Plan Review Details - Permit 06110144
Plan Review Stops For Permit 06110144
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-02-06 Cont ID  
Sent By jwitmer Date 2007-02-06 Time 10:03 Rev Time 1.22
Received By jwitmer Date 2007-02-06 Time 10:03 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-01-11 Cont ID  
Sent By jwitmer Date 2007-01-11 Time 10:11 Rev Time 1.22
Received By jwitmer Date 2007-01-11 Time 10:11 Sent To  
Notes
2007-01-11 10:19:48BUILDING PLAN REVIEW
 PERMIT: 06110144
 ADD: 500 AUSTRALIAN AVE SUITE# 910
 CONT: KARL CORP CONSTRUCTION SERVICES
 TEL: (561)718-3799
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) NOT CAUGHT ON THE FIRST REVIEW SEE SHEET
 M-1 STAIR TOWER # 1.
 1019.1.2 PENETRATIONS.
 PENETRATIONS INTO AND OPENINGS THROUGH AN EXIT
 ENCLOSURE ARE PROHIBITED EXCEPT FOR REQUIRED EXIT
 DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT
 PRESSURIZATION, SPRINKLER PIPING, STANDPIPES,
 ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION
 AND ELECTRICAL RACEWAY SERVING THE EXIT ENCLOSURE AND
 TERMINATING AT A STEEL BOX NOT EXCEEDING 16 SQUARE
 INCHES (0.010 M 2 ). SUCH PENETRATIONS SHALL BE
 PROTECTED IN ACCORDANCE WITH SECTION 712 . THERE SHALL
 BE NO PENETRATIONS OR COMMUNICATION OPENINGS, WHETHER
 PROTECTED OR NOT, BETWEEN ADJACENT EXIT ENCLOSURES.
  
 1019.1.3 VENTILATION.
 EQUIPMENT AND DUCTWORK FOR EXIT ENCLOSURE VENTILATION
 SHALL COMPLY WITH ONE OF THE FOLLOWING ITEMS:
 1.SUCH EQUIPMENT AND DUCTWORK SHALL BE LOCATED
 EXTERIOR TO THE BUILDING AND SHALL BE DIRECTLY
 CONNECTED TO THE EXIT ENCLOSURE BY DUCTWORK ENCLOSED IN
 CONSTRUCTION AS REQUIRED FOR SHAFTS.
 2.WHERE SUCH EQUIPMENT AND DUCTWORK IS LOCATED
 WITHIN THE EXIT ENCLOSURE, THE INTAKE AIR SHALL BE
 TAKEN DIRECTLY FROM THE OUTDOORS AND THE EXHAUST AIR
 SHALL BE DISCHARGED DIRECTLY TO THE OUTDOORS, OR SUCH
 AIR SHALL BE CONVEYED THROUGH DUCTS ENCLOSED IN
 CONSTRUCTION AS REQUIRED FOR SHAFTS.
 3.WHERE LOCATED WITHIN THE BUILDING, SUCH
 EQUIPMENT AND DUCTWORK SHALL BE SEPARATED FROM THE
 REMAINDER OF THE BUILDING, INCLUDING OTHER MECHANICAL
 EQUIPMENT, WITH CONSTRUCTION AS REQUIRED FOR SHAFTS.
 IN EACH CASE, OPENINGS INTO THE FIRE-RESISTANCE-RATED
 CONSTRUCTION SHALL BE LIMITED TO THOSE NEEDED FOR
 MAINTENANCE AND OPERATION AND SHALL BE PROTECTED BY
 SELF-CLOSING FIRE-RESISTANCE-RATED DEVICES IN
 ACCORDANCE WITH CHAPTER 7 FOR ENCLOSURE WALL OPENING
 PROTECTIVES.
 EXIT ENCLOSURE VENTILATION SYSTEMS SHALL BE INDEPENDENT
 OF OTHER BUILDING VENTILATION SYSTEMS.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-11-27 Cont ID  
Sent By jwitmer Date 2006-11-27 Time 08:18 Rev Time 1.11
Received By jwitmer Date 2006-11-27 Time 07:51 Sent To  
Notes
2006-11-27 08:17:49 
  
 BUILDING PLAN REVIEW
 PERMIT: 06110144
 ADD: 500 AUSTRALIAN AVE SUITE# 910
 CONT: KARL CORP CONSTRUCTION SERVICES
 TEL: (561)718-3799
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT
 G) NUMBER OF FLOORS
 H) SQ. FT. FOOTPRINT
 I )OCCUPANT LOAD
 J) 2004 EXISTING BUILDING CODE, LEVEL OF ALTERATION?
  
