| Plan Review Stops For Permit 06110327 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2007-03-09 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-03-09 |
Time |
14:04 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-03-09 |
Time |
13:52 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-03-06 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-03-06 |
Time |
07:36 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-03-06 |
Time |
05:55 |
Sent To |
PC |
|
| Notes |
| 2007-03-06 07:36:21 | BUILDING PLAN REVIEW | | | PERMIT: | | | ADD: | | | CONT: | | | TEL: (561)###-#### | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2)AGAIN*** ALL PLANS SUBMITTED AFTER OCTOBER, 1ST, | | | 2004 SHALL BE DESIGNED TO THE 2004 FLORIDA BUILDING | | | CODE. SEE SHEET #2. | | | | | | 3)F.S. 471.025ALL FINAL DRAWINGS, SPECIFICATIONS, | | | PLANS, REPORTS, OR DOCUMENTS PREPARED OR ISSUED BY THE | | | LICENSEE AND BEING FILED FOR PUBLIC RECORD AND ALL | | | FINAL DOCUMENTS PROVIDED TO THE OWNER OR THE OWNERS'S | | | REPRESENTATIVE SHALL BE SIGNED BY THE LICENSEE, DATED | | | AND SEALEW WITH SAID SEAL. SUCH SIGNATURE, DATE, AND | | | SEALSHALL BE EVIDENCE OF THE AUTHENTICITY OFTHAT TO | | | WHICH THEY ARE AFFIXED.THE INFORMATION FOR THE HEATER | | | TIE- DOWN HAS PHOTO-COPIED SEAL AND SIGNATURE OF THE | | | ENGINEER WHICH IS NOT ACCEPTABLE. THE ENGINEER SEAL AND | | | SIGNATURE SHALL BE ORIGINAL. | | | | | | 4)WPB AMENDMENTS 108.3*THE CLAIMED VALUAATION ON | | | THE PERMIT APPLICATION IS LOW. FOR PERMITTING PURPOSES, | | | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL | | | REEPLACEMENT COST EXCLUDING LAND VALUE.OUR VALUATION | | | REFERENCE IS ICC (BVD), MARSHALL-SWIFT AND MEANS COST | | | ANALYSIS. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | 805-6726 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-02-12 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-03-05 |
Time |
11:19 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-02-12 |
Time |
07:45 |
Sent To |
PC |
|
| Notes |
| 2007-02-12 09:20:58 | BUILDING PLAN REVIEW | | | PERMIT: 06110327 | | | ADD: 3008 EL CAMINO REAL | | | CONT: CUSHING POOLS CONST. INC. | | | TEL: (561)798-1441 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW 1ST | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2)ALL PLANS SUBMITTED AFTER OCTOBER, 1, | | | 2004 SHALL BE DESIGNED TO THE 2004 | | | FLORIDA BUILDING CODE. SEE SHEET #2 | | | | | | 3) WPB AMENDMENTS 108.3*THE CLAIMED VALUAATION ON THE | | | PERMIT APPLICATION IS LOW. FOR PERMITTING PURPOSES, | | | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL | | | REEPLACEMENT COST EXCLUDING LAND VALUE.OUR VALUATION | | | REFERENCE IS ICC (BVD), MARSHALL-SWIFT AND MEANS COST | | | ANALYSIS. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | 805-6726 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2007-03-05 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-03-05 |
Time |
09:55 |
Rev Time |
0.33 |
| Received By |
btrobaug |
Date |
2007-03-05 |
Time |
09:25 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-02-05 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-02-05 |
Time |
16:44 |
Rev Time |
0.33 |
| Received By |
btrobaug |
Date |
2007-02-05 |
Time |
16:35 |
Sent To |
P |
|
| Notes |
| 2007-02-05 16:49:53 | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} THE HEAT PUMP INDICATED IN THE SPECIFICATIONS IS NOT | | | ON THE SCHEMATIC. | | | | | | 2} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2. FBC. | | | THIS APPLIES TO THE LOAD CALCULATION, ALSO PUT THE | | | ADDRESS ON SAME. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2007-02-07 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-02-07 |
Time |
10:58 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2007-02-07 |
Time |
10:58 |
Sent To |
B |
|
| Notes |
| 2007-02-07 10:59:14 | NOTE: ELECTRIC HEAT PUMP |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2007-03-09 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-03-09 |
Time |
13:35 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-03-09 |
Time |
13:35 |
Sent To |
B |
|
| Notes |
| 2007-03-09 13:36:05 | TO "MJACOBS" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2007-02-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-02-27 |
Time |
10:06 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-02-27 |
Time |
10:06 |
Sent To |
E |
|
| Notes |
| 2007-02-27 10:07:12 | TO "BTROBAUG" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-02-22 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-02-22 |
Time |
13:29 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-02-22 |
Time |
13:29 |
Sent To |
Z |
|
| Notes |
| 2007-02-22 13:30:12 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-02-05 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-02-05 |
Time |
14:00 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-02-05 |
Time |
14:00 |
Sent To |
E |
|
| Notes |
| 2007-02-05 14:03:10 | TO "E" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-01-30 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-01-30 |
Time |
11:50 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-01-30 |
Time |
11:50 |
Sent To |
Z |
|
| Notes |
| 2007-01-30 11:51:27 | TO "Z" BOX/RESUB--ONLY REVIEWED BY "Z" FIRST TIME | | | AROUND |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-11-15 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-11-15 |
Time |
10:46 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-11-12 |
Time |
15:17 |
Sent To |
|
|
| Notes |
| 2006-11-12 15:17:27 | TO "Z" BOX |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2007-02-07 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2007-02-07 |
Time |
10:57 |
Rev Time |
0.33 |
| Received By |
mperson |
Date |
2007-02-07 |
Time |
10:57 |
Sent To |
G |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2007-02-25 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2007-02-25 |
Time |
18:36 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2007-02-25 |
Time |
18:36 |
Sent To |
I |
|
| Notes |
| 2007-02-25 18:38:37 | ***PROVISO*** | | | | | | 1) PER SECTION 94-304 OF THE CITY OF WPB ZONING AND | | | LAND DEVELOPMENT REGULATIONS, EVERY SWIMMING POOL SHALL | | | BE ENCLOSED BY A FENCE OR SIMILAR STRUCTURE WHICH IS | | | INSTALLED TO OBSTRUCT ACCESS BY PERSONS OTHER THAN THE | | | OWNERS OR OCCUPANTS OF THE RESIDENCE.BARRIERS/FENCES | | | SHALL BE A MINIMUM OF FOUR (4) FEET IN HEIGHT. | | | | | | QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER, | | | AT (561) 822-1435. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2007-02-03 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2007-02-03 |
Time |
11:28 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2007-02-03 |
Time |
11:28 |
Sent To |
I |
|
| Notes |
| 2007-02-03 11:33:13 | PER ANDREINA DAVILA, ANGELLA & ERIC MADE AN | | | ADMINISTRATIVE APPROVAL THAT THE PROPOSED POOL LOCATION | | | IS CONSIDERED THE SIDE PROPERTY.THE PROPOSED POOL | | | DOES NOT NEED A VARIANCE. | | 2007-02-03 11:29:54 | DENIED, 2ND REQUEST. | | | 1. PLEASE SHOW THE LOCATION OF THE PROPOSED POOL | | | EQUIPMENT ON THE TWO COPIES OF SURVEYS. | | | 2. THE SUBMITTED SURVEYS DOES NOT SHOW THE POOL | | | EQUIPMENT LOCATION. | | | | | | NOTE:SEC 94-303 MECHANICAL/POOL EQUIPMENT/GENERATOR | | | MAY NOT PROJECT MORE THAN FOUR FEET INTO A SETBACK. | | | | | | MICHELLE MCLEAN | | | ZONING TECHNICIAN | | | 805-6720 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2006-11-14 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-11-14 |
Time |
10:33 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-11-14 |
Time |
10:32 |
Sent To |
|
|
| Notes |
| 2006-11-15 10:45:36 | DENIED, | | | 1. THE PROPOSED POOL DOES NOT MEET THE REQUIRED FRONT | | | SETBACK OF 25FT FROM FRONT PROPERTY LINE. | | | 2. NEED CLARIFICATION FOR THE SIDE SETBACK FOR THE POOL | | | (SHOWS 4",3 2') ON THE TWO COPY OF SURVEYS? | | | 3. NEED TO SHOW THE POOL EQUIPMENT ON TWO COPIES OF | | | SURVEYS. | | | 4. NEED TO APPLY FOR A VARIANCE WITH THE PLANNING & | | | ZONING DEPT FOR THE LOCATION OF THE POOL. | | | 5. THE PROPOSED POOL (DIMENSION) WILL NOT MEET THE | | | REQUIRED FRONT SETBACK. | | | | | | MICHELLE MCLEAN | | | ZONING TECHNICIAN | | | 805-6720 |
|
|