Plan Review Details - Permit 06110096
Plan Review Stops For Permit 06110096
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2006-11-07 Cont ID  
Sent By lursu Date 2006-11-07 Time 08:16 Rev Time 0.00
Received By lursu Date 2006-11-07 Time 08:16 Sent To  
Notes
2006-11-07 08:17:27SINCE THIS UNITS IS PART OF THE CONDOMINIUM , THE NEW
 PCN ASSIGNED TO UNIT 105 IS , 74 43 43 19 22 000
 1050.PLS ATTACH PERMIT TO THIS RECORD.

Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-11-06 Cont ID  
Sent By lursu Date 2006-11-06 Time 11:24 Rev Time 0.00
Received By lursu Date 2006-11-06 Time 11:24 Sent To PC
Notes
2006-11-06 11:26:13CREATE THE NEW 10 DIGIT PCN= 7443431922.
 PERMIT MUST BE ATTACH TO UNIT #0001 FOR STE 105 UNDER
 THIS PCN.
 NOTICE OF COMMENCEMENT RECORDED ON THE INVALID PCN
 =74434319110000051.
 APPLICATION MUSTB ECORRECTED TO READ THE CORRECT PCN =
 7443431922.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 E-MAIL:[email protected]
2006-11-02 15:31:43DISCREPANCY REFERENCE PARCEL CONTROL NUMBER AND OWNER
 RECORD

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-01-10 Cont ID  
Sent By jwitmer Date 2007-01-10 Time 12:52 Rev Time 1.55
Received By jwitmer Date 2007-01-10 Time 12:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-01-05 Cont ID  
Sent By jwitmer Date 2007-01-05 Time 10:26 Rev Time 1.33
Received By jwitmer Date 2007-01-05 Time 10:26 Sent To P
Notes
2007-01-05 11:09:43PERMIT: 06110096
 ADD: 2247 PALM BEACH LAKES BLVD,SUITE 105
 CONT: AMODIE ENGINEERING & CONSTRUCTION
 TEL: (561)685-7500
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 2) 2ND REQUEST, 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) COMPLIED.
 B) COMPLIED.
  
 C) THE TYPE OF CONSTRUCTION"FOR THE BUILDING"
 AS DEFINED IN CHAPTER 6, TABLE 503.
 THIS WILL DEFINE WHAT MATERIALS WILL OR WILL
 NOT BE ALLOWED IN THIS STRUCTURE.
 THE RESPONCE INDICATED A TYPE V BUILDING NOT INDICATING
 A OR B,
 AND TO THE ANSWER TO QUESTION "E" SPRINKLERS NOT
 REQUIRED.
 THIS BUILDING IS APPROX 12,500 SQ FT IN FOOTPRINT,
 TABLE 503ONLY ALLOWS 9.000SF
 FOR A TYPE V-B BUILDING. EITHER THIS IS A TYPE V-A OR
 TYPE V-B WITH AREA INCREASES
 OR THE AREA INCREASES FOR FIRE SPRINKLERS.
  
 D) COMPLIED.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 G) COMPLIED.
 H) LEVEL OF ALTERATIONS? 2004 EXISTING BUILDING CODE,
 SEE LEVEL 2, CHAPTER II.
  
 3) COMPLIED.
  
 4) COMPLIED.PRIVATE RESTROOMS ARE TO BE
 ADAPTABLE.11-4.1.3(11)
 ( REQUIRES BACKING IN WALLS.)
  
 5) 2ND REQUEST, YOUR RESPONCE TO A BREAK ROOM SINK
 VS A WORK SINK, WHAT TYPE OF WORK WILL BE ACCOMPLISHED
 THAT WILL TRANSFORM THISFROM A BREAK ROOM SINK TO A
 WORK SINK?
 WHEN THE E SHEETS SHOW THERE TO BE AN UNDER COUNTER
 REFRIGARATOR AND A GARBAGE DISPOSAL
 IT APPEARS THIS IS TRUELY A BREAK ROOM SINK.
 PLEASE SEE,11-4.24.2 SINKS, HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER NO HIGHER
 THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
  
  
 6) COMPLIED.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-11-27 Cont ID  
Sent By jwitmer Date 2006-11-27 Time 07:27 Rev Time 0.77
Received By jwitmer Date 2006-11-27 Time 07:22 Sent To PC
Notes
2006-11-27 07:41:00BUILDING PLAN REVIEW
 PERMIT: 06110096
 ADD: 2247 PALM BEACH LAKES BLVD,SUITE 105
 CONT: AMODIE ENGINEERING & CONSTRUCTION
 TEL: (561)685-7500
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 2)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 G ) NUMBER OF FLOORS
 H) LEVEL OF ALTERATIONS?
  
 3) FP-1 INDICATES ALL INTERIOR WALLS ARE NEW, PLEASE
 INDICATE WHAT EACH ROOM WILL BE USEDFOR?
  
 4) THE PLUMBING RISER INDICATES THERE IS A RETSROOM
 WITHIN THE
 UNIT, PLEASE SEE 11-4.22.2 DOORS.
 (1)ALL DOORS TO ACCESSIBLE TOILET ROOMS SHALL
 COMPLY WITH SECTION
 11-4.13 . DOORS SHALL NOT SWING INTO THE CLEAR FLOOR
 SPACE REQUIRED
 FOR ANY FIXTURE. ALSO SEE 11-4.22 THE MINIMUM
 REQUIREMENTS FOR TOLIET ROOMS.
  
 5) THE PLUMBING ISOMETRIC ALSO APPEARS TO HAVE POSSIBLY
 A BREAK ROOM SINK,
 PLEASE SEE,11-4.24.2 SINKS, HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER NO HIGHER
 THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
  
  
 6) PLEASE ALSO SEE THE MINIMUM REQUIRED CLEARENCES AT
 DOORS:
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARANCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARANCES SHALL BE
 CLEAR & LEVEL.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-01-14 Cont ID  
Sent By dpalmer Date 2007-01-14 Time 18:29 Rev Time 0.00
Received By dpalmer Date 2007-01-14 Time 18:16 Sent To I
Notes
2007-01-14 18:30:42PLANS REMOVED FROM INCOMING AS CONTRACTOR CALLED AND
 SAID ELECTRICALWAS THE LAST REVIEW, HOWEVER PLANS ARE
 BEING ROUTED BACK TO INCOMING AS THERE ARE NEW FIRE
 SHEETS IN SETS WHICH NEED REVIEW AND STAMPING IF OK.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-12-21 Cont ID  
Sent By dpalmer Date 2006-12-21 Time 11:44 Rev Time 0.00
Received By dpalmer Date 2006-12-21 Time 11:23 Sent To  
Notes
2006-12-21 11:45:49** UNSAT 2ND REVIEW **
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING. PLEASE SEE THE NOTES BELOW ARE
 TAKEN DIRECTLY FROM PREVIOUS REVIEW WITH A NOTATION OF
 OK OR NO IF COMMENT WAS OR WAS NOT ADDRESS FULLY.
 PLEASE SEE SOMETIMES A NO/OK IS PLACED AHEAD OF THE
 NOTE AS THE NOTE MAY HAVE ONLY BEEN PARTIALLY
 ADDRESSED.
  
 ** PLEASE ALSO SEE SOME NEW COMMENTS BASED ON PLANS
 SUBMITTED. THESE NEW COMMENTS ARE AT THE END OF THE
 FIRST REVIEW COMMENTS.
  
  
 1) NOTE:NO, PLEASE SEE NO ADDRESS FOR LOCATION AND
 SUITE IS YET ON THE TITLE BLOCKS FOR SAID PROJECT.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G1-16.004,
 61G15-23.002
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE VERIFY WORK LOCATION. PLANS MENTIONS WORK FOR
 CONTRACTOR/ENGINEERING OFFICE PERMIT APPLICATION
 MENTIONS UNIT #105? PLEASE INCLUDE SUITE OF THE SCOPE
 OF WORK BEING DONE.
  
 2) NOTE: NO/OK, PLEASE SEE THE SIZE OF THE EXISTING
 PANEL "AM" IS STILL IN QUESTION AND THE LOCATION ON
 PLANS APPEARS TO SHOW THIS IN A ROOM, HOWEVER NOT CLEAR
 IF THIS PANEL IS IN ANOTHER TENANT SPACE, SEPARATELY
 METERED ETC.
 PLEASE CLARIFY FURTHER AND SHOW.
 FBC 106.1.2
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CLARIFY THE PANEL MENTIONED AS "AM" PLEASE
 CLARIFY WHERE THIS PANEL IS AND HOW THIS PANEL IF IN A
 SEPARATE SPACE FEEDS THIS SPACE.
 PLEASE ALSO SUBMIT LOAD CALCULATIONS FOR THIS EXISTING"
 AM" PANEL WITH NEW " LP" PANEL ADDED.
 THIS SCENARIO IS NOT CLEAR AT THIS TIME.
 220.3,220.10,220.11,220.13,CONTINUOUS LOADS PER
 215.3,230.42 ETC.
 FBC ADMINISTRATIVE SECTION 106.1.2, AS ADOPTED BY THE
 CITY OF WEST PALM BEACH.
  
 3) NOTE: NO, PLEASE SEE THE CODE SECTIONS AS GIVEN
 BELOW IN PREVIOUS REVIEW. PLEASE SEE THE RESPONSE
 MENTIONS A TIME CLOCK BEING ADDED, HOWEVER NO DETAIL
 FOR THIS IS SHOWN. NO SCHEDULING, NO OVER RIDE CONTROLS
 IN SPACES AS REQUIRED AND NO TIMES ON OVER RIDES.
 PLEASE SEE THE DEVICES AND SYSTEM AS BEING SELECTED BY
 THE DESIGNER SHALL BE INDICATED ON PLANS AND CORRELATE
 WITH THE SYMBOL LEGEND.
 PLEASE SEE SECTIONS AS GIVEN FOR MISSING LIGHTING POWER
 DENSITIES?
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THIS APPEAR AND IS BEING SHOWN AS A NEW
 TENANT BUILD OUT LOCATED IN A BUILDING GREATER THAN 5K
 SQ FT. PLEASE SEE FBC 2004, 13-415.1.ABC.1.1, .1.2 AND
 .1.3
 13-415.2.ABC.1
 ** NEW NOTE **
  
 1) NOTE: PLEASE BE SURE PLANS REFLECT THE FOLLOWING
 MINIMUM CODES AS REQUIRED. STATING THE LATEST EDITION
 MAY NOT APPLY AS DEPENDING ON PERMIT APPLICATION WAS
 MADE, THIS WILL DICTATE WHICH CODES THE PLANS ARE UNDER
 AND RELEVANT TO THE DESIGNS.
 THIS COMMENT WAS MISSED BY THIS REVIEWER ON PREVIOUS
 REVIEW, HOWEVER IS REQUIRED.
 PLEASE KNOW PERMIT APPLICATIONS BEFORE 12/8/06 WILL
 PLACE ELECTRICAL UNDER NFPA-70 2002 (NEC) , 2003
 NFPA-101, 2002 NFPA-72 AND REV #5 TO THE 2004 FBC.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-11-13 Cont ID  
Sent By dpalmer Date 2006-11-13 Time 14:33 Rev Time 0.00
Received By dpalmer Date 2006-11-13 Time 14:12 Sent To  
Notes
2006-11-13 14:34:43**** UNSAT ****
  
 1) NOTE: PLEASE VERIFY WORK LOCATION. PLANS MENTIONS
 WORK FOR CONTRACTOR/ENGINEERING OFFICE,PERMIT
 APPLICATION MENTIONS UNIT #105? PLEASE INCLUDE SUITE OF
 THE SCOPE OF WORK BEING DONE.
  
