Plan Review Details - Permit 06110143
Plan Review Stops For Permit 06110143
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-01-11 Cont ID  
Sent By jwitmer Date 2007-01-11 Time 08:59 Rev Time 1.22
Received By jwitmer Date 2007-01-11 Time 08:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-12-12 Cont ID  
Sent By jwitmer Date 2006-12-12 Time 16:53 Rev Time 0.55
Received By jwitmer Date 2006-12-12 Time 16:49 Sent To PC
Notes
2006-12-12 16:58:53BUILDING PLAN REVIEW
 PERMIT: 06110143
 ADD: 500 S AUSTRALIAN SUITE# 930
 CONT: KARL CORP CONST
 TEL: (561)718-3799
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) SHEET A-0 PROJECT INFORMATION
 PROVIDE BUILDING TYPE II "A OR B"
  
 3) 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 ALSO THE 2004 EXISTING BUILDING CODE.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
  
 4) THE SAME CONDITION WILL EXIST AT THE ENTRY DOOR
 AND THE DOOR AT THE RECEPTIONIST IN BOTH CASES THE
 REQUIRED 18" ON THE LATCH, PULL SIDE OF THE DOOR IS
 REQUIRED.11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARANCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARANCES SHALL BE
 CLEAR & LEVEL.
 1003.3.3 HORIZONTAL PROJECTIONS.
 ELEMENTS CANNOT PROJECT OVER A WALKING SURFACE MORE
 THAN 4 INCHES (102 MM) WHEN THEY ARE LOCATED BETWEEN 27
 AND 80 INCHES (686 AND 2032 MM) ABOVE THE FLOOR.
 HANDRAILS CAN PROJECT UP TO 4? INCHES (114 MM) FROM THE
 WALL.
 11-4.4.1 GENERAL.
 OBJECTS PROJECTING FROM WALLS (FOR EXAMPLE, TELEPHONES)
 WITH THEIR LEADING EDGES BETWEEN 27 INCHES AND 80
 INCHES (685 MM AND 2030 MM) ABOVE THE FINISHED FLOOR
 SHALL PROTRUDE NO MORE THAN 4 INCHES (102 MM) INTO
 WALKS, HALLS, CORRIDORS, PASSAGEWAYS, OR AISLES [SEE
 FIGURE 11-8 (A)]. OBJECTS MOUNTED WITH THEIR LEADING
 EDGES AT OR BELOW 27 INCHES (685 MM) ABOVE THE FINISHED
 FLOOR MAY PROTRUDE ANY AMOUNT [SEE FIGURE 11-8 (A) AND
 FIGURE 11-8 (B)]. FREE-STANDING OBJECTS MOUNTED ON
 POSTS OR PYLONS MAY OVERHANG 12 INCHES (305 MM) MAXIMUM
 FROM 27 INCHES TO 80 INCHES (685 MM TO 2030 MM) ABOVE
 THE GROUND OR FINISHED FLOOR [SEE FIGURE 11-8 (C) AND
 FIGURE 11-8 (D)]. PROTRUDING OBJECTS SHALL NOT REDUCE
 THE CLEAR WIDTH OF AN ACCESSIBLE ROUTE OR MANEUVERING
 SPACE [SEE FIGURE 11-8 (E)].
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-01-12 Cont ID  
Sent By btrobaug Date 2007-01-12 Time 15:48 Rev Time 0.75
Received By btrobaug Date 2007-01-12 Time 15:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-11-07 Cont ID  
Sent By btrobaug Date 2006-11-07 Time 13:08 Rev Time 1.00
Received By btrobaug Date 2006-11-07 Time 08:19 Sent To I
Notes
2006-11-07 13:07:58 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} INDICATE COMPLIANCE WITH CHAPTER 13
 OF THE FLORIDA BLDG CODE. 13.413,
 13.414, 13.415. SHOW TIME CLOCK AND
 OCCUPANCY SENSOR LOCATIONS ON THE PLAN.
  
 2} PROVIDE PERFORMANCE CALCULATIONS FOR REVIEW PER
 13-415.2.AND CERTIFICATION PER 13-103.1.2.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-01-16 Cont ID  
Sent By mawillia Date 2007-01-16 Time 12:02 Rev Time 0.00
Received By mawillia Date 2007-01-16 Time 12:02 Sent To  
Notes
2007-01-16 12:04:41*****APPROVED*****
  
  
 PLAN SHEETS E-2 AND FP-1 WERE STAMPED, INITIALED, AND
 DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-12-04 Cont ID  
Sent By mawillia Date 2006-12-04 Time 15:30 Rev Time 0.00
Received By mawillia Date 2006-12-04 Time 15:30 Sent To  
Notes
2006-12-04 15:49:54*****UNSAT*****
  
  
  
 1.NFPA 101 - 2003 EDITION AND THE FLORIDA FIRE
 PREVENTION CODE - 2004 EDITION SHALL BE REFERENCED.
  
 2.AMEND SHEET A-1.01, KEYED NOTE #1, TO READ 2A:10BC
 FIRE EXTINGUISHER.
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-03-22 Cont ID  
Sent By adarroug Date 2007-03-22 Time 16:18 Rev Time 0.00
Received By adarroug Date 2007-03-22 Time 16:18 Sent To E
Notes
2007-03-22 16:18:35TO "BTROBAUG' DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status   Date 2007-03-22 Cont ID  
Sent By adarroug Date 2007-03-22 Time 16:14 Rev Time 0.00
Received By adarroug Date 2007-03-22 Time 16:14 Sent To  
Notes
2007-03-22 16:15:48TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-03-22 Cont ID  
Sent By adarroug Date 2007-03-22 Time 16:12 Rev Time 0.00
Received By adarroug Date 2007-03-22 Time 16:12 Sent To  
Notes
2007-03-22 16:13:07TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-01-09 Cont ID  
Sent By adarroug Date 2006-12-28 Time 14:24 Rev Time 0.00
Received By adarroug Date 2006-12-28 Time 14:31 Sent To  
Notes
2007-01-09 14:25:07TO "BOB"#15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-12-12 Cont ID  
Sent By jwitmer Date 2006-12-12 Time 16:49 Rev Time 0.00
Received By jwitmer Date 2006-11-08 Time 16:52 Sent To  
Notes
2006-11-20 16:21:38TO "BOB"#7
2006-11-08 16:52:42WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-03-28 Cont ID  
Sent By tgordon Date 2007-03-28 Time 09:50 Rev Time 0.25
Received By tgordon Date 2007-03-28 Time 09:50 Sent To  
Notes
2007-03-28 09:51:25MECHANICAL REVISION TO PLANS PAGE M-1.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-11-22 Cont ID  
Sent By tgordon Date 2006-11-22 Time 15:45 Rev Time 0.30
Received By tgordon Date 2006-11-22 Time 15:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-04-05 Cont ID  
Sent By jleech Date 2007-04-05 Time 09:11 Rev Time 0.00
Received By jleech Date 2007-04-05 Time 09:11 Sent To  
Notes
2007-04-05 09:15:35PROVISO;
  
 AIR ADMITTANCE VALVES CAN BE USED ON THE TOP 4 FLOOR OF
 BUILDING. SUBJECT TO FIELD INSPECTION. FBC-2004
 PLUMBING SECTION 917.3.1.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-01-16 Cont ID  
Sent By jleech Date 2007-01-16 Time 08:23 Rev Time 0.00
Received By jleech Date 2007-01-16 Time 08:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-12-06 Cont ID  
Sent By jleech Date 2006-12-06 Time 14:20 Rev Time 0.00
Received By jleech Date 2006-12-06 Time 14:20 Sent To  
Notes
2006-12-06 14:31:33DENIED;
 1. BREAK SINK;GARBAGE DISPOSAL WILL NOT ALLOW A
 FRONTAL APPROACH UNDER SINK. SEE FBC-2004 BUILDING
 CHAPTER 11 SECTION 11-4.24.3 KNEECLEARANCE.
 2. PLEASE ADD NOTES TO INTERIOR ELEVATION DETAIL 01 ON
 PAGE A-3.01;
 DEPTH OF SINK 6 1/2 " DEEP MAX.
 SEC11-4.23.4
 RAP EXPOSED PIPES. SEC. 11-4.24.6
 SPECIFY TYPE OF HANDLES ON SINK FAUSET
 SEC. 11-4.24.7.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695