Plan Review Details - Permit 06110263
Plan Review Stops For Permit 06110263
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2008-03-31 Cont ID  
Sent By shill Date 2008-03-31 Time 08:11 Rev Time 0.00
Received By shill Date 2008-03-31 Time 08:11 Sent To  
Notes
2008-03-31 08:28:01****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.SEE PREVIOUS LISTS REGARDING PROCESS FOR
 RESUBMITTAL.I WAS UNABLE TO LOCATE A RESPONSE LETTER.
 THIS EXPEDITES THE REVIEW PROCESS AND HELPS TO PREVENT
 AN ENTIRELY NEW REVIEW.
  
 2-5.ADDRESSED OR INFORMATIONAL.
  
 6.PLEASE SEE PREVIOUS LISTS REGARDING THE PRESTORM
 PREPARATION PLAN.USE OF REMOVABLE IMPACT PROTECTION
 ON COMMERCIAL BUILDINGS REQUIRES APPROVAL BY BUILDING
 OFFICIAL.A PLAN HAS BEEN SUBMITTED BY THE ARCHITECT,
 BUT THE AGREEMENT BETWEEN THE OWNER AND DOMINICK
 MASSERO WAS NOT PROVIDED AS REQUESTED.THE OWNER IS TO
 SIGN A COMMITMENT REGARDING IMPACT PROTECTION; THIS HAS
 BEEN REQUESTED BUT NOT PROVIDED.
  
 PLEASE NOTE THAT THE PLAN MAY BE SUBMITTED VIA EMAIL
 FOR PRELIMINARY REVIEW, SEPARATELY FROM THE PLAN REVIEW
 PROCESS.
  
 REGARDING THE PLAN SUBMITTED, PLEASE ADDRESS THE
 FOLLOWING:
  
 A.WHERE SPECIFICALLY WILL THE SHUTTERS BE STORED?
 WILL THEY BE STORED VERTICALLY OR STACKED ON THE
 GROUND?IF STORED VERTICALLY, METHOD OF SECURING THE
 SHUTTERS (TO PREVENT THEM FROM FALLING AND INJURING
 SOMEONE) WILL BE REQUIRED.IF STORED HORIZONTALLY, A
 FLOOR PLAN SHOWING THE LOCATION AND ADEQUATE FLOOR
 SPACE WILL BE REQUIRED.THE FLOOR PLAN ON A2.0 DOES
 NOT GIVE ANY DIMENSIONS FOR WHAT IS SHOWN AS THE
 HURRICANE SHUTTER STORAGE AREA.
  
 B.HOW WILL THE PANELS BE SECURED TO PREVENT THEFT?
 WHO HAS ACCESS TO THIS AREA?HOW WILL THE OWNER GET
 ACCESS TO THIS AREA, ESPECIALLY AS THIS APPEARS TO BE A
 DIFFERENT TENANT SPACE FROM THE LOCATION WHERE SOME OF
 THE PANELS WILL BE REQUIRED.
  
 C.ONLY ONE INDIVIDUAL IS SHOWN AS BEING RESPONSIBLE
 FOR THE SHUTTER INSTALLATION.WHAT WILL OWNER DO IN
 THE EVENT THAT THIS ONE INDIVIDUAL IS UNAVAILABLE
 (VACATION, ILLNESS)?
  
 PLEASE BE ADVISED THAT THIS IS ONLY A PRELIMINARY
 REVIEW.ONCE COMPLETE INFORMATION IS ESTABLISHED, THE
 PLAN IS FORWARDED TO THE BUILDING OFFICIAL FOR REVIEW
 AND APPROVAL.
  
 ALSO NOTE THAT, DUE TO FBC1003.6, IMPACT DOORS WILL BE
 REQUIRED.NOTE THAT YOU ARE PROPOSING TO BLOCK THE
 ONLY EXIT FOR THE TENANT SPACE NOTED AS 522 S DIXIE HWY
  
  
 7.SEE PREVIOUS LIST AND ATTACHED SAMPLE INSTALLATION
 SCHEDULE.THIS INFORMATION IS REQUIRED FOR HURRICANE
 SHUTTER PERMITS.IF REQUESTED, THIS CAN BE PROVIDED AS
 A SEPARATE HURRICANE SHUTTER PERMIT.
  
 8.PREVIOUS LIST INDICATED THAT THE NEW ENTRY DID NOT
 COMPLY WITH FBC11-4.13.6.A 2INCH ELEVATION CHANGE IS
 SHOWN BETWEEN THE EXISTING SIDEWALK AND FINISHED FLOOR.
 A NEW NOTE STATES THAT HEIGHT DIFFERENCE SHALL NOT
 EXCEED 1/2INCH.IT IS NOT CLEAR HOW 1/2INCH AT DOORWAY
 AND AGAIN FROM NEW SLAB TO SIDEWALK WILL EQUAL THE
 2INCH DIFFERENCE.ALSO SEE FBC11-4.5.2, ELEVATION
 DIFFERENCE IS TO BE LIMITED TO 1/4INCH.SEE
 FBC11-4.1.6, (1)(B).
  
 NEW COMMENTS:
  
 9.A2.0 DECLARES OCCUPANCY AS CLASS B, MERCANTILE.
 CLASS B IS BUSINESS, MERCANTILE IS CLASS M, 41
 OCCUPANTS.IF THIS IS M, GROUND FLOOR REQUIRES 30SF
 PER PERSON, MINIMUM OCCUPANT LOAD WOULD BE 46.PLANS
 APPEAR TO BE CODE COMPLIANT FOR OCCUPANT LOAD OF 46 BUT
 PLEASE EITHER CLARIFY OCCUPANT LOAD OF 41 AS STATED ON
 PLAN OR REVISE AND CONFIRM COMPLIANCE (NO RESPONSE
 OTHER THAN REVISION OF OCCUPANT LOAD REQUIRED).
 PLEASE NOTE THAT, HAD THE PLANS BEEN OTHERWISE CODE
 COMPLIANT, THIS ITEM WOULD NOT HAVE PREVENTED PERMIT
 ISSUANCE.
  
 10.FBC1003.6, ITEMS OTHER THAN THOSE ALLOWED IN
 CHAPTER 10 NOT PERMITTED IN THE EGRESS PATH.HURRICANE
 PANELS DO NOT COMPLY WITH THIS CODE SECTION.TO MY
 KNOWLEDGE THE ONLY PROVISION IN THE CODE FOR USE OF
 SHUTTERS IN EGRESS PATH IN EVENT OF AN EMERGENCY IS FOR
 RESIDENTIAL OCCUPANCY ONLY.SEE ALSO COMMENT 6, YOU
 ARE NOT ONLY BLOCKING THE REQUIRED EXIT BUT ALSO
 BLOCKING WHAT APPEARS TO BE THE ONLY EXIT FOR ONE OF
 THE TENANT SPACES.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-11-19 Cont ID  
Sent By jwitmer Date 2007-11-19 Time 14:29 Rev Time 3.33
Received By jwitmer Date 2007-11-19 Time 14:29 Sent To  
Notes
2007-11-19 16:01:34PERMIT: 06110263
 ADD: 518 S DIXIE HWY
 CONT: ROOSTH CONSTRUCTION
 TEL: (561)221-7721
 DATE: NOV 19, 2007
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 4THREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) COMPLIED.
  
 4) COMPLIED.
  
 5) COMMENT NUMBER (5) FROM THE PREVIOUS REVIEW, WPB
 ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE PRODUCT
 WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 THE DESIGNER OF RECORD IS TO REVIEW ALL PRODUCT
 APPROVALS REQUIRED BY RULE 9B-72 PLEASE PROVIDE A SHOP
 DRAWING STAMP. IF THE DESIGNER OF RECORD WISHES TO MAKE
 A COVER SHEET LISTING ALL PRODUCTS REVIEWED FOR THIS
 PROJECT, THEN THIS SHEET WOULD NEED TO BE SIGNED AND
 SEALED AND DATED.
  
 6) COMMENT NUMBER (6) FROM THE PREVIOUS REVIEW,DEALS
 WITH THE HURRICANE PREPAREDNESS PLAN. THE ARCHITECT
 INDICATES BY LETTER HE HAS REVIEWED THE INFORMATION
 REQUIRED AND FOUND IT TO BE CODE COMPLIANT, BUT HE
 FAILED TO SIGN AND SEAL SAID LETTER.
 PLEASE SEE THE PLANS DO NOT INDICATE WHERE UNIT 522 S
 DIXIE IS OR WHERE THE SHUTTERS WILL BE STORED.
 WE ALSO FAIL TO SEE A NOTIRIZED LETTER OR ANY CONTRACT
 BETWEEN THE OWNER AND DOMINICK MASSERO FOR THE
 INSTALLATION OF SHUTTERS IN THE EVENT THIS COUNTY IS
 PLACED UNDER A HURRICANE WARNING.
  
 IF THE BUILDING IS TO BE STORM SHUTTERED RATHER THAN
 LARGE IMPACT WINDOWS AND DOORS, THE BUILDING OFFICIALS
 INTERPRETATION
 OF THE CODE REQUIRES A HURRICANE PREPAREDNESS PLAN WITH
 THE FOLLOWING:104.6*/ 1609.1.4/ 1714.5 STANDARDS FOR
 WIND-BORNE DEBRIS IMPACT PROTECTION
 QUESTION# 13 RECOGNIZING SUCH CONCERNS AS ABSENTEE
 OWNERS, OR CASES WHERE LONGER TIME & EFFORT IS
 NECESSARY TO SECURE SHUTTERS ON LARGE OR MULTI-STORY
 BUILDINGS, WHAT MEASURES ARE BEING RECOMMENDED OR
 IMPLEMENTED TO ENSURE THAT COMPLETE INSTALLATION OR
 SECURING IS DONE SUFFICIENTLY IN ADVANCE OF THE
 HURRICANE?
  
 IN MATTERS CONCERNING PUBLIC SAFETY, HEALTH, AND THE
 GENERAL WELFARE NOT SPECIFICALLY ADDRESSED IN THE CODE,
 SECTION 104.6 OF THE FLORIDA BUILDING CODE,BUILDING,
 CHAPTER 1,
 ADMINISTRATIVE CODE2004 EDITION AS AMENDED BY THE CITY
 OF WEST PALM BEACH, PROVDES THE ABILITY FOR THE
 BUILDING OFFICIAL TO IMPLEMENT REQUIREMENTS FOR
 ENSURING STABILITY, STRENGTH, AND THE PROPER OPERATION
 OF EXISTING BUILDINGS.
  
 IN ORDER TO ASSURE THE SECURING OF SHUTTERS ON LARGE OR
 MULTI-STORY BUILDINGS, OR MULTIPLE BUILDINGS ON THE
 SAME PROPERTY, PRE-STORM PREPARATION PLANS MUST BE
 SUBMITTED BY THE PROPERTY OWNERS OR MANAGING AGENTS FOR
 REVIEW BY THE CONSTRUCTION SRVICES DEPARTMENT. ANY SUCH
 PLAN SHALL INCLUDE, AT A MINMUM, ON SITE LOCATION OF
 THE SHUTTERS, PARTY RESPONSIBLE FOR SECURING THE
 SHUTTERS ( SAID PARTY MUST BE LOCATED WITHIN PALM BEACH
 COUNTY), TOTAL NUMBER OF OPENINGS TO BE PROTECTED AND
 THE TOTAL TIME REQUIRED TO SECURE ALL OPENINGS.
 PROTECTION OF OPENINGS SHALL BE ACCOMPLISHEDWITHIN
 TWELVE (12) HOURS OR LESS OF THE
 OFFICIAL NOTIFICATION BY THE NATIONAL WEATHER SERVICES
 OF A HURRICANE WATCH.
  
 PROVISIONS IN THE BUILDING CODES (AND THIS STANDARD)
 ARE NOT INTENDED TO PROHIBIT THE USE OF ALTERNATE
 MATERIALS AND METHODS, AND THE BUILDING OFFICIAL TO
 REVIEW AND APPROVE ANY ALTERNATE DEEMED EQUIVALENT IN
 QUALITY, STRENGTH, EFFECTIVENESS, FIRE RESISTANCE,
 DURABILITY AND SAFETY PRESCRIBED BY THIS CODE. BASED
 UPON THIS CODE PROVISION, ACCEPTANCE OF ALTERNATE
 MATERIALS AND METHODS MAY BE APPROVED ON A CASE-BY-CASE
 BASIS AND SHALL REQUIRE SUFFICIENT EVIDENCE OR PROOF TO
 SUBSTANTIATE ANY CLAIM MADE REGARDING THE ALTERNATE.
  
 7) COMMENT# 7 FROM THE PREVIOUS REVIEW,DEALS WITH A
 KET PLAN INDICATING THE LOCATION OF THE OPENING, AND
 HIGHLIGHTING THE TYPE OF SHUTTER APPLICATION USED IN
 THE INSTALATION, NOR HAS THE TYPE OF FASTENER HIGH
 LIGHTED AND SPACING REQUIREMENTS AS SPECIFIED BELOW.
 PLEASE TAKE THE TIME TO CREATE A SCHEDULE THAT WILL
 CONFORM TO THE CITYS' REQUIREMENTS.
 STORM SHUTTER REQUIREMENTS: 2004FL BLD CODE 2001
 SECTION 104.6, 1609.1.4& 1714.5PROVIDE STORM PANEL
 INFORMATION WITH INSTALLATION SCHEDULE AND KEY PLAN
 WITH SPECIFIC ANCHORS AND MOUNTING TO BE USED FOR ALL
 NON-IMPACT GLAZING.
 FBC 1609.1.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.SEE ATTACHED EXAMPLE.
  
 8)NEW COMMENT, THE NEW FRONT ENTRYS DO NOT MEET THE
 REQUIREMENTS FOR CLEAR FLOOR SPACE AT DOORWAYS.
 11-4.13.6 MANEUVERING CLEARENCES AT DOORS. MINIMUM
 MANEUVERING CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC
 OR POWER-ASSISTED SHALL BE AS SHOWN IN FIG. 25. THE
 FLOOR OR GROUND AREA WITH IN THE REQUIRED CLEARANCES
 SHALL BE CLEAR & LEVEL.
  
  
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-06-15 Cont ID  
Sent By jwitmer Date 2007-06-15 Time 16:09 Rev Time 2.22
Received By jwitmer Date 2007-06-15 Time 16:08 Sent To  
Notes
2007-06-15 16:09:41PERMIT: 06110263
 ADD: 518 S DIXIE HWY
 CONT: ROOSTH CONSTRUCTION
 TEL: (561)221-7721
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) COMMENT NUMBER 5FROM THE PREVIOUS RVIEW,PRODUCT
 APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4) COMMENT NUMBER (6A) FROM THE PREVIOUS REVIEW, FL BLD
 CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) STOREFRONTWINDOWS REPORT ILLEGABLE PLEASE PROVIDE
 LEGIBLE REPORTS
 B) EXTERIOR GLAZED DOORS INDICATE OUTSWING WHILE THE
 PLANS INDICATE INSWING
 C) MULLIONS
 D) TRANSOMS
 E) SHUTTERS SEE ADDITIONAL INFORMATION REQUIRED SEE
 COMMENT # 6.
  
 5) COMMENT NUMBER 6B FROM THE PREVIOUS REVIEW,
 WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 6) COMMENT NUMBER 7 FROM THE PREVIOUS REVIEW,IF THE
 BUILDING IS TO BE STORM SHUTTERED RATHER THAN LARGE
 IMPACT WINDOWS AND DOORS, THE BUILDING OFFICIALS
 INTERPRETATION
 OF THE CODE REQUIRES A HURRICANE PREPAREDNESS PLAN WITH
 THE FOLLOWING:104.6*/ 1609.1.4/ 1714.5 STANDARDS FOR
 WIND-BORNE DEBRIS IMPACT PROTECTION
 QUESTION# 13 RECOGNIZING SUCH CONCERNS AS ABSENTEE
 OWNERS, OR CASES WHERE LONGER TIME & EFFORT IS
 NECESSARY TO SECURE SHUTTERS ON LARGE OR MULTI-STORY
 BUILDINGS, WHAT MEASURES ARE BEING RECOMMENDED OR
 IMPLEMENTED TO ENSURE THAT COMPLETE INSTALLATION OR
 SECURING IS DONE SUFFICIENTLY IN ADVANCE OF THE
 HURRICANE?
  
 IN MATTERS CONCERNING PUBLIC SAFETY, HEALTH, AND THE
 GENERAL WELFARE NOT SPECIFICALLY ADDRESSED IN THE CODE,
 SECTION 104.6 OF THE FLORIDA BUILDING CODE,BUILDING,
 CHAPTER 1,
 ADMINISTRATIVE CODE2004 EDITION AS AMENDED BY THE CITY
 OF WEST PALM BEACH, PROVDES THE ABILITY FOR THE
 BUILDING OFFICIAL TO IMPLEMENT REQUIREMENTS FOR
 ENSURING STABILITY, STRENGTH, AND THE PROPER OPERATION
 OF EXISTING BUILDINGS.
  
 IN ORDER TO ASSURE THE SECURING OF SHUTTERS ON LARGE OR
 MULTI-STORY BUILDINGS, OR MULTIPLE BUILDINGS ON THE
 SAME PROPERTY, PRE-STORM PREPARATION PLANS MUST BE
 SUBMITTED BY THE PROPERTY OWNERS OR MANAGING AGENTS FOR
 REVIEW BY THE CONSTRUCTION SRVICES DEPARTMENT. ANY SUCH
 PLAN SHALL INCLUDE, AT A MINMUM, ON SITE LOCATION OF
 THE SHUTTERS, PARTY RESPONSIBLE FOR SECURING THE
 SHUTTERS ( SAID PARTY MUST BE LOCATED WITHIN PALM BEACH
 COUNTY), TOTAL NUMBER OF OPENINGS TO BE PROTECTED AND
 THE TOTAL TIME REQUIRED TO SECURE ALL OPENINGS.
 PROTECTION OF OPENINGS SHALL BE ACCOMPLISHEDWITHIN
 TWELVE (12) HOURS OR LESS OF THE
 OFFICIAL NOTIFICATION BY THE NATIONAL WEATHER SERVICES
 OF A HURRICANE WATCH.
  
 PROVISIONS IN THE BUILDING CODES (AND THIS STANDARD)
 ARE NOT INTENDED TO PROHIBIT THE USE OF ALTERNATE
 MATERIALS AND METHODS, AND THE BUILDING OFFICIAL TO
 REVIEW AND APPROVE ANY ALTERNATE DEEMED EQUIVALENT IN
 QUALITY, STRENGTH, EFFECTIVENESS, FIRE RESISTANCE,
 DURABILITY AND SAFETY PRESCRIBED BY THIS CODE. BASED
 UPON THIS CODE PROVISION, ACCEPTANCE OF ALTERNATE
 MATERIALS AND METHODS MAY BE APPROVED ON A CASE-BY-CASE
 BASIS AND SHALL REQUIRE SUFFICIENT EVIDENCE OR PROOF TO
 SUBSTANTIATE ANY CLAIM MADE REGARDING THE ALTERNATE.
  
 7) COMMENT# 8 FROM THE PREVIOUS REVIEW,STORM SHUTTER
 REQUIREMENTS: 2004FL BLD CODE 2001 SECTION 104.6,
 1609.1.4& 1714.5PROVIDE STORM PANEL INFORMATION
 WITH INSTALLATION SCHEDULE AND KEY PLAN WITH SPECIFIC
 ANCHORS AND MOUNTING TO BE USED FOR ALL NON-IMPACT
 GLAZING.
 FBC 1609.1.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.SEE ATTACHED EXAMPLE.
  
 8) REVIEW COMMENT FOR 3900 N FLAGLERLATITE ROOFING?
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-02-09 Cont ID  
Sent By jwitmer Date 2007-02-09 Time 07:58 Rev Time 0.00
Received By jwitmer Date 2007-02-09 Time 07:50 Sent To  
Notes
2007-02-09 08:02:01BUILDING PLAN REVIEW
 PERMIT: 06110263
 ADD: 518 S DIXIE HWY
 CONT: ROOSTH CONSTRUCTION
 TEL: (561)221-7721
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) PLEASE PROVIDE A SURVEY WITH THE BUILDING LOCATION
 ON SURVEY.
 3202.2 ENCROACHMENTS ABOVE GRADE AND BELOW 8 FEET IN
 HEIGHT.
 ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY ABOVE GRADE
 AND BELOW
 8 FEET (2438 MM) IN HEIGHT SHALL BE PROHIBITED EXCEPT
 AS PROVIDED FOR
 IN SECTIONS 3202.2.1 THROUGH 3202.2.3 . DOORS AND
 WINDOWS SHALL NOT
 OPEN OR PROJECT INTO THE PUBLIC RIGHT-OF-WAY.
  
 4)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 THE COVERSHEET STILL REFLECTS THE 2001 FBC IN THE
 GENERAL NOTES# 01
  
 5) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6A) FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) STOREFRONT
 B) EXTERIOR DOORS
 C) MULLIONS
 D) TRANSOMS
 E) SHUTTERS
 6B) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 7) IF THE BUILDING IS TO BE STORM SHUTTERED RATHER
 THAN
 LARGE IMPACT WINDOWS AND DOORS, THE BUILDING OFFICIALS
 INTERPRETATION
 OF THE CODE REQUIRES A HURRICANE PREPAREDNESS PLAN WITH
 THE FOLLOWING:104.6*/ 1609.1.4/ 1714.5 STANDARDS FOR
 WIND-BORNE DEBRIS IMPACT PROTECTION
 QUESTION# 13 RECOGNIZING SUCH CONCERNS AS ABSENTEE
 OWNERS, OR CASES WHERE LONGER TIME & EFFORT IS
 NECESSARY TO SECURE SHUTTERS ON LARGE OR MULTI-STORY
 BUILDINGS, WHAT MEASURES ARE BEING RECOMMENDED OR
 IMPLEMENTED TO ENSURE THAT COMPLETE INSTALLATION OR
 SECURING IS DONE SUFFICIENTLY IN ADVANCE OF THE
 HURRICANE?
  
 IN MATTERS CONCERNING PUBLIC SAFETY, HEALTH, AND THE
 GENERAL WELFARE NOT SPECIFICALLY ADDRESSED IN THE CODE,
 SECTION 104.6 OF THE FLORIDA BUILDING CODE,BUILDING,
 CHAPTER 1,
 ADMINISTRATIVE CODE2004 EDITION AS AMENDED BY THE CITY
 OF WEST PALM BEACH, PROVDES THE ABILITY FOR THE
 BUILDING OFFICIAL TO IMPLEMENT REQUIREMENTS FOR
 ENSURING STABILITY, STRENGTH, AND THE PROPER OPERATION
 OF EXISTING BUILDINGS.
  
 IN ORDER TO ASSURE THE SECURING OF SHUTTERS ON LARGE OR
 MULTI-STORY BUILDINGS, OR MULTIPLE BUILDINGS ON THE
 SAME PROPERTY, PRE-STORM PREPARATION PLANS MUST BE
 SUBMITTED BY THE PROPERTY OWNERS OR MANAGING AGENTS FOR
 REVIEW BY THE CONSTRUCTION SRVICES DEPARTMENT. ANY SUCH
 PLAN SHALL INCLUDE, AT A MINMUM, ON SITE LOCATION OF
 THE SHUTTERS, PARTY RESPONSIBLE FOR SECURING THE
 SHUTTERS ( SAID PARTY MUST BE LOCATED WITHIN PALM BEACH
 COUNTY), TOTAL NUMBER OF OPENINGS TO BE PROTECTED AND
 THE TOTAL TIME REQUIRED TO SECURE ALL OPENINGS.
 PROTECTION OF OPENINGS SHALL BE ACCOMPLISHEDWITHIN
 TWELVE (12) HOURS OR LESS OF THE
 OFFICIAL NOTIFICATION BY THE NATIONAL WEATHER SERVICES
 OF A HURRICANE WATCH.
  
 PROVISIONS IN THE BUILDING CODES (AND THIS STANDARD)
 ARE NOT INTENDED TO PROHIBIT THE USE OF ALTERNATE
 MATERIALS AND METHODS, AND THE BUILDING OFFICIAL TO
 REVIEW AND APPROVE ANY ALTERNATE DEEMED EQUIVALENT IN
 QUALITY, STRENGTH, EFFECTIVENESS, FIRE RESISTANCE,
 DURABILITY AND SAFETY PRESCRIBED BY THIS CODE. BASED
 UPON THIS CODE PROVISION, ACCEPTANCE OF ALTERNATE
 MATERIALS AND METHODS MAY BE APPROVED ON A CASE-BY-CASE
 BASIS AND SHALL REQUIRE SUFFICIENT EVIDENCE OR PROOF TO
 SUBSTANTIATE ANY CLAIM MADE REGARDING THE ALTERNATE.
  