 2) NOTE: PLEASE CLARIFY THE PANEL MENTIONED AS "AM"
 PLEASE CLARIFY WHERE THIS PANEL IS AND HOW THIS PANEL
 IF IN A SEPARATE SPACE FEEDS THIS SPACE.
 PLEASE ALSO SUBMIT LOAD CALCULATIONS FOR THIS EXISTING"
 AM" PANEL WITH NEW " LP" PANEL ADDED.
 THIS SCENARIO IS NOT CLEAR AT THIS TIME.
 220.3,220.10,220.11,220.13,CONTINUOUS LOADS PER
 215.3,230.42 ETC.
 FBC ADMINISTRATIVE SECTION 106.1.2, AS ADOPTED BY THE
 CITY OF WEST PALM BEACH.
  
 3) NOTE: PLEASE SEE THIS APPEAR AND IS BEING SHOWN AS A
 NEW TENANT BUILD OUT LOCATED IN A BUILDING GREATER THAN
 5K SQ FT. PLEASE SEE FBC 2004, 13-415.1.ABC.1.1, .1.2
 AND .1.3
 13-415.2.ABC.1
 PLEASE ALSO AS THE SCOPE OF WORK APPEARS TO BE FOR A
 NEW TENANT BUILD OUT THIS WOULD BE REQUIRED.
  
 AS THE PLANS ARE NOT CLEAR WHERE THIS SPACE IS BEING
 FED FROM OR IF IT IS PART OF LARGER TENANT SPACE, THE
 COMMENTS MAY NOT BE COMPLETE AT THIS TIME.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-01-17 Cont ID  
Sent By mawillia Date 2007-01-17 Time 11:50 Rev Time 0.00
Received By mawillia Date 2007-01-17 Time 11:50 Sent To  
Notes
2007-01-17 12:01:10*****APPROVED*****
  
  
 PLAN SHEET F-1 STAMPED, INITIALED, AND DATED.
2007-01-14 18:24:56NEEDS REVIEW AS THERE ARE FIRE SHEETS WHICH ARE NEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-12-26 Cont ID  
Sent By mawillia Date 2006-12-26 Time 12:00 Rev Time 0.00
Received By mawillia Date 2006-12-26 Time 12:00 Sent To  
Notes
2006-12-26 12:08:44*****PROVISO*****
  
  
  
 1.THE ENTIRE ADDRESS OF WHERE THE SCOPE OF WORK IS
 BEING CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-11-20 Cont ID  
Sent By mawillia Date 2006-11-20 Time 09:31 Rev Time 0.00
Received By mawillia Date 2006-11-20 Time 09:31 Sent To  
Notes
2006-11-20 09:58:24****UNSAT****
  
  
  
 1.IN THE TITLE BLOCK OF THE SUBMITTED PLANS, THE
 ACTUAL LOCATION OF WHERE THE SCOPE OF WORK WILL BE
 CONDUCTED SHOULD BE INCLUDED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY.
  
 4.PLEASE PROVIDE EXISTING FLOOR PLAN THAT INCLUDES
 EXIT LIGHTS, EMERGENCY LIGHTS, FIRE EXTINGUISHER(S),
 ETC. FOR THIS TENANT SPACE.HOW WILL THEY BE AFFECTED
 BY THE SCOPE OF THE WORK?
  
 5.PLEASE DECLARE INTERIOR FINISH CLASSIFICATION FOR
 WALLS AND CEILINGS.
  
 6.IF THE FIRE ALARM AND SINCE THE SPRINKLER SYSTEM
 ARE MODIFIED BY THE SCOPE OF THE WORK, SEPARATE PLANS
 AND PERMIT ARE REQUIRED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE SHEET INDICATING HOW/WHERE EACH ITEM
 WAS ADDRESSED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-01-09 Cont ID  
Sent By adarroug Date 2007-01-09 Time 19:17 Rev Time 0.00
Received By adarroug Date 2007-01-09 Time 19:17 Sent To  
Notes
2007-01-09 19:17:34WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-12-01 Cont ID  
Sent By adarroug Date 2006-12-01 Time 16:21 Rev Time 0.00
Received By adarroug Date 2006-12-01 Time 16:21 Sent To  
Notes
2006-12-21 09:28:06TO "BOB"#1
2006-12-01 16:21:50WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-11-27 Cont ID  
Sent By jwitmer Date 2006-11-27 Time 07:22 Rev Time 0.00
Received By jwitmer Date 2006-11-06 Time 10:11 Sent To  
Notes
2006-11-12 14:07:22TO"BOB"#12
2006-11-06 10:12:44WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-11-13 Cont ID  
Sent By tgordon Date 2006-11-13 Time 09:35 Rev Time 0.30
Received By tgordon Date 2006-11-13 Time 09:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-01-10 Cont ID  
Sent By jleech Date 2007-01-10 Time 15:24 Rev Time 0.00
Received By jleech Date 2007-01-10 Time 15:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-01-06 Cont ID  
Sent By jleech Date 2007-01-06 Time 07:05 Rev Time 0.00
Received By jleech Date 2007-01-06 Time 06:32 Sent To  
Notes
2007-01-06 07:04:35DENIED;
 1. A PRIVATE TOILET ROOM IS FOR ONE PERSON NOT ALL 6
 EMPLOYEES. THIS IS A COMMON TOILET ROOM AND MUST COMPLY
 WITH FBC-2004 BUILDING CHAPTER 11. SEE SECTIONS
 11-4.1.3(11) AND 11-4.22.
 2. SINK IS NOT A WORK SINK. ELECTRICAL PLAN SHOWS AN
 OUTLET IN CABINET FOR A REF. AND GAR. DISP. SINK TO
 MEET HANDICAP REQUIREMENTS.
 3. SHOW CLEAR FRONTAL FLOORSPACEAT LACATORY AND
 SINK, AND TURNING RADIUS IN BATHROOM.
 4. SHOW DETAILS OF TOILET ROOM ,TOILET, LAVATORY AND
 SINK WITH ALL REQUIRED MEASUREMENTS.
 SEE THE FOLLOWING CODE SECTIONS FOR
 REFORANCE;
 TOILET:
 11-4.16.2 CLEAR FLOOR SPACE
 11-4.16.3 HEIGHT
 11-4.16.4 GRAB BAR
 11-4.16.5 FLUSH CONTROL
 11-4.16.6 DISPENSERS
 LAVATORY:
 11-4.19.2 HEIGHT AND CLEARANCE
 11-4.19.3 CLEAR FLOOR SPACE ( FRONTAL)
 11-4.19.4 EXPOSED PIPES
 11-4.19.5 FAUCET
 11-4.19.6 MIRROR
 SINK:
 11-4.24.2 HEIGHT
 11-4.24.3 KNEE CLEARANCE
 11-4.24.4 DEPTH OF SINK
 11-4.24.5 CLEAR FLOOR SPACE
 11-4.24.6 EXPOSED PIPES
 11-4.24.7 FAUCET
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-01-06 Cont ID  
Sent By jleech Date 2006-11-18 Time 10:01 Rev Time 0.00
Received By jleech Date 2006-11-18 Time 10:01 Sent To  
Notes
2006-11-18 10:09:57NOT ENOUGH INFORMATION;
 1. ARE THERE PUBLIC, HANDICAP TOILET ROOMS AND DRINKING
 FOUNTAINS?
 2. THE SINK BEING INSTALLED, IS IT A WORK SINK OR A
 BREAK SINK?
 3.HOW HIGH IS BUILDING? AIR ADMITTANCE VALVES SHALL
 COMPLY WITH FBC-2004 PLUMBING SECTION 917.3.1
 AAV'S CAN ONLY BE CONNECTED TO BUILDING DRAIN A
 MAXIMUM OF 4 BRANCH INTERALS FROM THE TOP OF THE
 STACK.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved