| Plan Review Stops For Permit 06110795 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2007-02-22 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2007-02-22 |
Time |
18:03 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2007-02-22 |
Time |
18:03 |
Sent To |
|
|
| Notes |
| 2007-02-22 18:24:11 | BUILDING PROVISO | | | | | | THE INSULATION IN THE CEILING IS REQUIRED TO HAVE A | | | MINIMUM R VALUE OF R-19 PER FBC 13-604.1.ABC.1. | | | | | | INSULATION ON RENOVATED WALLS SHALL COMPLY WITH FBC | | | 13-602.1.C.1.1 AND 13-602.1.C.2. | | | THE INSULATION AT MASONRY WALLS IS REQUIRED TO HAVE AN | | | R VALUE OF R-5. | | | THE INSULATION AT WOOD FRAME WALLS IS REQUIRED TO HAVE | | | AN R VALUE OF R-11 FOR 2 X 4 WALLS AND R-19 FOR 2 X 6 | | | WALLS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-02-05 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2007-02-05 |
Time |
15:40 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2007-02-05 |
Time |
14:53 |
Sent To |
|
|
| Notes |
| 2007-02-05 15:39:59 | DENIED BY BUILDING | | | | | | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT | | | MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) PLANS ARE REQUIRED TO HAVE THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THEM. FBC* 106. | | | | | | 3) FBC * 106.1.1 REQUIRES CONSTRUCTION DOCUMENTS SHALL | | | BE OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, | | | NATURE AND EXTENT OF THE WORK PROPOSED AND SHOW IN | | | DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS | | | CODE AND RELEVANT LAWS, ORDINANCES, RULES AND | | | REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
N |
Date |
2007-05-31 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-05-31 |
Time |
09:43 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2007-05-31 |
Time |
09:39 |
Sent To |
PC |
|
| Notes |
| 2007-05-31 09:42:57 | | | | REVISION DENIED/INCOMPLETE INFORMATION | | | | | | CONTRACTOR HAS FILE COPY AND APPLICATION FOR THIS | | | PROJECT. PER OUR PHONE CONVERSATION 5/29/07 HE WILL | | | BRING THEM IN AT WHICH TIME THIS REVISION CAN BE | | | REVIEWED | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2007-03-02 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-03-02 |
Time |
16:02 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2007-03-02 |
Time |
15:54 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-02-22 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-02-22 |
Time |
08:58 |
Rev Time |
1.00 |
| Received By |
btrobaug |
Date |
2007-02-22 |
Time |
07:24 |
Sent To |
M |
|
| Notes |
| 2007-02-22 08:47:49 | | | | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} SHOW THE PHYSICAL LOCATION OF ALL SERVICE EQUIPMENT | | | ON THE PLAN. 215.5,230.70(A)(1), 110.26. | | | | | | 2} PER 110.9 AND 110.10: OBTAIN THE | | | AVAILABLE FAULT CURRENT AT THE UTILITY | | | AND CALCULATE THE SAME AT THE EQUIPMENT. | | | INDICATE THE AIC RATING FOR THE | | | EQUIPMENT IS EQUAL TO OR GREATER THAN | | | THE AVAILABLE FAULT. THE INFORMATION FROM FPL WAS | | | SUBMITTED BUT THE RATING OF THE EQUIPMENT WAS NOT | | | INDICATED. | | | | | | 3} THE EQUIPMENT GROUND BETWEEN THE METER AND | | | DISCONNECT ON THE RISER DIAGRAM CREATES A PARALLEL PATH | | | TO GROUND WITH THE NEUTRAL AND MUST BE REMOVED. AN | | | ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE TO BE RAN | | | FROM THE FIRST MEANS OF DISCONNECT. 250.6. | | | | | | 4} THE A/C LOAD IN THE CALCULATION IS INCORRECT. THE | | | DESIGNER IS USING 220.83"THIS SECTION SHALL BE | | | PERMITTED TO BE USED TO DETERMINE IF THE EXISTING | | | SERVICE OR FEEDER IS OF SUFFICIENT CAPACITY TO SERVE | | | ADDITIONAL LOADS." ARTICLE 220.82 SHOULD BE USED WHEN | | | UNING AN OPTIONAL CALCULATION FOR A NEW SERVICE, | | | THEREFORE THE A/C LOAD WOULD BE CALCULATED AT 65%. THE | | | PROPOSED SERVICE IS SUFFICIENT, BUT CALCULATION NEEDS | | | TO BE CORRECT FOR CLARITY AND COMPLIANCE. | | | | | | 5} SHOW THE LOCATION OF THE A/C EQUIPMENT (CONDENSING | | | UNIT) ON THE PLAN. ALSO SHOW COMPLIANCE WITH THE | | | REQUIRED RECEPTACLE PER 210.63, DISCONNECT PER 440.14. | | | | | | 6} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH | | | 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. SEE REVIEWED | | | PLAN FOR LOCATIONS. | | | | | | 7} BEDROOM #2 RECEPTACLE SPACING MUST COMPLY WITH | | | 210.52(B). | | | | | | 8} THE SMOKE ALARM CIRCUIT LISTED IN THE PANEL SCHEDULE | | | MUST BE AFCI PER 210.12. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-12-06 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2007-02-05 |
Time |
15:40 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2006-12-06 |
Time |
07:39 |
Sent To |
M |
|
| Notes |
| 2006-12-06 08:55:09 | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW | | | | | | THE DESCRIPTION ON THE APPLICATION DOES NOT INDICATE TO | | | WHAT EXTENT THE ELECTRICAL SYSTEM IS TO BE AFFECTED BY | | | THIS PERMIT. | | | THEREFORE THIS REVIEW IS BASED ON A COMPLETE REWIRE. | | | SINCE THERE IS NO LOAD CALCULATIONS OR RISER DIAGRAM, | | | THIS REVIEW ASSUMES THE EXISTING SERVICE TO BE ADEQUATE | | | AND THEREFORE NOT PART OF THIS APPLICATION. | | | | | | 1}PLEASE PROVIDE A PANEL SCHEDULE(S) INDICATING | | | OVERCURRENTAND CONDUCTOR SIZES PER 310.16,ALSO | | | COMPLIANCE OF THE DEDICATED CIRCUIT ARTICLES FOR SMALL | | | APPLIANCES, BATHROOMS ETC, PER 408.4 NEC AND | | | 106.3.5.4(8) FBC. | | | | | | 2} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2. | | | | | | 3} SMOKE DETECTORS MUST BE INSTALLED TO COMPLY WITH | | | R313.1 RESIDENTIAL FLORIDA BUILDING CODE. | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-05-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-05-02 |
Time |
13:46 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-05-02 |
Time |
13:46 |
Sent To |
E |
|
| Notes |
| 2007-05-02 13:46:42 | TO "BTROBAUG" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-02-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-02-13 |
Time |
16:42 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-02-13 |
Time |
16:42 |
Sent To |
E |
|
| Notes |
| 2007-02-13 16:42:52 | TO "BTROBAUG" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-02-05 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2007-02-05 |
Time |
15:40 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2006-11-29 |
Time |
18:30 |
Sent To |
E |
|
| Notes |
| 2006-11-29 18:30:36 | TO ELECTRICAL BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2007-02-22 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-02-22 |
Time |
11:35 |
Rev Time |
0.25 |
| Received By |
tgordon |
Date |
2007-02-22 |
Time |
11:35 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2006-12-12 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-12-12 |
Time |
08:26 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2006-12-12 |
Time |
08:26 |
Sent To |
B |
|
| Notes |
| 2006-12-12 08:37:00 | *** DENIED *** | | | 1) MECHANICAL PLANS NEED TO BE SIGNED AND SEALED BY THE | | | ENGINEER OF GLOBAL ENGINEERING CONSULTANAS, INC. AS | | | THERE INFOMATION IS IN THE TITAL BLOCK, PER FAC | | | 61G15-23.002. | | | | | | 2) THE ENGINEERING FIRM GLOBAL ENGINEERING NEEDS THEIR | | | CERTIFICATE OF AUTHORIZATION NUMBER IN THE TITAL BLOCK, | | | PER FAC 61G15-23.002. | | | | | | 3) ALL OF THE RETURN AIR TRANSFER DUCTS ARE TO SMALL. | | | BALANCED RETURN AIR MAY BE ACHIEVED BY. | | | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY | | | INCREASING THE RETURN TRANSFER ONE AND | | | ONE HALF TIMES THE CROSS SECTIONAL AREA | | | (SQUARE INCHES) OF THE SUPPLY DUCT | | | ENTERING THE ROOM OR SPACE IT'S SERVING | | | AND THE DOOR HAVING AT LEAST AN | | | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE | | | PROPER RETURN AIR BALANCE. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|