Plan Review Details - Permit 06101156
| Plan Review Stops For Permit 06101156 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
8 |
Status |
P |
Date |
2010-09-13 |
|
|
Cont ID |
|
| Sent By |
dwise |
Date |
2010-09-13 |
Time |
15:40 |
Rev Time |
0.00 |
| Received By |
dwise |
Date |
2010-09-13 |
Time |
15:40 |
Sent To |
|
|
| Notes |
| 2010-09-13 15:41:36 | APPROVED WITH PROVISO BY R. MCDOUGAL ON 12/15/2009 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
F |
Date |
2009-12-15 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-12-15 |
Time |
12:07 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-12-15 |
Time |
07:50 |
Sent To |
|
|
| Notes |
| 2009-12-15 16:08:00 | REVISION REQUIRED THE FOLLOWING ITEMS HAVE BEEN DEEMED | | | DEFICIENT OR WERE NOTED TO BE MISSING UPON REVIEW: | | | | | | 1) TRUSS DRAWINGS AND LAYOUT SIGNED SEALED AND DATED BY | | | THE TRUSS ENGINEER AND REVIEWED BY THE DESIGNER OF | | | RECORD OF THE STRUCTURE. MUST BE REVIEWED AND APPROVED | | | PRIOR TO INSTALLATION. FBC 106.3.5 | | | | | | 2) TWO COPIES OF A KEY PLAN AND INSTALLATION SCHEDULE | | | FOR THE ACCORDION SHUTTERS. SPECIFY THE OPENING | | | LOCATIONS OF THE SHUTTERS, THE MOUNT TYPE, SPANS, | | | FASTENERS, FASTENER SPACING, ETC. FBC 1609.1.2 NOTE: IF | | | ALL OF THE REQUIRED INFORMATION IS SUBMITTED WITH THIS | | | PERMIT THE SHUTTERS WILL BE INCLUDED WITH THIS PERMIT. | | | IF NOT, A SEPARATE PERMIT AND FEES WILL BE REQUIRED AND | | | THE C.O. WILL NOT BE ISSUED UNTIL THEY HAVE BEEN | | | INSTALLED AND APPROVED. | | | | | | 3) TWO COPIES OF PRODUCT APPROVALS FOR THE BULLET | | | RESISTANT WINDOWS AND PAYMENT DRAWER ASSEMBLIES, THE | | | ROOFING MATERIALS AND THE WALL MOUNTED LOUVER VENTS FOR | | | ATTIC VENTILATION. DCA RULE 9B-72 | | | | | | 4) THE GLASS TYPE, MULLION TYPE AND ANCHOR TYPE OF THE | | | STOREFRONT WINDOWS. THIS INFORMATION DETERMINES THE | | | DESIGN PRESSURES FOR THE ASSEMBLIES. FBC 1604.9 THIS | | | INFORMATION CAN BE PROVIDED WITH THE SHOP DRAWINGS FROM | | | THE WINDOW COMPANY. THEY WILL NEED TO BE SUBMITTED AND | | | APPROVED PRIOR TO INSTALLATION. | | | | | | 5) THE HINGE OPTION AND IF THE STOREFRONT DOOR IS | | | REINFORCED OR NOT. THIS INFORMATION DETERMINES DESIGN | | | PRESSURES FOR THE ASSEMBLY. FBC 1604.9 THIS INFORMATION | | | CAN BE PROVIDED WITH THE SHOP DRAWINGS. | | | | | | | | | | | 2009-12-15 14:49:05 | TEMPORARY FAILED STATUS WILL REMAIN UNTIL A CONTRACTOR | | | IS DETERMINED. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
F |
Date |
2009-09-29 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-09-29 |
Time |
14:41 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-09-29 |
Time |
14:40 |
Sent To |
|
|
| Notes |
| 2009-09-29 16:19:24 | 2007 FBC W/2009 REVISIONS | | | CONVENIENCE STORE WITH FUEL DISPENSING | | | | | | DENIED BY BUILDING | | | | | | 1) ON SHEET S-1 THE COMPONENT AND CLADDING PRESSURES | | | ARE INCORRECT FOR EXPOSURE C WITH A 20' MEAN ROOF | | | HEIGHT. THE ONES LISTED ARE EXPOSURE 'B' PRESSURES. | | | PLEASE CORRECT. FBC 1609.4.1 | | | | | | 2) ON SHEET S-2 THE NOTES AT THE BOTTOM OF THE PAGE | | | LIST THE MEAN ROOF HEIGHT AS 30' AND THE BASIC WIND | | | PRESSURE AS 29.85 PSF. THESE ARE INCORRECT. THE MEAN | | | ROOF HEIGHT IS SPECIFIED AS 20' AND THE BASIC WIND | | | PRESSURE FOR EXPOSURE C AS 38.38 ON SHEET S-1. PLEASE | | | CORRECT. FBC 1609 | | | | | | 3) SUBMIT TRUSS DRAWINGS AND LAYOUT SIGNED SEALED AND | | | DATED BY THE TRUSS ENGINEER AND REVIEWED BY THE | | | DESIGNER OF RECORD OF THE STRUCTURE. MUST BE REVIEWED | | | AND APPROVED PRIOR TO INSTALLATION. FBC 106.3.5 | | | | | | 4) SUBMIT TWO COPIES OF A KEY PLAN AND INSTALLATION | | | SCHEDULE FOR THE ACCORDION SHUTTERS. SPECIFY THE | | | OPENING LOCATIONS OF THE SHUTTERS, THE MOUNT TYPE, | | | SPANS, FASTENERS, FASTENER SPACING, ETC. FBC 1609.1.2 | | | NOTE: IF ALL OF THE REQUIRED INFORMATION IS SUBMITTED | | | WITH THIS PERMIT THE SHUTTERS WILL BE INCLUDED WITH | | | THIS PERMIT. IF NOT, A SEPARATE PERMIT AND FEES WILL BE | | | REQUIRED AND THE C.O. WILL NOT BE ISSUED UNTIL THEY | | | HAVE BEEN INSTALLED AND APPROVED. | | | | | | 5) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE | | | BULLET RESISTANT WINDOWS AND PAYMENT DRAWER ASSEMBLIES. | | | DCA RULE 9B-72 | | | | | | 6) ON THE PRODUCT APPROVALS FOR THE STOREFRONT WINDOWS, | | | SPECIFY THE GLASS TYPE, MULLION TYPE AND ANCHOR TYPE BY | | | CIRCLING THE APPROPRIATE ITEMS IN THE TABLES. THIS | | | INFORMATION DETERMINES THE DESIGN PRESSURES FOR THE | | | ASSEMBLIES. FBC 1604.9 THIS INFORMATION CAN BE PROVIDED | | | WITH THE SHOP DRAWINGS FROM THE WINDOW COMPANY. THEY | | | WILL NEED TO BE SUBMITTED AND APPROVED PRIOR TO | | | INSTALLATION. | | | | | | 7) ON THE PRODUCT APPROVALS FOR THE STOREFRONT DOOR | | | SPECIFY THE HINGE OPTION AND IF REINFORCED OR NOT. THIS | | | INFORMATION DETERMINES DESIGN PRESSURES FOR THE | | | ASSEMBLY. FBC 1604.9 THIS INFORMATION CAN ALSO BE | | | PROVIDED WITH THE SHOP DRAWINGS. | | | | | | 8) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE | | | ROOFING MATERIALS AND THE WALL MOUNTED LOUVER VENTS FOR | | | ATTIC VENTILATION. DCA RULE 9B-72 | | | | | | 9) PLEASE RESPOND TO COMMENTS IN WRITING. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2009-07-24 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-07-24 |
