Plan Review Details - Permit 06110756
Plan Review Stops For Permit 06110756
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2007-10-23 Cont ID  
Sent By rmcdouga Date 2007-10-23 Time 17:32 Rev Time 0.00
Received By rmcdouga Date 2007-10-23 Time 16:31 Sent To  
Notes
2007-10-23 16:58:36REVISION TO CHANGE ROOF COVERING ON ADDITION AND
 EXISTING STRUCTURE FROM ASPHALT SHINGLE TO CLAY TILE IS
 OK. THE ENTIRE ROOF INCLUDING TRUSSES OF THE EXISTING
 STRUCTURE WAS REPLACED. THE VALUE OF THE WORK HAS BEEN
 INCREASED BY $8000.00, AN ADDITIONAL PERMIT FEE OF
 $88.00 IS DUE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-08-31 Cont ID  
Sent By rmcdouga Date 2007-08-31 Time 17:47 Rev Time 0.00
Received By rmcdouga Date 2007-08-31 Time 17:21 Sent To  
Notes
2007-08-31 17:47:11REVISED SHEET 1 THAT WAS DENIED BY PLUMBING HAS BEEN
 RESUBMITTED AND REVIEWED FOR COMPLIANCE AND OK'D. STAMP
 AND PROCESS REVISED SHEETS 1,2 AND 3.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-08-16 Cont ID  
Sent By rmcdouga Date 2007-08-16 Time 09:37 Rev Time 0.00
Received By rmcdouga Date 2007-08-16 Time 07:34 Sent To  
Notes
2007-08-31 17:20:54REVISION TO SHEETS 1,2 AND 3 INCREASING THE SCOPE OF
 WORK ARE OK FOR BUILDING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-07-20 Cont ID  
Sent By rmcdouga Date 2007-07-20 Time 14:13 Rev Time 0.00
Received By rmcdouga Date 2007-07-20 Time 14:13 Sent To  
Notes
2007-07-20 15:10:14REVISION DENIED BY BUILDING
  
 1) THE VALUE OF THE PROJECT HAS INCREASED SIGNIFICANTLY
 DUE TO THE ADDITIONAL SCOPE OF WORK. PLEASE INDICATE
 THE COSTS OF THE ADDITIONAL WORK SO THAT THE VALUE OF
 THE JOB CAN BE ADJUSTED. ADDITIONAL PERMIT FEES WILL BE
 ASSESSED.
  
 2)SPECIFY HOW THE GAS WATER HEATER IN THE GARAGE WILL
 BE PROTECTED FROM MECHANICAL DAMAGE AS REQUIRED BY FBC
 MECHANICAL 303.4.
  
 3)SHOW COMPLIANCE WITH R309.1 OPENING PROTECTION.
 OPENINGS FROM A PRIVATE GARAGE DIRECTLY INTO A ROOM
 USED FOR SLEEPING PURPOSES SHALL NOT BE PERMITTED.
 OTHER OPENINGS BETWEEN THE GARAGE AND RESIDENCE SHALL
 BE EQUIPPED WITH SOLID WOOD DOORS NOT LESS THAN 1-3 / 8
 INCHES (35 MM) IN THICKNESS, SOLID OR HONEYCOMB CORE
 STEEL DOORS NOT LESS THAN 1 3 / 8 INCHES (35 MM) THICK,
 OR 20-MINUTE FIRE-RATED DOORS. -
  
 4)SHOW COMPLIANCE WITH R309.2 SEPARATION REQUIRED.
 THE GARAGE SHALL BE SEPARATED FROM THE RESIDENCE AND
 ITS ATTIC AREA BY NOT LESS THAN 1/2 -INCH (12.7 MM)
 GYPSUM BOARD APPLIED TO THE GARAGE SIDE. GARAGES
 BENEATH HABITABLE ROOMS SHALL BE SEPARATED FROM ALL
 HABITABLE ROOMS ABOVE BY NOT LESS THAN 5 / 8 -INCH
 (15.9 MM) TYPE X GYPSUM BOARD OR EQUIVALENT. WHERE THE
 SEPARATION IS A FLOOR-CEILING ASSEMBLY, THE STRUCTURE
 SUPPORTING THE SEPARATION SHALL ALSO BE PROTECTED BY
 NOT LESS THAN 1/2-INCH (12.7 MM) GYPSUM BOARD OR
 EQUIVALENT.
  
 5) REVISE THE ROOF SHEATHING FASTENING NOTES ON SHEET 2
 TO COMPLY WITH FBC R803.2.3.1 OF 2006 REVISIONS TO 2004
 FBC RESIDENTIAL CODE. WHICH REQUIRES 8D RING-SHANK
 NAILS AT 6 INCHES ON CENTER IN ROOF ZONES 1 AND 2 AND 4
 INCHES ON CENTER IN ROOF ZONE 3 (CORNERS) IN ACCORDANCE
 WITH FIGURE R803.2.3.1.
  
 6) THE SIMPSON CONNECTOR CATALOG REQUIRES A MINIMUM 12"
 EMBED FOR THE MGT 5/8" EPOXY SET THREADED ROD. PLEASE
 REVISE CONNECTOR NOTE ON SHEET 2.
  
 7) SPECIFY THE GARAGE DOOR WINDLOAD PRESSURES ON THE
 PLANS. SEE SHEET 1.
  
 8)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. THE SIGNED AND SEALED
 LETTER SUBMITTED IS NOT SPECIFIC AND NOT ACCEPTABLE.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-03-20 Cont ID  
Sent By rmcdouga Date 2007-03-20 Time 18:41 Rev Time 0.00
Received By rmcdouga Date 2007-03-20 Time 18:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-02-28 Cont ID  
Sent By rmcdouga Date 2007-02-28 Time 07:37 Rev Time 0.00
Received By rmcdouga Date 2007-02-28 Time 06:14 Sent To  
Notes
2007-02-28 07:37:50DENIED BY BUILDING
  
 1) THE REAR SET BACK ON THE SURVEY DOES NOT CONCUR WITH
 THE SITE PLAN. PLEASE CORRECT. SEE ZONING COMMENTS.
  
 2) THE UPLIFT VALUE LISTED ON THE PLANS FOR THE RT16 IS
 INCORRECT FOR THE NUMBER AND TYPE OF FASTENERS THAT ARE
 SPECIFIED. ACCORDING TO THE USP TECHNICAL BULLETIN THE
 UPLIFT IS 700.
  
 3) RE- SUBMIT THE FIRST SHEET OF THE OLD PLANS WHICH
 HAS THE STAMP FOR THE COUNTY IMPACT FEES OR HAVE THE
 NEW PLANS STAMPED BY THE COUNTY.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-02-06 Cont ID  
Sent By rmcdouga Date 2007-02-06 Time 07:32 Rev Time 0.00
Received By rmcdouga Date 2007-02-05 Time 16:54 Sent To  
Notes
2007-02-06 07:32:08DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SUBMIT A COPY OF THE PAID RECEIPT FOR THE IMPACT
 FEES.
  
 3) ON SHEET 1, FOUNDATION NOTE 2 SPECIFIES 18 " DOWELS
 EMBEDDED 4" INTO EXISTING SLAB AND 18 " INTO NEW SLAB.
 THIS WOULD REQUIRE A 22" DOWEL PLEASE CORRECT.
  
 4) TRUSS DESIGN DRAWINGS, PREPARED IN CONFORMANCE WITH
 SECTION R802.1.6.1 , SHALL BE PROVIDED TO THE BUILDING
 OFFICIAL AND APPROVED PRIOR TO INSTALLATION. TRUSS
 DRAWINGS ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 TRUSS ENGINEER AND REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD FOR THE PROJECT.
  
 5) THE ROOF SHEATHING FASTENING NOTE ON SHEET 2
 SPECIFIES FASTENER SPACING 4" OC AT GABLES. THE 4"
 SPACING IS REQUIRED IN ROOF ZONE 3, WHICH ALSO INCLUDES
 THE OUTSIDE CORNERS OF HIP AND FLAT ROOFS. PLEASE
 REVISE. SEE FBC FIGURE 1609.6.2.2.
  
 6) THE TRUSS CONNECTOR SCHEDULE ON SHEET 2 SPECIFIES
 USP RT16A AND RT-16-2 WOOD FRAME TO WOOD TRUSS
 CONNETORS WITH 8D NAILS TO STRUCTURE. THESE ARE
 SPECIFIED AT THE EXISTING CONCRETE/MASONRY WALL. PLEASE
 CORRECT.
  
 7) TWO RT16-2 ARE SPECIFIED TO ANCHOR A GIRDER TRUSS TO
 THE EXISTING CBS STRUCTURE. IT DOES NOT APPEAR THAT TWO
 OF THESE CONNECTORS COULD BE INSTALLED AT THIS
 LOCATION. PLEASE REVIEW AND IF THIS IS CORRECT, PROVIDE
 A DETAIL AS TO HOW THEY SHOULD BE INSTALLED.
  
 8) SUBMIT PRODUCT APPROVALS FOR THE HALF-LITE OUTSWING
 DOORS AT THE MASTER BEDROOM AND THE KITCHEN.
  
 9) SUBMIT AN INSTALLATION SCHEDULE FOR THE STORM PANELS
 AT THE KITCHEN AND MASTER BEDROOM DOORS. SPECIFY THE
 FASTENER TYPE AND SPACING, THE TYPE OF MOUNT , THE
 CONNECTION TYPE, THE EDGE DISTANCE, THE PANEL SPAN, THE
 DESIGN LOAD, ETC.
  
 NOTE : VALUE OF THE WORK HAS BEEN INCREASED TO $
 162,068 AND RADON FEES ADDED. ADDITIONAL FEES ARE DUE.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-12-31 Cont ID  
Sent By btrobaug Date 2007-12-31 Time 12:14 Rev Time 0.00
Received By btrobaug Date 2007-12-31 Time 11:40 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-07-19 Cont ID  
Sent By btrobaug Date 2007-07-19 Time 11:15 Rev Time 0.00
Received By btrobaug Date 2007-07-19 Time 10:44 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-12-14 Cont ID  
Sent By btrobaug Date 2006-12-14 Time 12:57 Rev Time 0.50
Received By btrobaug Date 2006-12-14 Time 12:12 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2008-04-01 Cont ID  
Sent By adarroug Date 2008-04-01 Time 16:38 Rev Time 0.00
Received By adarroug Date 2008-04-01 Time 16:38 Sent To Z
Notes
2008-04-01 16:38:31TO "Z" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2008-03-14 Cont ID  
Sent By adarroug Date 2008-03-14 Time 16:03 Rev Time 0.00
Received By adarroug Date 2008-03-14 Time 16:03 Sent To Z
Notes
2008-03-14 16:03:56TO "Z" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2008-02-08 Cont ID  
Sent By adarroug Date 2008-02-08 Time 16:51 Rev Time 0.00
Received By adarroug Date 2008-02-08 Time 16:51 Sent To Z
Notes
2008-02-08 16:51:29TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2008-01-07 Cont ID  
Sent By adarroug Date 2008-01-07 Time 08:59 Rev Time 0.00
Received By adarroug Date 2008-01-07 Time 08:59 Sent To M
Notes
2008-01-07 08:59:30TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-12-21 Cont ID  
Sent By mmiller Date 2007-12-21 Time 16:35 Rev Time 0.00
Received By mmiller Date 2007-12-21 Time 16:34 Sent To E
Notes
2007-12-21 16:35:12SENT TO "BT" DESK MMILLER

