Plan Review Details - Permit 06110152
Plan Review Stops For Permit 06110152
Review Stop AD ADDRESSING
Rev No 5 Status P Date 2007-12-19 Cont ID  
Sent By lursu Date 2007-12-19 Time 16:48 Rev Time 0.00
Received By lursu Date 2007-12-19 Time 16:48 Sent To  
Notes
2007-12-19 16:48:54SITE ADDRESS IS CORRECT.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]
  

Review Stop AD ADDRESSING
Rev No 4 Status F Date 2007-11-05 Cont ID  
Sent By lursu Date 2007-11-05 Time 09:17 Rev Time 0.00
Received By lursu Date 2007-11-05 Time 09:17 Sent To  
Notes
2007-11-05 09:18:50SEE COMMENTS DATED 08/28/07& 05/07/07.THE NEW SITE
 ADDRESS MUST BE DEPICTED ON THE PLANS AND PERMIT
 APPLICATION.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 3 Status F Date 2007-08-28 Cont ID  
Sent By lursu Date 2007-08-28 Time 16:43 Rev Time 0.00
Received By lursu Date 2007-08-28 Time 16:43 Sent To  
Notes
2007-08-28 16:48:00SEE COMMENTS DATED MAY 7,2007 .THE NEW STRUCTURE WILL
 BE ASSIGNED WITH A NEW SITE ADDRESS 821 N FLAGLER DR
 .THE REVISED PLANS AND APPLICATION MUST HAVE THE NEW
 ADDRESS REFLECTED ON THEM.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2007-05-07 Cont ID  
Sent By lursu Date 2007-05-07 Time 14:05 Rev Time 0.00
Received By lursu Date 2007-05-07 Time 14:05 Sent To  
Notes
2007-05-07 14:08:36MULTIPLE BUILDINGS CAN NOT USE THE SAME ADDRESS
 NUMBER.EACH RESIDENCE/COMMERCIAL BUILDING MUST HAVE A
 UNIQUE ADDRESS .THE 911 EMERGENCY SERVICES ARE USING
 THESE SITE ADDRESSES TO LOCATE THESE BUILDINGS IN CASE
 OF AN EMERGENCY .BASED ON THIS STATEMENT EACH STRUCTURE
 MUST HAVE A UNIQUE ADDRESS .
  
 THE FOLLOWING ADDRESSES ARE PROPOSED FOR ALL BUILDINGS
 LOCATED ON THESE PARCELS:
  
 PCN = 74 43 43 15 21 004 0010
 PCN = 74 43 43 15 21 005 0070
 PCN = 74 43 43 15 20 009 0210
 PCN = 74 43 43 15 20 009 0110
 PCN = 74 43 43 15 20 009 0090
  
 PCN = 74 43 43 15 20 009 0070
 PCN = 74 43 43 15 20 009 0050
 PCN = 74 43 43 15 20 009 0070
 PCN = 74 43 43 15 20 002 0010
 PCN = 74 43 43 15 20 009 0020
 PCN = 74 43 43 15 20 002 0050
  
 - EXISTING MARY ALICE BUILDING - THE ADDRESS REMAINS AS
 807 N FLAGLER DR
 - MACHILIN THEATRE - NEW ADDRESS 815 N FALGLER DR
 - PROPOSED GYMNASIUM- 821 N FLAGLER DR
 - LEWIS HALL EAST - 801 N FLAGLERDR
 -LEWIS HALL WEST - 805 N FLAGLER DR
 - CASA MARIA - ADDRESS REMAINS AS 810 N OLIVE AVE
  
 FOR THESE PARCELS :
 PCN = 74 43 43 15 21 005 0011
 PCN = 74 43 43 15 21 005 0012
 PCN = 74 43 43 15 21 005 0013
 THE ADDRESSES REMAIN AS:
 - OFFICES FACING N OLIVE AVE- REMAINS AS 804 N OLIVE
 AVE
 - MONTESORRI CENTER - REMAINS AS 800 N OLIVE AVE
  
 THE UNITY OF TITLE MUST BE RECORDED FOR ALL THE PARCELS
 IN THE PROPERTY OF THE ROSARIAN ACADEMY. ALL THE
 REVISED SITE PLANS AND APLLICATION MUST CONTAIN THE NEW
 ADDRESS ASSIGNED.
 AN ADDRESS RANGE SIGN MUST BE INSTALLED AT THE MAIN
 ENTRANCE OF THE DEVELOPMENT.
  
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2007-04-24 Cont ID  
Sent By lursu Date 2007-04-24 Time 14:46 Rev Time 0.00
Received By lursu Date 2007-04-23 Time 14:23 Sent To  
Notes
2007-04-24 14:50:57A NEW SITE ADDRESS IS REQUIRED TO BE ASSIGNED TO THE
 NEW CONSTRUCTION.ALSO THE UNITY OF TITLE FOR ALL
 PARCELS INVOLVED IN THE PROJECT MUST BE RECEIVED BY
 THIS DEPARTMENT.PLEASE SUBMIT THE LAYOUT OF THIS
 PROJECT SO ALL THE EXISTING AND NEW BUILDINGS BE
 ASSIGNED WITH A NEW ADDRESS.THE MAIN BUILDING FACING N
 FLAGLER DR WILL MAINTAIN THE EXISTING ADDRESS 807 N
 FLAGLER DR .
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 19 Status P Date 2009-08-03 Cont ID  
Sent By jwitmer Date 2009-08-03 Time 16:58 Rev Time 0.50
Received By jwitmer Date 2009-08-03 Time 16:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 18 Status P Date 2009-07-14 Cont ID  
Sent By jwitmer Date 2009-07-14 Time 14:35 Rev Time 0.55
Received By jwitmer Date 2009-07-14 Time 14:35 Sent To  
Notes
2009-07-14 14:36:08BUILDING PLAN REVIEW
 PERMIT: 06110152
 ADD: 821 N. FLAGLER DR.
 CONT: ANDERSON-MOORE
 TEL: (561)662-1819
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS TO THE ADMINISTRATIVE
 CODE
  
 REVIEW
 ACTION: REVIEWED
 SUBMITTAL: BILCO HATCH LOCAL APPROVAL

Review Stop B BUILDING (STRUCTURAL)
Rev No 17 Status F Date 2009-06-15 Cont ID  
Sent By jwitmer Date 2009-06-15 Time 08:28 Rev Time 1.55
Received By jwitmer Date 2009-06-15 Time 08:28 Sent To  
Notes
2009-06-15 08:45:46BUILDING PLAN REVIEW
 PERMIT: 06110152
 ADD: 821 N. FLAGLER DR.
 CONT: ANDERSON-MOORE
 TEL: (561)662-1819
  
 JUNE 15, 2009
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS TO THE ADMINISTRATIVE
 CODE
 ORIGINAL REVIEW
 REVISION REVIEW DATED; 10-06-08
  
 ACTION:DENIED
  
 1) SHEET A3.2.1 & A5.2.3
  
 A) REVISION# 4 OF THIS SHEET INDICATES THE CHANGE IN
 FILL MATERIAL FROM EARTHENED FILL TO A GEO FOAM TO
 LESSEN THE LATERAL LOAD OR PRESSURES ON THE STAIR
 WALLS. PLEASE PROVIDE DOCUMENTATION THAT THE FOAM WILL
 MEET THE REQUIREMENTS OF SUPPORTING 3000 PSF FOUNDATION
 NOTES SHEET S-5. SHEET A.5.2.3 DETAIL# 1 INDICATES SEE
 STRUCTURAL DRAWINGS. STRUCTURAL SHEET S-2.1 THE WEST
 END OF THE SECOND FLOOR SLAB HAS A CUT SECTION DETAIL
 3/ S-9. WHEN REVIEWING THIS DETAIL THE PLANS STILL
 INDICATE EARTHENED FILL NOT A GEO FOAM, THE NOTE ON
 THIS SHEET INDICATES CONCRETE STAIRS ON GRADE SEE
 TYPICAL DETAIL. S-6 . S-6 AGAIN INDICATES EARTHENED
 FILL WITH WIRE MESH W.F 6X6 /W1.4XW1.4 NOT A STRUCTURAL
 STEEL REINFORCED SLAB.
  
 B CHAPTER 26 DEALS WITH FOAM PLASTICS WHEN USED IN
 CONSTRUCTION OF STRUCTURES AND BUILDINGS. THERE IS NO
 SECTION THAT INDICATES THE USE OF FOAM AS A FILLER
 BENEATH SLABS BUT TO USE FOAM FOR THIS APPLICATION IT
 WILL NEED TO COMPLY WITH 2603.8. SUCH TESTING SHALL BE
 RELATED TO THE ACTUAL END-USE CONFIGURATION AND BE
 PERFORMED ON THE FINISHED MANUFACTURED FOAM PLASTIC
 ASSEMBLY IN THE MAXIMUM THICKNESS INTENDED FOR USE.
  
 JUNE 15, 2008
 THE SUBMITTAL FOR GEO FOAM HAS NOT MET THE REQUIREMENTS
 OF 2603.8. THE 2004 NOR THE 2007 FBC DOES NOT RECONIZE
 THE ASTM D-6817 STANDARD. ALL CUT SHEETS INDICATE THE
 USE OF GEO FOAM IN GENERAL EARTHWORK APPLICATIONS,
 LEVEES, DIKES, BIRMS... NOT FOR WWITHIN BUILDINGS. THE
 GEO FOAM BROSHURE DOES INDICATE THAT IT IS COMBUSTIBLE!
 SECTION 603.1 DEALS WITH ALLOWED COMBUSTIBLES IN TYPE I
 OR II BUILDINGS, EXCEPTION 3 DEALS WITH PLASTICS (FOAM)
 IN ACCORDANCE WITH CHAPTER 26.
  
 TO ALLOW FOAM PLASTICS IN BUILDINGS THE FOLOWING MUST
 BE MET:
 2603.3 SURFACE-BURNING CHARACTERISTICS. UNLESS
 OTHERWISE INDICATED IN THIS SECTION, FOAM PLASTIC
 INSULATION AND FOAM PLASTIC CORES OF MANUFACTURED
 ASSEMBLIES SHALL HAVE A FLAME SPREAD INDEX OF NOT MORE
 THAN 75 AND A SMOKE-DEVELOPED INDEX OF NOT MORE THAN
 450 WHERE TESTED IN THE MAXIMUM THICKNESS INTENDED FOR
 USE IN ACCORDANCE WITH ASTM E 84.
  
 EXCEPTION #4 IS WHEN FOAM PLASTIC IS USED IN
 INSTALATIONS GREATER THAN 4". FOAM PLASTIC INSULATION
 GREATER THAN 4 INCHES (102 MM) IN THICKNESS SHALL HAVE
 A MAXIMUM FLAME SPREAD INDEX OF 75 AND A
 SMOKE-DEVELOPED INDEX OF 450 WHERE TESTED AT A MINIMUM
 THICKNESS OF 4 INCHES (102 MM), PROVIDED THE END USE IS
 APPROVED IN ACCORDANCE WITH SECTION 2603.8 USING THE
 THICKNESS AND DENSITY INTENDED FOR USE.
  
 2603.8 SPECIAL APPROVAL.
 FOAM PLASTIC SHALL NOT BE REQUIRED TO COMPLY WITH THE
 REQUIREMENTS OF SECTIONS 2603.4 THROUGH 2603.7, WHERE
 SPECIFICALLY APPROVED BASED ON LARGE-SCALE TESTS SUCH
 AS, BUT NOT LIMITED TO, FM 4880, UL 1040, NFPA 286 OR
 UL 1715. SUCH TESTING SHALL BE RELATED TO THE ACTUAL
 END-USE CONFIGURATION AND BE PERFORMED ON THE FINISHED
 MANUFACTURED FOAM PLASTIC ASSEMBLY IN THE MAXIMUM
 THICKNESS INTENDED FOR USE. FOAM PLASTICS THAT ARE USED
 AS INTERIOR FINISH ON THE BASIS OF SPECIAL TESTS SHALL
 ALSO CONFORM TO THE FLAME SPREAD REQUIREMENTS OF
 CHAPTER 8. ASSEMBLIES TESTED SHALL INCLUDE SEAMS,
 JOINTS AND OTHER TYPICAL DETAILS USED IN THE
 INSTALLATION OF THE ASSEMBLY AND SHALL BE TESTED IN THE
 MANNER INTENDED FOR USE.
  
 PLEASE PROVIDE THE FLAME SPREAD AND SMOKE DEVELOPMENT
 IN COMPLIANCE WITH 2603.3 OR THE TESTING FOR
 LARGE-SCALE TEST IN COMPLIANCE WITH 2603.8.

Review Stop B BUILDING (STRUCTURAL)
Rev No 16 Status P Date 2009-04-07 Cont ID  
Sent By jwitmer Date 2009-04-07 Time 11:08 Rev Time 1.77
Received By jwitmer Date 2009-04-07 Time 11:08 Sent To  
Notes
2009-04-07 11:09:53BUILDING PLAN REVIEW
 PERMIT: 06110152
 ADD: 821 N. FLAGLER DR.
 CONT: ANDERSON-MOORE
 TEL: (561)662-1819
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS TO THE ADMINISTRATIVE
 CODE
  
 REVISION REVIEW: DATED 2/26/09
 ACTION: REVIEWED
 A.2.2.1
 A.2.2.2
 A.3.1.1
 A.3.1.2

Review Stop B BUILDING (STRUCTURAL)
Rev No 15 Status P Date 2009-01-28 Cont ID  
Sent By jwitmer Date 2009-01-28 Time 15:19 Rev Time 2.22
Received By jwitmer Date 2009-01-28 Time 15:19 Sent To  
Notes
2009-01-28 16:02:35ARCHITECTURAL & STRUCTURAL REVISIONS DATED 10-06-09

Review Stop B BUILDING (STRUCTURAL)
Rev No 14 Status F Date 2009-01-27 Cont ID  
Sent By jwitmer Date 2009-01-27 Time 08:45 Rev Time 0.77
Received By jwitmer Date 2009-01-27 Time 08:45 Sent To  
Notes
2009-01-27 11:01:13BUILDING PLAN REVIEW
 PERMIT: 06110152
 ADD: 821 N. FLAGLER DR.
 CONT: ANDERSON-MOORE
 TEL: (561)662-1819
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS TO THE ADMINISTRATIVE
 CODE
  
 REVISION REVIEW DATED; 10-06-08
 ACTION:DENIED
  
 1) SHEET A3.2.1 & A5.2.3
  
 A) REVISION# 4 OF THIS SHEET INDICATES THE CHANGE IN
 FILL MATERIAL FROM EARTHENED FILL TO A GEO FOAM TO
 LESSEN THE LATERAL LOAD OR PRESSURES ON THE STAIR
 WALLS. PLEASE PROVIDE DOCUMENTATION THAT THE FOAM WILL
 MEET THE REQUIREMENTS OF SUPPORTING 3000 PSF FOUNDATION
 NOTES SHEET S-5. SHEET A.5.2.3 DETAIL# 1 INDICATES SEE
 STRUCTURAL DRAWINGS. STRUCTURAL SHEET S-2.1 THE WEST
 END OF THE SECOND FLOOR SLAB HAS A CUT SECTION DETAIL
 3/ S-9. WHEN REVIEWING THIS DETAIL THE PLANS STILL
 INDICATE EARTHENED FILL NOT A GEO FOAM, THE NOTE ON
 THIS SHEET INDICATES CONCRETE STAIRS ON GRADE SEE
 TYPICAL DETAIL. S-6 . S-6 AGAIN INDICATES EARTHENED
 FILL WITH WIRE MESH W.F 6X6 /W1.4XW1.4 NOT A STRUCTURAL
 STEEL REINFORCED SLAB.
  
 B CHAPTER 26 DEALS WITH FOAM PLASTICS WHEN USED IN
 CONSTRUCTION OF STRUCTURES AND BUILDINGS. THERE IS NO
 SECTION THAT INDICATES THE USE OF FOAM AS A FILLER
 BENEATH SLABS BUT TO USE FOAM FOR THIS APPLICATION IT
 WILL NEED TO COMPLY WITH 2603.8. SUCH TESTING SHALL BE
 RELATED TO THE ACTUAL END-USE CONFIGURATION AND BE
 PERFORMED ON THE FINISHED MANUFACTURED FOAM PLASTIC
 ASSEMBLY IN THE MAXIMUM THICKNESS INTENDED FOR USE.
  
 2) SHEET A4.1.2
  
 A) CITY STAMPED SET OF PLANS INDICATES A REVISION# 2
 DATED 7/13/07 MUSIC CLASSROOM # 3 WHERE REVISION# 2
 INDICATES A LEVEL FLOOR. IN TTHE REVISION SET,
 REVISION# 3 WHERE THE CITY PLANS SHOW A FLAT FLOOR
 SURFACE THE NEW REVISION 3 SET SHOWS DASHED LINES UNDER
 REVISION# 2, WHAT APPEARS TO BE RAISED PLATFORM? THIS
 WAS AN ISSUE THAT I BELIEVE YOU WERE GOING TO THE STATE
 FOR A WAIVER TO THE STATE FOR VERTICAL ACCESSIBILITY,
 IF YOU RECEIVED THE WAIVER PLEASE PROVIDE A COPY, IF
 NOT REMOVE THE DASHED LINES AS IN THE ISSUED SET OF
 PLANS.VERTICAL ACCESSIBILITY 11-4.1.3(5).
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 MEMBER OF BOAF, THE BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA: PROTECTING LIVES AND PROPERTY SINCE 1953.
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. UNDER FLORIDA STATE STATUTE SB 80, E-MAIL
 ADDRESSES ARE PUBLIC RECORDS.WRITTEN COMMUNICATIONS TO
 OR FROM LOCAL OFFICIALS REGARDING CITY BUSINESS ARE
 PUBLIC RECORD, AVAILABLE TO THE PUBLIC UPON REQUEST.
 YOUR E-MAIL COMMUNICATIONS ARE THEREFORE SUBJECT TO
 PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 13 Status P Date 2008-11-12 Cont ID  
Sent By jwitmer Date 2008-11-12 Time 13:32 Rev Time 0.77
Received By jwitmer Date 2008-11-12 Time 13:32 Sent To  
Notes
2008-11-12 13:37:02BUILDING PLAN REVIEW
 PERMIT: 06110152
 ADD: 821 N. FLAGLER DR.
 CONT: ANDERSON-MOORE
 TEL: (561)662-1819
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS TO THE ADMINISTRATIVE
 CODE
  
 REVIEW SHOP DRAWINGS
 ACTION:REVIEWED
  
 SUBMITTAL: STEEL SHOP DRAWINGS
 REPAIR OF J26
 REMOVAL OF EXTENSION LETTER
 REPAIR OF J7
 BRIDGING REPLACEMENTS FOR RTU'S AND DECK FIX
 REPAIRS OF T3, T4, T5 & T6.
 SHOP DRAWING FOR 1B5 SPLICE
 NUCOR VULCRAFT LAYOUT SHEET

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status P Date 2008-07-08 Cont ID  
Sent By jwitmer Date 2008-07-08 Time 11:29 Rev Time 3.55
Received By jwitmer Date 2008-07-08 Time 11:29 Sent To  
Notes
2008-07-08 11:41:35BUILDING PLAN REVIEW
 PERMIT: 06110152
 ADD: 821 N. FLAGLER DR.
 CONT: ANDERSON-MOORE
 TEL: (561)662-1819
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS TO THE ADMINISTRATIVE
 CODE
  
 REVISION
 ACTION: REVIEWED REVISION # 4 DATED 4/14/08

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status P Date 2008-06-30 Cont ID  
Sent By jwitmer Date 2008-06-30 Time 11:38 Rev Time 1.11
Received By jwitmer Date 2008-06-30 Time 11:38 Sent To  
Notes
2008-06-30 11:40:15BUILDING PLAN REVIEW
 PERMIT: 06110152
 ADD: 821 N. FLAGLER DR.
 CONT: ANDERSON-MOORE
 TEL: (561)662-1819
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS TO THE ADMINISTRATIVE
 CODE
  
 REVIEW
 ACTION:REVIEWED
 SUBMITTAL:
 SHORING 2ND FLOOR & 3RD FLOOR
 SHOP DRAWINGS MISC STEEL
 SHORING CERTIFICATION LETTER THIRD FLOOR

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2008-06-02 Cont ID  
Sent By jwitmer Date 2008-06-02 Time 14:27 Rev Time 2.22
Received By jwitmer Date 2008-06-02 Time 14:27 Sent To  
Notes
2008-06-02 14:47:22BAR JOIST SHOP DRAWINGS
 DECK PLACEMENT
 STEEL STAIRS AND
 MISCS STEEL

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status F Date 2008-05-06 Cont ID  
Sent By jwitmer Date 2008-05-06 Time 09:47 Rev Time 0.55
Received By jwitmer Date 2008-05-06 Time 09:47 Sent To PC
Notes
2008-05-06 09:53:59BUILDING PLAN REVIEW
 PERMIT: 06110152
 ADD: 821 N. FLAGLER DR.
 CONT: ANDERSON-MOORE
 TEL: (561)662-1819
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS TO THE ADMINISTRATIVE
 CODE
  
 REVIEW
 ACTION: DENIED
  
 SUBMITTAL:
 1) LETTER : SHORING LETTER FROM JOHN P. MCGREW, P.E.
 COPIED, NOT ORIGINAL SEAL NOR SIGNATURE
 2) LETTER : SHORING INSPECTION FROM JUAN A DIAZ, P.E.
 COPIED NOT ORINAL SEAL NORSIGNATURE
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2008-05-06 Cont ID  
Sent By jwitmer Date 2008-05-06 Time 09:37 Rev Time 1.10
Received By jwitmer Date 2008-05-06 Time 09:37 Sent To PC
Notes
2008-05-06 09:44:26BUILDING PLAN REVIEW
 PERMIT: 06110152
 ADD: 821 N. FLAGLER DR.
 CONT: ANDERSON-MOORE
 TEL: (561)662-1819
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS TO THE ADMINISTRATIVE
 CODE
  
 REVIEW
 ACTION: REVIEWED
 SUBMITTAL: STEEL SHOP DRAWINGS DIXIE METAL PRODUCTS
 STEEL BEAMS AND ACCESSORIES

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2008-04-16 Cont ID  
Sent By jwitmer Date 2008-04-16 Time 14:46 Rev Time 1.55
Received By jwitmer Date 2008-04-16 Time 14:46 Sent To  
Notes
2008-04-16 14:54:30STRUCTURAL STEEL SHOP DRAWINGS BEAMS & BOLT EMBEDS

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2008-02-21 Cont ID  
Sent By jwitmer Date 2008-02-21 Time 11:43 Rev Time 1.33
Received By jwitmer Date 2008-02-21 Time 11:43 Sent To PC
Notes
2008-02-21 11:45:01SUBMITTALS:CONCRETE DESIGN MIX
 PRECAST LINTELS

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-01-02 Cont ID  
Sent By jwitmer Date 2008-01-02 Time 10:50 Rev Time 4.44
Received By jwitmer Date 2008-01-02 Time 10:50 Sent To PC
Notes
2008-01-02 10:53:33BUILDING PLAN REVIEW
 PERMIT: 06110152
 ADD: 821 N FLAGLER DR
 CONT: ANDERSON-MOORE
 TEL: (561)662-1819
 JAN. 02,2007
 FL BLD CODE= 2004 FLORIDA BUILDING CODE W/ 2007 FBC
 REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
  
 ISSUED PERMIT:
 BUILDING PROVISOS:
 1) 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 2) 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE
 UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED
 MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS.
 AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION TO
 THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
 3) PRODUCT APPROVALS: C) ROOF HATCHES: THIS WILL BE A
 PROVISO, IF AT TIME OF CERTIFICATE OF COMPLETION THE
 MANUFACTURER HAS NOT RECEIVED EITHER STATE APPROVAL OR
 A MIAMI-DADE NOA A LOCAL PRODUCT APPROVAL WILL NEED TO
 BE ACHIEVED BEFORE C/O WILL BE ISSUED. 102.1* WHERE, IN
 ANY SPECIFIC CASE, DIFFERENT SECTIONS OF THIS CODE
 SPECIFY DIFFERENT MATERIALS, METHODS OF CONSTRUCTION OR
 OTHER REQUIREMENTS, THE MOST RESTRICTIVE SHALL GOVERN.
 WHERE THERE IS A CONFLICT BETWEEN A GENERAL REQUIREMENT
 AND A SPECIFIC REQUIREMENT, THE SPECIFIC REQUIREMENT
 SHALL BE APPLICABLE.
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-11-05 Cont ID  
Sent By jwitmer Date 2007-11-05 Time 12:47 Rev Time 3.33
Received By jwitmer Date 2007-11-05 Time 12:47 Sent To  
Notes
2007-11-05 12:53:55BUILDING PLAN REVIEW
 PERMIT: 06110152
 ADD: 807 N. FLAGLER DR.
 CONT: ANDERSON-MOORE
 TEL: (561)662-1819
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS TO THE ADMINISTRATIVE
 CODE
  
 4THREVIEW
 ACTION: DENIED
 PLANS ARE CODE COMPLIANT, REQUIRES IMPACT FEES PAID
 BEFORE ISSUANCE.
  
 1) PLEASE CORRECT ADDDRESS ON PLANS OF THE NEW
 BUILDING, NO LONGER AN ADDITION SINCE THE CONCEPT OF A
 4 HR FIRE WALL.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A PERMIT WILL BE
 ISSUED. NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE
 NOTICE OFCOMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE
 IS NULL & VOID.
  
 3) BUILDING PROVISO: 109.3.10 IMPACT OF CONSTRUCTION.
  
 4) BUILDING PROVISO: 109.3.10.1 HURRICANE PROTECTION.
  
 5) COMPLIED, SPECIAL INSPECTOR AGREEMENT, THANK YOU.
  
 6) COMPLIED, 3-SOILS REPORTS.
  
 7-30 COMPLIED.
  
 31) BUILDING PROVISO: (C)IF AT TIME OF CERTIFICATE OF
 COMPLETION THE MANUFACTURER HAS NOT RECEIVED EITHER
 STATE APPROVAL OR A MIAMI-DADE NOAA LOCAL PRODUCT
 APPROVAL WILL NEED TO BE ACHIEVED BEFORE C/O.
  
 32-35)COMPLIED.
  
 36)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-09-04 Cont ID  
Sent By jwitmer Date 2007-09-04 Time 15:59 Rev Time 12.00
Received By jwitmer Date 2007-09-04 Time 14:41 Sent To  
Notes
2007-09-04 14:42:58BUILDING PLAN REVIEW
 PERMIT: 06110152
 ADD: 807 N. FLAGLER DR.
 CONT: ANDERSON-MOORE
 TEL: (561)662-1819
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS TO THE ADMINISTRATIVE
 CODE
  
 3RDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A PERMIT WILL BE
 ISSUED. NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE
 NOTICE OFCOMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE
 IS NULL & VOID.
  
 3) BUILDING PROVISO: 109.3.10 IMPACT OF CONSTRUCTION.
  
 4) BUILDING PROVISO: 109.3.10.1 HURRICANE PROTECTION.
  
 5) COMPLIED, SPECIAL INSPECTOR AGREEMENT, THANK YOU.
  
 6) COMPLIED, 3-SOILS REPORTS.
  
 7)SECOND REQUEST,FLOOD ELEVATION CERTIFICATE WILL
 BE REQUIRED BEFORE THE ISSUANCE OF THE CERTIFICATE OF
 OCCUPANCY. THE ISSUE WITH THE FLOOD ELEVATION
 CERTIFICATE IS IT WILL BE REQUIRED FOR THE "WHOLE
 BUILDING" BEING THAT THE PROPOSED, THE ADDITION IS OVER
 50% WORTH OF THE EXISTING BUILDING "SUBSTANTIAL
 IMPROVEMENTS" NEED TO BE MET UNDER W. P. B. CODE OF
 ORDNANCES
 CITY CODEARTICLE XVII FLOOD PREVENTION & CONTROL SEE
 ATTACHED DOCUMENT FOR COMPLIANCE. NOTE UNDER SECTION
 94-546(B)(2) NONRESIDENTIAL CONSTRUCTION COMPLIANCE
 THROUGH
 FLOOD PROOFING.SEE THE EXISTING MARGARET TIGHE
 MACHLIN THEATER FINISH FLOOR IS 5.13'N A VD 88. SEE
 CIVIL PLAN C-1.
 CITY CODE OF ORDNANCES
 94-546 (B)(2)NONRESIDENTIAL CONSTRUCTION.ALL NEW
 CONSTRUCTION
 OR SUBSTANTIAL IMPROVEMENT OF ANY COMMERCIAL,
 INDUSTRIAL OR OTHER NONRESIDENTIAL STRUCTURE SHALL
 EITHER HAVE THE LOWEST FLOOR, BASE FLOOD ELEVATION OR,
 TOGETHER WITH ATTENDANT UTILITY AND SANITARY
 FACILITIES, BE FLOOD PROOFED SO THAT BELOW SIX INCHES
 ABOVE THE FLOOD BASE LEVEL THE STRUCTURE IS WATERTIGHT,
 WITH WALLS SUBSTANTIALLY IMPERMEABLE TO THE PASSAGE OF
 WATER AND WITH STRUCTURAL COMPONENTS HAVING THE
 CAPABILITY OF RESISTING HYDROSTATIC AND HYDRODYNAMIC
 LOADS AND EFFECTS OF BUOYANCY. A REGISTERED
 PROFESSIONAL ENGINEER OR ARCHITECT SHALL CERTIFY THAT
 THE STANDARDS OF THIS SUBSECTION ARE SATISFIED. SUCH
 CERTIFICATION SHALL BE PROVIDED TO THE CITY ENGINEER.
  
