Plan Review Details - Permit 06110708
Plan Review Stops For Permit 06110708
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-12-18 Cont ID  
Sent By mjacobs Date 2006-12-18 Time 17:56 Rev Time 0.00
Received By mjacobs Date 2006-12-18 Time 09:36 Sent To  
Notes
2006-12-18 09:40:46BUILDING PLAN REVIEW
 PERMIT:06110708
 ADD:299545TH STREET
 CONT: B & M CONSTRUCTION CO. INC.
 TEL: (954)427-4886
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW1ST
 ACTION: DENIED
  
  
 1)FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2)NOTE: A DEMOLITION PERMIT IS REQUIRED FOR THE
 INTERIOR DEMOLITION.
  
 3)FBC. 11.7IN ADDITION TO THE REQUIREMENTS OF
 SECTION 11-4.1 TO 11-4.35 THE DESIGN OF ALL AREAS USED
 FOR BUSINESS TRANSACATION WITH THE PUBLIC SHALL COMPLY
 WITH SECTION 11-7.PROVICE THE ELEVATION DRAWINGS
 SHOWING ALL REQUIRED DIMENTIONS FOR COUNTERS AND
 CHECK-OUT AISLES.NOTE THE ATM MACHINE SHALL MEET ALL
 ACCESSIBILITY REQUIREMENTS.
  
 4)106.3.3* PRODUCT APPROVALS- 2004
 THOSE PRODUCTS THAT ARE RGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.THE DESIGN PRESSURE ON THE
 STOREFRONTS PRODUCT ARE LOW COMPARE TO THE WALL
 PRESSURES LISTED IN FBC. TABLE 1609.6.2.1 (2) OR TABLE
 1609.6B. IF THE GLAZING AND FRAME OF THE STOREFRONT IS
 NON-IMPACT,IMPACT TESTED STORM SHUTTERS WILL BE
 REQUIRED AND SHALL BE IN PLACE AT TIME OF C.O. SEE
 1609.1.1 PROTECTION OF OPENINGS.
  
 5) THE PROJECT DESCRIPTION OF THE APPLICATION SHALL
 INDICATE THE REMOVAL AND REPLACEMENT OF THE STOREFRONT.
 IF THE BATHROOMS MEET THE ACCESSIBILITY REQUIREMENTS
 AND NO WORK WILL BE CARRIED OUT THERE, REMOVE OR STRIKE
 BATHROOMS FROM THE DESCRIPTION.
  
 6)W.P.B AMENDMENTS. 108.3* THE VALUE IS INDICATED IS
 LOW.FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SUSTEMS SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL,ELECTRIC, PLUMBING, MECHANICAL, INTERIOR
 FINISH, ARCHITECTURAL AND DESIGN FEES, MARKETING
 COSTS,OVERHEAD AND PROFIT EXCLUDING LAND VALUE.IF, IN
 THE OPINION OF THE BUILDING OFFICIAL, THE CLAIMED
 VALUATION OFBUILDING, ALTERATION,STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATED ON THE APPLICATION, THE PERMIT
 SHALL BE DENIED.
  
 7)2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 8)WHAT IS THE DESIGN OCCUPANT LOAD, SEE 1004.
 OCCUPANT LOAD
  
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-12-08 Cont ID  
Sent By dpalmer Date 2006-12-08 Time 18:06 Rev Time 0.00
Received By dpalmer Date 2006-12-07 Time 19:52 Sent To  
Notes
2006-12-08 18:07:33***UNSAT ***
  
  
 1) NOTE:PLEASE CORRELATE THE ADDRESS OF PROJECT.
 PLEASE SEE THE APPLIED ADDRESS FOR SITE IS INDICATED AS
 2995 45TH ST, ON PERMIT APPLICATION HOWEVER PLANS
 INDICATE 3225 CUMBERLAND DR.
  
 2) NOTE: PLEASE SHOW NEW OR EXISTING EXIT AND EMERGENCY
 LIGHTING PER NFPA-101 2003, 7.8, 7.9. PLEASE ALSO
 INDICATE CIRCUITING IF NEW ARE TO BE INSTALLED PER
 700.12E.
  
 3) NOTE:PLEASE INDICATE NEW OR EXISTING SIGN CIRCUIT
 PER 600.5, 220.3B6.
  