Time |
14:26 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-07-24 |
Time |
14:26 |
Sent To |
|
|
| Notes |
| 2009-07-24 12:22:54 | 2007 FBC W/2009 REVISIONS | | | CONVENIENCE STORE WITH FUEL DISPENSING | | | | | | DENIED BY BUILDING | | | | | | 1) ON SHEET S-1 AND THE TOP OF SHEET S-2 THE EXPOSURE | | | CATEGORY IS CORRECTLY SPECIFIED AS 'C'. HOWEVER, AT THE | | | BOTTOM OF SHEET S-2 THE EXPOSURE 'B' IS SPECIFIED ON | | | THE ROOF ZONE DETAIL. PLEASE CORRECT. FBC 1609.4.1 | | | | | | 2) THE COMPONENT AND CLADDING PRESSURES ON SHEET A-5 DO | | | NOT CORRESPOND WITH THOSE ON SHEET S-1. THE PRESSURES | | | ON A-5 ARE FOR EXPOSURE CATEGORY 'B'. PLEASE CORRECT. | | | FBC 1609 | | | | | | 3) SUBMIT TRUSS DRAWINGS AND LAYOUT SIGNED SEALED AND | | | DATED BY THE TRUSS ENGINEER AND REVIEWED BY THE | | | DESIGNER OF RECORD OF THE STRUCTURE. MUST BE REVIEWED | | | AND APPROVED PRIOR TO INSTALLATION. FBC 106.3.5 | | | | | | 4) SHEET A-1 AND S-2 OF THE PLANS SPECIFY IMPACT | | | WINDOWS AND NO SHUTTERS. HOWEVER, THE PRODUCT APPROVALS | | | THAT WERE SUBMITTED FOR THE STOREFRONTS ARE NOT IMPACT | | | RATED AND PRODUCT APPROVALS FOR ACCORDION SHUTTERS WERE | | | SUBMITTED. PLEASE CLARIFY. FBC 1609.1.2 | | | | | | 5) SUBMIT TWO COPIES OF A KEY PLAN AND INSTALLATION | | | SCHEDULE FOR THE ACCORDION SHUTTERS. SPECIFY THE | | | OPENING LOCATIONS OF THE SHUTTERS, THE MOUNT TYPE, | | | SPANS, FASTENERS, FASTENER SPACING, ETC. FBC 1609.1.2 | | | | | | 6) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE | | | BULLET RESISTANT WINDOWS AND PAYMENT DRAWER ASSEMBLIES. | | | DCA RULE 9B-72 | | | | | | 7) ON THE PRODUCT APPROVALS FOR THE STOREFRONT WINDOWS, | | | SPECIFY THE GLASS TYPE, MULLION TYPE AND ANCHOR TYPE BY | | | CIRCLING THE APPROPRIATE ITEMS IN THE TABLES. THIS | | | INFORMATION DETERMINES THE DESIGN PRESSURES FOR THE | | | ASSEMBLIES. FBC 1604.9 | | | | | | 8) ON THE PRODUCT APPROVALS FOR THE STOREFRONT DOOR | | | SPECIFY THE HINGE OPTION AND IF REINFORCED OR NOT. THIS | | | INFORMATION DETERMINES DESIGN PRESSURES FOR THE | | | ASSEMBLY. FBC 1604.9 | | | | | | 9) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE | | | ROOFING MATERIALS AND THE WALL MOUNTED LOUVER VENTS FOR | | | ATTIC VENTILATION. DCA RULE 9B-72 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2009-06-02 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-06-02 |
Time |
13:37 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-06-02 |
Time |
13:37 |
Sent To |
|
|
| Notes |
| 2009-06-02 14:54:26 | 2007 FBC W/2009 REVISIONS | | | CONVENIENCE STORE WITH FUEL DISPENSING | | | | | | | | | DENIED BY BUILDING | | | | | | 1) IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY, PLANS STAMPED BY THEM AND | | | COPY OF RECEIPT SUBMITTED TO CITY OF | | | WEST PALM BEACH BUILDING DEPARTMENT, | | | BEFORE A BUILDING PERMIT CAN BE ISSUED. | | | | | | 2) THE CODE THAT IS CURRENTLY IN EFFECT IS THE 2007 | | | FLORIDA BUILDING CODE WITH 2009 SUPPLEMENT. PLEASE | | | CORRECT CODE NOTE ON SHEET SP-1. | | | | | | 3) SPECIFY THE REQUIRED SOIL BEARING CAPACITY ON THE | | | PLANS. FBC 1804.1 | | | | | | 4) PLEASE UPDATE THE STANDARDS SPECIFIED ON SHEETS S-1 | | | AND S-2 TO THE EDITIONS SPECIFIED IN CHAPTER 35 OF THE | | | 2007 FBC. ASCE 7-05, ACI 318-05, ACI 315-05, TMS 402-05 | | | AND TMS 602-05. | | | | | | 5) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE | | | EXTERIOR WINDOWS, DOORS, STOREFRONTS, MULLIONS, ROOFING | | | MATERIAL, TRUSS CONNECTORS, IMPACT PROTECTION PRODUCTS, | | | ETC. AS REQUIRED BY FAC RULE 9B-72. | | | | | | 6) SUBMIT TRUSS DRAWINGS AND LAYOUT SIGNED, SEALED AND | | | DATED BY THE TRUSS ENGINEER AND REVIEWED AND APPROVED | | | BY THE DESIGNER OF RECORD FOR THE STRUCTURE. FBC | | | 106.3.5* CITY AMENDMENTS. NOTE: THE UPLIFT AT HIP | | | GIRDER TRUSSES MAY EXCEED 1500#. | | | | | | 7) SPECIFY THE REQUIRED SOIL BEARING CAPACITY ON THE | | | PLANS. FBC 1804.1. | | | | | | 8) THE ROOF VENTILATION NOTE ON A-4 SITES EXCEPTION #2 | | | TO FBC 1203.2. THIS EXCEPTION APPLIES TO UN-VENTED | | | ATTICS SUCH AS THOSE USING SPRAY FOAM INSULATION | | | APPLIED TO THE UNDERSIDE OF THE ROOF DECK. THE PLANS DO | | | NOT INDICATE THIS TYPE OF ATTIC. SHOW COMPLIANCE WITH | | | FBC 1203.2. | | | | | | 9) 2603.4.1.3 WALK -IN COOLERS . | | | IN NONSPRINKLERED BUILDINGS, FOAM PLASTIC HAVING A | | | THICKNESS THAT DOES NOT EXCEED 4 INCHES (102 MM) AND A | | | MAXIMUM FLAME SPREAD INDEX OF 75 IS PERMITTED IN WALK | | | -IN COOLERS OR FREEZER UNITS WHERE THE AGGREGATE FLOOR | | | AREA DOES NOT EXCEED 400 SQUARE FEET (37 M 2 ) AND THE | | | FOAM PLASTIC IS COVERED BY A METAL FACING NOT LESS THAN | | | 0.032-INCH-THICK (0.81 MM) ALUMINUM OR | | | CORROSION-RESISTANT STEEL HAVING A MINIMUM BASE METAL | | | THICKNESS OF 0.016 INCH (0.41 MM). A THICKNESS OF UP TO | | | 10 INCHES (254 MM) IS PERMITTED WHERE PROTECTED BY A | | | THERMAL BARRIER. THE WALK-IN COOLER SHOWN ON THE PLANS | | | APPEARS TO BE LARGER THAN THE 400 SQFT ALLOWED. SHOW | | | HOW WALK-IN COOLER COMPLIES. PROVIDE MANUFACTURER'S | | | SPECIFICATIONS AND DETAILS. | | | | | | 10) DOOR #S 3 AND 5 DO NOT HAVE THE MANEUVERING | | | CLEARANCES REQUIRED BY FBC 11-4.13.6. A MINIMUM OF 18" | | | IS REQUIRED ON THE PULL SIDE AT THE LATCH OF SIDE SWING | | | DOORS. | | | | | | 11) AS NOTED ON THE PLAN A SEPARATE PERMIT WILL BE | | | REQUIRED FOR THE STAND ALONE CANOPY AT GAS PUMPS. | | | | | | 12) THE LIFE SAFETY PLAN DOES NOT INDICATE THE TRAVEL | | | DISTANCE FROM INSIDE THE WALK-IN COOLER TO THE ONE | | | EXIT. THIS APPEARS TO BE A TRAVEL DISTANCE IN EXCESS OF | | | 75 FT, WHICH WOULD REQUIRE TWO EXITS. FBC 1019.2 AND | | | 1015.1 | | | | | | 13) ON LS-1, THE OCCUPANT LOAD FOR THE WALK-IN COOLER | | | SHOULD BE INCLUDED IN THE TABLE AS A STORAGE OCCUPANCY. | | | FBC TABLE 1004.1.1 AND TABLE 508.3 | | | | | | 14) THE WEST EXTERIOR WALL THAT IS LOCATED AT 6 FT FROM | | | THE PROPERTY LINE IS REQUIRED TO HAVE A ONE HOUR FIRE | | | RATING PER FBC TABLE 602. THE MAXIMUM AREA OF EXTERIOR | | | WALL OPENINGS IS 10 PERCENT PER TABLE 704.8. PLEASE | | | NOTE THIS ON PLANS. | | | | | | NOTE: FOR THE NORTH OR REAR WALL WHICH IS LOCATED ON AN | | | ALLEY, THE FIRE SEPARATION DISTANCE IS MEASURED FROM | | | THE FACE OF THE BUILDING TO THE CENTERLINE OF THE | | | ALLEY, WHICH IS 16 FEET BASED ON THE SITE PLAN. THIS | | | WALL IS NOT REQUIRED TO BE FIRE RATED BY TABLE 602 AND | | | FOOTNOTE I OF TABLE 704.8 ALLOWS UNLIMITED UNPROTECTED | | | OPENINGS. | | | | | | NOTE: ADDITIONAL COMMENTS MAY RESULT WHEN THESE | | | COMMENTS ARE ADDRESSED, DUE TO THE AMOUNT OF MISSING | | | INFORMATION. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2007-11-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2007-11-14 |
Time |
10:41 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2007-11-13 |
Time |
17:33 |
Sent To |
|
|
| Notes |
| 2007-11-14 11:46:58 | 2004 FBC | | | CONSTRUCT NEW CONVENIENCE STORE (PLAN REVIEW) | | | | | | DENIED BY BUILDING | | | | | | 1) IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY, PLANS STAMPED BY THEM AND | | | COPY OF RECEIPT SUBMITTED TO CITY OF | | | WEST PALM BEACH BUILDING DEPARTMENT, | | | BEFORE A BUILDING PERMIT CAN BE ISSUED. | | | | | | 2)A RECORDED COPY OF THE NOTICE OF COMMENCEMENT | | | MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 3) COMPLIED. | | | | | | 4) COMPLIED. | | | | | | 5) FBC SECTION 1603.1.2 THAT WAS SPECIFIED UNDER DESIGN | | | PARAMETERS ON SHEETS A2 AND A7 IS NOT THE APPROPRIATE | | | SECTION. PLEASE CORRECT. SPECIFY CHAPTER 16. | | | | | | 6) COMPLIED. | | | | | | 7) PROVIDESURVEY/SITE PLANS INDICATING THE LOCATION | | | OF THE STRUCTURE, DISTANCE TO PROPERTY LINES, DISTANCES | | | TO OTHER STRUCTURES ON THE PROPERTY FOR DETERMINING | | | FIRE SEPARATION DISTANCES. SEE FBC 702, 704.8 AND TABLE | | | 602. THE SURVEY THAT WAS SUBMITTED DOES NOT CORRESPOND | | | WITH THE SITE PLANS. THE SITE PLAN IS NOT SIGNED AND | | | SEALED. | | | | | | 8)SUBMIT ENERGY CALCULATIONS FOR THE STRUCTURE AS | | | REQUIRED BY FBC 13-4. | | | | | | 9)SUBMIT PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, | | | DOORS, STOREFRONTS, MULLIONS, ROOFING MATERIAL, IMPACT | | | PROTECTION PRODUCTS, ETC. | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. | | | | | | 10)WPB ADMIN CODE 106.3* PRODUCT | | | APPROVALS. THOSE PRODUCT WHICH ARE | | | REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL | | | FOR JURISDICTIONAL APPROVAL. | | | | | | 11) SPECIFY HOW IMPACT PROTECTION OF OPENINGS WILL BE | | | PROVIDED AS REQUIRED BY FBC 1609.1.4. IF STORM PANELS | | | ARE TO BE USED, SUBMIT 2 COPIES OF PRODUCT APPROVALS, A | | | KEY PLAN AND INSTALLATION SCHEDULE. SPECIFY THE MOUNT | | | TYPE, ANCHORS, ANCHOR SPACING, ETC. | | | | | | 12) SUBMIT TRUSS DRAWINGS AND LAYOUT SIGNED, SEALED AND | | | DATED BY THE TRUSS ENGINEER AND REVIEWED