Plan Review Details - Permit 06110599
Plan Review Stops For Permit 06110599
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-12-14 Cont ID  
Sent By lursu Date 2006-12-14 Time 16:51 Rev Time 0.00
Received By lursu Date 2006-12-14 Time 16:51 Sent To  
Notes
2006-12-14 16:54:03NEW ADDRESS HAS BEEN ISSUED AS 3800 NORTH SHORE DR,
 WEST PALM BEACH , FL 33407
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-12-08 Cont ID  
Sent By jgomez Date 2006-12-08 Time 17:56 Rev Time 0.00
Received By jgomez Date 2006-12-08 Time 17:36 Sent To  
Notes
2006-12-08 18:01:02BUILDING REVIEW CHECKLIST:
 1- PROVIDE NOTICE OF COMMENCEMENT AS REQUIRED BY SEC.
 713.13 FLORIDA STATUTES.
  
 2- PROVIDE COPY OF IMPACT FEES PAID RECEIPT.
  
 3- SHEET A-1: TOTAL AREA DOESN'T ADD UP. REVISE TOTAL
 AREA AS REQUIRED. BREAK DOWN BALCONY AREAS TO PROPERLY
 ACCESS RADON FEES. NEED SQUARE FOOTAGE OF BALCONY WITH
 ROOF OVER AND BALCONY WITHOUT ROOF OVER.
  
 4- PROVIDE SOIL TEST REPORT. R401.4 2004 FLORIDA
 RESIDENTIAL CODE.
  
 5- TRUSS PACKAGE WILL BE REQUIRED TO BE SUBMITTED TO
 THIS OFFICE PRIOR TO INSTALLATION. TRUSS PACKAGE TO BE
 REVIEWED AND APPROVED BY THE DESIGNER OF RECORD. SEE
 SEC. R802.10.1 2004 FL. RESIDENTIAL CODE AND PROVIDE
 ALL REQUIRED INFORMATION.
  
 6- PROVIDE PLANS/SPECS FOR LOT DRAINAGE AS REQUIRED BY
 SEC. R401.3 2004 FL. RESIDENTIAL CODE. PROVIDE POSITIVE
 DRAINAGE WITHOUT GOING TO NEIGHBOR'S PROPERTY.
  
 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) PRECAST LINTELS.
 B) WINDOW MULLIONS.
 C) ENTRY DOORS.
 D) SIDE GARAGE DOOR.
 E) ALL SIMPSON OR USP CONNECTORS SPECIFIED IN PLANS
 AND DETAILS.
  
 8- PROVIDE FIREPLACE SPECS AND UL LISTING AS REQUIRED
 BY SEC. R1002.1 AND R1002.4 2004 FL. RESIDENTIAL CODE.
  
 9- PROVIDE SPECIFICATIONS AND LISTING FOR BBQ GRILLTO
 BE INSTALLED IN THE REAR PORCH AS REQUIRED BY SEC.
 G2447 2004 FL. RESIDENTIAL CODE. SPECS TO SHOW THAT
 PRODUCTISDESIGNED FOR PORCH INSTALLATION.
  
 10- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 11- SPECIFY ON PLANS THE CHIMNEY TERMINATION AS
 REQUIRED BY SEC. G2427.5.3 2004 RESIDENTIAL CODE.
  
 12- PROVIDE MANUFACTURER SPECS AND LISTING FOR ROOFAT
 CHIMNEY TERMINATION AS REQUIRED BY SEC. R1002.2 2004
 FL. RESIDENTIAL CODE. REVISE ELEVATIONS TO MATCH
 MANUFACTURER'S SPECS.
  
 13- PROVIDE COMPLETE RAILING AND GUARDRAIL DETAILS
 SHOWING COMPLIANCE WITH SEC. R312 2004 FL. RESIDENTIAL
 CODE. THIS APPLIES TO INTERIOR RAILINGS AND BALCONY
 GUARDRAIL.
  
 14- PROVIDE COMPLETE ENGINEERED PACKAGE OF EPICORE
 FLOOR SYSTEM.PACKAGE TO BE REVIEWED AND APPROVED BY
 THE ENGINEEROF RECORD PRIOR TO SUBMITTAL. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 15- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING
 AS REQUIRED BY SEC. 106.1.1.2 CITY AMENDMENTS TO FBC
 2004. (NOTE SAYING INSTALLATION PER PRODUCT APPROVAL IS
 NOT ACCEPTABLE. DESIGNERNEEDS TO SPECIFY FASTENING TO
 DEMONSTRATE COMPLIANCE WITH WIND CRITERIA. PRODUCT
 APPROVAL IS TO DEMONSTRATE THAT THE PRODUCT MEETS THE
 DESIGN CRITERIA.
  
 16- REVISE ENERGY CALCULATIONS. PROVIDE:
 A) CORRECT ADDRESS.
 B) CORRECT BUILDER.
 C) CORRECT PERMITTING OFFICE.
 D) CORRECT JURISDICTION.
 E) OWNER/AGENT TO SIGN AND DATE AT BOTTOM OF FORM.
  
 17- SHEET SP-1:
 A) SITE PLAN SHOWSARROWS DIRECTING TOWARD FRONT
 AND BACK OF PROPERTY.IF THIS IS FOR DRAINAGE, THEN
 NEED TO REVISE. NEED TO PROVIDE POSITIVE DRAINAGE AND
 IT CAN'T GO TO NEIGHBOR'S PROPERTY.
  
 B) COMPLETE INFORMATION REGARDING SURVEY
 INFORMATION. SEE NOTE AT BOTTOM OF SHEET.
  
 18- SHEET A-5: NEED CRICKET BY CHIMNEY. SEC. R1001.17
 2004 FL. RESIDENTIAL CODE.
  
 19- THE WIDTH OF STAIRWAY LANDING SHALL NOT BE LESS
 THAN THE STAIRWAY SERVED.REVISE LANDING WIDTH AS
 REQUIRED. SEC. R311.5.4 2004 FL. RESIDENTIAL CODE.
  
 20- BUILDING SECTION B/A-6: CORRECT REFERENCE FOR
 EVERYTHING RELATED TO STAIRWAY IS R311, NOT SEC.
 1009.11 FBC. REVISE AS REQUIRED.
  
 21- BUILDING SECTION A/A-7: REVISE ELEVATION REFERENCE
 FOR FIRST FLOOR AND SECOND FLOOR.IT READS ROOF TRUSS
 BEARING AT 21'-0".
  
 22- SHEET S-4: FRONT ELEVATION ISMISSING THE
 CALCULATED DESIGN PRESSURES FOR OPENINGS AT LIVING ROOM
 AND FOYER. SEC. R301 2004 FL. RESIDENTIAL CODE.
  
 23- SHEET S-5:
 A) TRUSS TIE DOWN SCHEDULE: REVISE NOTE #6. SEE
 SIMPSON CATALOGUE FOR REQUIRED EMBEDMENT. OTHERWISE
 PROVIDE COMPLETE ENGINEERING ANALYSIS IF SPECIFICATIONS
 ARE DIFFERENT FROM THOSE TESTED AND PUBLISHED BY THE
 MANUFACTURER.SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 B) REVISE TYPICAL STEP FOOTING DETAIL TO COMPLY WITH
 SEC. R311.5.3.2 2004 FL. RESIDENTIAL CODE.
  
 C) ROOF WIND PRESSURE CHART LOCATED ON RIGHT HAND
 SIDE OF TRUSS TIE DOWN SCHEDULE IS FOR WALLS NOT FOR
 ROOFS. REVISE TITLE AS REQUIRED.
  
 D) DESIGN LOAD SCHEDULE: NEED ATTIC LIVE LOAD AS
 REQUIRED BY TALE R301.5 2004 FL. RESIDENTIAL CODE.
  
  
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-11-30 Cont ID  
Sent By dpalmer Date 2006-11-30 Time 20:13 Rev Time 0.00
Received By dpalmer Date 2006-11-30 Time 19:41 Sent To Z
Notes
2006-11-30 20:16:19*** UNSAT ***
  
  
 1) NOTE: PLEASE BE SURE TO SPECIFY THE FOLLOWING CODES
 ON THE PLANS.
 2002 NFPA-70 AND 2002 NFPA-72
  
 2) NOTE: PLEASE SEE DEFINITIONS IN NFPA-72 FOR SMOKE
 DEVICES. PLEASE KNOW IF THESE DEVICES ARE PART OF A LOW
 VOLTAGE ALARM SYSTEM THEN THE SD DESIGNATION FOR SMOKE
 DETECTORS IS OK, HOWEVER IF INDEED THESE ARE 120V
 DEVICES WHICH DETECT AND ACTUALLY HAVE AN ALARM, PLEASE
 INDICATE AS "SA". THIS WAS RECENTLY BROUGHT TO OUR
 ATTENTION FROM NFPA WHICH IS NOT THE SAME AS THE
 STANDARD WHICH HAS BEEN REQUESTED ON ALL PREVIOUS
 REVIEWS.
  
 3) NOTE: PLEASE NOTE DEVICE LOCATIONS AND INSTALLATIONS
 PER 11.5.1.1, AND 11.8.3, AS THESE DEVICES SHALL BE
 LOCATED WITHIN 12 INCHES ON A FLAT CEILING. PLEASE KNOW
 ANY CEILING WHICH CONTAINS A TRAY HIGHER THAN 12
 INCHES, THEN THE DEVICE MUST BE INSTALLED WITHIN THE
 12".
 PLEASE SEE MISSING SA/SD AT THE LOWER LEVEL OF DWELLING
 IN THE IMMEDIATE VICINITY LEADING TO THE FLOOR ABOVE.
 NFPA-72 11.8.3
  
 4) NOTE: PLEASE SUBMIT MANUFACTURE SPEC/CUT SHEETS FOR
 THE PROPOSED MTS.PLEASE SEE THIS UNIT SHALL BE
 SERVICE ENTRANCE RATED.
 PLEASE SEE REQUIREMENTS FOR SERVICE ENTRANCE RATED
 DEVICES.
 PLEASE SEE AS THE MTS IS NOT SHOWN, MAINS ARE NOT
 GROUPED AT THIS TIME. 230.72
 PLEASE SEE 230.76, 230.79, 230.70, 90.7, AND 110.3 ETC
 FBC 106.1.2 ADMIN SECTION.
  
 5) NOTE: PLEASE SEE 250.6 AND 250.24B, WHICH DOES NOT
 PERMIT EQUIPMENT GROUNDING CONDUCTORS INSTALLED UNTIL
 AFTER THE FIRST MEANS OF DISCONNECT.
 PLEASE SEE RISER AND ADJUST.
  
 6) NOTE: PLEASE SEE MISSING SERVICE ENTRANCE
 CONDUCTORS, THE NOTE SEEMS TO START TO LIST A CERTAIN
 SIZE MCM, BUT DOES NOT GIVE SIZE. PLEASE SEE 310.15B6
 FOR MINIMUM SIZES.
 240.4, 310.16
 FBC 106.1.2
  
 7) NOTE: PLEASE SEE MISSING DISCONNECT FOR WATER
 HEATER.
 422.31
  
 8) NOTE: PLEASE VERIFY THE SIZE OF THE OF THE WH HEAT.
 PLEASE SEE 4KW DOES NOT SEEM TO BE A COMMON SIZE.
 PLEASE KNOW IN EITHER CASE THE MAXIMUM OCP IS 150%,
 422.11E3, OR MIN IS 125%. 422.13.
  
 9) NOTE: PLEASE LIST ALL THE ARC FAULT PROTECTED
 CIRCUITS ON PANEL SCHEDULE.
 210.12
  
 10) NOTE: PLEASE SEE MISSING DEDICATED BATH ROOM
 CIRCUITS AS REQUIRED PER 210.52D, 210.11C3. PLEASE SEE
 THERE ARE SEVERAL CIRCUITS WHICH ARE SHOWN AS GFI, YET
 ARE THESE FOR THE BATH ROOMS?
 408.4, 310.16, ETC.
  
 11) NOTE: PLEASE SEE MISSING KITCHEN ISLAND RECEPTS PER
 210.52C2
  
 12) NOTE: PLEASE SEE MISSING KITCHEN COUNTER SPACE
 RECEPTS PER 210.52C1
  
 13) NOTE: PLEASE SEE 210.8A6, AS ALL RECEPTS SERVING
 KITCHEN COUNTER SPACE SHALL BE SHOWN AS GFI/GFI
 PROTECTED.
  
 14) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.16 AS
 1500VA SHALL BE FIGURED FOR EACH OF THE SMALL APPLIANCE
 CIRCUITS, EVEN IF MORE THAN 2. THERE ARE TWO SHOWN
 WHICH ARE OK, HOWEVER AS THE NOTED IN NOTE #10, THERE
 ARE SEVERAL GFI CIRCUITS, YET NOT CLEAR WHAT THESE ARE
 FOR.
  
 15) NOTE: PLEASE SEE ONE REDLINED SET FOR LOCATIONS FOR
 MISSING RECEPTS REQUIRED FOR WALL SPACE PER 210.52.
  
 16) NOTE: PLEASE SEE MISSING AIC RATINGS FOR ALL
 SERVICE EQUIPMENT.
 PLEASE KNOW THIS INCLUDES THE PROPOSED MTS.
 110.9, 702.5
  
 17) NOTE: PLEASE KNOW THE ADDRESS WHICH IS NOW KNOWN,
 SHALL BE INDICATED ON THE TITLE BLOCK. PLEASE SEE THE
 ADDRESS OF 3808 NORTHSHORE.
 FBC 106.1.2, FAC 61G1-16.004
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2006-11-30 20:13:27ROUTED BACK TO ZONING AT REQUEST PER ZONING.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-12-08 Cont ID  
Sent By jgomez Date 2006-12-08 Time 18:01 Rev Time 0.00
Received By jgomez Date 2006-11-29 Time 19:27 Sent To Z
Notes
2006-11-29 19:28:01SENT TO ZONING (SF RACK)

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-12-04 Cont ID  
Sent By tgordon Date 2006-12-04 Time 10:22 Rev Time 0.46
Received By tgordon Date 2006-12-04 Time 10:21 Sent To P
Notes
2006-12-04 10:48:06*** DENIED ***
 1) MECHANICAL PLANS DUCT LAY-OUT IS DIFFICULT TO READ,
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY.
 PER 2004 FBC 106.1.1.
  
