Plan Review Details - Permit 06110658
Plan Review Stops For Permit 06110658
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-11-30 Cont ID  
Sent By mawillia Date 2006-11-30 Time 14:48 Rev Time 0.00
Received By mawillia Date 2006-11-30 Time 14:48 Sent To  
Notes
2006-11-30 15:04:51*****APPROVED*****
  
  
  
  
 1.APRESSURE TEST WILL BE REQUIRED SINCE THE
 MODIFICATION AFFECTS MORE THAN 20 HEADS.HOWEVER, IF
 THE MODIFICATION CANNOT BE ISOLATED AS PER NFPA
 16.2.1.6, A LETTER FROM YOUR COMPANY STATING SUCH AT
 THE SAID LOCATION SHALL BE PROVIDED TO THE AHJ (WEST
 PALM BEACH FIRE PREVENTION BUREAU) PRIOR TO OR AT THE
 TIME OF INSPECTION.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-11-30 Cont ID  
Sent By mawillia Date 2006-11-30 Time 14:48 Rev Time 0.00
Received By mawillia Date 2006-11-21 Time 10:41 Sent To  
Notes
2006-11-21 10:41:16TO "F" BOX