| 2007-06-29 14:30:57 | BUILDING PLAN REVIEW |
| | PERMIT:06110765 |
| | ADD:9189TH STREET |
| | CONT: KING KAMREN CONST |
| | TEL: (561)502-1052 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW 2ND |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | NOTE: ONE OF THE REGISTERED PROFESSIONAL BELOW SHALL |
| | PERFORM THE WORK FOR THIS PROJECT. |
| | |
| | 1)A"REGISTERED ELEVATOR COMPANY" MEANS AN ENTITY |
| | REGISTERED WITH AND AUTHORIZED BY THE DIVISION |
| | EMPLOYING PERSONS TO CONSTRUCT, INSTALL, INSPECT, |
| | MAINTAIN, OR REPAIR ANY VERTICAL CONVEYANCE. EACH |
| | REGISTERED ELEVATOR COMPANY MUST ANNUALLY REGISTER WITH |
| | THE DIVISION AND MAINTAIN GENERAL LIABILITY INSURANCE |
| | COVERAGE IN THE MINIMUM AMOUNTS SET BY RULE. |
| | |
| | 2)A"CERTIFIED ELEVATOR TECHNICIAN" MEANS A NATURAL |
| | PERSON AUTHORIZED BY THE DIVISION TO CONSTRUCT, |
| | INSTALL, MAINTAIN, OR REPAIR ANY VERTICAL CONVEYANCE, |
| | AFTER HAVING BEEN ISSUED AN ELEVATOR CERTIFICATE OF |
| | COMPETENCY BY THE DIVISION. EACH CERTIFIED ELEVATOR |
| | TECHNICIAN MUST ANNUALLY REGISTER WITH THE DIVISION AND |
| | BE COVERED BY GENERAL LIABILITY INSURANCE COVERAGE IN |
| | THE MINIMUM AMOUNTS SET BY THE DIVISION. |
| | |
| | 3) CONTACT THEDEPARTMENT OF BUSINESS REGULATION |
| | BUREAU OF ELEVATOR INSPECTION AUTOMATED CALL SYSTEM: |
| | 1-850-487-1395, SELECT HOTELS & RESTAURANTS, THEN |
| | ELEVATORS WWW.STATE.FL.US/DBPR/HR/ELEVATORS |
| | |
| | NEW********************** |
| | |
| | 4)3001.1 SCOPE. |
| | THIS CHAPTER GOVERNS THE DESIGN, CONSTRUCTION, |
| | INSTALLATION, ALTERATION AND REPAIR OF ELEVATORS AND |
| | CONVEYING SYSTEMS AND THEIR COMPONENTS. |
| | NOTE: OTHER ADMINISTRATIVE AND PROGRAMMATIC PROVISIONS |
| | MAY APPLY. SEE THE DEPARTMENT OF BUSINESS AND |
| | PROFESSIONAL REGULATION [DBPR] CHAPTER 399, FLORIDA |
| | STATUTES, AND 61C-5, FLORIDA ADMINISTRATIVE CODE . THE |
| | REGULATION AND ENFORCEMENT OF THE FOLLOWING SECTIONS OF |
| | THE ADOPTED CODES, AND THEIR ADDENDA, ARE PREEMPTED TO |
| | THE BUREAU OF ELEVATOR SAFETY OF THE DEPARTMENT OF |
| | BUSINESS AND PROFESSIONAL REGULATION: ASME A 17.1, PART |
| | 8, ASME A17.3, SECTIONS 1.2, 1.5, ASME A 18.1, PART |
| | 10. |
| | |
| | 5)3001.5 DESIGN, INSTALLATION AND ALTERATION OF |
| | ELEVATORS. |
| | 1.EACH ELEVATOR SHALL COMPLY WITH THE ELEVATOR |
| | SAFETY CODE THAT WAS IN EFFECT AT THE TIME OF RECEIPT |
| | OF APPLICATION FOR THE CONSTRUCTION PERMIT FOR THE |
| | ELEVATOR. |
| | 2.EACH ALTERATION TO, OR RELOCATION OF, AN |
| | ELEVATOR SHALL COMPLY WITH THE ELEVATOR SAFETY CODE IN |
| | EFFECT AT THE TIME OF RECEIPT OF THE APPLICATION FOR |
| | THE CONSTRUCTION PERMIT FOR THE ALTERATION OR |
| | RELOCATION. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | 805-6726 |
| | |
| | |
| | |
| | |
| | |