Plan Review Details - Permit 06110325
Plan Review Stops For Permit 06110325
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-01-24 Cont ID  
Sent By jwitmer Date 2007-01-24 Time 16:26 Rev Time 1.11
Received By jwitmer Date 2007-01-24 Time 16:26 Sent To  
Notes
2007-01-24 16:38:01BUILDING PLAN REVIEW
 PERMIT:06110325
 ADD: 1611 WORTHINGTON RD.
 CONT: POOL TEK OF THE PALM BEACHES
 TEL: (561)514-1514
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 ---BUILDING REVIEW ----
  
 *** ISSUED PERMIT***
 -PLAN REVIEW HISTORY-
  
 THEATTACHED COMMENTS ARE PART OF THE
 PERMIT AND PLAN REVIEW PACKAGE AND ARE
 NOT TO BE REMOVED FROM THE ISSUED SET
 OF PLANS.104.2.1.2 ADMINISTRATIVE CODE.
  
 BUILDING PROVISO:
 13-412.1.ABC.2.6.2 COVERS REQUIRED.
 SPAS AND HEATED SWIMMING POOLS SHALL BE
 EQUIPPED WITH A COVER DESIGNED TO
 MINIMIZE HEAT LOSS AT TIME OF C/O.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-12-11 Cont ID  
Sent By jwitmer Date 2006-12-11 Time 13:18 Rev Time 1.11
Received By jwitmer Date 2006-12-11 Time 13:18 Sent To  
Notes
2006-12-11 13:24:59BUILDING PLAN REVIEW
 PERMIT: 06110325
 ADD: 1611 WORTHINGTON RD
 CONT: POOL TEC
 TEL: (561)514-1514
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
 13-412.1.ABC.2.6.2 POOL COVERS.
 HEATED POOLS SHALL BE EQUIPPED WITH A VAPOR RETARDANT
 POOL
 COVER ON OR AT THE WATER SURFACE. POOLS HEATED TO MORE
 THAN
 90?F (32?C) SHALL HAVE A POOL COVER WITH A MINIMUM
 INSULATION
 VALUE OF R -12.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-01-30 Cont ID  
Sent By dpalmer Date 2007-01-30 Time 17:44 Rev Time 0.00
Received By dpalmer Date 2007-01-30 Time 17:44 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-01-25 Cont ID  
Sent By dpalmer Date 2007-01-25 Time 13:02 Rev Time 0.00
Received By dpalmer Date 2007-01-25 Time 12:56 Sent To PC
Notes
2007-01-25 13:04:38*** UNSAT 2ND REVIEW**
  
 1) NOTE:PLEASE SEE NOTES FROM PREVIOUS REVIEW. PLANS
 AND SHEETS FOR EQUIPMENT, LIGHTING FEEDS ETC DO NOT
 CORRELATE. PLEASE SEE THERE ARE SEVERAL DIFFERENCES.
 NO GFI PROTECTION, ETC.
  
 ** PLEASE CORRELATE ALL SHEETS; PLEASE COMPLETE PLANS
 FOR 2002 NEC, 215.5, 680, 240.4, 310.16 ETC FOR CODE
 COMPLIANCE.
  
 2) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. ONE SET OF ELEC IS
 BEING RETAINED SHEETS 4 AND 5.
  
 3) NOTE:PLEASE KNOW THAT THE PLANS FOR THE ELECTRICAL
 DETAIL SHALL BE SPECIFIC TO THE SCOPE OF WORK ON THE
 JOB APPLIED FOR. PLEASE CORRELATE EQUIPMENT WITH NEW
 PROPOSED PANEL SCHEDULE AS SOME EQUIPMENT SHOWN IS NOT
 ON SCHEDULE?
 PLEASE SEE THE PANELS AS SHOWN ON PLANS DO NOT
 CORRELATE.
 408.4, 310.16,
 FBC 106.1.2
 FBC 106.3.5.1.2,106.3.5.5 ADMIN SECTION.
  
 4) NOTE: PLEASE LIST THE FEEDER TO THE NEW VAK-PAK
 PANEL.
 215.5, 215.3.
  
 5) NOTE: PLEASE COMPLETE THE LOAD CALCULATIONS FOR ALL
 AND INDICATE THE CONTINUOUS LOADS AT 125%.
 215.3, 230.42 ETC.
 ** PLEASE BE SURE TO KEEP ANY SHEETS WHICH CONTAIN
 PLUMBING STAMPS.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-11-21 Cont ID  
Sent By dpalmer Date 2006-11-21 Time 16:08 Rev Time 0.00
Received By dpalmer Date 2006-11-21 Time 15:57 Sent To  
Notes
2006-11-21 16:08:51*** UNSAT***
  
 ** PLEASE KNOW PERMIT PACKAGE CONTAIN ONE PLAN FOR
 COMMERCIAL POOL AND ONE FOR FOUNTAIN. LOCATED THE OTHER
 SET OF PLANS AND PLACED ALL SETS IN TO EACH OF THEIR
 RESPECTIVE PACKAGES.
  
