Plan Review Details - Permit 06110337
Plan Review Stops For Permit 06110337
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-02-06 Cont ID  
Sent By jwitmer Date 2007-02-06 Time 08:25 Rev Time 1.22
Received By jwitmer Date 2007-02-06 Time 08:25 Sent To PC
Notes
2007-02-06 08:33:47BUILDING PLAN REVIEW
 PERMIT:06110337
 ADD: 55205 GREENWOOD AVE
 CONT: HEDRICK BROTHERS
 TEL: (561568-8931
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION- ADDITIONAL DEMOLITION TO REMOVE THE EXTERIOR
 SKIN OF THE BUILDING.
  
  
  
 BUILDING PROVISO:
 1 ) 109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PERMORMED IN A MANNER
 SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS
 SUCH ACTIVITY IS PERMITTED TO AFFECT
 SAID PROPERTY PURSUANT TO A CONSENT BY
 THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE
 APPLICABLE PROPERTY OWNER.THIS INCLUDES
 BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF,
 DEBRIS, AND THE STORAGE OF CONSTRUCTION
 MATERIALS. NEW CONSTRUCTION ACTIVITY
 SHALL NOT ADVERSELY IMPACT HISTORIC
 SURFACE WATER DRAINAGE FLOWS SERVING
 ADJACENT PROPERTIES, & MAY REQUIRE
 SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES.
 ACCORDINGLY, DEVELOPERS, CONTRACTORS,
 AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR
 ITEMS, ON EXISTING PROPERTIES RESULTING
 IN A DECREASE IN EXCESS OF 800SQ FT OF
 PERMEABLE LAND AREA ON ANY PARCELL SHALL
 AS A PERMIT CONDITION, PROVIDE A
 PROFESSIONALLY PREPARED DRAINAGE PLAN
 CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 2) 109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-01-08 Cont ID  
Sent By jwitmer Date 2007-01-08 Time 16:50 Rev Time 1.33
Received By jwitmer Date 2007-01-08 Time 16:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-12-14 Cont ID  
Sent By jwitmer Date 2006-12-14 Time 15:45 Rev Time 1.22
Received By jwitmer Date 2006-12-14 Time 15:34 Sent To  
Notes
2006-12-14 15:50:22BUILDING PLAN REVIEW
 PERMIT: 06110337
 ADD: 5205 GREENWOOD
 CONT: HEDRICK BROTHERS
 TEL: (561) 689-8880
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1) THE DESIGN PROFESSIONALS PRINTED NAME SHALLAPPEAR
 ON ALL SIGNED AND SEALED SHEERTS.
 FL ADDMINISTRATIVE CODE 61G1-16.004
 61G15-23.002
  
 2) SHEET GV101- THE PLANS CALL OUT FOR THE BUILDING
 DESIGN TO BE A TYPE IV, THIS IS HEAVY TIMBER UNDERTHE
 2004 FBC?
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-01-05 Cont ID  
Sent By dpalmer Date 2007-01-05 Time 19:16 Rev Time 0.00
Received By dpalmer Date 2007-01-05 Time 18:53 Sent To  
Notes
2007-01-05 19:18:41*** REDLINED **
  
 EELECTRICAL DEMO PERMIT REQUIRED. MAY REFERENCE THESE
 PLANS.
  
 INSERTED NEW REVISED SHEET AD-101 NOT INSERTED INTO
 SETS AND REMOVED OLD SHEET IF SAME NUMERICAL
 IDENTIFICATION.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-11-27 Cont ID  
Sent By dpalmer Date 2006-11-27 Time 12:56 Rev Time 0.00
Received By dpalmer Date 2006-11-27 Time 12:25 Sent To  
Notes
2006-11-27 13:00:12** UNSAT **
  
  
 1) NOTE: PLEASE SEE FLORIDA ADMINISTRATIVE CODE
 61G1-16.004 AND 61G15-23.002 WHICH REQUIRES THE PRINTED
 NAME AND LICENSE NUMBER FOR EACH DESIGN PROFESSIONAL.
 THIS IS REQUIRED ON ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY OTHER REVIEWERS.
  
 ** PLEASE KNOW, IF A PERSON FROM THE DESIGN TEAM/
 CONTRACTOSRS OFFICE CAN SET UP AN APPOINTMENT TO COME
 IN AND PLACE EITHER A STAMP OR LABEL ON THE PLAN TITLE
 BLOCKS FOR THIS, THERE ARE CURRENTLY NO ELECTRICAL
 COMMENTS AS THIS IS FOR INTERIOR DEMO ONLY.
  
  
 PLEASE CALL IF THERE ARE ANY QUESTIONS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-01-09 Cont ID  
Sent By mawillia Date 2007-01-09 Time 15:40 Rev Time 0.00
Received By mawillia Date 2007-01-09 Time 15:40 Sent To  
Notes
2007-01-09 17:14:03*****APPROVED***** W/REMINDERS
  
  
  
 **WPBFR FIRE PREVENTION SHALL BE NOTIFIED WHEN IT IS
 NECESSARY TO SHUT DOWN THE FIRE PROTECTION SYSTEM (OR
 PORTION THEREOF) AND WHEN THE SYSTEM IS RETURNED TO
 SERVICE.**
  
 **WPBFR FIRE PREVENTION SHALL HAVE THE AUTHORITY TO
 REQUIRE ALTERNATE MEASURES OF PROTECTION UNTIL THE
 SYSTEM IS RETURNED TO SERVICE.**
  
  
 CAPT. MICHAEL A. WILLIAMS, WPBFR
 BUREAU OF FIRE PREVENTION
 561-804-4724
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-12-12 Cont ID  
Sent By mawillia Date 2006-12-12 Time 09:22 Rev Time 0.00
Received By mawillia Date 2006-12-12 Time 09:09 Sent To  
Notes
2006-12-12 09:43:58*****PROVISO*****
  
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID
 PROPERTY OF THE VICINITY THEREOF.
  
 3.COMBUSTIBLE WASTE, DUST, AND DEBRIS SHALL BE
 REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR MORE
 FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 4.DEMOLITION PLAN NOTE #7 STATES" FIRE ALARM PANEL
 TO REMAIN " .WILL THE FIRE ALARM SYSTEM BE
 OPERATIONAL DURING DEMOLITION OPERATIONS?IF SO, WHAT
 MEASURE(S) WILL BE UTILIZED TO PREVENT FALSE FIRE
 ALARMS?
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-01-31 Cont ID  
Sent By adarroug Date 2007-01-31 Time 14:04 Rev Time 0.00
Received By adarroug Date 2007-01-31 Time 14:03 Sent To B
Notes
2007-01-31 14:04:18TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-12-22 Cont ID  
Sent By adarroug Date 2006-12-22 Time 15:39 Rev Time 0.00
Received By adarroug Date 2006-12-22 Time 15:39 Sent To  
Notes
2007-01-05 18:53:29TO BOB BOARD , SPACE #8. 1/5/07
2006-12-22 15:40:06WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-12-14 Cont ID  
Sent By jwitmer Date 2006-12-14 Time 15:34 Rev Time 0.00
Received By jwitmer Date 2006-11-12 Time 14:28 Sent To  
Notes
2006-11-27 09:12:01TO "BOB"#12
2006-11-12 14:29:07WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-01-08 Cont ID  
Sent By tgordon Date 2007-01-08 Time 13:34 Rev Time 0.25
Received By tgordon Date 2007-01-08 Time 13:34 Sent To  
Notes
2007-01-08 13:35:04REMOVAL OF A/C SYSTEMS AND BATHROOM EXHAUST UNITS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-11-27 Cont ID  
Sent By tgordon Date 2006-11-27 Time 10:59 Rev Time 0.30
Received By tgordon Date 2006-11-27 Time 10:59 Sent To  
Notes
2006-11-27 11:01:05REMOVAL OF A/C SYSTEMS AND BATHROOM EXHAUST UNITS.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-01-09 Cont ID  
Sent By jleech Date 2007-01-09 Time 07:01 Rev Time 0.00
Received By jleech Date 2007-01-09 Time 07:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-12-11 Cont ID  
Sent By jleech Date 2006-12-11 Time 09:25 Rev Time 0.00
Received By jleech Date 2006-12-11 Time 09:24 Sent To  
Notes
2006-12-11 09:38:27DENIED;
 1.PRINTED NAME AND LICENSE NUMBER REQUIRED. SEE
 ELECTRICAL PLAN REVIEWER'S NOTE.
 2. NO DEAD ENDS PERMITED IN THE DRAINAGE SYSTEM. ALL
 SANITARYAND VENT PIPING THAT WILL NOT BE RE-USED IN
 THE SAME LOCATION SHALL BE REMOVED TO WITHIN 2' OF THE
 BUILDING DRAIN. FBC-2004 PLUMBING SECTION 704.5.
 3. A PLUMBING PERMIT IS REQUIRED BY A LICENSED PLUMBING
 CONTRACTOR TO DO THE PLUMBING DEMO. PLUMBING
 INSPECTIONS REQUIRED
 PLEASE ADD NOTES ON PLANS TO COVER NOTE 2 AND 3
 .
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695