Plan Review Details - Permit 06110681
Plan Review Stops For Permit 06110681
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-03-28 Cont ID  
Sent By mjacobs Date 2007-03-28 Time 08:16 Rev Time 0.00
Received By mjacobs Date 2007-03-28 Time 05:58 Sent To P
Notes
2007-03-28 08:16:42NOTE:THE REPORT FOR FLEXANE BRUSHABLE CURING AGENT
 MATERIAL SAFETY DATA SHEETS REQUIRES AN EMERGENCY
 SHOWER AND AN EYE WASH STATION. DUE TO THE FACT THAT
 THIS INFORMATION WAS JUST SUBMITTED, THE DRAWINGS WILL
 BE SENT TO PLUMBING FORREVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-02-24 Cont ID  
Sent By mjacobs Date 2007-02-24 Time 13:54 Rev Time 0.00
Received By mjacobs Date 2007-02-24 Time 10:43 Sent To E
Notes
2007-02-24 13:51:22BUILDING PLAN REVIEW
 PERMIT:
 ADD:
 CONT:
 TEL: (561)###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)61G15-23.002(2)EACH SHEET OF PLANS AND PRINTS
 MUST BE SEALED, SIGNED AND DATED BY THE PROFESSIONAL
 ENGINEER IN RESPONSIBLE CHARGE.ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME, ADDRESS, AND LICENSE
 NUMBER ON EACH SHEET.IF PRATICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS, AND CERTIFICATE OF AUTHORIZATION
 NUMBER OR THE ENGINEERING BUSINESS ON EACH SHEET.
  
 3)INDICATE THE 3' SEPERATION OF THE SPRAY BOOTH ON
 THE FLOOR PLANS. ALSO STATE THE FIRE RATINGS OF THE TWO
 IN THE FIRE WALLS. SEE FBC.TABLE 715.3 FOR MORE
 INFORMATION.
  
 4)106.1.3 THE BUILDING OFFICIAL
 MAY SET STANDARDS THROUGH DEPARTMENTAL
 POLICY STANDARDS FOR PLANS AND SPRCIFICA
 TIONS. "NO HANDWRITING ON DRAWINGS OR SPECIFICATIONS".
 ONLY THE DESIGNER OF RECORD CAN MAKE CHANGES TO THE
 PLANS AND SPECIFICATIONS.
  
 5)106.1 INDICATE THE MODEL NO. FOR THE SPRAY BOOTH
 FROM THE SPECIFICATIONS PROVIDED IN THE PACKAGE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-01-26 Cont ID  
Sent By mjacobs Date 2007-01-26 Time 13:59 Rev Time 0.00
Received By mjacobs Date 2007-01-26 Time 08:59 Sent To E
Notes
2007-01-26 11:25:22BUILDING PLAN REVIEW
 PERMIT:
 ADD:
 CONT:
 TEL: (561)###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)416.2.1THE INTERIOR SURFACES OF SPRAY ROOMS SHALL
 BE SMOOTH AND SHALL BE SO CONSTRUCTED TO PERMIT THE
 FREE PASSAGE OF EXHAUST AIR FROM ALL PARTS OF THE
 INTERIOR AND TO FACILITATE WASHING AND CLEANING, AND
 SHALL BE SO DESIGNED TO CONFINE RESIDUES WITHIN THE
 ROOM. ALUMINIUM SHALL BOT BE USED. IF THE BOOTH WILL BE
 WASHED SHOW HOW IT WILL MEET THE DRAINAGE REQUIREMENT.
  
 3)416.4AN AUTOMATIC FIRE-EXTINGUISHING SYSTEM SHALL
 BE PROVIDED IN ALL SPRAY, DIP AND IMMERSING SPACES AND
 STORAGE ROOMS, AND SHALL BE INSTALLED IN ACCORDANCE
 WITH CHAPTER 9. INDICATE IF THE SYSTEM WILL BE DESIGN
 TO A) AUTOMIC WATER SPRINKLERS B) DRY CHEMICAL C) HALON
 1211 / 1301.
  
 4)61G15-23.002ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, ADDRESS, AND LICENSE NUMBER ON EACH SHEET.
 IF PRATICING THROUGH A DULY AUTHORIZED ENGINEERING
 BUSINESS, ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME
 AND LICENSE NUMBER, AS WELL AS, THE NAME, ADDRESS, AND
 CERTIFICATE OF AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK ON EACH SHEET
 CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE
 NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND
 LICENSE NUMBER OF THE ENGINEE, AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT.
 THIS INFORMATION IS MISSING.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2007-01-29 Cont ID  
Sent By btrobaug Date 2007-01-29 Time 10:22 Rev Time 0.33
Received By btrobaug Date 2007-01-29 Time 10:21 Sent To PC
Notes
2007-01-29 10:21:47 
 3/9/07 SPOKE WITH IRV JOHNSON WHO SAID KASPER ELEC.
 WILL SUBMIT ELEC PLANS./WRT
 .
 ELECTRIC APPLIED FOR ON A SEPARATE PERMIT, #06060597
 KNIGHT ELEC./WRT.
  
 ALSO ELECTRIC PERMIT ISSUED 06060597. KASPER ELECTRIC.

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2006-12-20 Cont ID  
Sent By btrobaug Date 2006-12-20 Time 09:29 Rev Time 0.25
Received By btrobaug Date 2006-12-20 Time 09:26 Sent To FIRE
Notes
2006-12-20 09:29:46 
  
 ELECTRIC APPLIED FOR ON A SEPARATE PERMIT,
 #06060597./WRT.

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2007-06-11 Cont ID  
Sent By mawillia Date 2007-06-11 Time 10:41 Rev Time 0.00
Received By mawillia Date 2007-06-11 Time 10:37 Sent To  
Notes
2007-06-11 10:40:05*****APPROVED*****
  
  
 REVISON PLAN SHEET STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2007-06-06 Cont ID  
Sent By mawillia Date 2007-06-06 Time 19:30 Rev Time 0.00
Received By mawillia Date 2007-06-06 Time 19:21 Sent To M
Notes
2007-06-06 19:30:00*****UNSAT****
  
  
 PLEASE BE ADVISED THAT THE SUBMITTED PERMIT NUMBER ON
 THE APPLICATION WAS FOR THE INSTALLATION OF THE PAINT
 SPRAY BOOTH.ANY REVISIONS TO THE PAINT BOOTH'S
 SUPPRESSION SYSTEM SHOULD BE UNDER A SEPARATE PERMIT.
  
 FEEL FREE TO CONTACT ME IN REGARDS TO THIS MATTER.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-03-27 Cont ID  
Sent By mawillia Date 2007-03-27 Time 14:13 Rev Time 0.00
Received By mawillia Date 2007-03-27 Time 13:19 Sent To B
Notes
2007-03-27 14:11:23*****APPROVED*****
  
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED;PLAN SHEET 2 OF 4 WAS STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-02-23 Cont ID  
Sent By mawillia Date 2007-02-23 Time 15:55 Rev Time 0.00
Received By mawillia Date 2007-02-23 Time 15:55 Sent To B
Notes
2007-02-23 16:02:22*****UNSAT*****
  
 THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN
 REVIEW OF 12/28/2006 STILL NEED TO BE ADDRESSED. ALL
 OTHER COMMENTS WERE ADDRESSED.
  
  
  
  
 3.INDICATE THE FIRE RATING FOR THE EXISTING DOORS IN
 THE 1 HOUR RATED WALL.
  
 6.ILLUSTRATE REQUIRED GROUNDING AND BONDING FOR THE
 BOOTH OR ADD TO NOTES THAT THE BOOTH WILL BE PROPERLY
 GROUNDED AND BONDED.
  
 7. PROVIDE PRODUCT APPROVAL RATING AND SIZE OF SAFETY
 STORAGE CABINET.
  
 9.THE FIRE SUPPRESSION SYSTEM FOR THE BOOTH WILL
 REQUIRE SEPARATE PLANS AND PERMIT.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-12-28 Cont ID  
Sent By mawillia Date 2006-12-28 Time 09:52 Rev Time 0.00
Received By mawillia Date 2006-12-28 Time 09:52 Sent To B
Notes
2006-12-28 10:37:51*****UNSAT*****NEED ADDITIONAL INFO
  
  
  
 1.PLEASE INDICATE IF THIS A SINGLE TENANT ARRANGEMENT
 IN THE BUILDING.
  
 2.PROVIDE UL NUMBER AND WALL DETAIL FOR THE 1 HOUR
 RATED WALL.
  
 3.INDICATE THE FIRE RATING FOR THE EXISTING DOORS IN
 THE 1 HOUR RATED WALL.
  
 4.WHAT WILL BE THE DIRECTION OF THE PAINT SPRAY
 VAPORS UPON LEAVING THE PAINT DUCTS?
  
 5.PLEASE INDICATE THE SEPARATION DISTANCE BETWEEN THE
 INTAKE AND EXHAUST DUCTS.2004 FBC/M 502.7.3.6
  
 6.ILLUSTRATE REQUIRED GROUNDING AND BONDING FOR THE
 BOOTH OR ADD TO NOTES THAT THE BOOTH WILL BE PROPERLY
 GROUNDED AND BONDED.
  
 7. PROVIDE PRODUCT APPROVAL RATING AND SIZE OF SAFETY
 STORAGE CABINET.
  
 8.FIRE EXTINGUISHER(S) WITH A RATING OF AT LEAST
 2A:10BC SHALL BE CERTIFIED AND TAGGED.
  
 9.THE FIRE SUPPRESSION SYSTEM FOR THE BOOTH WILL
 REQUIRE SEPARATE PLANS AND PERMIT.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-8056722

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-05-23 Cont ID  
Sent By adarroug Date 2007-05-23 Time 08:39 Rev Time 0.00
Received By adarroug Date 2007-05-23 Time 08:38 Sent To FIRE
Notes
2007-05-23 08:39:19TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-04-12 Cont ID  
Sent By adarroug Date 2007-04-12 Time 16:06 Rev Time 0.00
Received By adarroug Date 2007-04-12 Time 16:06 Sent To P
Notes
2007-04-12 16:07:17TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-03-15 Cont ID  
Sent By adarroug Date 2007-03-15 Time 13:31 Rev Time 0.00
Received By adarroug Date 2007-03-15 Time 13:31 Sent To FIRE
Notes
2007-03-15 13:32:19TO "F" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-02-20 Cont ID  
Sent By adarroug Date 2007-02-20 Time 10:02 Rev Time 0.00
Received By adarroug Date 2007-02-20 Time 10:02 Sent To FIRE
Notes
2007-02-20 10:03:09TO "F" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-12-28 Cont ID  
Sent By adarroug Date 2006-12-28 Time 11:48 Rev Time 0.00
Received By adarroug Date 2006-12-28 Time 11:48 Sent To B
Notes
2006-12-28 11:49:12TO "MISC" BOX#3

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-12-16 Cont ID  
Sent By adarroug Date 2006-12-16 Time 16:27 Rev Time 0.00
Received By adarroug Date 2006-12-16 Time 16:27 Sent To M
Notes
2006-12-16 16:28:10TO "M" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-09 Cont ID  
Sent By btrobaug Date 2007-03-09 Time 10:50 Rev Time 0.00
Received By btrobaug Date 2006-11-21 Time 15:27 Sent To PC
Notes
2006-11-21 15:28:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-07-26 Cont ID  
Sent By hmoser Date 2007-07-26 Time 19:23 Rev Time 0.00
Received By hmoser Date 2007-07-26 Time 19:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-06-11 Cont ID  
Sent By tgordon Date 2007-06-11 Time 11:24 Rev Time 0.30
Received By tgordon Date 2007-06-11 Time 11:24 Sent To  
Notes
2007-06-11 11:26:46REVISION TO PAINT BOOTH FIRE SUPPRESSION SYSTEM.
  
 NOTE: ADDITIONAL MECH. PERMIT FOR EXHAUST SYSTEM AND
 FIRE PERMIT FOR FIRE SUPPRESSION REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-12-18 Cont ID  
Sent By tgordon Date 2006-12-18 Time 09:30 Rev Time 0.30
Received By tgordon Date 2006-12-18 Time 09:30 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-05-16 Cont ID  
Sent By kstevens Date 2007-05-16 Time 14:41 Rev Time 0.00
Received By kstevens Date 2007-04-25 Time 12:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-04-04 Cont ID  
Sent By kstevens Date 2007-04-04 Time 17:33 Rev Time 0.00
Received By kstevens Date 2007-04-04 Time 17:33 Sent To  
Notes
2007-04-04 17:51:01DENIED
 REFERENCE FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. ACCORDING TO THE MSDS SHEETS, AN EYE WASH/EMERGENCY
 SHOWER IS REQUIRED. SECTIONS 411 & 411.1.
  
 2. SUBMIT A FLOOR PLAN SHOWING THE LOCATION OF THE EYE
 WASH/EMERGENCY SHOWER. THE EW/SHR SHALL BE LOCATED IN
 CLOSE PROXIMITY TO THE HAZARD SOURCE.
  
 3. SUBMIT A WATER RISER DIAGRAM SHOWING PIPE SIZE,
 VALVES & POINT OF CONNECTION. SECTION
 106.3.5.1.3(3)(10)(13).
  
 4. EYE WASH/EMERGENCY SHOWER APPROVAL REQUIRED. SUBMIT
 MANUF. SPECIFICATION SHEETS. ISEA Z358.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2007-03-28 Cont ID  
Sent By jroach Date 2007-03-28 Time 08:25 Rev Time 0.00
Received By jroach Date 2007-03-28 Time 08:25 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2006-12-15 Cont ID  
Sent By mmclean Date 2006-12-15 Time 14:53 Rev Time 0.00
Received By mmclean Date 2006-12-15 Time 14:53 Sent To I
Notes
***NONE***