| Plan Review Stops For Permit 06110137 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2007-01-24 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-01-24 |
Time |
10:55 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-01-24 |
Time |
10:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-12-18 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-12-18 |
Time |
08:27 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-12-18 |
Time |
08:27 |
Sent To |
|
|
| Notes |
| 2006-12-18 08:56:29 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC EB | | | FLORIDA BUILDING CODE 2004 EXISTING BUILDING CODE | | | FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE | | | FBC2004 | | | | | | 1.)A002, CODE ANALYSIS, BUILDING TYPE, DECLARE A OR B | | | FBC 601. | | | | | | 2.)A002, EXISTING BUILDING IS DECLARED AS R, NEW | | | OCCUPANCY IS A-1 AND R-1, BUT THE PLANS SHOW THAT THIS | | | IS A RENOVATION TO AN EXISTING KITCHEN.IS THIS A | | | CHANGE OF OCCUPANCY? | | | | | | 3.)DECLARE GOVERNING CODE.INCLUDE FLORIDA BUILDING | | | CODE 2004 EXISTING BUILDING CODE. | | | | | | 4.)DELCARE LEVEL OF ALTERATION FBC EB CHAPTER 3. | | | | | | 5.)IF THIS IS A CHANGE OF OCCUPANCY, THE RENOVATION | | | IS TO COMPLY WITH FBC EB CHAPTER 8.PLEASE INDICATE ON | | | THE PLAN AND SHOW COMPLIANCE. | | | | | | 6.)SHEET A002 REFERS TO FIRE RESISTANCE REQUIREMENTS, | | | FBC TABLE 600.THIS IS FROM FBC2001.SEE FBC TABLE | | | 601, FBC TABLE 602, FBC CHAPTER 7. | | | | | | 7.)CODE ANALYSIS, A002, FIRE RESISTANCE, INTERIOR | | | NONBEARING PARTITIONS, CODE REFERENCES ARE FBC2001. | | | PLEASE REVISE OR REMOVE. | | | | | | 8.)CODE ANALYSIS, FIRE RESISTANCE, A002, EXTERIOR | | | BEARING WALLS, SHOWS A 4 HOUR WALL WITH NO LIMIT ON | | | OPENINGS.PLEASE CLARIFY WHAT THIS MEANS OR HOW IT | | | PERTAINS TO THIS PLAN. | | | | | | 9.)A0002, CODE ANALYSIS, FIRE RESISTANCE OF EXIT | | | ACCESS CORRIDORS, OCCUPANCY R1, SHOULD BE 1 HOUR, 1/2 | | | HOUR IS SHOWN.FBC TABLE 1016.1. | | | | | | 10.)EXIT REQUIREMENTS, FBC TABLE 1004, IS ALSO A | | | REFERENCE FROM FBC2001.REVISE AND CHECK ALL CODE | | | REFERENCES TO BE CONSISTENT WITH FBC2004. | | | | | | 11.)SHOW OCCUPANCY CLASSIFICATION FOR THE RENOVATED | | | AREA AS WELL AS ADJACENT OCCUPANCY CLASSIFICATION. SHOW | | | ANY REQUIRED FIRE RESISTANCE RATINGS ON THE FLOOR | | | PLAN. | | | | | | 12.)INDICATE TRAVEL DISTANCE TO EXITS ON THE PLAN. | | | | | | 13.)WHERE SPRINKLERS ARE REQUIRED FOR CODE | | | COMPLIANCE, FIRE SPRINKLER PLANS ARE TO BE A PART OF | | | THE PERMIT PACKAGE.SEE ATTACHED LETTER FROM DCA. | | | CALCULATIONS AND SHOPS ARE NOT REQUIRED AT THIS TIME; | | | SUBMIT WITH SEPARATE PERMIT.A FIRE SPRINKLER LAYOUT | | | IS REQUIRED IF THE SYSTEM IS TO BE MODIFIED. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2007-01-23 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-01-23 |
Time |
15:17 |
Rev Time |
0.75 |
| Received By |
btrobaug |
Date |
2007-01-23 |
Time |
12:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-11-21 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-11-21 |
Time |
13:50 |
Rev Time |
1.00 |
| Received By |
btrobaug |
Date |
2006-11-21 |
Time |
12:09 |
Sent To |
|
|
| Notes |
