Plan Review Details - Permit 06110142
Plan Review Stops For Permit 06110142
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-01-11 Cont ID  
Sent By jwitmer Date 2007-01-11 Time 10:03 Rev Time 1.33
Received By jwitmer Date 2007-01-11 Time 10:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-12-12 Cont ID  
Sent By jwitmer Date 2006-12-12 Time 16:27 Rev Time 0.77
Received By jwitmer Date 2006-12-12 Time 16:27 Sent To PC
Notes
2006-12-12 16:42:09BUILDING PLAN REVIEW
 PERMIT: 06110142
 ADD: 500 S AUSTRALIAN AV9TH FLOOR COMMON
 CORRIDOR
 CONT: KARL CORP CONSTRUCTION
 TEL: (561)718-3799
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 *** 2004 EXISTING BUILDING CODE
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 PLANS INDICATEA TYPE II BUILDING, TYPE "A OR B"
 DE)IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 3)PLEASE PROVIDE WALL AND CEILING CLASSIFICATION.
 TABLE 803.5 REQUIRED BY OCCUPANCY
 GENERAL.
 INTERIOR WALL AND CEILING FINISHES SHALL BE CLASSIFIED
 IN ACCORDANCE WITH ASTM E 84. SUCH INTERIOR FINISH
 MATERIALS SHALL BE GROUPED IN THE FOLLOWING CLASSES IN
 ACCORDANCE WITH THEIR FLAME SPREAD AND SMOKE-DEVELOPED
 INDEX.
 CLASS A:
 FLAME SPREAD INDEX 0-25; SMOKE-DEVELOPED INDEX 0-450.
 CLASS B:
 FLAME SPREAD INDEX 26-75; SMOKE-DEVELOPED INDEX 0-450.
  
 CLASS C:
 FLAME SPREAD INDEX 76-200; SMOKE-DEVELOPED INDEX 0-450.
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-01-12 Cont ID  
Sent By btrobaug Date 2007-01-12 Time 16:00 Rev Time 0.50
Received By btrobaug Date 2007-01-12 Time 15:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-11-07 Cont ID  
Sent By btrobaug Date 2006-11-07 Time 08:09 Rev Time 0.50
Received By btrobaug Date 2006-11-07 Time 06:40 Sent To I
Notes
2006-11-07 08:09:00 
  
 DENIED/INCOMPLETE INFORMATION
  
 1}INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS FOR
 DEVICES AND LIGHTING CIRCUITS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-01-16 Cont ID  
Sent By mawillia Date 2007-01-16 Time 12:44 Rev Time 0.00
Received By mawillia Date 2007-01-16 Time 12:44 Sent To  
Notes
2007-01-16 12:45:30*****APPROVED*****
  
  
 PLAN SHEETS E-1 AND FP-1 WERE STAMPED, INITIALED, AND
 DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-12-04 Cont ID  
Sent By mawillia Date 2006-12-04 Time 13:37 Rev Time 0.00
Received By mawillia Date 2006-12-04 Time 13:37 Sent To  
Notes
2006-12-04 14:33:24****DENIED*****
  
  
  
 1. NFPA 101 - 2003 EDITION AND THE FLORIDA FIRE
 PREVENTION CODE - 2004 EDITION SHALL BE REFERENCED.
  
 2.CONSTRUCTION OPERATIONS SHALL NOT INTERFERE OR
 HINDER EMERGENCY ACCESS TO THE SAID PROPERTY OR
 VICINITY THEREOF
  
 3.ON THE APPROPIATE ELEVATION DETAIL, SHOW/DISPLAY
 THE NUMERICAL ADDRESS OF THIS BUILDING FRONTING MERRY
 PLACE.AS PER WEST PALM BEACH CODE, THOSE NUMBERS
 SHALL BE NO LESS THAN 6" IN HEIGHT AND 1" IN WIDTH.
 INDIVIDUAL APARTMENT/UNIT SHALL BE NO LESS THAN 3" IN
 HEIGHT.
  
 4.THE ADDRESS OF THE STRUCTURE SHALL BE IN THE TITLE
 BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 5.FIRE EXTINGUISHERS ARE TO BE 2A-10BC RATED.
  
 6.AS PER NFPA 101 - 10.2.8.1 -2003 EDITION,
 INTERIOR FINISH FOR WALLS AND CEILINGS IN AN
 UNSPRINKLERED BUILDING SHALL BE CLASS "A" OR CLASS
 "B".
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-03-22 Cont ID  
Sent By adarroug Date 2007-03-22 Time 11:56 Rev Time 0.00
Received By adarroug Date 2007-03-22 Time 11:56 Sent To M
Notes
2007-03-22 11:57:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-12-28 Cont ID  
Sent By adarroug Date 2006-12-28 Time 14:13 Rev Time 0.00
Received By adarroug Date 2006-12-28 Time 14:12 Sent To  
Notes
2007-01-09 14:25:30TO "BOB"#16
2006-12-28 14:13:29WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-12-12 Cont ID  
Sent By jwitmer Date 2006-12-12 Time 16:27 Rev Time 0.00
Received By jwitmer Date 2006-11-08 Time 16:51 Sent To  
Notes
2006-11-20 16:11:44TO "BOB"#2
2006-11-08 16:52:11WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-03-28 Cont ID  
Sent By tgordon Date 2007-03-28 Time 10:01 Rev Time 0.20
Received By tgordon Date 2007-03-28 Time 10:01 Sent To  
Notes
2007-03-28 10:02:22REVISION TO MECH. PLANS PAGE M-1.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-01-10 Cont ID  
Sent By tgordon Date 2007-01-10 Time 13:49 Rev Time 0.30
Received By tgordon Date 2007-01-10 Time 13:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-12-05 Cont ID  
Sent By tgordon Date 2006-12-05 Time 15:45 Rev Time 0.45
Received By tgordon Date 2006-12-05 Time 15:45 Sent To  
Notes
2006-12-05 15:51:25*** DENIED ***
 1) DUCTS PASSING THROUGH RATED WALLS AND OVER RATED
 DOORS REQUIRE FIRE DAMPERS, SEE 2004 FBC/M 607.5.3.
  
 2) 14" FLEX DUCT MAY NOT PASS THROUGH A FIRE RATED WALL
 OR OVER A RATED DOOR, SEE 2004 FBC/M 607.7.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-12-09 Cont ID  
Sent By jleech Date 2006-12-09 Time 08:50 Rev Time 0.00
Received By jleech Date 2006-12-09 Time 08:50 Sent To  
Notes
2006-12-09 08:51:20NO PLUMBING SHOWN ON DRAWINGS.