 8) STORM SHUTTER REQUIREMENTS:
 2004FL BLD CODE 2001 SECTION 104.6,
 1609.1.4& 1714.5PROVIDE STORM PANEL INFORMATION
 WITH INSTALLATION SCHEDULE AND KEY PLAN WITH SPECIFIC
 ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1609.1.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.SEE ATTACHED EXAMPLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-12-14 Cont ID  
Sent By jwitmer Date 2006-12-14 Time 11:41 Rev Time 1.77
Received By jwitmer Date 2006-12-14 Time 11:40 Sent To  
Notes
2006-12-14 15:10:49BUILDING PLAN REVIEW
 PERMIT: 06110263
 ADD: 518 S DIXIE HWY
 CONT: ROOSTH CONSTRUCTION
 TEL: (561)221-7721
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) PLEASE PROVIDE A SURVEY WITH THE BUILDING LOCATION
 ON SURVEY.
 3202.2 ENCROACHMENTS ABOVE GRADE AND BELOW 8 FEET IN
 HEIGHT.
 ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY ABOVE GRADE
 AND BELOW
 8 FEET (2438 MM) IN HEIGHT SHALL BE PROHIBITED EXCEPT
 AS PROVIDED FOR
 IN SECTIONS 3202.2.1 THROUGH 3202.2.3 . DOORS AND
 WINDOWS SHALL NOT
 OPEN OR PROJECT INTO THE PUBLIC RIGHT-OF-WAY.
  
 4)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B(1) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 B(2)IS THIS A CHANGE OF OCCUPANCY?
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 5) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6) FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) STOREFRONT
 B) EXTERIOR DOORS
 C) MULLIONS
 D) TRANSOMS
 E) SHUTTERS
  
 7) IF THE BUILDING IS TO BE STORM SHUTTERED RATHER
 THAN
  
 LARGE IMPACT WINDOWS AND DOORS, THE BUILDING OFFICIALS
 INTERPRETATION
 OF THE CODE REQUIRES A HURRICANE PREPAREDNESS PLAN WITH
 THE FOLLOWING:104.6*/ 1609.1.4/ 1714.5 STANDARDS FOR
 WIND-BORNE DEBRIS IMPACT PROTECTION
 QUESTION# 13 RECOGNIZING SUCH CONCERNS AS ABSENTEE
 OWNERS, OR CASES WHERE LONGER TIME & EFFORT IS
 NECESSARY TO SECURE SHUTTERS ON LARGE OR MULTI-STORY
 BUILDINGS, WHAT MEASURES ARE BEING RECOMMENDED OR
 IMPLEMENTED TO ENSURE THAT COMPLETE INSTALLATION OR
 SECURING IS DONE SUFFICIENTLY IN ADVANCE OF THE
 HURRICANE?
  
 IN MATTERS CONCERNING PUBLIC SAFETY, HEALTH, AND THE
 GENERAL WELFARE NOT SPECIFICALLY ADDRESSED IN THE CODE,
 SECTION 104.6 OF THE FLORIDA BUILDING CODE,BUILDING,
 CHAPTER 1,
 ADMINISTRATIVE CODE2004 EDITION AS AMENDED BY THE CITY
 OF WEST PALM BEACH, PROVDES THE ABILITY FOR THE
 BUILDING OFFICIAL TO IMPLEMENT REQUIREMENTS FOR
 ENSURING STABILITY, STRENGTH, AND THE PROPER OPERATION
 OF EXISTING BUILDINGS.
  
 IN ORDER TO ASSURE THE SECURING OF SHUTTERS ON LARGE OR
 MULTI-STORY BUILDINGS, OR MULTIPLE BUILDINGS ON THE
 SAME PROPERTY, PRE-STORM PREPARATION PLANS MUST BE
 SUBMITTED BY THE PROPERTY OWNERS OR MANAGING AGENTS FOR
 REVIEW BY THE CONSTRUCTION SRVICES DEPARTMENT. ANY SUCH
 PLAN SHALL INCLUDE, AT A MINMUM, ON SITE LOCATION OF
 THE SHUTTERS, PARTY RESPONSIBLE FOR SECURING THE
 SHUTTERS ( SAID PARTY MUST BE LOCATED WITHIN PALM BEACH
 COUNTY), TOTAL NUMBER OF OPENINGS TO BE PROTECTED AND
 THE TOTAL TIME REQUIRED TO SECURE ALL OPENINGS.
 PROTECTION OF OPENINGS SHALL BE ACCOMPLISHEDWITHIN
 TWELVE (12) HOURS OR LESS OF THE
 OFFICIAL NOTIFICATION BY THE NATIONAL WEATHER SERVICES
 OF A HURRICANE WATCH.
  
 PROVISIONS IN THE BUILDING CODES (AND THIS STANDARD)
 ARE NOT INTENDED TO PROHIBIT THE USE OF ALTERNATE
 MATERIALS AND METHODS, AND THE BUILDING OFFICIAL TO
 REVIEW AND APPROVE ANY ALTERNATE DEEMED EQUIVALENT IN
 QUALITY, STRENGTH, EFFECTIVENESS, FIRE RESISTANCE,
 DURABILITY AND SAFETY PRESCRIBED BY THIS CODE. BASED
 UPON THIS CODE PROVISION, ACCEPTANCE OF ALTERNATE
 MATERIALS AND METHODS MAY BE APPROVED ON A CASE-BY-CASE
 BASIS AND SHALL REQUIRE SUFFICIENT EVIDENCE OR PROOF TO
 SUBSTANTIATE ANY CLAIM MADE REGARDING THE ALTERNATE.
  
 8) STORM SHUTTER REQUIREMENTS:
 2004FL BLD CODE 2001 SECTION 104.6,
 1609.1.4& 1714.5PROVIDE STORM PANEL INFORMATION
 WITH INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1609.1.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.SEE ATTACHED EXAMPLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2008-03-08 Cont ID  
Sent By dpalmer Date 2008-03-08 Time 20:47 Rev Time 0.00
Received By dpalmer Date 2008-03-08 Time 20:47 Sent To  
Notes
2008-03-08 20:47:54** DENIED REVIEW **
  
 1) NOTE: PLEASE SEE PREVIOUS REVIEW NOTES WITH RESPECT
 TO LIGHTING POWER DENSITIES. 13-415.2..ABC.1.1, .1.2
 AND .1.3, AND 13-415.2
 PLEASE SEE THE ALLOWANCES SUBMITTED STATE LOW BAY
 FIXTURES, WHEN THE FIXTURES ON PLANS ARE NOT LOW BAY
 FIXTURES. IN EITHER CASE PLEASE SEE THE DESIGN WATTAGE
 AS SHOWN EXCEEDS ALLOWANCES AS SHOW IN 13-415.2.B.
 PLEASE SEE PLANS SHOWS 1.2, WHICH EVEN IN ACTIVE
 STORAGE ON THIS TABLE ALLOWS ONLY .8.
 PLEASE SEE 13-415.2.ABC.1.3 FOR EXTERIOR.
 AS THE TOTAL FOR INTERIOR STILL SEEMS TO FALL BELOW THE
 OVER ALL ALLOWANCE SHOULD BE OK.
  
 ** PLEASE KNOW ONLY IF ALL OTHER TRADE REVIEWS PASS
 THAT A CONDITION KNOWN AS A *PROVISO* MAY BE ISSUED
 WHICH WILL REQUIRE REVISED PLANS BEFORE ROUGH.
  
 2) NOTE:** PLEASE SEE AS REQUESTED AND NOTED ON
 PREVIOUS REVIEW, PLEASE DO NOT LEAVE OLD/VOIDED SHEETS
 IN SETS. PLEASE REMOVE AND LABEL OLD/VOID
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-11-27 Cont ID  
Sent By dpalmer Date 2007-11-27 Time 08:26 Rev Time 0.00
Received By dpalmer Date 2007-11-26 Time 16:52 Sent To  
Notes
2007-11-27 08:26:20** DENIED**
  
  
  
 1) NOTE:PLEASE PROVIDE LIGHTING POWER DENSITIES PER
 13-415.2. MAY NOT USE METHOD A FOR *WHOLE BUILDING* AS
 THIS IS NOT A WHOLE BUILDING WHICH IS BEING BROUGHT UP
 TO CODE.
 PLEASE KNOW THIS WAS CONFIRMED ON SEPT 26, 2007 WITH
 THE STATE OF FLORIDA, FLORIDA BUILDING COMMISSION.
 THE ENERGY CALCULATIONS SUBMITTED BACK WERE THE SAME
 FROM PREVIOUS REVIEW WHICH HAD COMMENTS FOR
 COORDINATION.
 PLEASE KNOW ONLY LIGHTING PERFORMANCE CALCULATIONS NEED
 BE SUBMITTED FOR ELECTRICAL. PLEASE CALL TO GO OVER
 THIS MAY BE DONE IF THERE ARE ANY QUESTIONS.
 PLANS ARE ALREADY COMING BACK FOR COMMENTS FROM OTHER
 TRADES.
  
 PLEASE KNOW, STRUCTURAL REVIEW WILL BE DONE BY BUILDING
 REVIEWER.
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-04-25 Cont ID  
Sent By dpalmer Date 2007-04-25 Time 15:24 Rev Time 0.00
Received By dpalmer Date 2007-04-25 Time 15:05 Sent To  
Notes
2007-04-25 15:24:23** UNSAT3RD REVIEW**
  
 1) NOTE: PLEASE SEE THE NUMBER OF WINDOW RECEPTACLES IS
 NOT COMPLIANT AT THIS TIME. PLEASE SEE THE NORTH WINDOW
 WHICH SCALES TO BE LONGER THAN 12FT WHICH WOULD REQUIRE
 ONE ADDITIONAL RECEPTACLE.
 PLEASE ALSO SEE THE SOUTH WINDOW WHICH DOES NOT CONTAIN
 ANY DEVICE.
 THESE COULD BE REDLINED ON PLANS ONCE THE FOLLOWING
 COMMENT IS ADDRESSED.
  
 2) NOTE: PLEASE CORRELATE THE ENERGY CALCULATIONS FOR
 USE AND TYPE OF LIGHTING. (NOT LOW BAY MANUFACTURING).
 PLEASE ALSO SEE THE NUMBER OF FIXTURES SHOWN PLANS, THE
 WATTAGE AND THE TYPES OF FIXTURES DO NOT CORRELATE WITH
 THE PLANS AND FIXTURES AS SHOWN ON PLANS.
 PLEASE SEE THIS IS A NEW COMMENT AS THIS IS THE FIRST
 TIME ENERGY CALCULATIONS WERE SUBMITTED FOR REVIEW.
 PLEASE COORDINATE ALL FIXTURES, WATTAGES, TYPES, USE.
 13-415.1.A
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-01-19 Cont ID  
Sent By dpalmer Date 2007-01-19 Time 17:24 Rev Time 0.00
Received By dpalmer Date 2007-01-19 Time 12:05 Sent To  
Notes
2007-01-19 17:25:49** UNSAT2ND REVIEW **
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW STILL
 NEED TO BE ADDRESSED ALONG WITH SOME NEW COMMENTS BASED
 ON CHANGES MADE TO PLANS.
 PLEASE KNOW THAT THERE NEW COMMENTS BASED ON PLANS AND
 CHANGES MADE.
  
 ** PLEASE SEE THE COMMENTS BELOW ARE TAKEN DIRECTLY
 FROM PREVIOUS REVIEW IN THE SAME NUMERICAL ORDER. THEY
 WILL CONTAIN A NO, OK, OR NO/OK.
 A) NO WILL BE FOLLOWED BY FURTHER EXPLANATION OF THE
 PREVIOUS COMMENT.
 B) OK, MAY REFERENCE TO ANY NEW NOTES, HOWEVER WILL
 HAVE PREVIOUS NOTE REMOVED.
 C) NO/OK, WILL BE FOLLOWED BY FURTHER EXPLANATION AS
 PART OF THE COMMENT MAY NOT HAVE BEEN ADDRESSED FULLY
 AND PART OF THE PREVIOUS COMMENT MAY BE OK.
 D) OK/N/A, AS THE PREVIOUS NOTE DOES NOT APPLY ANY
 FURTHER AS PLANS HAVE DELETED OR CHANGED.
  
 ** ANY NEW NOTES WILL BE AT THE BOTTOM AND IDENTIFIED
 AS *** NEW NOTES ***.
  
 1) NOTE: NO/OK, PLEASE SEE SHEETS WHICH STILL INDICATE
 THE 2001 FBC.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PLANS REFLECT THE 2001 FBC; HOWEVER AS OF
 OCT 1ST, 2005 THE STATE OF FLORIDA ADOPTED THE 2004
 FBC. PLEASE ADJUST AND CHANGE AS NEED.
 PLEASE ALSO SEE TWO SEPARATE LS CODES ARE REFERENCED ON
 PLANS. (2000& 2003).
 PLEASE SEE OTHER LOCATIONS WHERE THE PLANS REFLECT THE
 "LATEST ADOPTED" ETC.
 PLEASE BE SURE THE FOLLOWING CODES ARE REFLECTED ON
 PLANS AS REQUIRED.
 2002 NFPA-70 (NEC), 2003 NFPA-101 (LS), 2004 FBC, AND
 ANY OTHER CODES FROM OTHER TRADES. SEE COMMENTS FROM
 OTHER REVIEWERS.
  
 2) NOTE: OK, HOWEVER SEE NEW NOTES.
  
 3) NOTE: OK/NO, PLEASE SEE THE OUTLET AND THE CIRCUIT
 WAS ADDED, HOWEVER PLEASE SEE THE LOCATION SHOULD BE
 SHOWN INSIDE OR OUTSIDE THE NEAREST POINT OF ENTRANCE.
 PLEASE SEE THAT PLANS ONLY NEED TO RELOCATE THIS OVER.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE A NEW OR EXISTING SIGN CIRCUIT(S) PEER
 600.5 THIS SPACE AND THE SPACE NEXT DOOR AS SCOPE OF
 WORK ON ARCHITECTURAL PLANS INDICATE WORK BEING DONE ON
 THE STOREFRONT NEXT DOOR.
 FBC 106.1.2 ADMIN SECT.
  
 4) NOTE: OK.
  
 5) NOTE:NO, PLEASE SEE SOME ADDED, HOWEVER NOT ALL AS
 REQUIRED. PLEASE SEE INDIVIDUAL SPACES AND WINDOWS
 WHICH EXCEED 12 LINEAR FT WILL BE REQUIRED TO CONTAIN
 ADDITIONAL RECEPTS.
 PLEASE ALSO SEE THE SECTION OF CODE GIVEN FOR LOAD
 CALCULATIONS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING SHOW WINDOW RECEPTS AS REQUIRED PER
 210.62 AND PLEASE ADJUST LOAD CALCULATIONS AS REQUIRED.
 220.12
  
 6) NOTE: OK. NO OTHER TENANT SPACE WILL BE FED FROM
 THIS METER/SERVICE.
 PLEASE SEE SERVICE NOTE AS THE SERVICE IS NOT CLEAR FOR
 FUTURE TENANT.
  
 7) NOTE: OK.
  
 8) NOTE: OK.
  
 9) NOTE:OK/NO, PLEASE SEE THE FUTURE TENANT SPACE(S)
 WHICH WILL A PART OF THIS BUILDING WILL NOT BE GRANTED
 AN ADDITIONAL SERVICE PER 230.2. THE RISER DOES NOT
 INDICATE ANY PROVISIONS FOR THIS POSSIBLE FUTURE TENANT
 AND THE NEW RISER WHICH IS BEING PROPOSED WOULD HAVE TO
 BE UPGRADED TO ACCOMMODATE THIS IN THE FUTURE. THE
 2-STORY BUILDING TO THE NORTH OF THE SINGLE STORY
 BUILDING WITH THE MULTIPLE METERED SERVICES MAY NOT
 FEED THIS FUTURE TENANT. BASED ON THE CONSTRUCTION AT
 THE SITE AND THE AERIALS, THIS TWO STRUCTURES APPEAR TO
 CONTAIN A FIRE WALL WHICH PENETRATES THE ROOF LINE AND
 SEPARATES THESE TWO AS BUILDINGS AS DEFINED IN THE
 FBC.
  
 PLEASE KNOW BASED ON THE SERVICE AS SHOWN THIS WILL
 ONLY BE ONE TENANT AND UNLESS UPGRADING THE NEW
 PROPOSED SERVICE IN THE FUTURE, NO OTHER SEPARATE
 TENANTS WILL OCCUPY FUTURE SPACE OR THE SPACE NOT BEING
 BUILT OUT AT THIS TIME.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CORRELATE SERVICE AS SHOWN ON PLANS AND THAT OF
 WHICH IS BEING SHOWN ON RISER. IF SERVICE IS GOING TO
 BE NEW AS SHOWN ON RISER, PLEASE SHOW. PLEASE VERIFY
 WHERE THE REST OF THE SERVICE IS FOR FEEDING THE
 BUILDING. PLEASE SEE 230.2, 230.72 FOR SERVICES
 PERMITTED, AND GROUPING.
 PLEASE SEE PLANS INDICATE 200A'S EXISTING AND RISER
 SHOWS 150A.
 PLEASE INDICATE THE SIZE OF THE SERVICE ENTRANCE
 CONDUCTORS IN THE EXISTING RISER. CAN NOT VERIFY THE
 SEC'S AT THIS TIME. (NONE SHOWN)
 215.5, 310.16, 240.4 ETC
 FBC 106.1.2
  
 10) NOTE: NO, PLEASE SEE RESPONSE LETTER DOES NOTE
 RESPOND TO THIS COMMENT, IT SEEMS TO REPLY TO #11. ?
 PLEASE SEE THE SECTIONS GIVEN AS THE LOAD
 SUMMARY/CALCULATIONS ARE STILL NEEDED FOR REVIEW.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT THE LOAD CALCULATIONS BASED ON THE NEC
 220.3, 220.10, 220.11, 220.13 AND CONTINUOUS LOADS AT
 125% 215.3, 230.42 ETC.
  
 11) NOTE: NO, THIS WAS IN RESPONSE LETTER AS COMMENT
 #10; HOWEVER PLEASE SEE THE ONLY AIC RATING WHICH COULD
 BE LOCATED ON E-2.0 WAS THE RATING FOR THE BRANCH
 BREAKERS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE THE AIC RATINGS FOR ALL SERVICE
 EQUIPMENT. PLANS INDICATE THE RATINGS FOR THE BRANCH
 BREAKERS ONLY ON THE PANEL SCHEDULE.
 PLEASE SEE 110.9, 240.12
 FBC 106.1.2 ADMIN SECT.
  
 12) NOTE: OK.
  
  
 *** NEW NOTES ***
  
 13) NOTE: PLEASE INDICATE ALL CIRCUITING ON PLANS AND
 CORRELATE WITH THE SUBMITTED PANEL SCHEDULE. 106.1.2,
 106.3.5.1.2
 NEC 408.4, 310.16, 240.4
  
 14) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS FOR SPACE
 PER CHAPTER 13 OF TEH FBC 2004. 13-415.1.AB.1
 THIS WAS NOT REQUESTED ON THE PREVIOUS REVIEW, HOWEVER
 DUE TO NEW STORE FRONT, OCCUPANCY, SPACE NOT CURRENTLY
 OCCUPIED , REMOVAL OF WALLS, NEW CEILING, NE INSULATION
 ETC, CALCULATIONS FOR LIGHTING ETC WILL BE NEEDED.
 PLEASE SEE MECHANICAL COMMENTS AS THE PLANS INDICATE
 NEW SPACE BEING INTRODUCED FOR CONDITIONING FROM AN
 EXISTING A/C SYSTEM.
 PLEASE SEE NOTE ON ARCHITECTURAL SHEETS WHICH MENTIONS
 NEW A/C WORK. PLEASE CLARIFY.
  
 15) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-11-21 Cont ID  
Sent By dpalmer Date 2006-11-21 Time 07:43 Rev Time 0.00
Received By dpalmer Date 2006-11-20 Time 20:17 Sent To  
Notes
2006-11-21 07:44:59*** UNSAT ***
  
 1) NOTE: PLEASE SEE PLANS REFLECT THE 2001 FBC; HOWEVER
 AS OF OCT 1ST, 2005 THE STATE OF FLORIDA ADOPTED THE
 2004 FBC. PLEASE ADJUST AND CHANGE AS NEED.
 PLEASE ALSO SEE TWO SEPARATE LS CODES ARE REFERENCED ON
 PLANS. (2000& 2003).
 PLEASE SEE OTHER LOCATIONS WHERE THE PLANS REFLECT THE
 "LATEST ADOPTED" ETC.
 PLEASE BE SURE THE FOLLOWING CODES ARE REFLECTED ON
 PLANS AS REQUIRED.
 2002 NFPA-70 (NEC), 2003 NFPA-101 (LS), 2004 FBC, AND
 ANY OTHER CODES FROM OTHER TRADES. SEE COMMENTS FROM
 OTHER REVIEWERS.
  
 2) NOTE: PLEASE 2004 FBC 13-415.1.ABC.1.1, .1.2 AND
 .1.3.
 PLEASE SEE 13-415.1.AB.1, 13-415.2
 THIS SPACE APPEARS TO BE IN A BUILDING (BY DEFINITION)
 LARGER THAN 5K SQ FT AND MEETS OTHER SECTIONS OF THE
 CODE WHICH INVOKE CHAPTER 13.
  
 3) NOTE: PLEASE INDICATE A NEW OR EXISTING SIGN
 CIRCUIT(S) PEER 600.5 THIS SPACE AND THE SPACE NEXT
 DOOR AS SCOPE OF WORK ON ARCHITECTURAL PLANS INDICATE
 WORK BEING DON ON THE STOREFRONT NEXT DOOR.
 FBC 106.1.2 ADMIN SECT.
  
 4) NOTE: PLEASE VERIFY THE SCOPE OF WORK BEING DONE ON
 THE TWO SPACES ADJACENT TO THIS SPACE. SEEMS TO BE
 INSTALLING NEW STOREFRONT, HOWEVER NO ELECTRICAL IS
 BEING SHOWN FOR SIGNAGE OR SHOW WINDOW RECEPTS. 600.5,
 210.62, 220.12.
 SUBMIT DETAILS/PLANS. FBC 106.1.2 ADMIN SECTION AS
 ADOPTED BY THE CITY OF WEST PALM BEACH.
  
 5) NOTE: PLEASE SEE MISSING SHOW WINDOW RECEPTS AS
 REQUIRED PER 210.62 AND PLEASE ADJUST LOAD CALCULATIONS
 AS REQUIRED. 220.12
  
 6) NOTE: PLEASE SEE PLANS APPEAR TO SHOW "COMMON AREA"
 LIGHTING WHICH IS BEING FED FROM THIS TENANT'S SPACE.
 PLEASE KNOW THIS IS NOT PERMITTED UNLESS THIS IS INDEED
 LOCATED ON THIS TENANT'S REAR SECTION OF SPACE. THE
 OTHER SCENARIO WOULD BE TO SERVE THE COMMON AREA LIGHT
 FROM A "HOUSE PANEL".
 210.25.
 230.2.
  
 7) NOTE: PLEASE SEE PLANS DO NOT SEEM TO INDICATE ANY
 LIGHTING IN THE TOILET AREA. THERE IS A SWITCH; HOWEVER
 THIS IS NOT SHOWN FEEDING ANYTHING?
 PLEASE SEE LS 101 7.8 WHICH WILL REQUIRE SOME SORT OF
 FIXTURE.
  
 8) NOTE: PLEASE SEE COLOR CODING FOR OTHER ELECTRICAL
 SYSTEM VOLTAGES ARE PRESENT ON PLANS, HOWEVER THERE ARE
 NO COLOR CODING FOR THE VOLTAGE ACTUALLY BEING
 INSTALLED.
 PLEASE SEE SERVICE IS BEING SHOWN AS A 120/240V
 /HIGH-LEGSERVICE.
 PLEASE SEE NEC 215.8
  
 9) NOTE: PLEASE CORRELATE SERVICE AS SHOWN ON PLANS AND
 THAT OF WHICH IS BEING SHOWN ON RISER. IF SERVICE IS
 GOING TO BE NEW AS SHOWN ON RISER, PLEASE SHOW. PLEASE
 VERIFY WHERE THE REST OF THE SERVICE IS FOR FEEDING THE
 BUILDING. PLEASE SEE 230.2, 230.72 FOR SERVICES
 PERMITTED, AND GROUPING.
 PLEASE SEE PLANS INDICATE 200A'S EXISTING AND RISER
 SHOWS 150A.
 PLEASE INDICATE THE SIZE OF THE SERVICE ENTRANCE
 CONDUCTORS IN THE EXISTING RISER. CAN NOT VERIFY THE
 SEC'S AT THIS TIME. (NONE SHOWN)
 215.5, 310.16, 240.4 ETC
 FBC 106.1.2
  
 10) NOTE: PLEASE SUBMIT THE LOAD CALCULATIONS BASED ON
 THE NEC 220.3, 220.10, 220.11, 220.13 AND CONTINUOUS
 LOADS AT 125% 215.3, 230.42 ETC.
  
 11) NOTE: PLEASE INDICATE THE AIC RATINGS FOR ALL
 SERVICE EQUIPMENT. PLANS INDICATE THE RATINGS FOR THE
 BRANCH BREAKERS ONLY ON THE PANEL SCHEDULE.
 PLEASE SEE 110.9, 240.12
 FBC 106.1.2 ADMIN SECT.
  
 12) NOTE: PLEASE SEE PLANS MENTIONS TO PLACE PANEL IN
 THE STOCKROOM WHICH WILL NOT BE PERMITTED. PLEASE
 RELOCATE AT THIS TIME. PLEASE SEE 408.7, 240.24, AND
 110.26.
  
 ** PLEASE KNOW AS THERE ARE MANY ITEMS NOT SUBMITTED OR
 WILL BE REQUIRED TO BE ADJUSTED, THERE MAY BE COMMENTS
 ON THE NEXT REVIEW.
  
  
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. **IF
 THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF THE
 NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE DO
 NOT HESITATEIN CONTACTING THIS REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2006-11-21 06:59:23IN PRGRESS
2006-11-20 20:28:01NOTES TO FOLLOW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2008-03-10 Cont ID  
Sent By mawillia Date 2008-03-10 Time 13:22 Rev Time 0.00
Received By mawillia Date 2008-03-10 Time 13:01 Sent To  
Notes
2008-03-10 13:21:51*****APPROVED*****
  
  
 PLAN SHEETS A-2.0, A-4.0, AND E-1.0 WERE STAMPED,
 INITIALED, AND APPROVED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-11-27 Cont ID  
Sent By mawillia Date 2007-11-27 Time 12:36 Rev Time 0.00
Received By mawillia Date 2007-11-27 Time 12:29 Sent To  
Notes
2007-11-27 12:32:22****PROVISO*****
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED;HOWEVER THE APPROPIATE PLAN(S) WILL BE
 STAMPED ALL OTHER PLAN REVIEWS HAVE BEEN SATISFIED.
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-05-07 Cont ID  
Sent By mawillia Date 2007-05-07 Time 14:43 Rev Time 0.00
Received By mawillia Date 2007-05-07 Time 14:33 Sent To  
Notes
2007-05-07 14:41:48****PROVISO*****
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED;HOWEVER THE APPROPIATE PLAN(S) WILL BE
 STAMPED ALL OTHER PLAN REVIEWS HAVE BEEN SATISFIED.
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-02-23 Cont ID  
Sent By mawillia Date 2007-02-23 Time 17:39 Rev Time 0.00
Received By mawillia Date 2007-02-23 Time 17:39 Sent To  
Notes
2007-02-23 17:50:58****UNSAT*****
  
 THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN
 REVIEW OF 12/11/2006 STILL NEED TO BE ADDRESSED.ALL
 OTHERS HAVE BEEN SATISFIED.
  
  
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD
 TO GENERAL DEMOLITION NOTES, SHEET A-1.0
  
 3. SHOW/DISPLAY THE NUMERICAL ADDRESS ON THE BUILDING
 AT THE APPROPIATE ELEVATION FRONTING SOUTH DIXIE
 HIGHWAY.IN ADDITION TO THE ADDRESS NUMBERS BEING NO
 LESS THAN 6 INCHES IN HEIGHT,THE WIDTH OR STROKE OF
 THOSE NUMBERS SHALL BE NO LESS THAN 1 INCH.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-12-11 Cont ID  
Sent By mawillia Date 2006-12-11 Time 15:34 Rev Time 0.00
Received By mawillia Date 2006-12-11 Time 15:34 Sent To  
Notes
2006-12-11 16:05:57*****DENIED*****
  
  
  
 1.NFPA 101-2003 EDITION AND THE FLORIDA FIRE
 PREVENTION CODE-2004 EDITION SHALL BE REFERENCED.SEE
 SHEET A-2.0 TENANT CALCULATION SECTION.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3. SHOW/DISPLAY THE NUMERICAL ADDRESS ON THE BUILDING
 AT THE APPROPIATE ELEVATION FRONTING SOUTH DIXIE
 HIGHWAY.AS PER WEST PALM BEACH CODE,THE NUMBERS
 SHALL BE NO LESS THAN 6" IN HEIGHT AND 1" IN WIDTH.
 HURRICANE SHUTTERS SHALL NOT BLOCK VIEW OF THE
 NUMERICAL ADDRESS.
  
 4.INTERIOR FINISH FOR WALL AND CEILINGS IN EXITS AND
 EXIT CORRIDORS SHALL BE CLASS "A" OR CLASS "B".
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-02-27 Cont ID  
Sent By adarroug Date 2008-02-27 Time 09:32 Rev Time 0.00
Received By adarroug Date 2008-02-27 Time 09:32 Sent To  
Notes
2008-02-27 09:33:08TO "COMM" BD#53

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-10-25 Cont ID  
Sent By adarroug Date 2007-10-25 Time 11:53 Rev Time 0.00
Received By adarroug Date 2007-10-25 Time 11:53 Sent To  
Notes
2007-11-13 09:41:35TO "COMM" BD#56
2007-10-25 11:53:37WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-04-23 Cont ID  
Sent By adarroug Date 2007-04-23 Time 09:03 Rev Time 0.00
Received By adarroug Date 2007-04-23 Time 09:03 Sent To  
Notes
2007-04-23 09:06:52TO "COMM" BD#44

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-01-19 Cont ID  
Sent By adarroug Date 2007-01-19 Time 09:15 Rev Time 0.00
Received By dpalmer Date 2007-01-19 Time 09:15 Sent To  
Notes
2007-01-19 13:02:58MOVED TO COMM BOARD #26
2007-01-19 09:17:47TO "BOB"#16

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-12-19 Cont ID  
Sent By jleech Date 2006-12-19 Time 14:30 Rev Time 0.00
Received By jleech Date 2006-11-09 Time 13:58 Sent To  
Notes
2006-11-20 16:31:35TO "BOB"#14
2006-11-09 13:58:56WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2008-02-29 Cont ID  
Sent By tgordon Date 2008-02-29 Time 09:14 Rev Time 0.30
Received By tgordon Date 2008-02-29 Time 09:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2007-11-14 Cont ID  
Sent By tgordon Date 2007-11-14 Time 11:12 Rev Time 0.45
Received By tgordon Date 2007-11-14 Time 11:12 Sent To  
Notes
2007-11-14 11:48:07PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) AS NOTED IN LAST REVIEW 4-30-07. SEE CONDENSER UNIT
 MOUNTING DETAIL ON PAGE M-2.0. ADD A NOTE STATING, IN
 COMPLIANCE WITH 2004 FBC 1609 TO WITHSTAND 140 MPH
 WINDS.
  
 2) NEED TO SUBMIT THE TECHNICAL DRAWINGS WITH THE
 NOTICE OF ACCEPTANCE FOR THE 12X12 O.A. LOUVER, SEE FS
 553.842(1) AND FAC 9B-72.010(31)(C).
  
 3) IF THE NOA 06-0602.04 FOR THE 12X12 LOUVERS HAS A
 PRODUCT APPROVAL FROM THE STATE OF FLORIDA PLEASE
 ATTACHE COVER SHEET.
  
 4) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 (A SHOP REVIEW STAMP AND SIGNATURE ON EACH PRODUCT
 APPROVAL WILL MEET THIS REQUIREMENT).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-04-30 Cont ID  
Sent By tgordon Date 2007-04-30 Time 15:56 Rev Time 0.35
Received By tgordon Date 2007-04-30 Time 15:56 Sent To  
Notes
2007-04-30 16:06:15*** DENIED ***
 1) SEE CONDENSER UNIT MOUNTING DETAIL, PLEASE ADD, IN
 COMPLIANCE WITH 2004 FBC 1609 TO WITHSTAND 140 MPH
 WINDS.
  
 2) PLEASE SUBMIT PRODUCT APPROVAL FOR12X12 O.A. LOUVER,
 SEE FS 553.842(1) AND FAC 9B-72.010(31)(C).
  
 **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-01-22 Cont ID  
Sent By tgordon Date 2007-01-22 Time 12:17 Rev Time 0.25
Received By tgordon Date 2007-01-22 Time 12:17 Sent To  
Notes
2007-01-22 12:23:28*** DENIED ***
 1) PLANS COVER SHEET STATES HVAC IS EXISTING NO NEW
 WORK. SEE PLAN A-4.0 HIGHLIGHTED NOTE STATING "REPLACE
 EXISTING A/C DUCTWORK".
  
 2) NO MECHANICAL PLANS WERE SUBMITTED FOR REVIEW.
 PLEASE SUBMIT MECHANICAL PLANS FOR REVIEW, PER 2004 FBC
 WPB AMEND. 106.3.5.1.4.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-01-22 Cont ID  
Sent By tgordon Date 2006-11-27 Time 09:00 Rev Time 0.00
Received By tgordon Date 2007-01-22 Time 12:15 Sent To  
Notes
2006-11-27 09:01:22NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.
  
 SEE REVIEW NOTES 1-22-07.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-05-03 Cont ID  
Sent By jleech Date 2007-05-03 Time 14:04 Rev Time 0.00
Received By jleech Date 2007-05-03 Time 14:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-02-03 Cont ID  
Sent By jleech Date 2007-02-03 Time 14:09 Rev Time 0.00
Received By jleech Date 2007-02-03 Time 14:02 Sent To  
Notes
2007-02-03 14:54:36DENIED;
 PLUMBING REVIEW COMMENTS ON 12/19/06 WERE NOT
 ADDRESSED;
 1. (SECOND REQUEST) PAGE A-1.0 SANITARY PLUMBING PIPES
 TO BE REMOVED BACK TO THE BUILDING DRAIN. NO DEAD ENDS
 PERMITTED IN THE DRAINAGE SYSTEM. FBC-2004 PLUMBING
 SECTION704.5. ADD NOTE TO DEMO PLAN "ALL PLUMBING DEMO
 WORK TO BE DONE BY A LICENSED PLUMBING CONTRACTOR
 PERMIT AND INSPECTIONS REQUIRED".
 2. (SECOND REQUEST) PAGE A-3.0 SANITARY RISER DIAGRAM.
 FUTURE SINKBRANCH DRAIN TO BE INSTALLED DOWN STREAM
 OF THE BATHROOM GROUO. SECTION 909.1.
 3. (SECOND REQUEST) PER TABLE 403.1 (6) M MINIMUM
 NUMBER OF FIXTURES REQUIRED, A DRINKING FOUNTAINIS
 REQUIRED. THE DRINKING FOUNTAIN MUST MEET THE
 REQUIREMENTS OF FBC-2004 BUILDING CHAPTER 11 SECTION
 11-4.1.3(10) HANDICAP AND FOR PEOPLE WITH BAD BACKS.
 SECTION 11-4.15.2 SPOUT HEIGHT, 11-4.15.3 SPOUT
 LOCATION, 11-4.15.4 CONTROLS, AND 11-4.15.5 CLEARANCES.
 SHOW ELEVATION ON DRAWINGS.
 4. (SECION REQUEST) PAGE A-3.0 WATER RISER DIAGRAM AIR
 CHAMBERS ARE NOT AN ENGINEER PRODUCT. REMOVE THE PLANS.
 WATER HAMMER ARRESTORS CAN BE INSTALLED AS REQUIRED PER
 SECTION 604.9 LIST MANUFACTURE AND MODEL NUMBER. WATER
 HAMMER ARRESTORS ARE TO BE INSTALL PER MANUFACTURE
 INSTALLATION INSTRUCTIONS AS CLOSE TO THE FIXTURE AS
 PERMITED NOT IN THE CEILING.
 5. (NEW COMMENTS) PLANS ARE BEING REVIEWED UNDER THE
 2004 CODE CORRECT UNDER GENERAL NOTES.
 6. (NEW COMMENT) PAGE A-3.0 BATHROOM WALL FINISH PAINT
 IS NOT A HARD SURFACE. SEE 2004 BUILDING SECTION
 12.10.2
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-12-19 Cont ID  
Sent By jleech Date 2006-12-19 Time 13:56 Rev Time 0.00
Received By jleech Date 2006-12-19 Time 13:56 Sent To  
Notes
2006-12-19 14:29:41DENIED;
 1. PAGE A-1.0 SANITARY PLUMBING PIPES TO BE REMOVED
 BACK TO THE BUILDING DRAIN. NO DEAD ENDS PERMITED IN
 THE DRAINAGE SYSTEM. FBC-2004 SECTION 704.5. PLEASE ADD
 NOTE TO DEMO. PLAN, "ALLPLUMBING DEMO WORK TO BE DONE
 BY A LICENSED PLUMBING CONTRACTOR PERMIT AND
 INSPECTIONS REQUIRED".
 2. PAGE A-3.0 SANITARY RISER DIAGRAM. FUTURE SINK
 BRANCH DRAIN TO BE INSTALLED DOWN STREAM OF THE
 BATHROOM GROUP. SECTION 909.1.
 3. PER TABLE 403.1 (6) M MINIMUM NUMBER OF FIXTURES
 REQUIRED, A DRINKING FOUNTAIN IS REQUIRED. THE DRINKING
 FOUNTAIN MUST MEET THE REQUIREMENTS OF FBC-2004
 BUILDING CHAPTER11 SECTIONS 11-4.1.3(10). HANDICAP
 AND PEOPLE WITH BAD BACKS. SECTION 11-4.15.2 SPOUT
 HEIGH. SECTION 11-4.15.3 SPOUT LOCATION, SECTION
 11-4.15.4 CONTROLS, SECTION 11-4.15.5 CLEARANCES.
 PLEASE SHOW ELEVATION ON DRAWINGS.
 4.PAGE A-3.0 WATER RISER AIR CHAMBERS ARE NOT AN
 ENGINEER PRODUCT. PLEASE REMOVE FROM PLANS. WATER
 HAMMER ARRESTORS CAN BE INSTALLED AS REQUIRED BY
 SECTION 604.9. LIST MANUFACTURE AND MODEL NUMBER. WHA'S
 ARE TO BE INSTALLED PER MANUFACTURE INSTALLATION
 INSTRUCTIONS, AS CLOSE TO THE SOURCE OF HAMMERAS
 PERMITED NOT IN THE CEILING.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop X PERMIT EXTENSION
Rev No 1 Status N Date 2008-09-29 Cont ID  
Sent By amckenzi Date 2008-09-29 Time 08:15 Rev Time 0.00
Received By amckenzi Date 2008-09-29 Time 08:15 Sent To  
Notes
2008-09-29 08:16:06PERMIT APPLICATION EXTENDED TO 12/27/08 PER RAB/AMM

Review Stop Z ZONING
Rev No 4 Status P Date 2008-03-04 Cont ID  
Sent By mflis Date 2008-03-04 Time 09:29 Rev Time 0.00
Received By mflis Date 2008-03-04 Time 09:29 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2007-12-02 Cont ID  
Sent By mflis Date 2007-12-02 Time 14:03 Rev Time 0.00
Received By mflis Date 2007-12-02 Time 14:03 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2007-04-25 Cont ID  
Sent By mflis Date 2007-04-25 Time 11:13 Rev Time 0.00
Received By mflis Date 2007-04-25 Time 11:13 Sent To  
Notes
2007-04-25 11:13:39ZONING REVIEW: PASSED
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 1 Status P Date 2007-01-29 Cont ID  
Sent By mflis Date 2007-01-29 Time 13:35 Rev Time 0.00
Received By mflis Date 2007-01-29 Time 13:35 Sent To  
Notes
2007-01-29 13:35:43ZONING REVIEW: PASSED
  
 - REVIEWED FOR EXTERIOR RENOVATIONS
  
 MATT FLIS 822-1445
2007-01-19 13:02:10NEEDS FOR DDA