 2) THE ARCHITECT JEFFREY GAPSTUR NEEDS TO SEAL THE
 MECHANICAL PLANS AS HIS INFORMATION IS IN THE TITLE
 BLOOK, PERFAC 61G1-16.003.
  
 3) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 4)PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR GAS
 FIREPLACE.
  
 5) OPEN GAS GRILL IN COVERED PORCH WILL NEED AN
 APPROVED EXHAUST HOOD, PER FBC/M 505.3.
  
 6) NEED TO SHOW AN A/C EQUIPMENT LISTING WITH ALL
 PERTINENT INFORMATION ON THE MECHANICAL PLANS.
  
 7) NEED TO PROVIDE COMBUSTION AIR FOR GAS CLOTHES DRYER
 OR PROVIDE COMBUSTION AIR CALCULATIONS, PER 2004 FBC/R
 M1701.1.
  
 8) MECHANICAL PLANS ARE SHOWING A GAS WATER HEATER, THE
 ELECTIRACL AND PLUMBING PLANS ARE SHOWING A ELECTRIC
 WATER HEATER, PLEASE CORRECT.
  
 9) 10" RETURN AIR TRANSFER DUCT TO MASTER SUITE NEEDS
 TO BE 18", SEE (A) AND (C) EXSEPT.
 BALANCED RETURN AIR MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  
  
  
  
 .

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-12-05 Cont ID  
Sent By jleech Date 2006-12-05 Time 14:49 Rev Time 0.00
Received By jleech Date 2006-12-05 Time 14:49 Sent To B
Notes
2006-12-05 14:58:23DENIED;
 SANITARY RISER DIAGRAM;
 1.AUOMATIC CLOTHES WASHER NOT SHOWN ON SANITARY RISER
 DIAGRAM. BRANCH DRAIN TO BE 3" WITH A CLEANOUT AT 48"
 AFF. SECTION 406.3.
 2.LAUNDRY SINK TO DISCHARGE DOWN STREAM OF THE BATHROOM
 GROUP. SEC. 909.1.
 3.FIRST FLOOR SHOWER NOT VENTED. MASTER BATH CANNOT
 DISCHARGE INTO THE VENT FOR THE 1ST FLOOR SHOWER.
 MASTER BATH MUST DISCHARGE DOWN STREAM OF THE FIRST
 FLOOR BATHROOM GROUP.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status F Date 2006-11-30 Cont ID  
Sent By jgomez Date 2006-12-08 Time 18:01 Rev Time 0.00
Received By mmclean Date 2006-11-30 Time 15:42 Sent To P
Notes
2006-11-30 15:57:39DENIED,
 1. PLEASE PROVIDE A COPY OF THE SURVEY.
 2. THE PROPOSED POST CAN ONLY BE A MAXIMUM OF 4FT HIGH
 WITHIN THE FIRST 25FT FRONT SETBACK.
 3. A SEPARATE PERMIT MUST BE SUBMITTED FOR THE
 POST/GATE/FENCE WITH EASMENT APPROVAL FROM THE CITY OF
 WEST PALM BEACH UTILITY DEPT.
 4. PLEASE PROVIDE THE DIMENSION OF THE PROPOSED WALKWAY
 AND DRIVEWAY (LENGTH & WIDTH).
  
 NOTE: MUST MAINTAIN 1000SQ FT OR 75% OF LANDSCAPE,
 WHICHEVER IS LESS WITHIN THE FIRST 25FT FRONT SETBACK.
  
 5. NEED TO SHOW THE PROPOSED A/C ON THE SITEPLAN.
  
 NOTE: SEC 94-303 MECHANICAL/POOL EQUIPMENT/GENERATOR
 MAY NOT PROJECT MORE THAN FOUR FEET INTO A SETBACK.
  
 6. PLEASE SHOW THE PROPOSED TRELLIS ON THE TWO COPY OF
 SITEPLAN WITH SETBACKS. (A-5).
 7. CHIMNEYS/FIREPLACE MAY NOT PROJECT NO MORE THAT 18
 INCHES INTO ANY SETBACKS (SEC 94-305(10).
  
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720
  