Plan Review Details - Permit 06110215
Plan Review Stops For Permit 06110215
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-10-16 Cont ID  
Sent By jleech Date 2007-10-16 Time 10:16 Rev Time 0.00
Received By lmartine Date 2007-10-16 Time 17:14 Sent To  
Notes
2007-10-16 17:15:03PRODUCT APPROVALS OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-05-09 Cont ID  
Sent By lmartine Date 2007-05-09 Time 11:02 Rev Time 0.00
Received By lmartine Date 2007-05-09 Time 11:02 Sent To M
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-04-12 Cont ID  
Sent By lmartine Date 2007-04-12 Time 15:43 Rev Time 0.00
Received By lmartine Date 2007-04-12 Time 15:43 Sent To  
Notes
2007-04-12 16:03:18 
 BUILDING REVIEW COMMENTS
  
  
  
 1]
 PRODUCT APPROVALS WERE NOT PROVIDED FOR THE STRAPS AND
 TIE DOWNS.
  
 2]
 SHOW SAFETY GLAZING AT TUB LOCATION RIGHT SIDE
 ELEVATION.
  
 3]
 PROVIDE SMOKE ALARMS PER SECTION R313.1, FBC
 RESIDENTIAL CODE.
  
 4]
 NOTICE OF COMMENCEMENT HAS EXPIRED (90 DAYS), PLEASE
 RE-CERTIFY.
  
  
  
  
  
  
  
 L.MARTINEZ
 561-805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-11-28 Cont ID  
Sent By alange Date 2006-11-28 Time 08:34 Rev Time 0.00
Received By alange Date 2006-11-28 Time 08:34 Sent To  
Notes
2006-11-28 09:09:29DENIED
  
  
 1.SHOW SIZE AND LOCATION OF ATTIC ACCESS COMPLYING
 WITH R-806.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.BASED ON ICC BUILDING VALUATION DATA THE PERMIT
 VALUE HAS BEEN REVISED TO $240,797.00.ADDITIONAL
 PERMIT FEES ARE DUE.
  
 4.SAFTEY GLAZING REQUIRED FOR WINDOWS AT TUB
 LOCATIONS.R-308.4
  
 5.PRODUCT APPROVALS REQUIRED FOR LINTELS, STRAPS AND
 TIE-DOWNS AND MULLIONS.OVERHEAD DOOR ONLY STATE
 PRODUCT APPROVAL SUBMITTED.
  
 6.ALL PRODUCT APPROVALS SUBMITTED WITH QUALITY
 ASSURANCE SHALL HAVE THE FOLLOWING STATE APPROVAL
 ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL SHEETS THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM THE STATE. IF
 THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT AN
 APPLICATION FOR LOCAL PRODUCT APPROVAL OR SITE SPECIFIC
 FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 7.THOSE PRODUCT APPROVALS WHICH ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.WPB AMENDMENT TO FBC 106.3.3.
  
  
 8.SUBMIT TWO SETS OF TRUSS DRAWINGS FOR REVIEW PER
 2004 FBC R-802.10.1TRUSS DRAWING REQUIRED TO BE
 APPROVED PRIOR TO INSTALLATION.
  
 9.SHOW PRESSURES ON DOOR AND WINDOW OPENINGS.
  
 10.R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION SO AS
 TO NOT CREATE A HAZARD. LOTS SHALL BE GRADED SO AS TO
 DRAIN SURFACE WATER AWAY FROM FOUNDATION WALLS. THE
 GRADE AWAY FROM FOUNDATION WALLS SHALL FALL A MINIMUM
 OF 6 INCHESWITHIN THE FIRST 10 FEET.
  
 11.SUBMIT A WINDOW, LINTEL AND SHUTTER SCHEDULE.
  
 12.SHOW DIMENTIONS ON ELEVATIONS.
  
 13.SMOKE DETECTORS FOR BEDROOMS SHALL COMPLY WITHR
 313.1
  
 14.ENGINEERS SEAL IS EXPIRED AND SHOULD READ
 "LICENSED"61G1-16.001
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. SUBMIT ONE
 COPY OF OLD PAGES FOR REFERENCE . A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DEPARTMENT
 561-805-6672
  
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-08-22 Cont ID  
Sent By dpalmer Date 2007-08-22 Time 14:30 Rev Time 0.00
Received By dpalmer Date 2007-08-22 Time 14:10 Sent To PC
Notes
2007-08-22 14:31:51STAMP REVISION.
 THE SIGNED COPY BY THE CONTRACTOR IS ON FILE. COPY FOR
 FEILD WAS NOT SIGNED BY CONTRACTOR FOR THEIR OWN
 RECORD. CONTRACTOR TO SIGN HIS COPY.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-05-16 Cont ID  
Sent By dpalmer Date 2007-05-16 Time 17:00 Rev Time 0.00
Received By dpalmer Date 2007-05-16 Time 15:51 Sent To M
Notes
2007-05-16 17:01:03*** PROVISO/REVISION ***
  
 1) NOTE: PLEASE SEE THE MICROWAVE AS SHOWN ON PANEL
 SCHEDULE IS NOT SHOWN OR FIGURED INTO LOAD
 CALCULATIONS.
 PLEASE ADJUST AND UPDATE. 220, 408.4.
 FBC 106.1.2, 106.3.5.4
  
 2) NOTE: PLEASE SEE THE DINING ROOM CIRCUIT WHICH IS
 BEING SHOWN AS 15AMP, WHEN 210.52B1, 210.11C1 REQUIRES
 THIS AS A 20AMP CIRCUIT.
  
 3) NOTE: PLEASE CORRECT ANY CIRCUITING ON PLANS AND
 CORRELATE WITH THE PANEL SCHEDULE. PLEASE SEE SOME
 CIRCUITS SHOWN, SOME NOT, AND SOME OF THE SHOWN
 CIRCUITS DO NOT CORRELATE WITH THE SUBMITTED PANEL
 SCHEDULE. 408.4
  
 ** PLEASE SUBMIT THE ABOVE CORRECTIONS ALONG WITH ANY
 OTHER REVISIONS BEFORE ANY ROUGH ELECTRICAL
 INSPECTION.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 561-805-6717

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-04-21 Cont ID  
Sent By dpalmer Date 2007-04-21 Time 07:45 Rev Time 0.00
Received By dpalmer Date 2007-04-21 Time 06:50 Sent To P
Notes
2007-04-21 07:46:48*** UNSAT 3RD REVIEW ***
  
 ** IMPORTANT**
 THE REVIEW PROCESS HAS BEEN STOPPED AND PLANS HAVE BEEN
 PLACED OUT FRONT UNTIL THE RE-SUB FEE IS PAID. ALL FEES
 ARE DUE AT THE TIME OF SUBMITTING PLANS. THIS OFFICE
 HAS INFORMED THE CONTRACTOR OF THIS ON SEVERAL
 OCCASIONS. THE FEE OF $290.80 MUST BE PAID BEFORE PLANS
 CONTINUE THE ROUTING/REVIEW PROCESS.
  
 ** PLEASE SEE THERE ARE SOME COMMENTS FROM PREVIOUS
 REVIEWS WHICH ARE STILL NOT DONE.
  
 1) NOTE: THIS WAS THE SAME NOTE ON PREVIOUS REVIEW.
 PLEASE SEE THAT THE PLANS WHEN FALLING UNDER THE
 EXCEPTIONS OF THE FLORIDA STATUTES FOR A SF RESIDENCE
 MUST STILL CONTAIN A *PRINTED NAME* AND *SIGNATURE* OF
 THE PERSON TAKING RESPONSIBILITY OF PLANS.
 FS 471.003, 481.229, 489
 FBC 106.1.2
  
 2) NOTE:PLEASE SEE THIS IS THE SAME NOTE FROM
 PREVIOUS REVIEWS. MANY ITEMS WERE CHANGED HOWEVER NOT
 ALL.
 PLEASE SEE THAT THERE ARE LOADS WHICH ARE SHOWN ON THE
 PANEL SCHEDULE WHICH DO NOT CORRELATE WITH THE LOAD
 CALCULATIONS. PLEASE CORRELATE AND SEE THE NEC FOR ALL
 MINIMUM LOADS TO BE SHOWN AND FIGURED FOR DEDICATED
 CIRCUITS AND APPLIANCE LOADS.
 PLEASE SEE STILL MISSING :
 MICROWAVE
 POOL PUMP
 EVEN IF THESE ITEMS ARE SHOWN AS OPTIONAL, THEY WOULD
 STILL BE FIGURED INTO THE LOAD CALCULATIONS.
 NEC 220.
 FBC 106.3.5.4
  
 3) NOTE: SAME NOTE AS TWO PREVIOUS REVIEWS.
 THIS LEADS DIRECTLY INTO THE FOLLOWING COMMENT.
 PLEASE SEE MISSING BATH DEDICATED CIRCUIT(S). 210.52D,
 210.11C3
 PREVIOUS NOTES.
  
 4) NOTE:PLEASE SEE THE TWO PREVIOUS REVIEWS REQUESTED
 A DETAILED PANEL SCHEDULE AS REQUIRED BY THE CODE.
 PLEASE SEE THAT THE PANEL SCHEDULE SHOWN IS MOSTLY SET
 UP AND LOAD CALCULATIONS. PLEASE KNOW THAT A PANEL
 SCHEDULE MUST SHOW ALL MINIMUM CIRCUITS (NOTE #3)
 PLEASE SEE IF A PANEL SCHEDULE STILL INDICATES A
 CERTAIN AMOUNT OF CIRCUITS AS GENERAL LTS, GENERAL
 RECEPTS, THEN THE MINIMUM REQUIRED DEDICATED CIRCUITS
 AS NOTED FOR NOTE #3 ABOVE, AND OTHER AREAS AS NOTED ON
 THE PREVIOUS REVIEW FOR DINING ROOM ETC CAN NOT BE
 VERIFIED.
 PLEASE COMPLETE. IT IS KNOWN THAT THESE ITEMS MAY BE
 CHANGED DURING CONSTRUCTION, HOWEVER THE *MINIMUM* IS
 REQUIRED BY CODE TO BE SHOWN.
 PLEASE SEE THAT THE PANEL SCHEDULE FOR ALL CIRCUITS
 SHALL BE SPECIFIC AS REQUESTED ON PREVIOUS REVIEW.
 PLEASE SEE THE FOLLOWING TEXT IS TAKEN DIRECTLY FROM
 THE NEC CODE COMMENTARY.
  
 *CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY
 CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE
 LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR
 WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME
 PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR
 EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY
 OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN
 COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL
 APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD,
 THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL
 RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR
 ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.''
 CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH
 ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE
 SUFFICIENT DETAIL REQUIRED BY THIS SECTION.* 408.4,
 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 5) NOTE: AS NOTED ON PREVIOUS REVIEWS AND AS THE PANEL
 SCHEDULE IS NOT COMPLETE AT THIS TIME THE MINIMUM
 CIRCUITS AND LOADS CAN NOT BE VERIFIED AT THIS TIME.
 PLEASE SEE 210.52B1, 210.11C1, 220.16 FOR ALL MINIMUM
 LOADS FOR ONE OR MORE OF THE SMALL APPLIANCE CIRCUITS.
 THE DINING ROOM, BREAKFAST ROOMS/AREAS ARE ALSO
 CONSIDERED IN THIS REQUIREMENT AS STATED IN 210.52B1.
 PLEASE SEE THE TOTAL OF 1500VA IS TO BE SHOWN FOR EACH
 OF THESE DEDICATED CIRCUITS. PLEASE INDICATE HOW THE
 DINING ROOM RECEPTACLES AND BREAKFAST AREA RECEPTACLES
 ARE BEING FED. PLEASE BE SURE TO ADJUST ANY LOAD
 CALCULATIONS AS NEEDED.
 PLEASE CORRELATE AND ADJUST.
  
 6) NOTE:PLEASE SEE PREVIOUS REVIEW GAVE A NOTICE TO
 THIS SECTION OF THE FLORIDA STATUTES WHICH REQUIRES A
 LOCAL JURISDICTION TO ASSESS A FEE WHEN *ANY* OF THE
 SAME REPEAT CODE COMPLIANT COMMENT IS MADE THREE OR
 MORE TIMES THIS FEE IS ASSESSED AS REQUIRED. A FEE OF
 $3,489.56 IS DUE UPON RE-SUBMITTAL OF PLANS.
 AS STATED IN THE TWO PREVIOUS REVIEWS, IF THERE ARE ANY
 QUESTIONS TO PLEASE CONTACT THIS OFFICE TO GO OVER
 COMMENTS.
 PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONALS AND REPEAT COMMENTS FOR CODE COMPLIANCE.
 PLEASE SEE THERE ARE SOME COMMENTS WHICH ARE THE SAME
 FROM PREVIOUS REVIEW. THIS IS ONLY GIVEN AS A NOTICE AT
 THIS TIME.
 PLEASE GO THROUGH ALL NOTES CAREFULLY AND ADJUST
 PLANS.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-03-21 Cont ID  
Sent By dpalmer Date 2007-03-21 Time 07:36 Rev Time 0.00
Received By dpalmer Date 2007-03-20 Time 20:18 Sent To M
Notes
2007-03-21 07:41:14NOTE ADDED, PLEASE SEE THE NOTICE OF COMMENCMENT HAS
 SINCE EXPIRED AND IS NOW VOID. FS 713.13(2).
2007-03-21 07:36:21 
 *** UNSAT 2ND REVIEW ***
  
 ** PLEASE SEE THERE ARE SOME COMMENTS FROM PREVIOUS
 REVIEWS AND MANY NEW COMMENTS AND NEW OR CHANGED
 ELECTRICAL SHEETS AND INFORMATION IS NOW SUBMITTED OR
 DIFFERENT ON PLANS SUBMITTED.
  
 1) NOTE: PLEASE SEE THAT THE PLANS WHEN FALLING UNDER
 THE EXCEPTIONS OF THE FLORIDA STATUTES FOR A SF
 RESIDENCE MUST STILL CONTAIN A *PRINTED NAME* AND
 *SIGNATURE* OF THE PERSON TAKING RESPONSIBILITY OF
 PLANS.
 FS 471.003, 481.229, 489
 FBC 106.1.2
  
 2) NOTE: PLEASE SEE PLANS STILL INDICATE A MAIN
 DISCONNECT OUTSIDE ON THE PLANS WHEREAS THE RISER DOES
 NOT INDICATE ANY MAIN. PLEASE CORRELATE AND KNOW IF A
 MAIN IS INSTALLED OUTSIDE, THEN AN EQUIPMENT GROUNDING
 CONDUCTOR WOULD BE REQUIRED FROM THE MAIN TO THE SUB
 PANEL INSIDE.
 PLEASE CORRELATE.
 NEC 215.5, 250.24B, 250.122
 FBC 106.1.2, 106.3.5.4
  
 3) NOTE: PLEASE SEE THAT THERE ARE NUMEROUS LOADS WHICH
 ARE SHOWN ON THE PANEL SCHEDULE WHICH DO NOT CORRELATE
 WITH THE LOAD CALCULATIONS. PLEASE CORRELATE AND SEE
 THE NEC FOR ALL MINIMUM LOADS TO BE SHOWN AND FIGURED
 FOR DEDICATED CIRCUITS AND APPLIANCE LOADS.
 PLEASE SEE:
 SMALL APPLIANCES
 GARAGE DOOR OPENER,
 WATER HEATER
 DRYER,
 MICROWAVE,
 DISHWASHER,
 DISPOSAL,
 ETC ETC.
 NEC 220.
  
 4) NOTE: PLEASE SEE MISSING BATH DEDICATED CIRCUIT(S).
 210.52D, 210.11C3
 PREVIOUS NOTES.
  
 5) NOTE: PLEASE SEE THAT THE PANEL SCHEDULE FOR ALL
 CIRCUITS SHALL BE SPECIFIC AS REQUESTED ON PREVIOUS
 REVIEW.
 PLEASE SEE THE FOLLOWING TEXT IS TAKEN DIRECTLY FROM
 THE NEC CODE COMMENTARY.
  
 *CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY
 CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE
 LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR
 WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME
 PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR
 EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY
 OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN
 COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL
 APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD,
 THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL
 RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR
 ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.''
 CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH
 ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE
 SUFFICIENT DETAIL REQUIRED BY THIS SECTION.* 408.4,
 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 6) NOTE: PLEASE SEE PLANS IN KITCHEN ARE MISSING THE
 RECEPTACLE OUTLETS FOR THE DISHWASHER AND DISPOSAL.
 PLEASE SEE THAT THE PANEL SCHEDULE INDICATES THESE ON A
 2-POLE BREAKER WHICH WOULD MEANS BOTH ARE BEING SERVED
 FROM THE SAME YOKE AS STATED IN 210.4, HOWEVER PLANS DO
 NOT SHOW ANY DEVICES.
 FBC 106.1.2
  
 7) NOTE: PLEASE SEE THE SAME AREA OF KITCHEN COUNTER
 SPACE AS DISH/DISPOSAL IS MISSING GFI RECEPTACLES AS
 REQUIRED PER 210.52C1. THIS WAS ON PREVIOUS NOTES. SEE
 REDLINED PLANS.
  
 8) NOTE: PLEASE SEE MISSING RECEPTACLE PER 210.52 IN
 BEDROOM #2.
  
 9) NOTE: PLEASE SEE 210.52B1, 210.11C1, 220.16 FOR ALL
 MINIMUM LOADS FOR ONE OR MORE OF THE SMALL APPLIANCE
 CIRCUITS. THE DINING ROOM, BREAKFAST ROOMS/AREAS ARE
 ALSO CONSIDERED IN THIS REQUIREMENT AS STATED IN
 210.52B1. PLEASE SEE THE SMALL APPLIANCE CIRCUITS AS
 BEING SHOWN AT 750VA EACH??? PLEASE SEE THE TOTAL OF
 1500VA IS BEING SHOWN FOR BOTH ON THE LOAD
 CALCULATIONS.
 PLEASE CORRELATE AND ADJUST.
  
 10) NOTE: PLEASE SEE MISPRINT FOR NFPA-70, SHOWS NFPA-7
 WHICH IS DIFFERENT CODE. THIS WOULD HAVE BEEN
 RED-LINED, HOWEVER PLANS ARE COMING BACK FOR OTHER
 COMMENTS.
  
 11) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 DESIGN PROFESSIONALS AND REPEAT COMMENTS FOR CODE
 COMPLIANCE. PLEASE SEE THERE ARE SOME COMMENTS WHICH
 ARE THE SAME FROM PREVIOUS REVIEW. THIS IS ONLY GIVEN
 AS A NOTICE AT THIS TIME.
 PLEASE GO THROUGH ALL NOTES CAREFULLY AND ADJUST
 PLANS.
  
 12) NOTE: PLEASE SEE PLANS AND PANEL SCHEDULE INDICATE
 SMOKE DEVICES AS *SD* AND SYMBOL LEGEND HAS THESE AS
 SMOKE DETECTORS.
 PLEASE SEENFPA-72 AS THE USE OF SD FOR SMOKE
 DETECTORS ON PLANS FOR RESIDENTIAL HOMES IS NOT
 ACCEPTABLE WHEN THESE DEVICES ANY ACTUALLY FALL UNDER
 THE DEFINITIONS OF SMOKE ALARMS WHICH WOULD BE SHOWN AS
 SA/SMOKE ALARMS.
 THIS USE OF SD ON PLANS WAS INGENERAL USED SMOKE
 DETECTORS AND WAS ALWAYS ACCEPTED HOWEVER AS THERE IS
 SPECIFIC DIFFERENCE IN THE CODE PLEASE CHANGE PLANS FOR
 ACTUAL DEIVCES. PLEASE SEE THAT THIS IS NOT A NEW
 CODE.
  
 BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE
 DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL
 NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY
 HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF
 SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS
 SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS
 SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS
 FOR OTHER NEW HOMES.
 ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC
 RESIDENTIAL CODE/ FBC AND IN NFPA-72.
 IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE*.
 PLEASE SEE NFPA-72 11.5.1.1, 11.8.3
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-03-20 20:35:432007-03-20 20:35:43
 NOTES TO FOLLOW

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-11-13 Cont ID  
Sent By dpalmer Date 2006-11-13 Time 10:11 Rev Time 0.00
Received By dpalmer Date 2006-11-13 Time 09:15 Sent To M
Notes
2006-11-13 10:12:00****** UNSAT ******
  
 1) NOTE: PLEASE SEE FAC 61G15-23.001, AS THE SEAL FOR
 THE ENGINEER OF RECORD IS NO LONGER VALID AS OF JANUARY
 1ST, 2006.
  
 2) NOTE: PLEASE SEE SHEETS WHICH DO NOT CONTAIN TITLE
 BLOCKS FOR SHEETS WHICH DO CONTAIN SEALS FROM THE
 ENGINEER. PLEASE ALSO SEE SHEETS WHICH ARE SEALED,
 HOWEVER NOT SIGNED BY THE ENGINEER. PLEASE SEE COMMENT
 #1, AS ALL SHEETS WILL BE REQUIRED TO BE RE-DONE. FAC
 61G15-23.002, FS 471.025
  
 3) NOTE: PLEASE SEE FS 481.229(C)1 WITH EXCEPTIONS OF
 WHO CAN DRAW RESIDENTIAL AND WHO SIGN AND SEAL PLANS
 DONE BY ANOTHER DESIGNER.
 PLEASE ALSO SEE FS 471.025/481.221
  
 4) NOTE: PLEASE KNOW THAT NO HAND DRAWN ITEMS MAY BE
 DONE TO PLANS WHICH ARE SIGNED AND SEALED BY ANY DESIGN
 PROFESSIONAL.
 PLEASE SEE BOTH FS 481, AND471.
  
 5) NOTE: PLEASE SEE 210.70 FOR MISSING EGRESS LIGHTING
 REQUIRED IN SEVERAL LOCATIONS. EGRESS IN AND OUT OF
 DWELLING, INTO HABITABLE ROOMS ETC. PLEASE SEE LIGHT
 FIXTURES OF SOME SORT WILL BE REQUIRED FOR FINAL.
 PLEASE ALSO SEE SOME ROOMS ONLY CONTAIN WHAT SEEMS TO
 BE A FAN.
 PLEASE SEE LS 101 7.8
  
 6) NOTE: PLEASE SEE MISSING AIC RATINGS FOR SERVICE
 EQUIPMENT. 110.9, 240.12, PLEASE SUBMIT.
  
 7) NOTE: PLEASE SEE MISSING REQUIRED FOOTER STEEL AS
 PART OF THE GROUNDING ELECTRODE SYSTEM PER 250.50.
  
 8) NOTE: PLEASE PROVIDE ALL ROOM AND AREA DESIGNATIONS
 ON PLANS AND CORRELATE WITH THE PANEL SCHEDULE(S)
 SUBMITTED.
 ALL CIRCUITING SHALL BE SPECIFIC TO ROOMS ETC. EXAMPLE:
 MASTER BEDRM LTS, KITCHEN LTS , BATH RECEPTS ETC.
 240.4,408.4,310.16
 FBC 106.1.2 ADMIN SECT.
  
 9) NOTE: PLEASE SEE MISSING DEDICATED BATH(S)
 CIRCUIT(S) PER 210.52D, 210.11C3.
 MUST BE 20A AND #12.
 PLEASE ALSO SEE A ROOM WHICH MENTIONS BEING
 STORAGE/UTILITY, HOWEVER IF CONTAINING BOTH THE ITEMS
 SHOWN AS A LAVATORY AND WATER CLOSET, GFI RECEPT AS
 REQUIRED PER ABOVE SHALL BE INSTALLED.
  
 10) NOTE: PLEASE SEE 424.3B FOR MIN OCP FOR THE AHU.
 PLEASE SEE A MIN OF 125% BASED ON THE 10KW HEAT.
  
 11) NOTE: PLEASE SEE MISSING COUNTER SPACE RECEPTS PER
 210.52C1
  
 12) NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTS SERVING
 KITCHEN COUNTER SPACE SHALL BE GFI/ GFI PROTECTED.
  
 13) NOTE: PLEASE SEE MISSING GFI DESIGNATION ON SEVERAL
 RECEPTACLE OUTLETS PER THE FOLLOWING.
 210.8A2, 210.8A1, 210.8A3 ETC.
  
 14) NOTE: PLEASE SEE NO LOAD INDICATED FOR THE
 DEDICATED GARAGE DOOR OPENER?
 CAN NOT REVIEW AT THIS TIME FOR COMPLIANCE FOR SIZING
 OF OCP AND AWG.
 310.16, 240.4, 430?
  
 15) NOTE: PLEASE SEE 210.11C1 AND 220.16 FOR MISSING
 REQUIRED LOAD FOR SMALL APPLIANCE CIRCUITS.
  
 16) NOTE: PLEASE SEE 210.11C2 AND 220.16 FOR MISSING
 REQUIRED LOAD FOR LAUNDRY/WASHER CIRCUIT.
  
 17) NOTE: PLEASE SEE SOME AREAS WHICH DO NOT INDICATE
 3-WAY SWITCHING WHERE SWITCH LEGS ON PLANS APPEAR TO
 SHOW THIS??
 PLEASE SEE OTHER AREAS WHERE CONTROL FOR EGRESS
 LIGHTING MAY BE REQUIRED ALSO.
 210.70
  
 18) NOTE: PLEASE SEE NO SYMBOL LEGEND OR SCHEDULE IS
 SHOWN OR WAS SUBMITTED ON SAID PLANS.
 PLEASE SUBMIT AND CORRELATE.
 FBC 106.1.2 ADMIN SECT.
  
 19) NOTE: PLEASE COMPLETE, SUBMIT AND SHOW LOAD
 CALCULATIONS BASED ON SERVICE AND DWELLING AS SHOWN.
 PLEASE SEE 220.31.
 UNABLE TO REVIEW FOR CODE COMPLIANCE AT THIS TIME BASED
 ON THE FACT THAT NO CALCULATIONS WERE SUBMITTED.
  
 20) NOTE: PLEASE INDICATE AND SHOWN SERVICE AND PANEL
 LOCATIONS ON PLANS.
 PLEASE SEE 230.70, 240.24 ETC. AS THE LOCATION WAS NOT
 SUBMITTED OR SHOWN.
  
 21) NOTE: PLEASE SEE MISSING SMOKE ALARMS AS REQUIRED
 PER NFPA-72 11.5.1.1, 11.8.3
  
 22) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE
 REFLECTED ON THE PLANS AS SUBMITTED.
 2002 NFPA-70 (NEC), 2002 NFPA-72
  
 ** PLEASE KNOW BASED ON THE COMMENTS ON THIS REVIEW,
 THERE MAY BE FURTHER COMMENTS DUE TO POSSIBLE CHANGES
 IN PLANS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-08-28 Cont ID  
Sent By adarroug Date 2007-08-28 Time 11:41 Rev Time 0.00
Received By adarroug Date 2007-08-28 Time 11:41 Sent To B
Notes
2007-08-28 11:41:51TO "LMARTINEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-08-14 Cont ID  
Sent By adarroug Date 2007-08-14 Time 10:34 Rev Time 0.00
Received By adarroug Date 2007-08-14 Time 10:34 Sent To E
Notes
2007-08-14 10:35:58TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-07-19 Cont ID  
Sent By adarroug Date 2007-07-19 Time 16:00 Rev Time 0.00
Received By adarroug Date 2007-07-19 Time 16:00 Sent To M
Notes
2007-07-19 16:01:06TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-07-11 Cont ID  
Sent By adarroug Date 2007-07-11 Time 13:41 Rev Time 0.00
Received By adarroug Date 2007-07-11 Time 13:41 Sent To M
Notes
2007-07-11 13:43:37TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-05-15 Cont ID  
Sent By adarroug Date 2007-05-15 Time 13:58 Rev Time 0.00
Received By adarroug Date 2007-05-15 Time 13:58 Sent To E
Notes
2007-05-15 13:58:35TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-04-18 Cont ID  
Sent By adarroug Date 2007-04-18 Time 09:16 Rev Time 0.00
Received By adarroug Date 2007-04-18 Time 09:16 Sent To E
Notes
2007-04-18 09:16:26TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-03-19 Cont ID  
Sent By adarroug Date 2007-03-19 Time 11:49 Rev Time 0.00
Received By adarroug Date 2007-03-19 Time 11:49 Sent To E
Notes
2007-03-19 11:49:37TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-10 Cont ID  
Sent By adarroug Date 2007-03-10 Time 15:44 Rev Time 0.00
Received By adarroug Date 2007-03-10 Time 15:44 Sent To Z
Notes
2007-03-10 15:44:33TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-11-28 Cont ID  
Sent By alange Date 2006-11-28 Time 09:09 Rev Time 0.00
Received By alange Date 2006-11-09 Time 14:32 Sent To  
Notes
2006-11-09 14:32:26TO "SFR" "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2007-07-20 Cont ID  
Sent By tgordon Date 2007-07-20 Time 08:37 Rev Time 0.25
Received By tgordon Date 2007-07-20 Time 08:37 Sent To  
Notes
2007-07-20 08:38:31REVISION TO MECH. PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-07-12 Cont ID  
Sent By tgordon Date 2007-07-12 Time 14:14 Rev Time 0.25
Received By tgordon Date 2007-07-12 Time 14:14 Sent To  
Notes
2007-07-12 14:15:29REVISION TO MECH. PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-05-17 Cont ID  
Sent By tgordon Date 2007-05-17 Time 08:52 Rev Time 0.25
Received By tgordon Date 2007-05-17 Time 08:52 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-05-09 Cont ID  
Sent By tgordon Date 2007-05-09 Time 11:30 Rev Time 0.20
Received By tgordon Date 2007-05-09 Time 11:30 Sent To  
Notes
2007-05-09 11:30:54*** DENIED ***
 1) MECHANICAL PLANS PAGE M-1 DO NOT MATCH THE BUILDING
 FLOOR PLAN PAGE A-1, SEE BATH STORAGE, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-05-02 Cont ID  
Sent By tgordon Date 2007-03-26 Time 11:05 Rev Time 0.25
Received By tgordon Date 2007-03-26 Time 11:05 Sent To B
Notes
2007-05-02 09:51:07*** DENIED ***
 1) MECHANICAL PLANS PAGE M-1 DO NOT MATCH THE BUILDING
 FLOOR PLAN PAGE A-1, SEE BATH STORAGE, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-11-13 Cont ID  
Sent By tgordon Date 2006-11-13 Time 14:04 Rev Time 0.30
Received By tgordon Date 2006-11-13 Time 14:04 Sent To P
Notes
2006-11-13 14:12:05*** DENIED ***
 1) THE MECHANICAL PLANS NEED THE JOB ADDRESS ON THEM.
  
 2) ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN. PER FBC 104.2.1 .
  
 3) PLEASE SHOW THE SIZE OF THE SUPPLY AIR DUCTS TO THE
 DINING ROOM AND THE KITCHEN.
  
 4) WATER CLOSET IN MASTER BATHROOM REQUIRES AN EXHAUST
 FAN, PER 2004 FBC/R M1506.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-05-21 Cont ID  
Sent By jleech Date 2007-05-21 Time 10:09 Rev Time 0.00
Received By jleech Date 2007-05-21 Time 10:09 Sent To B
Notes
2007-05-21 10:16:16PROVISO;
  
 RISER DIAGRAM TO BE SUBMITED THAT MATCHES THE FLOOR
 PLAN.

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-05-02 Cont ID  
Sent By tgordon Date 2007-05-02 Time 09:46 Rev Time 0.00
Received By jleech Date 2007-05-02 Time 08:59 Sent To M
Notes
2007-05-02 09:14:46DENIED;
 1. (2ND REQUEST) REMOVE OR CHANGE , PLUMBING NOTE # 1
 ON PAGE C-1. PIPES 2 1/2" OR LESS SHALL SLOPE 1/4" PER
 FOOT SEE SECTION 704.1.
 2. WATER HEATER NOT SHOWN ON FLOOR PLAN.
 3. PAGE E-1 IS NOT SIGNED OR DATED. STONE ELECTRIC
 CANNOT DESIGN A PLUMBING SANITARY RISER DIAGRAM.
 4. SANITARY RISER DIAGRAM LOOKS LIKE ONE OF THE
 BATHROOMS IS ON THE 2ND FLOOR OF A ONE STORE HOME.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-03-27 Cont ID  
Sent By jleech Date 2007-03-27 Time 09:35 Rev Time 0.00
Received By jleech Date 2007-03-27 Time 09:35 Sent To B
Notes
2007-03-27 09:41:42DENIED;
 1. PLUMBING NOTE # 1, HORIZONTAL SLOPE FOR PIPE 2 1/2"
 AND SMALLER TO BE 1/4" PER FT. TABLE 704.1 PLEASE
 CHANGE NOTE.
 2.ONE SET OF PLANS MARKED IN RED (SANITARY RISER
 DIAGRAM) CORRECT AS MARKED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-11-14 Cont ID  
Sent By jleech Date 2006-11-14 Time 07:22 Rev Time 0.00
Received By jleech Date 2006-11-14 Time 07:22 Sent To B
Notes
2006-11-14 07:30:28DENIED;
 NOT ENOUGH INFORMATION TO DO A PLUMBING PLAN REVIEW.
 PLEASE SUBMIT A SANITARY RISER DIAGRAM TO COMPLY WITH
 FBC-2004 BUILDING CHAPTER 1 WPB AMENDMENTS SECTION
 106.3.5.4.
 SIZE ALL PIPES, AND RISER DIAGRAM SHOULD MATCH FLOOR
 PLAN.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2007-03-16 Cont ID  
Sent By jroach Date 2007-03-16 Time 17:06 Rev Time 0.00
Received By jroach Date 2007-03-16 Time 17:06 Sent To I
Notes
2007-03-16 17:09:12***PROVISO***
  
 1) A SEPARATE PERMIT SHALL BE ACQUIRED FOR INSTALLATION
 OF ANY FENCE, PRIVACY WALL, ETC.
  
 2) THE A/C EQUIPMENT SHALL BE NO CLOSER THAN SIX (6)
 FEET TO THE REAR PROPERTY LINE.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-11-11 Cont ID  
Sent By mmclean Date 2006-11-11 Time 10:34 Rev Time 0.00
Received By mmclean Date 2006-11-11 Time 07:10 Sent To I
Notes
2006-11-11 07:16:43DENIED,
 1. PLEASE SUBMIT TWO COPIES OF SURVEYS, SHOWING THE
 PROPOSED NSFR WITH SETBACKS (SF11 - SEC 94-73.
 2. TWO COPIES OF SURVEYS MUST SHOW THE A/C UNIT WITH
 SETBACKS.
 3. PLEASE PROVIDE THE DIMENSION OF THE PROPOSED
 DRIVEWAY (WIDTH & LENGTH). NOTE: MUST MAINTAIN 1000SQ
 FT OR 75% OF
 LANDSCAPE, WHICHEVER IS LESS WITHIN THE FIRST 25FT
 FRONT SETBACK.
 4. SITEPLAN SUBMITTED HAS INSUFFICIENT INFORMATION FOR
 A COMPLETE REVIEW. DOES NOT PROVIDE THE SETBACKS (FRONT
 & REAR).
 5. FLOOR PLAN DOES NOT SHOW GARAGE DOOR FOR VEHICLE TO
 ENTER. PLEASE CLARIFY ON THE PLANS.
  
 NOTE: ANY FENCE/GATE/WALL MUST HAVE A SEPARATE PERMIT
 WITH EASEMENT APPROVAL FROM THE CITY OF WEST PALM BEACH
 UTILITY DEPT. (UTILITY EASEMENT).
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720