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-10-23 Cont ID  
Sent By adarroug Date 2007-10-23 Time 11:00 Rev Time 0.00
Received By adarroug Date 2007-10-23 Time 10:59 Sent To B
Notes
2007-10-23 11:00:23TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-08-22 Cont ID  
Sent By adarroug Date 2007-08-22 Time 13:17 Rev Time 0.00
Received By adarroug Date 2007-08-22 Time 13:17 Sent To P
Notes
2007-08-22 13:17:40TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-08-06 Cont ID  
Sent By adarroug Date 2007-08-06 Time 16:12 Rev Time 0.00
Received By adarroug Date 2007-08-06 Time 16:12 Sent To Z
Notes
2007-08-06 16:13:08TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-07-10 Cont ID  
Sent By adarroug Date 2007-07-10 Time 16:38 Rev Time 0.00
Received By adarroug Date 2007-07-10 Time 16:38 Sent To Z
Notes
2007-07-10 16:38:19TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-03-09 Cont ID  
Sent By adarroug Date 2007-03-09 Time 10:19 Rev Time 0.00
Received By adarroug Date 2007-03-09 Time 10:19 Sent To M
Notes
2007-03-09 10:20:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-03-05 Cont ID  
Sent By adarroug Date 2007-03-05 Time 09:30 Rev Time 0.00
Received By adarroug Date 2007-03-05 Time 09:30 Sent To Z
Notes
2007-03-05 09:30:47TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-02-26 Cont ID  
Sent By adarroug Date 2007-02-26 Time 16:06 Rev Time 0.00
Received By adarroug Date 2007-02-26 Time 16:06 Sent To M
Notes
2007-02-26 16:06:23TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-02-21 Cont ID  
Sent By adarroug Date 2007-02-21 Time 10:58 Rev Time 0.00
Received By adarroug Date 2007-02-21 Time 10:35 Sent To Z
Notes
2007-02-21 10:58:28TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-02-06 Cont ID  
Sent By rmcdouga Date 2007-02-06 Time 07:32 Rev Time 0.00
Received By rmcdouga Date 2006-11-29 Time 17:28 Sent To  
Notes
2006-11-29 17:28:46SENT TO ZONING

Review Stop L LANDSCAPING
Rev No 2 Status P Date 2008-04-04 Cont ID  
Sent By rkussner Date 2008-04-04 Time 16:14 Rev Time 0.00
Received By rkussner Date 2008-04-04 Time 16:13 Sent To PC
Notes
2008-04-04 16:15:21PROVISO--100% IRRIGATION COVERAGE TO ALL LANDSCAPED
 AREAS IS REQUIRED.AN IRRIGATION PERMIT MUST BE
 OBTAINED.

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2008-04-03 Cont ID  
Sent By rkussner Date 2008-03-24 Time 15:24 Rev Time 0.00
Received By rkussner Date 2008-04-03 Time 15:12 Sent To  
Notes
2008-03-24 15:32:041.FIVE SHADE OR FLOWERING TREES ARE REQUIRED AND ONLY
 35% OF THESE REQUIRED TREES CAN BE PALMS.PLEASE ADD
 (2) SHADE OR FLOWERING TREES.
  
 2.PROVIDE SOD AND IRRIGATION IN THE RIGHT-OF-WAY,
 ADJACENT TO THE PROPERTY LINE.
  
 3.THE EUGENIA SPECIES USED SHALL BE NATIVE.EUGENIA
 UNIFLORA IS PROHIBITED.
  
 4.STAFF SUGGESTS THAT A LOW GROUND COVER BE ADDED IN
 FRONT OF THE HEDGE ALONG THE FOUNDATION OF THE
 STRUCTURE TO CREATE A TIERED EFFECT.THE PALMS SHALL
 BE INCORPORATED INTO THE PLANT BED.THIS WILL REDUCE
 MAINTENANCE.
  
 5.STAFF SUGGESTS THAT DRIVEWAYS, PATIOS AND WALKWAYS
 SHOULD BE KEPT A MINIMUM OF FIVE FEET FROM ANY PROPERTY
 LINE FOR DRAINAGE PURPOSES.
  
 6.THE MULCHED AREA IN THE REAR OF THE SITE IS NOT
 PERMITTED.EITHER A PLANTING OF SHRUBS AND GROUND
 COVERS OR SOD IS REQUIRED FOR THAT AREA.

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2008-01-09 Cont ID  
Sent By tgordon Date 2008-01-09 Time 09:33 Rev Time 0.40
Received By tgordon Date 2008-01-09 Time 09:33 Sent To  
Notes
2008-01-09 09:35:11REVISION TO MECH. PLAN PAGE 2 AND RECEIVED COOLING LOAD
 CAL'S.

