Plan Review Details - Permit 06110243
Plan Review Stops For Permit 06110243
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2006-12-14 Cont ID  
Sent By mawillia Date 2006-12-14 Time 16:02 Rev Time 0.00
Received By mawillia Date 2006-12-14 Time 16:02 Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2006-12-13 Cont ID  
Sent By lursu Date 2006-12-13 Time 15:37 Rev Time 0.00
Received By lursu Date 2006-12-13 Time 15:37 Sent To  
Notes
2006-12-13 15:40:27SITE PLAN ADDRESS ( 1675 PALM BEACH LAKES BLVD) AND
 APPLICATION ADDRESS ( 1665 PALM BEACH LAKES BLVD) DO
 NOT MATCH .
 - NOTICE OF COMMENCEMENT MUST BE RECORDED FOR THE 1675
 PALM BEACH LAKES BLVD AND NOT 1665 PALM BEACH LAKES
 BLVD , IF THE WORK IS TO BE DONE AT 1675 PALM BEACH
 LAKES BLVD( KNOW AS FORUM ,BLDG A)
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 E-MAIL:[email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-12-13 Cont ID  
Sent By mawillia Date 2006-12-13 Time 14:08 Rev Time 0.00
Received By mawillia Date 2006-12-13 Time 14:08 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-11-27 Cont ID  
Sent By mawillia Date 2006-11-27 Time 14:40 Rev Time 0.00
Received By mawillia Date 2006-11-27 Time 14:40 Sent To  
Notes
2006-11-27 15:36:29*****DENIED*****
  
  
  
 1.THE PERMIT APPLICATION AND THE DOCUMENT SUBMITTAL
 SHEETS REFLECT THE JOB ADDRESS AS 1675 PALM BEACH LAKES
 BOULEVARD, WHEREAS THE ASSIGNED PERMIT NUMBER HAS THE
 ADDRESS OF 1665 PALM BEACH LAKES BOULEVARD.
  
 2.SINCE THE CONTRACT IS GREATER THAN $2500.00, THE
 APPLICANT SHALL FILE WITH THE AHJ EITHER A RECORDED
 NOTICE OF COMMENCEMENT OR A NOTORIZED STATEMENT THAT
 THE NOTICE HAS BEEN FILED FOR RECORDING, ALONG WITH A
 COPY THEREOF.
  
 3.THE LOCATION OF THE SCOPE OF THE WORK SHOULD BE IN
 THE TITLE BLOCK OF THE SUBMITTED PLANS.
  
 4.AS PER WPB FIRE PREVENTION, DUCT SMOKE DETECTORS
 SHALL INITIATE GENERAL FIRE ALARM.AMEND NOTE #8 ON
 LEGEND PLAN SHEET.
  
 5.HOW WILL THE PROPOSED FIRE ALARM WORK IN THE
 BUILDING BE SCHEDULED?I.E. HOW MANY FLOORS WILL BE
 DONE AT ONE TIME?
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-12-05 Cont ID  
Sent By adarroug Date 2006-12-05 Time 10:12 Rev Time 0.00
Received By adarroug Date 2006-12-05 Time 10:12 Sent To FIRE
Notes
2006-12-05 10:13:01TO "F" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-11-27 Cont ID  
Sent By mawillia Date 2006-11-27 Time 14:40 Rev Time 0.00
Received By mawillia Date 2006-11-15 Time 09:33 Sent To  
Notes
2006-11-15 09:33:22TO "F" BOX/APPL. TO INCOMING TODAY