| Plan Review Stops For Permit 06110096 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
P |
Date |
2006-11-07 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2006-11-07 |
Time |
08:16 |
Rev Time |
0.00 |
| Received By |
lursu |
Date |
2006-11-07 |
Time |
08:16 |
Sent To |
|
|
| Notes |
| 2006-11-07 08:17:27 | SINCE THIS UNITS IS PART OF THE CONDOMINIUM , THE NEW | | | PCN ASSIGNED TO UNIT 105 IS , 74 43 43 19 22 000 | | | 1050.PLS ATTACH PERMIT TO THIS RECORD. |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2006-11-06 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2006-11-06 |
Time |
11:24 |
Rev Time |
0.00 |
| Received By |
lursu |
Date |
2006-11-06 |
Time |
11:24 |
Sent To |
PC |
|
| Notes |
| 2006-11-06 11:26:13 | CREATE THE NEW 10 DIGIT PCN= 7443431922. | | | PERMIT MUST BE ATTACH TO UNIT #0001 FOR STE 105 UNDER | | | THIS PCN. | | | NOTICE OF COMMENCEMENT RECORDED ON THE INVALID PCN | | | =74434319110000051. | | | APPLICATION MUSTB ECORRECTED TO READ THE CORRECT PCN = | | | 7443431922. | | | | | | LACRAMIOARA URSU | | | MIS - GIS SUPPORT SPECIALIST | | | E-MAIL:[email protected] | | 2006-11-02 15:31:43 | DISCREPANCY REFERENCE PARCEL CONTROL NUMBER AND OWNER | | | RECORD |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2007-01-10 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-01-10 |
Time |
12:52 |
Rev Time |
1.55 |
| Received By |
jwitmer |
Date |
2007-01-10 |
Time |
12:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-01-05 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-01-05 |
Time |
10:26 |
Rev Time |
1.33 |
| Received By |
jwitmer |
Date |
2007-01-05 |
Time |
10:26 |
Sent To |
P |
|
| Notes |
| 2007-01-05 11:09:43 | PERMIT: 06110096 | | | ADD: 2247 PALM BEACH LAKES BLVD,SUITE 105 | | | CONT: AMODIE ENGINEERING & CONSTRUCTION | | | TEL: (561)685-7500 | | | | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2NDREVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | | | | 2) 2ND REQUEST, 110.2* W. P. B. ADMINISTRATIVE | | | CODE, INFORMATION THAT IS REQUIRED FOR | | | RECORD KEEPING & FOR CERTIFICATE OF | | | OCCUPANCY: | | | A) COMPLIED. | | | B) COMPLIED. | | | | | | C) THE TYPE OF CONSTRUCTION"FOR THE BUILDING" | | | AS DEFINED IN CHAPTER 6, TABLE 503. | | | THIS WILL DEFINE WHAT MATERIALS WILL OR WILL | | | NOT BE ALLOWED IN THIS STRUCTURE. | | | THE RESPONCE INDICATED A TYPE V BUILDING NOT INDICATING | | | A OR B, | | | AND TO THE ANSWER TO QUESTION "E" SPRINKLERS NOT | | | REQUIRED. | | | THIS BUILDING IS APPROX 12,500 SQ FT IN FOOTPRINT, | | | TABLE 503ONLY ALLOWS 9.000SF | | | FOR A TYPE V-B BUILDING. EITHER THIS IS A TYPE V-A OR | | | TYPE V-B WITH AREA INCREASES | | | OR THE AREA INCREASES FOR FIRE SPRINKLERS. | | | | | | D) COMPLIED. | | | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS | | | PROVIDED, WHETHER THE SPRINKLER SYSTEM | | | IS REQUIRED. | | | F) ANY SPECIAL STIPULATIONS & CONDITIONS | | | OF THE BUILDING PERMIT. | | | G) COMPLIED. | | | H) LEVEL OF ALTERATIONS? 2004 EXISTING BUILDING CODE, | | | SEE LEVEL 2, CHAPTER II. | | | | | | 3) COMPLIED. | | | | | | 4) COMPLIED.PRIVATE RESTROOMS ARE TO BE | | | ADAPTABLE.11-4.1.3(11) | | | ( REQUIRES BACKING IN WALLS.) | | | | | | 5) 2ND REQUEST, YOUR RESPONCE TO A BREAK ROOM SINK | | | VS A WORK SINK, WHAT TYPE OF WORK WILL BE ACCOMPLISHED | | | THAT WILL TRANSFORM THISFROM A BREAK ROOM SINK TO A | | | WORK SINK? | | | WHEN THE E SHEETS SHOW THERE TO BE AN UNDER COUNTER | | | REFRIGARATOR AND A GARBAGE DISPOSAL | | | IT APPEARS THIS IS TRUELY A BREAK ROOM SINK. | | | PLEASE SEE,11-4.24.2 SINKS, HEIGHT. SINKS SHALL | | | BE MOUNTED WITH THE COUNTER NO HIGHER | | | THAN 34" ABOVE THE FINISH FLOOR. | | | 11-4.24.3 KNEE CLEARANCE THAT IS AT | | | LEAST 27" HIGH 30" WIDE, AND 19" DEEP | | | SHALL BE PROVIDED UNDERNEATH SINKS. | | | | | | | | | 6) COMPLIED. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-11-27 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-11-27 |
Time |
07:27 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2006-11-27 |
Time |
07:22 |
Sent To |
PC |
|
| Notes |
| 2006-11-27 07:41:00 | BUILDING PLAN REVIEW | | | PERMIT: 06110096 | | | ADD: 2247 PALM BEACH LAKES BLVD,SUITE 105 | | | CONT: AMODIE ENGINEERING & CONSTRUCTION | | | TEL: (561)685-7500 | | | | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1STREVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | | | | 2)110.2* W. P. B. ADMINISTRATIVE | | | CODE, INFORMATION THAT IS REQUIRED FOR | | | RECORD KEEPING & FOR CERTIFICATE OF | | | OCCUPANCY: | | | A) THE EDITION OFTHE CODE UNDER WHICH | | | THE PERMIT WAS ISSUED. | | | B) THE USE AND OCCUPANCY, IN ACCORDANCE | | | WITH THE PROVISIONS OF CHAPTER 3. | | | C) THE TYPE OF CONSTRUCTION AS DEFINED | | | IN CHAPTER 6, TABLE 601. | | | D) THE DESIGN OCCUPANT LOAD, SEE 1004. | | | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS | | | PROVIDED, WHETHER THE SPRINKLER SYSTEM | | | IS REQUIRED. | | | F) ANY SPECIAL STIPULATIONS & CONDITIONS | | | OF THE BUILDING PERMIT. | | | G ) NUMBER OF FLOORS | | | H) LEVEL OF ALTERATIONS? | | | | | | 3) FP-1 INDICATES ALL INTERIOR WALLS ARE NEW, PLEASE | | | INDICATE WHAT EACH ROOM WILL BE USEDFOR? | | | | | | 4) THE PLUMBING RISER INDICATES THERE IS A RETSROOM | | | WITHIN THE | | | UNIT, PLEASE SEE 11-4.22.2 DOORS. | | | (1)ALL DOORS TO ACCESSIBLE TOILET ROOMS SHALL | | | COMPLY WITH SECTION | | | 11-4.13 . DOORS SHALL NOT SWING INTO THE CLEAR FLOOR | | | SPACE REQUIRED | | | FOR ANY FIXTURE. ALSO SEE 11-4.22 THE MINIMUM | | | REQUIREMENTS FOR TOLIET ROOMS. | | | | | | 5) THE PLUMBING ISOMETRIC ALSO APPEARS TO HAVE POSSIBLY | | | A BREAK ROOM SINK, | | | PLEASE SEE,11-4.24.2 SINKS, HEIGHT. SINKS SHALL | | | BE MOUNTED WITH THE COUNTER NO HIGHER | | | THAN 34" ABOVE THE FINISH FLOOR. | | | 11-4.24.3 KNEE CLEARANCE THAT IS AT | | | LEAST 27" HIGH 30" WIDE, AND 19" DEEP | | | SHALL BE PROVIDED UNDERNEATH SINKS. | | | | | | | | | 6) PLEASE ALSO SEE THE MINIMUM REQUIRED CLEARENCES AT | | | DOORS: | | | 11-4.13.6 MANEUVERING CLEARENCES | | | AT DOORS. MINIMUM MANEUVERING CLEARANCES | | | AT DOORS THAT ARE NOT AUTOMATIC OR | | | POWER-ASSISTED SHALL BE AS SHOWN IN | | | FIG. 25. THE FLOOR OR GROUND AREA WITH | | | IN THE REQUIRED CLEARANCES SHALL BE | | | CLEAR & LEVEL. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2007-01-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-01-14 |
Time |
18:29 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-01-14 |
Time |
18:16 |
Sent To |
I |
|
| Notes |
| 2007-01-14 18:30:42 | PLANS REMOVED FROM INCOMING AS CONTRACTOR CALLED AND | | | SAID ELECTRICALWAS THE LAST REVIEW, HOWEVER PLANS ARE | | | BEING ROUTED BACK TO INCOMING AS THERE ARE NEW FIRE | | | SHEETS IN SETS WHICH NEED REVIEW AND STAMPING IF OK. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2006-12-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-12-21 |
Time |
11:44 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-12-21 |
Time |
11:23 |
Sent To |
|
|
| Notes |
| 2006-12-21 11:45:49 | ** UNSAT 2ND REVIEW ** | | | | | | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL | | | IN NEED OF ADDRESSING. PLEASE SEE THE NOTES BELOW ARE | | | TAKEN DIRECTLY FROM PREVIOUS REVIEW WITH A NOTATION OF | | | OK OR NO IF COMMENT WAS OR WAS NOT ADDRESS FULLY. | | | PLEASE SEE SOMETIMES A NO/OK IS PLACED AHEAD OF THE | | | NOTE AS THE NOTE MAY HAVE ONLY BEEN PARTIALLY | | | ADDRESSED. | | | | | | ** PLEASE ALSO SEE SOME NEW COMMENTS BASED ON PLANS | | | SUBMITTED. THESE NEW COMMENTS ARE AT THE END OF THE | | | FIRST REVIEW COMMENTS. | | | | | | | | | 1) NOTE:NO, PLEASE SEE NO ADDRESS FOR LOCATION AND | | | SUITE IS YET ON THE TITLE BLOCKS FOR SAID PROJECT. | | | PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G1-16.004, | | | 61G15-23.002 | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE VERIFY WORK LOCATION. PLANS MENTIONS WORK FOR | | | CONTRACTOR/ENGINEERING OFFICE PERMIT APPLICATION | | | MENTIONS UNIT #105? PLEASE INCLUDE SUITE OF THE SCOPE | | | OF WORK BEING DONE. | | | | | | 2) NOTE: NO/OK, PLEASE SEE THE SIZE OF THE EXISTING | | | PANEL "AM" IS STILL IN QUESTION AND THE LOCATION ON | | | PLANS APPEARS TO SHOW THIS IN A ROOM, HOWEVER NOT CLEAR | | | IF THIS PANEL IS IN ANOTHER TENANT SPACE, SEPARATELY | | | METERED ETC. | | | PLEASE CLARIFY FURTHER AND SHOW. | | | FBC 106.1.2 | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE CLARIFY THE PANEL MENTIONED AS "AM" PLEASE | | | CLARIFY WHERE THIS PANEL IS AND HOW THIS PANEL IF IN A | | | SEPARATE SPACE FEEDS THIS SPACE. | | | PLEASE ALSO SUBMIT LOAD CALCULATIONS FOR THIS EXISTING" | | | AM" PANEL WITH NEW " LP" PANEL ADDED. | | | THIS SCENARIO IS NOT CLEAR AT THIS TIME. | | | 220.3,220.10,220.11,220.13,CONTINUOUS LOADS PER | | | 215.3,230.42 ETC. | | | FBC ADMINISTRATIVE SECTION 106.1.2, AS ADOPTED BY THE | | | CITY OF WEST PALM BEACH. | | | | | | 3) NOTE: NO, PLEASE SEE THE CODE SECTIONS AS GIVEN | | | BELOW IN PREVIOUS REVIEW. PLEASE SEE THE RESPONSE | | | MENTIONS A TIME CLOCK BEING ADDED, HOWEVER NO DETAIL | | | FOR THIS IS SHOWN. NO SCHEDULING, NO OVER RIDE CONTROLS | | | IN SPACES AS REQUIRED AND NO TIMES ON OVER RIDES. | | | PLEASE SEE THE DEVICES AND SYSTEM AS BEING SELECTED BY | | | THE DESIGNER SHALL BE INDICATED ON PLANS AND CORRELATE | | | WITH THE SYMBOL LEGEND. | | | PLEASE SEE SECTIONS AS GIVEN FOR MISSING LIGHTING POWER | | | DENSITIES? | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE THIS APPEAR AND IS BEING SHOWN AS A NEW | | | TENANT BUILD OUT LOCATED IN A BUILDING GREATER THAN 5K | | | SQ FT. PLEASE SEE FBC 2004, 13-415.1.ABC.1.1, .1.2 AND | | | .1.3 | | | 13-415.2.ABC.1 | | | ** NEW NOTE ** | | | | | | 1) NOTE: PLEASE BE SURE PLANS REFLECT THE FOLLOWING | | | MINIMUM CODES AS REQUIRED. STATING THE LATEST EDITION | | | MAY NOT APPLY AS DEPENDING ON PERMIT APPLICATION WAS | | | MADE, THIS WILL DICTATE WHICH CODES THE PLANS ARE UNDER | | | AND RELEVANT TO THE DESIGNS. | | | THIS COMMENT WAS MISSED BY THIS REVIEWER ON PREVIOUS | | | REVIEW, HOWEVER IS REQUIRED. | | | PLEASE KNOW PERMIT APPLICATIONS BEFORE 12/8/06 WILL | | | PLACE ELECTRICAL UNDER NFPA-70 2002 (NEC) , 2003 | | | NFPA-101, 2002 NFPA-72 AND REV #5 TO THE 2004 FBC. | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-11-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-11-13 |
Time |
14:33 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-11-13 |
Time |
14:12 |
Sent To |
|
|
| Notes |
| 2006-11-13 14:34:43 | **** UNSAT **** | | | | | | 1) NOTE: PLEASE VERIFY WORK LOCATION. PLANS MENTIONS | | | WORK FOR CONTRACTOR/ENGINEERING OFFICE,PERMIT | | | APPLICATION MENTIONS UNIT #105? PLEASE INCLUDE SUITE OF | | | THE SCOPE OF WORK BEING DONE. | | | | | | 2) NOTE: PLEASE CLARIFY THE PANEL MENTIONED AS "AM" | | | PLEASE CLARIFY WHERE THIS PANEL IS AND HOW THIS PANEL | | | IF IN A SEPARATE SPACE FEEDS THIS SPACE. | | | PLEASE ALSO SUBMIT LOAD CALCULATIONS FOR THIS EXISTING" | | | AM" PANEL WITH NEW " LP" PANEL ADDED. | | | THIS SCENARIO IS NOT CLEAR AT THIS TIME. | | | 220.3,220.10,220.11,220.13,CONTINUOUS LOADS PER | | | 215.3,230.42 ETC. | | | FBC ADMINISTRATIVE SECTION 106.1.2, AS ADOPTED BY THE | | | CITY OF WEST PALM BEACH. | | | | | | 3) NOTE: PLEASE SEE THIS APPEAR AND IS BEING SHOWN AS A | | | NEW TENANT BUILD OUT LOCATED IN A BUILDING GREATER THAN | | | 5K SQ FT. PLEASE SEE FBC 2004, 13-415.1.ABC.1.1, .1.2 | | | AND .1.3 | | | 13-415.2.ABC.1 | | | PLEASE ALSO AS THE SCOPE OF WORK APPEARS TO BE FOR A | | | NEW TENANT BUILD OUT THIS WOULD BE REQUIRED. | | | | | | AS THE PLANS ARE NOT CLEAR WHERE THIS SPACE IS BEING | | | FED FROM OR IF IT IS PART OF LARGER TENANT SPACE, THE | | | COMMENTS MAY NOT BE COMPLETE AT THIS TIME. | | | | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2007-01-17 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-01-17 |
Time |
11:50 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-01-17 |
Time |
11:50 |
Sent To |
|
|
| Notes |
| 2007-01-17 12:01:10 | *****APPROVED***** | | | | | | | | | PLAN SHEET F-1 STAMPED, INITIALED, AND DATED. | | 2007-01-14 18:24:56 | NEEDS REVIEW AS THERE ARE FIRE SHEETS WHICH ARE NEW. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2006-12-26 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2006-12-26 |
Time |
12:00 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2006-12-26 |
Time |
12:00 |
Sent To |
|
|
| Notes |
| 2006-12-26 12:08:44 | *****PROVISO***** | | | | | | | | | | | | 1.THE ENTIRE ADDRESS OF WHERE THE SCOPE OF WORK IS | | | BEING CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH | | | SUBMITTED PLAN SHEET. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2006-11-20 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2006-11-20 |
Time |
09:31 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2006-11-20 |
Time |
09:31 |
Sent To |
|
|
| Notes |
| 2006-11-20 09:58:24 | ****UNSAT**** | | | | | | | | | | | | 1.IN THE TITLE BLOCK OF THE SUBMITTED PLANS, THE | | | ACTUAL LOCATION OF WHERE THE SCOPE OF WORK WILL BE | | | CONDUCTED SHOULD BE INCLUDED. | | | | | | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 3. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. | | | | | | 4.PLEASE PROVIDE EXISTING FLOOR PLAN THAT INCLUDES | | | EXIT LIGHTS, EMERGENCY LIGHTS, FIRE EXTINGUISHER(S), | | | ETC. FOR THIS TENANT SPACE.HOW WILL THEY BE AFFECTED | | | BY THE SCOPE OF THE WORK? | | | | | | 5.PLEASE DECLARE INTERIOR FINISH CLASSIFICATION FOR | | | WALLS AND CEILINGS. | | | | | | 6.IF THE FIRE ALARM AND SINCE THE SPRINKLER SYSTEM | | | ARE MODIFIED BY THE SCOPE OF THE WORK, SEPARATE PLANS | | | AND PERMIT ARE REQUIRED. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING, | | | INCLUDE A RESPONSE SHEET INDICATING HOW/WHERE EACH ITEM | | | WAS ADDRESSED. | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-01-09 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-01-09 |
Time |
19:17 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-01-09 |
Time |
19:17 |
Sent To |
|
|
| Notes |
| 2007-01-09 19:17:34 | WAITING FOR "BOB" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-12-01 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-12-01 |
Time |
16:21 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-12-01 |
Time |
16:21 |
Sent To |
|
|
| Notes |
| 2006-12-21 09:28:06 | TO "BOB"#1 | | 2006-12-01 16:21:50 | WAITING FOR "BOB" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-11-27 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-11-27 |
Time |
07:22 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2006-11-06 |
Time |
10:11 |
Sent To |
|
|
| Notes |
| 2006-11-12 14:07:22 | TO"BOB"#12 | | 2006-11-06 10:12:44 | WAITING FOR "BOB" |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2006-11-13 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-11-13 |
Time |
09:35 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2006-11-13 |
Time |
09:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2007-01-10 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-01-10 |
Time |
15:24 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-01-10 |
Time |
15:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2007-01-06 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-01-06 |
Time |
07:05 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-01-06 |
Time |
06:32 |
Sent To |
|
|
| Notes |
| 2007-01-06 07:04:35 | DENIED; | | | 1. A PRIVATE TOILET ROOM IS FOR ONE PERSON NOT ALL 6 | | | EMPLOYEES. THIS IS A COMMON TOILET ROOM AND MUST COMPLY | | | WITH FBC-2004 BUILDING CHAPTER 11. SEE SECTIONS | | | 11-4.1.3(11) AND 11-4.22. | | | 2. SINK IS NOT A WORK SINK. ELECTRICAL PLAN SHOWS AN | | | OUTLET IN CABINET FOR A REF. AND GAR. DISP. SINK TO | | | MEET HANDICAP REQUIREMENTS. | | | 3. SHOW CLEAR FRONTAL FLOORSPACEAT LACATORY AND | | | SINK, AND TURNING RADIUS IN BATHROOM. | | | 4. SHOW DETAILS OF TOILET ROOM ,TOILET, LAVATORY AND | | | SINK WITH ALL REQUIRED MEASUREMENTS. | | | SEE THE FOLLOWING CODE SECTIONS FOR | | | REFORANCE; | | | TOILET: | | | 11-4.16.2 CLEAR FLOOR SPACE | | | 11-4.16.3 HEIGHT | | | 11-4.16.4 GRAB BAR | | | 11-4.16.5 FLUSH CONTROL | | | 11-4.16.6 DISPENSERS | | | LAVATORY: | | | 11-4.19.2 HEIGHT AND CLEARANCE | | | 11-4.19.3 CLEAR FLOOR SPACE ( FRONTAL) | | | 11-4.19.4 EXPOSED PIPES | | | 11-4.19.5 FAUCET | | | 11-4.19.6 MIRROR | | | SINK: | | | 11-4.24.2 HEIGHT | | | 11-4.24.3 KNEE CLEARANCE | | | 11-4.24.4 DEPTH OF SINK | | | 11-4.24.5 CLEAR FLOOR SPACE | | | 11-4.24.6 EXPOSED PIPES | | | 11-4.24.7 FAUCET | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-01-06 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-11-18 |
Time |
10:01 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-11-18 |
Time |
10:01 |
Sent To |
|
|
| Notes |
| 2006-11-18 10:09:57 | NOT ENOUGH INFORMATION; | | | 1. ARE THERE PUBLIC, HANDICAP TOILET ROOMS AND DRINKING | | | FOUNTAINS? | | | 2. THE SINK BEING INSTALLED, IS IT A WORK SINK OR A | | | BREAK SINK? | | | 3.HOW HIGH IS BUILDING? AIR ADMITTANCE VALVES SHALL | | | COMPLY WITH FBC-2004 PLUMBING SECTION 917.3.1 | | | AAV'S CAN ONLY BE CONNECTED TO BUILDING DRAIN A | | | MAXIMUM OF 4 BRANCH INTERALS FROM THE TOP OF THE | | | STACK. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|