Plan Review Details - Permit 06110326
Plan Review Stops For Permit 06110326
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-01-25 Cont ID  
Sent By jwitmer Date 2007-01-25 Time 06:52 Rev Time 1.11
Received By jwitmer Date 2007-01-25 Time 06:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-12-11 Cont ID  
Sent By jwitmer Date 2006-12-11 Time 12:55 Rev Time 1.55
Received By jwitmer Date 2006-12-11 Time 12:55 Sent To  
Notes
2006-12-11 13:12:34PASSED
 REFLECTING POOL & FOUNTAIN:
 NOT BUILT INTO A THRESHOLD BUILDING, NOT REQUIRED TO
 HAVE (3) SETS OF PLANS.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-01-30 Cont ID  
Sent By dpalmer Date 2007-01-30 Time 18:05 Rev Time 0.00
Received By dpalmer Date 2007-01-30 Time 18:05 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-01-25 Cont ID  
Sent By dpalmer Date 2007-01-25 Time 12:39 Rev Time 0.00
Received By dpalmer Date 2007-01-25 Time 12:10 Sent To PC
Notes
2007-01-25 12:45:42*** UNSAT 2ND REVIEW**
  
 1) NOTE:PLEASE SEE NOTE #1 FROM PREVIOUS REVIEW.
 PLANS AND SHEETS FOR EQUIPMENT, LIGHTING FEEDS ETC DO
 NOT CORRELATE. PLEASE SEE THERE ARE SEVERAL
 DIFFERENCES.
 PLEASE SEE ONE WHICH INDICATES ANEW SERVICE AND
 METER, ONE WHICH INDICATES MORE THAN ONE PANEL FEEDING
 LIGHTS, ETC.
 NO GFI PROTECTION, ETC.
  
 ** PLEASE CORRELATE ALL SHEETS, PLEASE COMPLETE PLANS
 FOR 2002 NEC CODE COMPLIANCE.
  
 2) NOTE: PLEASE SEE FS 553.80(2)(B).
  
  
 ** PLEASE BE SURE TO KEEP ANY SHEETS WHICH CONTAIN
 PLUMBIING STAMPS.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-11-21 Cont ID  
Sent By dpalmer Date 2006-11-21 Time 15:52 Rev Time 0.00
Received By dpalmer Date 2006-11-21 Time 15:02 Sent To  
Notes
2006-11-21 15:52:59*** UNSAT***
  
 ** PLEASE KNOW PERMIT PACKAGE CONTAIN ONE PLAN FOR
 COMMERCIAL POOL AND ONE FOR FOUNTAIN. LOCATED THE OTHER
 SET OF PLANS AND PLACED ALL SETS IN TO EACH OF THEIR
 RESPECTIVE PACKAGES.
  
 1) NOTE:PLEASE KNOW THAT THE PLANS FOR THE ELECTRICAL
 DETAIL SHALL BE SPECIFIC TO THE SCOPE OF WORK ON THE
 JOB APPLIED FOR. PLEASE SEE ELECTRICAL DETAIL SUBMITTED
 ON 4OF4 DOES NOT CORRELATE WITH EQUIPMENT FOR
 REFLECTING FOUNTAINS ETC.
 PLEASE SUBMIT COMPLETED PLANS FOR THIS AND PLEASE BE
 SURE TO INDICATE WHERE THESE ARE BEING FED FROM.
  
 PLEASE SEE 680
 FBC 106.3.5.1.2,106.3.5.5 ADMIN SECTION.
  
 2) NOTE: PLEASE KNOW AS THIS IS A THRESHOLD/ON-SITE
 INSPECTOR JOB, THREE SETS OF ALL PLANS MUST BE
 SUBMITTED.
 109.3.6, 106.1.2 ADMIN SECTION.
  
 ** PLEASE KNOW AS INFORMATION NEEDED WAS NOT SUBMITTED
 AT THIS TIME THEIR MAY BE COMMENTS ON THE FOLLOWING
 REVIEW.
  
 ** ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
 **IF THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF
 THE NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE
 DO NOT HESITATEIN CONTACTING THIS REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-01-17 Cont ID  
Sent By adarroug Date 2007-01-17 Time 11:56 Rev Time 0.00
Received By adarroug Date 2007-01-17 Time 11:56 Sent To Z
Notes
2007-01-17 11:56:47TO "Z" BOX/RESUB--NEW SHEETS FOR "Z" AND "BLDG"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-12-21 Cont ID  
Sent By mperson Date 2006-12-21 Time 16:24 Rev Time 0.00
Received By mperson Date 2006-11-13 Time 11:32 Sent To  
Notes
2006-11-17 13:16:02TO "COMM" BD#36
2006-11-13 11:33:39WAITING FOR "COMM" BD

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-01-24 Cont ID  
Sent By mperson Date 2007-01-24 Time 08:46 Rev Time 0.00
Received By mperson Date 2007-01-24 Time 08:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-12-21 Cont ID  
Sent By mperson Date 2006-12-21 Time 16:14 Rev Time 0.33
Received By mperson Date 2006-12-21 Time 16:14 Sent To  
Notes
2006-12-21 16:24:26DENIED
 REFERENCE: FBC-2004 SECTION 424 SWIMMING POOLS
  
 1. PLEASE CLARIFY ON SHEET 2 OF 4 SECTION C-2 DETAIL
 THE DIFERENCES OF THE INDICATED WATER LEVELS, ONE
 INDICATES WATER DEPTH SHALL NOT EXCEED 18", AND ON THE
 DETAIL IT INDICATES A MEASUREMENT OF 2'-2" PLEASE
 CORRELATE ON THE RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop Z ZONING
Rev No 3 Status P Date 2007-01-22 Cont ID  
Sent By jroach Date 2007-01-22 Time 23:02 Rev Time 0.00
Received By jroach Date 2007-01-22 Time 23:02 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2006-11-30 Cont ID  
Sent By jroach Date 2006-11-30 Time 16:38 Rev Time 0.00
Received By jroach Date 2006-11-30 Time 16:38 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2006-11-20 Cont ID  
Sent By jroach Date 2006-11-20 Time 11:46 Rev Time 0.00
Received By jroach Date 2006-11-20 Time 11:46 Sent To  
Notes
2006-11-20 11:48:31***FAILED***
  
 1) AT LEAST TWO (2) SETS OF ALL PLANS SHALL BE
 PROVIDED.ONLY ONE (1) SET WAS PROVIDED FOR THE
 REFLECTING POOL/FOUNTAINS.THE OTHER SET WAS FOR THE
 SWIMMING POOL.
  
 2) PERMIT APPLICATION INDICATES FOUNTAIN AND REFLECTING
 POOL....IS THE SWIMMING POOL A PART OF THIS PERMIT
 APPLICATION?PLEASE CLARIFY.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.