| 2006-11-21 13:50:36 | | | | | | | NONCOMPLIANT/INCOMPLETE INFORMATION | | | | | | | | | PLEASE PROVIDE ELECTRICAL PLANS PER 106.3.5.1.2 FBC, AS | | | AMENDED, FOR ALL NEW INSTALLATIONS AND AFFECTED | | | EXISTING INSTALLATIONS. | | | | | | PROVIDE A PANEL SCHEDULE WITH BRANCH CIRCUIT NUMBERS, | | | OCP AND CONDUCTOR SIZE. THE EQUIPMENT SCHEDULE DOES NOT | | | SATISFY THIS REQUIREMENT. | | | | | | INDICATE THE CIRCUIT NUMBERS AT TTHE DEVICES. | | | | | | INDICATE PANEL LOCATION ON THE ELECTRICAL PLAN | | | | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2007-01-16 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-01-16 |
Time |
12:58 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-01-16 |
Time |
12:58 |
Sent To |
|
|
| Notes |
| 2007-01-16 13:19:22 | *****APPROVED***** | | | | | | | | | ALL PREVIOUS FIRE PLAN REVIEW COMMENTS OF 12/12/2006 | | | HAVE BEEN ADDRESSED |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2006-12-12 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2006-12-12 |
Time |
10:50 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2006-12-12 |
Time |
10:50 |
Sent To |
|
|
| Notes |
| 2006-12-12 11:47:04 | *****DENIED***** | | | | | | | | | | | | 1.THE ADDRESS ON THE SUBMITTED PLANS DO NOT MATCH THE | | | ADDRESS ON THE PERMIT APPLICATION OR IN THE CITY'S | | | PERMITTING SYSTEM.THE CORRECT ADDRESS SHALL BE IN THE | | | TITLE BLOCK OF EACH SUBMITTED PLAN SHEET. | | | | | | 2.NFPA 101 (2003 EDITION), FLORIDA FIRE PREVENTION | | | CODE (2004 EDITION), NFPA 13 (2002 EDITION), AND NFPA | | | 72 (2002 EDITION) SHALL BE REFERENCED FOR FIRE AND LIFE | | | SAFETY CONCERNS.AMEND SHEET A002, GENERAL NOTE #1. | | | | | | 3.CONSTRUCTION, ALTERATION, OR DEMOLITION OPERATIONS | | | SHALL COMPLY WITH NFPA 241.ADD TO DEMO NOTES. | | | | | | 4.COMBUSTIBLE WASTE, DUST, AND DEBRIS SHALL BE | | | REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR MORE | | | FREQUENTLY AS NECESSARY FOR SAFE OPERATION.ADD TO | | | DEMO NOTES. | | | | | | 5.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT | | | INTERFERE OR HINDER ACCESS TO OR EGRESS FROM OTHER | | | AREAS OF THE BUILDING.ADD TO DEMO NOTES | | | | | | 6.IF THE FIRE ALARM AND/OR FIRE SPRINKLER SYSTEM IS | | | MODIFIED DUE TO THE SCOPE OF WORK, SEPARATE PLANS AND | | | PERMIT ARE REQUIRED. | | | | | | 7.SEPARATE MECHANICAL PERMITS WILL BE REQUIRED FOR | | | THE HOOD/FIRE SUPPRESSION SYSTEM. | | | | | | 8.PROVIDE INTERIOR FINISH CLASSIFICATION INFORMATION | | | FOR WALLS AND CEILINGS TO BE INSTALLED. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2007-05-31 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-05-31 |
Time |
17:00 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-05-31 |
Time |
17:00 |
Sent To |
|
|
| Notes |
| 2007-05-31 17:00:43 | | | | | | | | | | | | | REVISION OK--SHT P200 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2007-03-17 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-03-17 |
Time |
12:47 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-03-17 |
Time |
12:47 |
Sent To |
|
|
| Notes |
| 2007-03-17 12:50:26 | PASSED/PROVISO: | | | | | | 1. REVIEW BASED ON SCHEDULE 40 PIPE FOR KITCHEN GAS | | | APPLIANCES. | | | 2. SHUT OFF VALVE, REGULATOR, & UNION TO BE LOCATED | | | BELOW THE CEILING. | | | 3. THE REGULATOR SHALL BE APPROVED AND CORRECT MODEL | | | USED. | | | 4. A UNION IS REQUIRED DOWNSTREAM OF THE MANUAL SHUT | | | OFF VALVE AND PRIOR TO THE THE INTERLOCK VALVE. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2006-12-16 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-12-16 |
Time |
13:56 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-12-16 |
Time |
13:46 |
Sent To |
|
|
| Notes |
| 2006-12-16 13:56:15 | SEE SHT P001 FOR LIST OF EX GAS APPLIANCES. | | | TO BE VERIFIED BY FIELD INSPECTOR. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-05-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-05-18 |
Time |
14:19 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-05-18 |
Time |
14:19 |
Sent To |
G |
|
| Notes |
| 2007-05-18 14:20:37 | TO "G" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-03-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-03-13 |
Time |
13:36 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-03-13 |
Time |
13:36 |
Sent To |
P |
|
| Notes |
| 2007-03-13 13:37:04 | TO "TGORDON" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-01-09 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-01-09 |
Time |
15:53 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-01-09 |
Time |
15:53 |
Sent To |
|
|
| Notes |
| 2007-01-09 15:54:03 | TO "BOB"#8--EXPEDITED PERMIT-- |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-12-19 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2006-12-18 |
Time |
17:38 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2006-11-08 |
Time |
16:54 |
Sent To |
|
|
| Notes |
| 2006-11-20 16:27:24 | TO "BOB"#10 | | 2006-11-08 16:55:15 | WAITING FOR "BOB" |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2007-01-12 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-01-12 |
Time |
13:35 |
Rev Time |
0.45 |
| Received By |
tgordon |
Date |
2007-01-12 |
Time |
13:35 |
Sent To |
|
|
| Notes |
| 2007-01-12 13:39:10 | PLANS FOR KITCHEN HOOD ARE WITH MASTER PLANS. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2006-11-27 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-11-27 |
Time |
08:42 |
Rev Time |
0.45 |
| Received By |
tgordon |
Date |
2006-11-27 |
Time |
08:42 |
Sent To |
|
|
| Notes |
| 2006-11-27 08:49:32 | *** DENIED *** | | | 1) NEED ENGINEER OF RECORDS (CHARLES SZOLLOSY) TO | | | APPROVE HOOD SHOP DRAWINGS BY CAPTIVE AIRE. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2007-05-31 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-05-31 |
Time |
17:00 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-05-31 |
Time |
17:00 |
Sent To |
|
|
| Notes |
| 2007-05-31 17:01:36 | | | | | | | | | | | | | REVISION OK--SHT P100 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2007-03-17 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-03-16 |
Time |
12:53 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-03-16 |
Time |
12:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2007-01-20 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-01-20 |
Time |
17:40 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-01-20 |
Time |
17:39 |
Sent To |
|
|
| Notes |
| 2007-01-20 18:04:08 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 FUEL GAS | | | FBC-2004 CHAPTER 1 | | | | | | A. FROM PREVIOUS REVIEW: | | | | | | 1. PLANS SHALL BE ROUTED TO DBPR BUSINESS AND HOTEL | | | DIVISION FOR REVIEW. MINIMUM 2 SETS OF PLANS SHALL BE | | | REVIEWED AND STAMPED AND THE TWO PAGE "WORKSHEETS" | | | ATTACHED TO EACH SET OF PLANS PRIOR TO RESUBMITTING TO | | | CITY OF WEST PALM BEACH FOR REVIEW. PLEASE CONTACT DBPR | | | AT (850) 487-1395. | | | ****RESPONSE NOTED INDICATING "WE WILL COMPLY", BUT THE | | | STAMPED PLANS WITH WORKSHEETS WERE NOT SUBMITTED. | | | | | | 2. RE: GREASE WASTE SYSTEM CONTACT WPB WATER PLANT LAB | | | SUPERVISOR INDUSTRIAL COORDINATOR, LYNN MASSON. OFFICE | | | (561) 822-2271, E-MAIL [email protected]. ****RESPONSE | | | NOTED, BUT CONFIRMATION IS REQUIRED FROM THE | | | ENVIRONMENTAL COMPLIANCE MANAGER. I WILL CONFIRM THIS | | | WITH THEM. | | | | | | 3. OK | | | 4. OK | | | | | | THERE IS A NOTE COMMENTING ABOUT THE EXTENSIVE NUMBER | | | OF COMMENTS MADE TO THIS SET. - THE COMMENT ABOUT DBPR | | | STAMP AND THE WORKSHEET WAS NOT COMPLETLY ADDRESSED FOR | | | THE PREVIOUS PERMIT APPLICATION. BE THAT AS IT MAY, | | | WITH PRIOR NOTICE OF THIS REQUIREMENT, THIS SHOULD NOT | | | HAVE BEEN AN ISSUE AT THIS REVIEW. ALSO THE REQUIREMENT | | | FOR THE GREASE INTERCEPTOR WAS ADDRESSED DURING THE | | | PRIOR REVIEW PROCESS, BUT SINCE MR. SCHMITZ DID NOT DO | | | THE ORIGINAL PLAN REVIEW HE HAD NO PRIOR KNOWLEDGE OF | | | THE HISTORY OF THE GREASE INTERCEPTOR. I WILL MAKE SURE | | | THE PRIOR APPROVAL IS STILL OK. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2006-12-16 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-12-16 |
Time |
11:36 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-12-16 |
Time |
11:36 |
Sent To |
|
|
| Notes |
| 2006-12-16 11:49:02 | | | | PAUL SCHMITZ | | | [email protected] FBC 2004 PLUMBING | | | CODE PLAN REVIEW | | | FBC2004 FUEL GAS CODEPLAN REVIEW | | | FBC 2004 CH 11, FL ACESSIBILITY CODE | | | AMENDMENTS TO THE FLORIDA BUILDING CODE | | | | | | CHAPT.1, ADMINISTRATION, 2004 EDITION | | | | | | PLUMBING DENIED | | | | | | 1) PLANS SHALL BE ROUTED TO DBPR | | | BUSINESS AND HOTEL DIVISION FOR | | | REVIEW. MINIMUM 2 SETS OF PLANS | | | SHALL BE REVIEWED AND STAMPED | | | AND THE TWO PAGE ?WORKSHEETS? | | | ATTACHED TO EACH SET OF PLANS | | | PRIOR TO RESUBMITTING TO CITY OF WEST PALM BEACH | | | FOR REVIEW. PLEASE CONTACT DBPR | | | AT (850) 487-1395. | | | | | | 2) RE: GREASE WASTE SYSTEM | | | CONTACT W P BEACHWATERPLANT LAB SUPERVISOR | | | INDUSTRIAL COORDINATOR, LYNN MASSON | | | | | | OFFICE 561-822-2271E-MAIL [email protected] | | | | | | 3) SHT 100,SEC 604.9 WATER HAMMER. | | | THE FLOW VELOCITY OF THE WATER DISTRIBUTION SYSTEM | | | SHALL BE CONTROLLED TO REDUCE THE POSSIBILITY OF WATER | | | HAMMER. A WATER-HAMMER ARRESTOR SHALL BE INSTALLED | | | WHERE QUICK-CLOSING VALVES ARE UTILIZED. WATER-HAMMER | | | ARRESTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE | | | MANUFACTURER?S SPECIFICATIONS. WATER-HAMMER ARRESTORS | | | SHALL CONFORM TO ASSE 1010. | | | | | | 4) SHT P100 SEC 606.1 LOCATION OF FULL-OPEN VALVES. | | | FULL-OPEN VALVES SHALL BE INSTALLED IN THE FOLLOWING | | | LOCATIONS: | | | ON THE TOP OF EVERY WATER DOWN-FEED PIPE IN OCCUPANCIES | | | OTHER THAN ONE- AND TWO-FAMILY RESIDENTIAL | | | OCCUPANCIES. | | | | | | 5) SEE OTHER PLAN REVIEW COMMENTS, THAT MAY EFFECT | | | PLUMBING PLAN REVIEW. | | | | | | END OF COMMENTS, QUESTIONS 561-805-6692 |
|
|