Plan Review Details - Permit 06110070
Plan Review Stops For Permit 06110070
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-12-05 Cont ID  
Sent By lmartine Date 2006-12-05 Time 10:52 Rev Time 0.00
Received By lmartine Date 2006-12-05 Time 10:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-12-01 Cont ID  
Sent By jgomez Date 2006-12-01 Time 10:17 Rev Time 0.50
Received By jgomez Date 2006-12-01 Time 10:11 Sent To  
Notes
2006-12-01 10:23:58BUILDING REVIEW 2ND CHECKLIST:
  
 1- A) ENGINEER LETTER FOR ENHANCED FASTENING AT
 PERIMETER AND CORNER AREAS PREPARED BY DON ARPIN IS
 WRONG. ENGINEER'S DESIGN PRESSURES ( PG 16.20 EXP. B:
 -30.4, -51 AND -76.8) ARE FOR BASIC WIND SPEED OF
 130MPH-3 SECOND GUST.THE CITY OF WEST PALM BEACH
 ADOPTED THE 140MPH-3 SECOND GUST BASIC WIND SPEED. NEED
 TO REVISE DESIGN PRESSURES AS REQUIRED.
  
 B) ENGINEER TO IDENTIFY SPECIFIC APPROVED ASSEMBLY
 FROM NOA SUBMITTED. SPECIFY PAGE FROM THE NOA OR
 COMPLETELY IDENTIFY APPROVED SYSTEM FROM NOA.
  
 2- ENGINEER TO PROVIDE COMPLETE RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 OF LAST PAGE OF NOA
 06-0626.02. ENGINEER TO READ GENERAL LIMITATION #7 AND
 PROVIDE ALL REQUIRED INFORMATION.
  
 3- NEED FIELD WITHDRAWAL RESISTANCE TESTING AS REQUIRED
 BY GENERAL LIMITATION #7.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-11-03 Cont ID  
Sent By jgomez Date 2006-11-03 Time 11:17 Rev Time 0.75
Received By jgomez Date 2006-11-03 Time 11:04 Sent To  
Notes
2006-11-03 11:26:37BUILDING REVIEW CHECKLIST:
  
 1- PERMIT APPLICATION DESCRIPTION SPECIFIES ROOF TO BE
 LIGHT WEIGHT CONCRETE. PRODUCT APPROVAL NOA 06-0626.02
 SUBMITTED IS FOR STEEL DECK SYSTEMS. REVISE/CLARIFY AS
 REQUIRED AND PROVIDE CORRECT PRODUCT APPROVAL.
  
 2- CLEARLY IDENTIFY APPROVED ASSEMBLY TO BE INSTALLED.
 IF SELECTED APPROVED ASSEMBLY IS LIMITED BY GENERAL
 LIMITATION #7, THEN NEED TO PROVIDE RAS 117
 CALCULATIONS AND THEY SHALL BE DONE BY ANY ONE OF THE
 PROFESSIONALS LISTED IN GENERAL LIMITATION #7.
 IF SELECTED APPROVED ASSEMBLY IS LIMITED BY GENERAL
 LIMITATION #9, THEN IT MAY NOT BE ABLE TO BE USED IN
 THIS AREA. CHECK DESIGN PRESSURES ON ASCE 7-02 OR TABLE
 1609.6B FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712
  