX
 INDICATES A TOTAL OF 7 ACCESSIBLE UNITS, BUT THE FLOOR
 PLANS INDICATE A TOTAL OF 12 UNITS. PLEASE CORRELATE
 THE INFORMATION ON THE MATRIX AND THE FLOOR PLANS.
 SECTIONS 106.1.1 AND 11-9.1.2.
  
 8. SHT A-106 SUBMIT CALCULATIONS FOR THE PRIMARY AND
 SECONDARY ROOF DRAINS. SHOW THE AREA TO BE DRAINED FOR
 EACH ROOF DRAIN, AND INDICATE 1/2 THE AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS ADDED TO THAT AREA.
 ALSO INDICATE ALL AREAS FROM ROOF AREAS THAT DRAIN ONTO
 THE ROOF FROM ABOVE. SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS AND TABLES. INDICATE TOTAL AREA BEING
 DRAINED BY EACH DRAIN.
  
 9. SHT A-401 TOILET ROOM 134, NO FIXTURES ARE SHOWN.
 PLEASE CLARIFY. SECTION 1106.1.
  
 10. SHTS A-411, & A-412 SHOW THE CLEAR FLOOR SPACE FOR
 EACH FIXTURE AND SHOW EACH FIXTURE IN THE ACCESSIBLE
 UNITS. SECTIONS 11-4.16.
  
 11. SHT A-600 FINISH SCHEDULE FOR ROOMS 134, 150, & 151
 SHOW PAINT OR V.W.C. FOR THE WALLS. SECTION 1210.2
 CALLS FOR "SMOOTH, HARD, NONABSORBENT" SURFACES. PAINT
 AND V.W.C. DO NOT COMPLY WITH THE "HARD" REQUIREMENT.
 PLEASE COMPLY.
  
 12 SHT A-801 ELEVATION 15. THE SINK SHALL COMPLY WITH
 SECTION 11-4.24 AND ALL SUBSECTIONS. A FORWARD APPROACH
 CLEAR FLOOR SPACE IS REQUIRED AND SHALL EXTEND A
 MAXIMUM OF 19" UNDERNEATH THE SINK. CABINET DOORS ARE
 NOT APPROVED IN THE CLEAR FLOORSPACE AND ARE NOT TO
 BE INSTALLED.
  
 13. SHTS A-802 APPLICABLE ELEVATIONS 1 THRU 13,A-803
 APPLICABLE ELEVATIONS 1- THRU 14, A-804 APPLICABLE
 ELEVATIONS 1 THRU 15, SHALL COMPLY WITH SECTIONS
 11-4.16, 11-4.18, 11-4.19, 11-4.20, 11-4.21 & 11-4.22
 AND ALL SUBSECTIONS. PLEASE INDICATE ON ELEVATIONS.
 ALSO SHOW ALL W/C'S TO BE 18" OFF THE WALL TO THE
 CENTERLINE OF THE FIXTURE, & SHOW ALL LAVS TO BE MIN.
 15" OFF THE WALL TO THE CENTERLINE OF THE FIXTURE WHERE
 THE FIXTURES ARE ADJACENT TO THE WALLS. FIGURES 11-28
 AND 11-32.
  
 14. SHT A-806 DETAIL 5 INDICATE THE FOLLOWING:
 A. 11-4.24.4 SINK DEPTH
 B. 11-4.24.5 CLEAR FLOOR SPACE
 C. 11-4.24.7 FAUCETS
  
 15. SHT A-806 DETAILS 1,3,5 & 6 REFERENCE A BREAKFAST
 ROOM. THIS IS NOT SHOWN ON SHTS A-101 1ST FLOOR PLAN,
 NOR ON SHT A-401. PLEASE CLARIFY. IDENTIFY THIS ROOM ON
 THE FLOOR PLAN & INDICATE THE DETAIL NUMBERS AND THE
 SHT THAT THE DETAILS CAN BE FOUND ON THE FLOOR PLAN.
 SECTION 106.1.1.
  
 16. SHT A-812 DETAIL 1, INDICATES A WATER WALL FEATURE.
 MORE INFORMATION IS REQUIRED. WILL THERE BE A WATER
 SUPPLY LINE CONNECTED TO THE WATER FEATURE? WILL THE
 WATER FEATURE CONNECT TO THE SANITARY DRAINAGE SYSTEM.
 PLEASE CLARIFY.SECTION 106.1.1.
  
 17. SHT A-813 DETAIL 4, SHOW THE FOLLOWING:
 A. 11-4.19.2 CLEARANCE
 B. 11-4.19.5 FAUCETS
  
 18. ALL MPE SHEETS. A "WET SIGNATURE" IS REQUIRED AND
 SHALL BE AFFIXED TO THE PLANS WHEN THE DOCUMENT IS
 SEALED & DATED. "STAMP SIGNATURES" ARE NOT APPROVED.
 FAC 61G15-23.002(2) & FS 471.025.
  
 19. ALL MECH. AND PLMG. SHEETS. THE ENGINEER'S SEAL IS
 NOT APPROVED. THERE WAS A 2 YEAR GRACE PERIOD ENDING
 DEC. 31, 2006 ALLOWING THE USE OF THE OLDER SEALS THAT
 ARE OBSOLETE NOW AND HAD THE WORD "CERTIFICATE" ON THE
 SEAL. THE NEW SEAL SHALL HAVE THE WORD "LICENSE" ON THE
 SEAL. (SEE THE ATTACHED SHEET FROM THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS). PLEASE RESEAL ALL SHEETS
 DESIGNED BY ENGINEERS. FAC 61G15-23.001 & FS 471.025.
  
 20. SHTS P101 THRU P105 MINIMUM 1/8" SCALE PLANS
 REQUIRED. SECTION 106.1.3. PLEASE SUBMIT FLOOR PLANS
 THAT MEET THIS REQUIREMENT.
  
 21. SHT P101 PLUMBING KEYNOTES #14 AND FLOOR PLAN
 SHOWING THE ELEVATOR SUMP PUMP CONNECTING TO THE
 SANITARY SYSTEM. THIS IS NOT APPROVED AND THE
 WATER/WASTE/OIL FROM THE ELEVATOR SUMP PIT SHALL BE
 COLLECTED AND TREATED AS HAZARDOUS MATERIAL AND
 DISPOSED OF AS SUCH.MUNICIPAL CODE 90-125(B)(1).
  
 22. SHT P101 SOME RISERS AND SOME FIRST FLOOR FIXTURES
 SHOW NO PIPING OR BRANCH LINES CONNECTING THE
 RISERS/FIXTURES TO THE BUILDING DRAIN. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 23. SHTS P101 & CIVIL PLAN SHT 6 OF 9. SHT 6 OF 9 SHOWS
 A 3" METER, BACKFLOW, & WATER SERVICE. SHT P101 SHOWS
 4" DOMESTIC WATER ENTERING THE BUILDING. PLEASE SUBMIT
 CALCULATIONS FOR THE REQUIRED SIZE FOR THE WATER
 SERVICE PER SECTION 603.1 AND TABLE 603.1. SEE APPENDIX
 "E"
  
 24. SHT P101 TOILET ROOMS BY THE EXERCISE ROOM SHOW
 FLOOR DRAINS IN THE SHOWERS, BUT NO PIPING TO THE
 SHOWER DRAINS. PLEASE CLARIFY. SECTION 106.1.1.
  
 25. SHTS P101 THRU P105 GENERL NOTES #1. "ALL SANITARY
 AND WASTE PIPING SHALL SLOPE @ 1/8"/FT UNLESS OTHERWISE
 NOTED". PIPE SHALL BE SLOPED PER TABLE 704.1. PIPE
 2-1/2" OR LESS SHALL BE SLOPED MINIMUM 1/4" PER FT.
 PLEASE INDICATE ON PLANS.
  
 26. SHTP105 SHOW THE LOCATION OF ALL PRIMARY AND
 SECONDARY ROOF DRAINS. SHOW ALL RELATED PIPING. SECTION
 106.1.1.
  
 27. SHT P401 WATER HEATER ROOM. PLEASE INDICATE WHY A
 DOUBLE CHECK BACKFLOW PREVENTOR IS BEING CALLED FOR IN
 THE DISTRIBUTION WATER PIPING UPSTREAM OF THE BOOSTER
 PUMPS. AN RPZV BACKFLOW WILL BE INSTALLED DOWNSTREAM OF
 THE METER ON THE WATER SERVICE, AND A DOUBLE CHECK
 BACKFLOW IS NOT THE CORRECT USAGE FOR THE DISTRIBUTION
 OF POTABLE WATER. TABLE 608.1. PLEASE DELETE FROM
 PLANS. SECTION 106.1.1.
  
 28. SHT P401 FIRE PUMP ROOM, THE FLOOR DRAINS ARE NOT
 VENTED. SECTION 901.2.1. THE FLOOR PLAN DOES NOT
 REFLECT THE PIPING LAYOUT ON SHT P101. PLEASE CORRELATE
 THE FLOOR PLANS. SECTION 106.1.1.
  
 29. SHT P501 DETAIL 1 DOES NOT REFLECT THE FLOOR PLAN,
 (SHT P401).P-8 IS SHOWN FOR TUBS INDICATED AS P-9 ON
 SHT P401. PLEASE CORRELATE RISERAND FLOOR PLAN.
 SECTION 106.1.1. - THE BRANCH LINE FOR THE DETAIL IS
 SHOWN AS OFFSET, BUT THE FLOOR PLAN SHOWS THE PIPING TO
 THE CENTER OF THE BATHROOMS. PLEASE CORRELATE.
  
 30. SHT P501 DETAIL 2 DOES NOT REFLECT THE FLOOR PLAN,
 (SHT P401) . P-8 IS SHOWN FOR TUBS INDICATED AS P-9 ON
 SHT P401. PLEASE CORRELATE RISER AND FLOOR PLAN.
 SECTION 106.1.1. - THE BRANCH LINE FOR THE DETAIL IS
 SHOWN AS OFFSET, BUT THE FLOOR PLAN SHOWS THE PIPING TO
 THE CENTER OF THE BATHROOMS. PLEASE CORRELATE RISER AND
 FLOOR PLAN.
  
 31. SHT P501 DETAIL 7 DOES NOT REFLECT THE FLOOR PLAN
 FOR THE FIRST FLOOR. CORRELATE RISER AND FLOOR PLAN.
 SECTION 106.1.1.
  
 32. SUBMIT A SANITARY HORIZONTAL BUILDING DRAIN
 ISOMETRIC RISER DIAGRAM THAT REFLECT THE FLOOR PLAN.
 SHOW ALL PIPE SIZES, RISER LOCATIONS, TRAPS AND DFU'S
 AS THEY ACCUMULATE IN THE SYSTEM. SECTION 106.3.5.1.3.
 -SHOW ALL THE FIRST FLOOR FIXTURES NOT CONNECTED TO A
 VERTICAL RISER ON THE HORIZONTAL RISER DIAGRAM. (SEE
 BREAK ROOM, FOOD PREP, LAUNDRY ROOM, TOILET ROOMS, PUMP
 ROOM ETC.).
  
 32. SUBMIT A HORIZONTAL BUILDING WATER ISOMETRIC RISER
 DIAGRAM. SHOW ALL PIPE SIZES, VALVES, WATER HAMMER
 ARRESTORS, (REQUIRED BY SECTION 604.9 FOR ICE MAKERS,
 WASH MACHINES, AND DISHWASHERS).
  
 33 SUBMIT A HORIZONTAL BUILDING CONDENSATE ISOMETRIC
 RISER DIAGRAM AND VERTICAL RISER DIAGRAMS. SHOW ALL
 PIPE SIZES AND INDICATE THE TERMINATION POINT.
  
 34. INDICATE A NUMBER DESIGNATION FOR EACH RISER
 INCLUDING ALL SANT., WATER, STORM, CONDENSATE. (EXAMPLE
 SANT-1, SANT-2, RWL-1, RWL-2, CON-1, CON-2, W-1, W-2
 ETC.). THIS WILL AID IN TRACKING ALL RISERS FROM THE
 UNDERGROUND PIPING THROUGH THE ROOF. SECTIONS
 106.3.5.1.3 & SECTION 106.1.1.--INDICATE WHICH
 RISER IS TYPICAL OF WHICH RISER ISOMETRIC DIAGRAM.
 (EXAMPLE SANT-1 SANT-4 TYPICAL OF DETALI 4 SHT P401) --
 INDICATE ROOM NUMBER EACH RISER CAN BE LOCATED.
  
 35. ROUTE PLANS TO THE DEPT. OF BUSINESS REGULATION,
 HOTEL & RESTURANT DIVISION FOR REVIEW PRIOR TO
 RESUBMITTING TO THE CITY FOR REVIEW. A MINIMUM OF TWO
 SETS OF PLANS, STAMPED BY DBPR AND TWO PAGE
 "WORKSHEETS" ATTACHED TO PLAN ARE REQUIRED. SECTION
 102.2.1.
  
 36. SHT 602 DETAIL 1 SHOWS A GREASE TRAP INSIDE THE
 FOOD PREP AREA. THIS IS NOT APPROVED PER SECTION
 90-124(7)(B) OF THE MUNICIPAL CODE. A MINIMUM 750 GAL.
 INTERCEPTOR IS REQUIRED. PLEASE CONTACT LMASSON,
 ENVIRONMENTAL COMPLIANCE MANAGER FOR SIZING OF THE
 GREASE INTERCEPTOR. CONTACT HER BY PHONE (561)
 822-2271, FAX (561) 822-2279, OR E-MAIL
 [email protected].
  
 37. PLANS DO NOT APPEAR TO BE 100% AT THIS TIME AND
 MORE OR DIFFERENT COMMENTS MAY BE FORTHCOMING DEPENDING
 ON THE REVISIONS OR COMMENT RESPONSES.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 -PLEASE RESUBMIT ONE SET OF OLD SHEETS
 FOR COMPARISON.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  
  
  
  

Review Stop Z ZONING
Rev No 11 Status P Date 2009-07-29 Cont ID  
Sent By lfranco Date 2009-07-14 Time 17:49 Rev Time 0.00
Received By lfranco Date 2009-07-14 Time 17:49 Sent To  
Notes
2009-07-29 17:53:26PLANNING AND ZONING: **** PASSED - THIS APPROVAL IS
 ONLY FOR THE CORRECTIONS TO PHASING REVISION COMMENTS
 DATED 6-11-09 ****
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]

Review Stop Z ZONING
Rev No 10 Status F Date 2009-06-11 Cont ID  
Sent By lfranco Date 2009-06-11 Time 10:52 Rev Time 0.00
Received By lfranco Date 2009-06-11 Time 10:52 Sent To  
Notes
2009-06-11 11:48:25PLANNING AND ZONING: **** FAILED- PHASING SUBMITTAL****
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. SHEET SP-1, - EXTERIOR REFUSE RECEPTACLE/STORAGE -
 THE MINIMUM WIDTH DIMENSION FOR THE DUMSTER SHALL BE
 13'-8", A REVISION CLOUD NEXT TO THE GATE OPENING SHOWS
 THE DIMENSION AT 13 FEET IN WIDE.
  
 3. COMPACT SPACES ARE SHOWN AT THE EAST SIDE OF THE
 SPRINGHILL HOTEL. THE SITE PLAN APPROVAL DID NOT
 INCLUDE ANY COMPACT PARKING SPACES. PLEASE CLARIFY THE
 NEED FOR THE COMPACT SPACES. IF INDEED THE COMPACT
 SPACES ARE NECESSARY, THEN THE FOLLOWING SHALL BE
 PROVIDED, PURSUANT TO SECTION 94-485(N)(1):
 A. SHOW A BREAK DOWN OF THE PERCENTAGE OF COMPACT
 SPACES VS. REGULAR SPACES; AND,
 B. DELINEATE THE COMPACT PARKING FROM THE REMAINDER
 REGULAR PARKING SPACES ON THE SITE PLAN BY LABELING
 THEM WITH A ???C??? OR MARKING ???SMALL CARS ONLY???
 C. PROVIDE SIGNAGE DETAIL PER 94-485(N)(1)(D.)
  
 4. SEE LANDSCAPE COMMENTS FOR THE SIDEWALK
 CONFIGURATION AND LANDSCAPING ADJACENT TO THE
 SPRINGHILL SUITES HOTEL PORTE-COCHERE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME AT THE
 NUMBER BELOW.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]

Review Stop Z ZONING
Rev No 9 Status P Date 2009-04-17 Cont ID  
Sent By lfranco Date 2009-04-17 Time 18:33 Rev Time 0.00
Received By lfranco Date 2009-04-17 Time 18:32 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 8 Status F Date 2008-10-23 Cont ID  
Sent By lfranco Date 2008-10-23 Time 17:06 Rev Time 0.00
Received By lfranco Date 2008-10-23 Time 17:06 Sent To  
Notes
2008-10-23 17:06:29PLANNING AND ZONING: **** FAILED****
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. SUBMITTAL INDICATES NEW SIDEWALKS WERE ADDED TO BOTH
 HOTELS (SPRINGHILL AND HOMEWOOD). ADD A BUBBLE ON WHAT
 HAS BEEN REVISED. ON HOTEL 1 ("HOMEWOOD SUITES"), A NEW
 SIDEWALK IS REFLECTED BY THE DUMPSTER ENCLOSURE, BUT
 THE SIDEWALK IS GOING INTO THE SIDE OF A PARKING STALL?
  
 RE-SUBMITTAL - BASED ON SHEET LP-1 SHOWING ONE BUBBLE
 ON HOTEL 1 (HOMEWOOD), THE SIDEWALK LOCATION GOING INTO
 A PARKING STALL IS NOT THE MOST CONDUCIVE AREA, IF THE
 PURPOSE IS FOR ACCESSIBILITY TO MAINTENANCE AND/OR
 PEDESTRIANS. IF A CAR HAPPENS TO BE PARKED IN THAT
 STALL, ACCESS WILL BE PROHIBITED. ALSO, CONSIDERATION
 SHALL BE MADE REGARDING THE LOCATION OF SAID SIDEWALK,
 SINCE IT HAS LEFT LESS SPACE FOR THE LANDSCAPING TO
 GROW ADEQUATELY. SEE LANDSCAPE COMMENTS.
  
 3. SHEET E-602 SITE LIGHTING CALCULATIONS DOES NOT
 CORRELATE WITH THE SITE PLANS. SPECIFICALLY, BUT NOT
 LIMITED TO THE NORTHEAST AREA OF HOMEWOOD SUITES, HOTEL
 1, WHICH DEPICTS PARKING STALLS WHERE A LOADING AREA
 SHOULD BE AND DUMPSTER ENCLOSURE IS DEPICTED IN THE
 LANDSCAPE TERMINAL ISLAND. REVISE DRAWING ACCORDINGLY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME AT THE
 NUMBER BELOW.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPT.
 TEL: (561) 822-1443
 EMAIL: [email protected]

Review Stop Z ZONING
Rev No 7 Status F Date 2008-08-15 Cont ID  
Sent By lfranco Date 2008-08-15 Time 14:11 Rev Time 0.00
Received By lfranco Date 2008-08-15 Time 14:11 Sent To  
Notes
2008-08-15 14:24:44PLANNING AND ZONING:**** FAILED****
  
 1.RESPOND TO COMMENTS IN WRITING.
  
 2.REPEAT COMMENT PURSUANT TO SECTION 94-443, FIGURE
 XV-2, BACK OF WHEEL STOPS SHALL BE SET BACK 2 FEET FROM
 THE EDGE-OF-PAVEMENT TO ELIMINATE ANY VEHICULAR
 ENCROACHMENT INTO THE DIVIDER LANDSCAPE STRIPS.
 LANDSCAPING SITE PLAN SP-1 [PARKING AND STRIPPING]),
 STILL SHOWS THE DIMS FROM FRONT OF WHEEL STOP.
  
 3.SUBMITTAL INDICATE NEW SIDEWALKS WERE ADDED TO BOTH
 HOTELS (SPRINGHILL AND HOMEWOOD).ADD A BUBBLE ON WHAT
 HAS BEEN REVISED.ON HOTEL 2, HOMEWOOD, A NEW SIDEWALK
 IS REFLECTED BY THE DUMPSTER ENCLOSURE, BUT THE
 SIDEWALK IS GOING INTO THE SIDE OF A PARKING STALL?
 PLEASE CLARIFY.
  
 4.PROVIDE AN EXTRA COPY OF THE SP-1 AND LP-1 THROUGH
 LP-3 TO PLANNING AND ZONING DEPARTMENT TO REFLECT
 REQUIRED CHANGES, INCLUDING THE REVISED LOCATION WHEN
 RE-SUBMITTING OR SUBBING SHEETS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME AT THE
 NUMBER BELOW.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPT.
 TEL: (561) 822-1443
 EMAIL: [email protected]

Review Stop Z ZONING
Rev No 6 Status F Date 2008-05-02 Cont ID  
Sent By lfranco Date 2008-05-02 Time 19.23 Rev Time 0.00
Received By lfranco Date 2008-05-02 Time 16:14 Sent To  
Notes
2008-05-02 16:35:39PLANNING AND ZONING:**** FAILED****
  
 1.RESPOND TO COMMENTS IN WRITING.
  
 2.PURSUANT TO SECTION 94-443, FIGURE XV-2, BACK OF
 WHEEL STOPS SHALL BE SET BACK 2 FEET FROM THE
 EDGE-OF-PAVEMENT TO ELIMINATE ANY VEHICULAR
 ENCROACHMENT INTO THE DIVIDER LANDSCAPE STRIPS.
 LANDSCAPE STRIPS MUST BE AT LEAST FIVE (5) FEET IN
 WIDTH WITHOUT ANY VEHICULAR ENCROACHMENT (REVISE, CIVIL
 SHEET 2 OF 9 [DETAIL "A"], LANDSCAPING LP-2 AND SITE
 SP-1 [PARKING AND STRIPPING]).
 RESPONSE TO RE-SUBMITTAL:SEE COMMENT NUMBER 2
 REGARDING THE REQUIREMENTS FOR THE WHEEL STOPS. IN
 ADDITION, ALL CURBING AND WHEEL STOPS SHALL BE SHOWN ON
 PLANS (I.E. LANDSCAPING LP-2). IN REFERENCE TO THE
 7-FOOT WIDE LANDSCAPE SEPARATOR STRIPS, THE WHEEL STOPS
 ARE SHOWN AT LESS THAN THE 2 FEET THAT ARE REQUIRED. IF
 THE WHEEL STOPS ARE REMOVED AND CURBING IS USED AT THE
 EDGE THEN THE WIDTH OF THE STRIP BETWEEN TWO PARKING
 ROWS HAS TO BE AT LEAST 9 FEET.
  
 3.PROVIDE AN EXTRA COPY OF THE SP-1 AND LP-1 THROUGH
 LP-3 TO PLANNING AND ZONING DEPARTMENT TO REFLECT
 REQUIRED CHANGES, INCLUDING THE REVISED LOCATION WHEN
 RE-SUBMITTING OR SUBBING SHEETS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME AT THE
 NUMBER BELOW.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPT.
 TEL: (561) 822-1443
 EMAIL: [email protected]

Review Stop Z ZONING
Rev No 5 Status P Date 2008-02-26 Cont ID  
Sent By lfranco Date 2008-02-26 Time 18:40 Rev Time 0.00
Received By lfranco Date 2008-02-26 Time 18:40 Sent To  
Notes
2008-02-26 18:43:03 
 PLANNING AND ZONING:**** PASSED WITH PROVISO - IF
 PROVISO IS NOT ADDRESSED WITHIN 60-DAYS OF PERMIT
 ISSUANCE, THE PERMIT WILL BE REVOKED. ****
  
 1.PROVIDE RESPONSE TO COMMENTS IN WRITING.
  
  
 2. THE REFUSE/STORAGE ENCLOSURE NEEDS TO BE MOVED AWAY
 FROM ADJACENT PARKING SPACE, SINCE ACCESS TO THE
 ENCLOSURE CAN BE BLOCKED OFF IF A CAR IS PARKED IN THAT
 SPACE.ALL SHEETS INCLUDING BUT NOT LIMITED TO THE
 FOLLOWING SHEETS WILL NEED TO REFLECT THE REVISED
 LOCATION (I.E. CIVIL SHEETS 2 OF 9 (DRAINAGE), 5 OF 9
 (POLLUTION), 6 OF 9; ARCHITECTURAL, SITE PLAN SP-1
 (WITH LATEST REVISION 1-04-08), AND LANDSCAPING, LP-1,
 THE PROPOSED DAHOON HOLLY TREE WILL NEED TO BE SHIFTED
 A LITTLE TO ACCOMMODATE THE DUMPSTER/STORAGE
 ENCLOSURE.)
  
 ADDITIONALLY, A FEW OF THE CIVIL SHEETS SHOW AN OPENING
 OF THE DUMPSTER ENCLOSURE GOING INTO THE LANDSCAPED
 AREA, OTHER SHEETS (INCLUDING DETAIL OF ENCLOSURE DO
 NOT SHOW AN OPENING), COORDINATE ALL SHEETS
 ACCORDINGLY.IF THERE IS A PROPOSED OPENING FOR ACCESS
 TO THE DUMPSTER ENCLOSURE TO THE SIDE, IT WILL NEED
 REVISED TO OPEN FROM THE SIDEWALK FOR ACCESSIBILITY,
 INSTEAD.
  
 3.PROVIDE AN EXTRA COPY OF THE SP-1 AND LP-1 TO
 PLANNING AND ZONING DEPARTMENT TO REFLECT REQUIRED
 CHANGES, INCLUDING THE REVISED LOCATION WHEN
 RE-SUBMITTING OR SUBBING SHEETS.
  
 4.PERMIT NO. 06111071- HOMEWOOD HOTEL SHALL REFLECT
 THE SAME CHANGES ON THE SITE PLAN SHEETS AND PERTINENT
 SHEETS ACCORDINGLY.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 OFFICE: (561) 822-1443
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 OFFICE: (561) 822-1443
 EMAIL: [email protected]

Review Stop Z ZONING
Rev No 4 Status F Date 2008-01-18 Cont ID  
Sent By lfranco Date 2008-01-18 Time 16:31 Rev Time 0.00
Received By lfranco Date 2008-01-16 Time 10:31 Sent To  
Notes
2008-01-18 17:32:42PLANNING AND ZONING:**** FAILED ****
  
 1.PROVIDE RESPONSE TO COMMENTS IN WRITING.
  
 2, THE ENGINEERING DRAWINGS, SHEET 2 OF 9 SHOWS THE
 DUMPSTER/STORAGE ENCLOSURE THAT MEETS CODE, HOWEVER, A
 NOTE REFERS TO THE ARCHITECTURAL DRAWINGS, THE AC102
 SHEET (DETAILS) DOES NOT HAVE THE DUMPSTER/STORAGE
 ENCLOSURE SHOWN (ADJACENT TO THE HOMEWOOD SUITES
 HOTEL).SEE COMMENTS ON THE HOMEWOOD SUITES HOTEL
 (PERMIT 06111071, WHICH NOTES THAT THIS ENCLOSURE NEEDS
 TO BE MOVED AWAY FROM THE PARKING SPACE TO THE SOUTH IN
 ORDER TO PROVIDE CLEARANCE WHEN A CAR IS PARKED, SO
 THAT IT DOES NOT BLOCK ACCESS TO IT.ALL SHEETS
 INCLUDING BUT NOT LIMITED TO THE FOLLOWING SHEETS WILL
 NEED TO REFLECT THE REVISED LOCATION (I.E. CIVIL SHEETS
 5 AND 6 OF 9; ARCHITECTURAL, SITE PLAN SP-1AND
 LANDSCAPING, LP-1, THE PROPOSED DAHOON HOLLY TREE WILL
 NEED TO BE SHIFTED A LITTLE TO ACCOMMODATE THE
 DUMPSTER/STORAGE ENCLOSURE.)
  
 3.PROVIDE AN EXTRA COPY OF THE SP-1 AND LP-1 TO
 PLANNING AND ZONING DEPARTMENT TO REFLECT REQUIRED
 CHANGES, INCLUDING THE REFUSE/STORAGE DETAILS AND
 REVISED LOCATION WHEN RE-SUBMITTING OR SUBBING SHEETS.
  
 4.PERMIT NO. 06111067- SPRINGHILL HOTEL SHALL REFLECT
 THE SAME CHANGES ON THE SITE PLAN SHEETS AND PERTINENT
 SHEETS ACCORDINGLY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 OFFICE: (561) 822-1443
 EMAIL: [email protected]

Review Stop Z ZONING
Rev No 3 Status F Date 2007-10-02 Cont ID  
Sent By lfranco Date 2007-10-02 Time 19:23 Rev Time 0.00
Received By lfranco Date 2007-10-02 Time 19:08 Sent To  
Notes
2007-10-02 19:16:25PLANNING AND ZONING:**** FAILED ****
  
 1.PROVIDE RESPONSE TO COMMENTS IN WRITING.
  
 2, ARCHITECTURAL SHEET AC102 (CONSTRUCTION SET), DETAIL
 #6 - DUMPSTER ENCLOSURE PLAN DOES NOT MEET THE MINIMUM
 DEPTH REQUIREMENTS OF 13'-8". PLEASE REFER TO THE
 APPROVED SITE PLANS, SUBMITTED TO THE PLANNING AND
 ZONING DEPARTMENT.
  
 3.PROVIDE ALL THE SITE PLANS AND LANDSCAPE PLANS
 SUBMITTED TO THE PLANNING AND ZONING DEPARTMENT AS PART
 OF THE MINOR PLANNED DEVELOPMENT AMENDMENT TO THE
 METROCENTRE HOTELS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 OFFICE: (561) 822-1443
 EMAIL: [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2007-04-04 Cont ID  
Sent By lfranco Date 2007-04-04 Time 19:50 Rev Time 0.00
Received By lfranco Date 2007-04-02 Time 18:18 Sent To I
Notes
2007-04-04 19:50:22PLANNING AND ZONING:***** FAILED *****
  
 1.RESPOND TO COMMENTS IN WRITING.
  
 2.THE SITE PLAN'S SITE DATA, I.E. BUILDING SQUARE
 FOOTAGE EXCEED AND DO NOT MATCH THE SITE PLANS APPROVED
 BY THE PLANNING AND ZONING DEPARTMENT.THE SUBJECT
 PROJECT IS PART OF THE METROCENTRE CPD, THEREFORE, AN
 APPLICATION SHALL BE FILED TO THE PLANNING AND ZONING
 DEPARTMENT FOR A MINOR AMENDMENT TO THE METROCENTRE
 CPD, PRIOR TO ANY APPROVALS FOR BUILDING PERMITS.
  
 3. ADDITIONALLY, THE "REMAINING" VESTED SQUARE FOOTAGE
 IN METROCENTRE CPD SHALL REFLECT THE REVISED SQUARE
 FOOTAGE FOR THESE TWO HOTELS (HOMEWOOD SUITES AND
 SPRINGHILL SUITES).
 THESE CHANGES MAY BE SUBJECT TO A REQUIREMENT FOR A
 NEW/REVISED LETTER FROM THE METROCENTRE'S CPD
 ARCHITECTURAL REVIEW BOARD.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL ME AT THE NUMBER
 BELOW.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2007-01-10 Time   Rev Time 0.00
Received By lfranco Date 2007-01-10 Time 17:23 Sent To  
Notes
2007-01-10 17:27:04PLANNING AND ZONING : FAILED
  
 1.PROVIDE RESPONSE TO COMMENTS IN WRITING.
  
 2, ARCHITECTURAL SHEET AC101 DOES NOT MATCH APPROVED
 PLAN, THE SITE DATA CONTAINING PARKING REQUIREMENTS AND
 PROVIDED DO NOT COMPLY WITH APPROVED PLANS OF THE MINOR
 AMENDMENT.REVISE ACCORDINGLY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 OFFICE: (561) 822-1443