Plan Review Details - Permit 06110536
Plan Review Stops For Permit 06110536
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-01-20 Cont ID  
Sent By mjacobs Date 2007-01-20 Time 06:44 Rev Time 0.00
Received By mjacobs Date 2007-01-20 Time 06:27 Sent To PC
Notes
2007-01-20 06:33:34BUILDING PROVISO:
 TO BE IN PLACE AT C.O.:
  
 1) 424.2.17.1 OUTDOOR SWIMMING POOLS.
 OUTDOOR SWIMMING POOLS SHALL BE PROVIDED
 WITH A BARRIER COMPLYING WITH
 424.2.17.1.1 THROUGH 424.2.17.1.14.
  
 424.2.17.1.5 CHILD SAFETY BARRIER
 ASTM D5034 100 LB TENSILE STRNGTH
 ASTM D3787 150 LB BALL BURST STRENGTH
  
 2) 13-612.1.ABC.2.3.2 COVERS REQUIRED.
 SPAS AND HEATED SWIMMING POOLS SHALL BE
 EQUIPPED WITH A COVER DESIGNED TO
 MINIMIZE HEAT LOSS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-12-26 Cont ID  
Sent By mjacobs Date 2006-12-26 Time 10:09 Rev Time 0.00
Received By mjacobs Date 2006-12-26 Time 05:59 Sent To PC
Notes
2006-12-26 09:53:48BUILDING PLAN REVIEW
 PERMIT:06110536
 ADD:108 CORTEZ RD.
 CONT: STREAMLINE POOL CO. INC.
 TEL: (561)723-0162
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1)WPB AMENDMENTS. 108.3*.THE CLAIMED VALUATION OF
 THE POOL IS TO LOW. FOR PERMITTING PURPOSES,VALUATION
 FOR SYSTEMS SHALL BE TOTAL REPLACEMENT COST EXCLUDING
 LAND VALUE. OUR VALUATION REFERENCE IS ICC (BVD),
 MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES.
 ADDITIONAL FEES ARE DUE IN THE AMOUNT OF $222.40 . ON
 THE APPLICATION DISCRIPTION INCIACTE IF A HEAT PUMP ON
 SHEET #3 WILL BE INSTALLED. IF THERE WILL BENO HEAT
 PUMP REMOVE THIS INFORMATION FROM THE DIAGRAM.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-01-18 Cont ID  
Sent By btrobaug Date 2007-01-18 Time 15:57 Rev Time 0.25
Received By btrobaug Date 2007-01-18 Time 15:52 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-12-01 Cont ID  
Sent By btrobaug Date 2006-12-01 Time 10:44 Rev Time 0.50
Received By btrobaug Date 2006-12-01 Time 10:24 Sent To P
Notes
2006-12-01 10:44:26 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 PLEASE SUBMIT DETAILS FOR THE PANEL SHOWN ON THE
 SCHEMATIC, FEEDER AND CONDUIT SIZE AND TYPE, PANEL
 RATING AND OCP,PANEL SCHEDULE AND COMPUTED LOAD, ETC.
 IF THIS PANEL IS AN EXISTING POOL PANEL, SIMPLY LABEL
 IT AS SUCH.
 IF AN ELECTRIC HEATER IS TO BE INSTALLED AS SHOWN ON
 THE ELECTRICAL SCHEMATIC,PLEASE SUBMIT CALCULATIONS
 FOR THE MAIN SERVICE AND SPECIFICATIONS FOR THE
 HEATER.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-01-18 Cont ID  
Sent By adarroug Date 2007-01-18 Time 11:49 Rev Time 0.00
Received By adarroug Date 2007-01-18 Time 11:49 Sent To E
Notes
2007-01-18 11:49:39TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-12-27 Cont ID  
Sent By adarroug Date 2006-12-27 Time 13:28 Rev Time 0.00
Received By adarroug Date 2006-12-27 Time 13:28 Sent To Z
Notes
2006-12-27 13:28:57TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2006-12-26 Time   Rev Time 0.00
Received By mmiller Date 2006-11-29 Time 17:57 Sent To  
Notes
2006-11-29 17:57:54SENT TO ELECTRICAL BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-12-26 Time   Rev Time 0.00
Received By adarroug Date 2006-11-17 Time 15:37 Sent To  
Notes
2006-11-17 15:38:08TO "Z" BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-01-19 Cont ID  
Sent By mperson Date 2007-01-19 Time 16:00 Rev Time 0.45
Received By mperson Date 2007-01-19 Time 16:00 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-12-04 Cont ID  
Sent By mperson Date 2006-12-04 Time 15:34 Rev Time 0.33
Received By mperson Date 2006-12-04 Time 15:34 Sent To B
Notes
2006-12-04 15:56:24DENIED
 REFERENCE: FBC-2004 SEC. 424.2 OR FBCR-2004 SEC.4101
  
 PLEASE ADJUST YOUR NOTES, DETAILS, OR SUBMITTALS TO
 REFLECT THE FOLLOWING INFORMATION REQUIRED FOR PLUMBING
 PLAN REVIEW:
  
 1) FBC-2004 SEC. 424.2.6.6.5, OR
 FBCR-2004 SEC. R4101.6.6.5 WHERE
 PROVIDED, THE VACUUM OR PRESSURE CLEANER
 FITTING SHALL BE LOCATED AT LEAST 6" AND
 NOT GREATER THAN 12" BELOW THE MINIMUM
 OPERATING WATER LEVEL OR AS AN
 ATTACHMENT TO THE SKIMMER.
 NOTE: PLEASE PROVIDE MANUFACTURE CUT SHEET OR LIST MAKE
 AND MODEL NUMBER OF CLEANING FITTING ON PRINTS.
  
 2) ON SHEET 3 OF 3 THERE IS A HEAT PUMP INDICATED ON
 THE ELECTRICAL SCHEMATIC IS THIS PART OF THE POOL? IF
 NOT PLEASE REMOVE. IF THIS IS PART OF THE POOL PLEASE
 ADD TO PLUMBING SCHEMATIC AND PROVIDE THE FOLLOWING.
 A) FBC-2004 SEC. 424.2.14.1, OR
 FBCR-2004 SEC. R4101.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. (MANUFACTURE
 SHEETS REQUIRED, PLEASE SUBMIT)
 B) FBC-2004 SEC. 424.2.14.2, OR
 FBCR-2004 SEC. R4101.14.2 WATER
 RETENTION, PROVIDE A POSITIVE MEANS OF
 RETAINING WATER IN THE HEATER WHEN PUMP
 IS SHUT OFF.(MANUFACTURE SHEETS
 REQUIRED, PLEASE SUBMIT)
 C) FBC-2004 SEC. 424.2.14.4, OR
 FBCR-2004 SEC. R4101.14.4 CONNECTIONS,
 ALL WATER HEATING EQUIPMENT SHALL BE
 INSTALLED WITH FLANGES OR UNION
 CONNECTIONS ADJACENT TO THE HEATER.
 (ADD TO NOTES)
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop Z ZONING
Rev No 2 Status P Date 2007-01-17 Cont ID  
Sent By jroach Date 2007-01-17 Time 16:11 Rev Time 0.00
Received By jroach Date 2007-01-17 Time 16:11 Sent To I
Notes
2007-01-17 16:13:081/17/06 ***PASSED WITH PROVISOS***
  
 1) THIS PERMIT IS ONLY FOR THE POOL, POOL EQUIPMENT AND
 POOL DECK.
 2) SEPARATE PERMIT APPLICATION SHALL BE SUBMITTED FOR
 THE FENCE/POOL ENCLOSURE.
 3) FINAL INSPECTION OF THE POOL SHALL NOT OCCUR UNTIL
 AFTER THE C.O. HAS BEEN ISSUED FOR THE RESIDENCE.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT JOHN ROACH, SENIOR
 PLANNER, AT (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-11-26 Cont ID  
Sent By mmclean Date 2006-11-26 Time 22:58 Rev Time 0.00
Received By mmclean Date 2006-11-26 Time 22:58 Sent To I
Notes
2006-11-26 23:02:08DENIED.
 1. NEED TO SHOW THE LOCATION OF THE PROPOSED POOL
 EQUIPMENT ON TWO COPIES OF SURVEYS WITHIN THE
 EASEMENTS.
 2. PLEASE CLAIFY IF THE PROPOSED LANI IS APART OF THE
 POOL PERMIT. NEED TO GENERATE A SEPERATE MISC PERMIT
 FOR THE PROPOSED WORK.
 3. NEED TO SHOW INTERIOR ACCESS OF THE MAIN HOUSE TO
 THE PROPOSED LANI. 2 COPIES OF FLOOR PLANS NEEDED AND
 ELEVATION PLANS.
 4. PLEASE PROVIDE THE SIDE SETBACK OF THE PROPOSED
 LANI.
  
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720