Plan Review Details - Permit 06110610
Plan Review Stops For Permit 06110610
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2007-08-29 Cont ID  
Sent By shill Date 2007-08-29 Time 18:34 Rev Time 0.00
Received By shill Date 2007-08-29 Time 18:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2007-07-31 Cont ID  
Sent By shill Date 2007-07-31 Time 08:41 Rev Time 0.00
Received By shill Date 2007-07-31 Time 08:41 Sent To  
Notes
2007-07-31 08:43:08****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)PROVIDE A REASONABLE VALUE FOR THIS JOB OR AN
 ESTIMATE WILL BE DONE FOR YOU USING MARSHALL & SWIFT.
  
 2.)TWO SETS REQUIRED, ONLY ONE PRODUCT APPROVAL FOR
 THE SHUTTERS AND ONE INSTALLATION SCHEDULE WAS
 PROVIDED.
  
 3.)THE INSTALLATION SCHEDULE COLUMN FOR ANCHOR
 SPACING IS BLANK.PLEASE COMPLETE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2007-07-16 Cont ID  
Sent By shill Date 2007-07-16 Time 18:05 Rev Time 0.00
Received By shill Date 2007-07-16 Time 18:05 Sent To  
Notes
2007-07-16 18:08:43****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LISTS:
  
 3.)PROVIDE PRODUCT APPROVALS FOR THE WINDOWS,
 MULLIONS AND IMPACT PROTECTION.FLORIDA STATE OR LOCAL
 PRODUCT APPROVAL REQUIRED IN ADDITION TO EVALUATION
 REPORTS, FAC9B72, WWW.FLORIDABUILDING.ORG
  
 4.)PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER
 OF RECORD, FBC*106.3.3.
  
 THIS CAN BE DONE WITH A SHOP DRAWING REVIEW STAMP OR A
 LETTER.ARCHITECT'S REVIEW REQUIRED.
  
 5.)ADDRESSED.
  
 6.) IF HURRICANE SHUTTERS ARE USED FOR IMPACT
 PROTECTION, COMPLETE THE ATTACHED INSTALLATION SCHEDULE
 OR SUBMIT ALL REQUIRED INFORMATION IN ANOTHER FORMAT.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-06-04 Cont ID  
Sent By shill Date 2007-06-04 Time 15:27 Rev Time 0.00
Received By shill Date 2007-06-04 Time 15:26 Sent To  
Notes
2007-06-04 15:47:36****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 3.)PROVIDE PRODUCT APPROVALS FOR THE WINDOWS,
 MULLIONS AND IMPACT PROTECTION.FLORIDA STATE OR LOCAL
 PRODUCT APPROVAL REQUIRED IN ADDITION TO EVALUATION
 REPORTS, FAC9B72, WWW.FLORIDABUILDING.ORG
  
 4.)PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER
 OF RECORD, FBC*106.3.3.
  
 5.)SEE FIRST CORRECTION LISTS.THE OWNER/BUILDER
 AFFIDAVIT IS NOT IN THE PACKAGE.THIS IS SHOWN AS A
 GARAGE APARTMENT; OWNER BUILDER CANNOT DO WORK ON A
 RENTAL.PLEASE CLARIFY USE; PROPERTY APPRAISER SHOWS
 TWO UNITS.***THIS IS A RENTAL UNIT, CANNOT DO OWNER
 BUILDER!!!!***
  
 NEW COMMENT:
  
 IF HURRICANE SHUTTERS ARE USED FOR IMPACT PROTECTION,
 COMPLETE THE ATTACHED INSTALLATION SCHEDULE OR SUBMIT
 ALL REQUIRED INFORMATION IN ANOTHER FORMAT.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-04-18 Cont ID  
Sent By shill Date 2007-04-18 Time 12:26 Rev Time 0.00
Received By shill Date 2007-04-18 Time 12:26 Sent To E
Notes
2007-04-18 12:28:13****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)THE SCOPE OF WORK IS NOT CLEAR.THE APPLICATION
 STATES THAT A HOLE WILL BE CUT IN THE KITCHEN WALL, NO
 NEW WORK SHOWN OTHER THAN CABINETS AND INFILL IN THE
 KITCHEN.APPLICATION STATES THAT DRYWALL AND 2X4 STUDS
 WILL BE INSTALLED, WHERE?APPLICATION STATES STRAPS
 WILL BE INSTALLED, WHERE?
  
 2.)THE PLAN SHOWS THE CATALOG PAGE FOR STRAPS BUT THE
 DETAIL STATES "SEE ROOF PLAN", BUT NO ROOF PLAN WAS
 PROVIDED.WHICH STRAP IS REQUIRED FOR THIS JOB?
  
