Plan Review Details - Permit 06110378
Plan Review Stops For Permit 06110378
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status N Date 2007-12-13 Cont ID  
Sent By shill Date 2007-12-13 Time 16:16 Rev Time 0.00
Received By shill Date 2007-12-13 Time 16:16 Sent To  
Notes
2007-12-13 16:16:26RESTAMP, ROUTED TO ZONING FOR PROVISO/STAMPS

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2007-01-18 Cont ID  
Sent By shill Date 2007-01-18 Time 14:52 Rev Time 0.00
Received By shill Date 2007-01-18 Time 14:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2007-12-14 Cont ID  
Sent By btrobaug Date 2007-12-14 Time 15:35 Rev Time 0.00
Received By btrobaug Date 2007-12-14 Time 15:34 Sent To G
Notes
2007-12-14 15:35:23 
  
  
 RESTAMP, SENT TO MIKE./WRT.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-01-31 Cont ID  
Sent By btrobaug Date 2007-01-31 Time 07:14 Rev Time 0.50
Received By btrobaug Date 2007-01-31 Time 06:45 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-11-30 Cont ID  
Sent By btrobaug Date 2006-11-30 Time 16:26 Rev Time 0.33
Received By btrobaug Date 2006-11-30 Time 16:10 Sent To M
Notes
2006-11-30 16:26:48 
  
 DENIED/INCOMPLETE INFORMATION
  
 PROVIDE THE MANUFACTURERES RECOMMENDATION FOR SETBACK
 FROM STRUCTURES.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2007-12-17 Cont ID  
Sent By mperson Date 2007-12-17 Time 07:26 Rev Time 0.00
Received By mperson Date 2007-12-17 Time 07:26 Sent To M
Notes
2007-12-17 07:27:46RESTAMP SENT TO TOM G. /MRPERSON

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-02-07 Cont ID  
Sent By mperson Date 2007-02-07 Time 14:29 Rev Time 0.33
Received By mperson Date 2007-02-07 Time 14:29 Sent To M
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-12-12 Cont ID  
Sent By mperson Date 2006-12-12 Time 13:59 Rev Time 0.33
Received By mperson Date 2006-12-12 Time 13:59 Sent To B
Notes
2006-12-12 14:26:30DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN
 REVIEW TO MEET CODE COMPLIANCE:
  
 1. PLEASE INDICATE THE TYPE OF GAS, (LP OR NATURAL) ON
 THE DRAWINGS. THE PERMIT APPLICATION INDICATES NATURAL
 GAS BUT THE SUBMITTED DRAWINGS INDICATE A 1ST AND 2ND
 STAGE REGULATOR WHICH ARE USED FOR LP GAS SYSTEMS.
 PLEASE CORRELATE THIS ON THE RESUBMITTAL.
  
 2. PLEASE INDICATE THE DELIVERY PRESSURE (PSI) ON THE
 DRAWINGS
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 3. PLEASE SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT (MP REGULATORS IF DELIVERY PRESSURE IS 2LB)
 TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 4. PLEASE SUBMIT MANUFACTURE INSTALLATION INSTRUCTIONS
 FOR THE GENERATOR TO VERIFY MANUFACTURER'S
 RECOMMENDATIONS FOR SETBACK FROM STRUCTURES.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-12-07 Cont ID  
Sent By adarroug Date 2007-12-07 Time 15:20 Rev Time 0.00
Received By adarroug Date 2007-12-07 Time 15:20 Sent To B
Notes
2007-12-07 15:20:24TO "SHILL' DESK/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-01-30 Cont ID  
Sent By adarroug Date 2007-01-30 Time 17:44 Rev Time 0.00
Received By adarroug Date 2007-01-30 Time 17:44 Sent To E
Notes
2007-01-30 17:44:28TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-11-16 Cont ID  
Sent By adarroug Date 2006-11-16 Time 14:56 Rev Time 0.00
Received By adarroug Date 2006-11-16 Time 14:56 Sent To E
Notes
2006-11-16 14:57:46TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-01-18 Cont ID  
Sent By shill Date 2007-01-18 Time 14:52 Rev Time 0.00
Received By shill Date 2006-11-13 Time 15:29 Sent To  
Notes
2006-11-13 15:30:01TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-12-17 Cont ID  
Sent By tgordon Date 2007-12-17 Time 08:18 Rev Time 0.20
Received By tgordon Date 2007-12-17 Time 08:18 Sent To  
Notes
2007-12-17 08:18:55RE-STAMP.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-02-08 Cont ID  
Sent By tgordon Date 2007-02-08 Time 11:39 Rev Time 0.30
Received By tgordon Date 2007-02-08 Time 11:39 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-12-01 Cont ID  
Sent By tgordon Date 2006-12-01 Time 15:40 Rev Time 0.20
Received By tgordon Date 2006-12-01 Time 15:40 Sent To G
Notes
2006-12-01 15:43:40*** DENIED ***
 1) PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S AND COMPLETE INSTALLATION INSTRUCTIONS
 FOR GENERATOR.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 3 Status P Date 2007-12-13 Cont ID  
Sent By choops Date 2007-12-13 Time 16:20 Rev Time 0.00
Received By choops Date 2007-12-13 Time 16:20 Sent To E
Notes
2007-12-13 16:21:32***APPROVED - RESTAMP***
  
 PROVISO:GENERATOR SHALL NOT BE CLOSER THAN 6.23' TO
 THE REAR PROPERTY LINE.
  
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 2 Status P Date 2007-02-09 Cont ID  
Sent By mmclean Date 2007-02-09 Time 11:56 Rev Time 0.00
Received By mmclean Date 2007-02-09 Time 11:56 Sent To  
Notes
2007-02-09 11:57:00THE PROPOSED GENERATOR SHALL NOT BE CLOSER THAN 6.23FT
 FROM REAR PROPERTY LINE.

Review Stop Z ZONING
Rev No 1 Status P Date 2006-11-15 Cont ID  
Sent By mmclean Date 2006-11-15 Time 18:50 Rev Time 0.00
Received By mmclean Date 2006-11-15 Time 18:50 Sent To I
Notes
2006-11-15 18:51:33THE PROPOSED GENERATOR SHALL NOT BE CLOSER THAN 6.23FT
 FROM REAR PROPERTY LINE.