Plan Review Details - Permit 06110061
Plan Review Stops For Permit 06110061
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-11-13 Cont ID  
Sent By jgomez Date 2006-11-13 Time 17:06 Rev Time 0.50
Received By jgomez Date 2006-11-13 Time 17:06 Sent To  
Notes
2006-11-13 17:22:30BUILDING REVIEW 2ND CHECKLIST:
  
 1- FLAT ROOF SYSTEM ON PAGE 25 OF NOA 02-1205.02
 DOESN'T WORK FOR THIS AREA BECAUSE THE DESIGN PRESSURES
 ARE TOO LOW FOR PERIMETER AND CORNER AREAS. SEE TABLE
 1609.6B OF 2004 FBC FOR REQUIRED DESIGN PRESSURES.
 SYSTEM IS LIMITED BY GENERAL LIMITATION #9 WHICH
 DOESN'T ALLOW NAIL ENHANCING TO INCREASE THE DESIGN
 PRESSURES OF THE SYSTEM. ONLY SYSTEMS THAT ARE LIMITED
 BY GENERAL LIMITATION #7 MAY HAVE ENHANCED FASTENING AT
 PERIMETER AND CORNER AREAS. SEE GENERAL LIMITATION #7
 ON LAST PAGE OF NOA. CALCULATIONS MUST BE DONE ONLY BY
 ANY ONE OF THOSE LISTED IN GENERAL LIMITATION #7.
 THEREFORE,SELECT A SYSTEM WITH LIMITATION #7 AND
 PROVIDE THE RAS 117 CALCULATIONS PREPARED BY ANY ONE OF
 THE LISTED PROFESSIONALS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-11-02 Cont ID  
Sent By jgomez Date 2006-11-02 Time 18:13 Rev Time 0.50
Received By jgomez Date 2006-11-02 Time 18:13 Sent To  
Notes
2006-11-02 18:24:41BUILDING REVIEW CHECKLIST:
  
 1- DADE COUNTY NOA #01-0522.03 FOR OAKRIDGE 30 AR
 SHINGLES EXPIRED ON 07/19/06. NEED TO PROVIDE CURRENT
 NOA.
  
 2- PROVIDE COMPLETE PRODUCT APPROVAL FOR FLAT ROOF
 SYSTEM. INFORMATION SUBMITTED IS NOT A PRODUCT
 APPROVAL.CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS
 GOING TO BE INSTALLED AND MARK SPECIFIC FASTENING
 OPTION TO BE USED.LOOK FOR GENERAL LIMITATION #7 OR
 #9 AND PROVIDE REQUIRED INFORMATION. SEE GENERAL
 LIMITATIONS ON PRODUCT APPROVAL. SEE ATTACHED COPY OF
 CITY POLICY FOR RE-ROOFING PERMITS AND PROVIDE ALL
 REQUIRED INFORMATION.
  
 3- NOTICE OF COMMENCEMENT IF EXPIRED AFTER 90 DAYS OF
 BEING RECORDED IF WORK IS NOT STARTED.SEC. 713.13(2)
 FLORIDA STATUTES. NEED RE-RECORDED NOTICE OF
 COMMENCEMENT.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712