Review Stop M MECHANICAL (A/C)
Rev No 7 Status F Date 2008-01-07 Cont ID  
Sent By tgordon Date 2008-01-07 Time 10:47 Rev Time 0.30
Received By tgordon Date 2008-01-07 Time 10:47 Sent To  
Notes
2008-01-07 10:57:14PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 ** MECHANICAL REVISION **
 *** DENIED ***
 1) THIS WAS PROVISO-ED 8-9-07 BUT NEEDS TO BE SUBMITTED
 WITH THIS REVISION. SUBMIT COOLING LOAD CALCULATIONS
 FOR REVIEW BEFORE DUCT ROUGH INSPECTION, SEE 2004 FBC
 13-607.1.ABC.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2007-08-30 Cont ID  
Sent By tgordon Date 2007-08-30 Time 08:06 Rev Time 0.15
Received By tgordon Date 2007-08-30 Time 08:06 Sent To B
Notes
2007-08-30 08:07:54REVISION PASSED REVIEW ON 8-9-07, WITH PROVISO.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-08-13 Cont ID  
Sent By tgordon Date 2007-08-09 Time 10:21 Rev Time 0.45
Received By tgordon Date 2007-08-09 Time 10:21 Sent To P
Notes
2007-08-09 10:53:00*** PROVISO ***
 1) SUBMIT COOLING LOAD CALCULATIONS FOR REVIEW BEFORE
 DUCT ROUGH INSPECTION, SEE 2004 FBC 13-607.1.ABC.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2007-07-24 Cont ID  
Sent By tgordon Date 2007-07-24 Time 09:30 Rev Time 0.30
Received By tgordon Date 2007-07-24 Time 09:30 Sent To P
Notes
2007-07-24 09:36:30*** REVISION DENIED ***
 1) PLEASE SUBMIT REVISED ENERGY CALCULATIONS, SEE 2004
 FBC 13-101.2.3.
  
 2) PROVIDE COMBUSTION AIR CALCULATIONS AND COMBUSTION
 AIR IF NEEDED FOR GAS WATER HEATER IN GARAGE, SEE 2004
 FBC/R G2407.1.
  
 3) PROVIDE COMBUSTION AIR CALCULATIONS AND COMBUSTION
 AIR OR MAKE-UP AIR FOR GAS CLOTHES DRYER, SEE 2004
 FBC/R G240.7.1 AND G2407.4.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-03-12 Cont ID  
Sent By tgordon Date 2007-03-12 Time 14:09 Rev Time 0.20
Received By tgordon Date 2007-03-12 Time 14:09 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-02-27 Cont ID  
Sent By tgordon Date 2007-02-27 Time 09:25 Rev Time 0.25
Received By tgordon Date 2007-02-27 Time 09:25 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-12-21 Cont ID  
Sent By tgordon Date 2006-12-21 Time 09:07 Rev Time 0.30
Received By tgordon Date 2006-12-21 Time 09:06 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 6 Status P Date 2007-08-24 Cont ID  
Sent By mperson Date 2007-08-24 Time 10:31 Rev Time 0.00
Received By mperson Date 2007-08-24 Time 10:31 Sent To Z
Notes
2007-08-24 10:35:35REVISION: SHEET 1 REV/#3,4,&5.
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]

Review Stop P PLUMBING
Rev No 5 Status F Date 2007-08-14 Cont ID  
Sent By mperson Date 2007-08-14 Time 08:34 Rev Time 0.33
Received By mperson Date 2007-08-14 Time 08:34 Sent To B
Notes
2007-08-14 08:43:07REVISION DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 1. SHEET 1 PLUMBING RISER DIAGRAM MUST REFLECT THE
 CHANGES IN BATH #3 WITH THE FOLLOWING INFORMATION PER
 FBC-2004 CHAPTER 1, SECTION 106.3.5.4 RESIDENTIAL (ONE
 AND TWO-FAMILY) PLEASE SUBMIT A PLUMBING SANITARY
 ISOMETRIC RISER DIAGRAM INDICATING ALL WASTE, VENTS,
 TRAPS AND SIZES WITH CLEANOUT LOCATIONS OF REVISED BATH
 #3.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]

Review Stop P PLUMBING
Rev No 4 Status F Date 2007-07-25 Cont ID  
Sent By tgordon Date 2007-08-13 Time 08:07 Rev Time 0.15
Received By mperson Date 2007-07-25 Time 11:50 Sent To PC
Notes
2007-07-25 13:24:29REVISION DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 FUEL GAS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET 1: PLEASE INDICATE HOW THE NEW GAS WATER
 HEATER IS TO BE PROTECTED IN THE PROPOSED 1 CAR GARAGE
 PER FBC-2004 FUEL GAS, SECTION 303.4 PROTECTION FROM
 PHYSICAL DAMAGE. APPLIANCES SHALL NOT BE INSTALLED IN A
 LOCATION WHERE SUBJECT TO PHYSICAL DAMAGE UNLESS
 PROTECTED BY APPROVED BARRIERS MEETING THE REQUIREMENTS
 OF THE FLORIDA FIRE PREVENTION CODE. FOR EXAMPLE, AN
 APPLIANCE (WATER HEATER) INSTALLED IN A GARAGE MIGHT BE
 SUBJECT TO VEHICLE IMPACT. BARRIERS MUST BE APPROVED
 AND STRONG ENOUGH TO RESIST THE TYPE OF IMPACT
 ANTICIPATED.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-03-13 Cont ID  
Sent By mperson Date 2007-03-13 Time 16:13 Rev Time 0.33
Received By mperson Date 2007-03-13 Time 16:13 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-02-27 Cont ID  
Sent By mperson Date 2007-02-27 Time 10:42 Rev Time 0.33
Received By mperson Date 2007-02-27 Time 10:42 Sent To B
Notes
2007-02-27 11:00:27 
 NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL INSPECTION.
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-12-19 Cont ID  
Sent By mperson Date 2006-12-19 Time 16:18 Rev Time 0.55
Received By mperson Date 2006-12-19 Time 16:18 Sent To M
Notes
2006-12-19 16:51:56DENIED
 REFERENCE: FBC-2004 PLUMBING AND FBC-2004 CHAPTER 1
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE COMPLIANCE PLEASE REFERENCE
 THE ATTACHED CORRECTED SANITARY RISER DIAGRAM IN RED
 INK FOR THE RESUBMITTAL:
  
 1. SHEET 1, PER FBC-2003 CHAPTER 1, SEC. 106.3.5.4
 RESIDENTIAL (ONE AND TWO
 FAMILY) SUBMIT A PLUMBING SANITARY
 ISOMETRIC RISER DIAGRAM INDICATING ALL
 WASTE, VENTS, TRAPS WITH SIZES, AND
 CLEANOUT LOCATIONS.
 NOTE: NOT ALL TRAPS ARE SIZED AND THE DISH WASHER IS
 MISSING.
  
 2. SHEET 1, PER FBC-2004 PLUMBING, SEC. 917.4 THE AIR
 ADMITTANCE VALVE IS INDICATED WRONG. THE AIR ADMITTANCE
 VALVE SHALL BE LOCATED A MINIUM OF 4 INCHES ABOVE THE
 HORIZONTAL BRANCH DRAIN OR FIXTURE DRAIN BEING VENTED.
  
 3. SHEET 1, PER FBC-2004 PLUMBING, THE FOLLOWING IS
 REQUIRED FOR THE WASHING MACHINE.
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING. PLEASE INDICATE STANDPIPE ON DRAWING.
 (C)708.9 ACCESS. ACCESS SHALL BE PROVIDED TO ALL
 CLEANOUTS. CLEANOUT FOR THE WASHING MACHINE TO BE AT
 FOUR FEET ABOVE FINNISH FLOOR AND INDICATED AS SUCH ON
 THE RESUBMITTAL.
  
 4. PER FBC-2004, PLUMBING, SECTION 909.1
 WET VENT PERMITTED: ONLY THE FIXTURES
 WITHIN THE BATHROOM GROUPS SHALL CONNECT
 TO THE WET-VENTED HORIZONTAL BRANCH
 DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE WET VENT.
 NOTE: ON SHEET 1, SANITARY RISER DIAGRAM ALL
 BATHROOM-GROUPS ARE NON CODE COMPLIANT. PLEASE
 REFERENCE THE ATTACHED CORRECTED SANITARY RISER DIAGRAM
 IN RED INK FOR THE RESUBMITTAL.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  

Review Stop Z ZONING
Rev No 9 Status P Date 2008-04-04 Cont ID  
Sent By adavila Date 2008-04-04 Time 12:21 Rev Time 0.00
Received By adavila Date 2008-04-03 Time 12:20 Sent To L
Notes
2008-04-04 12:21:16PER ERIC SCHNEIDER, PRINCIPAL PLANNER.

