Plan Review Details - Permit 06110482
Plan Review Stops For Permit 06110482
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-12-11 Cont ID  
Sent By mawillia Date 2006-12-11 Time 12:52 Rev Time 0.00
Received By mawillia Date 2006-12-11 Time 12:52 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-11-30 Cont ID  
Sent By mawillia Date 2006-11-30 Time 12:39 Rev Time 0.00
Received By mawillia Date 2006-11-30 Time 12:35 Sent To  
Notes
2006-11-30 13:00:30*****UNSAT*****
  
  
  
 1.THE PERMIT APPLICATION AND THE CITY'S COMPUTER
 ENTRY SYSTEM STATES THAT THE ADDRESS IS 309 CLEMATIS
 STREET, HOWEVER THE ADDRESS REFLECTED ON THE SUBMITTED
 PLANS IS 311 CLEMATIS STREET.THE ADDRESS ON THE
 PERMIT AND PLANS MUST BE THE SAME.FOR ADDRESSING
 MATTERS, CONTACT LILI URSA AT 561-822-1239.
  
 2.APRESSURE TEST WILL BE REQUIRED SINCE THE
 MODIFICATION AFFECTS MORE THAN 20 HEADS.HOWEVER, IF
 THE MODIFICATION CANNOT BE ISOLATED AS PER NFPA
 16.2.1.6, A LETTER FROM YOUR COMPANY STATING SUCH AT
 THE SAID LOCATION SHALL BE PROVIDED TO THE FIRE
 PREVENTION BUREAUPRIOR TO OR AT THE TIME OF
 INSPECTION.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-12-01 Cont ID  
Sent By adarroug Date 2006-12-01 Time 16:23 Rev Time 0.00
Received By adarroug Date 2006-12-01 Time 16:23 Sent To FIRE
Notes
2006-12-01 16:24:16TO "F" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-11-30 Cont ID  
Sent By mawillia Date 2006-11-30 Time 12:35 Rev Time 0.00
Received By mawillia Date 2006-11-16 Time 09:59 Sent To  
Notes
2006-11-16 09:59:48TO "F" BOX