 8-12 COMPLIED.
  
 13) COMPLIED, NOTED THE EXISTING DROP OFF ZONE FOR THE
 ROSARIAN ACADEMY IS AT THE MARY ALICE FORTIN BUILDING.
  
 14-28)COMPLIED.
  
 29) 2ND REQUEST,1609.1.4 PROTECTION OF OPENINGS. IN
 WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE IN THE LOWER 60
 FEET (18.3 M) IN BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED OPENINGS IN THE REST
 OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT
 RECEIVES POSITIVE PRESSURE IS IMPACT RESISTANT OR
 PROTECTED WITH AN IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND ASTM E 1996,
 OR MIAMI-DADE TAS 201, 202 AND 203 REFERENCED THEREIN
 AS FOLLOWS: 1.GLAZED OPENINGS LOCATED WITHIN 30 FEET
 (9.1 M) OF GRADE SHALL MEET THE REQUIREMENTS OF THE
 LARGE MISSILE TEST. 2.GLAZED OPENINGS LOCATED MORE
 THAN 30 FEET (9.1 M) ABOVE GRADE SHALL MEET THE
 PROVISIONS OF THE SMALL MISSILE TEST.
  
 30)2ND REQUEST, PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED
 TO COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72.
  
 31)2ND REQUEST,FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT
 INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS FOLLOWS:A)
 EXTERIOR GLAZED SWING DOORS, SINGLE AND PAIRS ?OK
  
 B) EXTERIOR HOLLOW METAL FRAME DOORS, SINGLE AND PAIRS
 FL 6224- OK
  
 C) ROOF HATCHES: THIS WILL BE A PROVISO, IF AT TIME OF
 CERTIFICATE OF COMPLETION THE MANUFACTURER HAS NOT
 RECEIVED EITHER STATE APPROVAL OR A MIAMI-DADE NOAA
 LOCAL PRODUCT APPROVAL WILL NEED TO BE ACHIEVED BEFORE
 C/O.
  
 D) FIXED WINDOWS-OK
  
 E) OPERABLE WINDOWS-OK
  
 F) SPANDREL GLASS-OK
  
 G) MULLIONS VERTICAL AND HORIZONTAL PART OF NOA.
  
 H) WALL LOUVERS- OK
  
 I) STRUCTURAL ANCHORS TRUSS ANCHORS-NO APPROVALS
 SUBMITTED
  
 J) ROOFING ASSEMBLIES, ROOFING INSULATION, FLAT ROOFS
 MODIFIED
 ROOF TILE AND ASSEMBLIES. NOA 06-0606.06 ENTEGRA
 TILE PLEASE HIGHLIGHT THE METHOD OF ATTACHMENT FOUND ON
 PAGES 4 & 5.
  
 MODIFIED, THIS INFORMATION WILL BE NEEDED FOR A REVIEW
 OF ROOFING PRODUCTS:
 THIS FLAT ROOF (MODIFIED) IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
  
 _XX__NOTE ROOF IS OVER 4 FEET FROM GRADE, THE ROOF
 TABLE 1609.6.2.1(4) SEE HEIGHT
 ADJUSTMENT FACTOR 1.12.
 ___ CONTRACTOR DID NOT INDICATE THE ROOF PITCH. _XX__
 CONTRACTOR FAILED TO INDICATE WHICH SUB-SYSTEM TO BE
 USED.
 PAGES 9-26, PLEASE HIGHLIGHT WHICH SYSTEM WILL
 BE INSTALLED.
 _XX__ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR ZONE
 2& 3__ .
 _XX__ THE SYSTEM PROVIDED STATESLIMITATION# 7, SHOULD
 THE FASTENER RESISTANCE BE LESS THAN THATREQUIRED, AS
 DETERMINED BY THE BUILDING OFFICIAL, A REVISED FASTENER
 SPACING, PREPARED , SIGNED AND SEALED BY A FLORIDA
 REGISTERED PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOFCONSULTANT MAY BE
 SUBMITTED.
 ___THE SYSTEM PROVIDED INDICATES LIMITATION# 9, NO
 ENHANCED FASTENING ALLOWED.
  
 32) 2ND REQUEST, W P B ADMINISTRATIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED
 BY DCA RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 33-35) COMPLIED.
  
 36) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-06-09 Cont ID  
Sent By jwitmer Date 2007-06-09 Time 07:57 Rev Time 9.00
Received By jwitmer Date 2007-06-09 Time 07:57 Sent To  
Notes
2007-06-09 10:50:04 
  
 BUILDING PLAN REVIEW
 PERMIT: 06110152
 ADD: 807 N. FLAGLER DR.
 CONT: ANDERSON-MOORE
 TEL: (561)662-1819
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS TO THE ADMINISTRATIVE
 CODE
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) BUILDING PROVISO:
 THIS NOTE IS FOR THE CONTRACTOR FOR DURING
 CONSTRUCTION,
 BEING IN THE WPB ADMINISTRATIVE CODE IF THE CONTRACTOR
 DOESN'T COMPLY IT IS
 AN AVENUE THAT CAN BE USED FOR ENFORCEMENT.
 NOTE:109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PERMORMED IN A MANNER
 SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS
 SUCH ACTIVITY IS PERMITTED TO AFFECT
 SAID PROPERTY PURSUANT TO A CONSENT BY
 THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE
 APPLICABLE PROPERTY OWNER.THIS INCLUDES
 BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF,
 DEBRIS, AND THE STORAGE OF CONSTRUCTION
 MATERIALS. NEW CONSTRUCTION ACTIVITY
 SHALL NOT ADVERSELY IMPACT HISTORIC
 SURFACE WATER DRAINAGE FLOWS SERVING
 ADJACENT PROPERTIES, & MAY REQUIRE
 SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES.ACCORDINGLY,
 DEVELOPERS, CONTRACTORS,
 AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR
 ITEMS, ON EXISTING PROPERTIES RESULTING
 IN A DECREASE IN EXCESS OF 800SQ FT OF
 PERMEABLE LAND AREA ON ANY PARCELL SHALL
 AS A PERMIT CONDITION, PROVIDE A
 PROFESSIONALLY PREPARED DRAINAGE PLAN
 CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 4 )BUILDING PROVISO:
 THIS NOTE IS FOR THE CONTRACTOR FOR DURING
 CONSTRUCTION,
 BEING IN THE WPB ADMINISTRATIVE CODE IF THE CONTRACTOR
  
 DOESN'T COMPLY IT IS AN AVENUE THAT CAN BE USED FOR
 ENFORCEMENT.
 NOTE: 109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS. ANY PERSONS WHO FAILS TO COMPLY TO REMOVE OR
 SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00. IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 5) 2ND REQUESST,WPB AMENDMENT
 105.13.6. W.P.B. CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 6) COMPLIED.
  
 7) FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED BEFORE
 THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY. THE ISSUE
 WITH THE FLOOD ELEVATION CERTIFICATE IS IT WILL BE
 REQUIRED FOR THE "WHOLE BUILDING" BEING THAT THE
 PROPOSED, THE ADDITION IS OVER 50% WORTH OF THE
 EXISTING BUILDING "SUBSTANTIAL IMPROVEMENTS" NEED TO BE
 MET UNDER W. P. B. CODE OD ORDANCES
 CITY CODEARTICLE XVII FLOOD PREVENTION & CONTROL SEE
 ATTACHED DOCUMENT FOR COMPLIANCE. NOTE UNDER SECTION
 94-546(B)(2) NONRESIDENTIAL CONSTRUCTION COMPLIANCE
 THROUGH
 FLOOD PROOFING.SEE THE EXISTING MARGARET TIGHE
 MACHLIN THEATER FINISH FLOOR IS 5.13'N A VD 88. SEE
 CIVIL PLAN C-1. A COPY OF THE CITY ORDANCE IS
 ATTACHED.
  
 8) COMPLIED.
  
 9A) COMPLIED.
  
 9B) COMPLIED.
  
 10)COMPLIED.
  
 11)2ND EQUEST, THE DESIGN ATEMPTED TO CORRECT THE
 PROBLEMS WITH THE TOP LANDING FOUND ON SHEET A4.1.4 BY
 REROUTING THE EGRESS PATH BY MAKING THE EGRESS PATH
 TURN AROUND THE COLUMN. THIS HAS CREATED TWO NEW
 ISSUES:
  
 11A) TOP LANDING AND THE NEWLY CREATED TURN, PLEASE SEE
 11-4.8.4(3)THE KEY IS IF RAMPS CHANGE DIRECTION "AT
 LANDINGS" THE MINIMUM LANDING SIZE SHALL BE 60" X 60".
  
 11B) THE SECOND ISSUE IS THE HAND RAIL AND RETAINING
 WALL DO PASS BY THE TOP OF THE SLOPED PART OF THE RAMP
 BUT WITH THE CHANGE IN DIRECTION AT THETOP LANDING
 THE HANDRAIL DOES STOP BUT THERE IS NO PROTECTION FOR
 EDGE PROTECTION (11-4.8.7) ALLOWING PEOPLE TO SLIP OFF
 THE EDGE.
  
 12)COMPLIED.
  
 13) 13) 2ND REQUEST,AT THIS TIME I WOULD LIKE TO MAKE
 A COMMENT ON THE RESPONCE TO # 14, WE TOTALLY AGREE
 WITH THE FLORIDA ATTORNEY GENERAL ADVISORY LEGAL
 OPINION THAT CHURCHES ARE EXEMPT FORM NOT ONLY ADA BUT
 CHAPTER 11 FLORIDA ACCESSIBILITY CODE, WITH THE
 CLARIFYING STATMENTFL S S 553.505(1995BY CHAP 97-76
 RELIEVED BUILDINGS USED FOR THE COMMUNAL RELIGIOUS
 OBSERVANCES FROM THE ACCESSIBITY REQUIREMENTS OF THIS
 ACT . THIS DID NOT INCLUDE HOSPITALS, SCHOOLS OR
 PORTIONS OF CHUCHES THAT WOULD BE RENTED OUT TO THE
 GENERAL PUBLIC, ONLY THE SANCTUARY, THE PLACE OF
 WORSHIP. PLEASE SEE MEMO DATED 8/16/1998 FROM THE
 ASSISTANT GENERAL COUNSEL ALFRED O. BRAGG, III. A COPY
 IS ATTACHED.
  
 LS2.1.0 THIS PLAN INDICATES THE FIRST FLOOR LEVEL,
 PLANS DO NOT INDICATE WHAT GRADE LEVELS THIS SCHOOL
 WILL BE USED FOR ELEMENTARYM OR MIDDLE SCHOOLS ETC? IT
 COULD BE ASSUMED THAT THERE WILL BE A CHILD DROP OFF
 ZONE, NOT DEPICTED ON THIS PLAN, IF CHILDREN ARE TO BE
 DROPPED OFF THE DROP OFF ZONE SHALL COMPLY WITH :
 11-4.6.6 PASSENGER LOADING ZONES. PASSENGER LOADING
 ZONES SHALL PROVIDE AN ACCESS AISLE AT LEAST 60 INCHES
 (1525 MM) WIDE AND 20 FEET (6096 MM) LONG ADJACENT AND
 PARALLEL TO THE VEHICLE PULL-UP SPACE(SEE FIGURE
 11-10 ). IF THERE ARE CURBS BETWEEN THE ACCESS AISLE
 AND THE VEHICLE PULL-UP SPACE, THEN A CURB RAMP
 COMPLYING WITH SECTION 11-4.7 SHALL BE PROVIDED.
 VEHICLE STANDING SPACES AND ACCESS AISLES SHALL BE
 LEVEL WITH SURFACE SLOPES NOT EXCEEDING 1:50 (2
 PERCENT) IN ALL DIRECTIONS.
  
 14)COMPLIED.
  
 15) COMPLIED.
  
 16) ENLARGED STAIR PLAN FOUND ON SHEET A4.1.3 THANK YOU
 FOR THE ENLARGED LAYOUT PER FLOOR, THE DOOR SWING OVER
 THE REQUIREDLANDING ON THE SECOND FLOOR,1009.4 SEE
 EXCEPTION# 2. DOORS OPENING ONTO A LANDING SHALL NOT
 REDUCE THE LANDING TO LESS THAN ONE-HALF THE REQUIRED
 WIDTH. WHEN FULLY OPEN, THE DOOR SHALL NOT PROJECT MORE
 THAN 7 INCHES (178 MM) INTO A LANDING.
  
 17) COMPLIED.
  
 18) COMPLIED.
  
 19) COMPLIED.
  
 20) 2ND REQUEST, SHEET A2.2.1 THE CLASSROOM# 3
 INDICATES THE USE OF VERTICAL RISERS, SHOW COMPLIANCE
 WITH VERTICAL ACCESSIBILITY TO ALL LEVELS OF THE
 RISERS?11-4.1.2 VERTICAL ACCESSIBILITY, NOTHING IN
 THIS CODE SHALL BE CONSTRUED TO RELIEVE THE OWNER OF
 ANY BUILDING, SSTRUCTURE OR FACILITY FROM THE DUTY TO
 PROVIDE VERTICAL ACCESSIBILITY TO ALL LEVELS ABOVE OR
 BELOW THE OCCUPIAABLE GRADE LEVEL. PLEAS SEE THE
 ATTACHED MEMO THAT RELIGIOUS SCHOOLS ARE NOT EXEMPT
 FORM CHAPTER 11 FLORIDA ACCESSIBILITY. THE OPTION NOT
 TO PROVIDE VERTICAL ACCESSIBLITY IS TO APPLY TO THE
 STATE DEPARTMENT OF COMMUNITY AFFAIRS FLORIDA BUILDING
 COMMISSION. A COPY IS ATTACHED.
  
 21) 2ND REQUEST, SHEET A2.2.1 CLOSET 224E IS MISSING
 THE 18" ON THE PULL SIDE OF DOOR. 11-4.13.6 MANEUVERING
 CLEARENCES AT DOORS. MINIMUM MANEUVERING CLEARANCES AT
 DOORS THAT ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL BE
 AS SHOWN IN FIG. 25. THE FLOOR OR GROUND AREA WITH IN
 THE REQUIRED CLEARANCES SHALL BE CLEAR & LEVEL.
 OPENINGS MORE THAN 24" IN DEPTH SHALL COMPLY WITH
 SECTIONS 11-4.2.1AND 11-4.3.3. SEE FIGURE
 11-24(E).EXCEPTION: DOORS NOT REQUIRING FULL USER
 PASSAGE, SUCH AS SHALLOW CLOSETS, MAY HAVE THE CLEAR
 OPENINGS REDUCED TO 20 ".
  
 22) 2ND REQUEST, SHEET A2.2.1CLASSROOM# 2 (DRAMA) DOOR
 A/232A ALSO IS MISSING THE 18" ON THE PULL SIDE OF
 DOOR.11-4.13.6 MANEUVERING CLEARENCES AT DOORS. MINIMUM
 MANEUVERING CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC
 OR POWER-ASSISTED SHALL BE AS SHOWN IN FIG. 25. THE
 FLOOR OR GROUND AREA WITH IN THE REQUIRED CLEARANCES
 SHALL BE CLEAR & LEVEL.
 THE RESPONSE SHEET INDICATES THAT A FIRE EXTINGUISHER
 IS ON THE ADJACENT WALL SEE SECTION11-4.4 21 11-4.4.1
 GENERAL. OBJECTS PROJECTING FROM WALLS (FOR EXAMPLE,
 TELEPHONES) WITH THEIR LEADING EDGES BETWEEN 27 INCHES
 AND 80 INCHES (685 MM AND 2030 MM) ABOVE THE FINISHED
 FLOOR SHALL PROTRUDE NO MORE THAN 4 INCHES (102 MM)
 INTO WALKS, HALLS, CORRIDORS, PASSAGEWAYS, OR AISLES
 [SEE FIGURE 8 (A)]. OBJECTS MOUNTED WITH THEIR LEADING
 EDGES AT OR BELOW 27 INCHES (685 MM) ABOVE THE FINISHED
 FLOOR MAY PROTRUDE ANY AMOUNT [SEE FIGURE 8 (A) AND
 FIGURE 8 (B)]. FREE-STANDING OBJECTS MOUNTED ON POSTS
 OR PYLONS MAY OVERHANG 12 IN (305 MM) MAXIMUM FROM 27
 INCHES TO 80 INCHES (685 MM TO 2030 MM) ABOVE THE
 GROUND OR FINISHED FLOOR [SEE FIGURE 8 (C) AND FIGURE 8
 (D)]. PROTRUDING OBJECTS SHALL NOT REDUCE THE CLEAR
 WIDTH OF AN ACCESSIBLE ROUTE OR MANEUVERING SPACE [SEE
 FIGURE 8 (E)].
  
 23)2ND REQUEST, SHEET A2.2.1 GYMNASIUM DOES INDICATE
 DISSABLED SEATING ON THE MAIN FLOOR BUT NO SEATING
 ABOVE THE MAIN FLOOR, MISSING VERTICAL ACCESSIBILITY.
 11-4.1.2 VERTICAL ACCESSIBILITY, NOTHING IN THIS CODE
 SHALL BE CONSTRUED TO RELIEVE THE OWNER OF ANY
 BUILDING, STRUCTURE OR FACILITY FROM THE DUTY TO
 PROVIDE VERTICAL ACCESSIBILITY TO ALL LEVELS ABOVE OR
 BELOW THE OCCUPIAABLE GRADE LEVEL. 11-4.33.3 GIVES AN
 EXCEPTION IF THE FLOOR HAS A SLOPED FLOOR GREATER THAN
 5%. THE GYMNASIUM FLOOR HAS NO SLOPE. THE OWNER MAY
 WANT TO APPLY TO THE STATE FOR A VARIANCE TO THE
 VERTICAL ACCESSIBLITY REQUIREMENTS.RESPONSE
 INDICATES REFRENENCE TO FLORIDA ATTORNEY GENERAL
 STATEMENT ON CHURCHES. WE TOTALLY AGREE WITH THE
 FLORIDA ATTORNEY GENERAL ADVISORY LEGAL OPINION THAT
 CHURCHES ARE EXEMPT FORM NOT ONLY ADA BUT CHAPTER 11
 FLORIDA ACCESSIBILITY CODE, WITH THE CLARIFYING
 STATMENTFL S S 553.505(1995BY CHAP 97-76 RELIEVED
 BUILDINGS USED FOR THE COMMUNAL RELIGIOUS OBSERVANCES
 FROM THE ACCESSIBITY REQUIREMENTS OF THIS ACT . THIS
 DID NOT INCLUDE HOSPITALS, SCHOOLS OR PORTIONS OF
 CHUCHES THAT WOULD BE RENTED OUT TO THE GENERAL PUBLIC,
 ONLY THE SANCTUARY, THE PLACE OF WORSHIP. PLEASE SEE
 MEMO DATED 8/16/1998 FROM THE ASSISTANT GENERAL COUNSEL
 ALFRED O. BRAGG, III. A COPY IS ATTACHED.
 THE OPTION NOT TO PROVIDE VERTICAL ACCESSIBLITY IS TO
 APPLY TO THE STATE DEPARTMENT OF COMMUNITY AFFAIRS
 FLORIDA BUILDING COMMISSION. A COPY IS ATTACHED.
  
 24)2ND REQUEST,SHEET A3.2.1 DETAIL# 3,A 5.1.3
 DETAIL# 2 & S-8 DETAIL# 3 ALL INDICATETHAT THERE IS 2
 LAYERS OF SHEATHING ON TOP OF METAL DECK CONTNECTED TO
 METAL TRUSSES.
 IN ALL CASES THERE IS NO MENTION AS TO WHAT TYPE OF
 MATERIAL WILL MAKE UP THE 2 LAYERS OF ROOF SHEATHING?
 106.2.1*. ADDITIONAL INFORMATION REQUIRED.NOTED THE
 RESPONSE:SEE SPECIFICATIONS SECTION 06160-
 SHEATHING, WITHOUT THE PRODUCT APPROVALS THAT ARE TO BE
 SUPPLIED BY THE CONTRACTOR, WE DO NOT KNOW IF ONE OD
 THE DENSE DECK PRODUCTS CAN BE USED, SECOND IF IT WILL
 ALLOW THE ENHANCEDFASTENING THAT WILL BE NEEDED ON
 ZONES 2 & 3 AND THE THIRD AREA OF CONCERN WAS THERE ARE
 2 LAYERS OF SHEATHING , I'M ONLY ASSUMING THIS SECOND
 LAYER WOULD BETHE
 ROOF INSULATION SINCE THE PLANS DO NOT SHOW IT AT A
 LOWER LEVEL. AGAIN THE ROOFING REPORT AND THE SUBSYSTEM
 THAT HAS NOT YET BEEN IDENTIED WILL INDICATE THESE
 UNKNOWNS. SEE ROOFING ASSEMBLIES LISTED UNDER COMMENT
 (31I).
  
 25)2ND REQUEST,SHEET A5.1.1:PLANS INDICATE ON THE
 EXTERIOR OF THE BUILDING MOULDINGS AT VARIOUS AREAS,
 PLEASE PROVIDE ADDITIONAL INFORMATION AS TO THE TYPE OF
 MOULDING AND ATTACHMENT. 1406.2.2 ARCHITECTURAL TRIM.
 IN BUILDINGS OF TYPE I, II, III AND IV CONSTRUCTION
 THAT DO NOT EXCEED THREE STORIES OR 40 FEET (12 192 MM)
 IN HEIGHT ABOVE GRADE PLANE, EXTERIOR WALL COVERINGS
 SHALL BE PERMITTED TO BE CONSTRUCTED OF WOOD WHERE
 PERMITTED BY SECTION 1405.4 OR OTHER EQUIVALENT
 COMBUSTIBLE MATERIAL. COMBUSTIBLE EXTERIOR WALL
 COVERINGS, OTHER THAN FIRE-RETARDANT-TREATED WOOD
 COMPLYING WITH SECTION 2303.2 FOR EXTERIOR
 INSTALLATION, SHALL NOT EXCEED 10 PERCENT OF AN
 EXTERIOR WALL SURFACE AREA WHERE THE FIRE SEPARATION
 DISTANCE IS 5 FEET (1524 MM) OR LESS. ARCHITECTURAL
 TRIM THAT EXCEEDS 40 FEET (12 192 MM) IN HEIGHT ABOVE
 GRADE PLANE SHALL BE CONSTRUCTED OF APPROVED
 NONCOMBUSTIBLE MATERIALS AND SHALL BE SECURED TO THE
 WALL WITH METAL OR OTHER APPROVED NONCOMBUSTIBLE
 BRACKETS.
 POLYURETHANE- ETYMOLOGY: INTERNATIONAL SCIENTIFIC
 VOCABULARY : ANY OF VARIOUS POLYMERS THAT CONTAIN NHCOO
 LINKAGES AND ARE USED ESPECIALLY IN FLEXIBLE AND RIGID
 FOAMS, ELASTOMERS, AND RESINS (AS FOR COATINGS)PLEASE
 SEE WE NEED TO SEE A REPORT THAT THIS PRODUCT MEETS THE
 TEST OF NONCOMBUSTIBILITY AND FOR WIND, (2) SEPERATE
 REPORTS.
 703.4 NONCOMBUSTIBILITY TESTS.
 THE TESTS INDICATED IN SECTIONS 703.4.1 AND 703.4.2
 SHALL SERVE AS CRITERIA FOR ACCEPTANCE OF BUILDING
 MATERIALS AS SET FORTH IN SECTIONS 602.2 , 602.3 AND
 602.4 IN TYPE I, II, III AND IV CONSTRUCTION. THE TERM
 ?NONCOMBUSTIBLE? DOES NOT APPLY TO THE FLAME SPREAD
 CHARACTERISTICS OF INTERIOR FINISH OR TRIM MATERIALS. A
 MATERIAL SHALL NOT BE CLASSIFIED AS A NONCOMBUSTIBLE
 BUILDING CONSTRUCTION MATERIAL IF IT IS SUBJECT TO AN
 INCREASE IN COMBUSTIBILITY OR FLAME SPREAD BEYOND THE
 LIMITATIONS HEREIN ESTABLISHED THROUGH THE EFFECTS OF
 AGE, MOISTURE OR OTHER ATMOSPHERIC CONDITIONS. 703.4.1
 ELEMENTARY MATERIALS.
 MATERIALS REQUIRED TO BE NONCOMBUSTIBLE SHALL BE TESTED
 IN ACCORDANCE WITH ASTM E 136.
  
 703.4.2 COMPOSITE MATERIALS.
 MATERIALS HAVING A STRUCTURAL BASE OF NONCOMBUSTIBLE
 MATERIAL AS DETERMINED IN ACCORDANCE WITH SECTION
 703.4.1 WITH A SURFACING NOT MORE THAN 0.125 INCH (3.18
 MM) THICK THAT HAS A FLAME SPREAD INDEX NOT GREATER
 THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 SHALL
 BE ACCEPTABLE AS NONCOMBUSTIBLE MATERIALS.
  
 25B)2ND REQUEST, BAR JOIST ALSO INDICATE SPRAY ON
 FIREPROOFING, PLEASE PROVIDE THE MANUFACTURER'S
 ADDITIONAL INFORMATION AS TO THE PRODUCT INFORMATION,
 106.2.1*
 TABLE 601 BUILDING ELEMENT RATINGS FOR A TYPE IIA
 BUILDING.
  
 25C)2ND REQUEST, PLANS ALSO INDICATE THE USE OF 12"
 BLOCK WITH FOAM IN PLACE INFORMATION, PLEASE PROVIDE
 PRODUCT INFORMATION, 106.2.1*. RESPONSE INDICATES SEE
 SPECS 7215. PLEASE PROVIDE THE MANUFSTURER'S COMPLIANCE
 WITH 1.4 SEEFETY PRECAUTIONS MEETING THE REQUIREMENTS
 OF ASTM C 930. ALSO PROVIDE AT WHAT DENSITY THE FOAM
 WILL BE USED TO PROVIDE WHAT R-FACTOR. ALSO PROVIDE THE
 FIRE PROTECTION CHARACTERISTICS OF BEING EEITHER SELF
 EXTINGUISHING OR NON-COMBUSTIBLE.
  
 26)2ND REQUEST,A5.2.1 PLEASE PROVIDE A CROSS
 SECTION OF THE SPANDREL GLASS AND SLAB DETAIL PROVIDING
 INFORMATION AS TO FIRE RATING AND MATERIALS USED TO DO
 SO. PLEASE ALSOPROVIDE THE UL LISTING FOR THIS
 HORIZONTAL FLOOR ASSEMBLY. 711.3 FIRE RESISTANCE
 RATING. THE RESPONSE DOES PROVIDE A NEW DETAIL , DETAIL
 27/ A6.1.2 BUT THERE IS NO FIRE ASSMBLY LISTING
 PROVIDED.
  
 27)COMPLIED.
  
 28)COMPLIED.
  
 29) 2ND REQUEST,1609.1.4 PROTECTION OF OPENINGS. IN
 WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IN THE LOWER 60 FEET (18.3 M) IN
 BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED
 OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IS IMPACT RESISTANT OR PROTECTED WITH AN
 IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND
 ASTM E 1996, OR MIAMI-DADE TAS 201, 202
 AND 203 REFERENCED THEREIN AS FOLLOWS:
 1.GLAZED OPENINGS LOCATED WITHIN 30
 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN
 30 FEET (9.1 M) ABOVE GRADE SHALL MEET
 THE PROVISIONS OF THE SMALL MISSILE
 TEST.
  
 30)2ND REQUEST, PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 31)2ND REQUEST,FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT
 INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS FOLLOWS:A)
 EXTERIOR GLAZED SWING DOORS, SINGLE AND PAIRSB)
 EXTERIOR HOLLOW METAL FRAME DOORS, SINGLE AND PAIRSC)
 ROOF HATCHES
 D) FIXED WINDOWS
 E) OPERTABLE WINDOWS
 F) SPANDREL GLASS
 G) MULLIONS VERTICAL AND HORIZONTAL
 H) WALL LOUVERS
 I) ROOFING ASSEMBLIES, ROOFING INSULATION, FLAT ROOFS
 MODIFIED,
 J) STRUCTURAL ANCHORS TRUSS ANCHORS
 ROOF TILE AND ASSEMBLIES.
 THIS INFORMATION WILL BE NEEDED FOR A REVIEW OF ROOFING
 PRODUCTS:
 THIS ROOF IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
  
 ___ CONTRACTOR DID NOT PROVIDE THE MEAN
  
 ROOF HEIGHT.
  
 ___ CONTRACTOR DID NOT INDICATE THE ROOF
 PITCH.
  
 ___ CONTRACTOR FAILED TO INDICATE WHICH
 SYSTEM TO BE USED.
  
 ___ THE SYSTEM PROVIDED HAS A LOW
 PRESSURE FOR ZONE ___ .
  
 ___ THE SYSTEM PROVIDED STATES
 LIMITATION# 7, SHOULD THE FASTENER
 RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE
 BUILDING OFFICIAL, A REVISED
 FASTENER SPACING, PREPARED , SIGNED
 AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
  
 ___THE SYSTEM PROVIDED INDICATES
 LIMITATION# 9, NO ENHANCED
 FASTENING ALLOWED.
  
 32) 2ND REQUEST, W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 33) COMPLIED.
  
 34) COMPLIED.
  
 35)2ND REQUEST,A9.1.1500 SERIES CONCRETE MASONARY
 UNITS VARIOUS SHEETS INDICATE THE BLOCK TO BE PART OF A
 RATED ASSEMBLY, BUT THERE IS NO INFORMATION HOW THE 1
 HR RATING WILL BE MAINTAINED WHEN ADJOINING TO PAN
 DECK? SECTION 713.1 FIRE RESISTANT JOINT SYSTEMS PLEASE
 PROVIDE THE U L LISTING.
  
 713.1 GENERAL. JOINTS INSTALLED IN OR BETWEEN
 FIRE-RESISTANCE-RATED WALLS, FLOOR OR FLOOR/CEILING
 ASSEMBLIES AND ROOFS OR ROOF/CEILING ASSEMBLIES SHALL
 BE PROTECTED BY AN APPROVED FIRE-RESISTANT JOINT SYSTEM
 DESIGNED TO RESIST THE PASSAGE OF FIRE FOR A TIME
 PERIOD NOT LESS THAN THE REQUIRED FIRE-RESISTANCE
 RATING OF THE WALL, FLOOR OR ROOF IN OR BETWEEN WHICH
 IT IS INSTALLED. FIRE-RESISTANT JOINT SYSTEMS SHALL BE
 TESTED IN ACCORDANCE WITH SECTION 713.3 . THE VOID
 CREATED AT THE INTERSECTION OF A FLOOR/CEILING ASSEMBLY
 AND AN EXTERIOR CURTAIN WALL ASSEMBLY SHALL BE
 PROTECTED IN ACCORDANCE WITH SECTION 713.4 .
  
 713.3 FIRE TEST CRITERIA.
  
 FIRE-RESISTANT JOINT SYSTEMS SHALL BE TESTED IN
 ACCORDANCE WITH THE REQUIREMENTS OF EITHER ASTM E 1966
 OR UL 2079. NONSYMMETRICAL WALL JOINT SYSTEMS SHALL BE
 TESTED WITH BOTH FACES EXPOSED TO THE FURNACE, AND THE
 ASSIGNED FIRE-RESISTANCE RATING SHALL BE THE SHORTEST
 DURATION OBTAINED FROM THE TWO TESTS. WHEN EVIDENCE IS
 FURNISHED TO SHOW THAT THE WALL WAS TESTED WITH THE
 LEAST FIRE-RESISTANT SIDE EXPOSED TO THE FURNACE,
 SUBJECT TO ACCEPTANCE OF THE BUILDING OFFICIAL, THE
 WALL NEED NOT BE SUBJECTED TO TESTS FROM THE OPPOSITE
 SIDE.
 EXCEPTION: FOR EXTERIOR WALLS WITH A HORIZONTAL FIRE
 SEPARATION DISTANCE GREATER THAN 5 FEET (1524 MM), THE
 JOINT SYSTEM SHALL BE REQUIRED TO BE TESTED FOR
 INTERIOR FIRE EXPOSURE ONLY.
  
 713.4 EXTERIOR CURTAIN WALL/FLOOR INTERSECTION. WHERE
 FIRE- RESISTANCE-RATED FLOOR OR FLOOR/CEILING
 ASSEMBLIES ARE REQUIRED, VOIDS CREATED AT THE
 INTERSECTION OF THE EXTERIOR CURTAIN WALL ASSEMBLIES
 AND SUCH FLOOR ASSEMBLIES SHALL BE SEALED WITH AN
 APPROVED MATERIAL OR SYSTEM TO PREVENT THE INTERIOR
 VERTICAL SPREAD OF FIRE. SUCH MATERIAL OR SYSTEMS SHALL
 BE SECURELY INSTALLED AND CAPABLE OF PREVENTING THE
 PASSAGE OF FLAME AND HOT GASES SUFFICIENT TO IGNITE
 COTTON WASTE WHERE SUBJECTED TO ASTM E 119
 TIME-TEMPERATURE FIRE CONDITIONS UNDER A MINIMUM
 POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH OF WATER
 (2.49 PA) FOR THE TIME PERIOD AT LEAST EQUAL TO THE
 FIRE-RESISTANCE RATING OF THE FLOOR ASSEMBLY. HEIGHT
 AND FIRE-RESISTANCE REQUIREMENTS FOR CURTAIN WALL
 SPANDRELS SHALL COMPLY WITH SECTION 704.9 .
  
 36) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 37)THE PROPOSED BUILDING STRUCTURE TRANSGRESSES LEGAL
 BOUNDARY LINES BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'.A 'UNITY OF TITLE' SHALL BE RECORDED AT
 THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE RECORDED
 'UNITY OF OF TITLE' DOCUMENT SO THAT FBC TABLE 601
 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED NOT
 APPLICABLE.
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-12-04 Cont ID  
Sent By jwitmer Date 2006-12-04 Time 13:46 Rev Time 8.88
Received By jwitmer Date 2006-12-04 Time 13:46 Sent To  
Notes
2006-12-04 16:24:25 
  
  
 BUILDING PLAN REVIEW
 PERMIT: 06110152
 ADD: 807 N. FLAGLER DR.
 CONT: ANDERSON-MOORE
 TEL: (561)662-1819
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS TO THE ADMINISTRATIVE
 CODE
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
  
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) NOTE:109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PERMORMED IN A MANNER
 SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS
 SUCH ACTIVITY IS PERMITTED TO AFFECT
 SAID PROPERTY PURSUANT TO A CONSENT BY
 THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE
 APPLICABLE PROPERTY OWNER.THIS INCLUDES
 BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF,
 DEBRIS, AND THE STORAGE OF CONSTRUCTION
 MATERIALS. NEW CONSTRUCTION ACTIVITY
 SHALL NOT ADVERSELY IMPACT HISTORIC
 SURFACE WATER DRAINAGE FLOWS SERVING
 ADJACENT PROPERTIES, & MAY REQUIRE
 SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES.ACCORDINGLY,
 DEVELOPERS, CONTRACTORS,
 AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR
 ITEMS, ON EXISTING PROPERTIES RESULTING
 IN A DECREASE IN EXCESS OF 800SQ FT OF
 PERMEABLE LAND AREA ON ANY PARCELL SHALL
 AS A PERMIT CONDITION, PROVIDE A
 PROFESSIONALLY PREPARED DRAINAGE PLAN
 CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 4) NOTE: 109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 5)WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION
 SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 6) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 7) PROVIDE FLOOD ZONE ELEVATION
 CERTIFICATE FOR NEW CONSTRUTION WITH
 BASE FLOOD ELEVATION, CITY CODE REQUIRES
 AN ADDITIONAL 6".
  
 8)SHEET LS2.1.0 THE EXISTING AUDITORIUM (SOUTHWEST
 CORNER) 4 SETS OF DOUBLE DOORS
 2 SETS SAY NO EXITS THERE IS NO EXIT SIGNS LOCATED AT
 THE OTHER
 REMAINING DOORWAY.IF IN FACT THE 2 REMAINING
 DOORWAYS ARE THE REQUIRED EXITS
 THE ISSUE IS THE SOUTH PAIR OF DOORS, AS AN ACCESSIBLE
 MEANS OFEGRESS.THERE
 APPEARS TO BE A NEW RETAINING WALL AND STAAIRWAY.
 PLEASE PROVIDE THE DIMENSION
 FROM THE CORNER OF THE BUILDING TO THE END OF THE
 HORIZONTAL PROJECTION OF THE STAIR
 HANDRAIL?
 1020.2 WIDTH. THE WIDTH OF EXIT PASSAGEWAYS SHALL BE
 DETERMINED AS SPECIFIED IN
 SECTION 1005.1 BUT SUCH WIDTH SHALL NOT BE LESS THAN 44
 INCHES (1118 MM), EXCEPT
 THAT EXIT PASSAGEWAYS SERVING AN OCCUPANT LOAD OF LESS
 THAN 50 SHALL NOT BE LESS
 THAN 36 INCHES (914 MM) IN WIDTH.
  
 9A) SHEET LS2.1.0 STAIR# 4 VERSES THE CORRIDOR DIRECTLY
 TO THE NORTH. THE CORRIDOR
 INDICATES THERE WILL BE AN OCCUPANT LOAD OF 203, BUT
 SCALES OUT TO BE APPROXIMATELY 4.5' NOT THE MINIMUM
 REQUIRED 72".
 1016.2 EXCEPTION# 4.SEVENTY-TWO INCHES (1829 MM) IN
 GROUP E WITH A
 CORRIDOR HAVING A REQUIRED CAPACITY OF 100 OR MORE.
 NOTE THE ENLARGED EXISTING AUDITORIUM FLOOR EGRESS PLAN
 DOES NOT HAVE A SCALE TO REFRENCE TOO.
  
 9B) SHEET LS2.10 FIRST FLOOR LOBBY INDICATES AN
 OCCUPANT LOAD, BUT THE ENTRY NOR THE ELEVATOR LOBBY DO
 NOT SHOW AN OCCUPANT LOAD, THE SAME HOLDS TRUE FOR THE
 2ND FLOOR ELEVATOR LOBBY,
 CAN BE CONSIDERED A PREFUNCTION AREA. TAKE OUT THE
 REQUIRED EGRESS PATH AND ASIGN AN
 OCCUPANT LOAD TO THE REMAINING AREA.TABLE 1004.1.2.
 THIS MAY REQUIRE ADDITIONAL EXITS TABLE 1018.1 AND THE
 AMOUNT OF ACCESSIBLE ENTRANCES.
  
 10)LS2.1.0 & A4.1.4 FIRST FLOOR ENTRY RAMP, THE
 INTERMEDIATE LANDING
 DOES NOT MEET THE REQUIRED MINIMUM LANDING SIZE.
 11-4.8.4(3) IF RAMPS
 CHANGE DIRECTION AT LANDINGS, THE MINIMUM LANDING SIZE
 SHALL BE 60" X 60".
  
 11)A4.1.4 FIRST FLOOR ENTRY RAMP THERE IS A COLUMN AT
 THE TOP
 OF THE LANDING WITH A CLEAR MEASUREMENT OF 3'-0".
 11-4.8.3. CLEAR WIDTH. THE MINIMUM
 CLEAR WIDTH OF A RAMP SHALL BE 36".
 EXCEPTION: RAMPS THAT ARE PART OF A
 REQUIRED MEANS OF EGRESS SHALL NOT BE
 LESS THAN 44 INCHES WIDE.
  
 12) A4.1.4 RAMP WITH HANDRAILS SHOWS A DIMENSION OF
 3'-7 1/4" OVER ALL WHERE AS
 11-4.8.3 REQUIRES A 44" CLEAR WIDTH, SEE FIGURE 17 44"
 IS TAKEN BETWEEN THE HANDRAILS.
  
 13) LS2.1.0 THIS PLAN INDICATES THE FIRST FLOOR LEVEL,
 PLANS DO NOT INDICATE
 WHAT GRADE LEVELS THIS SCHOOL WILL BE USED FOR
 ELEMENTARYM OR MIDDLE
 SCHOOLS ETC? IT COULD BE ASSUMED THAT THERE WILL BE A
 CHILD DROP OFF ZONE,
 NOT DEPICTED ON THIS PLAN, IF CHILDREN ARE TO BE
 DROPPED OFF THE DROP OFF
 ZONE SHALL COMPLY WITH : 11-4.6.6 PASSENGER LOADING
 ZONES.
 PASSENGER LOADING ZONES SHALL PROVIDE AN ACCESS AISLE
 AT LEAST 60 INCHES (1525 MM) WIDE
 AND 20 FEET (6096 MM) LONG ADJACENT AND PARALLEL TO THE
 VEHICLE PULL-UP SPACE
 (SEE FIGURE 11-10 ). IF THERE ARE CURBS BETWEEN THE
 ACCESS AISLE AND THE VEHICLE PULL-UP
 SPACE, THEN A CURB RAMP COMPLYING WITH SECTION 11-4.7
 SHALL BE PROVIDED. VEHICLE STANDING
 SPACES AND ACCESS AISLES SHALL BE LEVEL WITH SURFACE
 SLOPES NOT
 EXCEEDING 1:50 (2 PERCENT) IN ALL DIRECTIONS.
  
 14) SHEET LS2.1.0 INDICATES THE USE OF DISSABLED
 PARKING IN THE GARAGE, NO INFORMATION ON "VAN
 ACCESSIBLE "
 PARKING.
 11-4.6.4 SIGNAGE.
 EACH ACCESSIBLE PARKING SPACE MUST BE PROMINENTLY
 OUTLINED WITH BLUE PAINT, AND
 MUST BE REPAINTED AS NECESSARY, TO BE CLEARLY
 DISTINGUISHABLE AS A PARKING SPACE
 DESIGNATED FOR PERSONS WHO HAVE DISABILITIES AND MUST
 BE POSTED WITH A PERMANENT
 ABOVE-GRADE SIGN BEARING THE INTERNATIONAL SYMBOL OF
 ACCESSIBILITY, MEETING THE
 REQUIREMENTS OF COLOR AND DESIGN APPROVED BY THE
 DEPARTMENT OF TRANSPORTATION, OF
 SECTION 11-4.30.7 AND THE CAPTION ?PARKING BY DISABLED
 PERMIT ONLY.? SUCH
 SIGN ERECTED AFTER OCTOBER 1, 1996, MUST INDICATE THE
 PENALTY FOR ILLEGAL USE OF THE SPACE.
 VAN ACCESSIBLE PARKING SPACES LOCATED WITHIN A PARKING
 STRUCTURE SHALL HAVE AN
 ADDITIONAL SIGN READING ?VAN ACCESSIBLE? MOUNTED BELOW
 THE SYMBOL OF ACCESSIBILITY.
 SUCH SIGNS SHALL BE LOCATED SO THEY CANNOT BE OBSCURED
 BY A VEHICLE PARKED IN THE SPACE.
  
 15) SIGNAGE REQUIEMENTS: 11-4.1.2(7) (7)BUILDING
 SIGNAGE. SIGNS WHICH DESIGNATE
 PERMANENT ROOMS AND SPACES SHALL COMPLY WITH SECTIONS
 11-4.30.1 , 11-4.30.4 ,
 11-4.30.5 AND 11-4.30.6 . OTHER SIGNS WHICH PROVIDE
 DIRECTION TO, OR INFORMATION ABOUT,
 FUNCTIONAL SPACES OF THE BUILDING SHALL COMPLY WITH
 SECTIONS 11-4.30.1 , 11-4.30.2 ,
 11-4.30.3 , AND 11-4.30.5 . ELEMENTS AND SPACES OF
 ACCESSIBLE FACILITIES WHICH SHALL
 BE IDENTIFIED BY THE INTERNATIONAL SYMBOL OF
 ACCESSIBILITY AND WHICH SHALL COMPLY WITH
 SECTION 11-4.30.7 ARE:
 (A)PARKING SPACES DESIGNATED AS RESERVED FOR
 INDIVIDUALS WITH DISABILITIES;
 (B)ACCESSIBLE PASSENGER LOADING ZONES;
 (C) ACCESSIBLE ENTRANCES WHEN NOT ALL ARE ACCESSIBLE
 (INACCESSIBLE ENTRANCES
  
 16)PLEASE IDENTIFY ON EITHER LIFE SAFETY OR
 ACHITECTURAL PLAN A CUT SECTION
 THROUGH THE STAIRWELLS TO TIE TO THE SECTIONS ON
 A5.2.1/ A5.2.2.
  
 17) SHEET A5.2.1 STAIR WELL DETAIL# 2 IS MISSING THE
 1'-0" HORIZONTAL EXTENSION ,
 EVEN THOUGH THERE ISA NOTE INDICATING SUCH!
 11-4.9.4(2)
  
 18)SHEET A5.2.1/ A5.2.2 BOTH INDICATE STEEL STAIRS
 ,PLEASE NOTE
 OPEN RISERS ARE NOT PERMITTED. 11-4.9.2.
  
 19) A2.1.1 PLEASE PROVIDE SIGNAGE IN STAIR TOWER# 1 AS
 TO WHICH DOOR
 LEADS YOU TO THE EXTERIOR OF THE BUILDING AND NOT BACK
 INTO THE PARKING GARAGE.
 PLEASE PROVIDE THE SAME SIGNAGE FOR STAIR TOWER# 2.
  
 20)SHEET A2.2.1 THE CLASSROOM# 3 INDICATES THE USE OF
 VERTICAL RISERS, SHOW COMPLIANCE WITH VERTICAL
 ACCESSIBILITY TO ALL LEVELS OF THE RISERS?11-4.1.2
 VERTICAL ACCESSIBILITY,
 NOTHING IN THIS CODE SHALL BE CONSTRUED
 TO RELIEVE THE OWNER OF ANY BUILDING,
 SSTRUCTURE OR FACILITY FROM THE DUTY TO
 PROVIDE VERTICAL ACCESSIBILITY TO ALL
 LEVELS ABOVE OR BELOW THE OCCUPIAABLE
 GRADE LEVEL.
  
 21) SHEET A2.2.1 CLOSET 224E IS MISSING THE 18" ON THE
 PULL SIDE OF DOOR.
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARANCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARANCES SHALL BE
 CLEAR & LEVEL.
  
 22) SHEET A2.2.1CLASSROOM# 3 (DRAMA) DOOR A/232A ALSO
 IS
 MISSING THE 18" ON THE PULL SIDE OF DOOR.11-4.13.6
 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARANCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARANCES SHALL BE
 CLEAR & LEVEL.
  
 23) SHEET A2.2.1 GYMNASIUM DOES INDICATE DISSABLED
 SEATING ON THE MAIN FLOOR BUT NO
 SEATING ABOVE THE MAIN FLOOR, MISSING VERTICAL
 ACCESSIBILITY.
 11-4.1.2 VERTICAL ACCESSIBILITY,
 NOTHING IN THIS CODE SHALL BE CONSTRUED
 TO RELIEVE THE OWNER OF ANY BUILDING,
 SSTRUCTURE OR FACILITY FROM THE DUTY TO
 PROVIDE VERTICAL ACCESSIBILITY TO ALL
 LEVELS ABOVE OR BELOW THE OCCUPIAABLE
 GRADE LEVEL. 11-4.33.3 GIVES AN EXCEPTION IF THE FLOOR
 HAS A
 SLOPED FLOOR GREATER THAN 5%. THE GYMNASIUM FLOOR HAS
 NO SLOPE.
 THE OWNER MAY WANT TO APPLY TO THE STATE FOR A
 VARIANCE
  
 TO THE VERTICAL ACCESSIBLITY
 REQUIREMENTS.
  
 24)SHEET A3.2.1 DETAIL# 3,A 5.1.3DETAIL# 2 & S-8
 DETAIL# 3 ALL INDICATE
 THAT THERE IS 2 LAYERS OF SHEATHING ON TOP OF METAL
 DECK CONTNECTED TO METAL TRUSSES.
 IN ALL CASES THERE IS NO MENTION AS TO WHAT TYPE OF
 MATERIAL WILL MAKE UP THE 2
 LAYERS OF ROOF SHEATHING? 106.2.1*. ADDITIONAL
 INFORMATION REQUIRED.
  
 25)SHEET A5.1.1:
 25A) PLANS INDICATE ON THE EXTERIOR OF THE BUILDING
 MOULDINGS AT VARIOUS AREAS, PLEASE PROVIDE ADDITIONAL
 INFORMATION AS TO THE TYPE OF MOULDING AND ATTACHMENT.
 1406.2.2 ARCHITECTURAL TRIM.
 IN BUILDINGS OF TYPE I, II, III AND IV CONSTRUCTION
 THAT DO NOT EXCEED THREE STORIES OR 40 FEET (12 192 MM)
 IN HEIGHT ABOVE GRADE PLANE, EXTERIOR WALL COVERINGS
 SHALL BE PERMITTED TO BE CONSTRUCTED OF WOOD WHERE
 PERMITTED BY SECTION 1405.4 OR OTHER EQUIVALENT
 COMBUSTIBLE MATERIAL. COMBUSTIBLE EXTERIOR WALL
 COVERINGS, OTHER THAN FIRE-RETARDANT-TREATED WOOD
 COMPLYING WITH SECTION 2303.2 FOR EXTERIOR
 INSTALLATION, SHALL NOT EXCEED 10 PERCENT OF AN
 EXTERIOR WALL SURFACE AREA WHERE THE FIRE SEPARATION
 DISTANCE IS 5 FEET (1524 MM) OR LESS. ARCHITECTURAL
 TRIM THAT EXCEEDS 40 FEET (12 192 MM) IN HEIGHT ABOVE
 GRADE PLANE SHALL BE CONSTRUCTED OF APPROVED
 NONCOMBUSTIBLE MATERIALS AND SHALL BE SECURED TO THE
 WALL WITH METAL OR OTHER APPROVED NONCOMBUSTIBLE
 BRACKETS.
  
 25B)BAR JOIST ALSO INDICATE SPRAY ON FIREPROOFING,
 PLEASE PROVIDE ADDITIONAL INFORMATION AS TO THE PRODUCT
 INFORMATION, 106.2.1*
  
 25C)PLANS ALSO INDICATE THE USE OF 12" BLOCK WITH
 FOAM IN PLACE INFORMATION, PLEASE PROVIDE PRODUCT
 INFORMATION, 106.2.1*.
  
 26)A5.2.1 PLEASE PROVIDE A CROSS SECTION OF THE
 SPANDREL GLASS AND SLAB DETAIL
 PROVIDING INFORMATION AS TO FIRE RATING AND MATERIALS
 USED TO DO SO. PLEASE ALSO
 PROVIDE THE UL LISTING FOR THIS HORIZONTAL FLOOR
 ASSEMBLY. 711.3 FIRE RESISTANCE RATING.
  
 27)SHEET A5.2.3STAIR DETAIL# 1. PLANS INDICATE THE
 CENTER HANDRAILS BUT NOT THE OUTER GUARDRAILS.1012.1.
  
 28)A7.2.1 DOOR SCHEDULE INDICATES DOOR RATINGS AS "B"
 RATINGS, PLEASE
 SEE TABLE 715.3 DOOR RATINGS ARE INDICATIED IN HRS. B
 LABEL DOORS COULD HAVE A 1 HR RATING
  
 29)1609.1.4 PROTECTION OF OPENINGS.
 IN WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IN THE LOWER 60 FEET (18.3 M) IN
 BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED
 OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IS IMPACT RESISTANT OR PROTECTED WITH AN
 IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND
 ASTM E 1996, OR MIAMI-DADE TAS 201, 202
 AND 203 REFERENCED THEREIN AS FOLLOWS:
 1.GLAZED OPENINGS LOCATED WITHIN 30
 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN
 30 FEET (9.1 M) ABOVE GRADE SHALL MEET
 THE PROVISIONS OF THE SMALL MISSILE
 TEST.
  
 30)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 31)FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) EXTERIOR GLAZED SWING DOORS, SINGLE AND PAIRSB)
 EXTERIOR HOLLOW METAL FRAME DOORS, SINGLE AND PAIRSC)
 ROOF HATCHES
 D) FIXED WINDOWS
 E) OPERTABLE WINDOWS
 F) SPANDREL GLASS
 G) MULLIONS VERTICAL AND HORIZONTAL
 H) WALL LOUVERS
 I) ROOFING ASSEMBLIES, ROOFING INSULATION, FLAT ROOFS
 MODIFIED,
 J) STRUCTURAL ANCHORS TRUSS ANCHORS
 ROOF TILE AND ASSEMBLIES.
 THIS INFORMATION WILL BE NEEDED FOR A REVIEW OF ROOFING
 PRODUCTS:
 THIS ROOF IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
  
 ___ CONTRACTOR DID NOT PROVIDE THE MEAN
  
 ROOF HEIGHT.
  
 ___ CONTRACTOR DID NOT INDICATE THE ROOF
 PITCH.
  
 ___ CONTRACTOR FAILED TO INDICATE WHICH
 SYSTEM TO BE USED.
  
 ___ THE SYSTEM PROVIDED HAS A LOW
 PRESSURE FOR ZONE ___ .
  
 ___ THE SYSTEM PROVIDED STATES
 LIMITATION# 7, SHOULD THE FASTENER
 RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE
 BUILDING OFFICIAL, A REVISED
 FASTENER SPACING, PREPARED , SIGNED
 AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
  
 ___THE SYSTEM PROVIDED INDICATES
 LIMITATION# 9, NO ENHANCED
 FASTENING ALLOWED.
  
 32) )W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 33) S-3.1 DISCREPANCY, TRUSS ANCHOR SCHEDULE THE VALUE
  
 FOR THE ANCHORS IS REVERSED, PLEASE SEE ATTACHED SHEET
 FROM SIMPSON STRONGTIE.
  
 34)SHEET LS2.2.0 & LS2.3.0 PLEASE PROVIDE
 DOCUMENTATION OR COMPLIANCE WITH:
 1025.4.1 EVERY ROOM OR SPACE GREATER THAN 250 SQUARE
 FEET (23.2 M 2 ) IN EDUCATIONAL
 OCCUPANCIES USED FOR CLASSROOM OR OTHER EDUCATIONAL
 PURPOSES OR NORMALLY SUBJECT TO
 STUDENT OCCUPANCY AND EVERY ROOM OR SPACE NORMALLY
 SUBJECT TO CLIENT OCCUPANCY,
 OTHER THAN BATHROOMS, IN GROUP D OCCUPANCIES SHALL HAVE
 NOT LESS THAN ONE OUTSIDE
 WINDOW FOR EMERGENCY RESCUE THAT COMPLIES WITH THE
 FOLLOWING:
 1.SUCH WINDOWS SHALL BE OPENABLE FROM THE INSIDE
 WITHOUT THE USE OF TOOLS AND SHALL
 PROVIDE A CLEAR OPENING OF NOT LESS THAN 20 INCHES (508
 MM) IN WIDTH, 24 INCHES
 (610 MM) IN HEIGHT, AND 5.7 SQUARE FEET (0.53 M 2 ) IN
 AREA.
 2.THE BOTTOM OF THE OPENING SHALL BE NOT MORE THAN
 44 INCHES (1118 MM) ABOVE
 THE FLOOR, AND ANY LATCHING DEVICE SHALL BE CAPABLE OF
 BEING OPERATED FROM NOT MORE
 THAN 54 INCHES (1372 MM) ABOVE THE FINISHED FLOOR.
  
 35)A9.1.1 500 SERIES CONCRETE MASONARY UNITS VARIOUS
 SHEETS
 INDICATE THE BLOCK TO BE PART OF A RATED ASSEMBLY, 1
 HR
  
 BUT THERE IS NO INFORMATION HOW THE 1 HR RATING WILL BE
 MAINTAINED
 WHEN ADJOINING TO PAN DECK? SECTION 713.1 FIRE
 RESISTANT JOINT SYSTEMS
  
 36) BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 9 Status F Date 2009-04-03 Cont ID  
Sent By dpalmer Date 2009-04-03 Time 15:04 Rev Time 0.00
Received By dpalmer Date 2009-04-03 Time 15:04 Sent To  
Notes
2009-04-03 15:04:28** TEMPORARY DENIED **
  
  
 1) NOTE: CALLED AND SPOKE WITH ROSE.
 NEED TO COORDINATE ALL SETS INTO COMPLETE SETS WITH ALL
 NEW SHEETS INSERTED. ANY MISSING SHEETS NEED TO BE
 PLACED INTO SETS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2008-08-14 Cont ID  
Sent By dpalmer Date 2008-08-14 Time 09:02 Rev Time 0.00
Received By dpalmer Date 2008-08-14 Time 09:02 Sent To PC
Notes
2008-08-14 09:05:51THIS NEW BUILDING SHALL HAVE NOTHAVE ANY SYSTEMS FROM
 THE EXISTING THEATRE BUILDIING. PLANS INDICATE A 4HR
 FIRE WALL AND ALL SHALL BE SEPARATE INCLUDING LOW
 VOLTAGE, FIRE SPRINKLERS ETC
  
 SHEET 5.1 STILL INDICATES MAIN 2 OF 2 FOR CALCULATIONS.

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2009-02-13 Cont ID  
Sent By dpalmer Date 2009-02-13 Time 14:12 Rev Time 0.00
Received By dpalmer Date 2009-02-13 Time 14:12 Sent To  
Notes
2009-02-13 14:13:04** DENIED REVIEW **
  
 REVISIONS
  
  
 1) NOTE: PLEASE GO THROUGH AND COORDINATE ALL CHANGES
 AND REVISIONS.
  
 FOR EXAMPLE: SHEET E4.1 NOW HAS EQUIPMENT AND MAINS IN
 THE MAIN ELECTRICAL ROOM REMOVED HOWEVER THE POWER
 PLANS STILL SHOW THIS EQUIPMENT AND OTHER EQUIPMENT. IF
 THIS EQUIPMENT AND OTHERS ARE NO LONGER LOCATED IN THIS
 ROOM PLEASE SUBMIT PLANS FOR NEW LOCATION(S).
 110.26,240.24, 230.71,230.71 ETC
  
 FOR EXAMPLE: PLEASE SEE RISER AS MAIN IS STILL NOTED AS
 MAIN 2 OF 2. THIS WOULD BE MAIN ONE IF THIS IS STILL A
 SEPARATE BUILDING AS STATED IN PREVIOUS REVIEWS AND
 REVISIONS.
 230.2E
  
 FOR EXAMPLE: RISER NOW SHOWS A REVISION WITH THE
 ADDITION OF A NEW PANEL *L2AB* HOWEVER THE RISER SHOWS
 THIS PANEL BEING FED FROM *DP2A*. IF YOU GO TO THE
 PANEL *DP2A* YOU WILL NOT FIND ANY SUCH PANEL.
  
 ** PLEASE COORDINATE ALL OF THE ABOVE.
 215.5,230,240,220 ETC
  
 2) NOTE: PLEASE REMOVE DESIGNATION OF IT ROOM FROM ALL
 SHEETS AS THIS DOES NOT MEET 645.4. PLEASE ALSO INCLUDE
 NOTE WHICH WILL STATE:
 THIS IS NOT AN IT ROOM WIRING METHODS PER NEC 645 NOT
 PERMITTED. (OR WORDS TO THAT AFFECT).
  
  
  
 ** NOT ALL NOTES PROVIDED ON SHEETS SUBMITTED DENOTING
 CHANGES MATCH WITH PLANS.
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2008-07-17 Cont ID  
Sent By dpalmer Date 2008-07-17 Time 08:55 Rev Time 0.00
Received By dpalmer Date 2008-07-17 Time 08:54 Sent To  
Notes
2008-07-17 08:55:45** DENIEDREVISIONS **
  
  
 1) NOTE:PLEASE PROVIDE WHERE THE MAIN ONE OF ONE
 WENT. PLEASE KNOW ALL MAINS SHALL BE GROUPED PER
 230.72.
 THE EXISTING ELECTRICAL ROOM SERVICE EQUIPMENT IS NO
 LONGER ON PLANS YET THIS BUILDING IS PART OF THE NEW
 BUILDING.
 IT IS UNCLEAR WHAT THE INTENT IS AND WHERE ELECTRICAL
 SERVICE EQUIPMENT IS.
 230.70,230.2,230.71,230.72, 230.76, 230.79
  
 ** CALLED WAS PLACED TO ENGINEER, AS OF REVIEW NOTES
 WAITING FOR RETURN CALL.
  
 2) NOTE: REVISED EENRGY CALCULATIONS NOT REVIEWED. NEED
 TO SUBMI WITH ANY OTHER CHANGES DURING PROJECT BEFORE
 FINAL.
  
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-11-09 Cont ID  
Sent By dpalmer Date 2007-11-09 Time 16:54 Rev Time 0.00
Received By dpalmer Date 2007-11-09 Time 16:54 Sent To  
Notes
2007-11-09 16:56:12PASSED WITH CONDITIONS.
  
 ENERGY CALCULATIONS PENDING MECH REVIEW. ELEC OK.
  
 ** ADDRESS IS STILL NEEDED TO BE CHNAGED ON ALL
 DOCUMENTS ON TITLE BLOCKS TO 821 N FLAGLER.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-11-03 Cont ID  
Sent By dpalmer Date 2007-11-03 Time 10:45 Rev Time 0.00
Received By dpalmer Date 2007-11-02 Time 16:49 Sent To  
Notes
2007-11-03 10:45:15 
 ** DENIED 4TH REVIEW **
  
  
 1) NOTE: PLEASE SEE THE ENERGY CALCULATIONS AS
 SUBMITTED ARE IN NEED OF COMPLIANCE WITH THE FBC
 CHAPTER 13.
 PLEASE SEE THE VERSION AS NOW SUBMITTED IS INCORRECT
 FOR THE PERMIT APPLIED DATE. THIS PROJECT WAS SUBMITTED
 UNDER THE 2004 FBC BEFORE THE DECEMBER 8TH, 2006
 CHANGES THEREFORE THE VERSION AS ADOPTED SHOULD BE
 2.11. THE VERSION WHICH IS NOW BEING SUBMITTED FOR THE
 FIRST TIME IS 2.5 WHICH WAS NOT ADOPTED UNTIL DECEMBER
 8TH, 2006.
 13-415.1.A, 13- 400.3.A
  
 2) NOTE: PLEASE SEE THAT THERE WERE COMMENTS DATED
 8/28/07 FROM THE ADDRESSING REVIEW WHICH STATES THE NEW
 ADDRESS WILL BE ASSIGNED AS 821 N. FLAGLER AND THAT ALL
 DOCUMENTS, PLANS PERMIT APPLICATION WOULD NEED TO BE
 REVISED ACCORDINGLY. THIS WAS NOT DONE. THIS WAS NOT ON
 ELECTRICAL REVIEW COMMENTS AS THE CHANGE OF ADDRESS WAS
 NOT KNOWN. THIS IS BEING CONFIRMED WITH THE ADDRESSING
 REVIEWER BEFORE CHANGES ARE TO BE MADE TO ALL SHEETS.
 THE NEW ELECTRICAL SERVICE RE-FEEDS THE EXISTING
 BUILDING WHICH FACES FLAGLER.
 IF THE ADDRESS IS CONFIRMED AS 821, THEN THESE CHANGES
 CAN BE DONE BY PRINTING/CHANGING NUMERICAL DESIGNATIONS
 ON PLANS. THIS IS ALL TO BE CONFIRMED.
  
 ** PLEASE ADDRESS COMMENT NUMBER #1 ABOVE. PLEASE KNOW
 THE ELECTRICAL PLANS ARE OK, AND ALL THREE SETS HAVE
 BEEN STAMPED.
 THE NEW REVISED ENERGY CALCULATIONS UNDER THE 2.11
 VERSION ARE YET TO BE REVIEWED.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-08-26 Cont ID  
Sent By dpalmer Date 2007-08-26 Time 13:30 Rev Time 0.00
Received By dpalmer Date 2007-08-25 Time 19:13 Sent To  
Notes
2007-08-26 13:30:522007-08-26 13:30:52
  
 *** DENIED 3RD REVIEW***
  
  
 ROSARIAN ACADEMY
  
  
 ** PLEASE SEE THERE ARE STILL ITEMS FROM THE PREVIOUS
 TWO REVIEWS WHICH ARE IN NEED OF ADDRESSING. THERE ARE
 SOME NEW COMMENTS FOR COORDINATION AS SOME ITEMS HAVE
 BEEN REVISED ON PLANS OR ARE NOW SHOWN FOR REVIEW.
  
 ** PLEASE SEE THERE ARE TWO NEW COMMENTS WHICH WERE NOT
 ON PREVIOUS REVIEW. THESE ARE MINOR IN NATURE WHICH
 COULD BE REDLINED HOWEVER AS PLANS ARE GOING BACK FOR
 CORRECTIONS PLEASE ADJUST AT THIS TIME.
  
  
 1) NOTE: ** IMPORTANT**
 PLEASE SEE THAT ONE SET CONTAINS SOME REDLINES FOR
 AREAS FOR SOME OF THE NOTES BELOW. THIS REVIEWER IS
 REQUESTING FOR DESIGN PROFESSIONAL(S) RESPONSIBLE FOR
 ELECTRICAL PLANS AND DESIGN CALL TO SET UP A MEETING TO
 GO OVER COMMENTS AND PLANS BEFORE PLANS ARE
 RE-SUBMITTED. PLEASE KNOW IT MAY HELP TO DO THIS ONCE
 ALL REVIEWS ARE DONE. IF THERE ARE ANY COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT THE ELECTRICAL PLANS OR
 DESIGN THESE WOULD BENEFIT THE ELECTRICAL DESIGN TEAM
 TO OBTAIN ANY POSSIBLE COMMENTS BEFORE THE MEETING IS
 HELD.
  
 2) NOTE: PLEASE SEE THE RESPONSE LETTER FROM DESIGN
 TEAM WHICH STATES THE REVIEWER'S COMMENTS AND THEN
 PLACES A RESPONSE FROM THE DESIGN TEAM DIRECTLY BELOW.
 PLEASE BE SURE WHEN *QUOTING* THE REVIEWER'S COMMENTS
 TO TRANSCRIBE AS THE NOTES WERE WRITTEN. ANY CHANGES IN
 THE REVIEWER'S COMMENTS MAY LEAD TO SOME CONFUSION OF
 PARTIES INVOLVED READING THESE NOTES AND RESPONSES.
 *PLEASE SEE FOR EXAMPLE COMMENT #4 WHICH WAS TYPED AND
 MIXED IN WITH WHAT APPEARS TO BE MECHANICAL REVIEW
 NOTES BEING STATED AS THIS REVIEWERS PREVIOUS REVIEW
 COMMENT.
 IT IS UNDERSTOOD BY THIS REVIEWER THAT THIS SEEMS TO BE
 A MISPRINT OF NOTES AND IS ONLY NOTED.
  
 3) NOTE:PLEASE SEE THE PREVIOUS REVIEW NOTE #1 GAVE
 SPECIFICALLY THE RELATED CODES NEEDING TO BE STATED AND
 REFERENCED ON PLANS. PLEASE SEE THE LIFE SAFETY CODE IS
 STILL BEING SHOWN UNDER THE 2000 EDITION. THIS SHOULD
 BE THE 2003 NFPA-101 LIFE SAFETY CODE.
 IF THIS WERE ONE OF THE MINOR COMMENTS IT WOULD HAVE
 BEEN REDLINED ON PLANS HOWEVER AS THE PLANS ARE COMING
 BACK FOR OTHER CORRECTIONS, PLEASE ADJUST AT THIS
 TIME.
  
 4) NOTE: PLEASE SEE THAT COMPLIANCE WITH THE FBC
 CHAPTER 13 HAS NOT YET BEEN MET.
 PLEASE SEE THERE ARE SEVERAL ITEMS AND AREAS WHICH ARE
 STILL IN NEED OF ADDRESSING/CLARIFICATION/CORRECTIONS
 AND COORDINATION OF INFORMATION ON PLANS WITH THAT OF
 SUPPORTING DOCUMENTS. IT WILL BE THE ATTEMPT OF THIS
 REVIEWER TO TYPE AS MANY ITEMS IN DETAIL AS POSSIBLE
 HOWEVER MANY OF THESE ITEMS BEING NOTED BELOW WILL BE
 IN GENERAL AS THERE ARE SEVERAL LOCATIONS ON PLANS
 WHICH ARE IN QUESTION.THE DETAILS FOR EACH AND EVERY
 LOCATION WILL BE GONE OVER IN A MEETING AND WITH THE
 REDLINED PLANS.
  
 A) PLEASE SEE AS STATED IN THE TWO PREVIOUS REVIEWS:
 PLEASE BE SURE TO CORRELATE ALL LIGHTING ON PLANS WITH
 THE SUBMITTED ENERGY CALCULATIONS AS SUBMITTED. PLEASE
 SEE THERE ARE ITEMS ON PLANS WHICH ARE STILL NOT BEING
 ENTERED IN THE *INPUT DATA REPORT*. THE INPUT DATA
 REPORT IN NOTES WILL BE NOTED AS IDR IN THE REST OF THE
 COMMENTS;
 PLEASE SEE THE LC IN THE COMMENTS BELOW WILL BE
 ABBREVIATION FOR LIGHTING CONTACTOR:
  
 PLEASE SEE AS STATED ON THE PREVIOUS REVIEWS, NO
 EXTERIOR LIGHTING IS BEING ENTERED IN THE IDR. THE
 SUMMARY SHEETS DO NOT SHOW ANY EITHER. HOW IS THIS
 POSSIBLE WHEN THE PLANS CLEARLY SHOW A SUBSTANTIAL
 AMOUNT OF EXTERIOR LIGHTING? PLEASE SEE
 13-415.2.ABC.1.3, 13-415.0, 13-415.2, 13-415.1.A.
  
 B) PLEASE ALSO SEE THE METHOD OF CONTROL FOR EXTERIOR
 LIGHTING PER 13-415.1.ABC.1.4. THERE ARE SOME AREAS
 WHICH MAY FALL UNDER LIGHTING EXCEPTION FOR SECURITY
 HOWEVER MOST OF THESE ARE BEING SHOWN THROUGH A
 LIGHTING CONTACTOR (LC) OF SOME KIND WITH OUT ANY
 INFORMATION FOR PHOTO-SENSOR, ASTRONOMICAL TIME CLOCKS.
 MORE INFORMATION IS NEEDED AND WILL BE GONE OVER.
  
 C) PLEASE SEE WEST EXTERIOR LIGHTS ON SHEET E2.2.1,
 WHICH SHOWS 7 *D* FIXTURES IN SHADED NOTATION AND
 ANOTHER *D* FIXTURE WITHOUT BEING SHADED. PLEAS SEE
 THIS AREA FOR EXAMPLE IS BEING NOTED BY THE KEY NOTES
 TO BE WIRED THROUGH THE LIGHTING CONTACTOR. IF THE DARK
 SHADED FIXTURES ARE ACTUALLY *DE* FIXTURES AS SHOWN ON
 THE REST OF THE PLANS, THEN THIS WOULD PLACE ONLY ONE
 FIXTURE ON THE LC AND THE REST TO BE WIRED AHEAD OF THE
 LC. THIS WOULD LEAVE ALL OF THE FIXTURES ON ALL THE
 TIME. PLEASE SEE THAT IT IS KNOWN AND OK TO LEAVE SOME
 FIXTURES ON FOR *SECURITY* AND/OR 24HRSHOWEVER IT IS
 UNCLEAR WHAT IS BEING SHOWN IN THIS AREA OF DESIGN.
 THIS WILL NEED TO BE GONE OVER IN MEETING.
 (THIS WILL AFFECT THE EMERGENCY LIGHTING COMMENTS
 ALSO)
  
 D) PLEASE SEE MANY AREAS ON LIGHTING PLANS CONTAIN *KEY
 NOTES* (#2, #3 ETC) WHICH CALL FOR NOTES WHICH STATES
 LIGHTING TO BE CONTROLLED THROUGH LC YET WHEN LOOKING
 AT THE LC ON SHEETS THESE SPECIFY AN OVER RIDE SWITCH
 OF SOME KIND WHICH DOES NOT GIVE ANY INFORMATION ON THE
 REQUIRED OVER RIDE MAXIMUM TIMES. PLEASE SEE EACH OF
 THESE MOMENTARY SWITCHES ON THE LC IS NOTED WITH
 ANOTHER KEY NOTE #1. THIS NOTE AT THE BOTTOM OF EACH LC
 SCHEDULE MENTIONS TO SEE SHEET E2.1 FOR LOCATIONS OF
 ALL OF THESE OVER RIDE LOCATIONS.
  
 **(NOTE: THIS IS SPELLED AS *LWAATIONS* (MISPRINT) ON
 MANY OF THESE NOTES AND IS BEING ASSUMED THIS IS FOR
 *LOCATIONS*) PLEASE SEE FOR EXAMPLE LC-1A, LC-1B AND
 OTHERS ON LIGHTING SHEETS. THE FAILURE COMMENT IS NOT
 BASED ON THE SPELLING OF THIS WORD.)**
  
 PLEASE SEE THAT THE FIRST ITEM IS THAT THE REQUIREMENTS
 OF 13-415.1ABC.1.1 AND 13-415.1.ABC.1.2 IS THAT THE
 OVER RIDES ARE LOCATED SO THAT THE OCCUPANT CAN READILY
 SEE THE LIGHTING BEING CONTROLLED. THERE IS AN
 EXCEPTION FOR *PILOT LIGHTS* HOWEVER PLEASE SEE SOME
 AREAS CONTAIN KEY NOTES FOR LIGHTING TO BE THROUGH LC
 AND PLANS ALSO SHOWS A *SO*. HOW IS THE *SO* (OCCUPANCY
 SWITCH/DEVICE) GOING TO WIRED INTO THIS AS THE LC DOES
 NOT DETAIL THIS AND HOW WILL THE OCCUPANT BE ABLE TO
 OVER RIDE THE LIGHTING IN THE AREAS.
 PLEASE SEE HALLWAYS AND CORRIDORS E2.2.1, E2.1.2,
 E2.2.2 ETC.
 PLEASE SEE KEY NOTE #3 ON SHEETS E2.1.1 AND E2.1.2
 WHICH MENTIONS TO SEE LC-1C ON SHEET E2.1.1, YET THIS
 LC DETAIL IS ON E2.1.2. (MISPRINT)?
 PLEASE CLARIFY HOW THESE LC MOMENTARY SWITCHES AS NOTED
 WILL MEET THE SECTIONS AS NOTEDFOR OVER RIDES,
 MAXIMUM TIMES, AND LOCATIONS FOR CONTROLS.
 PLEASE CLARIFY THE OCCUPANCY TYPE DEVICES WHICH ARE
 BEING SHOWN IN HALL, CORRIDOR LOCATIONS WHICH IF A WALL
 TYPE OCCUPANCY SENSOR TYPE DEVICE WILL NOT COVER SOME
 AREAS FOR THE OCCUPANT IF THE LC IS TURNED TO THE OFF
 POSITION.
 PLEASE KNOW THERE ARE SEVERAL AREAS AND ITEMS WHICH ARE
 REDLINED ON PLANS AND WILL NEED TO BE GONE OVER IN A
 MEETING.
  
 E) PLEASE SEE CLASSROOM #4 WHICH INDICATES PER THE
 SYMBOLS ON PLANS AND SYMBOLS ON LEGEND THAT THESE
 DEVICES ARE STANDARD SWITCHES. PLEASE CLARIFY HOW THESE
 MEET 13-415.1.ABC.1.2, AND .1.1.
 PLEASE SEE THESE ARE REDLINED ON PLANS ON ONE SET. THIS
 IS ON SHEET E2.2.2
  
 F) PLEASE COORDINATE THE IDR WITH THE FIXTURE LEGEND
 FOR TYPES OF FIXTURES AND WATTAGES. SOME OF THE NUMBERS
 ON THE IDR AND THE PLANS/FIXTURE LEGEND DO NOT
 CORRELATE AT THIS TIME.
 13-415.1.A,
 FBC 106.1.2
  
 5) NOTE: PLEASE SEE THE TWO PREVIOUS REVIEWS REQUESTED
 FOR COMPLETED PHOTO-METRICS FOR NORMAL AND EMERGENCY
 EGRESS PATHS OUT AND AWAY FROM BUILDING UNDER **NORMAL
 AND EMERGENCY* CONDITIONS.
 THE REVIEWS ALSO REQUESTED FOR THE LIGHT FIXTURES WHICH
 IS PLACED ON THE LIGHTING PLANS TO COORDINATE WITH THE
 LIGHT FIXTURES ON THE PHOTO-METRICS SHEETS.
 MOST OF THESE ARE DONE AND SUBMITTED HOWEVER NOT ALL.
  
 A) PLEASE SEE SHEET E1.2.1 WHICH SHOWS THE TABLE WHICH
 THE DESIGNATIONS FOR THE STAIRS 1, 2 AND WEST STAIRS
 ARE NOT SHOWN ON TABLES FOR NORMAL LEVELS AS REQUIRED.
 PLEASE SEE THE LEVELS UNDER NORMAL FOR STAIR 1 AND 2
 SEEM LOW AND THE STAIRS ON WEST SIDE DO NOT INDICATE
 ANY LEVELS UNDER NORMAL.
  
 B) PLEASE SEE SHEET E1.2.2 EAST SIDE FIRST FLOOR EXIT
 AREA AS NO LEVELS ARE SHOWN UNDER NORMAL?
  
 C) PLEASE SEE SHEET E1.2.1E AS THE WEST EXIT AREA FOR
 EM TYPE FIXTURES DOES NOT CORRELATE WITH THE FIXTURE
 DESIGNATIONS ON THE LIGHTING PLANS SHEET E2.2.1 FOR
 THIS SAME AREA.(CORRIDOR/OUTSIDE AREA).
  
 D) PLEASE SEE SHEET E1.3.1 FOR AREA ON WEST SIDE DOES
 NOT INCLUDE STAIRS EITHER. THE NORMAL LIGHTING LEVELS
 FOR EGRESS STAIRS NEEDS TO BE SHOWN ON THIS SHEET OR
 SHEET NOTED ABOVE IN PART *A* OF THIS COMMENT NUMBER
 5.
  
 ** PLEASE SEE AS WITH COMMENT ABOVE (#4) WITH RESPECT
 TO CONTROLS OF LIGHTING FOR CHAPTER 13 AND THOSE ITEMS
 REQUIRED IN THIS COMMENT FOR LIFE SAFETY CODE IS
 REDLINED ON PLANS AND WILL NEED TO BE GONE OVER IN
 MEETING TO BE HELD.
  
 6) NOTE: PLEASE BE SURE THE OWNER AGENT IS SIGNED ON
 THE ENERGY CALCULATIONS.
 13-103.1.1.1.
  
 7) NOTE: ( NEW NOTE)PLEASE SEE THE CLASSROOM #4 AND
 SOME OTHER REDLINED LOCATIONS ON PLANS WHICH A LIGHTING
 FIXTURE IS BEING SHOWN IN STORAGE CLOSETS WHICH DO NOT
 MEET 410.8 FOR MINIMUM CLEARANCES.
 PLEASE SEE THIS NOTE IS FOR THE SMALLER CLOSETS AND FOR
 MINIMUM AREAS FROM FIXTURES FROM COMBUSTIBLES AND
 EASILY IGNITABLE MATERIALS.
 THESE WERE REDLINED ON SHEETS.
 THIS COMMENT WAS NOT MADE ON PREVIOUS REVIEW AND MISSED
 BY THIS REVIEWER.
 THIS IS STILL A CODE RELATED AND SAFETY ISSUE AND
 SHOULD BE ADDRESSED AT THIS TIME AS PLANS ARE BEING
 REVISED FOR OTHER COMMENTS.
  
 8) NOTE: (NEW NOTE) PLEASE SEE THE DESIGNATIONS ON
 RISER FOR CIRCUITING OF PANELS DP3A, DP2A, DP1A, DP1B,
 DP2B WHICH ARE ALL DESIGNATED TO *SBA*, WHEN THE MAIN
 SWITCH BOARD DESIGNATION IS SSA.
 THIS WAS MISSING ON THE PREVIOUS REVIEW BY THIS REVIEW
 EVEN THOUGH THIS WAS SHOWN THE SAME.
 THESE LOCATIONS ARE REDLINED ON PLANS.
 IF SHEET DOES NOT NEED TO BE REVISED FOR ANY OTHER
 COMMENTS, THEN THIS ITEM CANE BE REDLINED ON SHEETS AS
 IS. (MISPRINT)
  
 9) NOTE: PLEASE SEE THE PREVIOUS REVIEW GAVE NOTICE TO
 FS 553.80(2)(B) WITH RESPECT TO REPEAT COMMENTS FOR
 CODE COMPLIANCE.
 THESE WILL BE GONE OVER IN A PEER REVIEW WITH THE
 ASSISTANT BUILDING OFFICIAL AS ITEMS FROM THE FIRST AND
 SECOND REVIEW FOR CODE COMPLIANCE HAS NOT BEEN MET. THE
 PLANS HOWEVER HAVE BEEN REVISED EACH TIME TO PARTIALLY
 ADDRESS COMMENTS.
 THE 4X FEE FOR PLAN REVIEW HAS NOT BEEN ASSESSED AT
 THIS TIME. THIS WILL BE UNDER FURTHER REVIEW. **ONE
 COPY OF ELECTRICAL PLANS AND ENERGY CALCULATIONS WILL
 BE RETAINED BY THIS OFFICE.
  
 AS STATED IN THE TWO PREVIOUS REVIEWS:
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
 TO DATE THIS PROJECT HAS NOT BEEN GONE OVER WITH THE
 DESIGN TEAM.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-08-26 07:50:472007-08-26 07:50:47
 REVIEW IN PROGRESS
2007-08-25 20:01:332007-08-25 20:01:33
 PLANS IN ELECTRIC FOR REVIEW.
 REVIEW TO COMMENCE ON 8/26/07

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-04-21 Cont ID  
Sent By dpalmer Date 2007-04-21 Time 12:51 Rev Time 0.00
Received By dpalmer Date 2007-04-21 Time 07:57 Sent To  
Notes
2007-04-21 12:53:122007-04-21 12:53:12
  
 ** UNSAT 2ND REVIEW**
  
 ** PLEASE SEE ANY REFERENCES TO THE FBC CHAPTER 1 ARE
 THE ADMINISTRATIVE SECTION AS ADOPTED BY THE CITY OF
 WEST PALM BEACH.
  
 ** PLEASE SEE THERE ARE MANY ITEMS FROM THE PREVIOUS
 REVIEW WHICH ARE STILL IN NEED OF ADDRESSING ALONG WITH
 SOME NEW COMMENTS AS WELL AS COMMENT WHICH COULD NOT BE
 MADE YET AS THE PLANS SUBMITTED CONTAIN SOME MISSING
 SHEETS ETC. PLEASE SEE NOTES BELOW WHICH WILL FURTHER
 EXPLAIN.
 ** SOME OF THE COMMENTS BELOW ARE NOT RELEVANT TO KAMM
 CONSULTING.
  
 ** PLEASE SEE THAT ONE SET CONTAINS SOME REDLINES FOR
 AREAS FOR SOME OF THE NOTES.
  
 1) NOTE: PLEASE BE SURE ALL PLANS REFLECT THE FOLLOWING
 CODES AT A MINIMUM.
 2002 NFPA-70, 2003 NFPA-101, 2002 NFPA-72
 THIS IS REQUIRED ON THE ARCHITECTURAL SHEETS AS WELL.
 THE ELECTRICAL SHEETS WERE CORRECTED WITH THE UPDATED
 CODE INFORMATION..
  
 2) NOTE: PLEASE SEE THAT COMPLIANCE WITH THE FBC
 CHAPTER 13 HAS NOT YET BEEN MET. PLEASE SEE THE
 RESPONSE LETTER ONLY RESPONDED TO THE FIRST SENTENCE OF
 THE PREVIOUS NOTES AND THE REST OF THE NOTE #2 FROM
 PREVIOUS REVIEW WAS LEFT.
  
 A) PLEASE SEE THAT THE PREVIOUS REVIEW NOTE WILL BE
 LEFT AS IS AND NEW EXPLANATORY NOTES ARE LISTED AS
 FOLLOWS.
  
 B) PLEASE SEE SOME OF THE CIRCUITING SHOWN ON PLANS
 WHICH INDICATE CONTROLS THROUGH THE LCPS ARE NOT LISTED
 ON THE LCPS OR DO NOT CORRELATE. PLEASE SEE THAT
 CIRCUIT/CONTROL DESIGNATIONS ARE SHOWN AS AB ON ONE AND
 BA ON ANOTHER.
  
 C) PLEASE SEE THERE ARE STILL DEVICES AND SYMBOLS ON
 PLANS WHICH ARE NOT LISTED ON THE SYMBOL LEGEND FOR
 OVER RIDE DEVICES ON THE SYMBOL LEGEND FOR ELECTRICAL
 DEVICES.
  
 D) PLEASE SEE THAT THE LEGEND FOR OVER RIDE DEVICES DO
 NOT INDICATE ANY MAXIMUM TIME FOR PERMITTED OVER RIDES
 AS REQUIRED.
  
 E) PLEASE SEE THAT MANY AREAS LIKE HALLWAYS, BATHROOMS
 AND OTHER AREAS ETC CONTAIN AN *SO* AND *SW* TYPE
 DEVICES WHICH WILL NOT PROVIDE COVERAGE FOR LIGHTING
 CONTROL FOR LIFE SAFETY OR NORMAL OVER RIDE CONTROL.
 PLEASE SEE SOME HALLS WHICH CONTAIN THIS DEVICE AT ONE
 END OF THE HALL OR ON ONE SIDE WITH WALLS ETC BLOCKING
 ANY DETECTION FROM OTHER AREAS FOR OVER RIDE. PLEASE
 SEE *SK* DEVICE WHICH IS NOT LISTED FOR CONTROL OR WHAT
 TYPE OF OPERATION.
  
 F) PLEASE SEE ROOMS AND AREAS WHICH DO CONTAIN FLOOR TO
 CEILING HEIGHT PARTITIONS OR WALLS WHICH THESE ROOMS
 ARE SEPARATE AND NO OVER RIDE DEVICES ARE SHOWN ON
 PLANS.
  
 G) PLEASE THE COMPLETE REVIEW FOR LIGHTING AS SHOWN ON
 PLANS AND LIGHTING ON FIXTURE LEGEND AND LIGHTING ON
 ENERGY CALCULATIONS CAN NOT BE REVIEWED AS THE ENERGY
 CALCULATIONS DO NOT CORRELATE WITH PLANS FOR LIGHTING
 OR WITH FIXTURE LEGEND FOR TYPES OF FIXTURES, NUMBER OF
 FIXTURES, AND WATTAGE ON FIXTURES.
  
 H) PLEASE SEE THE TYPE OF CONTROLS FOR LIGHTING DOES
 NOT CORRELATE. THE ENERGY CALCULATIONS STILL INDICATE
 *MANUAL ON/OFF8 FOR CONTROL?
  
 I) PLEASE SEE SOME CIRCUITS WHICH ARE NOTED AS BEING
 CONTROLLED THROUGH A LIGHTING DIMMING PANEL WHICH IS
 NOT INDICATED IN ANY LIGHTING CONTROL PANEL OR ON
 LIGHTING CONTROL DEVICES.
 PLEASE PROVIDE MORE DETAILS ON HOW THIS OPERATION WILL
 TAKE PLACE. NEED TO PROVIDE MORE INFORMATION FOR
 REVIEW. FBC 106.1.2
  
 ** PLEASE KNOW AS THERE ARE MANY ITEMS WHICH ARE NOT
 YET CLEAR OR SHOWN, COMPLETE REVIEW FOR SOME ITEMS CAN
 NOT BE DONE.
  
 * PREVIOUS REVIEW NOTE FROM REVIEW #1*
 PLEASE SEE FBC CHAPTER 13. PLEASE SEE
 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE THERE ARE MANY AREAS WHICH INDICATE SOME
 SORT OF SYMBOL NEXT TO SWITCH, HOWEVER AS THIS SYMBOL
 IS NOT LOCATED ON THE SYMBOL SCHEDULE IT IS UNCLEAR
 WHAT THIS IS FOR REVIEW OF COMPLIANCE WITH ANY LIGHTING
 CONTROL REQUIREMENTS.
 PLEASE SEE MANY OTHER AREAS WHICH A SWITCH IS BEING
 SHOWN AND THE CIRCUIT IS NOT LABELED GOING THROUGH THE
 LIGHTING CONTROL PANEL.
 ** PLEASE KNOW THE LIGHTING CONTROL PANEL WILL BE NOTED
 AS "LCP" IN THE NOTES FORM HERE OUT.
 PLEASE SPECIFY THE SYSTEM WHICH IS BEING INSTALLED OR
 SPECIFIED FOR THE SCOPE OF WORK AND INTENDED
 CONTROL.110.3, 90.7
 PLEASE SEE EACH SPACE SHALL CONTAIN A DEVICE WHICH OVER
 -RIDES A SYSTEM, OR PROVIDES CONTROLS MEANS AS OTHER
 METHODS LISTED IN 13-415.1.ABC.1.1, .1.2.
 PLEASE SEE THERE ARE SEVERAL ROOMS WHICH DO NOT
 INDICATE ANY KIND OF OVER RIDE DEVICE, OCCUPANT SENSOR
 ETC.
 PLEASE SEE THE OVER RIDE TYPE DEVICE IS ALSO REQUIRED
 TO BE LOCATED IN THE AREAS IN WHICH THE OCCUPANT CAN
 SEE THE LIGHTING BEING CONTROLLED.
 PLEASE SEE MISSING AUTO SHUT OFF OF PIT LIGHTS. PLEASE
 BE SURE THE LCP PANEL ONLY CONTROL LIGHTING WHICH
 SHOULD NOT BE TURNED OFF, :IE: PLEASE CIRCUIT WHICH ARE
 SHOWN BEING WIRED TO THE LCP'S , HOWEVER PLEASE SEE
 THERE ARE ALSO EMERGENCY LIGHTING ON THOSE SAME
 CIRCUITS. PLEASE PROVIDE DETAIL ON THE LCP
 RISER/DIAGRAM WHERE ALL EXIT AND EMERGENCY LIGHTING IS
 CIRCUITED AHEAD OF THE LOCAL LIGHTING CONTROL DEVICES.
 PLEASE SEE MISSING PERFORMANCE CALCULATIONS FOR ALL
 AREAS. PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED DO
 NOT INDICATE ANY EXTERIOR LIGHTING; HOWEVER THE PLANS
 INDICATE LIGHTING IN MANY LOCATIONS.
 PLEASE SEE ENERGY CALCULATIONS DO NOT INDICATE THE
 REQUIRED AUTOMATED CONTROLS WHERE LISTING TYPE OF
 CONTROL.
 PLEASE SEE 13-415.1.AB.1, 13-415.2, 13-415.2.ABC.1,
 13-415.2.ABC.1.3.
 PLEASE SEE FBC CHAPTER 13, AS THERE ARE MANY AREAS AND
 ITEMS AS NOTED ABOVE WHICH NEEDS TO BE ADJUSTED.
  
 3) NOTE: PLEASE CORRELATE ALL SQ FT ON ALL DOCUMENTS.
 THIS NOTE REMAINS AS THE SQ FT ON PERMIT APPLICATION IS
 ONE, THE SQ FT ON PLANS ARE ANOTHER AND THE SQ FT ON
 ENERGY CALCULATIONS ARE YET ANOTHER. PLEASE COORDINATE
 ALL OF THESE.
 PLEASE BE SURE TO COORDINATE WITH ALL SHEETS ELECTRICAL
 AND OTHER WISE.
  
 4) NOTE: PLEASE SEE MISSING NORMAL AND EMERGENCY
 PHOTO-METRICS IN ALL EGRESS PATH AREAS. PLEASE SEE
 MISSING STAIR WAYS. PLEASE SEE NFPA-101 2003, 7.8.1.3,
 AND 7.9.2.2.
 A) STAIRS REQUIRE A MINIMUM OF 10FT CANDLES UNDER
 NORMAL AND 1FT CANDLE UNDER EMERGENCY.
 B) PLEASE SEE THIS IS FOR ALL EXIT STAIRS TO THE PUBLIC
 RIGHT OF WAY FOR EGRESS PATHS.
  
 PLEASE SEE PREVIOUS NOTES WHICH REQUESTED ALL MINIMUM
 LIGHTING LEVELS AS REQUIRED PER THE LIFE SAFETY CODE TO
 BE SHOWN.
 PLEASE SEE NO NORMAL LIGHTING LEVELS FOR EGRESS AREAS
 WERE SUBMITTED FOR REVIEW?
 PLEASE SEE THERE ARE DISCREPANCIES IN THE PLANS. PLEASE
 SEE THE LIGHTINGPLANS AND PHOTO-METRICS ETC AS THE
 SOME OF THE FIXTURES ARE MISSING FROM PHOTO-METRICS,
 SOME OF THE FIXTURES SHOWN ON PHOTO-METRICS ARE NOT THE
 SAME NUMBER OF FIXTURES ON PLANS ETC.
 PLEASE SEE SOME AREAS WHICH SHOW LIGHTING FOR EGRESS OR
 THE NUMBER AND TYPE OF FIXTURES DO NOT CORRELATE.
 PLEASE SEE SOME OF THE AREAS WHICH ARE NOTED FOR
 EXAMPLE WHICH ARE NOT ALL LOCATIONS WHICH COORDINATION
 IS NEEDED.
 PLEASE SEE: STAIRS 3, STAIR 4, EGRESS AREAS FROM SECOND
 FLOOR ON WEST SIDE OF GYM, AREAS ON WEST SIDE, AREAS ON
 NORTH SIDE, ETC
 PLEASE GO THROUGH ALL FIXTURES ON PLANS AND COORDINATE
 WITH THE FIXTURES ON PHOTO-METRICS AND ENERGY
 CALCULATIONS.
 PLEASE SEE SOME FIXTURES WHICH SEEM TO BE SHADED FOR A
 TYPICAL EM FIXTURE YET THE DESIGNATION IS THAT OF A
 NORMAL FIXTURE W/OUT BATTERY BACK UP.
 PLEASE SEE NFPA-101 7.8, 7.9, 7.8.1.3, 7.9.2.2 WHICH
 REQUIRES LIGHTING AND EMERGENCY LIGHTING TO THE PUBLIC
 RIGHT OF WAY. PLEASE SEE ALL EXTERIOR STAIRS INCLUDING
 LARGE AND SMALLER STAIRS AREAS WILL REQUIRE SOME SORT
 OF BATTERY BACK UP FIXTURES WHICH WILL PROVIDE THE
 MINIMUM FT CANDLES TO THE PUBLIC RIGHT OF WAY, OUT AND
 AWAY FROM THE BUILDING.
 PLEASE SEE THIS INCLUDES RAMP AREAS.
  
 5) NOTE: PLEASE SEE ELEVATOR EQUIPMENT ROOMS WHICH WILL
 REQUIRE A CHANGE IN FIXTURE TYPE OR AN ADDITIONAL
 FIXTURE. PLEASE SEE 700.16. THIS IS THE SAME COMMENT AS
 THESE ROOMS STILL ONLY INDICATE ONE FIXTURE. PLEASE
 PROVIDE A FIXTURE WHICH CONTAINS MORE THAN A SINGLE
 BALLAST CONTROLLING EACH BULB, OR ADJUST THE NUMBER OF
 FIXTURES OR ADJUST BY SOME OTHER MEANS. PLEASE SEE
 620.23 WHICH REQUIRE DEDICATED BRANCH CIRCUITS FOR
 THESE CIRCUITS FOR LIGHTING AND RECEPTACLES. PLEASE SEE
 THE POWER PLANS WHICH INDICATE A NOTE #3 WHICH STATES
 THE GFI WILL BE FED FROM THE VFD.(VARIABLE FREQUENCY
 DRIVE) WHICH CAN NOT BE DONE OR IS PERMITTED.
 PLEASE SEE ONLY ONE OF THE TWO ELEVATOR EQUIPMENT ROOMS
 CONTAINS A DEDICATED LIGHTING CIRCUIT. PLEASE SEE THE
 CIRCUIT FOR ROOM #1 LIGHTING IS LISTED ON PANEL
 SCHEDULE *L1AA* AS A CIRCUIT WHICH FEEDS A *REFG*
 PANEL?
 PLEASE ADJUST ALL CIRCUITING FOR ELEVATOR ROOMS AND
 LIGHTING.
  
 6) NOTE: PLEASE SEE 110.26, 408.7, AND 240.24D WHICH DO
 NOT PERMIT ELECTRICAL PANELS TO BE LOCATED IN STORAGE
 ROOMS OR CLOSETS. PLEASE ADJUST LOCATIONS OF EQUIPMENT
 OR CREATE DEDICATED ELECTRICAL ROOMS/CLOSETS AS DONE IN
 SOME OTHER LOCATIONS ON PLANS.
 PLEASE KNOW THAT THIS NOTE REMAINS AS NOT ONLY ARE MANY
 LOCATIONS ON PLANS FOR THESE SAME LOCATIONS STILL
 IDENTIFIED AS *STORAGE ROOMS* BUT AS TO THE LOCATIONS,
 SIZE ETC THE FOLLOWING CONSIDERATION IS TO BE MADE FOR
 ROOM 113 ADJACENT TO THE *MULTI-PURPOSE ROOM*. THIS
 ROOM WHICH CONTAINS THESE ELECTRICAL PANELS IS THE ONLY
 ROOM WHICH IS ADJACENT TO THIS MULTI-PURPOSE ROOM WHICH
 CONTAINS NO OTHER ADJACENT STORAGE ROOMS OR CLOSETS.
 THUS, THIS ROOM DUE TO IS SIZE, PROXIMITY AND THE LACK
 OF ANY OTHER STORAGE AREAS WILL MOST CERTAINLY BE
 UTILIZED AS A STORAGE ROOM OF SORTS. THE NEC AND LIFE
 SAFETY CODE REQUIRE THAT NOT ONLY ARE ITEMS NOT
 PERMITTED TO BE STORED IN THESE ROOMS THEY ALSO
 PROHIBIT THE STORING OF COMBUSTIBLES AND EASILY
 IGNITABLE MATERIALS ABOUT ELECTRICAL EQUIPMENT
 CONTAINING OVER CURRENT PROTECTION. IN THE INTEREST OF
 NOT ONLY THE FIRE HAZARD TO PROPERTY, THE LIFE SAFETY
 TO OCCUPANTS SHOULD BE CONSIDERED TO CHANGE THIS
 AREA/WALLS/LAYOUT TO PERHAPS PROVIDE A SEPARATE STORAGE
 AREA FOR THIS MULTI-PURPOSE ROOM AND THE MECHANICAL AND
 ELECTRICAL ROOMS TO CONTAIN NOT ONLY LOCKED DOORS, BUT
 TO ALLEVIATE THE STORAGE POTENTIAL. THIS WILL BE GONE
 OVER IN DETAIL WITH THE FIRE MARSHAL AND FIRE PLAN
 REVIEWER. PLEASE CONSULT WITH THIS OFFICE AND FIRE
 DEPARTMENT FOR ANY OTHER LOCATIONS/PROPOSED CHANGES. **
 ACCESS TO ELECTRICAL ROOMS SHALL BE FOR *QUALIFIED
 PERSONNEL* AS DEFINED IN THE NEC.
 *** PLEASE SEE ACCESS TO ELECTRICAL EQUIPMENT SHOULD
 ALSO NOT BE THROUGH STORAGE ROOMS. EQUIPMENT SHOULD BE
 LOCATED IN A MANNER WHICH READY ACCESS CAN BE GRANTED
 AND QUITE OFTEN STORAGE ROOMS BECOME A LOCATION WHERE
 THINGS IMPEDE ACCESS AS NEEDED.
  
 7) NOTE: PLEASE SEE THE CIVIL SHEETS ARE MISSING
 REQUIRED INFORMATION ON TITLE BLOCKS AS REQUIRED PER
 FAC 61G15-23.002 AND FS 471.023. NOT A COMMENT FOR KAMM
 CONSULTING.
 MISSING PRINTED NAME, PRINTED LICENSE NUMBER ALONG WITH
 MISSING CERTIFICATE OF AUTHORIZATION NUMBER. THIS IS
 REQUIRED WHETHER OR NOT COMMENT IS MADE BY ANY OTHER
 TRADE.
  
 8) NOTE:PLEASE COORDINATE ALL FIXTURES ON PLANS AND
 IDENTIFY ALL FIXTURES. PLEASE SEE PLANS STILL CONTAIN
 SEVERAL FIXTURES WHICH ARE NOT IDENTIFIED OR COORDINATE
 WITH FIXTURE LEGEND, LIGHTING PLANS AND PHOTO-METRIC
 PLANS AS NOTED ABOVE IN NOTE #2.
 FBC 106.1.2 ADMIN SECTION.
  
 9) NOTE: SAME NOTE AS ON PREVIOUS REVIEW WHICH WILL
 REMAIN AS COORDINATION OF CIRCUITS, CONTROLS ETC AS
 NOTED IN NOTE #2 ABOVE NEEDS TO BE DONE.
 PLEASE SEE THERE ARE SEVERAL CIRCUITS ON PLANS WHICH
 DO NOT SEEM TO BE SHOWN GOING THROUGH ANY OF THE
 LCP'S?
 PLEASE PROVIDE A COMPLETE LCP SCHEDULE FOR ALL
 CIRCUITS.
 13-415.1.ABC.1.1, .1.2, AND .1.3.
  
 10) NOTE: PLEASE PROVIDE MORE INFORMATION ON MAIN 1 OF
 2. PLEASE INDICATE SIZE, VOLTAGE ETC.
 THIS NOTE REMAINS AS ONLY INFORMATION ON THE EXISTING
 PANEL/MAIN IN THE AMPHITHEATRE WAS NOTED.
 THE SIZE, VOLTAGE, OVER CURRENT PROTECTION CAN NOT BE
 ASSUMED. THE RESPONSE LETTER MENTIONS TO SEE REVISED
 E5.1, YET NO CHANGES OR INFORMATION COULD BE FOUND.
 PLEASE SEE THE RISER SHOWS *DASHED LINES* FOR MAIN 1
 AND MAIN 2, WHICH AS NOTED ON THE RIGHT OF RISER, THE
 *DASHED LINES* REPRESENT THESE AS *EXISTING*, HOW IS
 THIS POSSIBLE WHEN THE BUILDING IS BEING BUILT AND THIS
 EQUIPMENT IS NOT INSTALLED AT THIS TIME?
 PLEASEADJUST DESIGNATIONS.
 230, 240, 110.3, 90.7
 FBC 106.1.2
  
 11) NOTE: PLEASE ADJUST NOTED #12 FOR RISER AS THE NOTE
 TENDS TO LEND TO THE DISCONNECTING OF THE EXISTING
 GROUNDING ELECTRODE SYSTEM.
 PLEASE ADJUST NOTE WITH WORDS WHICH REQUIRES THE
 *SEPARATION* OF THE EXISTING NEUTRAL AND GROUNDING
 ELECTRODE SYSTEM BOND, SO THAT THE NEW EQUIPMENT
 GROUNDING CONDUCTOR FROM THE NEW MAIN IS CONNECTED TO
 THE EXISTING GROUNDING ELECTRODE SYSTEM. (WORDS TO THE
 SAME AFFECT TO BE CHOSEN BY DESIGNER) (PLEASE CONTACT
 THIS OFFICE FOR ANY QUESTIONS OR TO GO OVER IF NEED
 BE)
 250.6, 250.50, 250.24, 250.110 ETC.
  
 12) NOTE: PLEASE SEE LIGHTING ON PLANS WHICH DO NOT
 CONTAIN SOME CIRCUITING DESIGNATIONS.
 PLEASE ALSO SEE SOME EM LTS, WHICH DO NOT INDICATE
 CIRCUITING.(GYM)
 PLEASE SEE FBC 106.3.5.1.2, 106.1.2 FOR COORDINATION
 AND SEE 700.12E FOR CIRCUITING OF EMERGENCY AND EXIT
 LIGHTS TO LOCAL LIGHTING CIRCUITS AS SHOWN ON MOST OF
 THE PLANS.
  
 13) NOTE: PLEASE SEE NO LOAD CALCULATIONS OR LOAD
 SUMMARY COULD BE LOCATED.
 220.3, 220.10, 220.11, 220.13, 215.3 AND 230.42 ETC.
 FBC ADMIN SECTION 106.3.5.1.2
  
 14) NOTE: PLEASE SEE SETS OF PLANS SUBMITTED ARE NOT
 COMPLETE AT THIS TIME FOR REVIEW. PLEASE SEE PLANS ARE
 MISSING THE FIRST FLOOR WEST SIDE POWER PLANS.SETS
 FOR POWER PLANS AND SHEETS START AT E3.1.2. PLEASE SEE
 THE PREVIOUS PLANS SUBMITTED DID CONTAIN A E3.1.1. FBC
 106.3.5.1.2, 106.1.2
  
 15) NOTE: PLEASE BE SURE THAT ALL SHEETS IN ALL SETS
 ARE SIGNED, DATED AND SEAL BY THE DESIGN PROFESSIONALS
 AS REQUIRED UNDER FAC 61G15-23.002 AND FS 471.025.
 PLEASE SEE THAT MULTIPLE SHEETS IN SOME SETS ARE NOT
 SIGNED, DATED OR SEALED AT ALL FOR M, E, P AND FA
 SHEETS. THIS SEEMS TO BE THE NEW REVISED SHEETS ONLY.
 THIS REVIEWER CHECKED AT LEAST ONE OTHER SET SUBMITTED
 AND THIS WAS DONE HOWEVER NOT ALL SETS WERE DONE.
 PLEASE BE SURE TO DO THIS FOR ALL SHEETS, ALL SETS AND
 ALL DOCUMENTS.
  
 16) NOTE: PLEASE SEE INDICATE ANY FIRE SPRINKLER WATER
 LINE AS PART OF THE GROUNDING ELECTRODE SYSTEM.
 250.106
 PLEASE SEE RESPONSE MENTIONS TO *CONNECT TO THE
 EXISTING FS LINE* THIS IS OR AT LEAST SHOULD BE PART OF
 THE EXISTING FIRE SPRINKLER SYSTEM AT THE EXISTING
 SERVICE LOCATION, HOVER NOTE SHOULD INDICATE NOT ONLY
 THE METALLIC COLD WATER LINE , BUT ALSO THE FIRE
 SPRINKLER LINE.
  
 17) NOTE: PLEASE SEE FBC 2004 11-4.28.2 AND
 11-4.28.3(4) FOR ALL AUDIBLE AND VISUAL DEVICES. PLEASE
 SEE 11-4.28.1 FOR LOCATION REQUIREMENTS. PLEASE BE SURE
 FA PLANS INDICATE ALL THE MINIMUM LEVELS PER ADA AND
 PLACES NOTES ALSO FOR FBC SECTIONS AS GIVEN. PLEASE SEE
 THIS IS THE SAME NOTE AND THE RESPONSE LETTER ACTUALLY
 DOES NOT CONTAIN ANY WRITTEN RESPONSE TO THIS? PLEASE
 SEE THAT THE ONLY REVISED SHEET INSERTED IN THE FA
 SHEETS IS THAT OF SHEET FA0.1.
 PLEASE SEE SECTION 11-4.28.1 OF THE FBC 2004 FOR
 LOCATIONS WHICH INCLUDE ALL COMMON AND ACCESSIBLE AREAS
 FOR THESE TYPES OF DEVICES. THE MINIMUM LEVELS FOR ADA
 COMPLIANCE ARE 75CD, MANY SHOWN AS 15CD.
 PLEASE ADJUST FA SHEETS FOR THESE LOCATIONS.
  
 18) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENT FOR CODE COMPLIANCE AS THIS IS ONLY
 GIVEN AS A NOTICE AT THIS TIME.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
2007-04-19 16:35:021-ROLL IN ELEC FOR REVIEW

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-11-28 Cont ID  
Sent By dpalmer Date 2006-11-28 Time 07:52 Rev Time 0.00
Received By dpalmer Date 2006-11-26 Time 15:02 Sent To  
Notes
2006-11-28 07:52:39*** UNSAT ***
  
 1) NOTE: PLEASE BE PLANS REFLECT THE FOLLOWING CODES AT
 A MINIMUM.
 2002 NFPA-70, 2003 NFPA-101, 2002 NFPA-72 AND THE
 ELECTRICAL PLANS SHOULD ALSO STATE THE 2004 FBC.
  
 2) NOTE: PLEASE SEE FBC CHAPTER 13. PLEASE SEE
 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE THERE ARE MANY AREAS WHICH INDICATE SOME
 SORT OF SYMBOL NEXT TO SWITCH, HOWEVER AS THIS SYMBOL
 IS NOT LOCATED ON THE SYMBOL SCHEDULE IT IS UNCLEAR
 WHAT THIS IS FOR REVIEW OF COMPLIANCE WITH ANY LIGHTING
 CONTROL REQUIREMENTS.
 PLEASE SEE MANY OTHER AREAS WHICH A SWITCH IS BEING
 SHOWN AND THE CIRCUIT IS NOT LABELED GOING THROUGH THE
 LIGHTING CONTROL PANEL.
 ** PLEASE KNOW THE LIGHTING CONTROL PANEL WILL BE NOTED
 AS "LCP" IN THE NOTES FORM HERE OUT.
 PLEASE SPECIFY THE SYSTEM WHICH IS BEING INSTALLED OR
 SPECIFIED FOR THE SCOPE OF WORK AND INTENDED
 CONTROL.110.3, 90.7
 PLEASE SEE EACH SPACE SHALL CONTAIN A DEVICE WHICH OVER
 -RIDES A SYSTEM, OR PROVIDES CONTROLS MEANS AS OTHER
 METHODS LISTED IN 13-415.1.ABC.1.1, .1.2.
 PLEASE SEE THERE ARE SEVERAL ROOMS WHICH DO NOT
 INDICATE ANY KIND OF OVER RIDE DEVICE, OCCUPANT SENSOR
 ETC.
 PLEASE SEE THE OVER RIDE TYPE DEVICE IS ALSO REQUIRED
 TO BE LOCATED IN THE AREAS IN WHICH THE OCCUPANT CAN
 SEE THE LIGHTING BEING CONTROLLED.
 PLEASE SEE MISSING AUTO SHUT OFF OF PIT LIGHTS. PLEASE
 BE SURE THE LCP PANEL ONLY CONTROL LIGHTING WHICH
 SHOULD NOT BE TURNED OFF, :IE: PLEASE CIRCUIT WHICH ARE
 SHOWN BEING WIRED TO THE LCP'S , HOWEVER PLEASE SEE
 THERE ARE ALSO EMERGENCY LIGHTING ON THOSE SAME
 CIRCUITS. PLEASE PROVIDE DETAIL ON THE LCP
 RISER/DIAGRAM WHERE ALL EXIT AND EMERGENCY LIGHTING IS
 CIRCUITED AHEAD OF THE LOCAL LIGHTING CONTROL DEVICES.
 PLEASE SEE MISSING PERFORMANCE CALCULATIONS FOR ALL
 AREAS. PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED DO
 NOT INDICATE ANY EXTERIOR LIGHTING; HOWEVER THE PLANS
 INDICATE LIGHTING IN MANY LOCATIONS.
 PLEASE SEE ENERGY CALCULATIONS DO NOT INDICATE THE
 REQUIRED AUTOMATED CONTROLS WHERE LISTING TYPE OF
 CONTROL.
 PLEASE SEE 13-415.1.AB.1, 13-415.2, 13-415.2.ABC.1,
 13-415.2.ABC.1.3.
 PLEASE SEE FBC CHAPTER 13, AS THERE ARE MANY AREAS AND
 ITEMS AS NOTED ABOVE WHICH NEEDS TO BE ADJUSTED.
  
 3) NOTE: PLEASE CORRELATE THE SQ FT ON PERMIT
 APPLICATION WITH THAT OF THE PLANS.
  
 4) NOTE: PLEASE SEE MISSING NORMAL AND EMERGENCY
 PHOTO-METRICS IN ALL EGRESS PATH AREAS. PLEASE SEE
 MISSING STAIR WAYS. PLEASE SEE NFPA-101 2003, 7.8.1.3,
 AND 7.9.2.2.
 A) STAIRS REQUIRE A MINIMUM OF 10FT CANDLES UNDER
 NORMAL AND 1FT CANDLE UNDER EMERGENCY.
 B) PLEASE SEE THIS IS FOR ALL EXIT STAIRS TO THE PUBLIC
 RIGHT OF WAY FOR EGRESS PATHS.
  
 5) NOTE: PLEASE SEE NFPA-101 7.8, 7.9, WHICH REQUIRES
 LIGHTING AND EMERGENCY LIGHTING TO THE PUBLIC RIGHT OF
 WAY. PLEASE SEE ALL EXTERIOR STAIRS INCLUDING LARGE AND
 SMALLER STAIRS AREAS WILL REQUIRE SOME SORT OF BATTERY
 BACK UP FIXTURES WHICH WILL PROVIDE THE MINIMUM FT
 CANDLES TO THE PUBLIC RIGHT OF WAY, OUT AND AWAY FROM
 THE BUILDING.
 PLEASE SEE THIS INCLUDES RAMP AREAS.
  
 5) NOTE: PLEASE SEE ELEVATOR EQUIPMENT ROOMS WHICH WILL
 REQUIRE A CHANGE IN FIXTURE TYPE OR AN ADDITIONAL
 FIXTURE. PLEASE SEE 700.16.
  
 6) NOTE: PLEASE SEE 110.26, 408.7, AND 240.24D WHICH DO
 NOT PERMIT ELECTRICAL PANELS TO BE LOCATED IN STORAGE
 ROOMS OR CLOSETS. PLEASE ADJUST LOCATIONS OF EQUIPMENT
 OR CREATE DEDICATED ELECTRICAL ROOMS/CLOSETS AS DONE IN
 SOME OTHER LOCATIONS ON PLANS.
 *** PLEASE SEE ACCESS TO ELECTRICAL EQUIPMENT SHOULD
 ALSO NOT BE THROUGH STORAGE ROOMS. EQUIPMENT SHOULD BE
 LOCATED IN A MANNER WHICH READY ACCESS CAN BE GRANTED
 AND QUITE OFTEN STORAGE ROOMS BECOME A LOCATION WHERE
 THINGS IMPEDE ACCESS AS NEEDED.
  
 7) NOTE: PLEASE SEE POSSIBLE BUILDING OR FIRE REVIEW
 COMMENTS WITH RESPECT TO STAIRWAY #4.IT IS UNCLEAR AS
 THIS SEEMS TO EXIT OCCUPANTS BACK INTO THE BUILDING.
 THERE ARE SOME INSTANCES WHERE THIS IS PERMITTED;
 HOWEVER DEPENDING ON POSSIBLE COMMENTS THIS WILL AFFECT
 THE ELECTRICAL PLANS AND LAYOUT IF ANY CHANGES ARE
 NEEDED. THIS IS ONLY A NOTE AT THIS TIME.
  
 8) NOTE: PLEASE BE SURE ALL FIXTURES ARE IDENTIFIED BY
 THEIR FIXTURE DESIGNATIONS. PLEASE SEE SOME FIXTURES
 ARE MISSING THIS.
 PLEASE SEE OTHER FIXTURES WHICH ARE INDICATED AS "UT",
 HOWEVER THIS FIXTURE IS NOT LOCATED ON FIXTURE
 SCHEDULED AND THE SYMBOL AROUND THE FIXTURE IS NOT
 SIMILAR AND COULD NOT BE LOCATE ANY OTHER DESIGNATION
 OR REFERENCE ON PLANS. PLEASE CLARIFY THIS?
 FBC 106.1.2 ADMIN SECTION.
  
 9) NOTE: PLEASE SEE THERE ARE SEVERAL CIRCUITS ON PLANS
 WHICH DO NOT SEEM TO BE SHOWN GOING THROUGH ANY OF THE
 LCP'S?
 PLEASE PROVIDE A COMPLETE LCP SCHEDULE FOR ALL
 CIRCUITS.
 13-415.1.ABC.1.1, .1.2, AND .1.3.
  
 10) NOTE: PLEASE PROVIDE MORE INFORMATION ON MAIN 1 OF
 2. PLEASE INDICATE SIZE, VOLTAGEETC.
 230, 240, 110.3, 90.7
 FBC 106.1.2
  
 11) NOTE: PLEASE SEE MISSING AN EQUIPMENT GROUNDING
 CONDUCTOR FROM THIS MAIN 1 OF 2 TO THE EXISTING MDP
 PANEL.
 IT IS NOTED THAT THE SYSTEM SHALL SEPARATE ALL NEUTRAL
 AND GROUND CONNECTIONS AT THE EXISTING MDP. 250.24B,
 250.110, 250.122
 FBC 106.1.2 ADMIN SECTION.
  
 12) NOTE: PLEASE SEE AN "EQUIPMENT GROUNDING CONDUCTOR"
 IS BEING SHOWN FROM THE FPL TRANSFORMER TO THE NEW MAIN
 2 OF 2? PLEASE SEE 250.6, AND 250.24 AS EQUIPMENT
 GROUNDING CONDUCTORS ARE ONLY INSTALLED AFTER THE FIRST
 MEANS OF DISCONNECT.
  
 13) NOTE: PLEASE INDICATE ALL CONTINUOUS LOADS AND THE
 LARGEST MOTOR LOADS ON EACH PANEL AND SERVICE AT 125%.
 PLEASE SEE NO LOAD CALCULATIONS OR LOAD SUMMARY COULD
 BE LOCATED.
 220.3, 220.10, 220.11, 220.13, 215.3 AND 230.42 ETC.
 FBC ADMIN SECTION 106.3.5.1.2
  
 14) NOTE: PLEASE SEE PANEL "L2 AA" IS BEING SHOWN FED
 FROM MULTIPLE PANELS. PLEASE SEE THIS PANEL IS SHOWN
 FED FROM BOTH "DP2A" AND "DP2B". PLEASE CORRELATE AND
 ADJUST.
 PLEASE SEE RISER AS THE RISER SHOWS THIS PANEL ONLY
 BEING FED FROM DP2A.
 FBC 106.1.2.
  
 15) NOTE: PLEASE SEE PANEL "DP1B" WHICH INDICATES A
 FEED TO A PANEL "L1BB" , YET NO PANEL SCHEDULE COULD BE
 LOCATED ON THE PLANS SUBMITTED.
 FBC 106.1.2
  
 16) NOTE: PLEASE SEE A PANEL SCHEDULE FOR "L3AB" WAS
 SUBMITTED ON PANEL SCHEDULES, HOWEVER COULD NOT LOCATED
 ON ANY OTHER OF THE PANEL SCHEDULE WHERE THIS IS FED
 FROM OR COULD NOT LOCATED THIS ON THE ELECTRICAL RISER
 DIAGRAM EITHER.PLEASE CLARIFY.
 FBC 106.1.2, 106.3.5.1.2
  
 17) NOTE: PLEASE BE SURE TO GO THROUGH PLANS AND
 CORRELATE ALL PANELS SHOWN ON PLANS WITH THE RISER
 DIAGRAM AND PANEL SCHEDULES SUBMITTED.
 FBC 106.1.2, 106.3.5.1.2
  
 18) NOTE: PLEASE SEE INDICATE ANY FIRE SPRINKLER WATER
 LINE AS PART OF THE GROUNDING ELECTRODE SYSTEM.
 250.106
  
 19) NOTE: PLEASE SEE FBC 2004 11-4.28.2 AND
 11-4.28.3(4) FOR ALL AUDIBLE AND VISUAL DEVICES. PLEASE
 SEE 11-4.28.1 FOR LOCATION REQUIREMENTS. PLEASE BE SURE
 FA PLANS INDICATE ALL THE MINIMUM LEVELS PER ADA AND
 PLACES NOTES ALSO FOR FBC SECTIONS AS GIVEN.
  
 ** PLEASE KNOW AS THERE ARE MANY ITEMS NOT SHOWN OR
 MISSING, THERE MAY BE COMMENTS ON THE FOLLOWING
 REVIEW.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2006-11-27 07:00:34REVIEW IN PROGRESS
2006-11-26 15:03:26ONE ROLL INELECTRICALFOR REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2007-08-29 Cont ID  
Sent By rchokshi Date 2007-08-29 Time 09:14 Rev Time 0.00
Received By rchokshi Date 2007-08-29 Time 09:13 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2007-08-16 Cont ID  
Sent By rchokshi Date 2007-08-16 Time 13:37 Rev Time 0.00
Received By rchokshi Date 2007-08-16 Time 13:09 Sent To  
Notes
2007-08-16 13:37:34FAILED FOR FOLLOWING REASONS:
  
 WE HAVE A NEW FOLLOWING REQUIREMENTS, PLEASE RESPOND
 THIS TOO.
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
 THIS IS KIND OF A NEW REQUIREMENTS. YOU MAY HAVE
 ALREADY APPLIED FOR NOI. JUST SEND US A COPY NOITHAT
 YOU APPLY AT FDEP, NPDES STORM WATER SECTION,.
  
 2. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 3. PLEASE SHOW ON CALCULATION HOW DID YOU DETERMINE
 FIRST FLOOR ELEVATION, CENTER LINE OF ROAD ELEVATION ,
 SIDEWALK ELEVATION. YOU ALSOMUST MEET FLOOD ZONE OF
 THAT AREA, FL BLDG CODE. PLEASE SHOW ON CALS WHAT
 CRITERIA YOU USED IN DETERMINING FIRST FLOOR ELEVATION
 LIKE 5 YEAR,10 YEAR, 25 YEAR, 100 YEAR FLOOD, PLEASE
 SHOW ALL THESE IN CALCULATIONS,YOU NEED TO USE THE
 WORST CASE TO GET SAFER DESIGN FOR FIRST FLOOR
 ELEVATION. THEN SHOW THE RESULT FROM CALCULATIONS THAT
 FIRST FLOOR ELEVATION IS HIGH ENOUGH.
 4. PLEASE PROVIDE A COPY OF SFWMD PERMIT, & RESUBMIT
 GEOTECH REPORT AGAIN.
 5.IN YOUR STORM WATER QUALITY CALCULATIONS, YOU DID NOT
 USE THE WORST CASE FOR SAFER DESIGN, 2.5" CRITERIA,
 YOU SAID" PER CARLOSDEROJA ONLY 1" RUNOFF..."
 WELL,YOU NEED TO PROVIDE A LETTER FROM CARLOS FOR
 THAT REASONOTHERWISEYOU NEED TO USE 2.5" CRITERIA
 FOR WATER QUALITY CALS.
 6.HOW DIDYOU CONNECT TO THE STORM WATER PIPES IN YOUR
 SITE? ITS DETAILS.PLEASE SHOW ALL STORM WATER PIPES
 AROUND YOUR SITE SO, WE CANSEE THE BEST STORM WATER
 PIPE TO CONNECT WITH THE STORM WATERFROM ALL OTHER
 STORM WATER PIPES. PLEASE SHOW DETAIL OF THE CONTROL
 STRUCTURES WITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC DID YOU USE EXFILTRATION TRENCH ?
 7.POLLUTION PREVENTION: YOUR PLANS SHOW SILT FENCE
 PARTIALLY AT SOME LOCATIONS NOTAROUND THE WHOLE SITE.
 SILT FENCE MUST BE COMPLETELY AROUND THE SITE.
 8. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVE
 9. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS.
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2007-05-10 Cont ID  
Sent By rchokshi Date 2007-05-10 Time 16:12 Rev Time 0.00
Received By rchokshi Date 2007-05-10 Time 15:31 Sent To  
Notes
2007-05-10 16:12:42 
 FAILED FOR FOLLOWING REASONS: VERY IMPORTANT,PLEASE
 RESPOND EACH ITEM OF THE LINE#.
  
 1. PLEASE SHOW ON DRAWINGS ALL STANDARDS NOTES OF CITY
 OF WPB FOR SIDEWALK WIDTH , ITS SLOPE, DRIVEWAY,
 PARKING, HANDICAP PARKING, PAINTPER CITY CODES
 ETC.YOU CAN GET A CD FROM 100045TH STREET ENG.,, MUST
 MEETALSO ADA,,STANDARDS AND PLEASE SHOW ON THE
 DRAWINGS.
 2. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 3. PLEASE SHOW ON DRAWINGS FIRST FLOOR ELEVATION,
 CENTER LINE OF ROAD ELEVATION , SIDEWALK ELEVATION MUST
 MEET FLOOD ZONE OF THAT AREA & FL BLDG CODE.WHAT
 CRITERIA YOU USED IN DETERMINING FIRST FLOOR ELEVATION
 LIKE 5 YEAR,10 YEAR, 25 YEAR, 100 YEAR FLOOD, PLEASE
 SHOW ALL THESE CALCULATIONS,YOU NEED TO USE THE WORST
 CASE TO GET SAFER DESIGN FOR FIRST FLOOR ELEVATION.
 PLEASE SHOW ON THE DRAWINGSTHAT ON FIRST FLOOR
 ELEVATION.
 4. PLEASE PROVIDE A COPY OF SFWMD PERMIT, & GEOTECH
 REPORT AGAIN.
 5.IN YOUR STORM WATER QUALITY CALCULATIONS, WHY YOU DID
 NOT USE THE WORST CASE FOR SAFER DESIGN, 2.5" CRITERIA,
 YOU CALCULATED RETENTION VOLUME 0.45 ACRE-FEET ,
 INSTEAD YOU USED .07 ACRE-FEET. TO DETERMINE THE LENGTH
 OF EXFILTRATION TRENCH,WOULD HAVE BEEN LONGER AND
 SAFER IF YOU USED 0.45 ACRE-FEET.. PLEASE EXPLAIN.
 PLEASE GET A COPY OF THIS CRITERIA FROM SFWMD FOR
 DETAIL CALS & METHODS.
 6. PLEASE PROVIDE ON DRAWINGS THE TOTAL SITE AREA,
 PERVIOUS AREA, GREEN, LAKES, ETC,IMPERVIOUS
 AREA,BUILDING,PARKING LOT,SIDEWALK ETC.
 7. HOW DIDYOU CONNECT TO THE STORM WATER PIPES IN
 YOUR SITE? ITS DETAILS.PLEASE SHOW ALL STORM WATER
 PIPES AROUND YOUR SITE SO, WE CANSEE THE BEST STORM
 WATER PIPE TO CONNECT WITH THE STORM WATERFROM ALL
 OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE
 CONTROL STRUCTURES WITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC DID YOU USE EXFILTRATION TRENCH ?
 8. POLLUTION PREVENTION DETAILS,CLOTHES USED FOR SILT
 ETC., PLANS SHOWING SILT FENCE AROUND THE SITE
 9. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVE
 10. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS.
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2006-11-18 Cont ID  
Sent By rchokshi Date 2006-11-18 Time 10:22 Rev Time 0.00
Received By rchokshi Date 2006-11-18 Time 10:22 Sent To  
Notes
2006-11-18 10:22:18WE DID NOT RECEIVED CIVIL PLANS FOR REVIEW. SO MAKE
 SURE YOU HAVE INCLUDED THE FOLLOWING INFO IN YOUR
 SUBMITTAL TO EXPEDITE THE PERMITTING PROCESS.
 1. PLEASE PROVIDE DRAINAGE/STORM WATERPLANS. LIKE
 SHEET C-1, C-2, ETC, JUST A SUGESTION
 2. PLEASE SHOW ALL STANDARDS NOTES OF CITY OF WPB ON
 DRAWINGSFOR SIDEWALK WIDTH , ITS SLOPE, DRIVEWAY,
 PARKING, HANDICAP PARKING, PAINTPER CITY CODES ETC.,,
 MUST MEET PER ADA,,ETC.,
 3. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 4. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD ,
 SIDEWALK ELEVATION MUST MEET FL BLDG CODE,PLEASE SHOW
 ON THE DRAWINGS THAT YOU MEET FL BLDG CODES.
 5. PLEASE PROVIDE A COPY OF SFWMD PERMIT, & GEOTECH
 REPORT
 6.PLEASE SHOW STORM WATER CALCULATIONS, WHAT CRITERIA
 YOU ASSUMEDFOR RUNOFF CAL.,, LIKE 1" OVER ENTIRE SITE
 OR2.5"CRITERIA, ?PERVIOUS AREA, LIKE GREEN,
 LAKES, ETC,IMPERVIOUS AREA CAL.,
 7. WHAT IS THE SITE AREA, YOU ARE DEVELOPING FOR THIS
 PROJECT ONLY ? SO, WE CAN CHECK PERVIOUS, IMPERVIOUS
 CAL.
 8. HOW DIDYOU CONNECT TO THE STORM WATER PIPES IN
 YOUR SITE? ITS DETAILS.PLEASE SHOW ALL STORM WATER
 PIPES AROUND YOUR SITE SO, WE CANSEE THE BEST STORM
 WATER PIPE TO CONNECT WITH THE STORM WATERFROM ALL
 OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE
 CONTROL STRUCTURES WITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC DID YOU USE EXFILTRATION TRENCH ?
 9. POLLUTION PREVENTION DETAILS,CLOTHES USED FOR SILT
 ETC., PLANS SHOWING SILT FENCE AROUND THE SITE
 10. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVE
 11. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 9 Status P Date 2009-04-14 Cont ID  
Sent By mawillia Date 2009-04-14 Time 16:10 Rev Time 0.00
Received By mawillia Date 2009-04-14 Time 15:40 Sent To  
Notes
2009-04-14 16:00:06****REVISION APPROVED*****
  
 REVISED PLAN SHEETS A3.1.1, E2.1.1, E2.1.2, E.2.2.1,
 AND E2.2.2 WERE STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 8 Status F Date 2009-02-24 Cont ID  
Sent By mawillia Date 2009-02-24 Time 13:24 Rev Time 0.00
Received By mawillia Date 2009-02-24 Time 12:33 Sent To  
Notes
2009-02-24 12:41:52*****DENIED*****
  
 1. THE REVISED PLANS SHALL BE SUBMITTED UNDER THE THE
 FIRE SPRINKLER PERMIT (PERMIT # 08060337).
  
 2. THE NUMERICAL ADDRESS SHOWN IN THE TITLE BLOCK OF
 THE PLANS SHOULD BE REFLECTED AS 821 NORTH FLAGLER
 DRIVE.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status P Date 2009-02-17 Cont ID  
Sent By mawillia Date 2009-02-17 Time 12:43 Rev Time 0.00
Received By mawillia Date 2009-02-17 Time 11:28 Sent To  
Notes
2009-02-17 12:43:55*****REVISIONS #7 (07/0708) & #13 (10/02/08) APPROVED
  
  
 REVISED PLAN SHEETS FA 2.1.2, FA 2.2.2, AND FA 2.3 WERE
 STAMPED, INITIALED AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2008-07-18 Cont ID  
Sent By mwennerg Date 2008-07-18 Time 13:41 Rev Time 0.00
Received By mwennerg Date 2008-07-18 Time 13:41 Sent To  
Notes
2008-07-18 13:42:15REVISION DATED 4/14/08

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2007-12-13 Cont ID  
Sent By mawillia Date 2007-12-13 Time 17:42 Rev Time 0.00
Received By mawillia Date 2007-12-13 Time 17:39 Sent To  
Notes
2007-12-13 17:42:23*****APPROVED*****
  
 PLAN SHEETS LS2.1.0 THRU LS2.3.0, A3.1.1, FA0.1 THRU
 FA2.4.2, AND FS0.1 THRU FS2.3.2 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-11-19 Cont ID  
Sent By mawillia Date 2007-11-19 Time 12:47 Rev Time 0.00
Received By mawillia Date 2007-11-19 Time 11:36 Sent To  
Notes
2007-11-19 11:48:18*****PROVISO*****
  
 * OLD COMMENTS:ALL COMMENTS FROM THE PREVIOUS FIRE
 PLAN REVIEWS HAVE BEEN ADDRESSED;HOWEVER, THE
 APPROPIATE PLAN SHEETS TO BE FIRE-STAMPED WHEN THE
 BELOW COMMENT AS WELL AS ANY OTHER CONCERNS OF THE
 OTHER PLAN REVIEWERS HAVE BENN SATISFIED
  
 * NEW COMMENT:THE NUMERICAL ADDRESS FOR THE BUILDING
 IS 821 INSTEAD OF 807 AS LISTED ON THE SUBMITTED PLAN
 SHEETS.
  
 A.)THE CORRECT/ACTUALADDRESS OF THE PROJECT SITE
 SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED PLAN
 SHEET
  
 B.)ON THE APPROPIATE EXTERIOR ELEVATION, DISPLAY/SHOW
 THE NUMERICAL ADDRESS SO THAT IT DISTINGUISHABLE FROM
 THE OTHER CAMPUS BUILDINGS
  
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2007-09-14 Cont ID  
Sent By mawillia Date 2007-09-14 Time 18:58 Rev Time 0.00
Received By mawillia Date 2007-09-14 Time 18:33 Sent To  
Notes
2007-09-14 18:58:24*****DENIED*****
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED:
 .
 09. ALL FIRE DOORS AND WINDOWS SHALL COMPLY WITH NFPA
 80.PANIC HARDWARE OR FIRE EXIT PANIC HARDWARE SHALL
 REQUIRED ON ALL EXIT DOORS THAT SERVE AND OCCUPANT LOAD
 OF 100 OR MORE PERSONS.ADD COMMENT TO AN APPROPIATE
 PLAN SHEET
  
  
 14.INTERIOR WALL AND CEILING FINISH CLASSIFICATION
 SHALL BE CLASS A OR CLASS B IN GENERAL ASSEMBLY AREAS
 HAVING AN OCCUPANT LOAD OF MORE THAN 300 AND SHALL BE
 CLASS A, CLASS B, OR CLASS C IN ASSEMBLY AREAS HAVING
 OCCUPANTS OF 300 OR FEWER.SPECIFY
  
 15.ELEVATORS TO COMPLY WITH ASME A17.1; WARNING SIGNS
 WILL BE REQUIRED IN ELEVATOR LOBBY.THE ELEVATORS (OR
 AT LEAST ONE ELEVATOR) SHOULD BE ACCESSIBLE FOR AN
 EMERGENCY MEDICAL STRETCHER OR GOURNEY.ADD COMMENT TO
 AN APPROPIATE PLAN SHEET
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE (ON THE PLANS) EACH COMMENT
 WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-05-21 Cont ID  
Sent By mawillia Date 2007-05-21 Time 14:38 Rev Time 0.00
Received By mawillia Date 2007-05-21 Time 13:59 Sent To  
Notes
2007-05-21 14:38:18*****DENIED*****
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED:
  
  
 01.THE ADDRESS OF WHERE THE SCOPE OF WORK WILL BE
 CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED
 PLAN SHEET.
 02.NFPA 101- 2003 EDITION AND THE FLORIDA FIRE
 PREVENTION CODE - 2004 EDITION SHALL BE REFERENCED. 03.
 STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. 04.
 CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 HINDER OR INTERFERE WITH EMERGENCY RESPONSE ACCESS TO
 THE SAID PROPERTY OR THE VICINITY THEREOF (INCLUDING
 FIRE LANES).
 07. KNOX BOX FOR THE BUILDING WILL BE REQUIRED. CONTACT
 THE FIRE PREVENTION BUREAU AT (561) 804-4724 FOR
 APPLICATIONS.
 09. ALL FIRE DOORS AND WINDOWS SHALL COMPLY WITH NFPA
 80.PANIC HARDWARE OR FIRE EXIT PANIC HARDWARE SHALL
 REQUIRED ON ALL EXIT DOORS THAT SERVE AND OCCUPANT LOAD
 OF 100 OR MORE PERSONS.
 10. DELAYED-EGRESS LOCKS OR ACCESS-CONTROLLED EGRESS
 DOORS SHALL COMPLY NFPA 101, CH. 7.2.1.6
 11.EXIT/EGRESS FROM THE BUILDING AND/OR FLOOR SHALL
 COMPLY WITH APPLICABLE FIRE AND BUILDING CODES (SEE
 BUILDING PLAN REVIEW COMMENTS).
 12.NO EQUIPMENT SHALL BE ALLOWED INSIDE OR PENETRATE
 EXIT ENCLOSURES UNLESS THE EXCEPTIONS OF NFPA 101,
 7.1.3.2.1. (6) ARE MET.
 14.INTERIOR WALL AND CEILING FINISH CLASSIFICATION
 SHALL BE CLASS A OR CLASS B IN GENERAL ASSEMBLY AREAS
 HAVING AN OCCUPANT LOAD OF MORE THAN 300 AND SHALL BE
 CLASS A, CLASS B, OR CLASS C IN ASSEMBLY AREAS HAVING
 OCCUPANTS OF 300 OR FEWER.
 15.ELEVATORS TO COMPLY WITH ASME A17.1; WARNING SIGNS
 WILL BE REQUIRED IN ELEVATOR LOBBY.THE ELEVATORS (OR
 AT LEAST ONE ELEVATOR) SHOULD BE ACCESSIBLE FOR AN
 EMERGENCY MEDICAL STRETCHER OR GOURNEY.
 17.IF SO EQUIPPED WITH A COOKING HOOD, SEPARATE PLANS
 AND PERMIT WILL BE REQUIRED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE (ON THE PLANS) EACH COMMENT
 WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-02-08 Cont ID  
Sent By mawillia Date 2007-02-08 Time 13:22 Rev Time 0.00
Received By mawillia Date 2007-02-08 Time 13:22 Sent To  
Notes
2007-02-08 15:28:56*****DENIED*****
  
  
 01.THE ADDRESS OF WHERE THE SCOPE OF WORK WILL BE
 CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED
 PLAN SHEET.
 02.NFPA 101- 2003 EDITION AND THE FLORIDA FIRE
 PREVENTION CODE - 2004 EDITION SHALL BE REFERENCED. 03.
 STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. 04.
 CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 HINDER OR INTERFERE WITH EMERGENCY RESPONSE ACCESS TO
 THE SAID PROPERTY OR THE VICINITY THEREOF (INCLUDING
 FIRE LANES).
 05.FIRE DEPARTMENT CONNECTIONS (FDC) SHALLBE
 POSITIONED AS TO NOT BEING BLOCKED BY LANDSCAPING,
 STORAGE, VESSELS, AND SUPPLIES.PROPER CLEARANCES ARE
 TO BE MAINTAINED AT ALL TIMES.
 06.KNOXLOCKING CAPS ARE REQUIRED FOR NEW FIRE
 DEPARTMENT CONNECTIONS.
 07. KNOX BOX FOR THE BUILDING WILL BE REQUIRED. CONTACT
 THE FIRE PREVENTION BUREAU AT (561) 804-4724 FOR
 APPLICATIONS.
 08.THE FIRE SPRINKLER SYSTEM IN CONJUNCTION WITH THE
 FIRE ALARM SYSTEM SHALL BE MONITORED BY A LICENSED UL
 LISTED CENTRAL STATION APPROVED FOR CENTRAL STATION
 SERVICE.
 09. ALL FIRE DOORS AND WINDOWS SHALL COMPLY WITH NFPA
 80.PANIC HARDWARE OR FIRE EXIT PANIC HARDWARE SHALL
 REQUIRED ON ALL EXIT DOORS THAT SERVE AND OCCUPANT LOAD
 OF 100 OR MORE PERSONS.
 10. DELAYED-EGRESS LOCKS OR ACCESS-CONTROLLED EGRESS
 DOORS SHALL COMPLY NFPA 101, CH. 7.2.1.6
 11.EXIT/EGRESS FROM THE BUILDING AND/OR FLOOR SHALL
 COMPLY WITH APPLICABLE FIRE AND BUILDING CODES (SEE
 BUILDING PLAN REVIEW COMMENTS).
 12.NO EQUIPMENT SHALL BE ALLOWED INSIDE OR PENETRATE
 EXIT ENCLOSURES UNLESS THE EXCEPTIONS OF NFPA 101,
 7.1.3.2.1. (6) ARE MET.
 13. PLEASE PROVIDE PRESCRIPTIVE STRENGHT REQUIREMENTS
 FOR ALL NEW HANDRAILS AND GUARDRAILS (INCLUDING
 EMERGENCY OVERFLOW AREA).
 14.INTERIOR WALL AND CEILING FINISH CLASSIFICATION
 SHALL BE CLASS A OR CLASS B IN GENERAL ASSEMBLY AREAS
 HAVING AN OCCUPANT LOAD OF MORE THAN 300 AND SHALL BE
 CLASS A, CLASS B, OR CLASS C IN ASSEMBLY AREAS HAVING
 OCCUPANTS OF 300 OR FEWER.
 15.ELEVATORS TO COMPLY WITH ASME A17.1; WARNING SIGNS
 WILL BE REQUIRED IN ELEVATOR LOBBY.THE ELEVATORS (OR
 AT LEAST ONE ELEVATOR) SHOULD BE ACCESSIBLE FOR AN
 EMERGENCY MEDICAL STRETCHER OR GOURNEY.
 16.DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS.AMEND
 SHEET FA0.1, FIRE ALARM NOTE #17.
 17.IF SO EQUIPPED WITH A COOKING HOOD, SEPARATE PLANS
 AND PERMIT WILL BE REQUIRED.
 18.HOW WILL EMISSIONS FROM VEHICLES IN THE PARKING
 GARAGE BE CONTROLLED OR MANAGED AS TO NOT COMMUNICATE
 TO OTHER AREAS OF THE STRUCTURE?
  
  
 TO EXPEIDITE THE PLAN REVIEW PROCESS, INCLUDE A
 RESPONSE LETTER INDICATING HOW/WHERE EACH ITEM WAS
 ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 32 Status N Date 2009-07-31 Cont ID  
Sent By btrobaug Date 2009-07-31 Time 13:48 Rev Time 0.00
Received By btrobaug Date 2009-07-31 Time 13:47 Sent To B
Notes
2009-07-31 13:48:07 
  
 TO JIM W./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 31 Status N Date 2009-07-10 Cont ID  
Sent By jgomez Date 2009-07-10 Time 09:25 Rev Time 0.00
Received By jgomez Date 2009-07-10 Time 09:25 Sent To  
Notes
2009-07-10 09:26:03SENT TO WITMER'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 30 Status   Date 2009-07-31 Cont ID  
Sent By btrobaug Date 2009-06-12 Time 13:46 Rev Time 0.00
Received By btrobaug Date 2009-06-12 Time 11:10 Sent To  
Notes
2009-06-12 11:11:04SENT TO KS DESK (REVISION)

Review Stop I INCOMING/PROCESSING
Rev No 29 Status N Date 2009-06-02 Cont ID  
Sent By btrobaug Date 2009-06-02 Time 15:08 Rev Time 0.00
Received By btrobaug Date 2009-06-02 Time 15:08 Sent To B
Notes
2009-06-02 15:08:45TO JIM

Review Stop I INCOMING/PROCESSING
Rev No 28 Status N Date 2009-05-21 Cont ID  
Sent By dpalmer Date 2009-05-21 Time 11:24 Rev Time 0.00
Received By dpalmer Date 2009-05-21 Time 11:24 Sent To  
Notes
2009-05-21 11:25:09TO RR DESK

Review Stop I INCOMING/PROCESSING
Rev No 27 Status N Date   Cont ID  
Sent By   Date 2009-05-21 Time   Rev Time 0.00
Received By jgomez Date 2009-05-19 Time 11:58 Sent To  
Notes
2009-05-19 11:59:05TO RON'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 26 Status N Date   Cont ID  
Sent By   Date 2009-05-13 Time   Rev Time 0.00
Received By jwitmer Date 2009-05-13 Time 08:34 Sent To Z
Notes
2009-05-13 08:35:31INCOMING TO ZONING SHEET L-1 LANDSCAPE REVISION

Review Stop I INCOMING/PROCESSING
Rev No 25 Status N Date 2009-05-05 Cont ID  
Sent By dpalmer Date 2009-05-05 Time 11:24 Rev Time 0.00
Received By dpalmer Date 2009-05-05 Time 11:24 Sent To M
Notes
2009-05-05 11:24:49TO RR

Review Stop I INCOMING/PROCESSING
Rev No 24 Status N Date 2009-05-01 Cont ID  
Sent By lmartine Date 2009-05-01 Time 16:36 Rev Time 0.00
Received By lmartine Date 2009-05-01 Time 16:35 Sent To  
Notes
2009-05-01 16:35:55TO C-18

Review Stop I INCOMING/PROCESSING
Rev No 23 Status N Date 2009-04-02 Cont ID  
Sent By adarroug Date 2009-04-02 Time 11:23 Rev Time 0.00
Received By adarroug Date 2009-04-02 Time 11:23 Sent To Z
Notes
2009-04-02 11:23:42TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 22 Status N Date 2009-03-13 Cont ID  
Sent By adarroug Date 2009-03-13 Time 11:21 Rev Time 0.00
Received By adarroug Date 2009-03-13 Time 11:21 Sent To Z
Notes
2009-03-13 11:21:21TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 21 Status N Date 2009-03-09 Cont ID  
Sent By adarroug Date 2009-03-09 Time 15:13 Rev Time 0.00
Received By adarroug Date 2009-03-09 Time 15:13 Sent To  
Notes
2009-03-09 15:13:45TO "COMM" BD#43

Review Stop I INCOMING/PROCESSING
Rev No 20 Status N Date 2009-03-02 Cont ID  
Sent By adarroug Date 2009-03-02 Time 16:08 Rev Time 0.00
Received By adarroug Date 2009-03-02 Time 16:08 Sent To Z
Notes
2009-03-02 16:08:40TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 19 Status N Date 2009-02-25 Cont ID  
Sent By adarroug Date 2009-02-25 Time 15:46 Rev Time 0.00
Received By adarroug Date 2009-02-25 Time 15:46 Sent To FIRE
Notes
2009-02-25 15:46:59TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2009-02-13 Cont ID  
Sent By adarroug Date 2009-02-13 Time 16:38 Rev Time 0.00
Received By adarroug Date 2009-02-13 Time 16:38 Sent To Z
Notes
2009-02-13 16:39:39TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2009-02-09 Cont ID  
Sent By adarroug Date 2009-02-09 Time 16:48 Rev Time 0.00
Received By adarroug Date 2009-02-09 Time 16:48 Sent To FIRE
Notes
2009-02-09 16:49:12TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2009-01-21 Cont ID  
Sent By adarroug Date 2009-01-21 Time 09:56 Rev Time 0.00
Received By adarroug Date 2009-01-21 Time 09:56 Sent To  
Notes
2009-01-21 09:58:04TO "COMM" BD#8/PLANS ON RACK--3 LARGE FOLDED PLANS

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2008-10-30 Cont ID  
Sent By adarroug Date 2008-10-30 Time 14:36 Rev Time 0.00
Received By adarroug Date 2008-10-30 Time 14:36 Sent To B
Notes
2008-10-30 14:38:40TO "JWITMER" DESK/SUBMITTED

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2008-07-29 Cont ID  
Sent By adarroug Date 2008-07-29 Time 16:21 Rev Time 0.00
Received By adarroug Date 2008-07-29 Time 16:20 Sent To  
Notes
2008-07-29 16:22:56TO "COMM" BD#48

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2008-06-19 Cont ID  
Sent By adarroug Date 2008-06-19 Time 14:12 Rev Time 0.00
Received By adarroug Date 2008-06-19 Time 14:12 Sent To  
Notes
2008-06-19 14:12:14TO "COMM" BD#28

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2008-06-16 Cont ID  
Sent By adarroug Date 2008-06-16 Time 14:33 Rev Time 0.00
Received By adarroug Date 2008-06-16 Time 14:33 Sent To B
Notes
2008-06-16 14:33:41TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2008-05-30 Cont ID  
Sent By adarroug Date 2008-05-30 Time 16:57 Rev Time 0.00
Received By adarroug Date 2008-05-30 Time 16:57 Sent To B
Notes
2008-05-30 16:57:38TO "JWITMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-05-15 Cont ID  
Sent By adarroug Date 2008-05-15 Time 14:31 Rev Time 0.00
Received By adarroug Date 2008-05-15 Time 14:31 Sent To B
Notes
2008-05-15 14:32:37TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-05-01 Cont ID  
Sent By adarroug Date 2008-05-01 Time 12:47 Rev Time 0.00
Received By adarroug Date 2008-05-01 Time 12:47 Sent To B
Notes
2008-05-01 12:47:48TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-05-01 Cont ID  
Sent By adarroug Date 2008-05-01 Time 09:55 Rev Time 0.00
Received By adarroug Date 2008-05-01 Time 09:55 Sent To B
Notes
2008-05-01 09:56:14TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-04-07 Cont ID  
Sent By adarroug Date 2008-04-07 Time 15:58 Rev Time 0.00
Received By adarroug Date 2008-04-07 Time 15:58 Sent To B
Notes
2008-04-07 15:58:33TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-12-12 Cont ID  
Sent By adarroug Date 2007-12-12 Time 08:43 Rev Time 0.00
Received By adarroug Date 2007-12-12 Time 08:43 Sent To  
Notes
2007-12-12 08:44:15TO "COMM" BD#9/PLANS ON RACK-3 ROLLS

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-10-12 Cont ID  
Sent By adarroug Date 2007-10-12 Time 09:04 Rev Time 0.00
Received By adarroug Date 2007-10-12 Time 09:04 Sent To  
Notes
2007-11-02 09:24:46TO "COMM" BD#11--PLANS ON RACK/4 ROLLS
2007-10-12 09:05:11WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-08-07 Cont ID  
Sent By dpalmer Date 2007-08-07 Time 18:09 Rev Time 0.00
Received By dpalmer Date 2007-08-07 Time 18:09 Sent To  
Notes
2007-08-07 18:09:36TO COMM BOARD # 10, PLANS ON RACK.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-07-26 Cont ID  
Sent By adarroug Date 2007-07-26 Time 14:34 Rev Time 0.00
Received By adarroug Date 2007-07-26 Time 14:34 Sent To  
Notes
2007-07-26 14:34:36WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-29 Cont ID  
Sent By dpalmer Date 2007-03-29 Time 18:40 Rev Time 0.00
Received By dpalmer Date 2007-03-29 Time 18:40 Sent To  
Notes
2007-04-04 17:08:47TO COMM BOARD # 45
2007-03-29 18:40:40WAITING FOR COMM BOARD.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-02-08 Cont ID  
Sent By mawillia Date 2007-02-08 Time 13:22 Rev Time 0.00
Received By mawillia Date 2006-11-15 Time 10:52 Sent To  
Notes
2006-11-15 10:53:13TO "COMM" BD#38

Review Stop L LANDSCAPING
Rev No 4 Status P Date 2009-05-26 Cont ID  
Sent By rkussner Date 2009-05-26 Time 13:46 Rev Time 0.00
Received By rkussner Date 2009-05-26 Time 13:46 Sent To  
Notes
2009-05-26 13:51:08***LANDSCAPE REVIEW PASSED WITH 'PROVISO'***
  
 FINAL C/O WILL NOT BE ISSUED UNTIL MINOR AMENDMENT HAS
 BEEN SUBMITTED AND APPROVED BY THE PLANNING DEPARTMENT
 TO INCLUDE CHANGES OUTSIDE OF THE WORK LIMITS. ALL
 PLANS SHALL REFLECT ACCURATE INFORMATION. THE APPLICANT
 SHALL BE RESPONSIBLE TO OBTAIN ALL REQUIRED PERMITS AND
 HAVE THEM APPROVED AND FINALED PRIOR TO C/O. RAK & AMA
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462,

Review Stop L LANDSCAPING
Rev No 3 Status F Date 2009-05-14 Cont ID  
Sent By rkussner Date 2009-05-14 Time 16:08 Rev Time 0.00
Received By rkussner Date 2009-05-14 Time 16:08 Sent To  
Notes
2009-05-14 16:16:50***LANDSCAPE REVIEW FAILED***
  
 1. THE CONCRETE APRON ON 8TH STREET SHALL BE REDUCED
 DOWN TO THE WIDTH OF THE FENCE OPENING AS WAS
 ORIGINALLY SHOWN ON THE LANDSCAPE PLAN. SOD, IRRIGATION
 AND THE LIVE OAK SHALL BE PLANTED IN THAT AREA AS
 ORIGINALLY APPROVED..
  
 2. THE COCONUT TREES PLANTED ALONG THE ATLHLETIC FIELD
 SHALL BE SHOWN ON THE LANDSCAPE PLAN.
  
 3. THE WALKWAY ACROSS FROM THE ACCESS INTO THE GARAGE
 SHALL BE SHOWN AS IT EXISTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop L LANDSCAPING
Rev No 2 Status P Date 2009-04-07 Cont ID  
Sent By rkussner Date 2009-04-07 Time 09:16 Rev Time 0.00
Received By rkussner Date 2009-04-07 Time 09:16 Sent To Z
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2009-03-26 Time   Rev Time 0.00
Received By rkussner Date 2009-03-25 Time 15:04 Sent To  
Notes
2009-03-25 15:23:01***LANDSCAPE REVIEW FAILED***
  
 PLEASE PROVIDE RESPONSES TO LANDSCAPE COMMENTS IN
 WRITTEN FORMAT.
  
 1. PLEASE PROVIDE THE TABULATION NECESSARY FOR THE
 EVALUATION OF COMPLIANCE WITH ARTICLE XIV OF THE ZONING
 AND LAND DEVELOPMENT REGULATIONS, INCLUDING THE
 XERISCAPE OPTIONS.
  
 2. PLEASE ADD ONE LIVE OAK AT THE EAST END OF THE
 BUMP-OUT AND THE TWO ADDITIONAL COCONUT PALMS AT THE
 WEST END OF THE GYM AS WAS ORIGINALLY APPROVED.
  
 3. PLEASE PROVIDE THE PLANT QUANTITIES IN EACH
 LANDSCAPE BED.
  
 4. ADD FOUNDATION LANDSCAPING ALONG WALL ON SOUTH SIDE
 OF BUILDING AT WEST END AND MOVE THE SIDEWALK TO THE
 SOUTH.
  
 5. SHOW ALL FENCES ON LANDSCAPE PLAN. IF THE FENCE
 BETWEEN THE BASKETBALL COURT AND BUILDING TO REMAIN OR
 BE REMOVED?
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop M MECHANICAL (A/C)
Rev No 11 Status P Date 2009-06-01 Cont ID  
Sent By rregueir Date 2009-06-01 Time 15:13 Rev Time 0.00
Received By rregueir Date 2009-06-01 Time 14:14 Sent To PC
Notes
2009-06-01 15:12:46PAGES CA-1-1, AC-1-2, AC-2-1, AC-3-1, M2.4.1, M2.4.2
 REVISION DELTA 24
 PAGE M7.2 REVISION DELTA 21

Review Stop M MECHANICAL (A/C)
Rev No 10 Status P Date 2009-05-15 Cont ID  
Sent By rregueir Date 2009-05-15 Time 16:03 Rev Time 0.00
Received By rregueir Date 2009-05-15 Time 15:52 Sent To PC
Notes
2009-05-15 16:03:22REVISION #22 PAGES M0.1, AC-1-2, MP4-1, MP4-2, MP4-3,
 MP5-1, MP5-2

Review Stop M MECHANICAL (A/C)
Rev No 9 Status P Date 2009-05-15 Cont ID  
Sent By rregueir Date 2009-05-15 Time 08:20 Rev Time 0.00
Received By rregueir Date 2009-05-14 Time 16:28 Sent To  
Notes
2009-05-15 08:20:28AC 1-2, AC 2-2, M7.2 REVISION #20

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2009-02-21 Cont ID  
Sent By rregueir Date 2009-02-21 Time 17:00 Rev Time 0.00
Received By rregueir Date 2009-02-21 Time 17:00 Sent To  
Notes
2009-02-21 17:00:21REVISED 18 MECH PAGES.

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2008-08-11 Cont ID  
Sent By rregueir Date 2008-08-11 Time 09:33 Rev Time 0.00
Received By rregueir Date 2008-08-08 Time 16:35 Sent To  
Notes
2008-08-11 09:32:58M2.1.1 REV 7, M2.1.2 REV 6, M2.3.2 REV 8, M2.4.1 REV 5,
 M5.1 REV 8, M5.2 REV 5, M6.1 REV 5

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2008-07-09 Cont ID  
Sent By rregueir Date 2008-07-09 Time 15:37 Rev Time 0.00
Received By rregueir Date 2008-07-08 Time 14:58 Sent To  
Notes
2008-07-09 15:37:50REVIEW #: REVISIONS
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC
 CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. M2.1.1: REFRIGERANT SENSORS HAVE BEEN MOVED OUT OF
 THE MACHINERY ROOM. REFRIGERANT DETECTORS IN MACHINERY
 ROOMS SHALL BE PROVIDED AS REQUIRED BY THE FLORIDA FIRE
 PREVENTION CODE IN ACCORDANCE WITH FBCM 1105.3.
  
 2. M2.3.2: CHANGES ON THIS PAGE ARE NOT IDENTIFIED.
 PLEASE IDENTIFY THE LOCATION AND NATURE OF ALL CHANGES
 RELATED TO THIS REVISION. FBC 106.1.2, FBCB 106.4.
  
 3. M5.1: SEE COMMENT #1 ABOVE.
  
 NOTE: SOME REVISED PAGES DID NOT HAVE ANY COMMENTS.
 HOWEVER, SINCE ALL THE CHANGES ARE RELATED, ALL PAGES
 AND CALCULATIONS ASSOCIATED WITH THIS REVISION WILL NOT
 BE INCORPORATED INTO THE PERMIT SET OF PLANS UNTIL THE
 ABOVE COMMENTS ARE ADDRESSED. PLEASE CORRECT AND
 RESUBMIT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-11-17 Cont ID  
Sent By rregueir Date 2007-11-17 Time 15:30 Rev Time 0.00
Received By rregueir Date 2007-11-17 Time 15:14 Sent To  
Notes
2007-11-17 15:30:35REVISED ENERGY CALCS SUBMITTED: OK

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2007-11-13 Cont ID  
Sent By rregueir Date 2007-11-10 Time 08:50 Rev Time 0.00
Received By rregueir Date 2007-11-10 Time 08:45 Sent To M
Notes
2007-11-13 08:50:13RESUBMITTED ENERGY CALCULATIONS. THE NUMBERS ARE OK.
 HOWEVER, THE COMPLIANCE CERTIFICATION APPEARS TO HAVE
 BEEN SEALED BY THE ENGINEER OF RECORD, MIRCEA PELLA,
 BUT THE SIGNATURE USED DOES NOT MATCH THE ONE ON
 PREVIOUSLY SUBMITTED CALCULATIONS OR THE ONE ON THE
 MECHANICAL PLANS SUBMITTED FOR THIS PERMIT APPLICATION.
 THESE CALCULATIONS ARE BEING RETAINED BY THIS OFFICE
 FOR SUBMITTAL TO FBPE AS A POTENTIAL VIOLATION OF F.S.
 471 AND FAC RULE 61G15-23.002.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-08-13 Cont ID  
Sent By rregueir Date 2007-08-13 Time 10:58 Rev Time 0.00
Received By rregueir Date 2007-08-10 Time 15:01 Sent To  
Notes
2007-08-13 10:58:24***********PROVISO**************
 PROVIDE MIN. 290 CFM MECHANICAL EXHAUST FOR MACHINERY
 ROOM 103 WHEN NOT IN EMERGENCY CONDITIONS IN ACCORDANCE
 WITH FBC,M 1105.6. REVISE PGAES M2.1.1, M6.1 AND ANY
 OTHER EFFECTED PAGES, SHOWING COMPLIANCE, PRIOR TO
 ROUGH INSPECTION.
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-04-30 Cont ID  
Sent By rregueir Date 2007-04-30 Time 16:39 Rev Time 0.00
Received By rregueir Date 2007-04-30 Time 15:15 Sent To  
Notes
2007-04-30 16:39:36---------------DENIED------------------
  
 THE FIRST SET OF COMMENTS ARE NUMBERED TO CORRESPOND
 WITH PREVIOUS REVIEW COMMENTS FOR CONTINUITY:
  
 1.OK
  
 2. MACHINERY ROOM EXHAUST TERMINATES 11'6" FROM
 PROPERTY LINE AND IS ADJASCENT TO AN OPENING INTO THE
 PARKING GARAGE. THE REQUIREMENTS OF FBC,M 1105.6.1 HAVE
 NOT BEEN MET.
  
 3. OK
  
 4. WHAT PROVISIONS AHVE BEEN MADE FOR REQUIRED MINIMUM
 VENTILATION UNDER NON-EMERGENCY CONDITIONS PER FBC,M
 1105.6 AND IN QUANTITIES DETERMINED BY FBC,M 1105.6.3?
 NOTES INDICATE FAN IS ONLY ENERGIZED AND MAKE-UP AIR
 DAMPERS ARE ONLY OPEN UNDER EMERGENCY CONDITIONS.
  
 5. OK
  
 NEW COMMENTS:
  
 A. M2.3.1 AND M2.3.2: BALCONY (ROOM 316) COULD NOT BE
 FOUND ON ARCHITECTURAL FLOOR PLANS. ALSO, SEVERAL FIRE
 DAMPERS ARE SHOWN IN WALLS WHICH ARE NOT SHOWN TO BE
 RATED ON ARCHITECTURAL PLANS OR LIFE SAFETY PLANS.
 PLEASE COORDINATE DRAWINGS SHOWING LOCATION OF RATED
 BARRIERS/PARTITIONS (IF NEEDED) WHICH CORRESPONDS WITH
 DUCT PENETRATION OPEN ING PROTECTIVES (IF NEEDED).
  
 B. M2.1.1: A TWO-HOUR RATED WALL IS SHOWN BETWEEN ROOM
 100 AND 101/101A ON PAGE LS2.1.0. THERE ARE THREE
 MECHANICAL PENETRATIONS IN THIS WALL FROM AHU 1-2
 REQUIRING OPENING PROTECTIVES PER FBC,M 607.5. ALSO,
 PLEASE SHOW SIZE AND TYPE OF DIFFUSERS (IF ANY) TO BE
 USED AT THESE WALL TERMINATIONS.
  
 C. AHU 1-1: WHAT IS THE SIZE OF RETURN OPENING IN
 MACHINERY ROOM 103? ALSO, AIR FROM AHU 1-1 SHALL NOT BE
 RECIRCULATED PER FBC,M 403.2.1 AND FBC,M 1105.6.2.
  
 D. M2.1.2: AHU 1-3 CALLS FOR 6000 CFM ON SCHEDULE BUT
 SHOWS 6275 ON FLOOR PLAN. WHICH IS CORRECT?
  
 E. M2.1.2 ROOM 113: GRILL DESIGNATION SAYS "TYPICAL OF
 7" BUT PLAN SHOWS 8 GRILLS IN ROOM. PLEASE CLARIFY.
  
 F. M2.2.1 BOYS/GIRLS LOCKER ROOMS: BOTH AREAS SHOW
 RETURN AIR FROM LOCKER ROOMS. RECIRCULATION OF AIR FROM
 LOCKER ROOMS/RESTROOMS IS PROHIBITED PER FBC,M TABLE
 403.3 NOTE (B).
  
 G. M2.2.1: PLAN SHOWS A FIRE DAMPER ON TWO 1 1/4" WATER
 LINES AT VESTIBULE 201. PLEASE CLARIFY.
  
 H. AHU 2-4: PLAN SHOWS 800 CFM SUPPLY WITH 500 CFM R/A
 AND 80 CFM O.A.HOW IS THIS SYSTEM TO BE BALANCED?
  
 I. M2.2.2: R/A FROM ROOMS 229/230 DO NOT MEET THE
 EXCEPTIONS FOR BALANCED RETURN UNDER FBC,M 601.4.
 UNLESS THE TRANSFER DUCT IS DESIGNED TO 1 1/2 TIMES THE
 SQUARE INCHES OF SUPPLY, A FIELD TEST IS REQUIRED TO
 SHOW THE PRESSURE DIFFERENTIAL TO BE 0.01" WC OR LESS
 PER FBC,M 601.4. THIS APPLIES TO ANY AREAS UTILIZING
 TRANSFER DUCTS/GRILLS FOR BALANCED RETURN.
  
 J. M2.2.2 AHU 2-9: PLEASE SHOW SIZES OF BRANCH DUCTS AT
 TEE ON SUPPLY DUCT SYSTEM. FBC 106.1.1
  
 K. AHU SYSTEMS: MOST SYSTEMS APPEAR TO BE DESIGNED WITH
 EQUAL AMOUNTS OF SUPPLY AND RETURN AIR. EXAMPLE: AHU
 2-6 SHOWS 1600 CFM SUPPLY, 1600 CFM RETURN AMD 330 CFM
 O.A. HOW WILL O/A BE INTRODUCED OF 100% OF SUPPLY IS
 BEING RETURNED? PLEASE CHECK ALL A/C SYSTEMS FOR PROPER
 BALANCE IN ACCORDANCE WITH FBC,M 403.1.
  
 L. ALL EXIT ENCLOSURES: EQUIPMENT AND DUCTWORK FOR EXIT
 ENCLOSURE VENTILATION SHALL COMPLY WITH THE
 REQUIREMENTS FBC,M 401.4. SOME ASPECTS OF THE A/C
 SYSTEMS MAY NEED TO BE MODIFIED TO MEET THIS
 REQUIREMENT. A REVIEW OF CHANGES WITH POSSIBLE NEW
 COMMENTS WILL BE DONE AT TIME OF RESUBMITTAL.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-01-09 Cont ID  
Sent By pkrauss Date 2007-01-09 Time 06:35 Rev Time 0.00
Received By pkrauss Date 2007-01-04 Time 13:55 Sent To  
Notes
2007-01-09 08:04:43DENIED:
 1.PLAN SHEET M2.1.1 & DETAIL ON SHEET M7.3, DOES NOT
 INDICATE TERMINATION OF THE REFRIGERANT RELIEF VENT.
 PLEASE SHOW COMPLIANCE WITH 2004 FMC 1105.7,PRESSURE
 RELIEF DEVICES, PURGE SYSTEMS, FUSIBLE PLUGS LOCATED
 WITHIN THE MACHINERY ROOM SHALL TERMINATE OUTSIDE OF
 THE BUILDING NOT LESS THAN 15 FT ABOVE THE ADJOINING
 GRADE AND NOT LESS THAN 20 FT FROM ANY WINDOW,
 VENTILATION OPENING OR EXIT.
  
 2.PLAN SHEET M2.1.1, CHILLER ROOM EXHAUST TERMINATION
 SHALL BE DISCHARGED NOT LESS THAN 20 FT FROM A PROPERTY
 LINE OR OPENINGS INTO BUILDINGS PER 2004 FMC 1105.6.
  
 3.PLAN SHEET M2.1.1 KEY NOTE 5 INDICATES REFRIGERANT
 MONITORING PANEL.PLEASE INDICATE LOCATATION AND
 NUMBER OF DETECTORS TIED INTO THE PANEL.
  
 4.PLAN SHEET M6.1 INDICATES EXHAUST AIR CALCULATION
 AS REQUIRED IN ASHRAE 15.PLEASE PROVIDE THE NORMAL
 VENTILATION REQUIREMENTS PER 2004 FMC 1105.6.
  
 5.PLEASE NOTE, THE MECHANICAL PORTION OF THE SPEC
 BOOK REFER TO THE MECHANICAL DRAWINGS FOR
 SPECIFICATIONS.PLEASE PROVIDE INFORMATION ON PIPE
 MATERIAL PER 2004 FMC CHAPTER 12.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719 OR E-MAIL [email protected].

Review Stop P PLUMBING
Rev No 12 Status P Date 2009-06-15 Cont ID  
Sent By kstevens Date 2009-06-15 Time 13:35 Rev Time 0.00
Received By kstevens Date 2009-06-15 Time 13:35 Sent To  
Notes
2009-06-15 13:40:16REVISIONS OK -- SHTS P2.2.2, P2.4.1, P5.1 & P6.1.

Review Stop P PLUMBING
Rev No 11 Status F Date 2009-05-11 Cont ID  
Sent By kstevens Date 2009-05-11 Time 08:14 Rev Time 0.00
Received By kstevens Date 2009-05-08 Time 16:45 Sent To  
Notes
2009-05-11 08:41:15DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 ****FROM PREVIOUS REVIEW:
  
 ******FROM PREVIOUS REVIEWS:
  
 1. SHT P2.2.2 SUBMIT CALCULATIONS FOR THE EXISTING ROOF
 DRAINS THAT HAVE THE ADDED VERTICAL CONTRIBUTION FROM
 THE NEW ADDIITION PLEASE INDICATE TOTAL SQUARE FOOTAGE
 BEING DRAINED BY THE DRAINS ADJACENT TO THE NEW
 ADDITION. SHOW EXISTING SF AND 1/2 AREA OF NEW VERTICAL
 WALL ADDED TO SF. INDICATE THE SIZE OF THE EXISTING
 ROOF DRAINS AND THE SIZE OF THE EXISTING ROOF LEADERS.
 SECTIONS 1106 & 1107 WITH ALL SUBSECTIONS. SHOW ALL
 SECONDARY ROOF DRAINS/SCUPPERS AND INDICATE THE SIZE OF
 THE SECONDARY ROOF DRAINS/SCUPPERS AND THE SIZE OF THE
 LEADERS OF THE SECONDARY ROOF DRAINS. THE REASON FOR
 THIS COMMENT IS BECAUSE OF THE FACT THAT THE ROOF
 DRAINS BEING DELETED WERE SHOWN ON THE PLANS TO ADDRESS
 THE VERTICAL CONTRIBUTION FROM THE NEW BUILDING.
 ****RESPONSE INDICATES THAT THE EXISTING ROOF HAS
 GUTTERS & DOWNSPOUTS. WITH THE NEW VERTICAL
 CONTRIBUTION THE CALCULATIONS WILL STILL BE REQUIRED
 FOR SIZING THE GUTTERS AND DOWNSPOUTS. PLEAS SUBMIT THE
 CALCULATIONS AS WELL AS THE GUTTER SIZE, DOWNSPOUT
 SIZE, LOCATION OF DOWNSPOUTS, AND INDICATE THE SLOPE OF
 THE GUTTERS INDICATING THE HIGH POINT OF THE GUTTERS
 AND DIRECTION OF FLOW TO THE DOWNSPOUTS. TABLES 1106.3
 & 1106.6.
 ******RESPONSE NOTED, BUT STORM CALCULATIONS FOR
 EXISTING BUILDING PART ROOF "B" DOES NOT SHOW ANY AREA
 FOR THE VERTICAL WALLS IN THE CALCULATIONS FOR UPPER
 ROOF "B". PLEASE CLARIFY. DOES UPPER ROOF "B" NOT HAVE
 PARAPET WALLS AS DOES UPPER ROOF "A"? -- GUTTER AND
 DOWNSPOUT SIZES ARE NOT INDICATED ON THE PLANS AS
 REQUESTED. -- CALCULATIONS FOR THE GUTTERS AND
 DOWNSPOUTS ARE REQUIRED TO BE PER TABLES 1106.3 &
 1106.6 OF THE FBC-2004 PLUMBING CODE, NOT SMACNA AS
 THAT IS NOT A REFERENCED MATERIAL IN THE PLUMBING CODE.
  
  
  
 **********NEW COMMENT**********
  
 1B. SHT P6.1 THE RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN BY THE DRINKING FOUNTAIN. THE RISER DIAGRAM
 SHOWS A NEW CONNECTION LOCATION FOR THE HOT & COLD
 WATER TO THE 2 INCH WATER MAIN, DOES NOT SHOW THE LINES
 TO THE ROOF AS SHOWN ON THE FLOOR PLAN, AND DOES NOT
 SHOW THE OLD CONNECTION TO THE WATER MAINS AS SHOWN ON
 THE FLOOR PLAN. PLEASE CORRELATE THE RISER WITH THE
 FLOOR PLAN. SECTIONS 106.1.1 & 601.1.
 ****RESPONSE NOTED, BUT REVISION 19 HAS NOT BEEN FOUND
 ON THE RISER DIAGRAMS. PLEASE SHOW THE LOCATION OF EACH
 REVISION NUMBER ON THE RISER DIAGRAM.
  
 **********NEW COMMENTS*********
  
 1C. SHT P3.1.2 NO CHANGES FOUND. REVISION 6 WAS
 REVIEWED ON SHEET SIGNED, SEALED & DATED ON 5-1-08.
 SECTION 106.1.3.
  
 2C. SHT P3.4 NO CHANGES FOUND FROM SHEET SIGNED, SEALED
 & DATED 7-13-07.
  
 3C. SHT P5.1 EVERY DRY VENT SHALL RISE VERTICALLY TO A
 MINIMUM OF 6 INCHES ABOVE THE FLOOD RIM LEVEL OF THE
 HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED. SECTION
 905.4. THE VENT FOR THE FLOOR DRAIN OFFSETS
 HORIZONTALLY BELOW THE FLOOR DRAIN. -- REVISION 19 HAS
 NOT BEEN FOUND ON THE RISER DIAGRAM. PLEASE SHOW THE
 LOCATION OF EACH REVISION NUMBER ON THE RISER. DIAGRAM.
 SECTION 106.1.3.
  
 4C. SHT P6.1 REVISION 19 HAS NOT BEEN FOUND ON THE
 RISER DIAGRAM. PLEASE SHOW THE LOCATION OF EACH
 REVISION NUMBER ON THE RISER DIAGRAM. SECTION 106.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 10 Status P Date 2009-05-08 Cont ID  
Sent By kstevens Date 2009-05-08 Time 16:45 Rev Time 0.00
Received By kstevens Date 2009-05-08 Time 16:45 Sent To  
Notes
2009-05-08 16:46:29REVISIONS OK -- SHTS P0.1, P2.2.1, P2.4.1, P3.1.1 &
 P3.2.1.

Review Stop P PLUMBING
Rev No 9 Status F Date 2009-04-14 Cont ID  
Sent By kstevens Date 2009-04-14 Time 10:38 Rev Time 0.00
Received By kstevens Date 2009-04-14 Time 10:38 Sent To  
Notes
2009-04-14 10:45:58DENIED
 REFERENCE:
 FBC-2004 PLUMBING
  
 1. SHT P2.2.2 SUBMIT CALCULATIONS FOR THE EXISTING ROOF
 DRAINS THAT HAVE THE ADDED VERTICAL CONTRIBUTION FROM
 THE NEW ADDIITION PLEASE INDICATE TOTAL SQUARE FOOTAGE
 BEING DRAINED BY THE DRAINS ADJACENT TO THE NEW
 ADDITION. SHOW EXISTING SF AND 1/2 AREA OF NEW VERTICAL
 WALL ADDED TO SF. INDICATE THE SIZE OF THE EXISTING
 ROOF DRAINS AND THE SIZE OF THE EXISTING ROOF LEADERS.
 SECTIONS 1106 & 1107 WITH ALL SUBSECTIONS. SHOW ALL
 SECONDARY ROOF DRAINS/SCUPPERS AND INDICATE THE SIZE OF
 THE SECONDARY ROOF DRAINS/SCUPPERS AND THE SIZE OF THE
 LEADERS OF THE SECONDARY ROOF DRAINS. THE REASON FOR
 THIS COMMENT IS BECAUSE OF THE FACT THAT THE ROOF
 DRAINS BEING DELETED WERE SHOWN ON THE PLANS TO ADDRESS
 THE VERTICAL CONTRIBUTION FROM THE NEW BUILDING.
 ****RESPONSE INDICATES THAT THE EXISTING ROOF HAS
 GUTTERS & DOWNSPOUTS. WITH THE NEW VERTICAL
 CONTRIBUTION THE CALCULATIONS WILL STILL BE REQUIRED
 FOR SIZING THE GUTTERS AND DOWNSPOUTS. PLEAS SUBMIT THE
 CALCULATIONS AS WELL AS THE GUTTER SIZE, DOWNSPOUT
 SIZE, LOCATION OF DOWNSPOUTS, AND INDICATE THE SLOPE OF
 THE GUTTERS INDICATING THE HIGH POINT OF THE GUTTERS
 AND DIRECTION OF FLOW TO THE DOWNSPOUTS. TABLES 1106.3
 & 1106.6.
  
 **********NEW COMMENT**********
  
 1B. SHT P6.1 THE RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN BY THE DRINKING FOUNTAIN. THE RISER DIAGRAM
 SHOWS A NEW CONNECTION LOCATION FOR THE HOT & COLD
 WATER TO THE 2 INCH WATER MAIN, DOES NOT SHOW THE LINES
 TO THE ROOF AS SHOWN ON THE FLOOR PLAN, AND DOES NOT
 SHOW THE OLD CONNECTION TO THE WATER MAINS AS SHOWN ON
 THE FLOOR PLAN. PLEASE CORRELATE THE RISER WITH THE
 FLOOR PLAN. SECTIONS 106.1.1 & 601.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 8 Status P Date 2009-04-14 Cont ID  
Sent By kstevens Date 2009-04-14 Time 10:37 Rev Time 0.00
Received By kstevens Date 2009-04-14 Time 10:37 Sent To  
Notes
2009-04-14 10:38:40REVISIONS OK -- SHTS P2.1.1, P2.1.2, P2.4.1, P2.4.2,
 P3.2.1, P5.2 & P5.3.

Review Stop P PLUMBING
Rev No 7 Status F Date 2009-02-24 Cont ID  
Sent By kstevens Date 2009-02-24 Time 09:49 Rev Time 0.00
Received By kstevens Date 2009-02-24 Time 09:49 Sent To  
Notes
2009-02-24 09:54:01DENIED
 REFERENCE:
 FBC-2004 PLUMBING
  
 1. SHTS P2.2.2 & P5.2 SUBMIT CALCULATIONS FOR THE
 EXISTING ROOF DRAINS THAT HAVE THE ADDED VERTICAL
 CONTRIBUTION FROM THE NEW ADDIITION PLEASE INDICATE
 TOTAL SQUARE FOOTAGE BEING DRAINED BY THE DRAINS
 ADJACENT TO THE NEW ADDITION. SHOW EXISTING SF AND 1/2
 AREA OF NEW VERTICAL WALL ADDED TO SF. INDICATE THE
 SIZE OF THE EXISTING ROOF DRAINS AND THE SIZE OF THE
 EXISTING ROOF LEADERS. SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS. SHOW ALL SECONDARY ROOF DRAINS/SCUPPERS
 AND INDICATE THE SIZE OF THE SECONDARY ROOF
 DRAINS/SCUPPERS AND THE SIZE OF THE LEADERS OF THE
 SECONDARY ROOF DRAINS. THE REASON FOR THIS COMMENT IS
 BECAUSE OF THE FACT THAT THE ROOF DRAINS BEING DELETED
 WERE SHOWN ON THE PLANS TO ADDRESS THE VERTICAL
 CONTRIBUTION FROM THE NEW BUILDING.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 6 Status P Date 2009-02-24 Cont ID  
Sent By kstevens Date 2009-02-24 Time 09:48 Rev Time 0.00
Received By kstevens Date 2009-02-24 Time 09:48 Sent To  
Notes
2009-02-24 09:48:55REVISIONS OK -- SHTS P2.1.1, P2.2.1, P5.1 & P5.3.

Review Stop P PLUMBING
Rev No 5 Status P Date 2008-07-21 Cont ID  
Sent By kstevens Date 2008-07-21 Time 08:27 Rev Time 0.00
Received By kstevens Date 2008-07-21 Time 08:27 Sent To  
Notes
2008-07-21 08:28:37REVISION OK - REV. #6--SHTS P0.1, P2.3.2, P3.1.1,
 P3.1.2, P3.2.1, P3.2.2, P3.3, P5.1 & P6.1

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-12-01 Cont ID  
Sent By kstevens Date 2007-12-01 Time 05:34 Rev Time 0.00
Received By kstevens Date 2007-12-01 Time 05:34 Sent To  
Notes
2007-12-01 05:39:48 
  
  
  
  
 PASSED/PROVISO
  
 A REVISION FOR SHEET P2.2.1 IS REQUIRED TO RESPOND TO
 COMMENT NUMBER 9 ADDRESSING THE VENT BETWEEN THE
 SANITARY RISER AND FIRST SET OF WATER CLOSETS SHOWN ON
 THE SANITARY RISER DIAGRAM.
  
  
  
  
  
  
  
  
  
  
  
  
  
 .

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-09-08 Cont ID  
Sent By kstevens Date 2007-09-08 Time 05:25 Rev Time 0.00
Received By kstevens Date 2007-09-07 Time 19:00 Sent To  
Notes
2007-09-08 05:59:32DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 ****FROM PREVIOUS REVIEW:
 ******FROM PREVIOUS REVIEWS:
  
 1. OK
 2. OK
 3. OK
 4. OK
 5. OK
 6. OK
 7. OK
  
 8. SHT P3-1.1 RPZV BACKFLOWS ARE REQUIRED ON EACH WATER
 SUPPLY LINE INTO THE BUILDING. SECTION 608.13.2. SHOW
 ON THE PLANS.
 ****RESPONSE NOTED, BUT THE CIVIL SHEET WERE NOT
 SUBMITTED WITH THESE PLANS. PLEASE INDICATE ON THE
 PLANS LOCATION OF REQUIRED BACKFLOWS.
 ******RESPONSE NOTED, BUT THE RPZV BACKFLOWS ARE NOT
 INDICATED ON THE CIVIL PLANS AS REQUIRED FOR EACH
 BUILDING.
  
 9. SHT P5.1 VENT SHOWN UPSTREAM OF THE SANITARY STACK
 AND PRIOR TO THE FIRST WATER CLOSETS IS NOT SHOWN ON
 THE FLOOR PLAN. (TOILET ROOMS 221 & 223). PLEASE
 CORRELATE INFORMATION BETWEEN THE FLOOR PLAN AND THE
 RISER DIAGRAM. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. ROOMS
 221 & 223 ARE ONLY SHOWN ON SHT P2.2 AND NO CHANGE TO
 FLOOR PLAN SHOWN.
 ******RESPONSE NOTED, BUT THE VENT IS STILL NOT SHOWN
 ON THE FLOOR PLAN TO REFLECT THE RISER DIAGRAM.
  
 10. OK
 11. OK
  
 12. SHT P6.1 DOMESTIC WATER ISOMETRIC. SHOW THE
 REQUIRED RPZV BACKFLOWS ON THE WATER SERVICES, AND SHOW
 AN RPZV ON THE SUPPLY LINE FOR THE 2" MAKE UP WATER TO
 THE ROOF. SECTION 608.13.2.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. - NOT
 SHOWN ON ISOMETRIC AS INDICATED.
 ******RESPONSE NOTED, BUT THE RPZV BACKFLOWS ARE NOT
 SHOWN ON THE WATER SERVICE TO EACH BUILDING.
  
 13. OK
 14. OK
 15. OK
 16. OK
  
 **********NEW COMMENTS**********
  
 1B. ALL SHEETS FOR PME SHALL BE SIGNED, SEALED & DATED
 ON THE DATE THE SEAL & SIGNATURE ARE AFFIXED TO SAID
 PLANS. SECTION 106.1.
 ******RESPONSE NOTED, BUT ONE ELECTRICAL SHEET DOES NOT
 HAVE A SIGNATURE ON ONE SET.
  
 2B. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-06-13 Cont ID  
Sent By kstevens Date 2007-06-13 Time 14:05 Rev Time 0.00
Received By kstevens Date 2007-06-13 Time 14:05 Sent To  
Notes
2007-06-13 14:53:14DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHT A0.0.1 INDICATES ASSEMBLY OCCUPANCY FOR THE 1ST
 & 2ND FLOORS. PER SECTION 403.1.1, POTTY PARITY,
 RESTROOMS WHICH ARE OPEN TO THE PUBLIC, MUST HAVE A
 RATIO OF 3:2 WATER CLOSETS PROVIDED FOR WOMEN AS THE
 COMBINED TOTAL OF WATER CLOSETS & URINALS PROVIDED FOR
 MEN. POTTY PARITY DOES NOT SEEM TO BE COMPLIED WITH.
 PLEASE SHOW COMPLIANCE WITH SECTION 403.1.1.
 ****RESPONSE NOTED, BUT ACCORDING TO TABLE 403.1, FIRST
 FLOOR ASSEMBLY OF 271 FOR WOMEN @ 1/65 COMES OUT TO
 4.169 AND ALL FRACTIONS SHALL BE ROUNDED UP. SO THE
 TOTAL WOMENS W/C'S REQUIRED IS 18, NOT 17 AS SHOWN.
  
 2. SHT A2.4.1 SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS PER SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS & TABLES. SHOW THE SQUARE FOOTAGE OF EACH
 AREA TO BE DRAINED, AND 1/2 AREA OF ALL VERTICAL WALLS
 INCLUDING PARAPETS AS WELL AS ANY ROOF AREA FROM ABOVE
 THAT DRAINS ON TO THE LOWER ROOFS IN THE CALCULATIONS.
 SECTIONS 106.3.5.1.3(7)(13) & TABLES 1106.2, 1106.3 &
 1106.6. INDICATE THE SIZE OF THE GUTTERS AND SHOW SLOPE
 WITH THE HIGH POINTS OF THE GUTTER INDICATED.
 ****RESPONSE NOTED, BUT NO CALCULATIONS WERE FOUND. THE
 1/2 AREA OF ALL VERTICAL WALLS WAS NOT INDICATED AND NO
 SQUARE FOOTAGE IS INDICATED FOR THE ROOF DRAINS SHOWN
 ON SHT P2.3.1 & ASSOCIATED DRAINS ON THE STORM RISER
 DIAGRAM SHT P5.2. UPON FURTHER REVIEW, NO CALCULATIONS
 WERE FOUND FOR THE EXISTING ROOF DRAINS THAT HAVE THE
 ADDED VERTICAL CONTRIBUTION FROM THE NEW ADDIITION
 PLEASE INDICATE TOTAL SQUARE FOOTAGE BEING DRAINED BY
 THE DRAINS ADJACENT TO THE NEW ADDITION. SHOW EXISTING
 SF AND 1/2 AREA OF NEW VERTICAL WALL ADDED TO SF.
 INDICATE THE SIZE OF THE EXISTING ROOF DRAINS AND THE
 SIZE OF THE EXISTING ROOF LEADERS.
  
 3. SHTS A4.1.1 & A4.1.2 SHOW THE CLEAR FLOOR SPACE FOR
 THE URINAL, ACCESSIBLE SHOWERS AND DRINKING FOUNTAINS
 PER SECTIONS 11-4.18..3, 11-4.21.2, & 11-4.15.5. ****NO
 RESPONSE, NOT ADDRESSED.
  
 4. SHT A7.1.1 FINISH SCHEDULE. BOY'S RESTROOM 107 &
 GIRL'S RESTROOM 109 INDICATE PAINTED GWB FOR THE WALL
 FINISH. SECTION 1210.2 REQUIRES A "SMOOTH, HARD,
 NONABSORBENT" SURFACE. PAINTED GWB IS NOT CONSIDERED A
 "HARD" SURFACE. PLEASE INDICATE HOW THIS REQUIREMENT
 WILL BE COMPLIED WITH. ALSO SEE BOY'S RESTROOM 302 AND
 GIRL'S RESTROOM 304. NO FINISH IS INDICATED. PLEASE
 INDICATE WALL FINISH TO COMPLY WITH SECTION 1210.2.
 ****NO RESPONSE, NOT ADDRESSED.
  
 5. SHT A8.1.3 SHOW THE FOLLOWING REQUIREMENTS:
 A. 11-4.16.6 DISPENSERS (FIG 29(B)
 B. 11-4.18.4 FLUSH CONTROLS
 C. 11-4.19.5 FAUCETS
 D. 11-4.21.2 SIZE & CLEARANCES
 E. 11-4.21.3 SEAT
 F. 11-4.21.4 GRAB BARS (FIG 11-37)
 G. 11-4.21.5 CONTROLS
 H. 11-4.21.6 SHOWER UNIT
 ****NO RESPONSE, NOT ADDRESSED.
  
 6. SUBMIT A DETAIL FOR THE ACCESSIBLE DRINKING
 FOUNTAINS. SHOW COMPLIANCE WITH SECTION 11-4.15 AND ALL
 SUBSECTIONS INCLUDING ALSO SECTION 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING AND
 STOOPING.
 ****NO RESPONSE, NOT ADDRESSED.
  
 7. SHT P0.1 WATER HEATER DETAIL. SUBMIT CALCULATION FOR
 THE EXPANSION TANK FOR THE 1230 GAL W/H. SUBMIT THE
 MANUF. SPECIFICATION SHEETS AND INDICATE THE MODEL
 NUMBER SHOWING TANK SIZE. SECTION 607.3.2. ****RESPONSE
 NOTED, BUT THE CALCULATIONS WERE NOT SUBMITTED. (SEE
 EXAMPLES OF TWO DIFFERENT MANUF. CALCULATIONS FOR
 EXPANSION TANKS).
  
 8. SHT P3-1.1 RPZV BACKFLOWS ARE REQUIRED ON EACH WATER
 SUPPLY LINE INTO THE BUILDING. SECTION 608.13.2. SHOW
 ON THE PLANS.
 ****RESPONSE NOTED, BUT THE CIVIL SHEET WERE NOT
 SUBMITTED WITH THESE PLANS. PLEASE INDICATE ON THE
 PLANS LOCATION OF REQUIRED BACKFLOWS.
  
 9. SHT P5.1 VENT SHOWN UPSTREAM OF THE SANITARY STACK
 AND PRIOR TO THE FIRST WATER CLOSETS IS NOT SHOWN ON
 THE FLOOR PLAN. (TOILET ROOMS 221 & 223). PLEASE
 CORRELATE INFORMATION BETWEEN THE FLOOR PLAN AND THE
 RISER DIAGRAM. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. ROOMS
 221 & 223 ARE ONLY SHOWN ON SHT P2.2 AND NO CHANGE TO
 FLOOR PLAN SHOWN.
  
 10. SHT P5.1 SANITARY RISER DIAGRAM. SHOW THE DFU'S AS
 THEY ACCUMULATE IN THE SYSTEM TO VERIFY THE PIPE SIZES.
 SECTION 106.1.1 AND TABLES 709.1, 710.1(1) & 710.1(2).
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED.
  
 11. OK
  
 12. SHT P6.1 DOMESTIC WATER ISOMETRIC. SHOW THE
 REQUIRED RPZV BACKFLOWS ON THE WATER SERVICES, AND SHOW
 AN RPZV ON THE SUPPLY LINE FOR THE 2" MAKE UP WATER TO
 THE ROOF. SECTION 608.13.2.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. - NOT
 SHOWN ON ISOMETRIC AS INDICATED.
  
 13. SHT P6.1 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURES IN AN "EFFECTIVE RANGE" NOT IN THE
 CEILING AS SHOWN. PDI-WH 201 AND MANUF. INSTALLATION
 INSTRUCTIONS.
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
  
 14. SHT P6.1 SHUT OFF VALVES ARE REQUIRED ON BOTH SIDES
 OF THE CIRCULATION PUMP FOR THE WATER HEATERS. ALSO
 SHOW THE VALVES ON THE WATER HEATER DETAIL SHT P0.1.
 SECTION 606.2(3).
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED FOR SHUT OFF
 VALVES FOR THE CIRCULATION PUMP.
  
 15. SUBMIT A STORM RISER ISOMETRIC RISER DIAGRAM. SHOW
 ALL PIPE SIZES, OFFSETS, AND SQUARE FOOTAGE AS IT
 ACCUMULATES IN THE SYSTEM. SECTION 106.3.5.1.3.
 ****RESPONSE NOTED, BUT THE SQUARE FOOTAGE AS IT
 ACCUMULATES IN THE SYSTEM IS NOT SHOWN ON THE RISER.
 THE RISER DIAGRAM DOES NOT REFLECT THE FLOOR PLAN FOR
 THE 6" @3535SF.
  
 16. OK
  
 **********NEW COMMENTS**********
  
 1B. ALL SHEETS FOR PME SHALL BE SIGNED, SEALED & DATED
 ON THE DATE THE SEAL & SIGNATURE ARE AFFIXED TO SAID
 PLANS. SECTION 106.1.
  
 2B. SEE THE ATTACHED SHEET CONCERNING FS 553.80(2)(B)
 AND THE DESIGN PROFESSIONAL. THIS IS GIVEN AS A NOTICE
 AT THIS TIME.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-01-06 Cont ID  
Sent By kstevens Date 2007-01-06 Time 15:50 Rev Time 0.00
Received By kstevens Date 2007-01-04 Time 08:35 Sent To  
Notes
2007-01-06 17:09:55DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHT A0.0.1 INDICATES ASSEMBLY OCCUPANCY FOR THE 1ST
 & 2ND FLOORS. PER SECTION 403.1.1, POTTY PARITY,
 RESTROOMS WHICH ARE OPEN TO THE PUBLIC, MUST HAVE A
 RATIO OF 3:2 WATER CLOSETS PROVIDED FOR WOMEN AS THE
 COMBINED TOTAL OF WATER CLOSETS & URINALS PROVIDED FOR
 MEN. POTTY PARITY DOES NOT SEEM TO BE COMPLIED WITH.
 PLEASE SHOW COMPLIANCE WITH SECTION 403.1.1.
  
 2. SHT A2.4.1 SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS PER SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS & TABLES. SHOW THE SQUARE FOOTAGE OF EACH
 AREA TO BE DRAINED, AND 1/2AREA OF ALL VERTICAL WALLS
 INCLUDING PARAPETS AS WELL AS ANY ROOF AREA FROM ABOVE
 THAT DRAINS ON TO THE LOWER ROOFS IN THE CALCULATIONS.
 SECTIONS 106.3.5.1.3(7)(13) & TABLES 1106.2, 1106.3 &
 1106.6. INDICATE THE SIZE OF THE GUTTERS AND SHOW SLOPE
 WITH THE HIGH POINTS OF THE GUTTER INDICATED.
  
 3. SHTS A4.1.1 & A4.1.2 SHOW THE CLEAR FLOOR SPACE FOR
 THE URINAL, ACCESSIBLE SHOWERS AND DRINKING FOUNTAINS
 PER SECTIONS 11-4.18..3, 11-4.21.2, & 11-4.15.5.
  
 4. SHT A7.1.1 FINISH SCHEDULE. BOY'S RESTROOM 107 &
 GIRL'S RESTROOM 109 INDICATE PAINTED GWB FOR THE WALL
 FINISH. SECTION 1210.2 REQUIRES A "SMOOTH, HARD,
 NONABSORBENT" SURFACE. PAINTED GWB IS NOT CONSIDERED A
 "HARD" SURFACE. PLEASE INDICATE HOW THIS REQUIREMENT
 WILL BE COMPLIED WITH. ALSO SEE BOY'S RESTROOM 302 AND
 GIRL'S RESTROOM 304. NO FINISH IS INDICATED. PLEASE
 INDICATE WALL FINISH TO COMPLY WITH SECTION 1210.2.
  
 5. SHT A8.1.3 SHOW THE FOLLOWING REQUIREMENTS:
 A. 11-4.16.6 DISPENSERS (FIG 29(B)
 B. 11-4.18.4 FLUSH CONTROLS
 C. 11-4.19.5 FAUCETS
 D. 11-4.21.2 SIZE & CLEARANCES
 E. 11-4.21.3 SEAT
 F. 11-4.21.4 GRAB BARS (FIG 11-37)
 G. 11-4.21.5 CONTROLS
 H. 11-4.21.6 SHOWER UNIT
  
 6. SUBMIT A DETAIL FOR THE ACCESSIBLE DRINKING
 FOUNTAINS. SHOW COMPLIANCE WITH SECTION 11-4.15 AND ALL
 SUBSECTIONS INCLUDING ALSO SECTION 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING AND
 STOOPING.
  
 7. SHT P0.1 WATER HEATER DETAIL. SUBMIT CALCULATION FOR
 THE EXPANSION TANK FOR THE 1230 GAL W/H. SUBMIT THE
 MANUF. SPECIFICATION SHEETS AND INDICATE THE MODEL
 NUMBER SHOWING TANK SIZE. SECTION 607.3.2.
  
 8. SHT P3-1.1 RPZV BACKFLOWS ARE REQUIRED ON EACH WATER
 SUPPLY LINE INTO THE BUILDING. SECTION 608.13.2. SHOW
 ON THE PLANS.
  
 9. SHT P5.1 VENT SHOWN UPSTREAM OF THE SANITARY STACK
 AND PRIOR TO THE FIRST WATER CLOSETS IS NOT SHOWN ON
 THE FLOOR PLAN. (TOILET ROOMS 221 & 223). PLEASE
 CORRELATE INFORMATION BETWEEN THE FLOOR PLAN AND THE
 RISER DIAGRAM. SECTION 106.1.1.
  
 10. SHT P5.1 SANITARY RISER DIAGRAM. SHOW THE DFU'S AS
 THEY ACCUMULATE IN THE SYSTEM TO VERIFY THE PIPE SIZES.
 SECTION 106.1.1 AND TABLES 709.1, 710.1(1) & 710.1(2).
  
 11. SHTS P2.3.1, P2.4.1, AND P2.4.2 SHOW THE VENTS THRU
 THE ROOF ON THE ROOF PLANS TO REFLECT THE RISER
 DIAGRAM. SECTION 106.1.1.
  
 12. SHT P6.1 DOMESTIC WATER ISOMETRIC. SHOW THE
 REQUIRED RPZV BACKFLOWS ON THE WATER SERVICES, AND SHOW
 AN RPZV ON THE SUPPLY LINE FOR THE 2" MAKE UP WATER TO
 THE ROOF. SECTION 608.13.2.
  
 13. SHT P6.1 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURES IN AN "EFFECTIVE RANGE" NOT IN THE
 CEILING AS SHOWN. PDI-WH 201 AND MANUF. INSTALLATION
 INSTRUCTIONS.
  
 14. SHT P6.1 SHUT OFF VALVES ARE REQUIRED ON BOTH SIDES
 OF THE CIRCULATION PUMP FOR THE WATER HEATERS. ALSO
 SHOW THE VALVES ON THE WATER HEATER DETAIL SHT P0.1.
 SECTION 606.2(3).
  
 15. SUBMIT A STORM RISER ISOMETRIC RISER DIAGRAM. SHOW
 ALL PIPE SIZES, OFFSETS, AND SQUARE FOOTAGE AS IT
 ACCUMULATES IN THE SYSTEM. SECTION 106.3.5.1.3.
  
 16. SUBMIT A CONDENSATE RISER ISOMETRIC RISER DIAGRAM.
 SHOW ALL PIPE SIZES. SECTION 106.3.5.1.3.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 10 Status P Date 2009-04-07 Cont ID  
Sent By aaponte Date 2009-04-07 Time 09:24 Rev Time 0.00
Received By aaponte Date 2009-04-07 Time 09:23 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 9 Status F Date 2009-03-03 Cont ID  
Sent By aaponte Date 2009-03-03 Time 12:59 Rev Time 0.00
Received By aaponte Date 2009-03-03 Time 12:58 Sent To  
Notes
2009-03-03 12:59:08OWNER CALLED AND ASKED FOR THE DRAWINGS TO BE RETURNED.
 HE WILL CHANGE THE DRAWINGS AGAIN AND RESUBMIT.

Review Stop Z ZONING
Rev No 8 Status F Date 2009-02-24 Cont ID  
Sent By aaponte Date 2009-02-24 Time 16:12 Rev Time 0.00
Received By aaponte Date 2009-02-24 Time 16:12 Sent To  
Notes
2009-02-24 16:13:22DRAWINGS SHOULD BE CLOUDED TO INDICATE CHANGES. PLEASE
 SUBMIT A DETAILED EXPLANATION OF PROPOSED CHANGES.

Review Stop Z ZONING
Rev No 7 Status N Date 2009-01-30 Cont ID  
Sent By aaponte Date 2009-01-30 Time 15:04 Rev Time 0.00
Received By aaponte Date 2009-01-30 Time 15:04 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 6 Status P Date 2008-08-08 Cont ID  
Sent By astelly Date 2008-08-08 Time 14:49 Rev Time 0.00
Received By astelly Date 2008-08-08 Time 14:49 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 5 Status P Date 2007-12-21 Cont ID  
Sent By astelly Date 2007-12-21 Time 17:59 Rev Time 0.00
Received By astelly Date 2007-12-21 Time 17:59 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status F Date   Cont ID  
Sent By   Date 2007-11-15 Time   Rev Time 0.00
Received By astelly Date 2007-11-15 Time 08:56 Sent To  
Notes
2007-11-15 09:09:04AMY STELLY
 URBAN DESIGN
 822-1440
  
 COMMENTS FROM PREVIOUS REVIEW HAVE NOT BEEN ADDRESSED.
  
 REPEAT COMMENT: PLEASE SHOW THE LOCATION OF THE TRASH
 RECEPTACLE AND IT'S ENCLOSURE ON THE SITE OR
 ARCHITECTURAL PLANS. ALSO INDICATE THE TYPE OF
 SCREENING PROVIDED FOR THE DUMPSTER ENCLOSURE.
  
 ADDITIONAL COMMENT: PLEASE SUBMIT INFORMATION REGARDING
 THE CAPACITY OF THE CURRENT CENTRALIZED DUMPSTER
 FACILITY. ALSO INCLUDETHE SQUARE FOOTAGE ADDED BY THE
 NEW GYM AS WELL AS THE TOTAL SQUARE FOOTAGE OF THE ALL
 CAMPUS BUILDINGS INCLUDING THE ADDITION WHICH WILL
 DEPEND ON THE CENTRALIZED TRASH FACILITY.
  
 LANDSCAPE PLANS MUST BE INCLUDED FOR REVIEW.

Review Stop Z ZONING
Rev No 3 Status F Date 2007-10-11 Cont ID  
Sent By astelly Date 2007-08-21 Time 12:20 Rev Time 0.00
Received By astelly Date 2007-08-21 Time 12:19 Sent To  
Notes
2007-08-21 18:20:50PLEASE SUBMIT THE SIGNED AND SEALED TRAFFIC PLAN AS PER
 ORDINANCE 3941-06.
 ALL PARCELS MUST BE UNIFIED AS STIPULATED BY ORDINANCE
 3941-06.
  
 PLEASE SHOW THE LOCATION OF THE TRASH RECEPTACLE AND
 IT'S ENCLOSURE ON THE SITE OR ARCHITECTURAL PLANS. ALSO
 INDICATE THE TYPE OF SCREENING PROVIDED FOR THE
 DUMPSTER ENCLOSURE.
  
 AMY F. STELLY
 URBAN DESIGN
 822-1440

Review Stop Z ZONING
Rev No 2 Status F Date 2007-04-23 Cont ID  
Sent By astelly Date 2007-04-23 Time 09:21 Rev Time 0.00
Received By astelly Date 2007-04-23 Time 09:21 Sent To  
Notes
2007-04-23 09:24:39PLEASE SUBMIT THE SIGNED AND SEALED TRAFFIC PLAN AS PER
 ORDINANCE 3941-06.
 ALL PARCELS MUST BE UNIFIED AS STIPULATED BY ORDINANCE
 3941-06.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-11-22 Cont ID  
Sent By astelly Date 2006-11-22 Time 15:51 Rev Time 0.00
Received By astelly Date 2006-11-22 Time 15:50 Sent To  
Notes
2006-11-22 15:53:24ACCORDING TO THE DEVELOPMENT ORDER, ORDINANCE NO.
 3941-06, A TRAFFIC PLAN DEVELOPED AND SEALED BY AN
 ENGINEER MUST BE SUBMITTED WITH THE CONSTRUCTION
 DOCUMENTS.


Account Summary | Usage Policy | Privacy Policy