Plan Review Details - Permit 06110027
Plan Review Stops For Permit 06110027
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-01-19 Cont ID  
Sent By rmcdouga Date 2007-01-19 Time 07:56 Rev Time 0.00
Received By rmcdouga Date 2007-01-19 Time 07:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-12-15 Cont ID  
Sent By rmcdouga Date 2006-12-15 Time 12:39 Rev Time 0.00
Received By rmcdouga Date 2006-12-15 Time 12:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-11-09 Cont ID  
Sent By rmcdouga Date 2006-11-09 Time 08:26 Rev Time 0.00
Received By rmcdouga Date 2006-11-09 Time 07:01 Sent To  
Notes
2006-11-09 08:26:41DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SPECIFY THE TYPE OF CONSTRUCTION BASED ON 2004 FBC
 DESIGNATIONS. SPECIFY A OR B. SEE FBC TABLE 601.
  
 3) CLARIFY THE SCOPE OF WORK FOR THIS PERMIT. IS THIS A
 TENANT BUILD OUT, A CHANGE OF OCCUPANCY OR ALTERATIONS
 TO AN EXISTING TENANT SPACE.
  
 4) SPECIFY THE LEVEL OF ALTERATION PER 2004 FBC
 EXISTING BUILDING CODE CHAPTER 3.
  
 5) THE DOOR SCHEDULE SPECIFIES A NEW 3-0 DOOR #1. WHERE
 IS THIS DOOR LOCATED ON THE FLOOR PLAN?
  
 6) PLANS HAVE NOT BEEN SEALED WITH THE EMBOSSED SEAL OF
 THE ARCHITECT AS REQUIRED BY FAC 61G1-16.003.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-01-14 Cont ID  
Sent By dpalmer Date 2007-01-14 Time 19:06 Rev Time 0.00
Received By dpalmer Date 2007-01-14 Time 18:46 Sent To I
Notes
2007-01-14 19:10:03PLANS REMOVED FROM INCOMING FOR REVIEW, ROUTED BACK TO
 INCOMING AWAITING SPACE ON THE BOB BOARD.
  
 *** PLANS REDLINED AS NOT ALL CIRCUITING FOR NEW WAS
 SHOWN. PLEASE SEE 700.12E FOR CIRCUITING OF EM/EXT
 LTS.
  
 ** PREVIOUS PLANS WHICH INCLUDED WATER HEATER HAS NOW
 REMOVED WATER HEATER. REDLINED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-12-17 Cont ID  
Sent By dpalmer Date 2006-12-17 Time 10:23 Rev Time 0.00
Received By dpalmer Date 2006-12-17 Time 10:07 Sent To  
Notes
2006-12-17 10:24:04*** UNSAT 2ND REVIEW***
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW WHICH
 STILL NEEDS TO BE CLARIFIED OR ADDRESSED.
  
 1) NOTE: OK.
  
 2) NOTE: OK.
  
 3) NOTE:NO, PLEASE SEE ALL CIRCUITING FOR NEW SHALL
 BE INDICATE ON PLANS AT A MINIMUM AND CORRELATE WITH A
 PANEL SCHEDULE TO BE SUBMITTED. PLEASE KNOW DUE TO THE
 NEW LOAD(S) BEING ADDED, A LOAD CALCULATIONS ON THE
 EXISTING FEEDERS/PANEL SHALL BE DONE AND SUBMITTED WITH
 THE PANEL SCHEDULE.
 PLEASE INDICATE ALL EXISTING WITH THE SYMBOL AS SHOWN
 ON SYMBOL LEGEND. THE E LOCATED NEXT TO THE EXIT LIGHTS
 ONLY INDICATES EXISTING DOORS. PLEASE INDICATE NEW OR
 EXISTING CIRCUITING FOR EM/EXT LTS PER 700.12E.
 PLEASE SEE THAT ALL RELOCATED DEVICES INDICATE "R" OR
 SOME INDICATION OF WHICH THESE ARE..
 106.1.2, 106.3.5.1.2 FBC ADMIN SECTION. 408.4, 310.16,
 ETC.
  
  
 **PREVIOUS REVIEW NOTE **
 PLEASE CLARIFY IF THIS IS A BUILD OUT OF A NEW
 TENANT SPACE OR AN EXISTING TENANT AND OCCUPANT? PLEASE
 PROVIDE CIRCUITING ON PLANS FOR NEW ELECTRICAL AND
 CORRELATE WITH A PANEL SCHEDULE TO BE SUBMITTED. 240.4,
 408.6, 310.16
 FBC ADMIN SECT AS ADOPTED BY THE CITY OF WEST PALM
 BEACH 106.1.2, 106.3.5.1.2
  
 4) NOTE:NO, SEE NOTE #3 ABOVE.
 PLEASE SHOW NEW OR EXISTING LIGHTING. PLEASE INDICATE
 NEW OR EXISTING EXT/ EM LTS WHICH MEET LS 101, 7.8,
 7.9, AND NEC 700.12 E.
  
  
 ** NEW NOTE **
  
 1) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE.
  
 2) NOTE: PLEASE ALSO SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE NEW WATER HEATER. PLANS SEEM TO INDICATE
 INSTA-HOT, YET ALSO SHOWS 6-GAL STORAGE TYPE.
 110.3, 90.7, FBC ADMIN SECTION 106.1.2
  
 NO REVIEW OF SOME ELECTRICAL ITEMS CAN BE DONE AT THIS
 TIME AS SOME INFORMATION WAS NOT SUBMITTED FOR REVIEW.
 PLEASE KNOW THERE MAY BE FURTHER COMMENTS DUE TO
 INFORMATION NOT YET SUBMITTED.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-11-04 Cont ID  
Sent By dpalmer Date 2006-11-04 Time 17:51 Rev Time 0.00
Received By dpalmer Date 2006-11-04 Time 17:38 Sent To I
Notes
2006-11-04 17:51:38*** UNSAT ***
  
 1) NOTE: PLEASE SEE THAT THE FOLLOWING CODES AT A
 MINIMUM SHALL BE STATED ON PLANS.
 2002 NFPA-70(NEC), 2003 NFPA-101, 2002 NFPA-72
 ** PLEASE SEE PLANS ON FRONT COVER SHEET REFLECT A NFPA
 2004.
 PLEASE SEE WRONG LIFE SAFETY CODE IS ALSO REFLECTED.
 (2004).
 (PLEASE KNOW THE NEXT ADOPTED EDITION OF THE NFPA-70
 WILL BE THE 2005.)
  
 2) NOTE: PLEASE SEE MISSING INFORMATION REQUIRED ON
 TITLE BLOCKS FOR ENGINEERING FIRM AND ENGINEER OF
 RECORD PER FLORIDA ADMINISTRATIVE CODE 61G15-23.002.
 PLEASE SEE MISSING THE PRINTED NAME AND LICENSE NUMBER
 OF ENGINEER AND MISSING THE PLANS ARE NOT SEALED, AS
 REQUIRED PER FS 471.025.
  
 THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY OTHER REVIEWER(S).
 PLEASE ALSO SEE FRONT COVER SHEET.
  
 3) NOTE:PLEASE CLARIFY IF THIS IS A BUILD OUT OF A
 NEW TENANT SPACE OE AN EXISTING TENANT AND OCCUPANT?
 PLEASE PROVIDE CIRCUITING ON PLANS FOR NEW ELECTRICAL
 AND CORRELATE WITH A PANEL SCHEDULE TO BE SUBMITTED.
 240.4, 408.6, 310.16
 FBC ADMIN SECT AS ADOPTED BY THE CITY OF WEST PALM
 BEACH 106.1.2, 106.3.5.1.2
  
 4) NOTE: PLEASE SHOW NEW OR EXISTING LIGHTING. PLEASE
 INDICATE NEW OR EXISTING EXT/ EM LTS WHICH MEET LS 101,
 7.8, 7.9, AND NEC 700.12 E.
  
 NO REVIEW OF SOME ELECTRICAL ITEMS CAN BE DONE AT THIS
 TIME AS SOME INFORMATION WAS NOT SUBMITTED FOR REVIEW.
 PLEASE KNOW THERE MAY BE FURTHER COMMENTS DUE TO
 INFORMATION NOT YET SUBMITTED.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2006-11-04 17:38:24REMOVED FROM INCOMING.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-01-17 Cont ID  
Sent By mawillia Date 2007-01-17 Time 17:31 Rev Time 0.00
Received By mawillia Date 2007-01-17 Time 17:31 Sent To  
Notes
2007-01-17 17:33:51*****APPROVED*****
  
  
 PLAN SHEET A-1 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-12-18 Cont ID  
Sent By mawillia Date 2006-12-18 Time 10:50 Rev Time 0.00
Received By mawillia Date 2006-12-18 Time 10:49 Sent To  
Notes
2006-12-18 10:51:33*****APPROVED******
  
  
  
  
 TO BE STAMPED WHEN ALL PLAN REVIEWS HAVE BEEN SATISFIED

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-11-14 Cont ID  
Sent By mawillia Date 2006-11-14 Time 11:22 Rev Time 0.00
Received By mawillia Date 2006-11-14 Time 11:22 Sent To  
Notes
2006-11-14 11:45:52*****UNSAT*****
  
  
  
 1.NFPA 101 - 2003 EDITIONAND FIRE PREVENTION CODE -
 2004 EDITION SHALL BE REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.INTERIOR RENOVATION OPERATIONS SHALL NOT INTERFERE
 OR HINDER EMERGENCY ACCESS TO THE SAID PROPERTY OR
 VICINITY THEREOF (INCLUDING FIRE LANES).
  
 4.INDICATETHE LOCATION OF EXIT LIGHTS, EMERGENCY
 LIGHTS, FIRE EXTINGUISHERS AND ANY OTHER LIFE SAFETY
 SYSTEMS.HOW WILL THEY BE AFFECTED BY THE SCOPE OF THE
 WORK?
  
 5.IF THE INTERIOR BUILDOUT REQUIRES MODIFICATION OF
 THE FIRE SPRINKLER AND/OR FIRE ALARM SYSTEM, SEPARATE
 PERMIT AND PLANS WILL BE REQUIRED.
  
 6.INTERIOR FINISHING FOR WALLS AND CEILINGS IN EXITS
 AND EXIT ACCESS CORRIDORS SHALL BE CLASS "A" OR CLASS
 "B".
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW OR WHERE EACH
 ITEM WAS ADDRESSED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-01-12 Cont ID  
Sent By adarroug Date 2007-01-12 Time 10:00 Rev Time 0.00
Received By adarroug Date 2007-01-12 Time 10:00 Sent To  
Notes
2007-01-17 08:47:45TO "BOB"#4
2007-01-12 10:00:30WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-12-14 Cont ID  
Sent By adarroug Date 2006-12-14 Time 16:23 Rev Time 0.00
Received By adarroug Date 2006-12-14 Time 16:23 Sent To  
Notes
2006-12-14 16:27:06TO "BOB"#6
2006-12-14 16:23:48WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-12-15 Cont ID  
Sent By mmiller Date 2006-11-29 Time 19:13 Rev Time 0.00
Received By rmcdouga Date 2006-11-29 Time 19:13 Sent To Z
Notes
2006-11-30 10:57:2311/30/06--WAITING FOR "BOB"/DOES NOT NEED ZONING.
 ADARROUGH
2006-11-29 19:13:56SENT TO ZONING

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-11-16 Cont ID  
Sent By adarroug Date 2006-11-14 Time 13:40 Rev Time 0.00
Received By adarroug Date 2006-11-04 Time 16:00 Sent To  
Notes
2006-11-07 15:21:56TO "BOB"#14
2006-11-04 16:01:46WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2007-01-12 Cont ID  
Sent By tgordon Date 2007-01-12 Time 15:59 Rev Time 0.15
Received By tgordon Date 2007-01-12 Time 15:59 Sent To  
Notes
2007-01-12 16:00:44NO MECHANICAL WORK TO BE DONE, MECHANICAL PERMIT
 #06110029 HAS BEEN VOIDED.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-12-19 Cont ID  
Sent By tgordon Date 2006-12-19 Time 14:23 Rev Time 0.25
Received By tgordon Date 2006-12-19 Time 14:23 Sent To  
Notes
2006-12-19 14:26:10*** DENIED ***
 1) NO MECHANICAL PLANS WERE SUBMITTED FOR
 REVIEW. IF NO MECHANICAL WORK IS TO BE DONE YOU NEED TO
 VOID YOUR MECHANICAL PERMIT NUMBER 06110029 SO YOUR
 BUILDING PLANS MAY BY-PASS A MECHANICAL REVIEW.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-11-07 Cont ID  
Sent By tgordon Date 2006-11-07 Time 16:26 Rev Time 0.20
Received By tgordon Date 2006-11-07 Time 16:26 Sent To  
Notes
2006-11-07 16:32:07*** DENIED ***
 1) MECHANICAL PERMIT APPLIED FOR #06110029, NO
 MECHANICAL PLANS SUBMITTED FOR REVIEW, PLEASE SUBMIT
 MECHANICAL PLANS FOR REVIEW, PER 2004 FBC WPB AMEND.
 106.3.5.1.4.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  