Review Stop Z ZONING
Rev No 8 Status F Date 2008-03-25 Cont ID  
Sent By adavila Date 2008-03-25 Time 10:25 Rev Time 0.00
Received By adavila Date 2008-03-24 Time 16:21 Sent To I
Notes
2008-03-25 10:26:23PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. PLEASE INDICATE WHETHER THE PAVERS WILL BE SEALED OR
 UNSEALED PAVERS.IN THE EVENT OF SEALED PAVERS, THE
 LESSER OF 1,000 SQUARE FEET OR 75 PERCENT OF THE FRONT
 YARD AREA SHALL BE LANDSCAPED.
  
 2. PREVIOUSLY APPROVED PLANS SHOWED THE A/C UNIT ALONG
 THE NORTH BUILDING FA?ADE; HOWEVER THE LANDSCAPE PLAN
 SHOWS THE A/C UNIT TO BE LOCATED ALONG THE SOUTH
 BUILDING FA?ADE OF THE NEW ADDITION.PROVIDE SETBACK
 DIMENSIONS TO THE A/C UNIT.PLEASE NOTE THAT PER
 SECTION 94-305(B)(4), MECHANICAL EQUIPMENTS MAY NOT
 PROJECT MORE THAN 4 FEET INTO A SETBACK.
  
 3. PURSUANT TO ARTICLE XIX OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS, OPEN SPACE MEANS AN OPEN,
 UNENCLOSED AREA CONSISTING OF SETBACKS, LANDSCAPING,
 BUFFERS, VEHICULAR AND PEDESTRIAN CIRCULATION FEATURES,
 AND SURFACE PARKING.LANDSCAPING CALCULATIONS SHALL BE
 REVISED TO INCLUDE THE ACTUAL OPEN SPACE AREA OF THE
 PROPERTY.
  
 4. PURSUANT TO SECTION 94-442(B)(1), ALL OPEN SPACE,
 EXCLUDING VEHICULAR AND PEDESTRIAN CIRCULATION FEATURES
 AND SURFACE PARKING, SHALL BE COVERED WITH GRASS,
 GROUND COVER, SHRUBBERY, OR OTHER SUITABLE PLANT
 MATERIAL.PROVIDE DETAILS OF WHAT THE MULCH AREA NORTH
 OF THE BUILDING IS GOING TO BE USED FOR.IF THIS IS TO
 BE OPEN SPACE OR YARD, THEN MULCH MAY NOT BE USED.
  
 5. SHOW COMPLIANCE WITH THE XERISCAPE REQUIREMENTS
 OUTLINED IN SECTION 94-442(G) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 7 Status F Date 2008-02-13 Cont ID  
Sent By adavila Date 2008-02-13 Time 08:21 Rev Time 0.00
Received By adavila Date 2008-02-12 Time 10:00 Sent To I
Notes
2008-02-13 08:21:44PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. PROVIDE THE TOTAL SQUARE FOOTAGE OF THE PROPOSED
 CONCRETE DRIVEWAY AND WALKWAYS WITHIN THE FRONT YARD.
  
 2. PROVIDE WIDTH AND DEPTH DIMENSIONS OF THE WALKWAY IN
 FRONT OF THE MAIN FRONT ENTRANCE.
  
 3. PURSUANT TO SECTION 94-482(A), THE LESSER OF 1,000
 SQUARE FEET OR 75 PERCENT OF THE FRONT YARD AREA MUST
 BE LANDSCAPED.PROVIDE LANDSCAPE AREA CALCULATIONS.
  
 4. PURSUANT TO SECTION 94-441(C)(2), RENOVATIONS,
 REPAIR, ALTERATION OR REDEVELOPMENT WHICH EXCEED 50
 PERCENT OF THE VALUE OF THE STRUCTURE SHALL COMPLY WITH
 ARTICLE XIV OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS.THE WORK VALUE OF THIS PERMIT ($206,000)
 EXCEEDS THE VALUE OF THE STRUCTURE PER THE PROPERTY
 APPRAISER?S OFFICE ($79,793).
  
 5. PROVIDE 2 COPIES OF A LANDSCAPE PLAN SHOWING
 COMPLIANCE WITH ARTICLE XIV OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS, TO INCLUDE THE COMMENTS STATED
 ABOVE.PLEASE NOTE THAT PER SECTION 94-442(A),
 LANDSCAPE PLANS FOR SINGLE-FAMILY DWELLING UNITS DO NOT
 NEED TO BE SIGNED AND SEALED BY A FLORIDA REGISTERED
 LANDSCAPE ARCHITECT.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 6 Status P Date 2007-08-29 Cont ID  
Sent By adavila Date 2007-08-29 Time 08:21 Rev Time 0.00
Received By adavila Date 2007-08-28 Time 08:21 Sent To M
Notes
2007-08-29 08:59:36PER ERIC SCHNEIDER, PRINCIPAL PLANNER.
  
 PLANNING AND ZONING DEPARTMENT
  
 ***PASSED***
  
 PLEASE NOTE THAT THE PROPOSED POOL AND POOL DECK SHALL
 BE APPROVED ON A DIFFERENT BUILDING PERMIT.

Review Stop Z ZONING
Rev No 5 Status P Date 2007-08-08 Cont ID  
Sent By adavila Date 2007-08-08 Time 13:04 Rev Time 0.00
Received By adavila Date 2007-08-07 Time 09:29 Sent To I
Notes
2007-08-08 13:05:01PER ERIC SCHNEIDER, PRINCIPAL PLANNER.
  
 PLANNING AND ZONING DEPARTMENT
  
 ***PASSED***
  
 PLEASE NOTE THAT THE PROPOSED POOL AND POOL DECK SHALL
 BE APPROVED ON A DIFFERENT BUILDING PERMIT.

Review Stop Z ZONING
Rev No 4 Status P Date 2007-07-12 Cont ID  
Sent By adavila Date 2007-07-12 Time 16:15 Rev Time 0.00
Received By adavila Date 2007-07-11 Time 17:07 Sent To M
Notes
2007-07-12 16:15:56PER ERIC SCHNEIDER, PRINCIPAL PLANNER.
  
 PLANNING AND ZONING DEPARTMENT
  
 ***PASSED***
  
 PLEASE NOTE THAT THE PROPOSED POOL AND POOL DECK SHALL
 BE APPROVED ON A DIFFERENT BUILDING PERMIT.

Review Stop Z ZONING
Rev No 3 Status P Date 2007-03-08 Cont ID  
Sent By adavila Date 2007-03-08 Time 16:19 Rev Time 0.00
Received By adavila Date 2007-03-07 Time 15:39 Sent To I
Notes
2007-03-08 16:20:34PER ERIC SCHNEIDER, PRINCIPAL PLANNER.
  
 PLANNING AND ZONING
  
 ***PASSED***
  
 PLEASE NOTE THAT THE PROPOSED POOL AND POOL DECK SHALL
 BE APPROVED ON A DIFFERENT BUILDING PERMIT.

Review Stop Z ZONING
Rev No 2 Status F Date 2007-02-23 Cont ID  
Sent By adavila Date 2007-02-23 Time 18:53 Rev Time 0.00
Received By adavila Date 2007-02-23 Time 18:53 Sent To I
Notes
2007-02-23 18:56:10PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. PLEASE PROVIDE RESPONSE TO COMMENTS IN WRITING.
  
 2. SURVEY SHOWS THE PROPOSED ADDITION'S REAR SETBACK IS
 8.9; HOWEVER, ACCORDING TO THE SITE PLAN, THE PROPOSED
 REAR SETBACK IS 8.45.PLEASE INDICATE THE CORRECT
 PROPOSED REAR SETBACK ON BOTH THE SURVEY AND SITE
 PLAN.
  
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL
 PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-12-09 Cont ID  
Sent By mmclean Date 2006-12-09 Time 16:10 Rev Time 0.00
Received By mmclean Date 2006-12-09 Time 16:10 Sent To I
Notes
2006-12-09 16:19:48DENIED,
 1. THE PROPOSED ADDITION MUST MEET THE REAR SETBACK OF
 15FT OR 10% OF LOT DEPT.PLANS SHOWS THE REAR SETBACK
 AT 8.45FT.
 2. PLEASE PROVIDE A COPY OF CURRENT SURVEY.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720