 4) NOTE: PLEASE SEE THE VALUE FOR COMPLETE SCOPE OF
 WORK SHALL INCLUDE ALL LABOR AND MATERIALS EVEN IF ANY
 MATERIALS ARE OWNER SUPPLIED. THE VALUE AS APPLIED FOR
 IS EXTREMELY LOW FOR SCOPE OF WORK SHOWN. PLEASE KNOW
 IF AN APPROPRIATE VALUE IS NOT SUBMITTED ONE WILL BE
 ASSESSED USING THE FBC TABLES ALONG WITH THE MARSHALL?S
 AND SWIFT GUIDE AS ADOPTED INTO THE FBC.
 108.3.
  
 5) NOTE: PLEASE KNOW THE PLANS SUBMITTED ARE NOT
 COMPLETE FOR CODE COMPLIANCE. PLEASE SEE ONLY SOME CODE
 ARTICLES BELOW ARE BEING GIVEN. PLEASE KNOW THERE IS A
 SUBSTANTIALLY AMOUNT OF CODE RELATED ITEMS NOT
 SUBMITTED OR SHOWN.
  
 A) PLEASE INDICATE AND SHOW ALL CIRCUITING ON PLANS AND
 CORRELATE WITH PANEL SCHEDULES TO BE SUBMITTED.
 240.4,310.16, 408.4
 FBC ADMINISTRATIVE SECTION AS ADOPTED BY THE CITY OF
 WEST PALM BEACH. 106.1.2, 106.3.5.1.2 ETC.
 PLEASE ALSO SEE 2002 NFPA-70, 2003 NFPA-101, 2002
 NFPA-72, NFPA-30A ETC ETC.
 B) PLEASE SUBMIT LOAD CALCULATIONS.NEC 220. PLEASE
 SEE MDP SHOWN WITH NO LOAD?
 C) PLEASE SEE NEC 511 FOR VERIFICATION OF EXISTING SITE
 COMPLIANCE.
 D) PLEASE SEE LS 101 7.8, 7.9 FOR MISSING EM/ EXT LTS,
 PLEASE ALSO SEE 700.12E FOR CIRCUITING. AS NOTED
 ABOVE.
 E) PLEASE SEE 210.62, 210.12 FOR MISSING NEW OR
 EXISTING SHOW/DISPLAY WINDOWSRECEPTACLES REQUIRED.
 F) PLEASE SEE 250.110, 250.110
 G) PLEASE SEE 250.50
 H) PLEASE SEE 210.8B3
 I) PLEASE SEE FBC CHAPTER 13(ALL APPLICABLE SECTIONS,
 TOO MANY TO LIST AT THIS TIME.
 J) PLEASE SEE 110.9, 240.12 FOR MISSING AIC RATINGS FOR
 NEW SERVICE EQUIPMENT,SELECTIVE COORDINATION DETAILS
 TO BE SUBMITTED.
 ETC.
  
 6) NOTE: PLEASE SEE HB 7121, HB 319, HB965 ETC THIS IS
 HOUSE BILL 7121 WHICH WAS JUST ADOPTED INTO LAW ON JULY
 1ST, 2006. PLEASE SEE FS 252 ETC, WHICH NOW REQUIRES
 ALL FUEL STATIONS UPON BEING NEW OR SUBSTANTIAL
 REMODEL, ETC INSTALL A COMPLETE EMERGENCY BACK UP
 GENERATOR SYSTEM. THIS WILL SUBSTANTIALLY CHANGE THE
 PLANS SUBMITTED.
 PLEASE SUBMIT SITE PLANS, ALL REQUIRED LOCATIONS PER
 NEC 500. PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT
 SHEETS FOR ALL EQUIPMENT, ATS, MTS, GEN, FUEL PRIME
 MOVER ETC ETC.
 PLEASE KNOW THIS IS AND WILL BE REQUIRED. 90.7, 110.3
 ETC
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-01-09 Cont ID  
Sent By mawillia Date 2007-01-09 Time 09:32 Rev Time 0.00
Received By mawillia Date 2007-01-09 Time 09:32 Sent To  
Notes
2007-01-09 10:11:44*****DENIED*****
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF THE SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 3.WILL THE BUILDING OR PORTION OF THE BUILDING BE
 OCCUPIED DURING THE SCOPE OF WORK?IF SO, HOW WILL THE
 REQUIRED MEANS OF EGRESS BE MAINTAINED?
  
 4.WHAT IS THE OCCUPANT LOAD FOR THE BUILDING?
  
 5.ON SHEET A-1, ONE OF THE TWO FRONT ENTRY/EXIT DOORS
 SWINGS BACK INTO THE STORE.BE ADVISED THAT THE
 DOOR(S) WILL BE REQUIRED TO SWING IN THE DIRECTION OF
 EGRESS TRAVEL WHERE SERVING A ROOM OR AREA WITH AN
 OCCUPANT LOAD OF 50 OR MORE.
  
 6.AN ADDITIONAL DEVICE DIRECTING PERSONS TO THE REAR
 EXIT MAY BE NEEDED IF THE EXIT/EMERGENCY LIGHT ABOVE
 THE REAR DOOR IS NOT VISIBLE.
  
 7.INDICATE THE MINIMUM INTERIOR FINISH CLASSIFICATION
 FOR THE NEW CEILING TILES IN TERMS OF CLASS A, B, OR
 C.
  
 8.ON THE APPROPIATE PLAN SHEETS, RECTIFY THE
 DISCREPANCY OF THE DOOR SWING IN THE FOOD PREP AREA
 NEAR THE OVEN (FOR EXAMPLE SEE SHEET E-2 COMPARED TO
 F-1).THE REFERENCED DOOR SHOULD NOT OPEN INTO THE
 PATH OF THE REAR EXIT ACCESS CORRIDOR.
  
 9.PROVIDE DETAIL ON THE TYPES OF FOOD THAT WILL BE
 PREPARED ON THE ROLLER GRILLS AND PLEASE EXPLAIN "HOT
 SANDWICHES".
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW / WPBFR
 561-805-6722
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By dpalmer Date 2006-11-29 Time 13:06 Sent To  
Notes
2006-12-07 09:56:15TO "COMM" BD#27
2006-11-29 13:06:43WAITING FOR COMM BOARD.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-01-13 Cont ID  
Sent By kstevens Date 2007-01-13 Time 09:24 Rev Time 0.00
Received By kstevens Date 2007-01-13 Time 09:24 Sent To  
Notes
2007-01-13 10:56:08DENIED
 REFERENCE: FBC-2004 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS DESIGNED BY THE ARCHITECT. THE PERSONAL
 SIGNATURE OF THE ARCHITECT IS REQUIRED ON THE SEAL. IT
 APPEARS TO BE INITIALS WHICH IS NOT APPROVED. IF THIS
 IS INDEED THE LEGAL SIGNATURE OF THE ARCHITECT, A
 SIGNED, SEALED, NOTORIZED LETTER SHOWING THE LEGAL
 SIGNATURE OF THE ARCHITECT SHALL BE SUBMITTED FOR OUR
 FILES. -ALSO THE BUSINESS NUMBER, (CERTIFICATE OF
 AUTHORIZATION), IS REQUIRED IN THE TITLE BLOCK OF EACH
 SHEET. FAC 61G1-16.003, 61G1-16.004(2)(5) & FS 481.219,
 481.2055. PLEASE MAKE SURE ALL REQUIREMENTS ARE
 ADDRESSED.
  
 2. ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME,
 ADDRESS, AND LICENSE NUMBER, AS WELL AS, THE NAME,
 ADDRESS, AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS ON EACH SHEET. FAC 61G15-23.002(2)
 & FS 471.025. PLEASE MAKE SURE ALL REQUIREMENTS ARE
 ADDRESSED.(SEE ATTACHED SHEET FROM DBPR WEBSITE).
  
 3. SHTS P-1 & P-2 SANT RISER DIAGRAM. THE PUMP AT THE
 SANDWICH STATION REQUIRES A VENT CONNECTED TO THE VENT
 SYSTEM OR VENTED THRU THE ROOF. SECTION 916.5. (AAV NOT
 APPROVED).
  
 4. SHT P-2 A FULL OPEN VALVE IS REQUIRED ON THE
 DISCHARGE SIDE OF THE CHECK VALVE FOR THE SUMP PUMP AT
 THE SANDWICH STATION. SECTION 712.2. PLEASE SHOW ON THE
 SANT. RISER DIAGRAM.
  
 5. SHT P-2 WATER HAMMER ARRESTORS ARE REQUIRED ON ALL
 QUICK CLOSING VALVES. (SEE ICE MAKER). SECTION 604.9.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved