| 2006-11-28 09:35:37 | DENIED BY BUILDING |
| | |
| | 1)PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. SUBMIT COVERSHEETS WITH STATE FL NUMBERS. |
| | |
| | 2) PRODUCT APPROVAL FOR CERTAINTEED MODIFIED SYSTEM HAS |
| | BEEN REVISED BY NOA 03-0827.02. PLEASE SUBMIT THIS NOA |
| | AND STATE COVERSHEET WITH FL 479-R1. |
| | |
| | 3) THE SBS MODIFIED SYSTEM THAT IS SPECIFIED HAS A |
| | MAXIMUM DESIGN PRESSURE OF -45 PSF WHICH IS TOO LOW FOR |
| | THE PERIMETER AND CORNER AREAS. LIMITATION #9 IS ALSO |
| | SPECIFIED, WHICH DOES NOT ALLOW THE PRESSURE TO BE |
| | INCREASE BY ENHANCED FASTENING. THEREFORE THIS SYSTEM |
| | IS NOT ACCEPTABLE. |
| | NOTE: LIMITATION NUMBER 7 DOES ALLOW ENHANCED |
| | FASTENING. HOWEVER, THE RAS 117 CALCULATIONS ARE |
| | REQUIRED TO BE PREPARED, SIGNED AND SEALED BY A FLORIDA |
| | REGISTERED ENGINEER, ARCHITECT OR REGISTERED ROOF |
| | CONSULTANT. SEE PAGE 30 OF THE NOA. |
| | |
| | 4) THE MINIMUM SLOPE FOR ASPHALT SHINGLES IS TWO UNITS |
| | VERTICAL IN 12 UNITS HORIZONTAL AND TWO LAYERS OF |
| | UNDERLAYMENT IS REQUIRED FOR SLOPES LESS THAN 4/12 PER |
| | FBC 1507.2.8. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |