| Plan Review Stops For Permit 06110326 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2007-01-25 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-01-25 |
Time |
06:52 |
Rev Time |
1.11 |
| Received By |
jwitmer |
Date |
2007-01-25 |
Time |
06:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2006-12-11 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-12-11 |
Time |
12:55 |
Rev Time |
1.55 |
| Received By |
jwitmer |
Date |
2006-12-11 |
Time |
12:55 |
Sent To |
|
|
| Notes |
| 2006-12-11 13:12:34 | PASSED | | | REFLECTING POOL & FOUNTAIN: | | | NOT BUILT INTO A THRESHOLD BUILDING, NOT REQUIRED TO | | | HAVE (3) SETS OF PLANS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2007-01-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-01-30 |
Time |
18:05 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-01-30 |
Time |
18:05 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-01-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-01-25 |
Time |
12:39 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-01-25 |
Time |
12:10 |
Sent To |
PC |
|
| Notes |
| 2007-01-25 12:45:42 | *** UNSAT 2ND REVIEW** | | | | | | 1) NOTE:PLEASE SEE NOTE #1 FROM PREVIOUS REVIEW. | | | PLANS AND SHEETS FOR EQUIPMENT, LIGHTING FEEDS ETC DO | | | NOT CORRELATE. PLEASE SEE THERE ARE SEVERAL | | | DIFFERENCES. | | | PLEASE SEE ONE WHICH INDICATES ANEW SERVICE AND | | | METER, ONE WHICH INDICATES MORE THAN ONE PANEL FEEDING | | | LIGHTS, ETC. | | | NO GFI PROTECTION, ETC. | | | | | | ** PLEASE CORRELATE ALL SHEETS, PLEASE COMPLETE PLANS | | | FOR 2002 NEC CODE COMPLIANCE. | | | | | | 2) NOTE: PLEASE SEE FS 553.80(2)(B). | | | | | | | | | ** PLEASE BE SURE TO KEEP ANY SHEETS WHICH CONTAIN | | | PLUMBIING STAMPS. | | | | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-11-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-11-21 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-11-21 |
Time |
15:02 |
Sent To |
|
|
| Notes |
| 2006-11-21 15:52:59 | *** UNSAT*** | | | | | | ** PLEASE KNOW PERMIT PACKAGE CONTAIN ONE PLAN FOR | | | COMMERCIAL POOL AND ONE FOR FOUNTAIN. LOCATED THE OTHER | | | SET OF PLANS AND PLACED ALL SETS IN TO EACH OF THEIR | | | RESPECTIVE PACKAGES. | | | | | | 1) NOTE:PLEASE KNOW THAT THE PLANS FOR THE ELECTRICAL | | | DETAIL SHALL BE SPECIFIC TO THE SCOPE OF WORK ON THE | | | JOB APPLIED FOR. PLEASE SEE ELECTRICAL DETAIL SUBMITTED | | | ON 4OF4 DOES NOT CORRELATE WITH EQUIPMENT FOR | | | REFLECTING FOUNTAINS ETC. | | | PLEASE SUBMIT COMPLETED PLANS FOR THIS AND PLEASE BE | | | SURE TO INDICATE WHERE THESE ARE BEING FED FROM. | | | | | | PLEASE SEE 680 | | | FBC 106.3.5.1.2,106.3.5.5 ADMIN SECTION. | | | | | | 2) NOTE: PLEASE KNOW AS THIS IS A THRESHOLD/ON-SITE | | | INSPECTOR JOB, THREE SETS OF ALL PLANS MUST BE | | | SUBMITTED. | | | 109.3.6, 106.1.2 ADMIN SECTION. | | | | | | ** PLEASE KNOW AS INFORMATION NEEDED WAS NOT SUBMITTED | | | AT THIS TIME THEIR MAY BE COMMENTS ON THE FOLLOWING | | | REVIEW. | | | | | | ** ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. | | | **IF THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF | | | THE NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE | | | DO NOT HESITATEIN CONTACTING THIS REVIEWER. | | | | | | | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-01-17 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-01-17 |
Time |
11:56 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-01-17 |
Time |
11:56 |
Sent To |
Z |
|
| Notes |
| 2007-01-17 11:56:47 | TO "Z" BOX/RESUB--NEW SHEETS FOR "Z" AND "BLDG" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-12-21 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2006-12-21 |
Time |
16:24 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2006-11-13 |
Time |
11:32 |
Sent To |
|
|
| Notes |
| 2006-11-17 13:16:02 | TO "COMM" BD#36 | | 2006-11-13 11:33:39 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2007-01-24 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-01-24 |
Time |
08:46 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2007-01-24 |
Time |
08:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2006-12-21 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2006-12-21 |
Time |
16:14 |
Rev Time |
0.33 |
| Received By |
mperson |
Date |
2006-12-21 |
Time |
16:14 |
Sent To |
|
|
| Notes |
| 2006-12-21 16:24:26 | DENIED | | | REFERENCE: FBC-2004 SECTION 424 SWIMMING POOLS | | | | | | 1. PLEASE CLARIFY ON SHEET 2 OF 4 SECTION C-2 DETAIL | | | THE DIFERENCES OF THE INDICATED WATER LEVELS, ONE | | | INDICATES WATER DEPTH SHALL NOT EXCEED 18", AND ON THE | | | DETAIL IT INDICATES A MEASUREMENT OF 2'-2" PLEASE | | | CORRELATE ON THE RESUBMITTAL. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2007-01-22 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2007-01-22 |
Time |
23:02 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2007-01-22 |
Time |
23:02 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2006-11-30 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2006-11-30 |
Time |
16:38 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2006-11-30 |
Time |
16:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2006-11-20 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2006-11-20 |
Time |
11:46 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2006-11-20 |
Time |
11:46 |
Sent To |
|
|
| Notes |
| 2006-11-20 11:48:31 | ***FAILED*** | | | | | | 1) AT LEAST TWO (2) SETS OF ALL PLANS SHALL BE | | | PROVIDED.ONLY ONE (1) SET WAS PROVIDED FOR THE | | | REFLECTING POOL/FOUNTAINS.THE OTHER SET WAS FOR THE | | | SWIMMING POOL. | | | | | | 2) PERMIT APPLICATION INDICATES FOUNTAIN AND REFLECTING | | | POOL....IS THE SWIMMING POOL A PART OF THIS PERMIT | | | APPLICATION?PLEASE CLARIFY. | | | | | | QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER, | | | AT (561) 822-1435. |
|
|