Plan Review Details - Permit 06110021
Plan Review Stops For Permit 06110021
Review Stop G GAS REVIEW
Rev No 2 Status   Date 2006-12-04 Cont ID  
Sent By mperson Date 2006-12-04 Time 11:38 Rev Time 0.33
Received By mperson Date 2006-12-04 Time 11:38 Sent To PC
Notes
2006-12-04 13:24:28DENIED 2ND TIME
 REFERENCE: FBC-2004 FUEL GAS AND FBC-2004 CHAPTER 1
  
 THE FOLLOWING CORRECTIONS ARE STILL REQUIRED FOR GAS
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. (OK)
 2. (OK)
 3. (OK)
 4. (OK)
  
 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
 NOTE: MANUFACTURE CUT SHEETS OF THE MP REGULATORS ARE
 STILL REQUIRED, PLEASE SUBMIT ON THE RESUBMITTAL.
  
 6. PER FBC-2004, CHAPTER 1, SECTION
 108.3, BUILDING PERMIT VALUATION: IF IN
 THE OPINION OF THE BUILDING OFFICIAL,
 THE CLAIMED VALUATION OF THE BUILDING,
 ALTERATION, STRUCTURE, ELECTRICAL, GAS
 MECHANICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATED ON THE APPLICATION,
 THE PERMIT SHALL BE DENIED. FOR
 PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR
 FINISH, NORMAL SITE WORK (EXCAVATION AND
 BACKFILL FOR BUILDINGS), ARCHITECTURAL
 AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND
 VALUE. VALUATION REFERENCES MAY INCLUDE
 THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS ECT.) WITH
 REGIONAL ADJUSTMENTS FOR LOCATION AS
 PUBLISHED BY INTERNATIONAL CODE
 CONGRESS.
 NOTE: THE INDICATED VALUE OF $495.00 STILL SEEMS WAY TO
 LOW. THE INDICATED APPLIANCES (WATER HEATER AND BBQ) ON
 THE DRAWING COST MORE THAN $495.00. AGAIN PLEASE ADJUST
 THE VALUE ON THE RESUBMITTAL OR AN ACCESSED VALUE WILL
 BE DONE ON THE RESUBMITTAL AND FEES MIGHT NEED TO BE
 PAID BEFORE A PERMIT IS ISSUED.
  
 *******************************************************
 *******************************************************
 *******************************************************
 *******************************************************
  
 THE FOLLOWING ARE NEW COMMENTS OF CORRECTIONS THAT ARE
 REQUIRED FOR GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 7. PER FBC-2004, CHAPTER 1, SECTION 106.1: TWO (2)
 COMPLETE SETS OF DRAWINGS ARE REQUIRED FOR PLAN REVIEW,
 ONLY ONE (1) WAS RESUBMITTED.
  
 8. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-11-07 Cont ID  
Sent By mperson Date 2006-11-07 Time 14:09 Rev Time 0.45
Received By mperson Date 2006-11-07 Time 14:09 Sent To PC
Notes
2006-11-07 14:59:32UNSAT
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN
 REVIEW TO MEET CODE COMPLIANCE:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE:THE SUBMITED DRAWING IS NOT AN ISOMETRIC. IT
 MIGHT INDICATE ALL CUT SECTIONS OF PIPE,YET IT IS
 VERY HARD TO DISTINGUISH ABOVE GROUND AND BELOW GROUND
 PIPING, AND THERE ARE NO CORRESPONDING LENGTHS
 INDICATED ON DRAWING.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 NOTE: NOT ALL PIPE SIZES OR MATERIAL ARE INDICATED ON
 DRAWING.
  
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 NOTE: PLEASE CORRECT THE TOTAL BTU LOAD FROM 144,000 TO
 244,000.
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
 NOTE: PLEASE SUBMIT MANUFACTURER CUT SHEETS OF THE MP
 REGULATORS AND CLEARLY INDICATE THERE LOCATION ON THE
 DRAWING.
  
 6. PER FBC-2004, CHAPTER 1, SECTION
 108.3, BUILDING PERMIT VALUATION: IF IN
 THE OPINION OF THE BUILDING OFFICIAL,
 THE CLAIMED VALUATION OF THE BUILDING,
 ALTERATION, STRUCTURE, ELECTRICAL, GAS
 MECHANICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATED ON THE APPLICATION,
 THE PERMIT SHALL BE DENIED. FOR
 PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR
 FINISH, NORMAL SITE WORK (EXCAVATION AND
 BACKFILL FOR BUILDINGS), ARCHITECTURAL
 AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND
 VALUE. VALUATION REFERENCES MAY INCLUDE
 THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS ECT.) WITH
 REGIONAL ADJUSTMENTS FOR LOCATION AS
 PUBLISHED BY INTERNATIONAL CODE
 CONGRESS.
 NOTE:THE INDICATED VALUE OF $495.00 SEEMS WAY TO LOW.
 THE INDICATED APPLIANCES (WATER HEATER AND BBQ) ON THE
 DRAWING COST MORE THAN $495.00. PLEASE ADJUST THE VALUE
 ON THE RESUBMITTAL OR AN ACCESSED VALUE WILL BE DONE ON
 THE RESUBMITTAL AND FEES MIGHT NEED TO BE PAID BEFORE A
 PERMIT IS ISSUED.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-11-27 Cont ID  
Sent By adarroug Date 2006-11-27 Time 16:09 Rev Time 0.00
Received By adarroug Date 2006-11-27 Time 16:09 Sent To G
Notes
2006-11-27 16:10:06TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-11-07 Cont ID  
Sent By mperson Date 2006-11-07 Time 15:00 Rev Time 0.00
Received By mperson Date 2006-11-03 Time 09:46 Sent To  
Notes
2006-11-03 09:46:26TO "G" BOX