Plan Review Details - Permit 06110556
Plan Review Stops For Permit 06110556
Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2008-02-01 Cont ID  
Sent By mjacobs Date 2008-02-01 Time 13:45 Rev Time 0.00
Received By lmartine Date 2008-02-01 Time 13:45 Sent To  
Notes
2008-02-01 13:46:37REVISION CHANGE BATHROOM LOCATION IN SUITE 'C' OK
 LM

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2007-08-29 Cont ID  
Sent By lmartine Date 2007-08-29 Time 15:02 Rev Time 0.00
Received By lmartine Date 2007-08-29 Time 15:02 Sent To  
Notes
2007-08-29 15:05:50FACADE COLUMN REVISIONS OK LM

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2007-08-16 Cont ID  
Sent By mjacobs Date 2007-08-16 Time 11:05 Rev Time 0.00
Received By mjacobs Date 2007-08-16 Time 11:01 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2007-08-09 Cont ID  
Sent By mjacobs Date 2007-08-09 Time 07:58 Rev Time 0.00
Received By mjacobs Date 2007-08-09 Time 07:55 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-07-16 Cont ID  
Sent By mjacobs Date 2007-07-16 Time 12:27 Rev Time 0.00
Received By mjacobs Date 2007-07-16 Time 11:19 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2007-07-12 Cont ID  
Sent By mjacobs Date 2007-07-12 Time 14:38 Rev Time 0.00
Received By mjacobs Date 2007-07-12 Time 07:43 Sent To PC
Notes
2007-07-12 14:38:30BUILDING PLAN REVIEW
 PERMIT:
 ADD:
 CONT:
 TEL: (561)###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 5TH
 ACTION: DENIED
  
 1)THE ENERGY CALCULATION FORMS SUBMITTED IS THE
 INCORRECT VERSION. SEE FBC. 13-400.3.A METHOD A FORMS.
 AN ACCURATELY COMPLETED FORM 400A-04R VERSION 2.5
 DEMONSTRATING THAT CODE COMPLIANCE HA BEENACHIVED SHALL
 BE SUBMITTED TO THE BUILDING OFFICIAL.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-06-16 Cont ID  
Sent By mjacobs Date 2007-06-16 Time 14:15 Rev Time 0.00
Received By mjacobs Date 2007-06-16 Time 13:18 Sent To Z
Notes
2007-06-16 14:15:42BUILDING PLAN REVIEW
 PERMIT: 06110556
 ADD: 2814 S. DIXIE HWY
 CONT: KARNS CONST.
 TEL: (561)805-7528
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 3RD
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)OK.
  
 3)OK.
  
 4)OK.
  
 5)OK
  
 6)OK
  
 7)FBC. 1210.2 WALLS WITHIN 2 FEET OF WATER CLOSETS
 SHALL HAVE A SMOOTH, HARD, AND NONABSORBENT SURFACE, TO
 A HEIGHT OF 4 FEET ABOVE THE FLOOR, AND EXCEPT FOR
 STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS
 SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY
 MOISTURE. PAINT ON DRYWALL IS NOT A HARD SURFACE.
  
 8)OK
  
 9)OK.
  
 10) OK
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-05-09 Cont ID  
Sent By mjacobs Date 2007-05-09 Time 11:58 Rev Time 0.00
Received By mjacobs Date 2007-05-08 Time 11:52 Sent To  
Notes
2007-05-08 12:48:24BUILDING PLAN REVIEW
 PERMIT: 06110556
 ADD: 2814 S. DIXIE HWY
 CONT: KARNS CONST.
 TEL: (561)805-7528
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 3RD
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)OK.
  
 3)OK.
  
 4)OK.
  
 5)WHEN RESUBMITTING, HAVE THE FRONT COUNTER STAFF
 ADJUST THE VALUE OF THE PROJECT AND PAY THE ADDITIONAL
 FEES ACCORDINGLY.
  
 6)SEE INFORMATION ABOUT THE CONSTRUCTION OF THE
 DUMPSTER ENCLOSURE IN THE PACKAGE AND FOLLOW THOSE
 GUIDELINES. DUMPSTER ENCLOSURE MUST HAVE MINIMUM OF
 12'-6" OPENING BETWEEN THE GATE POSTS. ON SHEET 2
 INDICATE ALL DIMENTIONS FOR THE DUMPSTER ENCLOSURE.
  
 7)FBC. 1210.2 WALLS WITHIN 2 FEET OF WATER CLOSETS
 SHALL HAVE A SMOOTH, HARD, AND NONABSORBENT SURFACE, TO
 A HEIGHT OF 4 FEET ABOVE THE FLOOR, AND EXCEPT FOR
 STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS
 SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY
 MOISTURE. PAINT IS NOT HARD.
  
 8)THE PLANS INDICATE IMPACT GLASS, HOWEVER, THE
 PRODUCT APPROVALS IS FOR NON-IMPACT GLASS. CLARIFY.
 PROVIDE THE CORRECT INFORMATION FOR THE STOREFRONT
 GLASS.
  
 9)OK.
  
 10)IF THE SIDEWALK WILL BE ALTERED THE PLANS SHALL BE
 REVIEW BY THE ENGINEERING DEPARTMENT.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-03-24 Cont ID  
Sent By mjacobs Date 2007-03-24 Time 13:07 Rev Time 0.00
Received By mjacobs Date 2007-03-24 Time 13:06 Sent To PC
Notes
2007-03-24 13:06:58BUILDING PLAN REVIEW
 PERMIT: 06110556
 ADD: 2814 S.DIXIE HWY #105
 CONT: KARNS CONST. CORP.
 TEL: (561)805-7528
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 2ND
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)FBC. 106.3.5THE EXAMINATION OF THE DOCUMENTS BY
 THE BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING
 MINIMUM CRITERIA AND DOCUMENTS: A FLOOR PLAN; SITE
 PLAN; FOUNDATION PLAN; FLOOR/LAYOUT;AND ALL EXTERIOR
 ELEVATIONS WITH THE ACCESSIBLE ROUTE TO EACH UNIT IN
 COMPLIANCE WITH FBC. 11-4.3.
  
 3)106.1.1W.P.B. ADMINISTRATIVE CODE CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE.
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES.
 SUCH INFORMATION SHALL BE SPECIFIC
 AND THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE
 TERM "LEGAL" OR ITS RQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION".
  
 4)IF THE NEW 4" CONCRETE SLAB IS CONSTRUCTED AT EACH
 DOOR HOW DOES EACH ENTRANCE COMPLY WITH THE
 ACCESSIBILITY CODE? SHOW COMPLIANCE. SEE 2004 FBC. FIG
 11 AND 12 OF CH. 11.SHEET 1 SHOWS THE ACCESSIBLE
 ROUTE TO SUITE 'A' ONLY WHAT ABOUT THE OTHER SUITES?
 ALSO FBC. 11-4.8.1 ANY PARTOF AN ACCESSIBLE ROUTE WITH
 A SLOPE GREATER THAN 1:20 SHALL BE CONSIDERED A RAME
 AND SHALL COMPLY WITH SECTION 11-4.8.
  
 5)WHEN RESUBMITING, HAVE THE FRONT COUNTER STAFF
 ADJUST THE VALUE OF THE PROJECT AND PAY THE ADDITIOINAL
 FEES ACCORDINGLY. FOR MORE INFORMATION SEE WPB.
 AMENDMENTS 108.3.
  
 6)SEE INFORMATION ABOUT THE CONSTRUCTION OF THE
 DUMPSTER ENCLOSURE IN THE PACKAGE AND FOLLOW THOSE
 GUIDELINES.
  
 7)FBC. 1210.2 WALLS WITHIN 2 FEET OF WATER CLOSETS
 SHALL HAVE A SMOOTH, HARD, AND NONABLORBENT SURFACE, TO
 A HEIGHT OF 4 FEET ABOVE THE FLOOR, AND EXCEPT FOR
 STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS
 SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY
 MOISTURE.
  
 8)ALL THE PRODUCT APPROVALS SUBMITTED SHALL BE
 APPROVED IN WRITING "(NO PHOTO-COPIES ALLOWED)" BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL.THE ONES
 SUBMITTED ARE PHOTOCOPIES. WPB.AMENDMENTS 106.3.3.
  
 9)ALL PAGES SUBMITTED SHALL BE SIGNED, DATED AND SEAL
 BY THE ARCHITECT OR ENGINEER IN RESPONSIBLE CHARGE. SEE
 F.A.C. 61G15-23.002 AND 61G1-16.004 / 471.025. FOR MORE
 INFORMATION. THE MECHINICAL SHEETS (M-1) HAS A
 CORPORATE SEAL. THIS SEAL HAS NO BEARING ON THE
 DRAWINGS. SHEET (M-2) IS NOT SEAL. NOTE ALL SIGNATURES
 SHALL BE ORIGINAL.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-12-21 Cont ID  
Sent By mjacobs Date 2006-12-21 Time 11:44 Rev Time 0.00
Received By mjacobs Date 2006-12-21 Time 11:43 Sent To  
Notes
2006-12-21 11:44:29BUILDING PLAN REVIEW
 PERMIT: 06110556
 ADD: 2814 S. DIXIE HWY.
 CONT: KARNS CONSTRUCTION CORP.
 TEL: (561)805-7528
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW1ST.
 ACTION: DENIED
  
 NOTE: ANY OTHER OCCUPANCY OTHER THAN WHAT IS STATED BY
 THE DESIGNER OF RECORD SHALL REQUIRE A SEPERATE
 PERMIT.
  
 1) 106.3.3* PRODUCT APPROVALS- 2004
 THOSE PRODUCTS THAT ARE RGULATED BY DCA. RULE 9B-72
 SHALL BE REVIEWED AND APPROVED IN WRITTING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. SUBMIT PRODUCT APPROVALS FOR
 THE IMPACT WINDOWS/DOORS/ROOF AND STOREFRONT.
  
 2)W.P.B. AMENDMENTS 108.3*IF IN THE OPINION OF THE
 BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING,ALTERATION APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL,ELECTRIC,PLUMBING,MECHANICAL,INTERIOR
 FINISH,ARCHITECTURAL AND DESIGN FEES,MARKETING COSTS,
 AND OVERHEAD AND PROFIT. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS
 SERVICES.
  
 3)SHEET #1. IN REFERENCE TO THE DUMPSTER PAD, SEE
 REQUIREMENTS DETAILS IN PACKAGE AND COMPLY
 ACCORDINGLY.
  
 4) FBC 11-4.3 SHOW THE ACCESSIBLE ROUTE TO THE BUILDING
 COMPLYING WITH THIS SECTION.
  
 5)SHEET #2. THE CODE SECTION ON THE DRAWINGS IN
 REFERENCE TO ROOF DOWNSPOUTS IS FROM THE 2001 FBC. SEE
 FBC 2004 FOR CORRECT REFERENCE.
  
 6)FBC 1503.4 UNLESS ROOF ARE SLOPED TO DRAIN OVER
 ROOF EDGES, DESIGN AND INSTALLATION OF ROOF DRAINAGE
 SYSTEMS SHALL COMPLY WITH THE FBC PLUMBING CH. 11.
  
 7)1503.4.3
 WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT
 PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR
 PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4
 INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND
 SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED
 VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND PARAPET
 SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING.
  
  
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  

Review Stop E ELECTRICAL
Rev No 9 Status P Date 2008-02-29 Cont ID  
Sent By dpalmer Date 2008-02-29 Time 12:38 Rev Time 0.00
Received By dpalmer Date 2008-02-29 Time 12:38 Sent To PC
Notes
2008-02-29 12:38:51REVISED VALUE.

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2008-01-22 Cont ID  
Sent By dpalmer Date 2008-01-22 Time 09:00 Rev Time 0.00
Received By dpalmer Date 2008-01-22 Time 09:00 Sent To  
Notes
2008-01-22 09:03:31VALUATION FOR COMPLETE SCOPE OF WORK FROM ORIGINAL
 APPLIED SCOPE PF WORK TO BE INCREASED PER FBC 108.3.
 PASSED PENDING.
 SPOKE TO GRACE FROM KARNSCONSTRUCTION AND SHE WILL
 GET INFORMATION FOR FINAL UPGRADE OF VALUATION.
  

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2007-07-16 Cont ID  
Sent By dpalmer Date 2007-07-16 Time 10:15 Rev Time 0.00
Received By dpalmer Date 2007-07-16 Time 10:10 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2007-07-06 Cont ID  
Sent By dpalmer Date 2007-07-06 Time 16:43 Rev Time 0.00
Received By dpalmer Date 2007-07-06 Time 16:43 Sent To  
Notes
2007-07-06 18:21:452007-07-06 18:21:45
 NOTE ADDED:
  
 *** PLEASE KNOW , NO FURTHER ELECTRICAL REVIEWS OF
 ENERGY CALCULATIONS WILL BE DONE UNTIL A MEETING IS
 HELD WITH THE DESIGNERS OF RECORD. THESE NOTES WILL
 NEED TO BE GONE OVER AT THAT TIME TO ALLEAVIATE ANY
 QUESTIONS, COMMENTS OR CONFUSION OF ANYKIND.
2007-07-06 16:43:502007-07-06 18:21:45
 NOTE ADDED:
  
 *** PLEASE KNOW , NO FURTHER ELECTRICAL REVIEWS OF
 ENERGY CALCULATIONS WILL BE DONE UNTIL A MEETING IS
 HELD WITH THE DESIGNERS OF RECORD. THESE NOTES WILL
 NEED TO BE GONE OVER AT THAT TIME TO ALLEVIATE ANY
 QUESTIONS, COMMENTS OR CONFUSION OF ANYKIND.
 THIS WAS CONFIRMED WITH THE ASSISTANT BUILDING OFFICIAL
 AFTER REVIEW OF SAID ENERGY CALCULATIONS.
  
  
  
  
  
 2007-07-06 16:43:50
 ** UNSAT 6TH REVIEW **
  
  
 1) NOTE: PLEASE SEE NOTES DATED 6/29/07 WHICH STATED
 THIS OFFICE WAS GOING TO PLACE REVIEW INTO A *TEMPORARY
 FAILED STATUS*. THIS WAS TO ALLOW REVISED CORRECTED
 ENERGY CALCULATIONS TO BE BROUGHT IN AS A SUBMITTAL
 UNDER THE CORRECT VERSION AS LONG AS NO CHANGES WERE
 MADE TO THE CALCULATIONS THEMSELVES.
 ON TUESDAY JULY 3RD 2007 REVISED ENERGY CALCULATIONS
 WERE BROUGHT IN AS A SUBMITTAL TO THIS OFFICE. UPON A
 QUICK GLANCE TO THE CALCULATIONS IT WAS NOTICED THE
 VERSION WAS NOW STATED UNDER JULY 05 2.0 VERSION WHICH
 WAS BEFORE THE PREVIOUS CODE CHANGE. (PLEASE SEE THE
 FBC CHANGED AS OF OCT 1ST, 2005 OF THAT YEAR). THIS
 REVIEWER PLACED CALL TO THE ARCHITECT OF RECORD
 NOTIFYING OF THE INCORRECT VERSION. WE THEN CALLED THE
 PERSON WHICH WAS PROVIDING THE CALCULATIONS.
 THIS OFFICE SPECIFICALLY INFORMED BOTH DESIGNERS THAT
 THE ENERGY CALCULATIONS NUMBERS WERE OK, HOWEVER NEEDED
 TO BE UNDER THE 2.1 VERSION AS PREVIOUSLY STATED IN THE
 REVIEWS.
 THIS OFFICE WAS INFORMED THAT REVISED ENERGY
 CALCULATIONS WITH THE CORRECT VERSION WOULD BE
 SUBMITTED BY 7/06/07.
 PLEASE SEE NEW ENERGY CALCULATIONS WERE ONCE AGAIN
 BROUGHT IN BY THE PERMIT EXPEDITOR AS A SUBMITTAL AND
 NO FEE WAS CHARGED ON 7/06/07.
 PLEASE SEE THIS TIME THE VERSION WAS CORRECT HOWEVER
 THE NUMBERS IN THE ENERGY CALCULATIONS WHICH WERE OK ON
 THE PREVIOUS CALCULATIONS HAVE ONCE AGAIN BEEN CHANGED
 AND DO NOT MATCH AND CORRELATE WITH PLANS.
 PLEASE SEE 13-415.1.A, 13-415.2
  
 ** THIS REVIEW IS DENIED, ONE COPY OF EACH THE
 SUBMITTED ENERGY CALCULATIONS ARE BEING RETAINED BY
 THIS OFFICE.
  
 AS STATED ON PREVIOUS REVIEWS: PLEASE CORRELATE THE
 ENERGY CALCULATIONS WITH THE PLANS. PLEASE TAKE THE
 CALCULATIONS FOR ELECTRICAL LIGHTING FROM THE VERSION
 3.0 WHICH WAS SUBMITTED AND TRANSFER THAT INFORMATION
 INTO THE CORRECT VERSION OF 2.1.
 THE NUMBER OF LUMINARIES, THE WATTAGE OF LUMINARIES
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2007-06-29 Cont ID  
Sent By dpalmer Date 2007-06-29 Time 15:41 Rev Time 0.00
Received By dpalmer Date 2007-06-29 Time 15:02 Sent To  
Notes
2007-06-29 15:45:42*** TEMPORARY FAILED***
  
 1) NOTE: THENEW ENERGY CALCULATIONS ARE NOW SUBMITTED
 UNDER A VERSION IN WHICHWAS NOT IN EFFECT AT THE TIME
 OF PERMIT APPLICAYION.THE VERSION SHOULD BE THAT OF THE
 2004 FBC WITH THE *2005* REVISIONS. (2.1).
 THIS REVIEWER HAS CALLED THE ARCHITECT AND NEW ENERGY
 CALCULATIONS ARE TO BE BROUGHT IN AS A SUBMITTAL TO DV
 PALMER. THE CALCULATIONS AND NUMBERSFOR ELECTRICAL ARE
 OK.
  
 ELECTRICAL PLANS ARE OK AND HAVE BEEN STAMPED. ONLY
 NEED TO ADDRESS THE ENERGY CALCULATIONS.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-06-10 Cont ID  
Sent By dpalmer Date 2007-06-10 Time 11:57 Rev Time 0.00
Received By dpalmer Date 2007-06-10 Time 10:58 Sent To  
Notes
2007-06-10 11:57:32** UNSAT 4TH REVIEW **
  
  
 1) NOTE: PLEASE SEE ENERGY CALCULATIONS SUBMITTED ARE
 SIGNED BY THE ARCHITECT, HOWEVER WAS INADVERTENTLY NOT
 SEALED AS NEEDED.
 PLEASE SEE ONLY ONE INPUT DATA REPORT WAS SUBMITTED.
 PLEASE SEE THE TOTAL AMOUNT OF FIXTURES, TYPES, AND
 WATTAGES DOES NOT MATCH PLANS.
 PLEASE SEE UNIT E FOR EXAMPLE>
 PLANS INDICATE RETAIL AS A TOTAL OF 11 FIXTURES, YET
 PLANS DO NOT INDICATE THE SAME AMOUNT OF FIXTURES ON
 THE PLANS.
 PLEASE SEE FIXTURE A, A TOTAL OF 7 OF THESE ARE ON
 PLANS, EACH OF THESE PER FIXTURE LEGEND IS 128WATTS.
 PLANS INDICATE A TOTAL OF 2-TYPE C WHICH ARE 32 WATTS
 EACH ON FIXTURE LEGEND.
 PLEASE SEE OFFICE AREA AS THE PLANS CALL FOR THIS
 FIXTURE AS 2-TYPE B EACH CONTAINING 3-32WATT BULBS AT A
 TOTAL OF 96WATTS, YET THE CALCULATIONS SHOWS 64WATTS.
 PLEASE SEE THE FIXTURE SCHEDULE WHICH CONTAINS FIXTURES
 WITH A DIFFERENT WATTAGE FOR THE SAME FIXTURES AS NOTED
 ON CALCULATIONS.
 UNIT ?E.
 7- A FIXTURES 128W EACH
 2-C FIXTURES 26 W EACH
 2-B FIXTURES 96W EACH.
 THE OTHER EXTERIOR LIGHT FIXTURES ARE:
 2- D FIXTURES 26W EACH
 1- E FIXTURE 26W.
 THE NUMBER OF FIXTURES SHOWN ON EXTERIOR INPUT DATA
 REPORT IS OK, ONLY NEED TO UPDATE THE WATTAGE FOR D
 FIXTURES.
  
 OTHER UNITS CONTAIN A DIFFERENT NUMBER OF FIXTURES,
 HOWEVER THE SAME COORDINATION NEEDS TO TAKE PLACE.
  
 ** PLEASE CALL THIS OFFICE TO GO OVER THIS OR IF THERE
 ARE ANY QUESTIONS OR COMMENTS IN ANY WAY AS STATED ON
 THE PREVIOUS THREE REVIEWS.
  
 2) NOTE: PLEASE SEE OWNER INFORMATION ON PERMIT
 APPLICATION DOES NOT SHOW THE SAME AS ON OUR SYSTEM.
 PLEASE OBTAIN UPDATED DEED, OR PALM BEACH COUNTY
 PROPERTY APPRAISER PRINT OUTS SO THE OWNER INFORMATION
 CAN BE UPDATED.
 *THIS IS NOT FOR ELECTRICAL CODE COMPLIANCE, HOWEVER
 THIS IS STILL REQUIRED.
  
 3) NOTE: PLEASE KNOW AS A NEW DESIGNER OF RECORD HAS
 TAKEN OVER FOR THE ENERGY CALCULATIONS, FS 553.80(2)(B)
 DOES NOT APPLY AT THIS TIME.
 PLEASE BE SURE TO ADDRESS COMMENT.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-04-24 Cont ID  
Sent By dpalmer Date 2007-04-24 Time 15:57 Rev Time 0.00
Received By dpalmer Date 2007-04-24 Time 15:30 Sent To  
Notes
2007-04-24 15:57:44 
 *** UNSAT 3RD REVIEW ***
  
 ** PLEASE NOTE, ALL REVIEWS WILL ONLY BE DONE UNDER
 PERMIT # 06110556.
 THE OTHER FOUR PREVIOUS ADDITIONAL PERMIT NUMBERS ARE
 NO LONGER IN-USE.
  
  
 1) NOTE: PLEASE CORRELATE ELECTRICAL LIGHTING PLANS
 WITH THE ENERGY CALCULATIONS SUBMITTED. PLEASE SEE THE
 NUMBER OF FIXTURES; THE WATTAGE PER FIXTURE AND THE
 TOTAL DO NOT CORRELATE WITH THAT OF THE FIXTURES AND
 LIGHTING ON PLANS.
 PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED AS THERE
 IS NOW NO INTERIOR LIGHTING SUBMITTED AND SHOWN IN THE
 INPUT DATA REPORT IN EITHER SET SUBMITTED.
 PLEASE SEE THE FIXTURES NOW ENTERED FOR EXTERIOR
 LIGHTING DOES NOT CORRELATE WITH PLANS OR THE TYPES OF
 FIXTURES ON PLANS.
 13-415.1.AB.1.1, 13-415.2 ETC.
  
 2) NOTE: PLEASE SEE FBC 103.1, 103.1.1.1 AS THE ENERGY
 CALCULATIONS MUST BE SIGNED, DATED AND SEALED BY THE
 DESIGN PROFESSIONALS. SHEETS CONTAIN SOME PRINTED
 INFORMATION AND SOME SIGNATURES, HOWEVER THE DESIGNER
 OF RECORD HAS NOT SIGNED AND SEALED SHEETS REQUIRED.
  
 3) NOTE: PLEASE SEE THAT THE COMMENTS FOR THE ENERGY
 CALCULATION ARE REPEATED FROM THE 2ND REVIEW.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-03-10 Cont ID  
Sent By dpalmer Date 2007-03-10 Time 18:16 Rev Time 0.00
Received By dpalmer Date 2007-03-10 Time 18:16 Sent To  
Notes
2007-03-10 18:16:45** UNSAT 2ND REVIEW **
  
  
 1) NOTE: PLEASE CORRELATE ELECTRICAL LIGHTING PLANS
 WITH THE ENERGY CALCULATIONS SUBMITTED. PLEASE SEE THE
 NUMBER OF FIXTURES; THE WATTAGE PER FIXTURE AND THE
 TOTAL DO NOT CORRELATE WITH THAT OF THE FIXTURES AND
 LIGHTING ON PLANS.
 PLEASE SEE THE ENERGY CALCULATIONS DO NOT INDICATE AN
 EXTERIOR LIGHTING, YET THE PLANS INDICATE EXTERIOR
 LIGHTING.
 13-415.1.AB.1.1
 13-415.2
  
 2) NOTE: PLEASE SEE FBC 103.1, 103.1.1.1 AS THE ENERGY
 CALCULATIONS MUST BE SIGNED, DATED AND SEALED BY THE
 DESIGN PROFESSIONAL EVEN WHEN/IF FALLING UNDER THE
 EXCEPTIONS THAT A MECHANICAL CONTRACTOR PERFORMS THE
 SCOPE OF WORK.
 PLEASE KNOW THE SCOPE DOES NOT APPEAR TO FALL UNDER THE
 EXCEPTIONS UNDER FS 471.003.
 ** PLEASE ALSO SEE THE MECHANICAL PLANS WHICH CONTAIN
 TITLE BLOCKS FROM AN ENGINEER AND ENGINEERING FIRM, YET
 THERE IS A SIGNATURE AND SEAL ON THESE SHEETS FROM A
 MECHANICAL CONTRACTOR. THIS IS NOT PERMITTED UNDER
 FLORIDA STATUTES 471.025 AND FLORIDA ADMINISTRATIVE
 CODE 61G15-23.002
 PLEASE ALSO SEE THE 2ND MECHANICAL SHEET IN EACH SET
 DOES NOT CONTAIN ANY SIGNATURE, DATE OR SEAL FROM
 ANYONE.
  
 3) NOTE: PLEASE KNOW DUE TO THE COMMENTS ONE SET OF
 PLANS AND ENERGY CALCULATIONS WILL BE RETAINED BY THIS
 OFFICE.
 **PLEASE BE SURE RE-PRINT THE 2ND SET OF ELECTRICAL. AS
 PLUMBING IS ON THE SAME SHEET WITH ELECTRICAL, PLUMBING
 WILL NEED TO RE-STAMP SHEETS IN SETS WHEN PLANS ARE
 CORRECTED AND RESUBMITTED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-12-07 Cont ID  
Sent By dpalmer Date 2006-12-07 Time 08:51 Rev Time 0.00
Received By dpalmer Date 2006-12-07 Time 08:51 Sent To  
Notes
2006-12-07 08:51:44*** UNSAT ***
  
 1) NOTE:PLEASE SEE LOADS FOR SHOW WINDOWS NEED TO BE
 CLARIFIED PER 220.12A. PLEASE SEE AS THE VA IS NOT
 SHOWN AND NO LOAD SUMMARY IS SHOWN, THE VA PER FOOT CAN
 NOT BE VERIFIED.
 210.62
  
 2) NOTE: PLEASE VERIFY THE LOAD SHOWN FOR THE SIGN
 CIRCUIT(S). PLEASE SEE 600.5, WHICH REFERENCES TO
 220.3B6 FOR THE MINIMUM VA TO USE TO FIGURE FOR SIGN
 CIRCUITS. PLEASE SEE THE LOAD OF 5A?S FOR EACH DOES NOT
 CORRELATE TO THE MINIMUM VA REQUIRED.
 PLEASE SEE NO LOAD SUMMARY IS SHOWN TO VERIFY THIS.
  
 3) NOTE: PLEASE CORRELATE LOADS ON PANEL FOR KNOWN
 RECEPTS ON A CIRCUIT. 220.13
  
 4) NOTE: PLEASE SEE A NOTE ON "E" UNIT INDICATES
 RECEPTACLE ABOVE CEILING AS TYPICAL FOR EACH SIGN
 CIRCUIT. PLEASE SEE 600.5, AS IT ONLY REQUIRES A
 CIRCUIT. PLEASE SEE 400.8(2) WHICH DO NOT PERMIT
 RECEPTACLES ABOVE CEILINGS AS THIS WOULD THEN CREATE
 THE ISSUE OF CORDS BEING RUN THROUGH CEILINGS WHICH IS
 NOT PERMITTED.
 PLEASE REVISE.
  
 5) NOTE: PLEASE CLARIFY THE GROUNDING ELECTRODE SYSTEM
 AS SHOWN. RISER SHOWS THE MAIN GROUNDING ELECTRODE
 BEING "TAPPED" AND SHOWN TO EACH MAIN DISCONNECT??
 PLEASE SEE 250.24B, 250.6. PLEASE KNOW WHEN INSTALLING
 THE GUTTER, THE NEUTRAL CONDUCTOR WOULD BE "BONDED" TO
 THE GUTTER WHICH MAY CONTAIN THE SOLE CONNECTION OF THE
 GEC. PLEASE SEE ONLY ONE SET OF PHASE AND NEUTRAL
 CONDUCTORS WOULD THEN BE ROUTED TO EACH METER AND MAIN.
 EACH NEUTRAL WOULD BE BONDED TO THE ENCLOSURE AT THE
 FIRST MEANS OF DISCONNECT.
 PLEASE SEE AS SHOWN THIS SEEM TO BE AN INTERESTING
 SCENARIO AT THE CONNECTION POINT SHOWN AT THE GROUND
 LEVEL LOCATION.
 ** PLEASE SEE THIS BEING AN EXISTING BUILDING AND THE
 CONCRETE ENCASED ELECTRODE ON AN EXISTING BUILDING IS
 NOT REQUIRED TO BE ATTACHED. PLEASE KNOW IF SHOWN ON
 GROUNDING ELECTRODE DETAIL BEING REQUIRED THEN THIS
 WILL BE REQUIRED IN THE FIELD. PLEASE VERIFY THIS BEING
 REQUIRED AND POSSIBLY AFFECTING THE STRUCTURAL
 INTEGRITY OF THE EXISTING FOOTER.
  
 6) NOTE: PLEASE LIST THE FOLLOWING RELEVANT CODES ON
 THE PLANS. 2002 NFPA-70, 2003 NFPA-101
  
 7) NOTE: PLEASE CORRELATE LOADS, OVER CURRENT
 PROTECTION, CONDUCTORS ETC FOR THE A/C SYSTEMS. PLEASE
 SEE ELECTRICAL PLANS SEEM TO INDICATE A POSSIBLE 5KW
 LOAD, HOWEVER AS KW RATINGS/ KVA LOADS ARE NOT SHOWN,
 THESE ARE UNCLEAR AT THIS TIME. PLEASE SEE MECHANICAL
 PLANS CALL FOR 8KW AND 10KW UNITS.
 PLEASE SEE 424.3B, 310.16, 240.4 ETC
 FBC 106.1.2 ADMIN SECTION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2008-01-28 Cont ID  
Sent By mawillia Date 2008-01-28 Time 09:56 Rev Time 0.00
Received By mawillia Date 2008-01-28 Time 09:28 Sent To  
Notes
2008-01-28 09:53:31*****REVISION APPROVED*****
  
  
 REVISED PLAN SHEETS 1 & 4 WERE STAMPED, INITIALED, AND
 DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-07-09 Cont ID  
Sent By mawillia Date 2007-07-09 Time 11:40 Rev Time 0.00
Received By mawillia Date 2007-07-09 Time 11:21 Sent To  
Notes
2007-07-09 11:21:39*****APPROVED*****
  
  
 PLAN SHEETS 1, 2, & 4 WERE STAMPED, INITIALED AND
 DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-06-12 Cont ID  
Sent By mawillia Date 2007-06-12 Time 17:21 Rev Time 0.00
Received By mawillia Date 2007-06-12 Time 17:16 Sent To  
Notes
2007-06-12 17:18:41*****PROVISO*****
  
  
 THE APPROPIATE PLAN SHEET(S) TO BE STAMPED WHEN ALL
 OTHER PLAN REVIEWERS HAVE BEEN SATISFIED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-05-10 Cont ID  
Sent By mawillia Date 2007-05-10 Time 16:46 Rev Time 0.00
Received By mawillia Date 2007-05-10 Time 16:35 Sent To  
Notes
2007-05-10 16:40:13*****PROVISO*****
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED;HOWEVER THE APPROPIATE PLAN SHEET(S)
 WILL BE STAMPED WHEN ALL REVIEWERS HAVE BEEN SATISFIED
  
  
  
  
  
 CAPT. MICHEAL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-12-12 Cont ID  
Sent By mawillia Date 2006-12-12 Time 16:15 Rev Time 0.00
Received By mawillia Date 2006-12-12 Time 16:15 Sent To  
Notes
2006-12-12 16:16:12*****DENIED*****
  
  
  
 1.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE
 PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED.
  
 2.CONSTRUCTION, ALTERATION, OR DEMOLITION OPERATIONS
 SHALL COMPLY WITH NFPA 241.
  
 3.COMBUSTIBLE WASTE, DUST, AND DEBRIS SHALL BE
 REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR MORE
 FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 4.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID
 PROPERTY OR VICINITY THEREOF (INCLUDING FIRE LANES).
  
 5.GASOLINE POWERED EQUIPMENT FOR DEMOLITION
 ACTIVITIES SHALL NOT BE USED TO PREVENTTHE
 POSSIBILITY OF CARBON DIOXIDE POISONING.
  
 6.SHOW/DISPLAY THE ADDRESS OF THE STRUCTURE ON THE
 EXTERIOR ELEVATION WHICH FRONTS SOUTH DIXIE HIGHWAY. AS
 PER WEST PALM BEACH CODE, THE NUMERICAL ADDRESS SHALL
 BE NO LESS THAN 6' IN HEIGHT AND 1" IN WIDTH.
 ADDITIONALLY, DISPLAY THE UNIT NUMBER (3" IN HEIGHT AND
 1" IN WIDTH) FOR THE FRONT ENTRANCE TO DISTINGUISH ONE
 UNIT FROM THE OTHER. FRONT UNIT NUMBERS SHALL NOT BE ON
 THE DOORS OR WINDOWS, HOWEVER REAR UNIT NUMBER CAN BE
 INSTALLED ON THE DOOR.HURRICANE SHUTTERS SHALL NOT
 BLOCK VISIBILITY OF BUILDING AND/OR UNIT ADDRESS.
  
 7.INTERIOR FINISH CLASSIFICATION IN AN UNSPRINKLERED
 BUILDING SHALL BE "A" OR "B".
  
 8.FIRE EXTINGUISHERS TO BE 2A:10BC RATED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 SHEET INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
 CAPT. MICHEAL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2008-01-30 Cont ID  
Sent By adarroug Date 2008-01-30 Time 12:07 Rev Time 0.00
Received By adarroug Date 2008-01-30 Time 12:07 Sent To M
Notes
2008-01-30 12:07:39TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2008-01-18 Cont ID  
Sent By adarroug Date 2008-01-18 Time 10:46 Rev Time 0.00
Received By adarroug Date 2008-01-18 Time 10:46 Sent To  
Notes
2008-01-18 10:47:02TO "BOB"#4

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2007-12-19 Cont ID  
Sent By adarroug Date 2007-12-19 Time 09:32 Rev Time 0.00
Received By adarroug Date 2007-12-19 Time 09:32 Sent To M
Notes
2007-12-19 09:33:11TO "TGORDON" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-12-13 Cont ID  
Sent By adarroug Date 2007-12-13 Time 09:26 Rev Time 0.00
Received By adarroug Date 2007-12-13 Time 09:26 Sent To B
Notes
2007-12-13 09:27:26TO "MJACOBS" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-11-21 Cont ID  
Sent By adarroug Date 2007-11-21 Time 08:11 Rev Time 0.00
Received By adarroug Date 2007-11-21 Time 08:11 Sent To M
Notes
2007-11-21 08:11:23TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-10-30 Cont ID  
Sent By adarroug Date 2007-10-30 Time 11:36 Rev Time 0.00
Received By adarroug Date 2007-10-30 Time 11:36 Sent To M
Notes
2007-10-30 11:36:25TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-08-09 Cont ID  
Sent By dpalmer Date 2007-08-09 Time 13:26 Rev Time 0.00
Received By dpalmer Date 2007-08-09 Time 13:26 Sent To  
Notes
2007-08-16 08:41:51SENT TO ERIC SCHNEIDER
2007-08-09 13:27:13WAITING FOR COMM BOARD.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status   Date 2007-08-08 Cont ID  
Sent By mmiller Date 2007-08-08 Time 18:17 Rev Time 0.00
Received By mmiller Date 2007-08-08 Time 18:16 Sent To B
Notes
2007-08-08 18:17:00SENT TO MYRON JACOB'S DESK MMILLER

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-07-13 Cont ID  
Sent By adarroug Date 2007-07-13 Time 16:07 Rev Time 0.00
Received By adarroug Date 2007-07-13 Time 16:07 Sent To  
Notes
2007-07-13 16:08:49WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-06-27 Cont ID  
Sent By adarroug Date 2007-06-27 Time 10:48 Rev Time 0.00
Received By adarroug Date 2007-06-27 Time 10:48 Sent To  
Notes
2007-07-06 07:29:40ON BOB BOARD#1
2007-06-27 10:48:56WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-06-05 Cont ID  
Sent By adarroug Date 2007-06-05 Time 13:25 Rev Time 0.00
Received By adarroug Date 2007-06-05 Time 13:25 Sent To  
Notes
2007-06-10 10:58:35TO BOB BOARD SPACE #9 ON 6/10
2007-06-05 13:25:57WAITING FOR" BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-04-20 Cont ID  
Sent By adarroug Date 2007-04-20 Time 12:01 Rev Time 0.00
Received By adarroug Date 2007-04-20 Time 12:01 Sent To  
Notes
2007-04-20 12:02:00TO "BOB"#10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-01-31 Cont ID  
Sent By jleech Date 2007-01-31 Time 14:56 Rev Time 0.00
Received By jleech Date 2006-11-27 Time 15:31 Sent To  
Notes
2006-12-06 15:31:41TO "BOB"#5--5 APPLICATIONS

Review Stop M MECHANICAL (A/C)
Rev No 10 Status P Date 2008-01-31 Cont ID  
Sent By tgordon Date 2008-01-31 Time 09:09 Rev Time 0.30
Received By tgordon Date 2008-01-31 Time 09:09 Sent To  
Notes
2008-01-31 09:10:42MECHANICAL REVISION TO PLANS M-1 AND M-2.

Review Stop M MECHANICAL (A/C)
Rev No 9 Status P Date 2007-12-20 Cont ID  
Sent By tgordon Date 2007-12-20 Time 09:01 Rev Time 0.25
Received By tgordon Date 2007-12-20 Time 09:00 Sent To  
Notes
2007-12-20 09:01:58MECH. REVISION TO PLANS PAGE M-1.

Review Stop M MECHANICAL (A/C)
Rev No 8 Status F Date 2007-11-29 Cont ID  
Sent By tgordon Date 2007-11-29 Time 11:53 Rev Time 0.25
Received By tgordon Date 2007-11-29 Time 11:53 Sent To  
Notes
2007-11-29 12:18:26PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) NEED WIND LOAD CALCULATIONS TO SHOW THAT CONDENSER
 STANDS WILL WITHSTAND 140 MPH WINDS PER 2004 FBC 1609.
 IF PER-ENGINEERED CONDENSER STANDS SUBMIT PRODUCT
 APPROVAL OR AN NOA FOR PER-ENGINEERED CONDENSER STANDS,
 SEE FS 553.842(1) AND FAC RULE 9B-72, 9B-72.005, AND
 FAC 9B-72.010(31)(G).
  
 2) PRODUCT APPROVALS SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO BEING
 SUBMITTED FOR JURISDICTIONAL APPROVAL (A SHOP REVIEW
 STAMP AND SIGNATURE WILL MEET REQUIREMENT). SEE WPB
 AMEND. 106.3.
  
 **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 7 Status F Date 2007-11-02 Cont ID  
Sent By tgordon Date 2007-11-02 Time 09:28 Rev Time 0.30
Received By tgordon Date 2007-11-02 Time 09:28 Sent To  
Notes
2007-11-02 09:38:33PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 MECHANICAL REVISION
 *** DENIED ***
 1) MECHANICAL PLAN ON FILE IS SIGNED AND SEALED BY AN
 ENGINEER (EDWARD J. KRANZ) AND ONLY HE CAN MAKE
 REVISIONS TO THE PLANS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2007-07-16 Cont ID  
Sent By tgordon Date 2007-07-16 Time 10:55 Rev Time 0.25
Received By tgordon Date 2007-07-16 Time 10:55 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2007-07-03 Cont ID  
Sent By tgordon Date 2007-07-03 Time 15:46 Rev Time 0.25
Received By tgordon Date 2007-07-03 Time 15:46 Sent To  
Notes
2007-07-03 15:52:37*** DENIED ***
 1) ENERGY CALCULATIONS ARE ON THE WRONG FORM.
  
 ** 2004 FBC 13-400.3.A METHOD A FORMS.
 AN ACCURATELY COMPLETED FORM 400A-04R (GENERATED BY THE
 FLA/COM-2004 COMPUTER PROGRAM, VERSION 2.5)
 DEMONSTRATING THAT CODE COMPLIANCE HAS BEEN ACHIEVED
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL FOR METHOD
 A COMPLIANCE. CALCULATIONS SHALL BE PERFORMED FOR THE
 CLIMATE ZONE IN WHICH THE BUILDING WILL BE LOCATED AND
 ACCORDING TO THE PROCEDURES SPECIFIED FOR METHOD A IN
 THIS SUBCHAPTER.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2007-06-12 Cont ID  
Sent By tgordon Date 2007-06-12 Time 13:54 Rev Time 0.30
Received By tgordon Date 2007-06-12 Time 13:54 Sent To  
Notes
2007-06-12 14:04:56*** DENIED ***
 1) ENERGY CALCULATIONS ARE MISSING THE ARCHITECT'S
 SEAL, SEE 2004 FBC 13-103.1.1.1, PLEASE CORRECT.
  
 2) PLEASE SUBMIT TWO COPY'S OF THE INPUT DATA REPORT
 FOR THE ENERGY CAL'S., AS ONLY ONE COPY WAS SUBMITTED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-04-24 Cont ID  
Sent By tgordon Date 2007-04-24 Time 09:55 Rev Time 1.00
Received By tgordon Date 2007-04-24 Time 09:55 Sent To  
Notes
2007-04-24 10:01:40*** DENIED ***
 1) ENERGY CALCULATIONS "PREPARED BY" NEED TO BE SIGNED
 AND SEALED BY AN ARCHITECT OR ENGINEER, SEE 2004 FBC
 13-103.1.1.1.
  
 2) ENERGY CALCULATIONS NEED A "MECHANICAL DESIGNER" WHO
 IS A ENGINEER, OR AN ARCHITECT, AIR CONDITIONING
 CONTRACTOR, OR MECHANICAL CONTRACTOR IF APPLICABLE, SEE
 2004 FBC 13-103.1.1.1 AND F.S. 471.003 (H).
  
 *** 2004 FBC 13-103.1.1.1 COMMERCIAL APPLICATIONS.
 COMPLETION OF PROCEDURES DEMONSTRATING COMPLIANCE WITH
 THIS CODE FOR COMMERCIAL BUILDINGS SHALL BE SIGNED AND
 SEALED BY AN ARCHITECT OR ENGINEER LICENSED TO PRACTICE
 IN THE STATE OF FLORIDA, WITH THE EXCEPTION OF
 BUILDINGS EXCLUDED BY SECTION 481.229, FLORIDA STATUTES
 , OR SECTION 471.003, FLORIDA STATUTES. CALCULATIONS
 FOR BUILDINGS FALLING WITHIN THE EXCEPTION OF SECTION
 471.003, FLORIDA STATUTES , MAY BE PERFORMED BY AIR
 CONDITIONING OR MECHANICAL CONTRACTORS LICENSED IN
 ACCORDANCE WITH CHAPTER 489, FLORIDA STATUTES , OR BY
 STATE OF FLORIDA CERTIFIED COMMERCIAL BUILDING ENERGY
 RATERS.
 DESIGN PROFESSIONALS RESPONSIBLE UNDER FLORIDA LAW FOR
 THE DESIGN OF LIGHTING, ELECTRICAL, MECHANICAL, AND
 PLUMBING SYSTEMS AND THE BUILDING SHELL, SHALL CERTIFY
 COMPLIANCE OF THOSE BUILDING SYSTEMS WITH THE CODE BY
 SIGNING AND PROVIDING THEIR PROFESSIONAL REGISTRATION
 NUMBER ON THE ENERGY CODE FORM PROVIDED AS PART OF THE
 PLANS AND SPECIFICATIONS TO THE BUILDING DEPARTMENT.
 EXCEPTION: TYPED NAMES AND REGISTRATION NUMBERS MAY BE
 PROVIDED IN LIEU OF A SIGNATURE WHERE ALL RELEVANT
 INFORMATION HAS BEEN INCLUDED ON SIGNED AND SEALED
 PLANS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-03-15 Cont ID  
Sent By tgordon Date 2007-03-15 Time 16:20 Rev Time 0.30
Received By tgordon Date 2007-03-15 Time 16:20 Sent To  
Notes
2007-03-15 16:20:59*** DENIED ***
 1) AS NOTED IN LAST REVIEW 11-21-06 NOTE #2. SEE
 COOLING LOAD CALCULATIONS SHOW THAT ALL FIVE BAYS
 TOGETHER WILL NEED OVER 460 TONS OF A/C, PLEASE SUBMIT
 CORRECTED COOLING LOAD CALCULATIONS, PER 2004 FBC
 13-407.1.ABC.1.
  
 2) THE ENGINEER EDWARD J. KRANZ WILL NEED TO SEAL THE
 MECHANICAL PLANS AS HIS INFORMATION IS IN THE TITLE
 BLOCK, SEE FAC 61G15-23.002. (SEE PLANS, PAGES M-1 AND
 M-2).
  
 3) SEE PLANS, PAGE M-1 "O/A INTAKE" IF THIS IS TYPICAL
 OF 5 PLEASE STATE SO ON PLANS IF NOT GIVE INFORMATION
 AT EACH INTAKE.
  
 4) SEE PLANS, PAGE M-1 " 6 INCH DUCT TO EXHAUST WALL
 LOUVER" IF TYPICAL OF 5 STATE SO ON PLANS IF NOT GIVE
 INFORMATION AT EACH EXHAUST.
  
 5) SEE PLANS, PAGE 4 ELECTRICAL PLANS SHOW 7 A/C
 CONDENSER UNITS, MECHANICAL PLANS ONLY SHOW 5, PLEASE
 CORRECT ELECT. PLANS.
  
 6) SEE PLANS, PAGE M-2A/C SCHEDULE SHOWS THE WRONG
 EQUIPMENT MANUFACTURE, CAPACITY (TOTAL) BTU'S, SENSIBLE
 BTU'S, AND A INCORRECT MODEL NUMBER FOR AHU #1. PLEASE
 REVIEW SUBMITTED MANUFACTURER'S SPECIFICATION'S FOR THE
 GOODMAN A/C AND CORRECT.
  
 7) SEE ELECTRICAL REVIEW NOTE #2 AND 3. AS A RESULT OF
 DOCUMENTS BEING RETAINED PLEASE BE CERTAIN TWO COPY'S
 OF ALL INFORMATION IS BEING SUBMITTED.
  
 8)SEE ATTACHED NOTICE FS 553.80(2)(B) REGARDING FOUR
 TIMES THE FEE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-11-21 Cont ID  
Sent By tgordon Date 2006-11-21 Time 16:27 Rev Time 0.30
Received By tgordon Date 2006-11-21 Time 16:27 Sent To P
Notes
2006-11-21 16:28:15*** DENIED ***
 1) PLEASE SUBMIT ENERGY CALCULATIONS, PER 2004 FBC
 13-101.1.1.6 .
  
 2) SEE COOLING LOAD CALCULATIONS PAGE 1, LOAD CAL'S
 SHOW THAT ALL FIVE BAYS TOGETHER WILL NEED OVER 460
 TONS OF A/C, PLEASE RE-DO LOAD CAL'S.
  
 3) CONDENSER UNITS APPEAR TO BE LOCATED IN THE BACK
 OFFICES, PLEASE CORRECT..
  
 4) PLEAS SHOW ON THE PLANS EQUIPMENT LISTING, THE
 SENSIBLE AND TOTAL BTU'S.
  
 5) PLEASE SHOW THE LOCATION OF ALL GRILLS.
  
 6) SEE UNIT B, PLEASE LABEL GRILLS IN BACK OFFICE.
  
 7) PLEASE PROVIDE DETAIL ON BATHROOM EXHAUST DUCTS, ARE
 THEY INDEPENDENTLY DUCTED TO THE OUTDOORS?
  
 8) PLEASE SHOW THE SIZE OF ALL SUPPLY AND RETURN AIR
 DUCTS (SEE HIGH LIGHTS ON PLANS).
  
 9) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-01-23 Cont ID  
Sent By jleech Date 2008-01-23 Time 08:37 Rev Time 0.00
Received By jleech Date 2008-01-23 Time 07:58 Sent To  
Notes
2008-01-23 08:37:49REVISION ADDED A BATHROOM

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-04-23 Cont ID  
Sent By jleech Date 2007-04-23 Time 08:52 Rev Time 0.00
Received By jleech Date 2007-04-23 Time 08:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-03-10 Cont ID  
Sent By jleech Date 2007-03-10 Time 13:16 Rev Time 0.00
Received By jleech Date 2007-03-10 Time 13:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-01-31 Cont ID  
Sent By jleech Date 2007-01-31 Time 14:56 Rev Time 0.00
Received By jleech Date 2007-01-31 Time 14:56 Sent To  
Notes
2007-01-31 14:57:52SEE PLUMBING PLAN REIEW NOTES UNDER PERMIT # 0611563

Review Stop Z ZONING
Rev No 6 Status P Date 2007-08-16 Cont ID  
Sent By eschneid Date 2007-08-16 Time 16:37 Rev Time 0.00
Received By eschneid Date 2007-08-16 Time 16:37 Sent To  
Notes
2007-08-16 16:38:15GIVEN TO L. MARTINEZ.

Review Stop Z ZONING
Rev No 5 Status P Date 2007-07-11 Cont ID  
Sent By eschneid Date 2007-07-11 Time 17:47 Rev Time 0.00
Received By eschneid Date 2007-07-11 Time 17:47 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status F Date 2007-06-20 Cont ID  
Sent By eschneid Date 2007-06-20 Time 16:45 Rev Time 0.00
Received By eschneid Date 2007-06-20 Time 16:45 Sent To  
Notes
2007-06-20 17:00:51FAILED - 4TH REVIEW
  
 1) THE COCOPLUM IS SHOWN AS CHR ON THE PLAN BUT AS COC
 ON THE PLANT LEGEND.
  
 2) THE PERMIT FOR THE IRRIGATION SYSTEM SHALL E
 SUBMITTED PRIOR TO APPROVAL OF THIS PERMIT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.

Review Stop Z ZONING
Rev No 3 Status F Date 2007-05-07 Cont ID  
Sent By eschneid Date 2007-05-07 Time 17:20 Rev Time 0.00
Received By eschneid Date 2007-05-07 Time 15:46 Sent To  
Notes
2007-05-07 17:20:39FAILED - 3RD REVIEW
  
 1) A LANDSCAPE PLAN, PREPARED BY A REGISTERED LANDSCAPE
 ARCHITECT, IS REQUIRED SINCE THERE ARE NEW LANDSCAPE
 AREAS BEING INSTALLED.
  
 2) THE NEW LANDSCAPE BUFFER ALONG THE SOUTHERN PROPERTY
 LINE SHALL BE A MINIMUM OF 5 FEET WIDE TO CONFORM TO
 THE LANDSCAPE CODE.IT SHALL INCLUDE THE TREES AND
 SHRUBS REQUIRED BY CODE.
  
 3) THE SITE DATA TABLE SHOWS THAT THE EXISTING SITE HAS
 90.56% IMPERVIOUS SURFACE (8,060 SQ. FT.).THE PLANS
 SHOW THE ADDITION OF THE SOUTHERN LANDSCAPE BUFFER, YET
 THE SITE DATA TABLE DOES NOT SHOW THIS ACCURATELY.THE
 TABLE SHOWS 8,106 SQ. FT. OF IMPERVIOUS AREA (AN
 INCREASE) AND 90.29% IMPERVIOUS AREA (A DECREASE).
 ADDITIONALLY, THE AMOUNT OF LANDSCAPE SHOWN IN THE DATA
 TABLE DID NOT CHANGE.
  
 4) THE SURVEY SHOWS THE SITE HAVING 8,932.79 SQ. FT.,
 WHILE THE SITE DATA TABLE LISTS 8,900 SQ. FT.THIS
 NEEDS TO BE CORRECTED.
  
 5) THE SPECIFICATIONS OF THE SCREEN HEDGE FOR THE
 DUMPSTER ENCLOSURE ARE REQUIRED (SPECIES, HEIGHT,
 LOCATION AND PLANTING) ON A LANDSCAPE PLAN PREPARED
 FOLLOWING THE PROVISIONS OF SECTION 94-448(D)(2) OF THE
 ZONING AND LAND DEVELOPMENT REGULATIONS.
  
 6) AN IRRIGATION PLAN IS REQUIRED.
  
 7) PLEASE NOTE THAT THE WHEEL STOPS SHALL BE 2 FEET
 FROM THE END OF THE SPACE, THE DOUBLE STRIPES ON THE
 PARKING SPACES SHALL BE 12 INCHES APART, AND THE ADA
 LOGO SHALL BE 2 FEET FROM THE MOUTH OF THE ADA SPACE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.

Review Stop Z ZONING
Rev No 2 Status F Date 2007-03-14 Cont ID  
Sent By eschneid Date 2007-03-14 Time 13:22 Rev Time 0.00
Received By eschneid Date 2007-03-14 Time 13:22 Sent To  
Notes
2007-03-14 13:22:58FAILED - 2ND REVIEW
  
 1) THE LETTER BY ROBERT BELL, DATED DECEMBER 27, 2007,
 STATES THAT THE VALUE OF THE RENOVATION TOTALS
 $230,000.THE APPRAISAL INCLUDED WITH THE RESUBMITTAL
 PACKAGE GIVES A VALUE OF THE ENTIRE SITE (LAND AND
 STRUCTURE).THE LANDSCAPE CODE SPECIFICALLY STATES
 THAT A SITE IS EXEMPT FROM THE REQUIREMENTS OF THE CODE
 IF THE RENOVATION DOES NOT EXCEED 50% OF THE VALUE OF
 THE STRUCTURE.IF NO EVIDENCE IS PROVIDED THAT THE
 VALUE OF THE STRUCTURE EXCEEDS $460,000, THE SITE SHALL
 BE BROUGHT INTO COMPLIANCE WITH THE LANDSCAPE CODE
 (SECTION 94-441).
  
 2) THE LANDSCAPE COMPLIANCE LISTED IN COMMENT #1
 REQUIRES A LANDSCAPE PLAN PREPARED BY A REGISTERED
 LANDSCAPE ARCHITECT.
  
 3) WHAT WILL BE PLANTED IN THE PLANTERS?PROVIDE AN
 IRRIGATION PLAN FOR THE PLANTERS.
  
 4) THE ZONING AND LAND DEVELOPMENT REGULATIONS ALLOW A
 MAXIMUM OF 85% IMPERVIOUS SURFACE.THE EXISTING SITE
 IS CURRENTLY NONCONFORMING AS IT HAS 90.56% IMPERVIOUS
 SURFACE (8,060 SQ. FT.).THE IMPERVIOUS SURFACE ON THE
 SITE MAY NOT EXCEED THIS AMOUNT.THE PROPOSED PLANS
 SHOW AN INCREASE IN IMPERVIOUS SURFACE.THIS IS NOT
 PERMITTED AND SHALL BE CORRECTED.IT MAY REQUIRE
 REMOVING IMPERVIOUS SURFACE IN ANOTHER AREA TO MAKE UP
 THE DIFFERENCE.
  
 5) THE PROPOSED DUMPSTER ENCLOSURE SHOWN ON THE PLAN
 DOES NOT MEET THE CODE REQUIREMENTS.A SET OF PLANS,
 STAMPED APPROVED BY THE CITY'S ENGINEERING SERVICES
 DEPARTMENT, SHOWING THE DUMPSTER AND ENCLOSURE SIZE AND
 LOCATION IS REQUIRED.THE SCREEN WALL FOR THE DUMPSTER
 MAY NOT BE CHAIN LINK W/SLATS.THE SPECIFICATIONS OF
 THE SCREEN HEDGE ARE REQUIRED (SPECIES, HEIGHT,
 LOCATION AND PLANTING) ON A LANDSCAPE PLAN PREPARED
 FOLLOWING THE PROVISIONS OF SECTION 94-448(D)(2) OF THE
 ZONING AND LAND DEVELOPMENT REGULATIONS.AN IRRIGATION
 PLAN IS REQUIRED.
  
 6) NO ACCESSIBLE ROUTE TO ALL OF THE BAYS IS SHOWN.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-01-31 Cont ID  
Sent By eschneid Date 2007-01-31 Time 13:53 Rev Time 0.00
Received By eschneid Date 2007-01-31 Time 13:53 Sent To  
Notes
2007-01-31 13:53:59FAILED
  
 1) THE VALUE OF THE 5 PERMITS TOTALS $95,000 AND THE
 PROPERTY APPRAISER SHOWS THE VALUE OF THE STRUCTURE AT
 $84,000.THIS REQUIRES THAT THE SITE BE BROUGHT INTO
 COMPLIANCE WITH THE LANDSCAPE CODE (SECTION 94-441).
  
 2) A LANDSCAPE PLAN PREPARED BY A REGISTERED LANDSCAPE
 ARCHITECT IS REQUIRED.
  
 3) EXISTING AND PROPOSED IMPERVIOUS SURFACE
 CALCULATIONS ARE REQUIRED.THE PROPOSED PLANS APPEAR
 TO SHOW AN INCREASE IN IMPERVIOUS MATERIAL.
  
 4) NO DUMPSTER DETAIL PROVIDED.THE DUMPSTER ENCLOSURE
 SHOWN ON THE PLAN DOES NOT APPEAR TO MEET THE CODE
 REQUIREMENTS.
  
 5) NO ACCESSIBLE ROUTE TO ALL OF THE BAYS IS SHOWN.
  
 6) THE PARKING SPACES ON THE WESTERN SIDE OF THE SITE
 ENCROACH INTO THE CURB CUT ON BOTH DIXIE AND MONCEAUX
 AND THUS PRESENT AN UNSAFE SITUATION.THE CURB CUTS
 SHALL BE CLOSED WHERE CONFLICTS EXIST OR THE PARKING
 SPACES SHALL BE ELIMINATED.
  
 7) NO SURVEY WAS PROVIDED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.