Plan Review Details - Permit 06110745
Plan Review Stops For Permit 06110745
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-03-09 Cont ID  
Sent By rmcdouga Date 2007-03-09 Time 17:52 Rev Time 0.00
Received By rmcdouga Date 2007-03-09 Time 12:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-02-05 Cont ID  
Sent By rmcdouga Date 2007-02-05 Time 14:12 Rev Time 0.00
Received By rmcdouga Date 2007-02-05 Time 11:19 Sent To  
Notes
2007-02-05 14:09:27DENIED BY BUILDING
  
 1)SUBMIT TWO CLEAR AND LEGIBLE COPIES OF THE ENERGY
 CALCULATION FORM SIGNED BY THE OWNER/AGENT.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) SHOW COMPLIANCE WITH SECTION 704 INSPECTION FOR
 TERMITES.
 IN ORDER TO PROVIDE FOR INSPECTION FOR TERMITE
 INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL COVERINGS
 AND FINAL EARTH GRADE ON THE EXTERIOR OF A BUILDING
 SHALL NOT BE LESS THAN 6 INCHES (152 MM). EXCEPTIONS:
 1.PAINT OR DECORATIVE CEMENTITIOUS FINISH LESS
 THAN 5 / 8 INCH (17.1 MM) THICK ADHERED DIRECTLY TO THE
 MASONRY FOUNDATION SIDEWALL.
 2.ACCESS OR VEHICLE RAMPS WHICH RISE TO THE
 INTERIOR FINISH FLOOR ELEVATION FOR THE WIDTH OF SUCH
 RAMPS ONLY.
 3.A 4-INCH (102 MM) INSPECTION SPACE ABOVE PATIO
 AND GARAGE SLABS AND ENTRY AREAS.
 4.IF THE PATIO HAS BEEN SOIL TREATED FOR TERMITES,
 THE FINISH ELEVATION MAY MATCH THE BUILDING INTERIOR
 FINISH FLOOR ELEVATIONS ON MASONRY CONSTRUCTION ONLY.
 5.MASONRY VENEERS.
  
 4) SHOW COMPLIANCE WITH R404.1.6 HEIGHT ABOVE FINISHED
 GRADE.
 CONCRETE AND MASONRY FOUNDATION WALLS SHALL EXTEND
 ABOVE THE FINISHED GRADE ADJACENT TO THE FOUNDATION AT
 ALL POINTS A MINIMUM OF 4 INCHES (102 MM) WHERE MASONRY
 VENEER IS USED AND A MINIMUM OF 6 INCHES (152 MM)
 ELSEWHERE.
  
 5) SHOW COMPLIANCE WITH R319.1.
 IN AREAS SUBJECT TO DECAY DAMAGE AS ESTABLISHED BY
 TABLE R301.2(1) , THE FOLLOWING LOCATIONS SHALL REQUIRE
 THE USE OF AN APPROVED SPECIES AND GRADE OF LUMBER,
 PRESSURE TREATED IN ACCORDANCE WITH AWPA C1, C2, C3,
 C4, C9, C15, C18, C22, C23, C24, C28, C31, C33, P1, P2
 AND P3, OR DECAY-RESISTANT HEARTWOOD OF REDWOOD, BLACK
 LOCUST, OR CEDARS.
 2.ALL WOOD FRAMING MEMBERS THAT REST ON CONCRETE
 OR MASONRY EXTERIOR FOUNDATION WALLS AND ARE LESS THAN
 8 INCHES (203 MM) FROM THE EXPOSED GROUND.
 5.WOOD SIDING, SHEATHING AND WALL FRAMING ON THE
 EXTERIOR OF A BUILDING HAVING A CLEARANCE OF LESS THAN
 6 INCHES (152 MM) FROM THE GROUND.
  
 6) PROVIDE EXTERIOR ELEVATIONS. FBC* 106.1.2.
  
 7) PROVIDE DETAIL OF FRAMING AND STRAPPING AT EXTERIOR
 WINDOWS.
  
 8) THE BOTTOM PLATE IS NOT SHOWN ON THE WALL SECTION ON
 SHEET 2.
  
 9)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE.
  
 10)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 11) SUBMIT PRODUCT APPROVALS FOR THE STRUCTURAL WINDOW
 MULLIONS USED TO CONNECT THE SINGLE HUNG WINDOWS TO THE
 FIXED WINDOWS ABOVE THEM.
  
 12) THE PRODUCT APPROVALS FOR THE PGT FRENCH DOORS ARE
 MISSING SOME OF THE PAGES OF DRAWING AND SOME ARE
 MISSING A PORTION OF THE TEXT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-03-08 Cont ID  
Sent By btrobaug Date 2007-03-08 Time 15:12 Rev Time 0.33
Received By btrobaug Date 2007-03-08 Time 15:03 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-12-06 Cont ID  
Sent By btrobaug Date 2006-12-06 Time 16:42 Rev Time 0.50
Received By btrobaug Date 2006-12-06 Time 15:45 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-03-07 Cont ID  
Sent By adarroug Date 2007-03-07 Time 13:43 Rev Time 0.00
Received By adarroug Date 2007-03-07 Time 13:43 Sent To E
Notes
2007-03-07 13:44:10TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-12-06 Cont ID  
Sent By adarroug Date 2006-12-06 Time 10:24 Rev Time 0.00
Received By adarroug Date 2006-12-06 Time 10:24 Sent To E
Notes
2006-12-06 10:24:46TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-02-05 Cont ID  
Sent By rmcdouga Date 2007-02-05 Time 14:12 Rev Time 0.00
Received By rmcdouga Date 2006-11-29 Time 17:29 Sent To  
Notes
2006-11-29 17:29:50SENT TO ZONING

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-03-09 Cont ID  
Sent By tgordon Date 2007-03-09 Time 09:29 Rev Time 0.25
Received By tgordon Date 2007-03-09 Time 09:29 Sent To B
Notes
2007-03-09 09:30:50INSTALLING TWO NEW SUPPLY AIR DUCTS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-12-12 Cont ID  
Sent By tgordon Date 2006-12-12 Time 08:02 Rev Time 0.15
Received By tgordon Date 2006-12-12 Time 08:02 Sent To B
Notes
2006-12-12 08:03:43NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop Z ZONING
Rev No 1 Status P Date 2006-12-03 Cont ID  
Sent By mmclean Date 2006-12-03 Time 23:29 Rev Time 0.00
Received By mmclean Date 2006-12-03 Time 23:29 Sent To I
Notes
***NONE***