 3.)PROVIDE PRODUCT APPROVALS FOR THE WINDOWS,
 MULLIONS AND IMPACT PROTECTION.FLORIDA STATE OR LOCAL
 PRODUCT APPROVAL REQUIRED IN ADDITION TO EVALUATION
 REPORTS, FAC9B72, WWW.FLORIDABUILDING.ORG
  
 4.)PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER
 OF RECORD, FBC*106.3.3.
  
 5.)SEE FIRST CORRECTION LISTS.THE OWNER/BUILDER
 AFFIDAVIT IS NOT IN THE PACKAGE.THIS IS SHOWN AS A
 GARAGE APARTMENT; OWNER BUILDER CANNOT DO WORK ON A
 RENTAL.PLEASE CLARIFY USE; PROPERTY APPRAISER SHOWS
 TWO UNITS.***THIS IS A RENTAL UNIT, CANNOT DO OWNER
 BUILDER!!!!***
  
 6.)THE SITE PLAN SHOWS TWO UNITS,THE WORK APPEARS
 TO BE IN THE ONE STORY RESIDENCE BUT THE PLAN DOES NOT
 STATE THIS.
  
 7.)THE ORIGINAL PLANS SUBMITTED BY THE OWNER HAS WORK
 WHICH IS NOT ON THE PLAN PREPARED BY THE ARCHITECT.
 PLEASE CONFIRM SCOPE OF WORK.
  
 8.)DOCUMENTS PREPARED BY AN ARCHITECT AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALSFS481.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-02-26 Cont ID  
Sent By shill Date 2007-02-26 Time 15:54 Rev Time 0.00
Received By shill Date 2007-02-26 Time 15:54 Sent To  
Notes
2007-02-26 16:02:26****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)SEE PREVIOUS LIST.PLANS PREPARED BY A DESIGN
 PROFESSIONAL REQUIRED.COMMENTS NOT PROPERLY
 ADDRESSED, AND NO PRODUCT APPROVALS WERE SUBMITTED.
 DRAFTSMAN HAD CALLED AND STATED THAT THIS IS INTERIOR
 ONLY.YOU ARE FRAMING WINDOW OPENINGS IN AN EXTERIOR
 WALL; THIS IS EXTERIOR WORK.THE PLANS ARE TO BE
 ARCHITECTURAL QUALITY AND TO CLEARLY SHOW SCOPE OF
 WORK.
  
 2.)OWNER CANNOT DO OWNER/BUILDER AS THIS IS TWO
 UNITS.OWNER/BUILDER AFFIDAVIT IS NO LONGER IN THE
 PACKAGE.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-01-23 Cont ID  
Sent By shill Date 2007-01-16 Time 13:11 Rev Time 0.00
Received By shill Date 2007-01-16 Time 13:06 Sent To  
Notes
2007-01-23 14:50:30****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
  
 1.)PROVIDE PRODUCT APPROVAL FOR THE NEW WINDOWS.
 IMPACT PROTECTION REQUIRED.IF THE WINDOWS ARE NON
 IMPACT, PROVIDE PRODUCT APPROVAL FOR THE SHUTTERS.
 COMPLETE THE INSTALLATION SCHEDULE IF YOU ARE USING
 SHUTTERS TO COMPLY WITH THE IMPACT REQUIREMENT, SEE
 ATTACHED.
  
 2.)PLANS ARE TO BE ARCHITECTURAL QUALITY AND OF
 SUFFICIENT CLARITY TO SHOW SCOPE OF WORK, FBC*106.1.1.
 PLANS SUBMITTED DO NOT SHOW ALL INFORMATION REQUIRED.
  
 3.)PROVIDE PLANS PREPARED BY A DESIGN PROFESSIONAL,
 FBC*106.1.
  
 4.)THE PLAN VIEW OF THE WEST ELEVATION DOES NOT MATCH
 ELV 2, WEST, AND ELV 1 NORTH PLAN VIEW DOES NOT MATCH
 THE ELEVATION.IT IS NOT CLEAR IF THIS IS AN INTERIOR
 OR EXTERIOR ELEVATION.
  
 5.)IT IS NOT CLEAR HOW THE LOADS WILL BE TRANSFERRED
 TO THE GROUND, CORNER OF THE KITCHEN WHERE YOU ARE
 REMOVING THE SECTION OF WALL.IN OTHER WORDS, WHAT
 WILL HOLD UP THE WALL AT THE CORNER?PROVIDE A
 DETAIL.
  
 6.)ELV 4 SHOWS NEW WINDOWS INSTALLED OVER GLASS
 BLOCK.GLASS BLOCK IS USUALLY NOT STRUCTURAL; WHAT
 WILL SUPPORT THE WINDOWS?PROVIDE A DETAIL.
  
 7.)YOU PROPOSE CUTTING A HOLE IN A WALL, ELV 4.HOW
 WILL THE LOADS (ROOF, WALL ABOVE THE PROPOSED WINDOWS)
 BE TRANSFERRED?PROVIDE A DETAIL.THE PLANS ARE TO
 SHOW ALL INFORMATION REQUIRED TO DETERMINE CODE
 COMPLIANCE.THE APPLICATION STATES THAT THIS IS A NON
 LOAD BEARING WALL.NOTE THAT EVEN IF THIS IS NOT LOAD
 BEARING, THE LOAD OF THE WALL ITSELF MUST STILL BE
 TRANSFERRED TO THE FOUNDATION.
  
 8.)TOP VIEW 2ND FLOOR PLAN DOES NOT MATCH THE FLOOR
 PLAN.ONE SHOWS A BUILDING WHICH IS A SQUARE; THE
 OTHER SHOWS AN L SHAPE.IS THIS A TWO STORY BUILDING?
 ALSO THE L SHAPE SHOWS A PORCH WHICH DOES NOT APPEAR ON
 THE SQUARE BUILDING.
  
 9.)HOW HAVE YOU DETERMINED WHICH STRAP TO USE?
 PROVIDE CALCULATIONS.IN THE CATALOG, THIS IS A WOOD
 TO WOOD CONNECTOR.PROVIDE A TECHNICAL BULLETIN OR
 OTHER INFORMATION FROM THE MANUFACTURER TO SHOW THAT
 THIS STRAP IS ACCEPTABLE IN A WOOD TO MASONRY
 APPLICATION.MANUFACTURER IS TO SPECIFY FASTENING AS
 THIS IS EITHER ENGINEERED OR TESTED.
  
 10.)TOP VIEW APPEARS TO SHOW BOTH THE FLOOR PLAN AND
 THE ROOF FRAMING PLAN.PROVIDE AS SEPARATE PLAN VIEWS.
 THE PORCH DOES NOT APPEAR ON THIS PLAN.ARE THEY TWO
 DIFFERENT UNITS; ONE ON THE FIRST FLOOR, ONE ON THE
 SECOND?
  
 11.)IF THE PORCH IS FULLY ENCLOSED, IS IT ALREADY
 INTERIOR SPACE?EXISTING CONDITIONS NOT CLEAR.
  
 12.)PROVIDE WIND DESIGN CRITERIA FBC R301.
  
 13.)THE APPLICATION STATES THAT YOU ARE REPLACING A
 BROKEN REAR WINDOW.SHOW ON THE PLAN.IF YOU ARE NOT
 PROVIDING IMPACT PROTECTION DUE TO THE EXCEPTION IN FBC
 EB 507.3, PROVIDE CALCULATIONS TO SHOW COMPLIANCE.
  
 14.)ELV 3 SHOWS A DOOR OPENING WHICH WILL BE FRAMED
 IN.PROVIDE A STRUCTURAL DETAIL.NO STRAPS SHOWN.NO
 INFORMATION PROVIDED AS TO HOW THE 2X8S WILL ATTACH TO
 THE BLOCK WALL.
  
 15.)THE ELV 4 SHOWS THREE WINDOWS.WHAT IS BETWEEN
 THE WINDOWS?IF MULLIONS ARE USED TO JOIN WINDOWS,
 PROVIDE A PRODUCT APPROVAL FOR THE MULLIONS.
  
 16.)IS THE PORCH CURRENTLY UNDER AIR?WILL IT NOW BE
 AIR CONDITIONED?
  
 17.)DECLARE GOVERNING CODE, INCLUDING FBC EB.
  
 18.)DECLARE LEVEL OF ALTERATION, FBC EB CHAPTER 3.

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2007-06-26 Cont ID  
Sent By btrobaug Date 2007-06-26 Time 14:54 Rev Time 0.00
Received By btrobaug Date 2007-06-26 Time 13:32 Sent To B
Notes
2007-06-26 15:26:47 
  
  
 R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS REQUIRED IN
 NEW DWELLINGS WHEN REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR. SEE ARTICLE FOR COMPLETE TEXT.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-05-22 Cont ID  
Sent By btrobaug Date 2007-05-22 Time 09:34 Rev Time 0.75
Received By btrobaug Date 2007-05-22 Time 09:05 Sent To B
Notes
2007-05-22 09:34:36 
 DENIED/INCOMPLETE INFORMATION
  
 1} CHANGE THE APPLICATION DESCRIPTION TO INCLUDE ALL
 ELECTRICAL WORK INTENDED UNDER THIS PERMIT. A PERMIT
 SHALL NOT BE ISSUED UNTIL FEES AUTHORIZED UNDER SECTION
 553.80, FLORIDA STATUTES, HAVE BEEN PAID. 108.1 FBC.
 ADJUST THE VALUE AT THE PERMIT CLERK?S DESK, AND PAY
 THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING.
  
 2} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS
 AMENDED.
  
 3} AT LEAST ONE WALL SWITCH-CONTROLLED LIGHTING OUTLET
 SHALL BE INSTALLED IN EVERY HABITABLE ROOM AND
 BATHROOM.210.70(A)(1), INDICATE COMPLIANCE FOR THE
 "FLORIDA ROOM" ON THE PLAN.
  
 4} ADD RECEPTACLES TO THE FLORIDA ROOM FOR SPACING
 REQUIREMENTS OF 210.52(A)(1).
  
 5}INDICATE IF THE PANEL IN THE "UTILITY AREA" IS NEW
 OR EXISTING. IF NEW UNDER THIS APPLICATION, SUBMIT A
 RISER DIAGRAM SHOWING HOW IT IS FED, OCP , CONDUIT AND
 CONDUCTOR SIZE AND TYPES.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-04-19 Cont ID  
Sent By btrobaug Date 2007-04-19 Time 07:52 Rev Time 0.33
Received By btrobaug Date 2007-04-19 Time 07:37 Sent To PC
Notes
2007-04-19 07:52:35 
  
  
 DENIED/INCOMPLETE INFORMATION
  
 1} THERE ARE ELECTRICAL PLANS PROVIDED BUT NO
 ELECTRICAL WORK IN THE DESCRIPTION ON THE APPLICATION.
 PLEASE INDICATE WHAT THE INTENDED WORK IS , INDICATE
 SAME ON THE APPLICATION AND INCREASE THE VALUE TO
 INCLUDE SAME.
  
 2} THE ARCHITECTURAL FIRM WHOSE TITLE BLOCK APPEARS ON
 THE PLANS, MUST SIGN AND SEAL THE PLAN PER
 481.221(1)(B)FS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-08-13 Cont ID  
Sent By adarroug Date 2007-08-13 Time 16:01 Rev Time 0.00
Received By adarroug Date 2007-08-13 Time 16:01 Sent To B
Notes
2007-08-13 16:01:17TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-07-30 Cont ID  
Sent By adarroug Date 2007-07-30 Time 16:26 Rev Time 0.00
Received By adarroug Date 2007-07-30 Time 16:26 Sent To B
Notes
2007-07-30 16:26:58TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-06-21 Cont ID  
Sent By adarroug Date 2007-06-21 Time 09:04 Rev Time 0.00
Received By adarroug Date 2007-06-21 Time 09:04 Sent To E
Notes
2007-06-21 09:04:58TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-05-11 Cont ID  
Sent By adarroug Date 2007-05-11 Time 16:04 Rev Time 0.00
Received By adarroug Date 2007-05-11 Time 16:04 Sent To  
Notes
2007-05-11 16:04:45TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-04-12 Cont ID  
Sent By adarroug Date 2007-04-12 Time 13:25 Rev Time 0.00
Received By adarroug Date 2007-04-12 Time 13:25 Sent To B
Notes
2007-04-12 13:25:40TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-02-15 Cont ID  
Sent By adarroug Date 2007-02-15 Time 11:18 Rev Time 0.00
Received By adarroug Date 2007-02-15 Time 11:18 Sent To B
Notes
2007-02-15 11:19:24TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-02-15 Cont ID  
Sent By adarroug Date 2007-02-15 Time 11:14 Rev Time 0.00
Received By adarroug Date 2007-02-15 Time 11:14 Sent To B
Notes
2007-02-15 11:15:10TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-01-23 Cont ID  
Sent By shill Date 2007-01-23 Time 14:50 Rev Time 0.00
Received By shill Date 2006-11-20 Time 12:38 Sent To  
Notes
2006-11-20 12:38:52TO "MISC" BOX#1

Review Stop Z ZONING
Rev No 1 Status N Date   Cont ID  
Sent By btrobaug Date   Time   Rev Time  
Received By btrobaug Date   Time   Sent To  
Notes
***NONE***