 1) NOTE:PLEASE KNOW THAT THE PLANS FOR THE ELECTRICAL
 DETAIL SHALL BE SPECIFIC TO THE SCOPE OF WORK ON THE
 JOB APPLIED FOR. PLEASE CORRELATE EQUIPMENT WITH NEW
 PROPOSED PANEL SCHEDULE AS SOME EQUIPMENT SHOWN IS NOT
 ON SCHEDULE?
 408.4, 310.16,
 FBC 106.1.2
 FBC 106.3.5.1.2,106.3.5.5 ADMIN SECTION.
  
 2) NOTE: PLEASE KNOW AS THIS IS A THRESHOLD/ON-SITE
 INSPECTOR JOB, THREE SETS OF ALL PLANS MUST BE
 SUBMITTED.
 109.3.6, 106.1.2 ADMIN SECTION.
  
 3) NOTE: PLEASE KNOW THAT NO WHITE OUT OR HAND WRITTEN
 CHANGES MAY BE DONE TO PLANS WHICH ARE SIGNED, DATED OR
 SEALED BY AN ENGINEER.
 PLEASE ALSO SEE THAT ATTACHED SHEETS CHANGING OR
 MODIFYING PLANS IN ANY WAY IS ALSO NOT PERMITTED UNLESS
 DONE BY THE ENGINEER OF RECORD, SIGNED, DATED, SEALED
 ALONG WITH TITLE BLOCKS AS REQUIRED PER FAC
 61G15-23.002, FS 471.025
  
 4) NOTE: PLEASE LIST THE FEEDER TO THE NEW VAK-PAK
 PANEL.
 215.5, 215.3.
  
 5) NOTE: PLEASE COMPLETE THE LOAD CALCULATIONS FOR ALL
 AND INDICATE THE CONTINUOUS LOADS AT 125%.
 215.3, 230.42 ETC.
  
  
 ** PLEASE KNOW AS INFORMATION NEEDED WAS NOT SUBMITTED
 AT THIS TIME THEIR MAY BE COMMENTS ON THE FOLLOWING
 REVIEW
  
 ** ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
  
 **IF THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF
 THE NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE
 DO NOT HESITATEIN CONTACTING THIS REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-12-21 Cont ID  
Sent By mperson Date 2006-12-21 Time 15:23 Rev Time 0.00
Received By mperson Date 2006-12-21 Time 15:23 Sent To  
Notes
2006-12-21 15:25:32CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL POOL INSPECTION.
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-01-17 Cont ID  
Sent By adarroug Date 2007-01-17 Time 11:50 Rev Time 0.00
Received By adarroug Date 2007-01-17 Time 11:50 Sent To Z
Notes
2007-01-17 11:51:13TO "Z" BOX/RESUB--NEW SHEETS FOR Z

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-12-21 Cont ID  
Sent By mperson Date 2006-12-21 Time 15:26 Rev Time 0.00
Received By mperson Date 2006-11-13 Time 11:30 Sent To  
Notes
2006-11-17 13:12:45TO "COMM" BD#14
2006-11-13 11:30:57WAITING FOR "COMM" BD

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-01-24 Cont ID  
Sent By mperson Date 2007-01-24 Time 11:36 Rev Time 0.00
Received By mperson Date 2007-01-24 Time 11:36 Sent To  
Notes
2007-01-24 11:47:48 
  
 ****************PROVISO****************
 PER FBC-2004 PLUMBING SECTION 802.1.4 SWIMMING POOLS:
 WHERE WASTEWATER FROM SWIMMING POOLS, BACKWASH FROM
 FILTERS SHALL DRAIN TO THE SANITARY SYSTEM.

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-12-21 Cont ID  
Sent By mperson Date 2006-12-21 Time 14:31 Rev Time 1.25
Received By mperson Date 2006-12-21 Time 14:31 Sent To G
Notes
2006-12-21 15:22:56DENIED
 REFERENCE: FBC-2004, SECTION 424 SWIMMING POOLS AND
 FLORIDA STATUTES
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PER FBC-2004 CHAPTER 1, SECTION 106.2 AND 109.3.6
 THREE SETS OF ALL PLANS AND SUBMITTALS ARE REQUIRED DUE
 TO THE FACT THAT THE JOB IS A THRESHOLD/ ON SITE
 INSPECTION JOB.
  
 2. SHEET 4 OF 5 VACUUM FITTING INDICATES (2 TYP) BUT
 ONLY ONE IS INDICATED ON DRAWINGS, PLEASE CLARIFY ON
 THE RESUBMITTAL.
  
 3. SHEET 5 OF 5 WHITE OUT OR HAND WRITTEN CHANGES ARE
 NOT ALLOWED ON SIGNED AND SEALED ENGINEERED PRINTS PER
 FS 471.025.
  
 4. PER FAC61G15-23.002 AND FS 471.025 ATTACHED SHEETS
 CHANGING OR MODIFYING PLANS IS NOT PERMITTED UNLESS
 DONE BY ENGINEER OF RECORD, SIGNED, SEALED, DATED,
 ALONG WTH A TITLE BLOCK.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop Z ZONING
Rev No 2 Status P Date 2007-01-22 Cont ID  
Sent By jroach Date 2007-01-22 Time 22:57 Rev Time 0.00
Received By jroach Date 2007-01-22 Time 22:57 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2006-11-30 Cont ID  
Sent By jroach Date 2006-11-30 Time 16:41 Rev Time 0.00
Received By jroach Date 2006-11-30 Time 16:41 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy