Plan Review Details - Permit 06110327
Plan Review Stops For Permit 06110327
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-03-09 Cont ID  
Sent By mjacobs Date 2007-03-09 Time 14:04 Rev Time 0.00
Received By mjacobs Date 2007-03-09 Time 13:52 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-03-06 Cont ID  
Sent By mjacobs Date 2007-03-06 Time 07:36 Rev Time 0.00
Received By mjacobs Date 2007-03-06 Time 05:55 Sent To PC
Notes
2007-03-06 07:36:21BUILDING PLAN REVIEW
 PERMIT:
 ADD:
 CONT:
 TEL: (561)###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)AGAIN*** ALL PLANS SUBMITTED AFTER OCTOBER, 1ST,
 2004 SHALL BE DESIGNED TO THE 2004 FLORIDA BUILDING
 CODE. SEE SHEET #2.
  
 3)F.S. 471.025ALL FINAL DRAWINGS, SPECIFICATIONS,
 PLANS, REPORTS, OR DOCUMENTS PREPARED OR ISSUED BY THE
 LICENSEE AND BEING FILED FOR PUBLIC RECORD AND ALL
 FINAL DOCUMENTS PROVIDED TO THE OWNER OR THE OWNERS'S
 REPRESENTATIVE SHALL BE SIGNED BY THE LICENSEE, DATED
 AND SEALEW WITH SAID SEAL. SUCH SIGNATURE, DATE, AND
 SEALSHALL BE EVIDENCE OF THE AUTHENTICITY OFTHAT TO
 WHICH THEY ARE AFFIXED.THE INFORMATION FOR THE HEATER
 TIE- DOWN HAS PHOTO-COPIED SEAL AND SIGNATURE OF THE
 ENGINEER WHICH IS NOT ACCEPTABLE. THE ENGINEER SEAL AND
 SIGNATURE SHALL BE ORIGINAL.
  
 4)WPB AMENDMENTS 108.3*THE CLAIMED VALUAATION ON
 THE PERMIT APPLICATION IS LOW. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL
 REEPLACEMENT COST EXCLUDING LAND VALUE.OUR VALUATION
 REFERENCE IS ICC (BVD), MARSHALL-SWIFT AND MEANS COST
 ANALYSIS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-02-12 Cont ID  
Sent By btrobaug Date 2007-03-05 Time 11:19 Rev Time 0.00
Received By mjacobs Date 2007-02-12 Time 07:45 Sent To PC
Notes
2007-02-12 09:20:58BUILDING PLAN REVIEW
 PERMIT: 06110327
 ADD: 3008 EL CAMINO REAL
 CONT: CUSHING POOLS CONST. INC.
 TEL: (561)798-1441
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)ALL PLANS SUBMITTED AFTER OCTOBER, 1,
 2004 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE. SEE SHEET #2
  
 3) WPB AMENDMENTS 108.3*THE CLAIMED VALUAATION ON THE
 PERMIT APPLICATION IS LOW. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL
 REEPLACEMENT COST EXCLUDING LAND VALUE.OUR VALUATION
 REFERENCE IS ICC (BVD), MARSHALL-SWIFT AND MEANS COST
 ANALYSIS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-03-05 Cont ID  
Sent By btrobaug Date 2007-03-05 Time 09:55 Rev Time 0.33
Received By btrobaug Date 2007-03-05 Time 09:25 Sent To B
Notes
2007-03-05 09:55:24 
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-02-05 Cont ID  
Sent By btrobaug Date 2007-02-05 Time 16:44 Rev Time 0.33
Received By btrobaug Date 2007-02-05 Time 16:35 Sent To P
Notes
2007-02-05 16:49:53 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE HEAT PUMP INDICATED IN THE SPECIFICATIONS IS NOT
 ON THE SCHEMATIC.
  
 2} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2. FBC.
 THIS APPLIES TO THE LOAD CALCULATION, ALSO PUT THE
 ADDRESS ON SAME.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2007-02-07 Cont ID  
Sent By mperson Date 2007-02-07 Time 10:58 Rev Time 0.00
Received By mperson Date 2007-02-07 Time 10:58 Sent To B
Notes
2007-02-07 10:59:14NOTE: ELECTRIC HEAT PUMP

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-03-09 Cont ID  
Sent By adarroug Date 2007-03-09 Time 13:35 Rev Time 0.00
Received By adarroug Date 2007-03-09 Time 13:35 Sent To B
Notes
2007-03-09 13:36:05TO "MJACOBS" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-02-27 Cont ID  
Sent By adarroug Date 2007-02-27 Time 10:06 Rev Time 0.00
Received By adarroug Date 2007-02-27 Time 10:06 Sent To E
Notes
2007-02-27 10:07:12TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-02-22 Cont ID  
Sent By adarroug Date 2007-02-22 Time 13:29 Rev Time 0.00
Received By adarroug Date 2007-02-22 Time 13:29 Sent To Z
Notes
2007-02-22 13:30:12TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-02-05 Cont ID  
Sent By adarroug Date 2007-02-05 Time 14:00 Rev Time 0.00
Received By adarroug Date 2007-02-05 Time 14:00 Sent To E
Notes
2007-02-05 14:03:10TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-01-30 Cont ID  
Sent By adarroug Date 2007-01-30 Time 11:50 Rev Time 0.00
Received By adarroug Date 2007-01-30 Time 11:50 Sent To Z
Notes
2007-01-30 11:51:27TO "Z" BOX/RESUB--ONLY REVIEWED BY "Z" FIRST TIME
 AROUND

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-11-15 Cont ID  
Sent By mmclean Date 2006-11-15 Time 10:46 Rev Time 0.00
Received By mmclean Date 2006-11-12 Time 15:17 Sent To  
Notes
2006-11-12 15:17:27TO "Z" BOX

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-02-07 Cont ID  
Sent By mmclean Date 2007-02-07 Time 10:57 Rev Time 0.33
Received By mperson Date 2007-02-07 Time 10:57 Sent To G
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2007-02-25 Cont ID  
Sent By jroach Date 2007-02-25 Time 18:36 Rev Time 0.00
Received By jroach Date 2007-02-25 Time 18:36 Sent To I
Notes
2007-02-25 18:38:37***PROVISO***
  
 1) PER SECTION 94-304 OF THE CITY OF WPB ZONING AND
 LAND DEVELOPMENT REGULATIONS, EVERY SWIMMING POOL SHALL
 BE ENCLOSED BY A FENCE OR SIMILAR STRUCTURE WHICH IS
 INSTALLED TO OBSTRUCT ACCESS BY PERSONS OTHER THAN THE
 OWNERS OR OCCUPANTS OF THE RESIDENCE.BARRIERS/FENCES
 SHALL BE A MINIMUM OF FOUR (4) FEET IN HEIGHT.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 2 Status F Date 2007-02-03 Cont ID  
Sent By mmclean Date 2007-02-03 Time 11:28 Rev Time 0.00
Received By mmclean Date 2007-02-03 Time 11:28 Sent To I
Notes
2007-02-03 11:33:13PER ANDREINA DAVILA, ANGELLA & ERIC MADE AN
 ADMINISTRATIVE APPROVAL THAT THE PROPOSED POOL LOCATION
 IS CONSIDERED THE SIDE PROPERTY.THE PROPOSED POOL
 DOES NOT NEED A VARIANCE.
2007-02-03 11:29:54DENIED, 2ND REQUEST.
 1. PLEASE SHOW THE LOCATION OF THE PROPOSED POOL
 EQUIPMENT ON THE TWO COPIES OF SURVEYS.
 2. THE SUBMITTED SURVEYS DOES NOT SHOW THE POOL
 EQUIPMENT LOCATION.
  
 NOTE:SEC 94-303 MECHANICAL/POOL EQUIPMENT/GENERATOR
 MAY NOT PROJECT MORE THAN FOUR FEET INTO A SETBACK.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2006-11-14 Cont ID  
Sent By mmclean Date 2006-11-14 Time 10:33 Rev Time 0.00
Received By mmclean Date 2006-11-14 Time 10:32 Sent To  
Notes
2006-11-15 10:45:36DENIED,
 1. THE PROPOSED POOL DOES NOT MEET THE REQUIRED FRONT
 SETBACK OF 25FT FROM FRONT PROPERTY LINE.
 2. NEED CLARIFICATION FOR THE SIDE SETBACK FOR THE POOL
 (SHOWS 4",3 2') ON THE TWO COPY OF SURVEYS?
 3. NEED TO SHOW THE POOL EQUIPMENT ON TWO COPIES OF
 SURVEYS.
 4. NEED TO APPLY FOR A VARIANCE WITH THE PLANNING &
 ZONING DEPT FOR THE LOCATION OF THE POOL.
 5. THE PROPOSED POOL (DIMENSION) WILL NOT MEET THE
 REQUIRED FRONT SETBACK.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720