Plan Review Details - Permit 06110070
| Plan Review Stops For Permit 06110070 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2006-12-05 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2006-12-05 |
Time |
10:52 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2006-12-05 |
Time |
10:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2006-12-01 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2006-12-01 |
Time |
10:17 |
Rev Time |
0.50 |
| Received By |
jgomez |
Date |
2006-12-01 |
Time |
10:11 |
Sent To |
|
|
| Notes |
| 2006-12-01 10:23:58 | BUILDING REVIEW 2ND CHECKLIST: | | | | | | 1- A) ENGINEER LETTER FOR ENHANCED FASTENING AT | | | PERIMETER AND CORNER AREAS PREPARED BY DON ARPIN IS | | | WRONG. ENGINEER'S DESIGN PRESSURES ( PG 16.20 EXP. B: | | | -30.4, -51 AND -76.8) ARE FOR BASIC WIND SPEED OF | | | 130MPH-3 SECOND GUST.THE CITY OF WEST PALM BEACH | | | ADOPTED THE 140MPH-3 SECOND GUST BASIC WIND SPEED. NEED | | | TO REVISE DESIGN PRESSURES AS REQUIRED. | | | | | | B) ENGINEER TO IDENTIFY SPECIFIC APPROVED ASSEMBLY | | | FROM NOA SUBMITTED. SPECIFY PAGE FROM THE NOA OR | | | COMPLETELY IDENTIFY APPROVED SYSTEM FROM NOA. | | | | | | 2- ENGINEER TO PROVIDE COMPLETE RAS 117 CALCULATIONS AS | | | REQUIRED BY GENERAL LIMITATION #7 OF LAST PAGE OF NOA | | | 06-0626.02. ENGINEER TO READ GENERAL LIMITATION #7 AND | | | PROVIDE ALL REQUIRED INFORMATION. | | | | | | 3- NEED FIELD WITHDRAWAL RESISTANCE TESTING AS REQUIRED | | | BY GENERAL LIMITATION #7. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-11-03 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2006-11-03 |
Time |
11:17 |
Rev Time |
0.75 |
| Received By |
jgomez |
Date |
2006-11-03 |
Time |
11:04 |
Sent To |
|
|
| Notes |
| 2006-11-03 11:26:37 | BUILDING REVIEW CHECKLIST: | | | | | | 1- PERMIT APPLICATION DESCRIPTION SPECIFIES ROOF TO BE | | | LIGHT WEIGHT CONCRETE. PRODUCT APPROVAL NOA 06-0626.02 | | | SUBMITTED IS FOR STEEL DECK SYSTEMS. REVISE/CLARIFY AS | | | REQUIRED AND PROVIDE CORRECT PRODUCT APPROVAL. | | | | | | 2- CLEARLY IDENTIFY APPROVED ASSEMBLY TO BE INSTALLED. | | | IF SELECTED APPROVED ASSEMBLY IS LIMITED BY GENERAL | | | LIMITATION #7, THEN NEED TO PROVIDE RAS 117 | | | CALCULATIONS AND THEY SHALL BE DONE BY ANY ONE OF THE | | | PROFESSIONALS LISTED IN GENERAL LIMITATION #7. | | | IF SELECTED APPROVED ASSEMBLY IS LIMITED BY GENERAL | | | LIMITATION #9, THEN IT MAY NOT BE ABLE TO BE USED IN | | | THIS AREA. CHECK DESIGN PRESSURES ON ASCE 7-02 OR TABLE | | | 1609.6B FBC 2004. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 | | | |
|
|
|