| 2006-12-10 16:48:20 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6652 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2004 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | F.S.= FLORIDA (STATE) STATUTE |
| | |
| | 1) THE SUBMITTED 'RIGHT-OF-WAY CONSTRUCTION PERMIT' IS |
| | FOR "SIDEWALK CLOSURE" FOR A PERIOD OF TEN DAYS.IT |
| | DOES NOT MAKE REFERENCE TO ALTERATION OF THE SIDEWALK. |
| | THE PLANS SHOW THE SIDEWALK WIDTH INCREASED BY 1'-6" |
| | USING PAVERS AND WILL THEREFORE BE REVIEWED BY RASIK |
| | CHOKSHI (TEL: 561 805 6723) OF ENGINEERING SERVICES |
| | DEPARTMENT. |
| | |
| | 2) FBC* 106.1THE TITLE BLOCK ON THE PLANS SHALL |
| | INCLUDE THE PRINTED LICENSE NUMBER AND FULL SIGNATURE |
| | OF CARL G. FORBES, P.E. |
| | ALSO, THE NEW TYPE OF ENGINEER'S SEAL IS REQUIRED FOR |
| | ALL PLANS SEALED AFTER 12/31/05.ENGINEER'S SEALS |
| | INCLUDING THE WORD "CERTIFICATE" ARE NO LONGER VALID. |
| | ON 2/5/04 THE FLORIDA BOARD OF PROFESSIONAL ENGINEERS |
| | AMENDED THE 'SEALS' RULE AND REQUIRED THAT ALL MEMBERS |
| | OBTAIN SEALS WITH THE WORD "LICENSE" INSTEAD OF |
| | "CERTIFICATE".THE EXTENDED GRACE PERIOD FOR |
| | COMPLIANCE ENDED ON 12/31/05.(REF: 471.025 F.S. AND |
| | RULE 61G15-23.001 F.A.C.) |
| | |
| | 3) RULE 61G15-23.002(2) F.A.C.THE CALCLULATION |
| | CONTENTS SHEET IS NOT SIGNED AND SEALED, AND THE |
| | CALCULATION SHEETS ARE NOT ALL NUMBERED.EITHER EACH |
| | SHEET OF THE CALCULATIONS SHALL BE SIGNED AND SEALED |
| | WITH A TITLE BLOCK, OR EACH SHEET MUST BE NUMBERED AND |
| | A SIGNED AND SEALED CONTENTS SHEET PROVIDED LISTING THE |
| | RELEVANT CALCULATION SHEET NUMBERS. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE: |
| | (561) 805 6652ROBERT BROWN |
| | E-MAIL: [email protected] |
| | |