Plan Review Details - Permit 06110137
Plan Review Stops For Permit 06110137
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-01-24 Cont ID  
Sent By shill Date 2007-01-24 Time 10:55 Rev Time 0.00
Received By shill Date 2007-01-24 Time 10:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-12-18 Cont ID  
Sent By shill Date 2006-12-18 Time 08:27 Rev Time 0.00
Received By shill Date 2006-12-18 Time 08:27 Sent To  
Notes
2006-12-18 08:56:29****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC EB
 FLORIDA BUILDING CODE 2004 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
  
 1.)A002, CODE ANALYSIS, BUILDING TYPE, DECLARE A OR B
 FBC 601.
  
 2.)A002, EXISTING BUILDING IS DECLARED AS R, NEW
 OCCUPANCY IS A-1 AND R-1, BUT THE PLANS SHOW THAT THIS
 IS A RENOVATION TO AN EXISTING KITCHEN.IS THIS A
 CHANGE OF OCCUPANCY?
  
 3.)DECLARE GOVERNING CODE.INCLUDE FLORIDA BUILDING
 CODE 2004 EXISTING BUILDING CODE.
  
 4.)DELCARE LEVEL OF ALTERATION FBC EB CHAPTER 3.
  
 5.)IF THIS IS A CHANGE OF OCCUPANCY, THE RENOVATION
 IS TO COMPLY WITH FBC EB CHAPTER 8.PLEASE INDICATE ON
 THE PLAN AND SHOW COMPLIANCE.
  
 6.)SHEET A002 REFERS TO FIRE RESISTANCE REQUIREMENTS,
 FBC TABLE 600.THIS IS FROM FBC2001.SEE FBC TABLE
 601, FBC TABLE 602, FBC CHAPTER 7.
  
 7.)CODE ANALYSIS, A002, FIRE RESISTANCE, INTERIOR
 NONBEARING PARTITIONS, CODE REFERENCES ARE FBC2001.
 PLEASE REVISE OR REMOVE.
  
 8.)CODE ANALYSIS, FIRE RESISTANCE, A002, EXTERIOR
 BEARING WALLS, SHOWS A 4 HOUR WALL WITH NO LIMIT ON
 OPENINGS.PLEASE CLARIFY WHAT THIS MEANS OR HOW IT
 PERTAINS TO THIS PLAN.
  
 9.)A0002, CODE ANALYSIS, FIRE RESISTANCE OF EXIT
 ACCESS CORRIDORS, OCCUPANCY R1, SHOULD BE 1 HOUR, 1/2
 HOUR IS SHOWN.FBC TABLE 1016.1.
  
 10.)EXIT REQUIREMENTS, FBC TABLE 1004, IS ALSO A
 REFERENCE FROM FBC2001.REVISE AND CHECK ALL CODE
 REFERENCES TO BE CONSISTENT WITH FBC2004.
  
 11.)SHOW OCCUPANCY CLASSIFICATION FOR THE RENOVATED
 AREA AS WELL AS ADJACENT OCCUPANCY CLASSIFICATION. SHOW
 ANY REQUIRED FIRE RESISTANCE RATINGS ON THE FLOOR
 PLAN.
  
 12.)INDICATE TRAVEL DISTANCE TO EXITS ON THE PLAN.
  
 13.)WHERE SPRINKLERS ARE REQUIRED FOR CODE
 COMPLIANCE, FIRE SPRINKLER PLANS ARE TO BE A PART OF
 THE PERMIT PACKAGE.SEE ATTACHED LETTER FROM DCA.
 CALCULATIONS AND SHOPS ARE NOT REQUIRED AT THIS TIME;
 SUBMIT WITH SEPARATE PERMIT.A FIRE SPRINKLER LAYOUT
 IS REQUIRED IF THE SYSTEM IS TO BE MODIFIED.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-01-23 Cont ID  
Sent By btrobaug Date 2007-01-23 Time 15:17 Rev Time 0.75
Received By btrobaug Date 2007-01-23 Time 12:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-11-21 Cont ID  
Sent By btrobaug Date 2006-11-21 Time 13:50 Rev Time 1.00
Received By btrobaug Date 2006-11-21 Time 12:09 Sent To  
Notes
2006-11-21 13:50:36 
  
 NONCOMPLIANT/INCOMPLETE INFORMATION
  
  
 PLEASE PROVIDE ELECTRICAL PLANS PER 106.3.5.1.2 FBC, AS
 AMENDED, FOR ALL NEW INSTALLATIONS AND AFFECTED
 EXISTING INSTALLATIONS.
  
 PROVIDE A PANEL SCHEDULE WITH BRANCH CIRCUIT NUMBERS,
 OCP AND CONDUCTOR SIZE. THE EQUIPMENT SCHEDULE DOES NOT
 SATISFY THIS REQUIREMENT.
  
 INDICATE THE CIRCUIT NUMBERS AT TTHE DEVICES.
  
 INDICATE PANEL LOCATION ON THE ELECTRICAL PLAN
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-01-16 Cont ID  
Sent By mawillia Date 2007-01-16 Time 12:58 Rev Time 0.00
Received By mawillia Date 2007-01-16 Time 12:58 Sent To  
Notes
2007-01-16 13:19:22*****APPROVED*****
  
  
 ALL PREVIOUS FIRE PLAN REVIEW COMMENTS OF 12/12/2006
 HAVE BEEN ADDRESSED

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-12-12 Cont ID  
Sent By mawillia Date 2006-12-12 Time 10:50 Rev Time 0.00
Received By mawillia Date 2006-12-12 Time 10:50 Sent To  
Notes
2006-12-12 11:47:04*****DENIED*****
  
  
  
 1.THE ADDRESS ON THE SUBMITTED PLANS DO NOT MATCH THE
 ADDRESS ON THE PERMIT APPLICATION OR IN THE CITY'S
 PERMITTING SYSTEM.THE CORRECT ADDRESS SHALL BE IN THE
 TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 2.NFPA 101 (2003 EDITION), FLORIDA FIRE PREVENTION
 CODE (2004 EDITION), NFPA 13 (2002 EDITION), AND NFPA
 72 (2002 EDITION) SHALL BE REFERENCED FOR FIRE AND LIFE
 SAFETY CONCERNS.AMEND SHEET A002, GENERAL NOTE #1.
  
 3.CONSTRUCTION, ALTERATION, OR DEMOLITION OPERATIONS
 SHALL COMPLY WITH NFPA 241.ADD TO DEMO NOTES.
  
 4.COMBUSTIBLE WASTE, DUST, AND DEBRIS SHALL BE
 REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR MORE
 FREQUENTLY AS NECESSARY FOR SAFE OPERATION.ADD TO
 DEMO NOTES.
  
 5.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 INTERFERE OR HINDER ACCESS TO OR EGRESS FROM OTHER
 AREAS OF THE BUILDING.ADD TO DEMO NOTES
  
 6.IF THE FIRE ALARM AND/OR FIRE SPRINKLER SYSTEM IS
 MODIFIED DUE TO THE SCOPE OF WORK, SEPARATE PLANS AND
 PERMIT ARE REQUIRED.
  
 7.SEPARATE MECHANICAL PERMITS WILL BE REQUIRED FOR
 THE HOOD/FIRE SUPPRESSION SYSTEM.
  
 8.PROVIDE INTERIOR FINISH CLASSIFICATION INFORMATION
 FOR WALLS AND CEILINGS TO BE INSTALLED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2007-05-31 Cont ID  
Sent By kstevens Date 2007-05-31 Time 17:00 Rev Time 0.00
Received By kstevens Date 2007-05-31 Time 17:00 Sent To  
Notes
2007-05-31 17:00:43 
  
  
  
 REVISION OK--SHT P200

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-03-17 Cont ID  
Sent By kstevens Date 2007-03-17 Time 12:47 Rev Time 0.00
Received By kstevens Date 2007-03-17 Time 12:47 Sent To  
Notes
2007-03-17 12:50:26PASSED/PROVISO:
  
 1. REVIEW BASED ON SCHEDULE 40 PIPE FOR KITCHEN GAS
 APPLIANCES.
 2. SHUT OFF VALVE, REGULATOR, & UNION TO BE LOCATED
 BELOW THE CEILING.
 3. THE REGULATOR SHALL BE APPROVED AND CORRECT MODEL
 USED.
 4. A UNION IS REQUIRED DOWNSTREAM OF THE MANUAL SHUT
 OFF VALVE AND PRIOR TO THE THE INTERLOCK VALVE.

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2006-12-16 Cont ID  
Sent By pschmitz Date 2006-12-16 Time 13:56 Rev Time 0.00
Received By pschmitz Date 2006-12-16 Time 13:46 Sent To  
Notes
2006-12-16 13:56:15SEE SHT P001 FOR LIST OF EX GAS APPLIANCES.
 TO BE VERIFIED BY FIELD INSPECTOR.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-05-18 Cont ID  
Sent By adarroug Date 2007-05-18 Time 14:19 Rev Time 0.00
Received By adarroug Date 2007-05-18 Time 14:19 Sent To G
Notes
2007-05-18 14:20:37TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-03-13 Cont ID  
Sent By adarroug Date 2007-03-13 Time 13:36 Rev Time 0.00
Received By adarroug Date 2007-03-13 Time 13:36 Sent To P
Notes
2007-03-13 13:37:04TO "TGORDON" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-01-09 Cont ID  
Sent By adarroug Date 2007-01-09 Time 15:53 Rev Time 0.00
Received By adarroug Date 2007-01-09 Time 15:53 Sent To  
Notes
2007-01-09 15:54:03TO "BOB"#8--EXPEDITED PERMIT--

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-12-19 Cont ID  
Sent By rbrown Date 2006-12-18 Time 17:38 Rev Time 0.00
Received By rbrown Date 2006-11-08 Time 16:54 Sent To  
Notes
2006-11-20 16:27:24TO "BOB"#10
2006-11-08 16:55:15WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-01-12 Cont ID  
Sent By tgordon Date 2007-01-12 Time 13:35 Rev Time 0.45
Received By tgordon Date 2007-01-12 Time 13:35 Sent To  
Notes
2007-01-12 13:39:10PLANS FOR KITCHEN HOOD ARE WITH MASTER PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-11-27 Cont ID  
Sent By tgordon Date 2006-11-27 Time 08:42 Rev Time 0.45
Received By tgordon Date 2006-11-27 Time 08:42 Sent To  
Notes
2006-11-27 08:49:32*** DENIED ***
 1) NEED ENGINEER OF RECORDS (CHARLES SZOLLOSY) TO
 APPROVE HOOD SHOP DRAWINGS BY CAPTIVE AIRE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-05-31 Cont ID  
Sent By kstevens Date 2007-05-31 Time 17:00 Rev Time 0.00
Received By kstevens Date 2007-05-31 Time 17:00 Sent To  
Notes
2007-05-31 17:01:36 
  
  
  
 REVISION OK--SHT P100

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-03-17 Cont ID  
Sent By kstevens Date 2007-03-16 Time 12:53 Rev Time 0.00
Received By kstevens Date 2007-03-16 Time 12:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-01-20 Cont ID  
Sent By kstevens Date 2007-01-20 Time 17:40 Rev Time 0.00
Received By kstevens Date 2007-01-20 Time 17:39 Sent To  
Notes
2007-01-20 18:04:08DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 A. FROM PREVIOUS REVIEW:
  
 1. PLANS SHALL BE ROUTED TO DBPR BUSINESS AND HOTEL
 DIVISION FOR REVIEW. MINIMUM 2 SETS OF PLANS SHALL BE
 REVIEWED AND STAMPED AND THE TWO PAGE "WORKSHEETS"
 ATTACHED TO EACH SET OF PLANS PRIOR TO RESUBMITTING TO
 CITY OF WEST PALM BEACH FOR REVIEW. PLEASE CONTACT DBPR
 AT (850) 487-1395.
 ****RESPONSE NOTED INDICATING "WE WILL COMPLY", BUT THE
 STAMPED PLANS WITH WORKSHEETS WERE NOT SUBMITTED.
  
 2. RE: GREASE WASTE SYSTEM CONTACT WPB WATER PLANT LAB
 SUPERVISOR INDUSTRIAL COORDINATOR, LYNN MASSON. OFFICE
 (561) 822-2271, E-MAIL [email protected]. ****RESPONSE
 NOTED, BUT CONFIRMATION IS REQUIRED FROM THE
 ENVIRONMENTAL COMPLIANCE MANAGER. I WILL CONFIRM THIS
 WITH THEM.
  
 3. OK
 4. OK
  
 THERE IS A NOTE COMMENTING ABOUT THE EXTENSIVE NUMBER
 OF COMMENTS MADE TO THIS SET. - THE COMMENT ABOUT DBPR
 STAMP AND THE WORKSHEET WAS NOT COMPLETLY ADDRESSED FOR
 THE PREVIOUS PERMIT APPLICATION. BE THAT AS IT MAY,
 WITH PRIOR NOTICE OF THIS REQUIREMENT, THIS SHOULD NOT
 HAVE BEEN AN ISSUE AT THIS REVIEW. ALSO THE REQUIREMENT
 FOR THE GREASE INTERCEPTOR WAS ADDRESSED DURING THE
 PRIOR REVIEW PROCESS, BUT SINCE MR. SCHMITZ DID NOT DO
 THE ORIGINAL PLAN REVIEW HE HAD NO PRIOR KNOWLEDGE OF
 THE HISTORY OF THE GREASE INTERCEPTOR. I WILL MAKE SURE
 THE PRIOR APPROVAL IS STILL OK.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-12-16 Cont ID  
Sent By pschmitz Date 2006-12-16 Time 11:36 Rev Time 0.00
Received By pschmitz Date 2006-12-16 Time 11:36 Sent To  
Notes
2006-12-16 11:49:02 
 PAUL SCHMITZ
 [email protected] FBC 2004 PLUMBING
 CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE
  
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
 PLUMBING DENIED
  
 1) PLANS SHALL BE ROUTED TO DBPR
 BUSINESS AND HOTEL DIVISION FOR
 REVIEW. MINIMUM 2 SETS OF PLANS
 SHALL BE REVIEWED AND STAMPED
 AND THE TWO PAGE ?WORKSHEETS?
 ATTACHED TO EACH SET OF PLANS
 PRIOR TO RESUBMITTING TO CITY OF WEST PALM BEACH
 FOR REVIEW. PLEASE CONTACT DBPR
 AT (850) 487-1395.
  
 2) RE: GREASE WASTE SYSTEM
 CONTACT W P BEACHWATERPLANT LAB SUPERVISOR
 INDUSTRIAL COORDINATOR, LYNN MASSON
  
 OFFICE 561-822-2271E-MAIL [email protected]
  
 3) SHT 100,SEC 604.9 WATER HAMMER.
 THE FLOW VELOCITY OF THE WATER DISTRIBUTION SYSTEM
 SHALL BE CONTROLLED TO REDUCE THE POSSIBILITY OF WATER
 HAMMER. A WATER-HAMMER ARRESTOR SHALL BE INSTALLED
 WHERE QUICK-CLOSING VALVES ARE UTILIZED. WATER-HAMMER
 ARRESTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER?S SPECIFICATIONS. WATER-HAMMER ARRESTORS
 SHALL CONFORM TO ASSE 1010.
  
 4) SHT P100 SEC 606.1 LOCATION OF FULL-OPEN VALVES.
 FULL-OPEN VALVES SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
 ON THE TOP OF EVERY WATER DOWN-FEED PIPE IN OCCUPANCIES
 OTHER THAN ONE- AND TWO-FAMILY RESIDENTIAL
 OCCUPANCIES.
  
 5) SEE OTHER PLAN REVIEW COMMENTS, THAT MAY EFFECT
 PLUMBING PLAN REVIEW.
  
 END OF COMMENTS, QUESTIONS 561-805-6692


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved