 |
Plan Review Details - Permit 06110708
| Plan Review Stops For Permit 06110708 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-12-18 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-12-18 |
Time |
17:56 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-12-18 |
Time |
09:36 |
Sent To |
|
|
| Notes |
| 2006-12-18 09:40:46 | BUILDING PLAN REVIEW | | | PERMIT:06110708 | | | ADD:299545TH STREET | | | CONT: B & M CONSTRUCTION CO. INC. | | | TEL: (954)427-4886 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW1ST | | | ACTION: DENIED | | | | | | | | | 1)FL S S 713.13 | | | NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT BEFORE A | | | PERMIT WILL BE ISSUED. NOTE: 713.13(2) | | | IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS | | | NOT ACTUALLY COMMENCED | | | WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. | | | | | | 2)NOTE: A DEMOLITION PERMIT IS REQUIRED FOR THE | | | INTERIOR DEMOLITION. | | | | | | 3)FBC. 11.7IN ADDITION TO THE REQUIREMENTS OF | | | SECTION 11-4.1 TO 11-4.35 THE DESIGN OF ALL AREAS USED | | | FOR BUSINESS TRANSACATION WITH THE PUBLIC SHALL COMPLY | | | WITH SECTION 11-7.PROVICE THE ELEVATION DRAWINGS | | | SHOWING ALL REQUIRED DIMENTIONS FOR COUNTERS AND | | | CHECK-OUT AISLES.NOTE THE ATM MACHINE SHALL MEET ALL | | | ACCESSIBILITY REQUIREMENTS. | | | | | | 4)106.3.3* PRODUCT APPROVALS- 2004 | | | THOSE PRODUCTS THAT ARE RGULATED BY DCA | | | RULE 9B-72 SHALL BE REVIEWED AND | | | APPROVED IN WRITTING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR | | | JURISDICTIONAL APPROVAL.THE DESIGN PRESSURE ON THE | | | STOREFRONTS PRODUCT ARE LOW COMPARE TO THE WALL | | | PRESSURES LISTED IN FBC. TABLE 1609.6.2.1 (2) OR TABLE | | | 1609.6B. IF THE GLAZING AND FRAME OF THE STOREFRONT IS | | | NON-IMPACT,IMPACT TESTED STORM SHUTTERS WILL BE | | | REQUIRED AND SHALL BE IN PLACE AT TIME OF C.O. SEE | | | 1609.1.1 PROTECTION OF OPENINGS. | | | | | | 5) THE PROJECT DESCRIPTION OF THE APPLICATION SHALL | | | INDICATE THE REMOVAL AND REPLACEMENT OF THE STOREFRONT. | | | IF THE BATHROOMS MEET THE ACCESSIBILITY REQUIREMENTS | | | AND NO WORK WILL BE CARRIED OUT THERE, REMOVE OR STRIKE | | | BATHROOMS FROM THE DESCRIPTION. | | | | | | 6)W.P.B AMENDMENTS. 108.3* THE VALUE IS INDICATED IS | | | LOW.FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS | | | AND SUSTEMS SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE | | | STRUCTURAL,ELECTRIC, PLUMBING, MECHANICAL, INTERIOR | | | FINISH, ARCHITECTURAL AND DESIGN FEES, MARKETING | | | COSTS,OVERHEAD AND PROFIT EXCLUDING LAND VALUE.IF, IN | | | THE OPINION OF THE BUILDING OFFICIAL, THE CLAIMED | | | VALUATION OFBUILDING, ALTERATION,STRUCTURE, | | | ELECTRICAL, GAS, MECHANICAL OR PLUMBING SYSTEMS APPEARS | | | TO BE UNDERESTIMATED ON THE APPLICATION, THE PERMIT | | | SHALL BE DENIED. | | | | | | 7)2004 FL. BLD CODE 1603.1.4 THE | | | FOLLOWING INFORMATION RELATED TO WIND | | | SHALL BE SHOWN ON THE CONSTRUCTION | | | DRAWINGS, | | | 1)- BASIC WIND SPEED, MPH | | | 2)- WIND IMPORTANCE FACTOR, & BUILDING | | | CATEGORY | | | 3)- WIND EXPOSURE | | | 4)- INTERNAL PRESSURE COEFFICIENT, | | | 5)- COMPONENTS & CLADDING, THE DESIGN | | | WIND PRESSURES IN TERMS OF PSF. | | | | | | 8)WHAT IS THE DESIGN OCCUPANT LOAD, SEE 1004. | | | OCCUPANT LOAD | | | | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | 805-6726 | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-12-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-12-08 |
Time |
18:06 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-12-07 |
Time |
19:52 |
Sent To |
|
|
| Notes |
| 2006-12-08 18:07:33 | ***UNSAT *** | | | | | | | | | 1) NOTE:PLEASE CORRELATE THE ADDRESS OF PROJECT. | | | PLEASE SEE THE APPLIED ADDRESS FOR SITE IS INDICATED AS | | | 2995 45TH ST, ON PERMIT APPLICATION HOWEVER PLANS | | | INDICATE 3225 CUMBERLAND DR. | | | | | | 2) NOTE: PLEASE SHOW NEW OR EXISTING EXIT AND EMERGENCY | | | LIGHTING PER NFPA-101 2003, 7.8, 7.9. PLEASE ALSO | | | INDICATE CIRCUITING IF NEW ARE TO BE INSTALLED PER | | | 700.12E. | | | | | | 3) NOTE:PLEASE INDICATE NEW OR EXISTING SIGN CIRCUIT | | | PER 600.5, 220.3B6. | | | | | | 4) NOTE: PLEASE SEE THE VALUE FOR COMPLETE SCOPE OF | | | WORK SHALL INCLUDE ALL LABOR AND MATERIALS EVEN IF ANY | | | MATERIALS ARE OWNER SUPPLIED. THE VALUE AS APPLIED FOR | | | IS EXTREMELY LOW FOR SCOPE OF WORK SHOWN. PLEASE KNOW | | | IF AN APPROPRIATE VALUE IS NOT SUBMITTED ONE WILL BE | | | ASSESSED USING THE FBC TABLES ALONG WITH THE MARSHALL?S | | | AND SWIFT GUIDE AS ADOPTED INTO THE FBC. | | | 108.3. | | | | | | 5) NOTE: PLEASE KNOW THE PLANS SUBMITTED ARE NOT | | | COMPLETE FOR CODE COMPLIANCE. PLEASE SEE ONLY SOME CODE | | | ARTICLES BELOW ARE BEING GIVEN. PLEASE KNOW THERE IS A | | | SUBSTANTIALLY AMOUNT OF CODE RELATED ITEMS NOT | | | SUBMITTED OR SHOWN. | | | | | | A) PLEASE INDICATE AND SHOW ALL CIRCUITING ON PLANS AND | | | CORRELATE WITH PANEL SCHEDULES TO BE SUBMITTED. | | | 240.4,310.16, 408.4 | | | FBC ADMINISTRATIVE SECTION AS ADOPTED BY THE CITY OF | | | WEST PALM BEACH. 106.1.2, 106.3.5.1.2 ETC. | | | PLEASE ALSO SEE 2002 NFPA-70, 2003 NFPA-101, 2002 | | | NFPA-72, NFPA-30A ETC ETC. | | | B) PLEASE SUBMIT LOAD CALCULATIONS.NEC 220. PLEASE | | | SEE MDP SHOWN WITH NO LOAD? | | | C) PLEASE SEE NEC 511 FOR VERIFICATION OF EXISTING SITE | | | COMPLIANCE. | | | D) PLEASE SEE LS 101 7.8, 7.9 FOR MISSING EM/ EXT LTS, | | | PLEASE ALSO SEE 700.12E FOR CIRCUITING. AS NOTED | | | ABOVE. | | | E) PLEASE SEE 210.62, 210.12 FOR MISSING NEW OR | | | EXISTING SHOW/DISPLAY WINDOWSRECEPTACLES REQUIRED. | | | F) PLEASE SEE 250.110, 250.110 | | | G) PLEASE SEE 250.50 | | | H) PLEASE SEE 210.8B3 | | | I) PLEASE SEE FBC CHAPTER 13(ALL APPLICABLE SECTIONS, | | | TOO MANY TO LIST AT THIS TIME. | | | J) PLEASE SEE 110.9, 240.12 FOR MISSING AIC RATINGS FOR | | | NEW SERVICE EQUIPMENT,SELECTIVE COORDINATION DETAILS | | | TO BE SUBMITTED. | | | ETC. | | | | | | 6) NOTE: PLEASE SEE HB 7121, HB 319, HB965 ETC THIS IS | | | HOUSE BILL 7121 WHICH WAS JUST ADOPTED INTO LAW ON JULY | | | 1ST, 2006. PLEASE SEE FS 252 ETC, WHICH NOW REQUIRES | | | ALL FUEL STATIONS UPON BEING NEW OR SUBSTANTIAL | | | REMODEL, ETC INSTALL A COMPLETE EMERGENCY BACK UP | | | GENERATOR SYSTEM. THIS WILL SUBSTANTIALLY CHANGE THE | | | PLANS SUBMITTED. | | | PLEASE SUBMIT SITE PLANS, ALL REQUIRED LOCATIONS PER | | | NEC 500. PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT | | | SHEETS FOR ALL EQUIPMENT, ATS, MTS, GEN, FUEL PRIME | | | MOVER ETC ETC. | | | PLEASE KNOW THIS IS AND WILL BE REQUIRED. 90.7, 110.3 | | | ETC | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-01-09 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-01-09 |
Time |
09:32 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-01-09 |
Time |
09:32 |
Sent To |
|
|
| Notes |
| 2007-01-09 10:11:44 | *****DENIED***** | | | | | | | | | 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 2.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL | | | BE REMOVED FROM THE SITE AT THE END OF THE SHIFT OR | | | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | | | 3.WILL THE BUILDING OR PORTION OF THE BUILDING BE | | | OCCUPIED DURING THE SCOPE OF WORK?IF SO, HOW WILL THE | | | REQUIRED MEANS OF EGRESS BE MAINTAINED? | | | | | | 4.WHAT IS THE OCCUPANT LOAD FOR THE BUILDING? | | | | | | 5.ON SHEET A-1, ONE OF THE TWO FRONT ENTRY/EXIT DOORS | | | SWINGS BACK INTO THE STORE.BE ADVISED THAT THE | | | DOOR(S) WILL BE REQUIRED TO SWING IN THE DIRECTION OF | | | EGRESS TRAVEL WHERE SERVING A ROOM OR AREA WITH AN | | | OCCUPANT LOAD OF 50 OR MORE. | | | | | | 6.AN ADDITIONAL DEVICE DIRECTING PERSONS TO THE REAR | | | EXIT MAY BE NEEDED IF THE EXIT/EMERGENCY LIGHT ABOVE | | | THE REAR DOOR IS NOT VISIBLE. | | | | | | 7.INDICATE THE MINIMUM INTERIOR FINISH CLASSIFICATION | | | FOR THE NEW CEILING TILES IN TERMS OF CLASS A, B, OR | | | C. | | | | | | 8.ON THE APPROPIATE PLAN SHEETS, RECTIFY THE | | | DISCREPANCY OF THE DOOR SWING IN THE FOOD PREP AREA | | | NEAR THE OVEN (FOR EXAMPLE SEE SHEET E-2 COMPARED TO | | | F-1).THE REFERENCED DOOR SHOULD NOT OPEN INTO THE | | | PATH OF THE REAR EXIT ACCESS CORRIDOR. | | | | | | 9.PROVIDE DETAIL ON THE TYPES OF FOOD THAT WILL BE | | | PREPARED ON THE ROLLER GRILLS AND PLEASE EXPLAIN "HOT | | | SANDWICHES". | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING, | | | INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH | | | ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW / WPBFR | | | 561-805-6722 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-11-29 |
Time |
13:06 |
Sent To |
|
|
| Notes |
| 2006-12-07 09:56:15 | TO "COMM" BD#27 | | 2006-11-29 13:06:43 | WAITING FOR COMM BOARD. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-01-13 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-01-13 |
Time |
09:24 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-01-13 |
Time |
09:24 |
Sent To |
|
|
| Notes |
| 2007-01-13 10:56:08 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. ALL SHEETS DESIGNED BY THE ARCHITECT. THE PERSONAL | | | SIGNATURE OF THE ARCHITECT IS REQUIRED ON THE SEAL. IT | | | APPEARS TO BE INITIALS WHICH IS NOT APPROVED. IF THIS | | | IS INDEED THE LEGAL SIGNATURE OF THE ARCHITECT, A | | | SIGNED, SEALED, NOTORIZED LETTER SHOWING THE LEGAL | | | SIGNATURE OF THE ARCHITECT SHALL BE SUBMITTED FOR OUR | | | FILES. -ALSO THE BUSINESS NUMBER, (CERTIFICATE OF | | | AUTHORIZATION), IS REQUIRED IN THE TITLE BLOCK OF EACH | | | SHEET. FAC 61G1-16.003, 61G1-16.004(2)(5) & FS 481.219, | | | 481.2055. PLEASE MAKE SURE ALL REQUIREMENTS ARE | | | ADDRESSED. | | | | | | 2. ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME, | | | ADDRESS, AND LICENSE NUMBER, AS WELL AS, THE NAME, | | | ADDRESS, AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE | | | ENGINEERING BUSINESS ON EACH SHEET. FAC 61G15-23.002(2) | | | & FS 471.025. PLEASE MAKE SURE ALL REQUIREMENTS ARE | | | ADDRESSED.(SEE ATTACHED SHEET FROM DBPR WEBSITE). | | | | | | 3. SHTS P-1 & P-2 SANT RISER DIAGRAM. THE PUMP AT THE | | | SANDWICH STATION REQUIRES A VENT CONNECTED TO THE VENT | | | SYSTEM OR VENTED THRU THE ROOF. SECTION 916.5. (AAV NOT | | | APPROVED). | | | | | | 4. SHT P-2 A FULL OPEN VALVE IS REQUIRED ON THE | | | DISCHARGE SIDE OF THE CHECK VALVE FOR THE SUMP PUMP AT | | | THE SANDWICH STATION. SECTION 712.2. PLEASE SHOW ON THE | | | SANT. RISER DIAGRAM. | | | | | | 5. SHT P-2 WATER HAMMER ARRESTORS ARE REQUIRED ON ALL | | | QUICK CLOSING VALVES. (SEE ICE MAKER). SECTION 604.9. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |