Plan Review Details - Permit 06110349
Plan Review Stops For Permit 06110349
Review Stop B BUILDING (STRUCTURAL)
Rev No 14 Status F Date 2008-07-31 Cont ID  
Sent By jwitmer Date 2008-07-31 Time 13:36 Rev Time 1.22
Received By jwitmer Date 2008-07-31 Time 13:36 Sent To PC
Notes
2008-07-31 13:38:02BUILDING PLAN REVIEW
 PERMIT: 06110349
 ADD: 5720 PREMIER PARK DR. BLDG# 3
 CONT:GLOBAL CONSTRUCTION ASSOCIATES
 LLC
 TEL: (954)444-8463
 DATE:7-31-08
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE WITH 2006
 REVISIONS
 * WEST PALM BEACH AMENDMENTS ADMINISTRATIVE CODE
  
 REVIEW- DENIED
 SUBMITTALS: J.B.GARAGE DOORS
 IN THE ORIGINAL SUBMITTALS FOR SECTIONAL DOORS THE
 DESIGNER OF RECORD ALSO SUBMITTED DESIGN CRITERIA FOR
 DOOR BUCK ATTACHMENTS. SINCE THIS IS A SEPERATE NOAAND
 DOOR SIZE IS CONSIDERABLY LARGEER THAN THE 100 SQ FT
 ORIGINALLY SUBMITTED THERE ARE TWO QUESTIONS THAT
 ARISE:
 1) ARE DOOR BUCKS TO BE INSTALLED AGAIN, IF SO PLEASE
 PROVIDE THE ENGINEERING FOR THE DOOR BUCKS, SEE SHEET 2
 OF 4 AND BUCK ATTACHMENTCOMMENTS AS WELL AS SHEET 1 OF
 4 COMMENT# 4 ANCHORING OR LOADING CONDITIONS OTHER THAN
 THOSE SHOWN IN THESE DETAILS ARE NOT PART OF THIS
 APPROVAL.
 2) IF BUCKS ARE NOT TO BE USED, THEN CIRCLE THE
 CONDITIONS TO BE USED FOR THIS INSTALATION.AND ON SHEET
 4 OF 4 CIRCLE HEIGHT OF DOOR TO BE INSTALLED.
  
 BUILDING PLAN REVIEW
 PERMIT: 06110347
 ADD: 5655 PREMIER PARK DR. BLDG# 1
 CONT:GLOBAL CONSTRUCTION ASSOCIATES
 LLC
 TEL: (954)444-8463
 DATE:4-28-08
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE WITH 2006
 REVISIONS
 * WEST PALM BEACH AMENDMENTS ADMINISTRATIVE CODE
  
 REVIEW- DENIED
 SUBMITTALS:

Review Stop B BUILDING (STRUCTURAL)
Rev No 13 Status P Date 2008-07-07 Cont ID  
Sent By jwitmer Date 2008-07-07 Time 13:44 Rev Time 1.22
Received By jwitmer Date 2008-07-07 Time 13:44 Sent To PC
Notes
2008-07-07 13:47:00PREMIER PARK BUILDING #3
  
  
 BUILDING PLAN REVIEW
 PERMIT: 06110349
 ADD: 5720 PREMIER PARK DR. BLDG# 3
 CONT:GLOBAL CONSTRUCTION ASSOCIATES LLC
 TEL: (954)444-8463
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE WITH 2006
 REVISIONS
 * WEST PALM BEACH AMENDMENTS ADMINISTRATIVE CODE
  
 REVIEW-PRODUCT APPROVALS
 ACTION: REVIEWED
 SUBMITTALS: ARCH ALUMINUM
 OUTSWING DOOR NOA 05-0829.08
 STOREFRONTNOA 05-0906.05

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status P Date 2008-07-07 Cont ID  
Sent By jwitmer Date 2008-07-07 Time 13:19 Rev Time 0.77
Received By jwitmer Date 2008-07-07 Time 13:19 Sent To PC
Notes
2008-07-07 13:32:57PREMIER PARK BUILDING #3
  
  
 BUILDING PLAN REVIEW
 PERMIT: 06110349
 ADD: 5720 PREMIER PARK DR. BLDG# 3
 CONT:GLOBAL CONSTRUCTION ASSOCIATES LLC
 TEL: (954)444-8463
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE WITH 2006
 REVISIONS
 * WEST PALM BEACH AMENDMENTS ADMINISTRATIVE CODE
  
 REVISION REVIEW-
 ACTION: REVIEWED
  
  
 REVISIONS: SHEET A-15 REVISION # 6
 PROVISO:
 EFIS/ EPS EXTERIOR MOLDINGSHOP DRAWINGS TO BE
 SUBMITTED REVIEWED BY THE DESIGN TEAM.

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status P Date 2008-07-07 Cont ID  
Sent By jwitmer Date 2008-07-07 Time 11:22 Rev Time 1.33
Received By jwitmer Date 2008-07-07 Time 11:22 Sent To PC
Notes
2008-07-07 11:53:57PERMIT: 06110347
 ADD: 5655 PREMIER PARK DR. BLDG# 1
 CONT:GLOBAL CONSTRUCTION ASSOCIATES
 LLC
 TEL: (954)444-8463
 DATE:7-07-08
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE WITH 2006
 REVISIONS
 * WEST PALM BEACH AMENDMENTS ADMINISTRATIVE CODE
  
 REVIEW:
 SUBMITTALS: ARCH ALUMINUMNOA 05-0906.05STOREFRONT
 IMPACT WALL 3000 SERIES
 ARCH ALUMINUM NOA05-0829.08
 OUTSWING DOOR

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2008-06-06 Cont ID  
Sent By jwitmer Date 2008-06-06 Time 16:22 Rev Time 1.22
Received By jwitmer Date 2008-06-06 Time 16:23 Sent To PC
Notes
2008-06-06 16:27:54REVISIONS:
 S2.1 REV# 2 6-2-08
 SS3.1 REV# 2 6-2-08
 A4 REV#6 5-30-08
 A6 REV#6 5-30-08
 A12 REV# 6 5-30-08

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status F Date 2008-06-06 Cont ID  
Sent By jwitmer Date 2008-06-06 Time 16:10 Rev Time 0.77
Received By jwitmer Date 2008-06-06 Time 16:10 Sent To PC
Notes
2008-06-06 16:15:55BUILDING PLAN REVIEW
 PERMIT: 06110349
 ADD: 5720 PREMIER PARK DR. BLDG# 3
 CONT:GLOBAL CONSTRUCTION ASSOCIATES
 LLC
 TEL: (954)444-8463
 DATE:
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE WITH 2006
 REVISIONS
 * WEST PALM BEACH AMENDMENTS ADMINISTRATIVE CODE
  
 REVISIONREVIEW:
 ACTION: DENIED
  
 SHEET A-15 REVISION# 6INDICATES THE REVISION OF TRIM
 TO BE SECURED TO WALL WITH ADHESIVE AND FASTENERS AT
 2'-0" O.C. AS REQUIRED BY APPROVED MANUFACTURES
 SPECIFICATIONS AND REVIEWED SHOP DRAWINGS BUT THE BACK
 UP INFORMATION WAS NOT SUBMITTED. 106.1.2 ADITIONAL
 INFORMATION REQUIRED.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2008-04-30 Cont ID  
Sent By jwitmer Date 2008-04-30 Time 17:11 Rev Time 0.77
Received By jwitmer Date 2008-04-30 Time 17:11 Sent To PC
Notes
2008-04-30 17:14:31 
 BUILDING PLAN REVIEW
 PERMIT: 06110349
 ADD: 5720 PREMIER PARK DR. BLDG# 3
 CONT:GLOBAL CONSTRUCTION ASSOCIATES
 LLC
 TEL: (954)444-8463
 DATE:
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE WITH 2006
 REVISIONS
 * WEST PALM BEACH AMENDMENTS ADMINISTRATIVE CODE
  
 REVIEW:
 ACTION: DENIED
  
 RAILING SHOP DRAWINGS TOP AND BOTTOM OF STAIR
 HANDRAILS, SEE FIGURE 11-19(C) AND FIGURE 11-19(D),
 HANDRAIL EXTENSIONS SHALL COMPLY WITH SECTION 11-4.4.
 SEE 27" NOT THE 2'-10" AS INDICATED ON PLANS.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2008-04-30 Cont ID  
Sent By jwitmer Date 2008-04-30 Time 16:55 Rev Time 3.55
Received By jwitmer Date 2008-04-30 Time 16:55 Sent To  
Notes
2008-04-30 16:56:17BUILDING PLAN REVIEW
 PERMIT: 06110349
 ADD: 5720 PREMIER PARK DR. BLDG# 3
 CONT:GLOBAL CONSTRUCTION ASSOCIATES
 LLC
 TEL: (954)444-8463
 DATE:
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE WITH 2006
 REVISIONS
 * WEST PALM BEACH AMENDMENTS ADMINISTRATIVE CODE
  
 REVIEW:
 SUBMITTALS:
 SUBMITTAL DRAWINGS (3.02)
 SUBMITTAL PARTIAL ROOFING PLAN (S.04)
 SUBMITTAL PANEL REINFORCING SPECS (S3.11) SUBMITTAL
 JOIST SHOP DRAWINGS (S.01)
 SUBMITTAL STEEL PANEL SHOP DRAWINGS
 SUBMITTAL ANCHOR BOLT, ROOF, PANEL EMBED DRAWINGS
 SUBMITTAL METAL DOOR,S FRAMES AND HARDWARE(8.02)
 SUBMITTAL OVERHEAD SECTIONAL DOORS (8.03) SUBMITTAL
 STUCCO & EFIS ACCESSORIES (9.01)

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2008-03-20 Cont ID  
Sent By shill Date 2008-03-20 Time 09:01 Rev Time 0.00
Received By shill Date 2008-03-20 Time 08:13 Sent To  
Notes
2008-03-20 09:28:38NOA 03-0501.06 WITH ENHANCED FASTENING CALCULATIONS
 SUBMITTED FOR ROOF (INFORMATIONAL ONLY)
  
 PROVISO
  
 AT RISK PERMIT (SHELL), CODE COMPLIANCE TO BE SHOWN FOR
 IMPACT FEES, EGRESS AND ACCESSIBILITY FOR TENANT
 BUILDOUTS

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2008-03-07 Cont ID  
Sent By shill Date 2008-03-07 Time 10:57 Rev Time 0.00
Received By shill Date 2008-03-07 Time 10:44 Sent To  
Notes
2008-03-07 10:58:30****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 3.FROM PREVIOUS LIST, REQUIRES THREE ORIGINAL
 ORIGINAL SIGNATURES, NOT COPIES.FBC1804.2.2, SOILS
 REPORT REQUIRED, FS471 REQUIRES SIGNED, SEALED, DATED
 ORIGINALS WHEN SUBMITTED FOR PUBLIC RECORD.ONE SHEET
 IN EACH REPORT IS AN ORIGINAL SIGNATURE, ONE SHEET IS A
 SEALED PHOTOCOPY, AND ONE SHEET IS AN UNSEALED
 PHOTOCOPY.PLEASE SIGN AND SEAL SHEETS WITH A
 SIGNATURE.
  
 7.PLEASE KEEP THE THREE SETS OF PRODUCT APPROVALS IN
 THE PERMIT PACKAGE.
  
 7C SKYLIGHTS, THE SKYLIGHT REPORTS ARE OK, PLANS NEED
 WELDING INFO FOR THE SKYLIGHT BASE TO THE BAR JOIST.I
 DO NOT SEE WHERE THIS HAS BEEN ADDRESSED IN THE PLAN
 AND IT WAS NOT REFERENCED IN THE RESPONSE LETTER.
  
 11.PLEASE KEEP ANCHORAGE OF EFIS MOLDING INFORMATION
 IN THE PERMIT PACKAGE.
  
 16.BEFORE A PERMIT TO CONSTRUCT MAY BE ISSUES, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY.THE PLANS MUST
 BE STAMPED AND THE RECEIPT ATTACHED TO THE APPLICATION.
 233-5025.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-01-15 Cont ID  
Sent By jwitmer Date 2008-01-15 Time 16:00 Rev Time 4.44
Received By jwitmer Date 2008-01-15 Time 16:00 Sent To  
Notes
2008-01-15 16:01:17BUILDING PLAN REVIEW
 PERMIT: 06110349
 ADD: 5720 PREMIER PARK DR. BLDG# 3
 CONT:GLOBAL CONSTRUCTION ASSOCIATES LLC
 TEL: (954)444-8463
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE WITH 2006
 REVISIONS
 * WEST PALM BEACH AMENDMENTS ADMINISTRATIVE CODE
  
 4THREVIEW- AS APERMIT APPLICATION!
 ACTION: DENIED
  
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE REMOVE & REPLACE ANY
 PAGES AS NECESSARY.
 A TRANSMITTAL LETTERLISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT BEFORE A PERMIT WILL BE ISSUED. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID.
  
 3) SEMI-COMPLIED, REQUIRES THREE "ORIGINAL"ORIGINAL
 SIGNATURES NOT COPIES!!!! AND RAISED EMBOSSED SEALED
 REPORTS. REPORTS SUPPLIED FROM JULY 17,2006 3RD
 REQUEST, SUBMITTED (3) REPORTS DATED MAY 21, 2004,
 STRUCTURAL SHEETS INDICATE A SOILS TEST WAS CONDUCTED
 BY NUTTING ENGINEERING, PROJECT# 14157.1, JULY 17,
 2006. PLEASE PROVIDE 3 ORIGINAL DOCUMENTS SIGNED AND
 SEALED.
 FL BLD CODE 1804.2.2 QUESTIONABLE SOILS, WHERE THE
 BEARINGCAPACITY IS NOT DEFINETLY KNOWN OR IS IN
 QUESTION. WHERE THE BEARING CAPACITY OF THE SOIL IS NOT
 DEFINITLY KNOWN OR IS IN QUESTION THE BUILDING OFFICIAL
 MAY REQUIRE EXPLORATIONS, TEST OR OTHER ADEQUATE PROOF
 AS TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDATIONS SUBMITTED
 TO VERIFY BEARING CAPACITY SHALL BE CERTIFIED BY A
 GEOTECHNICAL
 REPORT FROM A DESIGN PROFESSIONAL PROPERLY LICENSED IN
 THE STATE OF FLORIDA.
  
  
  
  
 4 -6 ) COMPLIED.
  
 7)FOURTHREQUEST,FL BLD CODE 1609.1.4:
 COMPONENTS & CLADDING, PROVIDE 2 COPIES(3 IF THRESHOLD
 OR RESIDENT INSPECTOR) OF PRODUCT TESTING REPORTS
 ,MISSING REPORTS ARE AS FOLLOWS:
 A) STOREFRONT WINDOWS REPORTS SUPPLIED FROM YKKWILL
 EITHER NEED ENGINERING CALCULATIONS OR THE DADE COUNTY
 REPORT. THE STATE COVER SHEET INDICATES IF ANCHOR
 CALCULATIONS HAVENOT BEEN VERIFIED BY A PE A 1/3RD
 DECREASE NEEDS TO BE TAKEN. ALSO HIGHLIGHT AS TO WHICH
 GLASS TYPE WILL BE INSTALLED IN THE FRAME FOR THE
 POSITIVE AND NEGATIVE PRESSURES TO BE USED.
 B) MULLIONS- UNDER STOREFRONT REPORT
 C) SKYLIGHTS- THE SKYLIGHTS REPORTS ARE OK, PLANS NEED
 WELDING INFO FOR THE SKYLIGHT BASE TO THE BARJOISTD)
 EXTERIOR GLAZED DOORSREPORTS SUPPLIED FROM YKKWILL
 EITHER NEED ENGINERING CALCULATIONS OR THE DADE COUNTY
 REPORT. THE STATE COVER SHEET INDICATES IF ANCHOR
 CALCULATIONS HAVENOT BEEN VERIFIED BY A PE A 1/3RD
 DECREASE NEEDS TO BE TAKEN. ALSO HIGHLIGHT AS TO WHICH
 GLASS TYPE WILL BE INSTALLED IN THE FRAME FOR THE
 POSITIVE AND NEGATIVE PRESSURES TO BE USED.
 E) EXTERIOR HOLLOW METAL DOORS-OK
 F) ROLL UP DOORS-OK
 G) LOUVERS- OK
 H) ROOFING ASSEMBLIES- THE REPORT FROM FEDERAL
 REFRENENCES THE WRONG NOA NUMBERAND THE AMOUNT OF PAGES
 FOUND IN THE REPORT.
  
 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1
 M) ABOVE GRADE SHALL MEET
 THE PROVISIONS OF THE SMALL MISSILE TEST.
  
 8-10) COMPLIED.
  
 11) BUILDING PROVISO: SHOP DRAWINGS TO BE SUBMITTED FOR
 ANCHORAGE OF EFIS MOLDINGS BEFORE START OF INSTALLATION
 WITH FASTENING INFORMATION.1406.2.2
  
 12-15) COMPLIED.
  
 16)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-11-01 Cont ID  
Sent By jwitmer Date 2007-11-01 Time 08:33 Rev Time 3.33
Received By jwitmer Date 2007-11-01 Time 08:33 Sent To  
Notes
2007-11-01 10:11:10BUILDING PLAN REVIEW
 PERMIT: 06110349
 ADD: 5720 PREMIER PARK DR. BLDG# 3
 CONT:GLOBAL CONSTRUCTION ASSOCIATES LLC
 TEL: (954)444-8463
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE WITH 2006
 REVISIONS
 * WEST PALM BEACH AMENDMENTS ADMINISTRATIVE CODE
  
 3RDREVIEW- AS APERMIT APPLICATION!
 ACTION: DENIED
  
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE REMOVE & REPLACE ANY
 PAGES AS NECESSARY.
 A TRANSMITTAL LETTERLISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT BEFORE A PERMIT WILL BE ISSUED. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID.
  
 3) SEMI-COMPLIED, REQUIRES THREE ORIGINAL SIGNED AND
 SEALED REPORTS FROM JULY 17,2006 3RD REQUEST, SUBMITTED
 (3) REPORTS DATED MAY 21, 2004, STRUCTURAL SHEETS
 INDICATE A SOILS TEST WAS CONDUCTED BY NUTTING
 ENGINEERING, PROJECT# 14157.1, JULY 17, 2006. PLEASE
 PROVIDE 3 ORIGINAL DOCUMENTS SIGNED AND SEALED.
 FL BLD CODE 1804.2.2 QUESTIONABLE SOILS, WHERE THE
 BEARINGCAPACITY IS NOT DEFINETLY KNOWN OR IS IN
 QUESTION. WHERE THE BEARING CAPACITY OF THE SOIL IS NOT
 DEFINITLY KNOWN OR IS IN QUESTION THE BUILDING OFFICIAL
 MAY REQUIRE EXPLORATIONS, TEST OR OTHER ADEQUATE PROOF
 AS TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDATIONS SUBMITTED
 TO VERIFY BEARING CAPACITY SHALL BE CERTIFIED BY A
 GEOTECHNICAL
 REPORT FROM A DESIGN PROFESSIONAL PROPERLY LICENSED IN
 THE STATE OF FLORIDA.
  
  
  
  
 4 A) FBC* 105.3RESIDENT INSPECTOR. SUBMIT INSPECTOR
 RESUME' AND LICENSE DOCUMENTS TO HAROLD PISKURA,
 DIRECTOR OF THE RESIDENT INSPECTOR PROGRAM.A RESIDENT
 INSPECTOR PROGRAM IS REQUIRED, ON THIS PROJECT, DUE TO
 ONE OR MORE OF THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQ FT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN
 OR METHODS OF CONSTRUCTION
  
 4B) SECOND REQUEST, SINCE THIS BUILDING WILL REQUIRE A
 RESIDENT INSPECTORSUBMITTALS(3) SETS OF PLANS,
 REPORTS, AND OR OTHER REQUIRED SUBMITTALS (PRODUCT
 APPROVALS) WILL BE REQUIRED FOR REVIEW.
 1) MISSING (1)SOILS REPORT LISTED ABOVE.
 2) LIGHTING POLES- ONLY 2 REPORT SUBMITTED, RAISED SEAL
 ILLEGIBLE, NOT EMBOSSED ENOUGH TO READ, MISSING THE
 PRINTED NAME OF ENGINEER IN TITLE BLOCK 61G15-23.002(2)
 FL. ADMIN. CODE. PLANS SIGNED & SEALED BY A
 PROFESSIONAL ENGINEER SHALL INCLUDE EITHER THE: NAME,
 ADDRESS AND LICENSE NUMBER OF THE ENGINEER OR, THE NAME
 AND LICENSE NUMBER OF THE ENGINEER AND THE NAME,
 ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS THROUGH WHICH THE ENGINEER IS
 PRACTICING (471.025 F.S. AND 471.023 F.S.).
  
 5-6 ) COMPLIED.
  
 7)THIRD REQUEST,FL BLD CODE 1609.1.4: COMPONENTS
 & CLADDING, PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT
 INSPECTOR) OF PRODUCT TESTING REPORTS ,MISSING REPORTS
 ARE AS FOLLOWS:
 A) STOREFRONT WINDOWS
 B) MULLIONS
 C) SKYLIGHTS
 D) EXTERIOR GLAZED DOORS
 E) EXTERIOR HOLLOW METAL DOORS
 F) ROLL UP DOORS
 G) LOUVERS
 H) ROOFING ASSEMBLIES
  
 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1
 M) ABOVE GRADE SHALL MEET
 THE PROVISIONS OF THE SMALL MISSILE TEST.
  
 8)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 9)WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 10) THIS SUBMITTAL DOESN'T INCORPORATE ANY ROOFING
 PRODUCT APPROVALS, HERE IS A LIST OF COMMON ISSUES THAT
 WILL FAIL A ROOFING REPORT SUBMITTAL:THIS ROOF IS
 MISSING OR NOT INCOMPLIANCE WITH THE FOLLOW
 ITEMS:
 ___ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF HEIGHT.
 ___ CONTRACTOR DID NOT INDICATE THE ROOF PITCH. ___
 CONTRACTOR FAILED TO INDICATE WHICH SYSTEM OR SUBSYSTEM
 WILL BE USED.
 ___ THE SYSTEM PROVIDED HAS A LOWPRESSURE FOR ZONE
 ___ .
 ___ THE SYSTEM PROVIDED STATES LIMITATION# 7, SHOULD
 THE FASTENERRESISTANCE BE LESS THAN THATREQUIRED,
 AS DETERMINED BY THE BUILDING OFFICIAL, A REVISED
 FASTENER SPACING, PREPAREDSIGNEDAND SEALED BY A
 FLORIDA REGISTERED PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF CONSULTANT MAY BE
 SUBMITTED.
 ___ THE SYSTEM PROVIDED INDICATES LIMITATION# 9, NO
 ENHANCED FASTENING ALLOWED.
  
 11) BUILDING PROVISO: SHOP DRAWINGS TO BE SUBMITTED FOR
 ANCHORAGE OF EFIS MOLDINGS BEFORE START OF INSTALLATION
 WITH FASTENING INFORMATION.1406.2.2
  
 12) COMPLIED.
  
 13) COMPLIED.
  
 14)COMPLIED.
  
 15) THIRD REQUEST, NOTE WITH THE PRODUCT APPROVALS NOT
 SUBMITTED THE ROLL UP DOORS MAY OR MAY NOT REQUIRE DOOR
 BUCKS AND ATTACHMENT.1714.5.4.2.
  
 16)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-06-28 Cont ID  
Sent By jwitmer Date 2007-06-28 Time 13:40 Rev Time 2.22
Received By jwitmer Date 2007-06-28 Time 13:40 Sent To  
Notes
2007-06-28 13:40:45PREMIER PARK BUILDING #3
  
  
 BUILDING PLAN REVIEW
 PERMIT: 06110349
 ADD: 5720 PREMIER PARK DR. BLDG# 3
 CONT:GLOBAL CONSTRUCTION ASSOCIATES LLC
 TEL: (954)444-8463
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE WITH 2006
 REVISIONS
 * WEST PALM BEACH AMENDMENTS ADMINISTRATIVE CODE
  
 1STREVIEW- AS APERMIT APPLICATION!
 ACTION: DENIED
  
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE REMOVE & REPLACE ANY
 PAGES AS NECESSARY.
 A TRANSMITTAL LETTERLISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT BEFORE A PERMIT WILL BE ISSUED. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID.
  
 3) 2ND REQUEST, STRUCTURAL SHEETS INDICATE A SOILS TEST
 WAS CONDUCTED BY NUTTING ENGINEERING, PROJECT# 14157.1,
 JULY 17, 2006. PLEASE PROVIDE 3 ORIGINAL DOCUMENTS
 SIGNED AND SEALED.
 FL BLD CODE 1804.2.2 QUESTIONABLE SOILS, WHERE THE
 BEARINGCAPACITY IS NOT DEFINETLY KNOWN OR IS IN
 QUESTION. WHERE THE BEARING CAPACITY OF THE SOIL IS NOT
 DEFINITLY KNOWN OR IS IN QUESTION THE BUILDING OFFICIAL
 MAY REQUIRE EXPLORATIONS, TEST OR OTHER ADEQUATE PROOF
 AS TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDATIONS SUBMITTED
 TO VERIFY BEARING CAPACITY SHALL BE CERTIFIED BY A
 GEOTECHNICAL
 REPORT FROM A DESIGN PROFESSIONAL PROPERLY LICENSED IN
 THE STATE OF FLORIDA.
  
  
  
  
 4 A) FBC* 105.3RESIDENT INSPECTOR. SUBMIT INSPECTOR
 RESUME' AND LICENSE DOCUMENTS TO HAROLD PISKURA,
 DIRECTOR OF THE RESIDENT INSPECTOR PROGRAM.A RESIDENT
 INSPECTOR PROGRAM IS REQUIRED, ON THIS PROJECT, DUE TO
 ONE OR MORE OF THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQ FT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN
 OR METHODS OF CONSTRUCTION
  
 4B) SECOND REQUEST, SINCE THIS BUILDING WILL REQUIRE A
 RESIDENT INSPECTORSUBMITTALS(3) SETS OF PLANS,
 REPORTS, AND OR OTHER REQUIRED SUBMITTALS (PRODUCT
 APPROVALS) WILL BE REQUIRED FOR REVIEW.
  
 5) SHEET A-0 CODE ANALYSIS:
  
 5A) SECOND REQUEST, CONSTRUCTION TYPE: PLANS INDICATE A
 BUILDING TYPE III-(UNPROTECTED)
 ( SPRINKLED) TO TAKE THE UNLIMITED AREA PROVISIONS IN
 507.2THE CODE REQUIRES THE BUILDINGS TO ?FIRE
 SPRINKLED?, REQUIRING A FIRE SPRINKLER PLAN.
  
 5B) COMPLIED.
  
 5C) NEW COMMENT: CODE ANALYSIS BLDG# 1 SEE UNLIMITED
 BLDG AREA 507.2 CORRECT THE 60 YARDS TO 60 FEET.
  
 5D) COMPLIED.
  
 5E)COMPLIED.
  
 5F) SECOND REQUEST,507.2 REQUIRES THE FIRE SPRINKLER
 PLANS FOR THE UNLIMITED AREA INCREASE! THE CODE
 ANALYSIS ALSO INDICATED THAT THIS IS TO BE A FIRE
 SPRINKLED BUILDING BUT NO FIRE SPRINKLER PLANS ,
 HYDRAULICS,FIRE PUMP OR FIRE PUMP CONTROLLER WERE
 SUBMITTED.FOR A BUILDING PERMIT TO BE ISSUED FOR
 MINIMUM PLAN REVIEW CRITERIA 106.3.51.1(4)* FIRE
 SPRINKLER PLANS ARE REQUIRED. 903.2.3 GROUP F-1.AN
 AUTOMATIC SPRINKLER SYSTEM SHALL BE PROVIDED THROUGHOUT
 ALL BUILDINGS CONTAINING A GROUP F-1 OCCUPANCY WHERE
 ONE OF THE FOLLOWING CONDITIONS EXISTS:
 1.WHERE A GROUP F-1 FIRE AREA EXCEEDS 12,000 SQUARE
 FEET (1115 M 2 ).
  
  
  
 6)COMPLIED.
  
 7)SECOND REQUEST,FL BLD CODE 1609.1.4: COMPONENTS
 & CLADDING, PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT
 INSPECTOR) OF PRODUCT TESTING REPORTS ,MISSING REPORTS
 ARE AS FOLLOWS:
 A) STOREFRONT WINDOWS
 B) MULLIONS
 C) SKYLIGHTS
 D) EXTERIOR GLAZED DOORS
 E) EXTERIOR HOLLOW METAL DOORS
 F) ROLL UP DOORS
 G) LOUVERS
 H) ROOFING ASSEMBLIES
  
 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1
 M) ABOVE GRADE SHALL MEET
 THE PROVISIONS OF THE SMALL MISSILE TEST.
  
 8)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 9)WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 10) THIS SUBMITTAL DOESN'T INCORPORATE ANY ROOFING
 PRODUCT APPROVALS, HERE IS A LIST OF COMMON ISSUES THAT
 WILL FAIL A ROOFING REPORT SUBMITTAL:THIS ROOF IS
 MISSING OR NOT INCOMPLIANCE WITH THE FOLLOW
 ITEMS:
 ___ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF HEIGHT.
 ___ CONTRACTOR DID NOT INDICATE THE ROOF PITCH. ___
 CONTRACTOR FAILED TO INDICATE WHICH SYSTEM OR SUBSYSTEM
 WILL BE USED.
 ___ THE SYSTEM PROVIDED HAS A LOWPRESSURE FOR ZONE
 ___ .
 ___ THE SYSTEM PROVIDED STATES LIMITATION# 7, SHOULD
 THE FASTENERRESISTANCE BE LESS THAN THATREQUIRED,
 AS DETERMINED BY THE BUILDING OFFICIAL, A REVISED
 FASTENER SPACING, PREPAREDSIGNEDAND SEALED BY A
 FLORIDA REGISTERED PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF CONSULTANT MAY BE
 SUBMITTED.
 ___ THE SYSTEM PROVIDED INDICATES LIMITATION# 9, NO
 ENHANCED FASTENING ALLOWED.
  
 11) 2ND REQUEST,SHEET A-8 PRECAST MOLDING DETAIL IS
 MISSING DETAIL REFERENCE NUMBER.
 FOUND ON SHEET A-15 DETAIL # 7. PLEASE PROVIDE
 CALCULATIONS WITH SAFETY FACTOR FOR THE SECURING THIS
 WEIGHT IN THIS MANNER.106.1.2*ADDITIONAL INFORMATION
 REQUIRED.
  
 12) COMPLIED.
  
 13) COMPLIED.
  
 14)SHEET A-14 DETAILS 8& 9 INDICATE THE USE OF WIRE
 LATH ON SOFFITS AND CEILING APPLICATIONS. THE PLAN NOW
 DECLARES THAT HIGH RIB LATH WILL BE FASTENED TO DENSE
 BOARD, HOW?NOTE,HI-RIB LATH 3/8? 3.4 LB/YD2 CAN
 SPAN 24?, EACH RIB WOULD REQUIRE FASTENING AS PER ASTM
 1063C TABLE 3.
  
 15) SECOND REQUEST, NOTE WITH THE PRODUCT APPROVALS NOT
 SUBMITTED THE ROLL UP DOORS MAY OR MAY NOT REQUIRE DOOR
 BUCKS AND ATTACHMENT.
  
 16)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PREMIER PK BLD 3 REVIEW 1.DOC

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-12-11 Cont ID  
Sent By jwitmer Date 2006-12-11 Time 14:31 Rev Time 0.00
Received By jwitmer Date 2006-12-11 Time 14:32 Sent To  
Notes
2006-12-11 14:40:55BUILDING PLAN REVIEW
 PERMIT: 06110349
 ADD: 5720 PREMIER PARK DR. BLDG# 3
 CONT: "PLAN REVIEW"
 TEL: (954)214-4039 ANDY PRIBY
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3)FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 4 A) FBC* 105.3RESIDENT INSPECTOR.
 SUBMIT INSPECTOR RESUME' AND LICENSE
 DOCUMENTS TO HAROLD PISKURA, DIRECTOR OF
 THE RESIDENT INSPECTOR PROGRAM.A
 RESIDENT INSPECTOR PROGRAM IS REQUIRED,
 ON THIS PROJECT, DUE TO ONE OR MORE OF
 THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQFT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN
 OR METHODS OF CONSTRUCTION
  
 4B) SINCE THIS BUILDING WILL REQUIRE A RESIDENT
 INSPECTOR
 (3) SETS OF PLANS, REPORTS, AND OR OTHER REQUIRED
 SUBMITTALS
 WILL BE REQUIRED FOR REVIEW.
  
 5) SHEET A-0 CODE ANALYSIS:
  
 5A) CONSTRUCTION TYPE: PLANS INDICATE A BUILDING TYPE
 IV(UNPROTECTED)
 THIS TERMINOLGY IS FROM THE 2001 FBC PLEASE CORRECT,
 UNDER THE CORRENT
 CODE THIS BUILDING IS TO BE BUILT AS "HEAVY TIMBER"
 CONSTRUCTION.
  
 5B)IT APPEARS THAT THE CODE ANYLSIS IS A COMBINATION
 OF ZONING & BUILDING.
 PLEASE EXPLAIN WHY THE TOTAL BUILDING FOOTPRINT IS
 302,092 WHEREAS
 ON SHEET A-1 BUILDING NUMBER 1 INDICATES THE SQ FT AREA
 TO BE 119,291 SQ FT.
 ALSO FURTHER DOWN THE PAGE BUILDING # 1 INDICATES
 GROUND FLOOR AREA TO BE
 95,391 AND POSSIBLE MEZZANINE LEVEL OF 23,900 SQ. FT.
 FOR THE PURPOSE OF
 BUILDING PLANS EITHER YOU ARE GOING TO BUILD THE
 MEZZANINE LEVEL UNDER THIS PERMIT
 WHICH WILL INCLUDE THIS FIGURE, IF NOTTO BE BUILT
 UNDER THIS PERMIT DO NOT INCLUDE IT.
  
 5C) IN EITHER CASE PLEASE IDENTIFY THE MINIMUM BUILDING
 TYPE AND IF IN TABLE 503
 THE PLANS ARE OVER THE ALLOWABLE SQUARE FOOTAGE,
 INDICATE ANY INCREASES
 TAKEN AND ALSO SHOW CALCULATIONS.
  
 5D) THE PERMIT APPLICATION IS BLANK WHERE THE
 DESCRIPTION OF PROJECT,
 OR WORK TO BE COVERED UNDER THIS PERMIT. FOR THE
 PURPOSES OF THIS REVIEW
 THIS BUILDING WILL BE CONSIDERED A SHELL BUILDING
 PERMIT. TENANT BUILD-OUTS TO BE UNDER
 SEPERATE PERMITS.
  
 5E) IS THIS SITE, ARE THE UNITS TO BE SOLD AS
 CONDOMINIUMS?
  
 5F) THE CODE ANALYSIS ALSO INDICATED THAT THIS IS TO BE
 A FIRE SPRINKLERED
 BUILDING BUT NO FIRE SPRINKLER PLANS , HYDROLICS,FIRE
 PUMP OR FIRE PUMP CONTROLLERE
 WERE SUBMITTED.FOR A BUILDING PERMIT TO BE ISSUED
 FORMINIMUM PLAN REVIEW CRITERIA
 106.3.51.1(4)* FIRE SPRINKLER PLANS ARE REQUIRED.
 903.2.3 GROUP F-1.
 AN AUTOMATIC SPRINKLER SYSTEM SHALL BE PROVIDED
 THROUGHOUT ALL BUILDINGS
 CONTAINING A GROUP F-1 OCCUPANCY WHERE ONE OF THE
 FOLLOWING CONDITIONS EXISTS:
 1.WHERE A GROUP F-1 FIRE AREA EXCEEDS 12,000 SQUARE
 FEET (1115 M 2 ).
  
 6)SHEET A-6:
  
 6A) SHEET A-6 , DISCREPANCY,
 THE ELEVATIONS INDICATES DO NOT INDICATE THE PRESSURE
 ZONES.
  
 7)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) STOREFRONT WINDOWS
 B) MULLIONS
 C) SKYLIGHTS
 D) EXTERIOR GLAZED DOORS
 E) EXTERIOR HOLLOW METAL DOORS
 F) ROLL UP DOORS
 G) LOUVERS
 H) EFIS SYSTEMS
 I) ROOFING ASSEMBLIES
  
 1609.1.4 PROTECTION OF OPENINGS.
 IN WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IN THE LOWER 60 FEET (18.3 M) IN
 BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED
 OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IS IMPACT RESISTANT OR PROTECTED WITH AN
 IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND
 ASTM E 1996, OR MIAMI-DADE TAS 201, 202
 AND 203 REFERENCED THEREIN AS FOLLOWS:
 1.GLAZED OPENINGS LOCATED WITHIN 30
 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN
 30 FEET (9.1 M) ABOVE GRADE SHALL MEET
 THE PROVISIONS OF THE SMALL MISSILE
 TEST.
  
 8)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 9)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 10) THIS SUBMITTAL DOESN'T INCORORATE ANY ROOFING
 PRODUCT APPROVALS,
 HERE IS A LIST OF COMMON ISSUES THAT WILL FAIL A
 ROOFING REPORT SUBMITTAL:
 THIS ROOF IS MISSING OR NOT INCOMPLIANCE WITH THE
 FOLLOW ITEMS:
  
 ___ CONTRACTOR DID NOT PROVIDE THE MEAN
  
 ROOF HEIGHT.
  
 ___ CONTRACTOR DID NOT INDICATE THE ROOF
 PITCH.
  
 ___ CONTRACTOR FAILED TO INDICATE WHICH
 SYSTEM OR SUBSYSTEM WILL BE USED.
  
 ___ THE SYSTEM PROVIDED HAS A LOW
 PRESSURE FOR ZONE ___ .
  
 ___ THE SYSTEM PROVIDED STATES
 LIMITATION# 7, SHOULD THE FASTENER
 RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE
 BUILDING OFFICIAL, A REVISED
 FASTENER SPACING, PREPARED , SIGNED
 AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
  
 ___THE SYSTEM PROVIDED INDICATES
 LIMITATION# 9, NO ENHANCED
 FASTENING ALLOWED.
  
  
 11) SHEET A-8 PRECAST MOULDING DETAIL IS MISSING DETAIL
 REFRENCE NUMBER.
 FOUND ON SHEET A-15 DETAIL # 7. PLEASE PROVIDE
 CALCULATIONS WITH SAFETY
 FACTOR FOR THE SECURING THIS WEIGHT IN THIS
 MANNER.106.1.2*ADDITIONAL INFORMATION REQUIRED.
  
 12)SHEET A-11 DETAIL # 3 INDICATES THE FIRE PUMP ROOM
 TO ALSO BE USED AS ASTORAGE ROOM?
  
 13) SHEET A-11 VARIOUS DETAILS INDICATE THE TRIANGLE
 AREA CREATED BY THE RISER AND TREAD,
 1012.3 LIMITS THIS AREA THA A 6"SPHERE CAN NOT PASS
 THROUGH. THE WORDING ON THE
 PLAN IS NOT CLEAR WHAT THE 6" IS FOR.
  
 14)SHEET A-14 DEPENDING ON THE BUILDING TYPE TO BE
 DECLAIRED, THE PLYOOD IN THE EXTERIOR WALLS MAY BE OF
 CONCERN. TABLE 601 &602.
  
 15)NOTE WITH THE PRODUCT APPROVALS NOT SUBMITTED THE
 ROLL UP DOORS MAY OR MAY NOT REQUIRE DOOR BUCKS AND
 ATTACHMENT.
  
 16)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-01-31 Cont ID  
Sent By dpalmer Date 2008-01-31 Time 17:29 Rev Time 0.00
Received By dpalmer Date 2008-01-31 Time 17:29 Sent To  
Notes
2008-01-31 17:30:25 
 ** ELECTRICAL PLANS STAMPED.
  
 FIRE REVIEWER STILL NEEDS TO STAMP PLANS AS STATED ON
 PREVIOUS PASSED REVIEW.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-12-23 Cont ID  
Sent By dpalmer Date 2007-12-23 Time 19:29 Rev Time 0.00
Received By dpalmer Date 2007-12-23 Time 19:29 Sent To  
Notes
2007-12-23 19:30:092007-12-23 19:30:09
  
 ** DENIED4TH REVIEW **
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
  
 1) NOTE: PLEASE KNOW A COMPLETE REVIEW OF ENERGY
 CALCULATIONS CAN NOT BE DONE AT THIS TIME AS SHEETS
 E1.1A, AND E1.2 DOES NOT CORRELATE.
 PLEASE SEE FIXTURES ON E1.1A FOR PARKING LOT SHOW
 DOUBLE FIXTURES ON WEST SIDE HOWEVER THE FIXTURES ON
 WEST SIDE OF E1.2 ARE ALL SINGLE FIXTURES.
 PLEASE SEE E1.1A AS THE FIXTURES ON THE NORTH, EAST AND
 SOUTH SIDES WHICH ARE SHOWN ON E1.2 ARE MISSING? CAN
 NOT CONFIRM LIGHTING ON THE INPUT DATA REPORT. PLEASE
 SEE THE LIGHTING FOR INTERIOR LIGHTING NEEDS TO BE
 ADJUSTED TO MATCH WITH PLANS.
 PLEASE SEE THE AMOUNT OF INTERIOR 64 WATT FIXTURES IS
 NOT THE SAME IN THE IDR AS SHOWN ON PLANS. (MISSING
 SEPARATE ROOMS).
 ** PLEASE CLARIFY THE 150 500W FIXTURES. IS THIS AN
 ASSUMPTION FOR FUTURE LIGHTS?
 IF SO, HOW IS IT THAT NO ASSUMPTION WAS FIGURED FOR
 BUILDING #1 FOR FUTURE?
 THIS WAS NOTED ON PREVIOUS REVIEW AND RESPONSE ONLY
 STATES TO *SEE REVISED ENERGY CALCULATIONS*. PLEASE SEE
 THE SQ FT DOES NOT CORRELATE WITH ARCHITECTURAL PLANS
 AND PLEASE SEE THE OCCUPANCY SHALL BE STATED AS ON
 ARCHITECTURAL SHEETS FOR F-1. THIS IS NOT RETAIL AS
 SHOWN ON COVER SHEET OF ENERGY CALCULATIONS.
 13-415.2, 13-415.1.B.
 **PLEASE PROVIDE CORRECTED SHEETS FOR COORDINATION OF
 SITE AND UPDATE ENERGY CALCULATIONS.
 **PLEASE ALSO BE SURE WHEN RE-SUBMITTING PLANS THE
 OWNER AGENT IS SIGNED ON CERTIFICATION SHEET.
 13-101.1.1.1
 ** PLEASE KNOW AS THE FIXTURES FOR SITE ARE NOT
 CONFIRMED, CIRCUITING, LOADS AND PANEL SCHEDULES CAN
 NOT BE CONFIRMED AT THIS TIME.
  
  
 ** AS GONE OVER IN MEETING BEFORE PLANS WERE
 RESUBMITTED, PLEASE BE SURE ALL LIGHTING ON PLANS IS
 PLACED AND FIGURED INTO THE ENERGY CALCULATIONS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-10-15 Cont ID  
Sent By dpalmer Date 2007-10-15 Time 09:14 Rev Time 0.00
Received By dpalmer Date 2007-10-14 Time 15:20 Sent To  
Notes
2007-10-15 09:14:432007-10-15 09:14:43
  
 **** DENIED 3RD REVIEW****
  
 ** PLEASE KNOW THIS IS THE SECOND REVIEW UNDER PERMIT
 APPLICATION AND THE THIRD REVIEW TOTAL.
 ** PLEASE SEE THERE ARE STILL SEVERAL COMMENTS FROM THE
 PREVIOUS TWO REVIEWS WHICH NEED TO BE ADDRESSED.
  
  
 1) NOTE: PLEASE SEE THE TWO PREVIOUS REVIEWS REQUESTED
 AND GAVE ALL CODES RELEVANT TO THE MINIMUM DESIGN TO BE
 PLACED ON PLANS. NFPA-20 2003 IS RELEVANT TO PROJECT
 AND WAS NOT PLACED ON PLANS WITH OTHER RELEVANT CODES.
 PLEASE ADD TO SHEETS FOR ELECTRICAL AND FORWARD TO
 ARCHITECT OF RECORD.
  
 2) NOTE: PLEASE SEE BOTH PREVIOUS REVIEWS WITH RESPECT
 TO FBC CHAPTER 13.
 PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED STILL DO
 NOT CORRELATE WITH PLANS.
 PLEASE SEE THE NUMBER OF FIXTURES DOES NOT CORRELATE.
 PLEASE SEE THE METHOD OF CONTROLS.
 PLEASE SEE THE WATTAGE OF FIXTURES DOES NOT CORRELATE.
 *FOR EXAMPLE: SEE THE INPUT DATA REPORT WHICH HAS
 500WATT FIXTURES FOR INTERIOR FIXTURES, YET THE FIXTURE
 LEGEND DOES NOT INDICATE ANY FIXTURES WITH THIS SAME
 WATTAGE, IN FACT THE THERE ARE SEVERAL OTHER WATTAGES
 NONE OF WHICH ARE ON THE INPUT DATA REPORT.
 PLEASE SEE TYPE OF BUILDING NEEDS TO BE VERIFIED AS
 THIS IS NOT RETAIL.
 PLEASE SEE THE EXTERIOR LIGHTING DOES NOT CORRELATE
 WITH PLANS AS THE INPUT DATA REPORT CONTAINS NO
 FIXTURES FOR EXTERIOR LIGHTING. HOW IS THIS POSSIBLE
 WHEN THE PLANS CONTAIN DOZENS OF FIXTURES??? PLEASE BE
 SURE THE ADDRESS IS LISTED ON CALCULATIONS. PLEASE SEE
 13-415.1.B, 13-415.2
  
 3) NOTE: PLEASE SEE METHOD OF CONTROLS FOR LIGHTING IS
 STILL NOT COMPLETE PER 13-415.1.ABC.1.1, .1.2. PLEASE
 OVER RIDE SWITCH LOCATIONS ARE NOT SHOWN ON PLANS AS
 REQUIRED FOR THE OCCUPANT ENTERING A SPACE AND BEING
 ABLE TO SEE THE LIGHTING IN WHICH IS BEING OVER
 RIDDEN.
 PLEASE SEE THERE ARE STILL STANDARD DEVICES SHOWN ON
 PLANS.
 PLEASE SEE NO TIME SCHEDULING, AND NO MAXIMUM TIMES ON
 OVER RIDES ARE SHOWN.
 NO ZONES, NO LAYOUTS ETC
 PLEASE SEE THE PREVIOUS TWO REVIEW NOTES BELOW:
  
 (REVIEW #2)
 **PREVIOUS REVIEW NOTES**
 PLEASE SEE FBC 2004 CHAPTER 13. THIS IS THE SAME
 COMMENT AS PREVIOUS REVIEW. PLEASE SEE THE VERSION AS
 SUBMITTED DOES NOT COMPLY WITH THE NEW CODE AS OF
 DECEMBER 8TH, 2006.
 PLEASE SEE AS THIS IS MENTIONED AS A SHELL BUILDING,
 PLEASE SEE METHOD.
 PLEASE SEE METHOD OF CONTROL STILL MENTIONS MANUAL
 ON/OFF WHICH IS NOT POSSIBLE WHEN AUTOMATED MEANS IS
 REQUIRED.
 PLEASE SEE MISSING OVER RIDE CONTROLS AT THE POINT OF
 ENTRANCE BY WAY OF CHOSEN DEVICES SO THE OCCUPANT CAN
 SEE THE LIGHTING WHICH IS BEING CONTROLLED. IF OS TYPE
 DEVICES ARE GOING TO BE INSTALLED FOR COVERAGE, PLEASE
 SHOW LOCATIONS, TYPE OF DEVICES AND MAXIMUM TIMES ON
 OVER RIDES
 PLEASE SEE SEPARATE SPACES WHICH ONLY INDICATE STANDARD
 SWITCHES.
 PLEASE SEE INTERIOR LIGHTING WHICH DOES NOT SHOW ANY
 AUTOMATED CONTROLS.
 PLEASE SEE ZONING NOT SHOWN FOR LARGER SPACES. PLEASE
 SEE ENERGY CALCULATIONS DO NOT INCLUDE ANY EXTERIOR
 LIGHTING AS PLANS DO.
 PLEASE BE SURE OWNER AGENT SIGNS ALL THREE COPIES.
 PLEASE SEE THE ADDRESS SHALL BE SPECIFIC ON
 CALCULATIONS.
 PLEASE SEE PREVIOUS REVIEW NOTES BELOW.
 PLEASE SEE FBC CHAPTER 13.
  
 (REVIEW #1)
 ** PREVIOUS NOTES**
 PLEASE SEE ENERGY CALCULATIONS WHICH INDICATE "MANUAL"
 FOR THE MEANS OF CONTROL FOR LIGHTING. PLEASE SEE
 ENERGY CALCULATIONS WHICH MENTIONS "NONE ENTERED" FOR
 EXTERIOR LIGHTING, HOWEVER PLANS DO INDICATE THIS.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE SEE
 13-415.1.AB.1, 13-415.2.ABC.1.
 PLEASE SEE SOME OF THE INTERIOR LIGHTS ARE BEING SHOWN
 CIRCUITED THROUGH THE LIGHTING CONTROL PANELS AND NOTED
 AS EXTERIOR LIGHTS WHEN THESE ARE INTERIOR FIXTURES.
 PLEASE SEE ALL AREAS WHICH CONTAIN FLOOR TO CEILING
 HEIGHT PARTITIONS SHALL ALSO CONTAIN LIGHTING CONTROL
 BY ONE OF THE MEANS AS STATED IN THE CODE. THIS OFFICE
 DOES NOT REQUIRE ONE DESIGN OVER ANOTHER.
 PLEASE SEE MORE THAN OPTION IS AVAILABLE. PLEASE BE
 SURE TO CORRELATE CIRCUITING AS AN EXAMPLE OF CIRCUIT
 "3HP-5". ON THE LIGHTING CONTROL PANEL IS SHOWS THIS
 CIRCUIT AS FEEDING EXTERIOR LIGHTS, YET ON PLANS THIS
 IS THE CIRCUIT WHICH FEEDS THE INTERIOR LIGHTS. PLEASE
 ALSO SEE THAT ALL EMERGENCY AND EXIT LIGHTS SHALL BE
 SHOWN IN DETAIL WIRED ON THE LINE SIDE OF ANY LIGHTING
 CONTROL PANEL. (700.12E).
  
  
 4) NOTE: PLEASE SEE THE LIGHTING LEVELS STILL DO NOT
 COMPLY WITH THE MINIMUM LEVELS AS REQUIRED FOR
 EXIT/EXIT DISCHARGE PER NFPA-101 7.8.1.3AND 7.9.2.2.
 PLEASE SEE PHOTO-METRICS INDICATE FOR NORMAL OR
 EMERGENCY FOR STAIRS LEADING TO THE PUBLIC RIGHT OF WAY
 HOWEVER THE LEVELS UNDER NORMAL ARE NOT MEETING THE
 MINIMUM OF 10FT CANDLES ON SEVERAL STAIRS. PLEASE ALSO
 SEE THE DESIGNATION OF STAIR #5 NORMAL AND EMERGENCY IS
 MISSING.
  
 5) NOTE: AS REQUESTED ON THE TWO PREVIOUS REVIEWS,
 PLEASE COMPLETE ALL INFORMATION ON PLANS FOR FIRE PUMP,
 FIRE PUMP CONTROLLER ETC.
 .
 THE RESPONSE LETTER MENTIONS THIS WILL BE *DONE BY THE
 FIRE SPRINKLER CONTRACTOR*
 SOME CUT SHEETS WERE SUBMITTED HOWEVER NOT ALL.
 AS STATED CLEARLY ON THE TWO PREVIOUS REVIEWS THIS
 INFORMATION IS REQUIRED FOR *MINIMUM* CODE COMPLIANCE
 FOR THE BASE BUILDING AND ALL INFORMATION SHALL BE
 SUBMITTED UNDER THE BASE BUILDING PERMIT APPLICATION.
 THIS IS IRRELEVANT OF THE SEPARATE PERMIT REQUIRED FOR
 FIRE SPRINKLER AT A LATER DATE.
 PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT SHEETS. PLEASE
 COMPLETE INFORMATION ON PLANS.
 NEC 695, NFPA-20 CHAPTER 6, 7 ETC
 CODES SECTIONS GIVEN BELOW FROM PREVIOUS REVIEWS REMAIN
 THE SAME.
  
 **PREVIOUS REVIEW #2 NOTE:
 AS NOTED ON PREVIOUS REVIEW. PLEASE COMPLETE ALL
 INFORMATION ON PLANS AND PLEASE SUBMIT ALL SPECS/CUT
 SHEETS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT THE MANUFACTURE SPEC/CUT SHEETS FOR THE
 FIRE PUMP AND FIRE PUMP CONTROLLER.THIS IS REQUIRED
 UNDER THE BASE BUILDING PLANS FOR REVIEW OF CODE
 COMPLIANCE FOR THE BUILDINGS ELECTRICAL SYSTEM AND
 FEEDS TO THIS PUMP. PLEASE KNOW EVEN THOUGH THE FIRE
 SPRINKLER SYSTEM IS UNDER A SEPARATE PERMIT. PLEASE SEE
 NFPA-20 2003, PLEASE SEE 9.3, 9.3.2.2 ALL SECTIONS
 FOLLOWING. PLEASE SEE WHERE LOCKED ROTOR CURRENT SHALL
 BE MARKED, DISCONNECTING MEANS, ISOLATING SWITCHES ETC
 SHALL BE SHOWN WITH PLANS AND SPECS SHEETS SUBMITTED.
 PLEASE ALSO SEE NEC 695.4(B)(1). PLEASE SEE CHAPTER 10
 OF NFPA-20 10.3.6, 10.4.2, 10.4.2.2 ETC.
 PLEASE KNOW THIS OFFICE IS UNABLE TO REVIEW FOR MANY
 CODE COMPLIANCE ITEMS AT THIS TIME AS THE ABOVE
 INFORMATION WAS NOT SUBMITTED.
 PLEASE SEE 110.3, AND 90.7.
 PLEASE SEE FBC ADMIN SECTION 106.1.2, 106.3.5.1.1PARA
 5
  
 6) NOTE:THIS NOTE FROM PREVIOUS REVIEW WILL REMAIN AS
 INFORMATION ON FIRE PUMP IS NOT COMPLETE AND
 VERIFICATION OF RISER CONDUCTORS ETC CAN NOT BE
 REVIEWED UNTIL ALL INFORMATION IS ON PLANS AND
 SUBMITTED.
 ** PREVIOUS REVIEW NOTE **
 PLEASE COMPLETE RISER FOR FIRE PUMP AS NOTED ABOVE FOR
 FEEDERS ETC.
 240.4, 310.16, 695, NFPA-20 CHAPTER 9
  
 7 NOTE:PLEASE SEE ACTUAL CALCULATIONS FOR LIGHT POLES
 WILL BE REVIEWED BY STRUCTURAL REVIEWER.
 ** NOTED FOR INFORMATION.
  
 8) NOTE: PLEASE SEE NOTICE TO FS 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE. AS THIS
 IS ONLY THE SECOND REVIEW UNDER PERMIT APPLICATION AS
 THE INITIAL REVIEW WAS UNDER *PLAN REVIEW*.
 PLEASE ADDRESS ALL COMMENTS.
  
 9) NOTE: PLEASE SEE ALL LANDSCAPE PLANS AS SUBMITTED
 ARE NOT SIGNED DATED OR SEALED BY THE RESPONSIBLE
 DESIGNER(S) OF RECORD.
 SEE ONLY SHEET 1 OF 6 WAS SIGNED, AND SEALED.
 FS 481.221
  
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES WHICH WILL
 AFFECT PLANS, SUBMITTED DOCUMENTS AND ELECTRICAL
 PLANS.
  
 ** IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-10-15 07:47:172007-10-15 07:47:17
  
 IN REVIEW
2007-10-14 16:02:302007-10-14 16:02:30
 REVIEW WILL CONTINUE ON 10/15, NOTES WILL FOLLOW ONCE
 COMPLETED.
 REVIEW WILL BE GOING INTO A *F* STATUS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-06-10 Cont ID  
Sent By dpalmer Date 2007-06-10 Time 10:31 Rev Time 0.00
Received By dpalmer Date 2007-06-10 Time 09:22 Sent To  
Notes
2007-06-10 10:32:03**** UNSAT 2ND REVIEW****
  
 ** PLANS NOW SUBMITTED FOR PERMIT. THIS IS THE FIRST
 REVIEW UNDER PERMIT.
 PLEASE SEE THERE ARE COMMENTS FROM PREVIOUS REVIEW
 UNDER *PLAN REVIEW* WHICH STILL NEED TO BE ADDRESSED
 ALONG WITH SOME NEW COMMENTS.
 ** PLEASE KNOW AS THERE ARE ITEMS NOT YET SUBMITTED IN
 DESIGN OR INFORMATION PROVIDED FOR CODE COMPLIANCE
 REVIEW, THERE MAY BE NEW COMMENTS ON THE FOLLOWING
 REVIEW WHICH CAN NOT YET BE MADE.
  
 1) NOTE: PLEASE SEE THE PLANS SUBMITTED CONTAIN STAMPS
 FROM ANOTHER BUILDING DEPARTMENT AND MUNICIPALITY WHICH
 IS NOT PERMITTED. PLEASE KNOW ALL NEW SHEETS WILL BE
 REQUIRED TO BE SUBMITTED.
 PLEASE SEE SOME SHEETS EVEN CONTAIN SIGN OFFS FROM THAT
 SAME JURISDICTION ALTHOUGH PLANS INDICATE WORK IN THE
 CITY OF WEST PALM BEACH?
  
 2) NOTE: PLEASE SEE THE PREVIOUS REVIEW AS STATED
 REQUESTS FOR ALL OLD/VOIDED SHEETS TO BE COMPLETELY
 REMOVED FROM SETS AND ONLY TO INSERT NEW REVISED SHEETS
 INTO THE COMPLETED SETS FOR REVIEW AND STAMPING. PLEASE
 SEE SETS STILL CONTAIN OLD SHEETS, PLEASE REMOVE.
 PLEASE SEE COMMENT ABOVE FOR NEW SHEETS NEEDED.
  
 3) NOTE: PLEASE SEE BUILDING REVIEW COMMENTS FOR
 *INITIALS* BEING USED IN LIEU OF ARCHITECT SIGNATURE.
 PLEASE SEE FS 481.221.
 A LETTER FOR SIGNATURE VERIFICATION WILL BE REQUIRED.
 THIS IS ONLY BEING NOTED BY THIS REVIEWER AT THIS TIME
 FOR INFORMATIONAL PURPOSE. OTHER SHEETS ARE SIGNED.
  
 4) NOTE: PLEASE SEE PREVIOUS NOTES FOR CODE TO BE
 STATED ON PLANS. PLEASE SEE MOST WERE DONE, HOWEVER
 PLEASE SEE THE FOLLOWING.
 2004 FBC W/2006 REVISIONS.
 2003 NFPA-20
  
 5) NOTE: PLEASE SEE FBC 2004 CHAPTER 13. THIS IS THE
 SAME COMMENT AS PREVIOUS REVIEW. PLEASE SEE THE VERSION
 AS SUBMITTED DOES NOT COMPLY WITH THE NEW CODE AS OF
 DECEMBER 8TH, 2006.
 PLEASE SEE AS THIS IS MENTIONED AS A SHELL BUILDING,
 PLEASE SEE METHOD.
 PLEASE SEE METHOD OF CONTROL STILL MENTIONS MANUAL
 ON/OFF WHICH IS NOT POSSIBLE WHEN AUTOMATED MEANS IS
 REQUIRED.
 PLEASE SEE MISSING OVER RIDE CONTROLS AT THE POINT OF
 ENTRANCE BY WAY OF CHOSEN DEVICES SO THE OCCUPANT CAN
 SEE THE LIGHTING WHICH IS BEING CONTROLLED. IF OS TYPE
 DEVICES ARE GOING TO BE INSTALLED FOR COVERAGE, PLEASE
 SHOW LOCATIONS, TYPE OF DEVICES AND MAXIMUM TIMES ON
 OVER RIDES
 PLEASE SEE SEPARATE SPACES WHICH ONLY INDICATE STANDARD
 SWITCHES.
 PLEASE SEE INTERIOR LIGHTING WHICH DOES NOT SHOW ANY
 AUTOMATED CONTROLS.
 PLEASE SEE ZONING NOT SHOWN FOR LARGER SPACES. PLEASE
 SEE ENERGY CALCULATIONS DO NOT INCLUDE ANY EXTERIOR
 LIGHTING AS PLANS DO.
 PLEASE BE SURE OWNER AGENT SIGNS ALL THREE COPIES.
 PLEASE SEE THE ADDRESS SHALL BE SPECIFIC ON
 CALCULATIONS.
 PLEASE SEE PREVIOUS REVIEW NOTES BELOW.
 PLEASE SEE FBC CHAPTER 13.
 ** PREVIOUS NOTES**
 PLEASE SEE ENERGY CALCULATIONS WHICH INDICATE "MANUAL"
 FOR THE MEANS OF CONTROL FOR LIGHTING. PLEASE SEE
 ENERGY CALCULATIONS WHICH MENTIONS "NONE ENTERED" FOR
 EXTERIOR LIGHTING, HOWEVER PLANS DO INDICATE THIS.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE SEE
 13-415.1.AB.1, 13-415.2.ABC.1.
 PLEASE SEE SOME OF THE INTERIOR LIGHTS ARE BEING SHOWN
 CIRCUITED THROUGH THE LIGHTING CONTROL PANELS AND NOTED
 AS EXTERIOR LIGHTS WHEN THESE ARE INTERIOR FIXTURES.
 PLEASE SEE ALL AREAS WHICH CONTAIN FLOOR TO CEILING
 HEIGHT PARTITIONS SHALL ALSO CONTAIN LIGHTING CONTROL
 BY ONE OF THE MEANS AS STATED IN THE CODE. THIS OFFICE
 DOES NOT REQUIRE ONE DESIGN OVER ANOTHER.
 PLEASE SEE MORE THAN OPTION IS AVAILABLE. PLEASE BE
 SURE TO CORRELATE CIRCUITING AS AN EXAMPLE OF CIRCUIT
 "3HP-5". ON THE LIGHTING CONTROL PANEL IS SHOWS THIS
 CIRCUIT AS FEEDING EXTERIOR LIGHTS, YET ON PLANS THIS
 IS THE CIRCUIT WHICH FEEDS THE INTERIOR LIGHTS. PLEASE
 ALSO SEE THAT ALL EMERGENCY AND EXIT LIGHTS SHALL BE
 SHOWN IN DETAIL WIRED ON THE LINE SIDE OF ANY LIGHTING
 CONTROL PANEL. (700.12E).
  
  
 6) NOTE: PLEASE SEE NFPA-101 7.8 AND 7.9. PLEASE SEE NO
 PHOTO-METRICS INDICATE FOR NORMAL OR EMERGENCY FOR
 STAIRS LEADING TO THE PUBLIC RIGHT OF WAY.
 PLEASE SEE PHOTO-METRICS SHOULD INDICATE LEVELS UNDER
 NORMAL/EMERGENCY ON FLAT EGRESS PATHS (SAME FOR BOTH
 CONDITIONS).
 ** NOTES FROM PREVIOUS REVIEW**
 PLEASE SEE THAT MINIMUM BATTERY BACK UP LIGHTS OF SOME
 KIND WILL BE REQUIRED FOR EGRESS AREAS WHICH INCLUDE
 EXTERIOR STAIRS TO THE PUBLIC RIGHT OF WAY. PLEASE SEE
 MINIMUM FOOT CANDLES UNDER NORMAL POWER AND MINIMUM
 FOOT CANDLES REQUIRED UNDER EMERGENCY POWER. 7.8.1.3,
 7.9.2.2. PLEASE KNOW THESE LIGHTING LEVELS SHOWN ON
 PHOTO-METRICS WILL BE REQUIRED ON ELECTRICAL PLANS FOR
 REVIEW WHETHER OR NOT THESE COMMENTS ARE MADE BY FIRE
 REVIEW.
  
 7) NOTE:AS NOTED ON PREVIOUS REVIEW, NOT ALL REQUIRED
 SIGNAGE OR NOTES IS ON PLANS.
 ** PREVIOUS REVIEW NOTES** PLEASE SEE 230.2E WHICH
 SPEAKS OF SIGNAGE REQUIRED FOR ALL SERVICE FEEDING ONE
 BUILDING. PLEASE SEE THAT RISER ONLY INDICATES 2-MAINS
 FOR THIS BUILDING, WHEN IN FACT THE MAIN FOR THE FIRE
 PUMP SHOULD ALSO BE NOTED AND LABELED. PLEASE ALSO
 PLACE NOTES ON RISER FOR SIGNAGE WHICH WILL BE REQUIRED
 FOR ALL MAINS AND SERVICE LOCATIONS. PLEASE SEE AS THE
 JOCKEY PUMP IS BEING FED FROM THE NORMAL HOUSE PANEL,
 THIS SHALL ALSO BE LABELED ACCORDINGLY. 695.4(B)3
  
 8) NOTE:AS NOTED ON PREVIOUS REVIEW. NO INFORMATION
 WAS SUBMITTED OR CHANGED ON PLANS.
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT THE MANUFACTURE SPEC/CUT SHEETS FOR THE
 FIRE PUMP AND FIRE PUMP CONTROLLER.THIS IS REQUIRED
 UNDER THE BASE BUILDING PLANS FOR REVIEW OF CODE
 COMPLIANCE FOR THE BUILDINGS ELECTRICAL SYSTEM AND
 FEEDS TO THIS PUMP. PLEASE KNOW EVEN THOUGH THE FIRE
 SPRINKLER SYSTEM IS UNDER A SEPARATE PERMIT. PLEASE SEE
 NFPA-20 2003, PLEASE SEE 9.3, 9.3.2.2 ALL SECTIONS
 FOLLOWING. PLEASE SEE WHERE LOCKED ROTOR CURRENT SHALL
 BE MARKED, DISCONNECTING MEANS, ISOLATING SWITCHES ETC
 SHALL BE SHOWN WITH PLANS AND SPECS SHEETS SUBMITTED.
 PLEASE ALSO SEE NEC 695.4(B)(1). PLEASE SEE CHAPTER 10
 OF NFPA-20 10.3.6, 10.4.2, 10.4.2.2 ETC.
 PLEASE KNOW THIS OFFICE IS UNABLE TO REVIEW FOR MANY
 CODE COMPLIANCE ITEMS AT THIS TIME AS THE ABOVE
 INFORMATION WAS NOT SUBMITTED.
 PLEASE SEE 110.3, AND 90.7.
 PLEASE SEE FBC ADMIN SECTION 106.1.2, 106.3.5.1.1PARA
 5
  
 9) NOTE:THIS NOTE FROM PREVIOUS REVIEW WILL REMAIN AS
 INFORMATION ON FIRE PUMP IS NOT COMPLETE AND
 VERIFICATION OF RISER CONDUCTORS ETC CAN NOT BE
 REVIEWED.
 ** PREVIOUS REVIEW NOTE **
 PLEASE COMPLETE RISER FOR FIRE PUMP AS NOTED ABOVE FOR
 FEEDERS ETC.
 240.4, 310.16, 695, NFPA-20 CHAPTER 9
  
 10) NOTE:SAME NOTE AS PREVIOUS REVIEW. NO INFORMATION
 SUBMITTED. AS THE POLES ON SITE ARE ALREADY BEING
 INSTALLED FOR OTHER BUILDINGS THIS INFORMATION SHOULD
 BE READILY AVAILABLE.
 ** PREVIOUS REVIEW NOTE**
 PLEASE SUBMIT OR INDICATE REQUIREMENTS FOR WIND LOAD
 CALCULATIONS FOR BUILDING REVIEW FOR FBC 2004 140MPH.
  
 11) NOTE: PLEASE CLARIFY WHY LEVELS FOR STROBES ON
 SCHEDULE ARE STILL BEING SHOWN AT 15CD?
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FBC 2004 CHAPTER 11, MORE SPECIFICALLY
 11-4.28, .1.2, AND .3(4). PLEASE ALSO SEE NFPA-72
 2002.
 THIS MAY OR MAY NOT CHANGE ACTUAL SHOWN UNITS. AS FOR
 MINIMUM CANDELA LEVELS SEE ABOVE AS NOTED.
  
  
 12) NOTE: PLEASE SEE THE RESPONSE LETTER AS SUBMITTED
 DOES NOT RESPOND TO ALL COMMENTS AS REVIEWED FROM
 PREVIOUS REVIEW.
 PLEASE SEE FIRE REVIEW AND BUILDING REVIEW COMMENTS
 WITH RESPECT TO THE FIRE SPRINKLERS AS THE BASE
 BUILDING PLANS ARE REQUIRED TO SHOW COMPLIANCE AND
 STATUTORY REQUIREMENTS AS WELL AS THE FBC.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
 ** PLEASE SEE POSSIBLE COMMENTS FROM OTHER TRADES WHICH
 MAY AFFECT ELECTRICAL PLANS OR DESIGN.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-12-04 Cont ID  
Sent By dpalmer Date 2006-12-04 Time 13:02 Rev Time 0.00
Received By dpalmer Date 2006-12-04 Time 12:57 Sent To  
Notes
2006-12-04 13:03:12**** UNSAT ****
  
 PERMIT # 06110349
 BUILDING # 3
 PLEASE KNOW THAT THE ADDRESS SHALL BE PLACE ON THE
 PLANS TITLE BLOCK AS IT HAS NOW BEEN DESIGNATED TO THIS
 BUILDING LOCATION.
  
 1) NOTE: PLEASE KNOW THAT THE PLANS HAVE ONLY BEEN
 SUBMITTED FOR "PLAN REVIEW" ONLY AND HAVE NOT BEEN
 SUBMITTED FOR PERMIT AT THIS TIME. PLEASE KNOW AS OF
 DECEMBER 8TH 2006 THE STATE OF FLORIDA WILL ADOPT THE
 NEW 2005 NATIONAL ELECTRICAL CODE NFPA-70. PLEASE ALSO
 KNOW THAT THE NEW 2006 REVISIONS TO THE 2004 FBC WILL
 ALSO GO INTO AFFECT.
 PLEASE KNOW THAT AS PERMITS HAVE NOT BEEN APPLIED FOR
 AT THIS TIME ALL NEW CODES AFTER THIS DATE WILL BE
 REQUIRED TO BE MET.
  
 2) NOTE: PLEASE BE SURE ALL THE FOLLOWING RELEVANT
 CODES ARE REFLECTED ON PLANS.
 2002 NFPA-70 ONLY IF A PERMIT IS APPLIED FOR BY THE 8TH
 OF DEC. PLEASE REFLECT THE 2005 NFPA-70, 2002 NFPA-72,
 2003 NFPA-101, 2003 NFPA-20 AND THE 2004 FBC.
  
 3) NOTE: PLEASE SEE FBC 2004 CHAPTER 13.
 PLEASE SEE ENERGY CALCULATIONS WHICH INDICATE "MANUAL"
 FOR THE MEANS OF CONTROL FOR LIGHTING. PLEASE SEE
 ENERGY CALCULATIONS WHICH MENTIONS "NONE ENTERED" FOR
 EXTERIOR LIGHTING, HOWEVER PLANS DO INDICATE THIS.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE SEE
 13-415.1.AB.1, 13-415.2.ABC.1.
 PLEASE SEE SOME OF THE INTERIOR LIGHTS ARE BEING SHOWN
 CIRCUITED THROUGH THE LIGHTING CONTROL PANELS AND NOTED
 AS EXTERIOR LIGHTS WHEN THESE ARE INTERIOR FIXTURES.
 PLEASE SEE ALL AREAS WHICH CONTAIN FLOOR TO CEILING
 HEIGHT PARTITIONS SHALL ALSO CONTAIN LIGHTING CONTROL
 BY ONE OF THE MEANS AS STATED IN THE CODE. THIS OFFICE
 DOES NOT REQUIRE ONE DESIGN OVER ANOTHER.
 PLEASE SEE MORE THAN OPTION IS AVAILABLE. PLEASE BE
 SURE TO CORRELATE CIRCUITING AS AN EXAMPLE OF CIRCUIT
 "3HP-5". ON THE LIGHTING CONTROL PANEL IS SHOWS THIS
 CIRCUIT AS FEEDING EXTERIOR LIGHTS, YET ON PLANS THIS
 IS THE CIRCUIT WHICH FEEDS THE INTERIOR LIGHTS. PLEASE
 ALSO SEE THAT ALL EMERGENCY AND EXIT LIGHTS SHALL BE
 SHOWN IN DETAIL WIRED ON THE LINE SIDE OF ANY LIGHTING
 CONTROL PANEL. (700.12E).
  
  
 4) NOTE: PLEASE SEE NFPA-101 7.8 AND 7.9, WHICH MAY
 ALSO BE PART OF THE FIRE REVIEWER COMMENTS WITH RESPECT
 TO A MINIMUM OF LIGHTING REQUIRED IN SPACE UNTIL SUCH
 TIME FOR TENANT BUILD OUT. PLEASE SEE THAT MINIMUM
 BATTERY BACK UP LIGHTS OF SOME KIND WILL BE REQUIRED
 FOR EGRESS AREAS WHICH INCLUDE EXTERIOR STAIRS TO THE
 PUBLIC RIGHT OF WAY. PLEASE SEE MINIMUM FOOT CANDLES
 UNDER NORMAL POWER AND MINIMUM FOOT CANDLES REQUIRED
 UNDER EMERGENCY POWER. 7.8.1.3, 7.9.2.2. PLEASE KNOW
 THESE LIGHTING LEVELS SHOWN ON PHOTO-METRICS WILL BE
 REQUIRED ON ELECTRICAL PLANS FOR REVIEW WHETHER OR NOT
 THESE COMMENTS ARE MADE BY FIRE REVIEW.
  
 5) NOTE: PLEASE SEE 230.2E WHICH SPEAKS OF SIGNAGE
 REQUIRED FOR ALL SERVICE FEEDING ONE BUILDING. PLEASE
 SEE THAT RISER ONLY INDICATES 2-MAINS FOR THIS
 BUILDING, WHEN IN FACT THE MAIN FOR THE FIRE PUMP
 SHOULD ALSO BE NOTED AND LABELED. PLEASE ALSO PLACE
 NOTES ON RISER FOR SIGNAGE WHICH WILL BE REQUIRED FOR
 ALL MAINS AND SERVICE LOCATIONS. PLEASE SEE AS THE
 JOCKEY PUMP IS BEING FED FROM THE NORMAL HOUSE PANEL,
 THIS SHALL ALSO BE LABELED ACCORDINGLY. 695.4(B)3
  
 6) NOTE: PLEASE SUBMIT THE MANUFACTURE SPEC/CUT SHEETS
 FOR THE FIRE PUMP AND FIRE PUMP CONTROLLER.THIS IS
 REQUIRED UNDER THE BASE BUILDING PLANS FOR REVIEW OF
 CODE COMPLIANCE FOR THE BUILDINGS ELECTRICAL SYSTEM AND
 FEEDS TO THIS PUMP. PLEASE KNOW EVEN THOUGH THE FIRE
 SPRINKLER SYSTEM IS UNDER A SEPARATE PERMIT. PLEASE SEE
 NFPA-20 2003, PLEASE SEE 9.3, 9.3.2.2 ALL SECTIONS
 FOLLOWING. PLEASE SEE WHERE LOCKED ROTOR CURRENT SHALL
 BE MARKED, DISCONNECTING MEANS, ISOLATING SWITCHES ETC
 SHALL BE SHOWN WITH PLANS AND SPECS SHEETS SUBMITTED.
 PLEASE ALSO SEE NEC 695.4(B)(1). PLEASE SEE CHAPTER 10
 OF NFPA-20 10.3.6, 10.4.2, 10.4.2.2 ETC.
 PLEASE KNOW THIS OFFICE IS UNABLE TO REVIEW FOR MANY
 CODE COMPLIANCE ITEMS AT THIS TIME AS THE ABOVE
 INFORMATION WAS NOT SUBMITTED.
 PLEASE SEE 110.3, AND 90.7.
 PLEASE SEE FBC ADMIN SECTION 106.1.2, 106.3.5.1.1PARA
 5
  
 7) NOTE: PLEASE SEE NFPA-72 AS THE BREAKER WHICH FEEDS
 THE FIRE ALARM CONTROL PANEL (FACP) SHALL BE A BREAKER
 WHICH CONTAINS A "LOCK-ON" DEVICE WHICH IS AN INTEGRAL
 PART OF THE BREAKER. PLEASE KNOW THAT A "SNAP ON" TYPE
 DEVICE WILL NOT BE ACCEPTABLE TO THE AHJ. NFPA-72.
 4.4.1.4.2.1THE DEDICATED BRANCH CIRCUIT(S) AND
 CONNECTIONS SHALL BE MECHANICALLY PROTECTED.
 4.4.1.4.2.2CIRCUIT DISCONNECTING MEANS SHALL HAVE A
 RED MARKING, SHALL BE ACCESSIBLE ONLY TO AUTHORIZED
 PERSONNEL, AND SHALL BE IDENTIFIED AS "FIRE ALARM
 CIRCUIT"
 4.4.1.4.2.3THE LOCATION OF THE CIRCUIT DISCONNECTING
 MEANS SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM
 CONTROL UNIT.
 PLEASE ALSO SEE 90.7, 110.3 AND 90.4.
 THIS CAN BE ADDRESSED WITH IDENTIFICATION ON THE PANEL
 SCHEDULE AND A NOTE ON PANEL FOR TYPE OF BREAKER TO BE
 USED FOR THIS CIRCUIT.
  
 8) NOTE: PLEASE COMPLETE RISER FOR FIRE PUMP AS NOTED
 ABOVE FOR FEEDERS ETC.
 240.4, 310.16, 695, NFPA-20 CHAPTER 9
  
 9) NOTE: PLEASE INDICATE "FLOATING NEUTRAL" ON THE
 METERS ON THE SECONDARY SIDE OF THE PRIMARY MAIN.
 250.6, 250.24B.
  
 10) NOTE: PLEASE SUBMIT OR INDICATE REQUIREMENTS FOR
 WIND LOAD CALCULATIONS FOR BUILDING REVIEW FOR FBC 2004
 140MPH.
  
 11) NOTE: PLEASE CLARIFY THE NOTIFICATION APPLIANCE
 CIRCUITS CALCULATIONS WHICH INDICATE A DATE OF
 9/25/01?
  
 PLEASE SEE FBC 2004 CHAPTER 11. , MORE SPECIFICALLY
 11-4.28, .1.2, AND .3(4). PLEASE ALSO SEE NFPA-72
 2002.
 THIS MAY OR MAY NOT CHANGE ACTUAL SHOWN UNITS. AS FOR
 MINIMUM CANDELA LEVELS SEE ABOVE AS NOTED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 6 Status P Date 2008-02-26 Cont ID  
Sent By rchokshi Date 2008-02-26 Time 09:44 Rev Time 0.00
Received By rchokshi Date 2008-02-26 Time 09:44 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 5 Status F Date 2008-01-09 Cont ID  
Sent By rchokshi Date 2008-01-09 Time 13:26 Rev Time 0.00
Received By rchokshi Date 2008-01-09 Time 13:23 Sent To  
Notes
2008-01-09 13:26:01***FAILED**** PLEASE PROVIDE THE FOLLOWING:
  
 1. CIVILP.E. STEVEN POWLYKNEED TO PUT A DATE OVER
 PE SEAL NEXT TO SIGNATURE ON ALL CIVIL DWGS,
  
 FOR EXAMPLE,MR. POWLYK DID NOT PUTDATEON SHEET
 1, 2, 5, 7, 9, AND ETC. ETCOF 29 ANDSO FORTH. MR .
 POWLYK HAS TO PUT A DATE, SIGN & SEAL EACH SET OFEACH
 OF THE SHEETS PER FBPE REQUIREMENTS.
  
  
 PLEASE CLEARIFY & RESPONDTO EXPEDITE YOUR PERMITTING
 PROCESS.
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 4 Status F Date 2007-12-20 Cont ID  
Sent By rchokshi Date 2007-12-20 Time 15:03 Rev Time 0.00
Received By rchokshi Date 2007-12-20 Time 14:40 Sent To  
Notes
2007-12-20 15:03:22***FAILED**** PLEASE PROVIDE THE FOLLOWING:
  
  
 PLEASE PROVIDE THE FOLLOWING REQUIREMENTS:
  
 PLEASE SHOW POLLUTION PREVENTION DETAILS ON THE
 DRAWINGS PER FDEPAND SHOW ON DRAWINGS THE SILT FENCE
 AROUND THE SITE.
  
 OUR RESPONSE TO YOUR LETTER 11/09/07: WE COULD NOT FIND
 POLLUTION PREVENTION DETAILS & SILT FENCE IN YOUR
 DRAWING SET.PLEASE EXPLAIN WHAT SHEET#S OFYOUR
 DRAWING SET.
 YOU ASKED US TO VISIT THE SITE TO CHECK POLLUTION
 PREVENTION IN YOUR LETTER. WE LIKE TO SEE POLLUTION
 PREVENTION DETAILS FIRST ON THE DRAWING AND THAN WE
 WILL VISIT PER YOUR REQUEST IF NECESSARY.
  
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2007-10-23 Cont ID  
Sent By rchokshi Date 2007-10-23 Time 13:29 Rev Time 0.00
Received By rchokshi Date 2007-10-23 Time 13:14 Sent To  
Notes
2007-10-23 13:28:58***FAILED**** PLEASE PROVIDE THE FOLLOWING:
  
 CIVILP.E. STEVEN POWLYKNEED TO PUT A DATE OVER PE
 SEAL NEXT TO SIGNATURE ON ALL CIVIL DWGS,
  
 YOU NEED TO SAY WHAT IS THE DIFFERENCE IN WATER QUALITY
 CALS FOR THIS JOB, SFWMD PERMIT,GEO-TECH REPORT, ETC.
 PLEASE ALSO PROVIDE A COPY OF EACH OF THESE.
  
  
 PLEASE ALSO PROVIDE THE FOLLOWING REQUIREMENTS:
  
 1.PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
 2.PLEASE SHOW ON DRAWINGSTHE LOCATION OF DUMPSTER &
 ITS ENCLOSURE PER CITY OF WPB, LOCATION MUST BE
 ACCESSIBLE FOR PICKUP TRUCK.
 3.PLEASE SHOW ON DRAWING THE SITE AREA OF THIS PROJECT,
 PERVIOUS AREA, IMPERVIOUS AREA, LAKE, GREEN AREA,
 PAVEMENT AREA, ETC. MAKE SURE THESE SITE AREAS SHOWN ON
 DRAWINGS MUST MATCH WITH AREAS USED IN STORM WATER
 QUALITY CALCULATIONS.
 4. PLEASE SHOW POLLUTION PREVENTION DETAILS AND SHOW ON
 DRAWINGS THE SILT FENCE AROUND THE SITE.
  
 PLEASE CREARIFY & RESPOND EACH ITEM IN DETAIL TO
 EXPEDITE YOUR PERMITTING PROCESS.THESE ARE THE SAME
 COMMENTS WE MADE LAST TIME. PLEASE EXPLAIN EACH OF THE
 COMMENTS.
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2007-07-23 Cont ID  
Sent By rchokshi Date 2007-07-23 Time 13:28 Rev Time 0.00
Received By rchokshi Date 2007-07-23 Time 13:09 Sent To  
Notes
2007-07-23 13:28:35***FAILED**** PLEASE PROVIDE THE FOLLOWING:
  
 WE ASKED FOR CIVIL PLANS IN REV 1, OF 1/19/07.THE
 CIVIL PLANS YOU SUBMITTED FOR THIS JOB ARE FOR PERMIT#
 06071716.WE ACCEPT ONLY ORIGINAL SEAL & SIGNED THE
 PLAN.YOUR SUBMITTED PLANS ARE COPIED OF SEAL &
 SIGNED.
 YOU NEED TO SAY WHAT IS THE DIFFERENCE IN WATER QUALITY
 CALS FOR THIS JOB, SFWMD PERMIT,GEO-TECH REPORT, ETC.
  
  
 PLEASE ALSO PROVIDE THE FOLLOWING NEW REQUIREMENTS:
  
 1.PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
 2.PLEASE SHOW ON DRAWINGSTHE LOCATION OF DUMPSTER &
 ITS ENCLOSURE PER CITY OF WPB, LOCATION MUST BE
 ACCESSIBLE FOR PICKUP TRUCK.
 3.PLEASE SHOW ON DRAWING THE SITE AREA OF THIS PROJECT,
 PERVIOUS AREA, IMPERVIOUS AREA, LAKE, GREEN AREA,
 PAVEMENT AREA, ETC. MAKE SURE THESE SITE AREAS SHOWN ON
 DRAWINGS MUST MATCH WITH AREAS USED IN STORM WATER
 QUALITY CALCULATIONS.
  
 PLEASE CREARIFY & RESPOND EACH ITEM IN DETAIL TO
 EXPEDITE YOUR PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2007-01-19 Cont ID  
Sent By rchokshi Date 2007-01-19 Time 11:43 Rev Time 0.00
Received By rchokshi Date 2007-01-19 Time 11:24 Sent To  
Notes
2007-01-19 11:42:54PLEASE SUBMIT CIVIL PLANS ALONG WITH A COPY OF SFWMD,
 GEO TECH REPORT, STORM WATER CALS. WHAT CHANGESYOU
 HAVE IN THIS PERMIT#FROM PERMIT #06071716, CIVIL SITE
 & DRAINAGE .
 PLEASE REPLY EACH ITEM TO EXPEDITE THE PERMITTING
 PROCESS.
  
 RASIK CHOKSHI 805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2008-02-21 Cont ID  
Sent By mawillia Date 2008-02-21 Time 19:20 Rev Time 0.00
Received By mawillia Date 2008-02-21 Time 18:14 Sent To  
Notes
2008-02-21 21:19:34*****APPROVED*****
  
  
 PLAN SHEETS A-4, A-6, A-11, A-16, E2.3.1, E2.3.1B,
 FA0.3, FA2.31, AND FP-1 THRU FP-4 WERE STAMPED,
 INITIALED, AND DATED

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-01-22 Cont ID  
Sent By mawillia Date 2008-01-22 Time 11:10 Rev Time 0.00
Received By mawillia Date 2008-01-22 Time 10:39 Sent To  
Notes
2008-01-22 10:46:54****PROVISO*****
  
  
 THE COMMENTS FROM THE PREVIOUS PLAN REVIEWS HAVE BEEN
 ADDRESSED;THE APPROPIATE PLAN SHEETS TO BE
 FIRE-STAMPED WHEN THE OTHER REVIEWERS HAVE BEEN
 SATISFIED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2007-10-25 Cont ID  
Sent By mawillia Date 2007-10-25 Time 16:49 Rev Time 0.00
Received By mawillia Date 2007-10-25 Time 15:38 Sent To  
Notes
2007-10-25 15:45:33****DENIED*****
  
  
 THE FOLLOWING COMMENTS FROM THE PREVIOUS PLAN REVIEW
 STILL NEED TO BE ADDRESSED:
  
 08.SINCE THIS WILL BE A SPRINKLERED BUILDING, PROVIDE
 A LAYOUT OF THE FIRE SPRINKLER SYSTEM.THE PROJECT
 SITE ADDRESS IN THE TITLE BLOCK OF THE SUBMITTED FIRE
 SPRINKLER SHEETS IS INCORRECT.PLEASE BE ADVISED THAT
 THE SUBMITTED SPRINKLER SHEETS WILL BE INCLUDED WITH
 THE MASTER PERMIT SET OF PLANS; SPRINKLER SPEC SHEETS
 NOT NEEDED AT THIS TIME, BUT SHALL BE REQUIRED WHEN THE
 SPRINKLER CONTRACTOR APPLIES FOR THE SEPARATE PLANS AND
 PERMIT.
  
 09.FIRE DEPARTMENT CONNECTIONS (FDC'S) SHALL BE
 POSITIONED SO THAT THEY CANNOT BE BLOCKED BY STORAGE,
 VESSELS, EQUIPMENT, ETC.COULD NOT LOCATE THIS COMMENT
 AS PER YOUR RESPONSE
  
 10.KNOX LOCKING CAPS ARE REQUIRED FOR NEW FIRE
 DEPARTMENT CONNECTIONS.COULD NOT LOCATE THIS COMMENT
 AS PER YOUR RESPONSE
  
 11.ELECTRONIC SWITCHES IN ADDITION TO CHAIN AND LOCK
 IS REQUIRED FOR DOUBLE CHECK DETECTOR ASSEMBLY.COULD
 NOT LOCATE THIS COMMENT AS PER YOUR RESPONSE
  
 12.KNOX BOX FOR THE BUILDING WILL BE REQUIRED. PLEASE
 CONTACT THE FIRE PREVENTION BUREAU AT (561) 804-4724
 FOR APPLICATIONS.COULD NOT LOCATE THIS COMMENT AS PER
 YOUR RESPONSE
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING WHERE ON THE PLAN
 EACH ITEM WAS ADDRESSED
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-07-11 Cont ID  
Sent By mawillia Date 2007-07-11 Time 13:41 Rev Time 0.00
Received By mawillia Date 2007-07-11 Time 12:06 Sent To  
Notes
2007-07-11 12:07:10****DENIED*****
  
  
 THE FOLLOWING COMMENTS FROM THE PREVIOUS PLAN REVIEW
 STILL NEED TO BE ADDRESSED:
  
  
 03.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION SHALL COMPLY WITH NFPA241.
  
 04.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL
 NOT INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID
 PROPERTY OR VICINITY THEREOF.
  
 08.SINCE THIS WILL BE A SPRINKLERED BUILDING, PROVIDE
 A LAYOUT OF THE FIRE SPRINKLER SYSTEM.
  
 09.FIRE DEPARTMENT CONNECTIONS (FDC'S) SHALL BE
 POSITIONED SO THAT THEY CANNOT BE BLOCKED BY STORAGE,
 VESSELS, EQUIPMENT, ETC.
  
 10.KNOX LOCKING CAPS ARE REQUIRED FOR NEW FIRE
 DEPARTMENT CONNECTIONS.
  
 11.ELECTRONIC SWITCHES IN ADDITION TO CHAIN AND LOCK
 IS REQUIRED FOR DOUBLE CHECK DETECTOR ASSEMBLY.
  
 12.KNOX BOX FOR THE BUILDING WILL BE REQUIRED. PLEASE
 CONTACT THE FIRE PREVENTION BUREAU AT (561) 804-4724
 FOR APPLICATIONS.
  
 13.ALL FIRE DOORS AND WINDOWS SHALL COMPLY WITH NFPA
 80.
  
 14.INTERIOR FINISH FOR WALLS AND CEILING IN EXITS AND
 EXIT ACCESS CORRIDORS SHALL BE CLASS "A" OR CLASS "B".
  
 16.FIRE EXTINGUISHERS ARE TO BE RATED 2A-10BC.
  
 17.SEPARATE SHOP DRAWINGS AND PERMITS ARE REQUIRED
 FOR FIRE SPRINKLER AND FIRE ALARM SYSTEMS.
  
 18.FIRE SPRINKLER SYSTEM IS TO BE MONITORED.
  
 19.FIRE ALARM SYSTEM IS TO BE CLASS A OR FULLY
 ADDRESSABLE.
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING WHERE ON THE PLAN
 EACH ITEM WAS ADDRESSED
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-01-30 Cont ID  
Sent By mawillia Date 2007-01-30 Time 15:08 Rev Time 0.00
Received By mawillia Date 2007-01-30 Time 15:08 Sent To  
Notes
2007-01-30 16:01:47****DENIED*****
  
  
 01.THE ACTUAL ADDRESS OF WHERE THE SCOPE OF WORK IS
 CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH PLAN
 SHEET.
  
 02.NFPA 101 - 2003 EDITION AND FLORIDA FIRE
 PREVENTION CODE - 2004 EDITION SHALL BE REFERENCED.
  
 03.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION SHALL COMPLY WITH NFPA241.
  
 04.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL
 NOT INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID
 PROPERTY OR VICINITY THEREOF.
  
 05.SHOW THE LOCATION OF FIRE HYDRANT(S) WITHIN
 300-500 FEET OF THE BUILDING.
  
 06.SHOW/DISPLAY THE NUMERICAL ADDRESS OF THE BUILDING
 ON THE PROPER ELEVATION VISIBLE FROM PREMIER PARK
 DRIVE.AS PER WEST PALM BEACH CODE, THOSE NUMBERS
 SHALL BE NO LESS THAN 6" IN HEIGHT AND 1" IN WIDTH.
 SUITE/UNIT/TENANT SPACE NUMBERS SHALL BE NO LESS THAN
 3" IN HEIGHT AND 1" IN WIDTH.
  
 07.IF A MONUMENT SIGN OR MARKEE IS REQUIRED, A
 NUMERICAL ADDRESS WILL ALSO BE POSTED.IF THERE ARE
 GOING TO BE SEVERAL ADDRESSED BUILDINGS WITHIN THE FED
 EX COMPLEX, A RANGE OF ADDRESSES FROM THE LOWEST TO THE
 HIGHEST WILL BE REQUIRED ON THE MONUMENT SIGN OR
 MARKEE.
  
 08.SINCE THIS WILL BE A SPRINKLERED BUILDING, PROVIDE
 A LAYOUT OF THE FIRE SPRINKLER SYSTEM.
  
 09.FIRE DEPARTMENT CONNECTIONS (FDC'S) SHALL BE
 POSITIONED SO THAT THEY CANNOT BE BLOCKED BY STORAGE,
 VESSELS, EQUIPMENT, ETC.
  
 10.KNOX LOCKING CAPS ARE REQUIRED FOR NEW FIRE
 DEPARTMENT CONNECTIONS.
  
 11.ELECTRONIC SWITCHES IN ADDITION TO CHAIN AND LOCK
 IS REQUIRED FOR DOUBLE CHECK DETECTOR ASSEMBLY.
  
 12.KNOX BOX FOR THE BUILDING WILL BE REQUIRED. PLEASE
 CONTACT THE FIRE PREVENTION BUREAU AT (561) 804-4724
 FOR APPLICATIONS.
  
 13.ALL FIRE DOORS AND WINDOWS SHALL COMPLY WITH NFPA
 80.
  
 14.INTERIOR FINISH FOR WALLS AND CEILING IN EXITS AND
 EXIT ACCESS CORRIDORS SHALL BE CLASS "A" OR CLASS "B".
  
 15.PROVIDE A LIFE SAFETY PLAN SHOWING THE TRAVEL
 DISTANCE TO AN EXIT MEASURED ON THE FLOOR OR OTHER
 WALKING SURFACE AS PER NFPA 1017.6.1*
  
 16.FIRE EXTINGUISHERS ARE TO BE RATED 2A-10BC.
  
 17.SEPARATE SHOP DRAWINGS AND PERMITS ARE REQUIRED
 FOR FIRE SPRINKLER AND FIRE ALARM SYSTEMS.
  
 18.FIRE SPRINKLER SYSTEM IS TO BE MONITORED.
  
 19.FIRE ALARM SYSTEM IS TO BE CLASS A OR FULLY
 ADDRESSABLE.
  
 20.ON SHEET FA0.3, FIRE ALARM NOTE 17, DELETE WORDING
 " SUPERVISORY SIGNAL ONLY" AND INSERT WORDING "A
 GENERAL FIRE ALARM".
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2009-02-18 Cont ID  
Sent By adarroug Date 2009-02-18 Time 09:30 Rev Time 0.00
Received By adarroug Date 2009-02-18 Time 09:30 Sent To Z
Notes
2009-02-18 09:31:31TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2008-12-26 Cont ID  
Sent By adarroug Date 2008-12-26 Time 10:24 Rev Time 0.00
Received By adarroug Date 2008-12-26 Time 10:24 Sent To P
Notes
2008-12-26 10:24:26TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2008-11-21 Cont ID  
Sent By adarroug Date 2008-11-21 Time 08:44 Rev Time 0.00
Received By adarroug Date 2008-11-21 Time 08:44 Sent To P
Notes
2008-11-21 08:44:52TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2008-09-29 Cont ID  
Sent By adarroug Date 2008-09-29 Time 12:28 Rev Time 0.00
Received By adarroug Date 2008-09-29 Time 12:28 Sent To P
Notes
2008-09-29 12:30:29TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2008-08-11 Cont ID  
Sent By adarroug Date 2008-08-11 Time 14:25 Rev Time 0.00
Received By adarroug Date 2008-08-11 Time 14:25 Sent To B
Notes
2008-08-11 14:26:25TO "JWITMER" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2008-08-08 Cont ID  
Sent By adarroug Date 2008-08-08 Time 10:57 Rev Time 0.00
Received By adarroug Date 2008-08-08 Time 10:57 Sent To B
Notes
2008-08-08 10:58:04TO "JWITMER' DESK/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2008-07-14 Cont ID  
Sent By adarroug Date 2008-07-14 Time 16:08 Rev Time 0.00
Received By adarroug Date 2008-07-14 Time 16:08 Sent To B
Notes
2008-07-14 16:09:14TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2008-06-25 Cont ID  
Sent By adarroug Date 2008-06-25 Time 16:40 Rev Time 0.00
Received By adarroug Date 2008-06-25 Time 16:40 Sent To B
Notes
2008-06-25 16:41:24TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-06-04 Cont ID  
Sent By adarroug Date 2008-06-04 Time 15:05 Rev Time 0.00
Received By adarroug Date 2008-06-04 Time 15:05 Sent To P
Notes
2008-06-04 15:05:53TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-06-04 Cont ID  
Sent By adarroug Date 2008-06-04 Time 15:01 Rev Time 0.00
Received By adarroug Date 2008-06-04 Time 15:01 Sent To B
Notes
2008-06-04 15:02:18TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-04-25 Cont ID  
Sent By adarroug Date 2008-04-25 Time 12:44 Rev Time 0.00
Received By adarroug Date 2008-04-25 Time 12:44 Sent To B
Notes
2008-04-25 12:45:00TO "JWITMER" DESK/9 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-03-17 Cont ID  
Sent By adarroug Date 2008-03-17 Time 08:54 Rev Time 0.00
Received By adarroug Date 2008-03-17 Time 08:54 Sent To B
Notes
2008-03-17 08:55:49TO "COMM" BD#1--PLANS ON RACK/LARGE FOLDED PLANS AND
 PAPERWORK

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-03-17 Cont ID  
Sent By adarroug Date 2008-03-17 Time 08:53 Rev Time 0.00
Received By adarroug Date 2008-03-17 Time 08:53 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-01-29 Cont ID  
Sent By adarroug Date 2008-01-29 Time 09:10 Rev Time 0.00
Received By adarroug Date 2008-01-29 Time 09:10 Sent To  
Notes
2008-01-29 09:11:07TO "COMM" BD#57/PLANS ON RACK--ROLDED PLANS AND
 PAPERWORK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-12-17 Cont ID  
Sent By adarroug Date 2007-12-17 Time 14:58 Rev Time 0.00
Received By adarroug Date 2007-12-17 Time 14:58 Sent To  
Notes
2007-12-17 14:58:18TO "COMM" BD#15/PLANS ON RACK/LARGE FOLDED PLANS AND
 PAPERWORK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-09-17 Cont ID  
Sent By adarroug Date 2007-09-17 Time 09:30 Rev Time 0.00
Received By adarroug Date 2007-09-17 Time 09:30 Sent To  
Notes
2007-10-09 15:05:53TO "COMM" BD#56
2007-09-17 09:30:55WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-18 Cont ID  
Sent By adarroug Date 2007-05-18 Time 13:55 Rev Time 0.00
Received By adarroug Date 2007-05-18 Time 13:55 Sent To  
Notes
2007-06-06 15:26:13TO "COMM" BD#59
2007-05-18 13:58:56WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-01-30 Cont ID  
Sent By mawillia Date 2007-01-30 Time 16:03 Rev Time 0.00
Received By mawillia Date 2006-11-13 Time 13:34 Sent To  
Notes
2006-11-14 10:26:29TO "COMM" BD#56
2006-11-13 13:35:02WAITING FOR "COMM"BD

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2009-02-19 Cont ID  
Sent By rkussner Date 2009-02-19 Time 09:32 Rev Time 0.00
Received By rkussner Date 2009-02-19 Time 09:32 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-12-18 Cont ID  
Sent By tgordon Date 2007-12-18 Time 10:46 Rev Time 0.45
Received By tgordon Date 2007-12-18 Time 10:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-10-12 Cont ID  
Sent By tgordon Date 2007-10-12 Time 16:27 Rev Time 0.30
Received By tgordon Date 2007-10-12 Time 16:27 Sent To  
Notes
2007-10-12 16:43:18PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) N.O.A. SUBMITTED FOR THE LOUVERS IS MISSING THE
 ASSEMBLIES & SECTIONS (DRAWINGS), PLEASE SUBMIT THE
 COMPLETE N.O.A.
  
 2) THOSE PRODUCT APPROVALS WHICH ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING
 (REVIEW STAMPED) BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.WPB AMENDMENT
 TO FBC 106.3.3.
  
 3) NOT NOTICED AT LAST REVIEW ENERGY CALCULATIONS SHOW
 NO SKYLIGHTS, PLEASE CORRECT AS SKYLIGHTS ARE BEING
 INSTALLED.
  
 4) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-07-24 Cont ID  
Sent By tgordon Date 2007-07-24 Time 08:50 Rev Time 0.35
Received By tgordon Date 2007-07-24 Time 08:50 Sent To  
Notes
2007-07-24 09:11:26*** FOR PERMIT ***
 *** DENIED ***
 1) ENERGY CALCULATIONS NEED TO SHOW ALL ASSUMED A/C
 SYSTEMS FOR FUTURE INSTALLATION 2004 FBC 13-101.1.6
 SHELL BUILDINGS.
 NONRESIDENTIAL BUILDINGS THAT ARE PERMITTED PRIOR TO
 DESIGN COMPLETION OR WHICH WILL BE FINISHED IN SECTIONS
 AT A TIME AFTER CONSTRUCTION OF THE SHELL SHALL COMPLY
 WITH EITHER METHOD B OR C OF SUBCHAPTER 13-4 OF THE
 CODE PRIOR TO GRANTING OF A PERMIT TO BUILD. ALL
 ASSUMPTIONS MADE ABOUT FEATURES NOT INSTALLED UNTIL
 LATER THAT ARE NOT ON THE BUILDING PLANS SHALL BE
 LISTED AND APPENDED TO THE COMPLIANCE FORM SUBMITTED TO
 THE BUILDING DEPARTMENT. UNLESS THE BUILDING IS
 COMPLETED AS PER ALL ASSUMPTIONS MADE IN THE ORIGINAL
 CODE COMPLIANCE SUBMITTAL, A REVISED CODE SUBMITTAL(S)
 USING METHODS A, B OR C SHALL BE SUBMITTED WHEN
 COMPLETION OF THE BUILDING (OR PART OF THE BUILDING) IS
 PERMITTED.
  
 2) PLEASE SUBMIT COOLING LOAD CALCULATIONS FOR FUTURE
 INSTALLATION, SEE 2004 FBC/M 13-407.1.ABC.1.
  
 3) AS REQUESTED IN LAST REVIEW, PLEASE SUBMIT STATE
 PRODUCT APPROVALS OR NOTICE OF ACCEPTANCE FOR LOUVERS
 TO BE INSTALLED (NOT JUST MANUFACTURER'S
 SPECIFICATION'S).
  
 4) SEE BUILDING REVIEW NOTES 8 AND 9, ALSO ELECTRICAL
 REVIEW NOTE 1, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-01-26 Cont ID  
Sent By tgordon Date 2007-01-26 Time 11:02 Rev Time 0.25
Received By tgordon Date 2007-01-26 Time 11:02 Sent To  
Notes
2007-01-26 11:02:47**FOR PLAN REVIEW ONLY NOT FOR PERMIT **
 *** DENIED ***
 1) JOB ADDRESS MUST APPEAR IN TITLE BLOCK
  
 2) PLEASE SUBMIT PRODUCT APPROVAL FOR LOUVERS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 8 Status P Date 2009-01-07 Cont ID  
Sent By lwagner Date 2009-01-07 Time 13:51 Rev Time 0.00
Received By lwagner Date 2009-01-07 Time 13:47 Sent To  
Notes
2009-01-07 13:51:13REVISION OK
  
 SHEETS : P0.1, P2.31A, P2.31B, P2.31C, P2.31D, P3.3.1A,
 P3.3.1B, P5.1

Review Stop P PLUMBING
Rev No 7 Status   Date 2008-12-22 Cont ID  
Sent By kstevens Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 6 Status F Date 2008-12-22 Cont ID  
Sent By kstevens Date 2008-12-22 Time 09:43 Rev Time 0.00
Received By kstevens Date 2008-12-19 Time 16:50 Sent To  
Notes
2008-12-22 09:44:08DENIED
 REFERENCE:
 FBC-2004 CHAPTER 1
 FBC-2004 PLUMBING
  
 1. SHT P2.31 THIS SHEET ON FILE FOR PUBLIC RECORD
 SIGNED, SEALED & DATED 06/02/08 HAS IN THE REVISION
 INDEX REVISION 8 (03/26/08) & REVISION 9 (03-28-08).
 THE NEW SHEET SUBMITTED FOR REVISION SIGNED, SEALED &
 DATED 11-17-08 HAS DELETED REVISIONS 8 & 9 AND ONLY
 SHOWS NEW REVISION NUMBER 12. ALL REVISIONS SHALL BE
 MAINTAINED IN THE REVISION INDEX FOR THE LIFE OF THE
 PROJECT. SECTION 106.1.3. ALL NEW REVISIONS SHALL BE
 CLOUDED & INDICATED WITH A NEW REVISION NUMBER. SOME
 REVISIONS ARE NOT CLOUDED NOR INDICATED WITH A REVISION
 NUMBER.
 FBC-2004 SECTION 106.1.2 QUALITY OF PLANS:
 BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH
 SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE
 MEDIUM. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS MANAGEMENT.
  
 2. SHT P3.1.1 THIS SHEET ON FILE FOR PUBLIC RECORD
 SIGNED, SEALED & DATED 06/02/08 HAS IN THE REVISION
 INDEX REVISION 8 (02-20-08), REVISION 9 (03-28-08), &
 REVISION 10 (05-21-08). THE NEW SHEET SUBMITTED FOR
 REVISION SIGNED, SEALED & DATED 11-17-08 HAS DELETED
 REVISIONS 3, 7, 8, & 9 AND NOW HAS NO REVISIONS SHOWN
 IN THE REVISION INDEX. ALL REVISIONS SHALL BE
 MAINTAINED IN THE REVISION INDEX FOR THE LIFE OF THE
 PROJECT. SECTION 106.1.3. ALL NEW REVISIONS SHALL BE
 CLOUDED & INDICATED WITH A NEW REVISION NUMBER. NO
 CHANGES WERE SEEN FROM THE PREVIOUS REVISION. IF NO
 CHANGES THE SHEET SHALL NOT BE REQUIRED TO BE SUBMITTED
 FOR REVISION. IF THERE ARE NEW REVISIONS THEN ALL
 REVISIONS SHALL BE CLOUDED AND INDICATED WITH A NEW
 REVISION NUMBER.
 FBC-2004 SECTION 106.1.2 QUALITY OF PLANS:
 BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH
 SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE
 MEDIUM. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS MANAGEMENT.
  
 3. SHT P5.1 THIS SHEET ON FILE FOR PUBLIC RECORD
 SIGNED, SEALED & DATED 06/02/08 HAS IN THE REVISION
 INDEX REVISION 4 (08-15-07), REVISION 8 (02-20-08),
 REVISION 9 (03-28-08) & REVISION 10 (05-21-08). THE NEW
 SHEET SUBMITTED FOR REVISION SIGNED, SEALED & DATED
 11-17-08 HAS DELETED REVISIONS 4, 8, 9 & 10 AND ONLY
 SHOWS NEW REVISION NUMBER 12. ALL REVISIONS SHALL BE
 MAINTAINED IN THE REVISION INDEX FOR THE LIFE OF THE
 PLANS. SECTION 106.1.3. ALL NEW REVISIONS SHALL BE
 CLOUDED & INDICATED WITH A NEW REVISION NUMBER. SOME
 REVISIONS ARE NOT CLOUDED NOR INDICATED WITH A REVISION
 NUMBER.
 FBC-2004 SECTION 106.1.2 QUALITY OF PLANS:
 BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH
 SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE
 MEDIUM. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS MANAGEMENT.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 5 Status F Date 2008-10-08 Cont ID  
Sent By kstevens Date 2008-10-08 Time 07:54 Rev Time 0.00
Received By kstevens Date 2008-10-08 Time 07:54 Sent To  
Notes
2008-10-08 08:04:58REVISIONS DENIED
 REFERENCE: FBC-2004 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT P2.31 A PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME PER FAC 61G15-23.002(1). INITIALS HAVE BEEN USED.
 PLEASE USE THE SIGNATURE REQUIRED. FS 471.025.
  
 2. SHT P2.31 SHOWS A HOSE BIBB IN THE METER ROOM. NO
 FLOOR DRAIN IS INDICATED. PLEASE SHOW COMPLIANCE WITH
 SECTION 301.2 WHICH STATES THAT PLUMBING SHALL BE
 INSTALLED WITH DUE REGARD TO PRESERVATION OF THE
 STRENGTH OF STRUCTURAL MEMBERS AND PREVENTION OF DAMAGE
 TO WALLS AND OTHER SURFACES THROUGH FIXTURE USEAGE.
  
 3. SHT P2.31 SHOWS THE 3" VTR BEING CHANGED TO AN AIR
 ADMITTANCE VALVE. SECTION 903.1 REQUIRES AT LEAST ONE
 VENT STACK THE SIZE OF WHICH IS NOT LESS THAN 1/2 OF
 THE REQUIRED SIZE OF THE BUILDING DRAIN TO RUN
 UNDIMINISHED IN SIZE AND DIRECTLY AS POSSIBLE FROM THE
 BUILDING DRAIN THROUGH TO THE OPEN AIR OR TO A VENT
 HEADER THAT EXTENDS TO THE OPEN AIR. PLEASE INDICATE
 HOW THIS WILL BE COMPLIED WITH.
  
 4. SHT P2.31 INDICATES A REVISION #10 ON THE FLOOR
 PLAN. REVISION #10 IS NOT INDICATED ON THE REVISION
 INDEX IN THE TITLE BLOCK. PLEASE CORRELATE. SECTION
 106.1.3.
  
 5. SHT P3.1.1 A PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME PER FAC 61G15-23.002(1). INITIALS HAVE BEEN USED.
 PLEASE USE THE SIGNATURE REQUIRED. FS 471.025.
  
 6. SHT P3.1.1 LATEST REVISION SUBMITTED IS REVISION
 #10. REVISION #10 WAS SUBMITTED PREVIOUSLY AND WAS
 SIGNED, SEALED & DATED ON 6-2-08. SHEET HAS BEEN DENIED
 BECAUSE NO NEW REVISION IS INDICATED. SECTION 106.1.3.
  
 7. SHT P5.1 A PROFESSIONAL ENGINEER SHALL SIGN HIS NAME
 PER FAC 61G15-23.002(1). INITIALS HAVE BEEN USED.
 PLEASE USE THE SIGNATURE REQUIRED. FS 471.025.
  
 8. SHT P5.1 SHOWS A HOSE BIBB IN THE METER ROOM. NO
 FLOOR DRAIN IS INDICATED. PLEASE SHOW COMPLIANCE WITH
 SECTION 301.2 WHICH STATES THAT PLUMBING SHALL BE
 INSTALLED WITH DUE REGARD TO PRESERVATION OF THE
 STRENGTH OF STRUCTURAL MEMBERS AND PREVENTION OF DAMAGE
 TO WALLS AND OTHER SURFACES THROUGH FIXTURE USEAGE.
  
 9. SHT P5.1 SHOWS THE 3" VTR BEING CHANGED TO AN AIR
 ADMITTANCE VALVE. SECTION 903.1 REQUIRES AT LEAST ONE
 VENT STACK THE SIZE OF WHICH IS NOT LESS THAN 1/2 OF
 THE REQUIRED SIZE OF THE BUILDING DRAIN TO RUN
 UNDIMINISHED IN SIZE AND DIRECTLY AS POSSIBLE FROM THE
 BUILDING DRAIN THROUGH TO THE OPEN AIR OR TO A VENT
 HEADER THAT EXTENDS TO THE OPEN AIR. PLEASE INDICATE
 HOW THIS WILL BE COMPLIED WITH.
  
 10. INFORMATIONAL. AS PREVIOUSLY REQUESTED, WHEN
 SUBMITTING REVISIONS, PLEASE TURN OFF ALL PREVIOUSLY
 CLOUDED REVISIONS ON THE FLOOR PLANS & RISERS AS WELL
 AS THE REVISION NUMBERS AS THIS CAUSES DELAYS IN THE
 PLAN REVIEW PROCESS. EACH CLOUD HAS TO BE SCRUTINIZED
 IN ORDER TO MAKE SURE ALL REVISIONS SUBMITTED HAVE BEEN
 REVIEWED. THE REVISION INDEX SHALL STILL SHOW ALL
 REVISION NUMBERS AND DATES. SECTION 106.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-07-11 Cont ID  
Sent By kstevens Date 2008-07-11 Time 10:51 Rev Time 0.00
Received By kstevens Date 2008-07-11 Time 10:51 Sent To  
Notes
2008-07-11 10:53:50REVISIONS OK--SHTS P0.1, P2.3.1, P3.3.1 & P5.1

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-11-10 Cont ID  
Sent By kstevens Date 2007-11-10 Time 08:17 Rev Time 0.00
Received By kstevens Date 2007-11-10 Time 08:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-06-18 Cont ID  
Sent By kstevens Date 2007-06-18 Time 17:35 Rev Time 0.00
Received By kstevens Date 2007-06-18 Time 17:35 Sent To  
Notes
2007-06-18 17:37:58DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK - SHELL INDICATED ON APPLICATION.
  
 2. SHT A-5 SUBMIT CALCULATIONS FOR THE PRIMARY AND
 SECONDARY ROOF DRAINS PER SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS & TABLES. IN THE CALCULATIONS SHOW 1/2 AREA
 OF ALL VERTICAL WALLS INCLUDING PARAPETS. THESE
 CALCULATIONS ARE REQUIRED FOR THE LOWER ROOFS ALSO.
 INDICATE THE ELEVATIONS FOR THE ROOF, HIGH END AND LOW
 END, TO VERIFY PARAPET WALL CONTRIBUTION.
 ****NO RESPONSE/NOT ADDRESSED.
  
 3. SHTS A-5 & P3.3.1. WITH THE SLOPE OF THE ROOF AS
 INDICATED ON SHT A-5, EXPLAIN HOW ALL ROOF DRAINS SHOW
 THE SAME SQUARE FOOTAGE, (18930SF), DRAINING THROUGH
 EACH DRAIN. ALSO THE ROOF DRAINS ON THE END AREAS OF
 THE BUILDING HAVE EXTRA PARAPET WALL SQUARE FOOTAGE
 THAT DOES NOT CONTRIBUTE TO THE INTERNAL SECTIONS OF
 THE ROOF.
 ****NO RESPONSE/NOT ADDRESSED.
  
 4. SHT A-8 DETAILS 1/A-8 & 3/A-8 BOTH SCALE OUT TO
 APPROXAMATELY 2'9" FROM THE ROOF TO THE TOP OF THE
 PARAPET. PLEASE CLARIFY AS THE ROOF PLAN INDICATES
 1/4"/FT SLOPE @ 150' AND THE PARAPET ON THE LOW END
 SHOULD BE APPROXAMATLY 4' HIGHER WITH BOTH PARAPETS
 BEING 33'-0" AFF.
 ****NO RESPONSE/NOT ADDRESSED.
  
 5. SUBMIT STORM RISER DIAGRAMS SHOWING ALL PIPE SIZES &
 OFFSETS. SECTION 106.3.5.1.3.ARE THE RISER DIAGRAMS
 TO BE PIPED TO THE CATCH BASINS INDIVIDUALLY, OR TO BE
 TIED TOGETHER PRIOR TO THE CATCH BASINS? IF TIED
 TOGETHER, SIZING SHALL BE PER TABLE 1106.3.
 ****NO RESPONSE/NOT ADDRESSED.
  
 6. NO INDICATION OF VENTING IS SHOWN. PLEASE INDICATE
 IF VENTS RUN THRU THE ROOF WILL BE INSTALLED UNDER THE
 SHELL PERMIT, OR WITH THE TENANT BUILDOUT
 PERMIT/PERMITS. SECTION 106.1.1.
 ****NO RESPONSE/NOT ADDRESSED.
  
 7. SHT P5.1 AN RPZV BACKFLOW IS REQUIRED ON THE WATER
 SERVICE OF THE BUILDING. SECTION 608.13.2. PLEASE
 INDICATE ON THE WATER RISER DIAGRAM OR THE PLUMBING
 FLOOR PLAN.
 ****NO RESPONSE/NOT ADDRESSED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-01-16 Cont ID  
Sent By kstevens Date 2007-01-16 Time 16:19 Rev Time 0.00
Received By kstevens Date 2007-01-16 Time 16:13 Sent To  
Notes
2007-01-16 16:19:25DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT A-4 INDICATES NO PLUMBING FIXTURES. THE PLANS DO
 NOT INDICATE THAT THIS WILL BE A SHELL PERMIT ONLY, NOR
 IS IT INDICATED IN ANY DESCRIPTION OF WORK ON THE
 SUBMITTAL SHEET OR THE PERMIT APPLICATION. SINCE THIS
 IS A PLAN REVIEW ONLY, I WILL ASSUME THAT IT IS A SHELL
 ONLY AND REVIEW IT AS SUCH. ALL MINIMUM FACILITIES WILL
 BE REQUIRED AT TENANT BUILDOUT. TABLES 1004.1.2 &
 403.1. PLEASE INDICATE IF THIS IS INCORRECT.
  
 2. SHT A-5 SUBMIT CALCULATIONS FOR THE PRIMARY AND
 SECONDARY ROOF DRAINS PER SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS & TABLES. IN THE CALCULATIONS SHOW 1/2 AREA
 OF ALL VERTICAL WALLS INCLUDING PARAPETS. THESE
 CALCULATIONS ARE REQUIRED FOR THE LOWER ROOFS ALSO.
 INDICATE THE ELEVATIONS FOR THE ROOF, HIGH END AND LOW
 END, TO VERIFY PARAPET WALL CONTRIBUTION.
  
 3. SHTS A-5 & P3.3.1. WITH THE SLOPE OF THE ROOF AS
 INDICATED ON SHT A-5, EXPLAIN HOW ALL ROOF DRAINS SHOW
 THE SAME SQUARE FOOTAGE, (18930SF), DRAINING THROUGH
 EACH DRAIN. ALSO THE ROOF DRAINS ON THE END AREAS OF
 THE BUILDING HAVE EXTRA PARAPET WALL SQUARE FOOTAGE
 THAT DOES NOT CONTRIBUTE TO THE INTERNAL SECTIONS OF
 THE ROOF.
  
 4. SHT A-8 DETAILS 1/A-8 & 3/A-8 BOTH SCALE OUT TO
 APPROXAMATELY 2'9" FROM THE ROOF TO THE TOP OF THE
 PARAPET. PLEASE CLARIFY AS THE ROOF PLAN INDICATES
 1/4"/FT SLOPE @ 150' AND THE PARAPET ON THE LOW END
 SHOULD BE APPROXAMATLY 4' HIGHER WITH BOTH PARAPETS
 BEING 33'-0" AFF.
  
 5. SUBMIT STORM RISER DIAGRAMS SHOWING ALL PIPE SIZES &
 OFFSETS. SECTION 106.3.5.1.3.ARE THE RISER DIAGRAMS
 TO BE PIPED TO THE CATCH BASINS INDIVIDUALLY, OR TO BE
 TIED TOGETHER PRIOR TO THE CATCH BASINS? IF TIED
 TOGETHER, SIZING SHALL BE PER TABLE 1106.3.
  
 6. NO INDICATION OF VENTING IS SHOWN. PLEASE INDICATE
 IF VENTS RUN THRU THE ROOF WILL BE INSTALLED UNDER THE
 SHELL PERMIT, OR WITH THE TENANT BUILDOUT
 PERMIT/PERMITS. SECTION 106.1.1.
  
 7. SHT P5.1 AN RPZV BACKFLOW IS REQUIRED ON THE WATER
 SERVICE OF THE BUILDING. SECTION 608.13.2. PLEASE
 INDICATE ON THE WATER RISER DIAGRAM OR THE PLUMBING
 FLOOR PLAN.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 6 Status P Date 2008-03-19 Cont ID  
Sent By eschneid Date 2008-03-19 Time 15:31 Rev Time 0.00
Received By eschneid Date 2008-03-19 Time 15:31 Sent To  
Notes
2008-03-19 15:31:48SIGNS SHALL BE APPROVED UNDER SEPARATE PERMIT.

Review Stop Z ZONING
Rev No 5 Status F Date 2008-02-20 Cont ID  
Sent By eschneid Date 2008-02-20 Time 12:44 Rev Time 0.00
Received By eschneid Date 2008-02-20 Time 12:43 Sent To  
Notes
2008-02-20 12:49:48FAILED
  
 1) REPEAT COMMENT - SITE/CIVIL PLANS DO NOT MATCH THE
 LANDSCAPE PLANS ALONG THE WESTERN ROW OF PARKING -
 DIFFERENT PLACEMENT OF LANDSCAPE ISLANDS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.

Review Stop Z ZONING
Rev No 4 Status F Date 2008-01-03 Cont ID  
Sent By eschneid Date 2008-01-03 Time 18:17 Rev Time 0.00
Received By eschneid Date 2008-01-03 Time 18:16 Sent To  
Notes
2008-01-03 18:36:24FAILED
  
 1) RESPOND TO COMMENTS IN WRITING.
  
 2) CORRECTED
  
 3) CORRECTED
  
 3) CORRECTED
  
 4) SHEET A1 SHALL SHOW ALL OF THE LATEST APPROVED
 REVISIONS TO THE OVERALL SITE PLAN.STAFF HAS NOT
 RECEIVED THE LATEST SITE PLAN FOR MINOR AMENDMENT
 APPROVAL. (REPEAT COMMENT)
  
 5) CORRECTED
  
 6) CORRECTED
  
 7) CORRECTED
  
 8)CORRECTED
  
 9) CORRECTED
  
 10) CORRECTED
  
 11) CORRECTED
  
 12) CORRECTED
  
 13) NOT ALL CONDITIONS OF ORD. NO. 3987-06 HAVE BEEN
 MET - REPEAT COMMENT.VERIFICATION FROM PALM BEACH
 COUNTY SHALL BE PROVIDED TO RELEASE THE TRAFFIC
 CONDITIONS.THE USE TABLE ITEMS HAVE NOT BEEN
 SUBMITTED.NEW - PER THE ORDINANCE, A MINOR AMENDMENT
 IS REQUIRED TO ACCEPT THE NEW COUNTY TRAFFIC LETTER
 ISSUED ON OCTOBER 28, 2007.STAFF NEEDS TO MEET WITH
 YOU TRAFFIC CONSULTANT TO ADDRESS THE ITEMS BELOW.
  
 A. THE PROPERTY OWNER SHALL POST SURETY IN THE AMOUNT
 OF ONE HUNDRED FIFTY THOUSAND DOLLARS ($150,000.00)
 WITHIN TWELVE (12) MONTHS OF THIS DEVELOPMENT ORDER
 (DUE BY OCTOBER 10, 2007) IN A FORM ACCEPTABLE TO THE
 COUNTY ATTORNEY TO ASSURE THE INSTALLATION OF THE
 TRAFFIC SIGNAL WHEN WARRANTED.NO PROOF THIS IS
 COMPLETED OR NO LONGER REQUIRED HAS BEEN SUBMITTED.
  
 B. AT SUCH TIME AS THE PROPERTY OWNER COMPLETES THE
 DRAINAGE PLAN FOR THE PROJECT, THE PROPERTY OWNER SHALL
 NOTIFY THE COUNTY'S ROADWAY PRODUCTION DIVISION IF THE
 PROJECT HAS ANY EXCESS STORMWATER RETENTION CAPACITY
 THAT CAN BE MADE AVAILABLE TO THE COUNTY FOR THE
 WIDENING OF 45TH STREET FROM TWO (2) LANES TO FOUR (4)
 LANES FROM HAVERHILL ROAD TO THE FLORIDA TURNPIKE.IF
 THERE IS EXCESS CAPACITY AVAILABLE, THE PROPERTY OWNER
 SHALL MAKE THAT CAPACITY AVAILABLE TO THE COUNTY
 THROUGH THE DEDICATION OF A TWENTY FOOT (20') DRAINAGE
 EASEMENT FROM THE ROAD RIGHT-OF-WAY TO THE ULTIMATE
 OUTFALL.THE DRAINAGE EASEMENT SHALL COVER THE ENTIRE
 POND. NO PROOF THIS IS COMPLETED OR NO LONGER REQUIRED
 HAS BEEN SUBMITTED.
  
 C. NO MORE THAN 1,146 NEW DAILY TRIPS MAY BE PERMITTED
 UNTIL CONTRACT IS LET FOR WIDENING OF HAVERHILL ROAD TO
 FIVE (5) LANES, FROM 45TH STREET TO CARIBBEAN
 BOULEVARD. PROVIDE PROOF THAT THIS HAS BEEN RELEASED.
  
 D. NO BUILDING PERMITS FOR DEVELOPMENT GENERATING MORE
 THAT 85 NEW EXTERNAL PM PEAK HOUR TRIPS PRIOR TO
 LETTING OF THE CONTRACT FOR THE FOUR (4) LANING OF
 HAVERHILL ROAD, FROM BEELINE HIGHWAY TO 45TH STREET.
 PROVIDE PROOF THAT THIS HAS BEEN RELEASED.
  
 E.NO BUILDING PERMITS FOR DEVELOPMENT GENERATING MORE
 THAT 103 NEW EXTERNAL PM PEAK HOUR TRIPS PRIOR TO
 LETTING OF THE CONTRACT FOR THE FOLLOWING IMPROVEMENTS
 AT THE INTERSECTION OF HAVERHILL ROAD AND ROEBUCK ROAD:
 PROVIDE PROOF THAT THESE HAVE BEEN RELEASED.
  
 1. ADDITION OF A SECOND EXCLUSIVE NORTHBOUND LEFT TURN
 LANE.
  
 2. ADDITION OF A SECOND EXCLUSIVE EASTBOUND LEFT TURN
 LANE.
  
 3. RECONFIGURE THE WESTBOUND APPROACH TO PROVIDE ONE
 EXCLUSIVE LEFT TURN LANE, TWO THROUGH LANES AND ONE
 EXCLUSIVE RIGHT-TURN LANE.
  
 F. NO BUILDING PERMITS FOR DEVELOPMENT GENERATING MORE
 THAN 261 NEW EXTERNAL AM PEAK HOUR TRIPS PRIOR TO THE
 LETTING OF THE CONTRACT FOR THE ADDITION OF A SECOND
 NORTHBOUND THROUGH LANE AT THE INTERSECTION OF
 HAVERHILL ROAD AND 45TH STREET.NEW - THE LATEST
 TRAFFIC LETTER APPROVES 272 AM TRIPS, YET THE MOST
 RECENT TRAFFIC STATEMENT STATES THERE ARE 274 TRIP
 ASSOCIATED WITH THE FEDEXS AND BLDGS 1 & 3.
  
 G. WITHIN SIX (6) MONTHS FROM THE DATE OF THE
 DEVELOPMENT ORDER (DUE BY APRIL 10, 2007), THE
 DEVELOPER MUST ENTER INTO A PUBLIC FACILITIES AGREEMENT
 (PFA) WITH PALM BEACH COUNTY TO FUND AND/OR TO
 CONSTRUCT ANY AND ALL IMPROVEMENTS AS THE TERM IS
 DEFINED BY THE TRAFFIC PERFORMANCE STANDARDS ORDINANCE.
 THE PFA MUST BE IN A FORM ACCEPTABLE TO THE COUNTY
 ENGINEER.THE CITY SHALL NOT ISSUE ANY BUILDING
 PERMITS ASSOCIATED WITH THE PROJECT UNLESS AND UNTIL
 THE PFA HAS BEEN APPROVED BY THE BOARD OF COUNTY
 COMMISSIONERS.NEW - THE PROPORTIONATE FAIR SHARE
 AGREEMENT WAS PROVIDED, IS THIS THE SAME AS THE PFA?
  
 H. CORRECTED
  
 I. A TRAFFIC STATEMENT, PREPARED BY A LICENSED TRAFFIC
 ENGINEER, SHALL BE SUBMITTED TO THE PLANNING AND ZONING
 AND CONSTRUCTION SERVICES DEPARTMENTS CONCURRENT WITH
 ALL BUILDING PERMIT APPLICATIONS OUTLINING THE NUMBER
 OF DAILY TRIPS, AM TRIPS AND PM TRIPS GENERATED FOR
 EACH USE AND ITS SQUARE FOOTAGE FOR EACH BUILDING.THE
 TRAFFIC STATEMENT SHALL INCLUDE THE TRIPS ASSOCIATED
 WITH THE SPECIFIC USE AND A CUMULATIVE TABLE FOR ALL OF
 THE USES APPROVED IN THE PREMIER PARK OF COMMERCE CPD
 PARTIALLY ADDRESSED - COMBINE LETTER FROM FEDEXS AND
 BLDGS 1 & 3.
  
 14) NEW - SITE/CIVIL PLANS DO NOT MATCH THE LANDSCAPE
 PLANS ALONG THE WESTERN ROW OF PARKING BASED ON
 REVISIONS MADE SINCE LAST REVIEW.
  
 15) NEW - THE PARKING COUNT ON THE FRONT SHEET DOES NOT
 MATCH THE ACTUAL NUMBER OF PROVIDED ON THE SITE PLAN.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435

Review Stop Z ZONING
Rev No 3 Status F Date 2007-10-30 Cont ID  
Sent By eschneid Date 2007-10-30 Time 15:20 Rev Time 0.00
Received By eschneid Date 2007-10-18 Time 21:05 Sent To  
Notes
2007-10-18 21:25:59FAILED
  
 1) RESPOND TO COMMENTS IN WRITING.
  
 2) ADA PARKING DETAILS DO NOT MEET CITY CODE (SHEET A3)
 - REPEAT COMMENT.THE DETAIL ON THE BOWYER SINGLETON
 PLANS SHEET 13 OF 29 IS CORRECT AND SHOULD BE USED.
 WHEEL STOPS AND HC SYMBOL LOCATIONS NEED CORRECTING ON
 A3.
  
 3) THE LANDSCAPE AREA FOR THE LONE DUMPSTER IN THE
 LOADING AREA IS NOT SHOWN ON SHEET A2 - REPEAT
 COMMENT.
  
 3) THE ELEVATIONS APPROVED BY ORDINANCE NO. 3987-06 AND
 SHOWN ON SHEET A6 DO NOT MATCH SECTIONS SHOWN ON SHEETS
 A8 AND A14 - PARTIAL REPEAT COMMENT.
  
 A. USE ELEVATIONS AS SHOWN ON SHEETS A6 AND A7.
  
 B. SHEET A8 SHOWS REVELS AT DIFFERENT SIZES THAN CALLED
 OUT ON SHEET A6 (4 INCH VS. 6 INCH).
  
 C. SHEET A8 (SECTION 4/A-8) DOES NOT SHOW THE MOLDING
 IN LINE WITH THE TOP OF THE BAHAMA SHUTTERS OR THE
 BAHAMA SHUTTERS THEMSELVES.
  
 D. SHEET A14 (SECTION DETAIL 3/A14) DOES NOT SHOW THE
 HORIZONTAL SCORE LINE THROUGH THE SQUARES AS THE
 ELEVATION SHOWN ON A6 DOES.
  
 E. WHERE ARE THE BAHAMA SHUTTER DETAILS.
  
 4) SHEET A1 AND A2 SHALL SHOW ALL OF THE LATEST
 APPROVED REVISIONS TO THE SITE PLANS.
  
 5) D-CURBS OR WHEEL STOPS ARE REQUIRED ALONG ALL
 LANDSCAPE AREAS.THE PLANS SHALL CALL OUT ALL CURBING
 AS SUCH.
  
 6) A PHOTOMETRIC PLAN IS REQUIRED.THE ILLUMINATION
 SHALL NOT EXCEED ONE FOOT CANDLE AT THE BOUNDARY OF THE
 PLANNED DEVELOPMENT.
  
 7) THE SOUTHEAST MOST LIGHT POLE IS NOT SHOWN IN THE
 SAME LOCATION ON THE SITE AND LANDSCAPE PLANS.
  
 8)MOST OF THE LIGHT POLES ARE WITHIN 5 FEET OF LIVE
 OAKS OR OTHER TREES.THE TREES OR THE LOCATION OF THE
 LIGHT POLES SHALL BE ADJUSTED SO THAT TREES TO NOT GROW
 INTO THE LIGHT POLES, MAKING THEM INEFFECTIVE.
  
 9) THE TWO SOUTHERNMOST CATCH BASINS ON THE EAST
 PROPERTY LINE WILL NOT BE ABLE TO SUPPORT A WHEEL STOP
 AND THUS THERE WILL BE INADEQUATE PROTECTION OF THE
 TREES SHOWN AT THE HEAD OF THE SPACE.THE TREES SHALL
 BE MOVED FROM DIRECTLY IN FRONT OF THE SPACE (NOTE THAT
 THE COMBINATION OF THE LIGHT POLE AND CATCH BASIN
 LOCATIONS MAY REQUIRE THE REMOVAL OF A TREE AND
 RELOCATION OF ANOTHER SO THE REMAINING TREE WILL AVOID
 OBSTACLES AND HAVE ROOM TO GROW).
  
 10) SOME OF THE FIRE HYDRANTS CONFLICT WITH THE TREE
 PLACEMENT.
  
 11) THE NEW SIGN SHOWN ON THE SOUTHWEST CORNER OF THE
 SITE HAS NEVER APPEARED ON ANY PREVIOUS PLAN.A SIGN
 AT THIS LOCATION REQUIRES THE APPROVAL OF A MINOR
 PLANNED DEVELOPMENT AMENDMENT.NOTE THAT IT SHALL BE 5
 FEET FROM THE PREMIER PARK DRIVE RIGHT-OF-WAY LINE AND
 24 FEET FROM THE PROPERTY LINE OF BUILDING #2.THE
 SIGN LOCATION ALSO INTERFERES WITH THE APPROVED
 LANDSCAPE PLANS AND IS NOT SHOWN ON THE CIVIL PLANS.
  
 12) NO BUILDING PERMITS WILL BE ISSUED FOR BUILDING #3
 UNTIL UNTIL THE DEVELOPER FINALIZES THE PROPORTIONATE
 SHARE AGREEMENTS WITH PALM BEACH COUNTY.
  
 13) NOT ALL CONDITIONS OF ORD. NO. 3987-06 HAVE BEEN
 MET - REPEAT COMMENT.VERIFICATION FROM PALM BEACH
 COUNTY SHALL BE PROVIDED TO RELEASE THE TRAFFIC
 CONDITIONS.THE USE TABLE ITEMS HAVE NOT BEEN
 SUBMITTED.
  
 A. THE PROPERTY OWNER SHALL POST SURETY IN THE AMOUNT
 OF ONE HUNDRED FIFTY THOUSAND DOLLARS ($150,000.00)
 WITHIN TWELVE (12) MONTHS OF THIS DEVELOPMENT ORDER
 (DUE BY OCTOBER 10, 2007) IN A FORM ACCEPTABLE TO THE
 COUNTY ATTORNEY TO ASSURE THE INSTALLATION OF THE
 TRAFFIC SIGNAL WHEN WARRANTED.
  
 B. AT SUCH TIME AS THE PROPERTY OWNER COMPLETES THE
 DRAINAGE PLAN FOR THE PROJECT, THE PROPERTY OWNER SHALL
 NOTIFY THE COUNTY'S ROADWAY PRODUCTION DIVISION IF THE
 PROJECT HAS ANY EXCESS STORMWATER RETENTION CAPACITY
 THAT CAN BE MADE AVAILABLE TO THE COUNTY FOR THE
 WIDENING OF 45TH STREET FROM TWO (2) LANES TO FOUR (4)
 LANES FROM HAVERHILL ROAD TO THE FLORIDA TURNPIKE.IF
 THERE IS EXCESS CAPACITY AVAILABLE, THE PROPERTY OWNER
 SHALL MAKE THAT CAPACITY AVAILABLE TO THE COUNTY
 THROUGH THE DEDICATION OF A TWENTY FOOT (20') DRAINAGE
 EASEMENT FROM THE ROAD RIGHT-OF-WAY TO THE ULTIMATE
 OUTFALL.THE DRAINAGE EASEMENT SHALL COVER THE ENTIRE
 POND.
  
 C. NO MORE THAN 1,146 NEW DAILY TRIPS MAY BE PERMITTED
 UNTIL CONTRACT IS LET FOR WIDENING OF HAVERHILL ROAD TO
 FIVE (5) LANES, FROM 45TH STREET TO CARIBBEAN
 BOULEVARD.
  
 D. NO BUILDING PERMITS FOR DEVELOPMENT GENERATING MORE
 THAT 85 NEW EXTERNAL PM PEAK HOUR TRIPS PRIOR TO
 LETTING OF THE CONTRACT FOR THE FOUR (4) LANING OF
 HAVERHILL ROAD, FROM BEELINE HIGHWAY TO 45TH STREET.
  
 E.NO BUILDING PERMITS FOR DEVELOPMENT GENERATING MORE
 THAT 103 NEW EXTERNAL PM PEAK HOUR TRIPS PRIOR TO
 LETTING OF THE CONTRACT FOR THE FOLLOWING IMPROVEMENTS
 AT THE INTERSECTION OF HAVERHILL ROAD AND ROEBUCK
 ROAD:
  
 1. ADDITION OF A SECOND EXCLUSIVE NORTHBOUND LEFT TURN
 LANE.
  
 2. ADDITION OF A SECOND EXCLUSIVE EASTBOUND LEFT TURN
 LANE.
  
 3. RECONFIGURE THE WESTBOUND APPROACH TO PROVIDE ONE
 EXCLUSIVE LEFT TURN LANE, TWO THROUGH LANES AND ONE
 EXCLUSIVE RIGHT-TURN LANE.
  
 F. NO BUILDING PERMITS FOR DEVELOPMENT GENERATING MORE
 THAN 261 NEW EXTERNAL AM PEAK HOUR TRIPS PRIOR TO THE
 LETTING OF THE CONTRACT FOR THE ADDITION OF A SECOND
 NORTHBOUND THROUGH LANE AT THE INTERSECTION OF
 HAVERHILL ROAD AND 45TH STREET.
  
 G. WITHIN SIX (6) MONTHS FROM THE DATE OF THE
 DEVELOPMENT ORDER (DUE BY APRIL 10, 2007), THE
 DEVELOPER MUST ENTER INTO A PUBLIC FACILITIES AGREEMENT
 (PFA) WITH PALM BEACH COUNTY TO FUND AND/OR TO
 CONSTRUCT ANY AND ALL IMPROVEMENTS AS THE TERM IS
 DEFINED BY THE TRAFFIC PERFORMANCE STANDARDS ORDINANCE.
 THE PFA MUST BE IN A FORM ACCEPTABLE TO THE COUNTY
 ENGINEER.THE CITY SHALL NOT ISSUE ANY BUILDING
 PERMITS ASSOCIATED WITH THE PROJECT UNLESS AND UNTIL
 THE PFA HAS BEEN APPROVED BY THE BOARD OF COUNTY
 COMMISSIONERS.
  
 H. A USE CHART SHALL BE SUBMITTED TO THE PLANNING AND
 ZONING AND CONSTRUCTION SERVICES DEPARTMENTS CONCURRENT
 WITH ALL BUILDING PERMIT AND/OR OCCUPATIONAL LICENSE
 APPLICATIONS STATING THE SQUARE FOOTAGE DEVOTED TO THE
 USES WITHIN BUILDINGS 1, 2 AND 3.THE SPECIFIC SQUARE
 FOOTAGE USE WITHIN EACH BUILDING MAY NOT EXCEED THE
 ALLOWANCES OUTLINED IN THE BUILDING USE SQUARE FOOTAGE
 TABLE (EXHIBIT F), UNLESS THE PROPERTY OWNER PROVIDES A
 TRAFFIC EQUIVALENCY STATEMENT, PREPARED BY A LICENSED
 TRAFFIC ENGINEER, DEMONSTRATING THAT THE APPROVED
 TRAFFIC CONCURRENCY FOR THE PROJECT IS NOT EXCEEDED.
  
 I. A TRAFFIC STATEMENT, PREPARED BY A LICENSED TRAFFIC
 ENGINEER, SHALL BE SUBMITTED TO THE PLANNING AND ZONING
 AND CONSTRUCTION SERVICES DEPARTMENTS CONCURRENT WITH
 ALL BUILDING PERMIT APPLICATIONS OUTLINING THE NUMBER
 OF DAILY TRIPS, AM TRIPS AND PM TRIPS GENERATED FOR
 EACH USE AND ITS SQUARE FOOTAGE FOR EACH BUILDING.THE
 TRAFFIC STATEMENT SHALL INCLUDE THE TRIPS ASSOCIATED
 WITH THE SPECIFIC USE AND A CUMULATIVE TABLE FOR ALL OF
 THE USES APPROVED IN THE PREMIER PARK OF COMMERCE CPD.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435

Review Stop Z ZONING
Rev No 2 Status F Date 2007-06-08 Cont ID  
Sent By eschneid Date 2007-06-08 Time 16:09 Rev Time 0.00
Received By eschneid Date 2007-06-08 Time 16:09 Sent To  
Notes
2007-06-08 16:10:21FAILED
  
 1) RESPOND TO COMMENTS IN WRITING.
  
 2) DUMPSTER AND ADA PARKING DETAILS DO NOT MEET CITY
 CODE (SHEET A3) - REPEAT COMMENT.
  
 3) WHERE IS THE LANDSCAPE AREA FOR THE LONE DUMPSTER
 BEHIND THE BUILDING - REPEAT COMMENT.
  
 4) THE ELEVATIONS DO NOT MATCH THOSE APPROVED BY
 ORDINANCE NO. 3987-06.
  
 5) SIGNS ARE TO BE UNDER A SEPARATE PERMIT.
  
 6) WHERE IS THE LANDSCAPE PLAN?
  
 7) THE 12 FOOT EASEMENT ALONG THE 45TH STREET FRONTAGE
 IS TO BE FOR FUTURE ROAD WIDENING, NOT UTILITY PURPOSES
 AS STATED ON THE SITE PLAN.
  
 8) NOT ALL CONDITIONS OF ORD. NO. 3987-06 HAVE BEEN
 MET:
  
 A) THE PROPERTY OWNER SHALL POST SURETY IN THE AMOUNT
 OF ONE HUNDRED FIFTY THOUSAND DOLLARS ($150,000.00)
 WITHIN TWELVE (12) MONTHS OF THIS DEVELOPMENT ORDER
 (DUE BY OCTOBER 10, 2007) IN A FORM ACCEPTABLE TO THE
 COUNTY ATTORNEY TO ASSURE THE INSTALLATION OF THE
 TRAFFIC SIGNAL WHEN WARRANTED.
  
 B) AT SUCH TIME AS THE PROPERTY OWNER COMPLETES THE
 DRAINAGE PLAN FOR THE PROJECT, THE PROPERTY OWNER SHALL
 NOTIFY THE COUNTY?S ROADWAY PRODUCTION DIVISION IF THE
 PROJECT HAS ANY EXCESS STORMWATER RETENTION CAPACITY
 THAT CAN BE MADE AVAILABLE TO THE COUNTY FOR THE
 WIDENING OF 45TH STREET FROM TWO (2) LANES TO FOUR (4)
 LANES FROM HAVERHILL ROAD TO THE FLORIDA TURNPIKE.IF
 THERE IS EXCESS CAPACITY AVAILABLE, THE PROPERTY OWNER
 SHALL MAKE THAT CAPACITY AVAILABLE TO THE COUNTY
 THROUGH THE DEDICATION OF A TWENTY FOOT (20?) DRAINAGE
 EASEMENT FROM THE ROAD RIGHT-OF-WAY TO THE ULTIMATE
 OUTFALL.THE DRAINAGE EASEMENT SHALL COVER THE ENTIRE
 POND.
  
 C) NO MORE THAN 1,146 NEW DAILY TRIPS MAY BE PERMITTED
 UNTIL CONTRACT IS LET FOR WIDENING OF HAVERHILL ROAD TO
 FIVE (5) LANES, FROM 45TH STREET TO CARIBBEAN
 BOULEVARD.
  
 D) NO BUILDING PERMITS FOR DEVELOPMENT GENERATING MORE
 THAT 85 NEW EXTERNAL PM PEAK HOUR TRIPS PRIOR TO
 LETTING OF THE CONTRACT FOR THE FOUR (4) LANING OF
 HAVERHILL ROAD, FROM BEELINE HIGHWAY TO 45TH STREET.
  
 E) NO BUILDING PERMITS FOR DEVELOPMENT GENERATING MORE
 THAT 103 NEW EXTERNAL PM PEAK HOUR TRIPS PRIOR TO
 LETTING OF THE CONTRACT FOR THE FOLLOWING IMPROVEMENTS
 AT THE INTERSECTION OF HAVERHILL ROAD AND ROEBUCK
 ROAD:
  
 1. ADDITION OF A SECOND EXCLUSIVE NORTHBOUND LEFT TURN
 LANE.
  
 2. ADDITION OF A SECOND EXCLUSIVE EASTBOUND LEFT TURN
 LANE.
  
 3. RECONFIGURE THE WESTBOUND APPROACH TO PROVIDE ONE
 EXCLUSIVE LEFT TURN LANE, TWO THROUGH LANES AND ONE
 EXCLUSIVE RIGHT-TURN LANE.
  
 F) NO BUILDING PERMITS FOR DEVELOPMENT GENERATING MORE
 THAN 261 NEW EXTERNAL AM PEAK HOUR TRIPS PRIOR TO THE
 LETTING OF THE CONTRACT FOR THE ADDITION OF A SECOND
 NORTHBOUND THROUGH LANE AT THE INTERSECTION OF
 HAVERHILL ROAD AND 45TH STREET.
  
 G) WITHIN SIX (6) MONTHS FROM THE DATE OF THE
 DEVELOPMENT ORDER (DUE BY APRIL 10, 2007), THE
 DEVELOPER MUST ENTER INTO A PUBLIC FACILITIES AGREEMENT
 (PFA) WITH PALM BEACH COUNTY TO FUND AND/OR TO
 CONSTRUCT ANY AND ALL IMPROVEMENTS AS THE TERM IS
 DEFINED BY THE TRAFFIC PERFORMANCE STANDARDS ORDINANCE.
 THE PFA MUST BE IN A FORM ACCEPTABLE TO THE COUNTY
 ENGINEER.THE CITY SHALL NOT ISSUE ANY BUILDING
 PERMITS ASSOCIATED WITH THE PROJECT UNLESS AND UNTIL
 THE PFA HAS BEEN APPROVED BY THE BOARD OF COUNTY
 COMMISSIONERS.
  
 H)A USE CHART SHALL BE SUBMITTED TO THE PLANNING AND
 ZONING AND CONSTRUCTION SERVICES DEPARTMENTS CONCURRENT
 WITH ALL BUILDING PERMIT AND/OR OCCUPATIONAL LICENSE
 APPLICATIONS STATING THE SQUARE FOOTAGE DEVOTED TO THE
 USES WITHIN BUILDINGS 1, 2 AND 3.THE SPECIFIC SQUARE
 FOOTAGE USE WITHIN EACH BUILDING MAY NOT EXCEED THE
 ALLOWANCES OUTLINED IN THE BUILDING USE SQUARE FOOTAGE
 TABLE (EXHIBIT F), UNLESS THE PROPERTY OWNER PROVIDES A
 TRAFFIC EQUIVALENCY STATEMENT, PREPARED BY A LICENSED
 TRAFFIC ENGINEER, DEMONSTRATING THAT THE APPROVED
 TRAFFIC CONCURRENCY FOR THE PROJECT IS NOT EXCEEDED.
  
 I)A TRAFFIC STATEMENT, PREPARED BY A LICENSED TRAFFIC
 ENGINEER, SHALL BE SUBMITTED TO THE PLANNING AND ZONING
 AND CONSTRUCTION SERVICES DEPARTMENTS CONCURRENT WITH
 ALL BUILDING PERMIT APPLICATIONS OUTLINING THE NUMBER
 OF DAILY TRIPS, AM TRIPS AND PM TRIPS GENERATED FOR
 EACH USE AND ITS SQUARE FOOTAGE FOR EACH BUILDING.THE
 TRAFFIC STATEMENT SHALL INCLUDE THE TRIPS ASSOCIATED
 WITH THE SPECIFIC USE AND A CUMULATIVE TABLE FOR ALL OF
 THE USES APPROVED IN THE PREMIER PARK OF COMMERCE CPD.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435

Review Stop Z ZONING
Rev No 1 Status F Date 2007-10-18 Cont ID  
Sent By eschneid Date 2006-11-22 Time 16:03 Rev Time 0.00
Received By eschneid Date 2006-11-22 Time 16:03 Sent To  
Notes
2006-11-22 16:13:55FAILED
  
 1) PLANS SHALL MATCH THE APPROVALS OF ORD. NO. 3987-06,
 AS AMENDED BY THE MINOR AMENDMENT APPROVED ON NOV. 27,
 2006.
  
 2) DUMPSTER AND ADA PARKING DETAILS DO NOT MEET CITY
 CODE.
  
 3) WHERE IS THE LANDSCAPE AREA FOR THE LONE DUMPSTER IN
 THE MIDDLE OF THE BUILDING?
  
 4) ALL CONDITIONS OF ORD. NO. 3987-06 SHALL BE ADHERED
 TO FOR THE BUILDING PERMIT SUBMISSION.