| 2006-12-06 19:43:36 | ***********UNSAT ************* |
| | |
| | PUBLIX GENERATOR |
| | #651 |
| | |
| | 1) NOTE:PLEASE SEE VALUE FOR SCOPE AHS BEEN INCREASED |
| | TO THE COST OF OTHER TYPICAL GENERATORS APPLIED FOR IN |
| | THIS JURISDICTION.PLEASE KNOW FALSIFYING INFORMATION |
| | ON AN APPLICATION IS GROUNDS FOR TURNING OVER TO THE |
| | STATE ECLB. PLEASE KNOW THIS COMMENT HAS BEEN MADE ON |
| | ALL OTHER PROJECTS SUBMITTED BY THIS CONTRACTOR FOR THE |
| | SAME SCOPE OF WORK AND THIS IS STILL BEING SUBMITTED |
| | WITH VALUES WAY LOW FOR ANY LABOR OR MATERIALS. PLEASE |
| | KNOW ANY FUTURE PROJECTS WILL NOT BE PROCESSED OR |
| | REVIEWED IF THIS IS DONE. THIS HAS NOW BEEN DOCUMENTED |
| | AS THE FOURTH PROJECT LOCATED IN THE CITY OF WEST PALM |
| | BEACH WHERE THE APPLICATIONS HAVE BEEN SUBMITTED BELOW |
| | ANY LEVELS OF VALUE ACCURATE TO THE SCOPE OF WORK. |
| | THE VALUE OF $10K ON PERMIT APPLICATION SUBMITTED IS |
| | EXTREMELY LOW. |
| | PLEASE KNOW THAT VALUE SHALL BE ALL LABOR AND MATERIALS |
| | EVEN IF MATERIALS ARE OWNER SUPPLIED.PLEASE SEE FBC |
| | 2004, ADMINISTRATIVE CODE SECTION 108.3 AS ADOPTED BY |
| | THE CITY OF WEST PALM BEACH. |
| | PLEASE KNOW, UNDER CONTRACTING LAWS AND RULES SET UP |
| | AND ADOPTED INTO FLORIDA |
| | STATUTES, 489, FBC ADMINISTRATIVE SECTION |
| | 105.5.1 ANY INFORMATION PROVIDED ON OFFICIAL PERMIT |
| | APPLICATION IF KNOWINGLY BEING FALSIFIED CAN |
| | VOID/REVOKE SUCH PERMIT/ APPLICATION. |
| | ** PLEASE KNOW THESE FEES OF $1975.80 ARE DUE AT THIS |
| | TIME AND WILL BE REQUIRED TO BE PAID BEFORE PICKING UP |
| | PLANS. NO EXCEPTIONS. |
| | |
| | 2) NOTE: PLEASE KNOW, ANY SYSTEMS LOCATED IN A FLOOD |
| | ZONE "A" WILL BE REQUIRED TO BE MOUNTED AT A MIN OF 6" |
| | ABOVE BFE. PLEASE SEE BUILDING REVIEW COMMENTS. |
| | |
| | 3) NOTE: PLEASE SUBMIT SPECS/MANUFACTURE CUT SHEETS. |
| | APS/ ATS DO NOT INDICATE THE REQUIRED MEANS OF |
| | DISCONNECT AS REQUIRED BY 230.76,230.79, 225.31-39. |
| | PLEASE SEE A MANUAL MEANS OF DISCONNECT COULD NOT BE |
| | LOCATED RATED FOR THE LOAD SERVED ON THE OUTSIDE OF |
| | EQUIPMENT SUBMITTED. |
| | THIS WAS NEVER VERIFIED FROM PREVIOUS PERMIT PULLED FOR |
| | PREVIOUS PROJECT. |
| | NO PERMITS WILL BE RELEASED UNLESS THIS IS VERIFIED ON |
| | ALL SUBMITTED SPECS AND PLANS SUBMITTED BEFORE PERMIT |
| | IS ISSUED. |
| | PLEASE SEE ALL EQUIPMENT SHALL BE LISTED FOR USE.90.7, |
| | 110.3 |
| | |
| | 4) NOTE: PLEASE INDICATE THE OCP AT THE GEN. PLEASE SEE |
| | 445.13 AS IT HAS COME TO OUR ATTENTION ON A PREVIOUS |
| | PROJECT THAT THE GEN MAY NOT CONTAIN OCP AND CAN NOT BE |
| | VERIFIED AT THIS TIME. |
| | |
| | 5) NOTE: PLEASE SEE NO LOAD CALCULATIONS WERE SUBMITTED |
| | FOR REVIEW. PLEASE SUBMIT. |
| | PLEASE SUBMIT AND INDICATE ANY LOAD SHEDDING DETAILS IF |
| | APPLICABLE. |
| | 702.5, 220 |
| | |
| | 6) NOTE: PLEASE PROVIDE INFORMATION IF THE GEN WILL BE |
| | FEEDING ANY "LEGALLY REQUIRED STAND-BY SYSTEMS". PLANS |
| | TO INDICATE THIS, NOT ONLY IN A RESPONSE LETTER. |
| | |
| | 7) NOTE:PLEASE SEE PLANS SHALL INDICATE THE CURRENT |
| | CODES IN EFFECT FOR INSTALLATION AS FOLLOWS. PLEASE SEE |
| | FBC 2004 CHAPTER 27FOR ADOPTED CODES RELEVANT TO |
| | POWER GENERATORS. |
| | 2002 NFPA-70, 2002 NFPA-110(WHERE CLASS 1 OR 2) |
| | |
| | 8) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT |
| | SHEETS FOR THE GENERATOR. NONE SUBMITTED AT THIS TIME, |
| | UNABLE TO REVIEW. |
| | 110.3, 90.7. ETC |
| | FCB 106.1.2 |
| | |
| | 9) NOTE: PLEASE SEE THE APS/ATS IS BECOMING THE NEW |
| | FIRST MEANS OF DISCONNECT HOWEVER THE NEW GROUNDING |
| | ELECTRODE SYSTEMS DOES NOT SEEM TO BE COMPLETE AS PER |
| | 250.50. |
| | PLEASE SEE GROUNDING DETAIL MENTIONS NEW SLAB STEEL |
| | WHICH IS OK, HOWEVER PLEASE INDICATE ATTACHMENT. |
| | THESE NEW SLAB/STEEL ATTACHMENTS DO NOT MEET THE MIN |
| | REQUIREMENTS PER |
| | 250.50, 250.52, 250.104 |
| | IF SLAB STEEL IS ONLY BEING BONDED, THEN PLEASE |
| | INDICATE. |
| | PLEASE COMPLETE GROUNDING ELECTRODE SYSTEM(S) AND |
| | BONDING FOR ALL AS ABOVE. |
| | PLEASE SEE DETAIL STILL INDICATES THE NEUTRAL AND |
| | EXISTING GROUNDING ELECTRODE SYSTEM BEING BONDED AT THE |
| | EXISTING SERVICE WHICH WILL PARALLEL THE NEW SYSTEM |
| | REQUIRED. |
| | 250.6, 250.24B. |
| | |
| | 10) NOTE: PLEASE SEE SETS OF CONDUITS AND FEEDERS DO |
| | NOT SEEM TO INDICATE THE NEW REQUIRED "EQUIPMENT |
| | GROUNDING CONDUCTOR" TO THE EXISTING MAINS. THESE ARE |
| | NO LONGER THE FIRST MEANS OF DISCONNECT. |
| | 250.110,250.122,250.24B, 250.6, AS NOTED ABOVE IN NOTE |
| | #9 |
| | |
| | 11) NOTE:PLEASE KNOW, BASED ON ALL PREVIOUS PROJECTS, |
| | IS THIS UNIT GOING TO BE "BI-FUEL"?? |
| | IF SO, SUBMIT ALL INFORMATION AND SPECS ON UNIT(S). |
| | 90.7, 110.3 |
| | |
| | 12) NOTE: PLEASE KNOW AS THE ORIGINAL PROJECT AT STORE |
| | #50 LOCATED AT 828 SOUTHERN BLVD HAS NOT PASSED |
| | INSPECTIONS AND THERE ARE SEVERAL UNANSWERED QUESITONS |
| | ON PROJECT,AS STATED ON OTHER GENERATOR PERMITS, |
| | THESE WILL NOT BE ISSUED UNTIL ALL CODE COMPLIANCE IS |
| | MET ON THE ORIGINAL PROJECT. |
| | PLEASE KNOW ALL PERMITS EXPIRE WITHIN 6 MONTHS OF IN- |
| | ACTIVITY. |
| | FBC ADMIN SECTION 105.3.2 |
| | |
| | |
| | ** PLEASE KNOW, AS MUCH INFORMATION WAS NOT SUBMITTED, |
| | A COMPLETE REVIEW COULD NOT BE DONE. |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |