Plan Review Details - Permit 06110795
Plan Review Stops For Permit 06110795
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-02-22 Cont ID  
Sent By rmcdouga Date 2007-02-22 Time 18:03 Rev Time 0.00
Received By rmcdouga Date 2007-02-22 Time 18:03 Sent To  
Notes
2007-02-22 18:24:11BUILDING PROVISO
  
 THE INSULATION IN THE CEILING IS REQUIRED TO HAVE A
 MINIMUM R VALUE OF R-19 PER FBC 13-604.1.ABC.1.
  
 INSULATION ON RENOVATED WALLS SHALL COMPLY WITH FBC
 13-602.1.C.1.1 AND 13-602.1.C.2.
 THE INSULATION AT MASONRY WALLS IS REQUIRED TO HAVE AN
 R VALUE OF R-5.
 THE INSULATION AT WOOD FRAME WALLS IS REQUIRED TO HAVE
 AN R VALUE OF R-11 FOR 2 X 4 WALLS AND R-19 FOR 2 X 6
 WALLS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-02-05 Cont ID  
Sent By rmcdouga Date 2007-02-05 Time 15:40 Rev Time 0.00
Received By rmcdouga Date 2007-02-05 Time 14:53 Sent To  
Notes
2007-02-05 15:39:59DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) PLANS ARE REQUIRED TO HAVE THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THEM. FBC* 106.
  
 3) FBC * 106.1.1 REQUIRES CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE LOCATION,
 NATURE AND EXTENT OF THE WORK PROPOSED AND SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS
 CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 4 Status N Date 2007-05-31 Cont ID  
Sent By btrobaug Date 2007-05-31 Time 09:43 Rev Time 0.50
Received By btrobaug Date 2007-05-31 Time 09:39 Sent To PC
Notes
2007-05-31 09:42:57 
 REVISION DENIED/INCOMPLETE INFORMATION
  
 CONTRACTOR HAS FILE COPY AND APPLICATION FOR THIS
 PROJECT. PER OUR PHONE CONVERSATION 5/29/07 HE WILL
 BRING THEM IN AT WHICH TIME THIS REVISION CAN BE
 REVIEWED
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-03-02 Cont ID  
Sent By btrobaug Date 2007-03-02 Time 16:02 Rev Time 0.50
Received By btrobaug Date 2007-03-02 Time 15:54 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-02-22 Cont ID  
Sent By btrobaug Date 2007-02-22 Time 08:58 Rev Time 1.00
Received By btrobaug Date 2007-02-22 Time 07:24 Sent To M
Notes
2007-02-22 08:47:49 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} SHOW THE PHYSICAL LOCATION OF ALL SERVICE EQUIPMENT
 ON THE PLAN. 215.5,230.70(A)(1), 110.26.
  
 2} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT. THE INFORMATION FROM FPL WAS
 SUBMITTED BUT THE RATING OF THE EQUIPMENT WAS NOT
 INDICATED.
  
 3} THE EQUIPMENT GROUND BETWEEN THE METER AND
 DISCONNECT ON THE RISER DIAGRAM CREATES A PARALLEL PATH
 TO GROUND WITH THE NEUTRAL AND MUST BE REMOVED. AN
 ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE TO BE RAN
 FROM THE FIRST MEANS OF DISCONNECT. 250.6.
  
 4} THE A/C LOAD IN THE CALCULATION IS INCORRECT. THE
 DESIGNER IS USING 220.83"THIS SECTION SHALL BE
 PERMITTED TO BE USED TO DETERMINE IF THE EXISTING
 SERVICE OR FEEDER IS OF SUFFICIENT CAPACITY TO SERVE
 ADDITIONAL LOADS." ARTICLE 220.82 SHOULD BE USED WHEN
 UNING AN OPTIONAL CALCULATION FOR A NEW SERVICE,
 THEREFORE THE A/C LOAD WOULD BE CALCULATED AT 65%. THE
 PROPOSED SERVICE IS SUFFICIENT, BUT CALCULATION NEEDS
 TO BE CORRECT FOR CLARITY AND COMPLIANCE.
  
 5} SHOW THE LOCATION OF THE A/C EQUIPMENT (CONDENSING
 UNIT) ON THE PLAN. ALSO SHOW COMPLIANCE WITH THE
 REQUIRED RECEPTACLE PER 210.63, DISCONNECT PER 440.14.
  
 6} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. SEE REVIEWED
 PLAN FOR LOCATIONS.
  
 7} BEDROOM #2 RECEPTACLE SPACING MUST COMPLY WITH
 210.52(B).
  
 8} THE SMOKE ALARM CIRCUIT LISTED IN THE PANEL SCHEDULE
 MUST BE AFCI PER 210.12.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-12-06 Cont ID  
Sent By rmcdouga Date 2007-02-05 Time 15:40 Rev Time 0.50
Received By btrobaug Date 2006-12-06 Time 07:39 Sent To M
Notes
2006-12-06 08:55:09 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW
  
 THE DESCRIPTION ON THE APPLICATION DOES NOT INDICATE TO
 WHAT EXTENT THE ELECTRICAL SYSTEM IS TO BE AFFECTED BY
 THIS PERMIT.
 THEREFORE THIS REVIEW IS BASED ON A COMPLETE REWIRE.
 SINCE THERE IS NO LOAD CALCULATIONS OR RISER DIAGRAM,
 THIS REVIEW ASSUMES THE EXISTING SERVICE TO BE ADEQUATE
 AND THEREFORE NOT PART OF THIS APPLICATION.
  
 1}PLEASE PROVIDE A PANEL SCHEDULE(S) INDICATING
 OVERCURRENTAND CONDUCTOR SIZES PER 310.16,ALSO
 COMPLIANCE OF THE DEDICATED CIRCUIT ARTICLES FOR SMALL
 APPLIANCES, BATHROOMS ETC, PER 408.4 NEC AND
 106.3.5.4(8) FBC.
  
 2} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2.
  
 3} SMOKE DETECTORS MUST BE INSTALLED TO COMPLY WITH
 R313.1 RESIDENTIAL FLORIDA BUILDING CODE.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-05-02 Cont ID  
Sent By adarroug Date 2007-05-02 Time 13:46 Rev Time 0.00
Received By adarroug Date 2007-05-02 Time 13:46 Sent To E
Notes
2007-05-02 13:46:42TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-02-13 Cont ID  
Sent By adarroug Date 2007-02-13 Time 16:42 Rev Time 0.00
Received By adarroug Date 2007-02-13 Time 16:42 Sent To E
Notes
2007-02-13 16:42:52TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-02-05 Cont ID  
Sent By rmcdouga Date 2007-02-05 Time 15:40 Rev Time 0.00
Received By rmcdouga Date 2006-11-29 Time 18:30 Sent To E
Notes
2006-11-29 18:30:36TO ELECTRICAL BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-02-22 Cont ID  
Sent By tgordon Date 2007-02-22 Time 11:35 Rev Time 0.25
Received By tgordon Date 2007-02-22 Time 11:35 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-12-12 Cont ID  
Sent By tgordon Date 2006-12-12 Time 08:26 Rev Time 0.30
Received By tgordon Date 2006-12-12 Time 08:26 Sent To B
Notes
2006-12-12 08:37:00*** DENIED ***
 1) MECHANICAL PLANS NEED TO BE SIGNED AND SEALED BY THE
 ENGINEER OF GLOBAL ENGINEERING CONSULTANAS, INC. AS
 THERE INFOMATION IS IN THE TITAL BLOCK, PER FAC
 61G15-23.002.
  
 2) THE ENGINEERING FIRM GLOBAL ENGINEERING NEEDS THEIR
 CERTIFICATE OF AUTHORIZATION NUMBER IN THE TITAL BLOCK,
 PER FAC 61G15-23.002.
  
 3) ALL OF THE RETURN AIR TRANSFER DUCTS ARE TO SMALL.
 BALANCED RETURN AIR MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.