| Plan Review Stops For Permit 06110427 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2007-04-05 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2007-04-05 |
Time |
07:26 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2007-04-04 |
Time |
18:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-03-27 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2007-03-27 |
Time |
12:27 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2007-03-27 |
Time |
12:27 |
Sent To |
|
|
| Notes |
| 2007-03-27 13:10:56 | DENIED BY BUILDING (2ND REVIEW) | | | | | | THE FOLLOWING ITEMS FROM THE FIRST REVIEW WERE NOT | | | ADDRESSED. | | | | | | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT | | | MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2)SPECIFY THE SIZE OF THE REMAINING WINDOW IN THE | | | BEDROOM ADJACENT TO THE NEW ADDITION. SEE R 310 FOR | | | EMERGENCY EGRESS REQUIREMENTS. | | | | | | 3)THE NEW BATHROOM DOOR IS REQUIRED TO HAVE A 29" | | | CLEAR OPENING. SEE R 322. | | | | | | 4) SUBMIT SIGNED AND SEALED TRUSS DRAWINGS REVIEWED AND | | | APPROVED BY THE DESIGNER OF RECORD AS REQUIRED BY | | | R802.1.6.1. GIVE TO BUILDING INSPECTOR IN THE FIELD. | | | | | | 5) SUBMIT A DRAINAGE PLAN SHOWING COMPLIANCE WITH THE | | | REQUIREMENTS OF R401.3. | | | | | | 6) THE TRUSS CONNECTION FOR THE SIMPSON HTSM16 REQUIRES | | | (8) 10D NAILS FOR THE STATED UPLIFT VALUE PER THE | | | SIMPSON CATALOG. PLEASE REVISE. | | | | | | 7) THE CORNERS OF HIP ROOFS ARE ALSO ZONE 3. PLEASE | | | CORRECT THE ROOF ZONE DIAGRAM ON SHEET 11. SEE FIGURE | | | 803.2.3.1 AND FBC FIGURE 1609.6.2.2. | | | | | | 8) SPECIFY THE ROOF VENTILATION AS REQUIRED BY R 806. | | | | | | 9) SPECIFY THE SIZE AND LOCATION OF THE ATTIC ACCESS | | | REQUIRED BY R 807. | | | | | | 10) SAFETY GLAZING IS REQUIRED IN BATHROOM WINDOW PER R | | | 308.4 IF BOTTOM OF WINDOW IS LESS THAN 60" ABOVE | | | FLOOR. | | | | | | 11) SUBMIT PRODUCT APPROVALS FOR THE STRUCTURAL WINDOW | | | MULLIONS. | | | | | | 12) SUBMIT FLORIDA PRODUCT APPROVAL COVERSHEETS FOR THE | | | 2004 CODE EDITION. MOST OF THE ONES SUBMITTED ARE FOR | | | 2001 CODE. | | | | | | 13) SEVERAL OF THE MIAMI-DADE NOAS THAT WERE SUBMITTED | | | ARE EXPIRED. PLEASE REVIEW THE PRODUCT APPROVALS AND | | | SUBMIT CURRENT INFORMATION. | | | | | | 14) ONLY TWO COMPLETE SETS OF PLANS AND SUBMITTALS ARE | | | REQUIRED. | | | | | | PLEASE SUBMIT A TRANSMITTAL LETTER WITH THE RESUBMITTAL | | | INDICATING HOW THE COMMENTS HAVE BEEN ADDRESSED. | | | | | | NEW ITEMS : | | | | | | 15) THE REAR ELEVATION ON SHEET 4 DOES NOT SHOW THE | | | EXTERIOR DOOR TO THE BATHROOM. | | | | | | 16) ON SHEET 9, SIMPSON META 14 CONNECTORS ARE | | | SPECIFIED AT AN EXISTING WALL OF THE NEW LAUNDRY ROOM. | | | PLEASE SPECIFY AN APPROPRIATE CONNECTOR. SEE RED MARKS | | | ON PLANS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-01-23 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2007-01-23 |
Time |
18:05 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2007-01-23 |
Time |
18:05 |
Sent To |
|
|
| Notes |
| 2007-01-24 06:36:02 | DENIED BY BUILDING | | | | | | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT | | | MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY, PLANS STAMPED BY THEM AND | | | COPY OF RECEIPT SUBMITTED TO CITY OF | | | WEST PALM BEACH BUILDING DEPARTMENT, | | | BEFORE A BUILDING PERMIT CAN BE ISSUED. | | | | | | 3) SUBMIT ENERGY CALCULATIONS REQUIRED BY FBC CHAPTER | | | 11. | | | | | | 4)SPECIFY THE SIZE OF THE REMAINING WINDOW IN THE | | | BEDROOM ADJACENT TO THE NEW ADDITION. SEE R 310 FOR | | | EMERGENCY EGRESS REQUIREMENTS. | | | | | | 5)THE NEW BATHROOM DOOR IS REQUIRED TO HAVE A 29" | | | CLEAR OPENING. SEE R 322. | | | | | | 6) SUBMIT SIGNED AND SEALED TRUSS DRAWINGS REVIEWED AND | | | APPROVED BY THE DESIGNER OF RECORD AS REQUIRED BY | | | R802.1.6.1. | | | | | | 7) SUBMIT A DRAINAGE PLAN SHOWING COMPLIANCE WITH THE | | | REQUIREMENTS OF R401.3. | | | | | | 8) THE TRUSS CONNECTION FOR THE SIMPSON HTSM16 REQUIRES | | | (8) 10D NAILS FOR THE STATED UPLIFT VALUE PER THE | | | SIMPSON CATALOG. PLEASE REVISE. | | | | | | 9) THE CORNERS OF HIP ROOFS ARE ALSO ZONE 3. PLEASE | | | CORRECT THE ROOF ZONE DIAGRAM ON SHEET 11. SEE FIGURE | | | 803.2.3.1 AND FBC FIGURE 1609.6.2.2. | | | | | | 10) SPECIFY THE ROOF VENTILATION AS REQUIRED BY R 806. | | | | | | 11) SPECIFY THE SIZE AND LOCATION OF THE ATTIC ACCESS | | | REQUIRED BY R 807. | | | | | | 12) SAFETY GLAZING IS REQUIRED IN BATHROOM WINDOW PER R | | | 308.4 IF BOTTOM OF WINDOW IS LESS THAN 60" ABOVE | | | FLOOR. | | | | | | 13) SUBMIT PRODUCT APPROVALS FOR THE STRUCTURAL WINDOW | | | MULLIONS. | | | | | | 14) SUBMIT FLORIDA PRODUCT APPROVAL COVERSHEETS FOR THE | | | 2004 CODE EDITION. MOST OF THE ONES SUBMITTED ARE FOR | | | 2001 CODE. | | | | | | 15) SEVERAL OF THE MIAMI-DADE NOAS THAT WERE SUBMITTED | | | ARE EXPIRED. PLEASE REVIEW THE PRODUCT APPROVALS AND | | | SUBMIT CURRENT INFORMATION. | | | | | | 16) ONLY TWO COMPLETE SETS OF PLANS AND SUBMITTALS ARE | | | REQUIRED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2006-11-28 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-11-28 |
Time |
14:03 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2006-11-28 |
Time |
13:56 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2007-04-02 |
|
|
Cont ID |
|
| Sent By |
spalmer |
Date |
2007-04-02 |
Time |
15:43 |
Rev Time |
0.00 |
| Received By |
spalmer |
Date |
2007-04-02 |
Time |
15:43 |
Sent To |
B |
|
| Notes |
| 2007-04-02 15:43:23 | TO ROBERT MCDOUGAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-03-10 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-03-10 |
Time |
12:10 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-03-10 |
Time |
12:10 |
Sent To |
M |
|
| Notes |
| 2007-03-10 12:10:44 | TO "M" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-12-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-12-06 |
Time |
10:35 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-12-06 |
Time |
10:35 |
Sent To |
M |
|
| Notes |
| 2006-12-06 10:35:51 | TO "M" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-12-04 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-12-04 |
Time |
11:58 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-12-04 |
Time |
11:58 |
Sent To |
Z |
|
| Notes |
| 2006-12-04 11:59:24 | PLANS ROUTED BACK TO "Z".PLANS STAMPED BY "Z", BUT NO | | | REVIEW WAS ENTERED IN SYSTEM.ADARROUGH |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-01-24 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2007-01-24 |
Time |
06:36 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2006-11-15 |
Time |
11:57 |
Sent To |
|
|
| Notes |
| 2006-11-15 16:15:02 | TO "E" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2007-03-12 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-03-12 |
Time |
14:29 |
Rev Time |
0.25 |
| Received By |
tgordon |
Date |
2007-03-12 |
Time |
14:29 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2006-12-11 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-12-11 |
Time |
16:12 |
Rev Time |
0.25 |
| Received By |
tgordon |
Date |
2006-12-11 |
Time |
16:12 |
Sent To |
P |
|
| Notes |
| 2006-12-11 16:17:05 | *** DENIED *** | | | 1) PLEASE SUBMIT ENERGY CALCULATIONS, PER 2004 FBC | | | 13-600.3.C. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2007-03-22 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-03-22 |
Time |
11:02 |
Rev Time |
0.33 |
| Received By |
mperson |
Date |
2007-03-22 |
Time |
11:02 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2006-12-12 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2006-12-12 |
Time |
13:17 |
Rev Time |
0.45 |
| Received By |
mperson |
Date |
2006-12-12 |
Time |
13:17 |
Sent To |
B |
|
| Notes |
| 2006-12-12 13:35:03 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | | | | THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING | | | PLAN REVIEW TO MEET CODE COMPLIANCE: | | | | | | 1. SHEET 13 0F 13 SANITARY RISER DIAGRAM DOES NOT | | | REFLECT THE FLOOR PLAN. PLEASE REFERENCE THE CORRECTED | | | SANITARY RISER DIAGRAM IN RED INK FOR THE RESUBMITTAL. | | | | | | A) BATHROOM LAVATORY NEEDS TO BE PIPED WITH A WYE | | | FITTING NOT OFF A DOUBLE COMBO FITTING | | | B) WASTE ARMS ARE MISSING FOR THE DOUBLE BOWL KITCHEN | | | SINK. | | | | | | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, | | | PLEASE REPLACE ONLY SHEETS | | | WHICH HAVE CHANGED AND PROVIDE ONE COPY | | | OF ALL OLD/VOIDED SHEETS FOR REFERENCE | | | ONLY. NOTE: ONLY ONE CORRECTED DRAWING | | | IN RED INK FOR REFERENCE FOR | | | RESUBMITTAL.AS INDICATED. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2006-12-01 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-12-01 |
Time |
09:38 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-12-01 |
Time |
09:38 |
Sent To |
I |
|
| Notes |
|
|