Plan Review Details - Permit 06110410
Plan Review Stops For Permit 06110410
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-03-05 Cont ID  
Sent By rmcdouga Date 2007-03-05 Time 18:46 Rev Time 0.00
Received By rmcdouga Date 2007-03-05 Time 18:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-01-22 Cont ID  
Sent By rmcdouga Date 2007-01-22 Time 12:44 Rev Time 0.00
Received By rmcdouga Date 2007-01-22 Time 12:44 Sent To  
Notes
2007-01-22 13:10:54DENIED BY BUILDING
  
 1)AN OWNER BUILDER CAN NOT BE ISSUED A PERMIT TO WORK
 ON A MULTIFAMILY RESIDENTIAL CONDOMINIUM.SEE FLORIDA
 STATUTES 489.103.
  
 2) USING 2004 FBC DESIGNATIONS, PLEASE SPECIFY THE
 CONSTRUCTION TYPE, NUMBER OF STORIES, SPRINKLERED OR
 NOT, ETC.
  
 3) IF THE BUILDING IS TYPE I OR TYPE II CONSTRUCTION,
 FBC 602.2 REQUIRES THE NON-LOAD BEARING INTERIOR
 PARTITIONS TO BE OF NONCOMBUSTABLE MATERIALS.
  
 4) SPECIFY THE LEVEL OF ALTERATION FOR THE SCOPE OF
 WORK AS REQUIRED BY THE 2004 FLORIDA EXISTING BUILDING
 CODE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-03-02 Cont ID  
Sent By btrobaug Date 2007-03-02 Time 09:12 Rev Time 0.50
Received By btrobaug Date 2007-03-02 Time 07:53 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-11-28 Cont ID  
Sent By btrobaug Date 2006-11-28 Time 10:24 Rev Time 1.00
Received By btrobaug Date 2006-11-28 Time 07:27 Sent To P
Notes
2006-11-28 10:24:48 
  
 1} PROVIDE A LOAD CALCULATION PER220 SECTION I OR
 220.31, INCLUDE EXISTING AND ADDED LOADS. THIS
 CALCULATION MUST BE DONE TO REVIEW COMPLIANCE OF THE
 ENTIRE SERVICE LOAD. INDICATE SERVICE RATING.
  
 2} PLEASE PROVIDE A RISER DIAGRAM PER 215.5. THE RISER
 SHOWN DOES NOT INDICATE DISCONNECTING MEANS OR
 OVERCURRECT PROTECTION FOR THE FEEDERS.
  
 3} PLEASE PROVIDE A SITE PLAN AND INDICATE THE AREA OF
 WORK APPLIED FOR 106.3.5.4 FBC AS AMMENDED.
  
 4} THE APPLIANCE LOCATED IN THE CLOSET IS DESIGNATED
 "EWC" ON THE PLAN AND LISTED AS A HEATER ON THE PANEL
 SCHEDULE, PLEASE CORRELATE.
  
 5} INDICATE THE LOCATION OF THE DISCONNECTING MEANS FOR
 THE WATER HEATER, SEE 422.31(B).
  
 6}A RECEPTACLE NEEDS TO BE ADDED IN THE BEDROOM FOR
 210.52 SPACING REQUIREMENTS, SEE REVIEWED SET FOR
 APPROXIMATE LOCATION.
  
 7}SMOKE DETECTORS MUST BE INSTALLED TO COMPLY WITH
 R313.1 RESIDENTIAL FLORIDA BUILDING CODE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-02-23 Cont ID  
Sent By adarroug Date 2007-02-23 Time 09:49 Rev Time 0.00
Received By adarroug Date 2007-02-23 Time 09:49 Sent To E
Notes
2007-02-23 09:49:50TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-01-22 Cont ID  
Sent By rmcdouga Date 2007-01-22 Time 13:11 Rev Time 0.00
Received By rmcdouga Date 2006-11-15 Time 09:43 Sent To  
Notes
2006-11-15 09:43:39TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-03-05 Cont ID  
Sent By rmcdouga Date 2007-03-05 Time 18:53 Rev Time 0.00
Received By rmcdouga Date 2007-03-05 Time 18:53 Sent To  
Notes
2007-03-05 18:56:33OK PER T. GORDON3/5/07RM
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-12-01 Cont ID  
Sent By tgordon Date 2006-12-01 Time 14:08 Rev Time 0.25
Received By tgordon Date 2006-12-01 Time 14:08 Sent To B
Notes
2006-12-01 14:12:05*** DENIED ***
 1) NEED TO SHOW ON PLANS HOW RETURN AIR IS TO GET BACK
 TO THE AIR HANDLER FROM THE LIVING ROOM AND BEDROOM,
 SEE 2004 FBC/R M1602.4.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-03-05 Cont ID  
Sent By mperson Date 2007-03-05 Time 11:46 Rev Time 0.33
Received By mperson Date 2007-03-05 Time 11:46 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-11-30 Cont ID  
Sent By btrobaug Date 2006-11-28 Time 10:25 Rev Time 0.45
Received By mperson Date 2006-11-30 Time 15:37 Sent To M
Notes
2006-11-30 16:29:55UNSAT
 REFERENCE: FBC-2004 PLUMBING,FBC-2004 CHAPTER 1 AND
 STATE STATUTES
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PER STATE STATUTES CHAPTER 489, PART 1 AN OWNER
 BUILDER CAN NOT DO THE WORK ON THEIR CONDO.
  
 2. PER FBC-2004, CHAPTER 1, SECTION 106.3.5.1.3: PLEASE
 SUBMIT A PLUMBING SANITARY ISOMETRIC RISER DIAGRAM
 INDICATING ALL WASTE, VENTS, TRAPS WITH SIZES, AND
 CLEANOUT LOCATIONS OF THE CHANGES IN THE KITCHEN.
  
 3. PER FBC-2004, CHAPTER 1, SECTION 106.3.5.1.3: PLEASE
 SUBMIT A WATER ISOMETRIC RISER DIAGRAM INDICATING
 SIZES, SHUT OFF VALVES, AND WATER HAMMER-ARRESTOR
 LOCATIONS IN RELATION TO QUICK-CLOSING VALVES.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  