Plan Review Details - Permit 06110735
Plan Review Stops For Permit 06110735
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-12-20 Cont ID  
Sent By mjacobs Date 2006-12-20 Time 07:51 Rev Time 0.00
Received By mjacobs Date 2006-12-20 Time 07:22 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-12-18 Cont ID  
Sent By dpalmer Date 2006-12-18 Time 12:27 Rev Time 0.00
Received By dpalmer Date 2006-12-18 Time 12:27 Sent To  
Notes
2006-12-18 12:28:32RE-STAMPED NEW SIGNED AND SEALED SHEETS.
 PREVIOUS PLANS STAMPED IN ERROR BY THIS REVIEWER.
 SHEETS WERE PHOTO-COPIES SUBMITTED OF SIGNED AND SEALED
 SHEETS. SHEETS STAMPED WIHT "VOID" STAMP.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-12-10 Cont ID  
Sent By dpalmer Date 2006-12-10 Time 09:36 Rev Time 0.00
Received By dpalmer Date 2006-12-10 Time 09:30 Sent To I
Notes
2006-12-10 09:36:30PLANS ROUTED BACK TO INCOMING.
2006-12-10 09:31:27PLANS REMOVED FROM INCOMING AND WILL BE ROUTED ABCK TO
 INCOMING TO AWAIT BOB BOARD ONCE REVIEW IS DONE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-12-18 Cont ID  
Sent By mawillia Date 2006-12-18 Time 12:47 Rev Time 0.00
Received By mawillia Date 2006-12-18 Time 11:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-12-20 Time   Rev Time 0.00
Received By spalmer Date 2006-11-29 Time 18:02 Sent To  
Notes
2006-12-12 17:20:40TO "BOB"#2
2006-11-29 18:03:06WAITING FOR "BOB" BOARD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-12-18 Cont ID  
Sent By tgordon Date 2006-12-18 Time 14:02 Rev Time 0.20
Received By tgordon Date 2006-12-18 Time 14:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-12-14 Cont ID  
Sent By tgordon Date 2006-12-14 Time 08:04 Rev Time 0.20
Received By tgordon Date 2006-12-14 Time 08:04 Sent To  
Notes
2006-12-14 08:07:44*** DENIED ***
 1) PLANS NEED TO BE SIGNED AND SEALED BY THE ENGINEER
 RENE I. BASULTO AS THE NAME AND INFORMATION APPEARS IN
 THE TITLE BLOCK, PER FAC 61G15-23.002.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.