 3) SHEET A-1.01 NOTE# 5 INDICATES THAT THE DRYWALL ON
 THE UN-OCCUPIED SIDE OF THE 1 HOUR FIRE RATED WALL BE
 UNFINISHED. DOES UNFINISHED MEAN NO PAINT OR THAT NO
 MUD AND TAPE TO BE APPLIED? PLEASE PROVIDE INFORMATION
 IN COMPLIANCE WITH 713.1 FOR FIRE-RESISTANCE JOINT
 SYSTEM
 THAT WILL BE USED?
  
 4) SHEET A-1.01 DETAIL# 2 INDICATESTHE USE OF A CUT
 IN FIRE
 EXTINGUISHER BOX BUT THE DETAIL ONLY SHOWS 1 LAYER OF
 DRYWALL?
 PLEASE PROVIDE A U.L. LISTING OR GYPSUM ASSOCIATION
 NUMBER
 WHERE THIS OCCURS?
  
 5) SHEET A-3.01 DETAIL 1 INTERIOR ELEVATIONS INDICATES
 A SINK
 AND CABINET BELOW, SHOW COMPLIANCE WITH:
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER NO HIGHER
 THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-04-05 Cont ID  
Sent By btrobaug Date 2007-04-05 Time 07:20 Rev Time 0.75
Received By btrobaug Date 2007-04-05 Time 06:35 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-02-09 Cont ID  
Sent By btrobaug Date 2007-02-09 Time 13:15 Rev Time 0.50
Received By btrobaug Date 2007-02-09 Time 10:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-01-29 Cont ID  
Sent By btrobaug Date 2007-01-29 Time 17:33 Rev Time 0.50
Received By btrobaug Date 2007-01-29 Time 17:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-01-12 Cont ID  
Sent By btrobaug Date 2007-01-12 Time 15:27 Rev Time 0.75
Received By btrobaug Date 2007-01-11 Time 17:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-11-07 Cont ID  
Sent By btrobaug Date 2006-11-07 Time 13:49 Rev Time 0.50
Received By btrobaug Date 2006-11-07 Time 13:18 Sent To I
Notes
2006-11-07 13:49:01 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} INDICATE COMPLIANCE WITH CHAPTER 13
 OF THE FLORIDA BLDG CODE. 13.413,
 13.414, 13.415. SHOW TIME CLOCK AND
 OCCUPANCY SENSOR LOCATIONS ON THE PLAN.
  
 2} PROVIDE PERFORMANCE CALCULATIONS FOR REVIEW PER
 13-415.2.AND CERTIFICATION PER 13-103.1.2.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-02-05 Cont ID  
Sent By mwennerg Date 2007-02-05 Time 13:20 Rev Time 0.00
Received By mwennerg Date 2007-02-05 Time 13:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-01-17 Cont ID  
Sent By mwennerg Date 2007-01-17 Time 09:57 Rev Time 0.00
Received By mwennerg Date 2007-01-17 Time 09:57 Sent To  
Notes
2007-01-17 10:03:01***DENIED***
  
 1) COMMENTS FROM LAST FIRE REVIEW HAVE BEEN ADDRESSED.
  
 2) PLEASE SEE BUILDING COMMENT #2 REGARDING
 PENETRATIONS INTO EXIT ENCLOSURES. IN ADDITION TO FBC,
 SEE NFPA 101 2003 EDITION, SEC.7.1.3.2.1 (6).
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 (561) 805-6722 OR 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-12-04 Cont ID  
Sent By mawillia Date 2006-12-04 Time 14:54 Rev Time 0.00
Received By mawillia Date 2006-12-04 Time 14:54 Sent To  
Notes
2006-12-04 15:18:32*****UNSAT*****
  
  
  
 1.NFPA 101 - 2003 EDITION AND THE FLORIDA FIRE
 PREVENTION CODE - 2004 EDITION SHALL BE REFERENCED.
  
 2.AMEND SHEET A-1.01, KEYED NOTE #1, TO READ 2A:10BC
 FIRE EXTINGUISHER.
  
 3.IN ADDITION TO THE NUMERICAL ADDRESS OF THE
 BUILDING, THE SUITE NUMBER (910) SHOULD ALSO BE
 INCLUDED IN THE TITLE BLOCK OF THE SUBMITTED PLANS TO
 PINPOINT THE LOCATION OF THE SCOPE OF WORK.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-03-22 Cont ID  
Sent By adarroug Date 2007-03-22 Time 11:55 Rev Time 0.00
Received By adarroug Date 2007-03-22 Time 11:55 Sent To M
Notes
2007-03-22 11:55:37TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-03-22 Cont ID  
Sent By adarroug Date 2007-03-22 Time 11:53 Rev Time 0.00
Received By adarroug Date 2007-03-22 Time 11:53 Sent To E
Notes
2007-03-22 11:54:14TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-03-22 Cont ID  
Sent By adarroug Date 2007-03-22 Time 11:50 Rev Time 0.00
Received By adarroug Date 2007-03-22 Time 11:50 Sent To P
Notes
2007-03-22 11:50:36TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-02-08 Cont ID  
Sent By adarroug Date 2007-02-08 Time 16:32 Rev Time 0.00
Received By adarroug Date 2007-02-08 Time 16:32 Sent To  
Notes
2007-02-08 16:35:00TO "BOB"#2

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-01-24 Cont ID  
Sent By adarroug Date 2007-01-24 Time 09:58 Rev Time 0.00
Received By adarroug Date 2007-01-24 Time 09:58 Sent To  
Notes
2007-01-24 10:02:06TO "BOB"#15

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-12-28 Cont ID  
Sent By adarroug Date 2006-12-28 Time 14:47 Rev Time 0.00
Received By adarroug Date 2006-12-28 Time 14:47 Sent To  
Notes
2007-01-09 16:01:50TO "BOB"#13
2006-12-28 14:48:15WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-12-06 Cont ID  
Sent By jleech Date 2006-12-06 Time 14:06 Rev Time 0.00
Received By jleech Date 2006-11-08 Time 16:51 Sent To  
Notes
2006-11-20 16:17:09TO "BOB"#5
2006-11-08 16:51:31WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-03-28 Cont ID  
Sent By tgordon Date 2007-03-28 Time 10:39 Rev Time 0.20
Received By tgordon Date 2007-03-28 Time 10:39 Sent To  
Notes
2007-03-28 10:39:51REVISION TO MECH. PLANS PAGE M-1.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-01-26 Cont ID  
Sent By tgordon Date 2007-01-26 Time 08:09 Rev Time 0.25
Received By tgordon Date 2007-01-26 Time 08:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-01-11 Cont ID  
Sent By tgordon Date 2007-01-11 Time 11:24 Rev Time 0.45
Received By tgordon Date 2007-01-11 Time 11:24 Sent To  
Notes
2007-01-11 11:30:48*** DENIED ***
 1) MISSED ON FIRST REVIEW. SEE PAGE M-1 EXISTING
 STAIRWAY. DUCTS ARE NOT PERMITTED IN STAIRWAYS ,SEE
 2004 FBC 1019.1.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-11-22 Cont ID  
Sent By tgordon Date 2006-11-22 Time 15:26 Rev Time 0.30
Received By tgordon Date 2006-11-22 Time 15:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-04-05 Cont ID  
Sent By jleech Date 2007-04-05 Time 09:37 Rev Time 0.00
Received By jleech Date 2007-04-05 Time 09:37 Sent To  
Notes
2007-04-05 09:40:28REVISION; CHANGED VENTED LINE TO MECHANICAL VENT AT
 BREAK SINK

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-02-06 Cont ID  
Sent By jleech Date 2007-02-06 Time 09:32 Rev Time 0.00
Received By jleech Date 2007-02-06 Time 09:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-01-17 Cont ID  
Sent By jleech Date 2007-01-17 Time 14:28 Rev Time 0.00
Received By jleech Date 2007-01-17 Time 14:28 Sent To  
Notes
2007-01-17 14:39:14DENIED;
 1.BREAK SINK CABINET DOORS CANNOT SWING INTO THE CLEAR
 FLOOR SPACE. SHOW DETAIL HOW GARBAGE DISPOSAL SHALL BE
 INSTALLED AND STILL ALLOW THE 19" REQUIRED UNDER SINK.
 2.WATER HAMMER ARRESTOR REQUIRED FOR ICE MAKER. SEE
 PLUMBING SECTION 604.9. SHOW ON WATER RISER DIAGRAM AND
 LIST MANUFACTURE AND TYPE ON PLANS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-12-06 Cont ID  
Sent By jleech Date 2006-12-06 Time 13:31 Rev Time 0.00
Received By jleech Date 2006-12-06 Time 13:31 Sent To  
Notes
2006-12-06 13:54:09DENIED;
 1.BREAKSINK;GARBAGE DISPOSAL WILL NOT ALLOW A
 FRONTAL APPROACH. SEEFBC-2004 CHAPTER 11 SECTION
 11-4.24.3 KNEE CLEARANCE.
 2. PLEASE ADD NOTES TO INTERIOR ELEVATION DETAIL 01;
 DEPTH OF SINK 6 1/2" DEEP. SEC. 11-4.24.4.RAPP
 EXPOSED PIPES UNDER SINK. SEC11-4.24.6.
 AND TYPE OF HANDLES ON FAUCET TO COMPLY WITH SEC.
 11-4.24.7
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695