Plan Review Details - Permit 06110024
Plan Review Stops For Permit 06110024
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-11-13 Cont ID  
Sent By btrobaug Date 2006-11-13 Time 14:00 Rev Time 0.33
Received By btrobaug Date 2006-11-13 Time 13:56 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-11-06 Cont ID  
Sent By btrobaug Date 2006-11-06 Time 07:59 Rev Time 0.50
Received By btrobaug Date 2006-11-06 Time 07:32 Sent To I
Notes
2006-11-06 07:57:30 
  
 DENIED /INCOMPLETE INFORMATION
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT
 CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE
 EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS
 EQUAL TO OR GREATER THAN THE AVAILABLE FAULT.
  
 2} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2.
  
 3} THE APPLICATION MUST BE FILLED OUT CORRECTLY. THE
 OWNERS NAME IS IN THE LOCATION FOR THE ADDRESS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-12-27 Cont ID  
Sent By adarroug Date 2006-12-27 Time 13:51 Rev Time 0.00
Received By adarroug Date 2006-12-27 Time 13:47 Sent To E
Notes
2006-12-27 13:50:00TO "JLEAHY" DESK/FOR "RCORDOVEZ"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-11-06 Cont ID  
Sent By btrobaug Date 2006-11-06 Time 08:10 Rev Time 0.00
Received By btrobaug Date 2006-11-04 Time 15:39 Sent To PC
Notes
2006-11-04 15:39:48TO "E" BOX