AND APPROVED | | | BY THE DESIGNER OF RECORD OF THE STRUCTURE. FBC | | | 106.3.5* CITY AMENDMENTS. NOTE: THE UPLIFT AT HIP | | | GIRDER TRUSSES MAY EXCEED 1500#. | | | | | | 13)SPECIFY THE ANCHOR TYPE, SIZE, EMBED DEPTH AND | | | SIZE OF THE HOLES FOR THE ANCHORS FOR THE STEEL COLUMN | | | BASE. SPECIFY THE WELD TYPE FOR THE COLUMN TO BASE | | | ATTACHMENT. PROVIDE A DETAIL SPECIFYING THE COLUMN CAP | | | FOR THE STEEL COLUMNS WITH FASTENERS, WELDS, ETC. | | | INDICATED. THE STEEL COLUMN THICKNESS ON A-3 IS NOT | | | LEGIBLE. | | | | | | 14) COMPLIED. | | | | | | 15)COMPLIED. | | | | | | 16) THE ROOF ZONE FIGURE FOR THE HIP ROOF ON A7 IS | | | INCORRECT. THE OUTSIDE CORNER AREAS OF THE HIP ROOF ARE | | | ZONE 3 . SEE FBC FIGURE 1609.6.2.2 W/2006 REVISIONS | | | (REVISED SHEETS). | | | | | | 17)SHOW HOW WALK-IN COOLER COMPLIES WITH 2603.4 | | | THERMAL BARRIER. PROVIDE MANUFACTURER'S SPECIFICATIONS | | | AND DETAILS. | | | EXCEPT AS PROVIDED FOR IN SECTIONS 2603.4.1 AND 2603.8 | | | , FOAM PLASTIC SHALL BE SEPARATED FROM THE INTERIOR OF | | | A BUILDING BY AN APPROVED THERMAL BARRIER OF 0.5-INCH | | | (12.7 MM) GYPSUM WALLBOARD OR EQUIVALENT THERMAL | | | BARRIER MATERIAL THAT WILL LIMIT THE AVERAGE | | | TEMPERATURE RISE OF THE UNEXPOSED SURFACE TO NOT MORE | | | THAN 250 DEGREES F (120 DEGREES C) AFTER 15 MINUTES OF | | | FIRE EXPOSURE, COMPLYING WITH THE STANDARD | | | TIME-TEMPERATURE CURVE OF ASTM E 119. THE THERMAL | | | BARRIER SHALL BE INSTALLED IN SUCH A MANNER THAT IT | | | WILL REMAIN IN PLACE FOR 15 MINUTES BASED ON FM 4880, | | | UL 1040, NFPA 286 OR UL 1715. COMBUSTIBLE CONCEALED | | | SPACES SHALL COMPLY WITH SECTION 717 . | | | 2603.4.1 THERMAL BARRIER NOT REQUIRED. | | | THE THERMAL BARRIER SPECIFIED IN SECTION 2603.4 IS NOT | | | REQUIRED UNDER THE CONDITIONS SET FORTH IN SECTIONS | | | 2603.4.1.1 THROUGH 2603.4.1.13 . | | | 2603.4.1.2 COOLER AND FREEZER WALLS. | | | FOAM PLASTIC INSTALLED IN A MAXIMUM THICKNESS OF 10 | | | INCHES (254 MM) IN COOLER AND FREEZER WALLS SHALL: 1. | | | HAVE A FLAME SPREAD INDEX OF 25 OR LESS AND A | | | SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450, WHERE | | | TESTED IN A MINIMUM 4 INCH (102 MM) THICKNESS. | | | 2.HAVE FLASH IGNITION AND SELF-IGNITION | | | TEMPERATURES OF NOT LESS THAN 600 DEGREES F AND 800 | | | DEGREES F (316 DEGREES C AND 427 DEGREES C), | | | RESPECTIVELY. | | | 3.HAVE A COVERING OF NOT LESS THAN 0.032-INCH (0.8 | | | MM) ALUMINUM OR CORROSION-RESISTANT STEEL HAVING A BASE | | | METAL THICKNESS NOT LESS THAN 0.0160 INCH (0.4 MM) AT | | | ANY POINT. | | | 4.BE PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM. | | | WHERE THE COOLER OR FREEZER IS WITHIN A BUILDING, BOTH | | | THE COOLER OR FREEZER AND THAT PART OF THE BUILDING IN | | | WHICH IT IS LOCATED SHALL BE SPRINKLERED. | | | WALK IN COOLERS | | | 2603.4.1.3 WALK -IN COOLERS . | | | IN NONSPRINKLERED BUILDINGS, FOAM PLASTIC HAVING A | | | THICKNESS THAT DOES NOT EXCEED 4 INCHES (102 MM) AND A | | | MAXIMUM FLAME SPREAD INDEX OF 75 IS PERMITTED IN WALK | | | -IN COOLERS OR FREEZER UNITS WHERE THE AGGREGATE FLOOR | | | AREA DOES NOT EXCEED 400 SQUARE FEET (37 M 2 ) AND THE | | | FOAM PLASTIC IS COVERED BY A METAL FACING NOT LESS THAN | | | 0.032-INCH-THICK (0.81 MM) ALUMINUM OR | | | CORROSION-RESISTANT STEEL HAVING A MINIMUM BASE METAL | | | THICKNESS OF 0.016 INCH (0.41 MM). A THICKNESS OF UP TO | | | 10 INCHES (254 MM) IS PERMITTED WHERE PROTECTED BY A | | | THERMAL BARRIER. | | | SHOW HOW WALK-IN COOLER COMPLIES. PROVIDE | | | MANUFACTURER'S SPECIFICATIONS AND DETAILS. | | | | | | 18) SUBMIT SITE PLANS SHOWING ACCESSIBLE PARKING, | | | ACCESSIBLE ROUTE TO THE BUILDING ENTRANCE, RAMPS, CURB | | | CUTS, ETC. AS REQUIRED BY FBC 11-4.1.3. THE PLAN WITH | | | THIS INFORMATION IS REQUIRED TO BE SIGNED AND SEALED BY | | | A FLORIDA LICENSED ARCHITECT OR ENGINEER. SEE FS 471 | | | AND 481. | | | | | | 19) COMPLIED. | | | | | | 20)COMPLIED. | | | | | | 21) COMPLIED. | | | | | | 22) COMPLIED. | | | | | | 23) COMPLIED. | | | | | | 24) COMPLIED. | | | | | | 25) A SEPARATE PERMIT WILL BE REQUIRED FOR THE STAND | | | ALONE CANOPY AT GAS PUMPS. | | | | | | 26) COMPLIED. | | | | | | 27) ADDITIONAL COMMENTS MAY RESULT WHEN THESE COMMENTS | | | ARE ADDRESSED, DUE TO THE AMOUNT OF MISSING | | | INFORMATION. | | | | | | 28) SPECIFY THE WIDTH OF THE STRUCTURE ON THE PLANS. | | | FBC 106.1* CITY AMENDMENTS | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-03-28 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2007-03-28 |
Time |
14:25 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2007-03-28 |
Time |
11:24 |
Sent To |
|
|
| Notes |
| 2007-03-28 14:24:55 | DENIED BY BUILDING | | | | | | 1) IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY, PLANS STAMPED BY THEM AND | | | COPY OF RECEIPT SUBMITTED TO CITY OF | | | WEST PALM BEACH BUILDING DEPARTMENT, | | | BEFORE A BUILDING PERMIT CAN BE ISSUED. | | | | | | 2)A RECORDED COPY OF THE NOTICE OF COMMENCEMENT | | | MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 3) THE CODE THAT IS CURRENTLY IN EFFECT IS THE 2004 | | | FLORIDA BUILDING CODE. PLEASE CORRECT GENERAL NOTE #1 | | | ON SHEET A-1. | | | | | | 4) THE WRONG EDITION OF ASCE 7 IS SPECIFIED UNDER | | | DESIGN PARAMETERS ON SHEETS A2 AND A7. THE EDITION | | | REFERENCED BY THE 2004 FBC IS ASCE 7-02. PLEASE | | | CORRECT. | | | | | | 5) FBC SECTION 1606.1.7 THAT WAS SPECIFIED UNDER DESIGN | | | PARAMETERS ON SHEETS A2 AND A7 IS NO LONGER IN THE | | | CODE. PLEASE CORRECT. | | | | | | 6) SPECIFY THE OCCUPANCY TYPE. SEE FBC 302.1. | | | | | | 7) PROVIDESURVEY/SITE PLANS INDICATING THE LOCATION | | | OF THE STRUCTURE, DISTANCE TO PROPERTY LINES, DISTANCES | | | TO OTHER STRUCTURES ON THE PROPERTY FOR DETERMINING | | | FIRE SEPARATION DISTANCES. SEE FBC 702, 704.8 AND TABLE | | | 602. | | | | | | 8)SUBMIT ENERGY CALCULATIONS FOR THE STRUCTURE AS | | | REQUIRED BY FBC 13-4. | | | | | | 9)SUBMIT PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, | | | DOORS, STOREFRONTS, MULLIONS, ROOFING MATERIAL, IMPACT | | | PROTECTION PRODUCTS, ETC. | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. | | | | | | 10)WPB ADMIN CODE 106.3* PRODUCT | | | APPROVALS. THOSE PRODUCT WHICH ARE | | | REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL | | | FOR JURISDICTIONAL APPROVAL. | | | | | | 11) SPECIFY HOW IMPACT PROTECTION OF OPENINGS WILL BE | | | PROVIDED AS REQUIRED BY FBC 1609.1.4. | | | | | | 12) SUBMIT TRUSS DRAWINGS AND LAYOUT SIGNED, SEALED AND | | | DATED BY THE TRUSS ENGINEER AND REVIEWED AND APPROVED | | | BY THE DESIGNER OF RECORD OF THE STRUCTURE. FBC | | | 106.3.5* CITY AMENDMENTS. NOTE: THE UPLIFT AT HIP | | | GIRDER TRUSSES MAY EXCEED 1500#. | | | | | | 13) PROVIDE DIMENSIONS TO INDICATE THE LOCATIONS OF THE | | | STEEL COLUMNS SHOWN IN DETAIL 2 ON A-3 ON THE | | | FOUNDATION PLAN. SPECIFY THE ANCHOR TYPE, SIZE, EMBED | | | DEPTH AND SIZE OF THE HOLES FOR THE ANCHORS FOR THE | | | STEEL COLUMN BASE. SPECIFY THE WELD TYPE FOR THE COLUMN | | | TO BASE ATTACHMENT. PROVIDE A DETAIL SPECIFYING THE | | | COLUMN CAP FOR THE STEEL COLUMNS WITH FASTENERS, WELDS, | | | ETC. INDICATED. | | | | | | 14) SPECIFY THE LOCATION AND SIZE OF THE ATTIC ACCESS | | | REQUIRED BY FBC 1209.2. | | | | | | 15)WALL SECTION 1 ON A-4 SPECIFIES ASPHALT ROOF | | | SHINGLES AND THE ELEVATIONS SHOW A METAL ROOF. PLEASE | | | CORRECT. | | | | | | 16) THE ROOF ZONE FIGURE FOR THE HIP ROOF ON A7 IS | | | INCORRECT. THE OUTSIDE CORNER AREAS OF THE HIP ROOF ARE | | | ZONE 3 . SEE FBC FIGURE 1609.6.2.2 (REVISED SHEETS). | | | | | | 17)SHOW HOW WALK-IN COOLER COMPLIES WITH 2603.4 | | | THERMAL BARRIER. PROVIDE MANUFACTURER'S SPECIFICATIONS | | | AND DETAILS. | | | EXCEPT AS PROVIDED FOR IN SECTIONS 2603.4.1 AND 2603.8 | | | , FOAM PLASTIC SHALL BE SEPARATED FROM THE INTERIOR OF | | | A BUILDING BY AN APPROVED THERMAL BARRIER OF 0.5-INCH | | | (12.7 MM) GYPSUM WALLBOARD OR EQUIVALENT THERMAL | | | BARRIER MATERIAL THAT WILL LIMIT THE AVERAGE | | | TEMPERATURE RISE OF THE UNEXPOSED SURFACE TO NOT MORE | | | THAN 250 DEGREES F (120 DEGREES C) AFTER 15 MINUTES OF | | | FIRE EXPOSURE, COMPLYING WITH THE STANDARD | | | TIME-TEMPERATURE CURVE OF ASTM E 119. THE THERMAL | | | BARRIER SHALL BE INSTALLED IN SUCH A MANNER THAT IT | | | WILL REMAIN IN PLACE FOR 15 MINUTES BASED ON FM 4880, | | | UL 1040, NFPA 286 OR UL 1715. COMBUSTIBLE CONCEALED | | | SPACES SHALL COMPLY WITH SECTION 717 . | | | 2603.4.1 THERMAL BARRIER NOT REQUIRED. | | | THE THERMAL BARRIER SPECIFIED IN SECTION 2603.4 IS NOT | | | REQUIRED UNDER THE CONDITIONS SET FORTH IN SECTIONS | | | 2603.4.1.1 THROUGH 2603.4.1.13 . | | | 2603.4.1.2 COOLER AND FREEZER WALLS. | | | FOAM PLASTIC INSTALLED IN A MAXIMUM THICKNESS OF 10 | | | INCHES (254 MM) IN COOLER AND FREEZER WALLS SHALL: 1. | | | HAVE A FLAME SPREAD INDEX OF 25 OR LESS AND A | | | SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450, WHERE | | | TESTED IN A MINIMUM 4 INCH (102 MM) THICKNESS. | | | 2.HAVE FLASH IGNITION AND SELF-IGNITION | | | TEMPERATURES OF NOT LESS THAN 600 DEGREES F AND 800 | | | DEGREES F (316 DEGREES C AND 427 DEGREES C), | | | RESPECTIVELY. | | | 3.HAVE A COVERING OF NOT LESS THAN 0.032-INCH (0.8 | | | MM) ALUMINUM OR CORROSION-RESISTANT STEEL HAVING A BASE | | | METAL THICKNESS NOT LESS THAN 0.0160 INCH (0.4 MM) AT | | | ANY POINT. | | | 4.BE PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM. | | | WHERE THE COOLER OR FREEZER IS WITHIN A BUILDING, BOTH | | | THE COOLER OR FREEZER AND THAT PART OF THE BUILDING IN | | | WHICH IT IS LOCATED SHALL BE SPRINKLERED. | | | WALK IN COOLERS | | | 2603.4.1.3 WALK -IN COOLERS . | | | IN NONSPRINKLERED BUILDINGS, FOAM PLASTIC HAVING A | | | THICKNESS THAT DOES NOT EXCEED 4 INCHES (102 MM) AND A | | | MAXIMUM FLAME SPREAD INDEX OF 75 IS PERMITTED IN WALK | | | -IN COOLERS OR FREEZER UNITS WHERE THE AGGREGATE FLOOR | | | AREA DOES NOT EXCEED 400 SQUARE FEET (37 M 2 ) AND THE | | | FOAM PLASTIC IS COVERED BY A METAL FACING NOT LESS THAN | | | 0.032-INCH-THICK (0.81 MM) ALUMINUM OR | | | CORROSION-RESISTANT STEEL HAVING A MINIMUM BASE METAL | | | THICKNESS OF 0.016 INCH (0.41 MM). A THICKNESS OF UP TO | | | 10 INCHES (254 MM) IS PERMITTED WHERE PROTECTED BY A | | | THERMAL BARRIER. | | | SHOW HOW WALK-IN COOLER COMPLIES. PROVIDE | | | MANUFACTURER'S SPECIFICATIONS AND DETAILS. | | | | | | 18) SUBMIT SITE PLANS SHOWING ACCESSIBLE PARKING, | | | ACCESSIBLE ROUTE TO THE BUILDING ENTRANCE, RAMPS, CURB | | | CUTS, ETC. AS REQUIRED BY FBC 11-4.1.3. | | | | | | 19) ALL DOORS ON THE ACCESSIBLE ROUTESARE REQUIRED TO | | | HAVE ADA COMPLIANT HARDWARE. SEE FBC 11-4.13.9. | | | | | | 20)SHOW THE REQUIRED CLEAR FLOOR SPACE AT THE WATER | | | CLOSET AND LAVATORY SPECIFY DIMENSIONS. SEE FBC | | | 11-4.16.2 AND 11-4.19.3. | | | | | | 21) PROVIDE AN ACCESSIBLE COUNTER AS REQUIRED BY FBC | | | 11-7.2. | | | | | | 22) DOOR 03DOES NOT HAVE THEMANEUVERING CLEARANCES | | | REQUIRED BY FBC 11-4.13.6. A MINIMUM OF 18" IS REQUIRED | | | ON THE PULL SIDE AT THE LATCH OF SIDE SWING DOORS. | | | | | | 23) FBC 11-4.16.3 REQUIRES THE HEIGHT OF WATER CLOSETS | | | TO BE 17" TO 19" MEASURED TO TOP OF THE TOILET SEAT. | | | PLEASE CORRECT DETAIL 5 ON A-4. | | | | | | 24) FBC 11-4.16.4 REQUIRES THE GRAB BAR BEHIND THE | | | WATER CLOSET TO BE 36" MINIMUM. | | | | | | 25) A SEPARATE PERMIT WILL BE REQUIRED FOR THE STAND | | | ALONE CANOPY AT GAS PUMPS. | | | | | | 26) THE FIRM'S LICENSE NUMBER IS REQUIRED TO BE IN THE | | | TITLE BLOCK ON EACH SHEET OF THE PLANS. SEE FS 481 AND | | | FAC 61G1-16.004. | | | | | | 27) ADDITIONAL COMMENTS MAY RESULT WHEN THESE COMMENTS | | | ARE ADDRESSED, DUE TO THE AMOUNT OF MISSING | | | INFORMATION. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-11-15 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2006-11-15 |
Time |
09:22 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2006-11-15 |
Time |
07:03 |
Sent To |
|
|
| Notes |
| 2006-11-15 13:43:43 | DENIED BY BUILDING | | | | | | 1) IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY, PLANS STAMPED BY THEM AND | | | COPY OF RECEIPT SUBMITTED TO CITY OF | | | WEST PALM BEACH BUILDING DEPARTMENT, | | | BEFORE A BUILDING PERMIT CAN BE ISSUED. | | | | | | 2) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT MUST | | | BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 3) THE CODE THAT IS CURRENTLY IN EFFECT IS THE 2004 | | | FLORIDA BUILDING CODE. PLEASE CORRECT GENERAL NOTE #1 | | | ON SHEET A-1. | | | | | | 4) SPECIFY THE CONSTRUCTION TYPE BASED ON THE 2004 FBC | | | DESIGNATIONS. SPECIFY A OR B. SEE FBC TABLE 601. | | | | | | 5) SPECIFY THE OCCUPANCY TYPE. SEE FBC 302.1. | | | | | | 6) PROVIDE SURVEY/SITE PLANS INDICATING THE LOCATION OF | | | THE STRUCTURE, DISTANCE TO PROPERTY LINES, DISTANCES TO | | | OTHER STRUCTURES ON THE PROPERTY FOR DETERMINING FIRE | | | SEPARATION DISTANCES. SEE FBC 702, 704.8 AND TABLE 602. | | | | | | 7) PLEASE CLARIFY THE SCOPE OF WORK. THE APPLICATION | | | INDICATES THAT THIS IS A REMODEL OF AN EXISTING | | | BUILDING AND THE PLANS APPEAR TO BE FOR NEW | | | CONSTRUCTION. | | | | | | 8) IF THIS IS A REMODEL, SUBMIT A DEMO PLAN FOR THE | | | EXISTING STRUCTURE. | | | | | | 9) IF REMODEL, SPECIFY THE LEVEL OF ALTERATION FOR THE | | | WORK AS SPECIFIED IN THE 2004 FBC EXISTING BUILDING | | | CODE. | | | | | | 10) SUBMIT ENERGY CALCULATIONS FOR THE STRUCTURE AS | | | REQUIRED BY FBC 13-4. | | | | | | 11) SPECIFY THE DESIGN DATA FOR THE STRUCTURE REQUIRED | | | BY FBC 1603.1.4. | | | | | | 12) SUBMIT PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, | | | DOORS, STOREFRONTS, MULLIONS, ROOFING MATERIAL, IMPACT | | | PROTECTION PRODUCTS, ETC. | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. | | | | | | 13) WPB ADMIN CODE 106.3* PRODUCT | | | APPROVALS. THOSE PRODUCT WHICH ARE | | | REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL | | | FOR JURISDICTIONAL APPROVAL. | | | | | | 14) SPECIFY HOW IMPACT PROTECTION OF OPENINGS WILL BE | | | PROVIDED AS REQUIRED BY FBC 1609.1.4. | | | | | | 15) SUBMIT TRUSS DRAWINGS AND LAYOUT SIGNED, SEALED AND | | | DATED BY THE TRUSS ENGINEER AND REVIEWED AND APPROVED | | | BY THE DESIGNER OF RECORD OF THE STRUCTURE. FBC | | | 106.3.5* CITY AMENDMENTS. NOTE: THE UPLIFT AT HIP | | | GIRDER TRUSSES MAY EXCEED 1500#. | | | | | | 16) INDICATE WHERE ON THE FOUNDATION PLAN THE STEEL | | | COLUMN IN DETAIL 2 ON A-3 IS LOCATED. | | | | | | 17) SPECIFY THE LOCATION AND SIZE OF THE ATTIC ACCESS | | | REQUIRED BY FBC 1209.2. | | | | | | 18) WALL SECTION 1 ON A-4 SPECIFIES ASPHALT ROOF | | | SHINGLES AND THE ELEVATIONS SHOW A METAL ROOF. PLEASE | | | CORRECT. | | | | | | 19) 2603.4 THERMAL BARRIER. | | | EXCEPT AS PROVIDED FOR IN SECTIONS 2603.4.1 AND 2603.8 | | | , FOAM PLASTIC SHALL BE SEPARATED FROM THE INTERIOR OF | | | A BUILDING BY AN APPROVED THERMAL BARRIER OF 0.5-INCH | | | (12.7 MM) GYPSUM WALLBOARD OR EQUIVALENT THERMAL | | | BARRIER MATERIAL THAT WILL LIMIT THE AVERAGE | | | TEMPERATURE RISE OF THE UNEXPOSED SURFACE TO NOT MORE | | | THAN 250?F (120?C) AFTER 15 MINUTES OF FIRE EXPOSURE, | | | COMPLYING WITH THE STANDARD TIME-TEMPERATURE CURVE OF | | | ASTM E 119. THE THERMAL BARRIER SHALL BE INSTALLED IN | | | SUCH A MANNER THAT IT WILL REMAIN IN PLACE FOR 15 | | | MINUTES BASED ON FM 4880, UL 1040, NFPA 286 OR UL 1715. | | | COMBUSTIBLE CONCEALED SPACES SHALL COMPLY WITH SECTION | | | 717 . | | | 2603.4.1 THERMAL BARRIER NOT REQUIRED. | | | THE THERMAL BARRIER SPECIFIED IN SECTION 2603.4 IS NOT | | | REQUIRED UNDER THE CONDITIONS SET FORTH IN SECTIONS | | | 2603.4.1.1 THROUGH 2603.4.1.13 . | | | 2603.4.1.2 COOLER AND FREEZER WALLS. | | | FOAM PLASTIC INSTALLED IN A MAXIMUM THICKNESS OF 10 | | | INCHES (254 MM) IN COOLER AND FREEZER WALLS SHALL: 1. | | | HAVE A FLAME SPREAD INDEX OF 25 OR LESS AND A | | | SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450, WHERE | | | TESTED IN A MINIMUM 4 INCH (102 MM) THICKNESS. | | | 2. HAVE FLASH IGNITION AND SELF-IGNITION TEMPERATURES | | | OF NOT LESS THAN 600?F AND 800?F (316?C AND 427?C), | | | RESPECTIVELY. | | | 3. HAVE A COVERING OF NOT LESS THAN 0.032-INCH (0.8 MM) | | | ALUMINUM OR CORROSION-RESISTANT STEEL HAVING A BASE | | | METAL THICKNESS NOT LESS THAN 0.0160 INCH (0.4 MM) AT | | | ANY POINT. | | | 4. BE PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM. WHERE | | | THE COOLER OR FREEZER IS WITHIN A BUILDING, BOTH THE | | | COOLER OR FREEZER AND THAT PART OF THE BUILDING IN | | | WHICH IT IS LOCATED SHALL BE SPRINKLERED. | | | WALK IN COOLERS | | | 2603.4.1.3 WALK -IN COOLERS . | | | IN NONSPRINKLERED BUILDINGS, FOAM PLASTIC HAVING A | | | THICKNESS THAT DOES NOT EXCEED 4 INCHES (102 MM) AND A | | | MAXIMUM FLAME SPREAD INDEX OF 75 IS PERMITTED IN WALK | | | -IN COOLERS OR FREEZER UNITS WHERE THE AGGREGATE FLOOR | | | AREA DOES NOT EXCEED 400 SQUARE FEET (37 M 2 ) AND THE | | | FOAM PLASTIC IS COVERED BY A METAL FACING NOT LESS THAN | | | 0.032-INCH-THICK (0.81 MM) ALUMINUM OR | | | CORROSION-RESISTANT STEEL HAVING A MINIMUM BASE METAL | | | THICKNESS OF 0.016 INCH (0.41 MM). A THICKNESS OF UP TO | | | 10 INCHES (254 MM) IS PERMITTED WHERE PROTECTED BY A | | | THERMAL BARRIER. | | | SHOW HOW WALK-IN COOLER COMPLIES. PROVIDE | | | MANUFACTURER'S SPECIFICATIONS AND DETAILS. | | | | | | 20) SUBMIT SITE PLANS SHOWING ACCESSIBLE PARKING, | | | ACCESSIBLE ROUTE TO THE BUILDING ENTRANCE, RAMPS, CURB | | | CUTS, ETC. AS REQUIRED BY FBC 11-4.1.3. | | | | | | 21) ALL DOORS ON THE ACCESSIBLE ROUTES ARE REQUIRED TO | | | HAVE ADA COMPLIANT HARDWARE. SEE FBC 11-4.13.9. | | | | | | 22) SHOW THE REQUIRED CLEAR FLOOR SPACE AT THE WATER | | | CLOSET AND LAVATORY SPECIFY DIMENSIONS. SEE FBC | | | 11-4.16.2 AND 11-4.19.3. | | | | | | 23) PROVIDE AN ACCESSIBLE COUNTER AS REQUIRED BY FBC | | | 11-7.2. | | | | | | 24) DOORS 03 AND 04 DO NOT HAVE THE MANEUVERING | | | CLEARANCES REQUIRED BY FBC 11-4.13.6. A MINIMUM OF 18" | | | IS REQUIRED ON THE PULL SIDE AT THE LATCH OF SIDE SWING | | | DOORS. | | | | | | 25) FBC 11-4.16.3 REQUIRES THE HEIGHT OF WATER CLOSETS | | | TO BE 17" TO 19" MEASURED TO TOP OF THE TOILET SEAT. | | | PLEASE CORRECT DETAIL 5 ON A-4. | | | | | | 26) FBC 11-4.16.4 REQUIRES THE GRAB BAR BEHIND THE | | | WATER CLOSET TO BE 36" MINIMUM. | | | | | | 27) A SEPARATE PERMIT WILL BE REQUIRED FOR THE STAND | | | ALONE CANOPY AT GAS PUMPS. | | | | | | 28) ADDITIONAL COMMENTS MAY RESULT WHEN THESE COMMENTS | | | ARE ADDRESSED, DUE TO THE AMOUNT OF MISSING | | | INFORMATION. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
8 |
Status |
P |
Date |
2010-09-13 |
|
|
Cont ID |
|
| Sent By |
dwise |
Date |
2010-09-13 |
Time |
15:47 |
Rev Time |
0.00 |
| Received By |
dwise |
Date |
2010-09-13 |
Time |
15:46 |
Sent To |
|
|
| Notes |
| 2010-09-13 15:47:56 | APPROVED BY DEWEY PALMER ON 12/9/2009 PENDING LICENSED | | | CONTRACTOR.DBW |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
7 |
Status |
F |
Date |
2009-12-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-12-09 |
Time |
14:50 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-12-09 |
Time |
14:50 |
Sent To |
|
|
| Notes |
| 2009-12-09 14:51:17 | STILL IN TEMPORARY FAILED STATUS UNTIL LICENSED | | | CONTRACTOR IS SIGNED ON PERMIT APPLICATION. | | | ELECTRICAL PLANS ALREADY STAMPED ON PREVIOUS REVIEW. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
F |
Date |
2009-12-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-09-30 |
Time |
14:33 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-09-30 |
Time |
14:33 |
Sent To |
|
|
| Notes |
| 2009-12-09 14:34:02 | CONTRACTOR NOT YET SIGNED ON. | | | PLANS STAMPED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2009-08-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-08-11 |
Time |
10:04 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-08-11 |
Time |
10:04 |
Sent To |
|
|
| Notes |
| 2009-08-11 10:04:15 | | | | ** DENIED REVIEW ** | | | | | | 1) NOTE: PERMIT HAS NOT YET BEEN APPLIED FOR BY | | | LICENSED CONTRACTOR. | | | | | | 2) NOTE: THE SUBMITTED CALCULATIONS NEED TO INCLUDE ALL | | | EXTERIOR LIGHTING PER 13-415.AB.5, 13-415.AB.2.2. THIS | | | WAS A SPECIFIC NOTE ON THE PREVIOUS REVIEW YET THE SAME | | | ITEMS NEED TO BE ADDRESSED. | | | | | | ** AS PERMIT HAS BEEN APPLIED UNDER PERMIT APPLICATION | | | AS *TBD* TO BE DETERMINED*, IF CALCULATIONS ARE | | | SUBMITTED BACK AGAIN WITH THE SAME ITEMS FS | | | 553.80(2)(B) | | | | | | 3) NOTE: PLANS ARE STILL SHOWING SOME LOCATIONS IN | | | WHICH THERE ARE NOTES FOR 2008 GLITCHES TO THE 2007 | | | FBC. THERE ARE ONLY 2009 SUPPLEMENTS TO THE 2007 FBC. | | | | | | 4) NOTE: PLEASE SUBMIT THE SPECS/MANUFACTURES CUT | | | SHEETS ON MANUAL TRANSFER SWITCH. COULD NOT LOCATE ON | | | THE SPECS SUBMITTED FOR THE DOUBLE THROW SWITCH AS THIS | | | BEING LISTED AS A MANUAL TRANSFER SWITCH? THIS IS | | | LEGALLY REQUIRED TRANSFER SWITCH PER STATUTES. IF THIS | | | EQUIPMENT IS LISTED AS SUCH PLEASE PROVIDE. | | | 110.3,90.7,701.7, FS 526.143 | | | | | | ** PLANS ARE NO LONGER RELEASED PER BUILDING DIRECTOR. | | | A TIME WILL NEED TO BE SET UP TO BRING IN NEW REVISIONS | | | AND CHANGE OUT SHEETS. | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2009-05-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-05-29 |
Time |
08:28 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-05-29 |
Time |
08:28 |
Sent To |
|
|
| Notes |
| 2009-05-29 08:28:49 | **DENIED 4TH REVIEW ** | | | | | | | | | | | | ** THIS IS THE FIRST REVIEW UNDER PERMIT APPLICATION | | | WHICH WAS ONLY MADE ON MAY 13, 2009 | | | | | | ** PLANS ARE ALSO UNDER A COMPLETELY NEW DESIGN TEAM. | | | ** SOME COMMENTS FROM PREVIOUS REVIEWS ALONG NOW WITH | | | SOME NEW COMMENTS BASED ON NEW PLANS AND DOCUMENTS | | | SUBMITTED. | | | PLEASE SEE NOTES BELOW. | | | | | | 1) NOTE: PLANS SUBMITTED AFTER MARCH 1ST, 2009 SHALL BE | | | UNDER NEW CODES. PLANS STATE THE NEW 2007 FBC HOWEVER | | | SOME REFERENCE 2008 GLITCHES AND SOME AREAS REFERENCE | | | 20007 GLITCHES. BASED ON THE ADOPTED CODES AND GLITCHES | | | AS OF MARCH 1ST, 2009 THE CODE IS AS FOLLOWS. | | | 2007 FBC WITH 2009 GLITCHES. | | | 2005 NFPA-70 (ALREADY DONE) | | | 2006 NFPA-101 | | | 2006 NFPA-1 | | | | | | 2) NOTE: PLEASE BE SURE THE SUBMITTED ENERGY | | | CALCULATIONS COORDINATES WITH THE SUBMITTED PLANS. | | | PREVIOUS REVIEWS STATED COMMENTS TO OTHER DESIGN TEAMS | | | TO BE SURE THIS IS DONE. | | | 13-415.AB.5 | | | | | | ** ONE EXAMPLE FOR METHOD *A* WHICH IS FOR *WHOLE* | | | BUILDING COMPLIANCE IS THE EXTERIOR LIGHTING. THE INPUT | | | DATA REPORT ONLY INCLUDES 7-32 WATT FIXTURES. HOW IS | | | THIS POSSIBLE WHEN THE PLANS CLEARLY INDICATE OTHER | | | FIXTURES SUCH AS CANOPY AND NEW SITE LIGHTING POLE | | | LIGHTS WITH WATTAGES EXCEEDING 250W. | | | PLEASE INCLUDE *ALL* FIXTURES ON PLANS AND LOCATION. | | | | | | IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE BE | | | SURE TO CALL AND GO OVER WITH THIS PLANS EXAMINER. | | | | | | 3) NOTE: PLEASE SEE 422.13 WAS STORAGE TYPE WATER | | | HEATERS IN THE 2005 NEC ARE CONSIDERED CONTINUOUS LOADS | | | WITH RESPECT TO LOAD CALCULATIONS FOR FEEDERS AND | | | SERVICES. | | | THIS WAS A REVISION FROM THE PREVIOUS 2002 CODE WHICH | | | ONLY REQUIRED THE SIZING OF BRANCH CIRCUIT AND OCP TO | | | BE SET AT 125%. | | | PLEASE SEE COMMENTARY IN 2005 NEC HANDBOOK. | | | ANY QUESTIONS PLEASE CALL. | | | | | | 4) NOTE: PLEASE INDICATE LOADS FOR SHOW WINDOW | | | RECEPTACLES PER 220.14G FOR BRANCH CIRCUIT SIZING AND | | | 220.43A FOR LOAD WHICH IS REQUIRED TO BE USED FOR | | | SIZING SERVICE. | | | | | | 5) NOTE: PLEASE SEE 600.5 WHICH REQUIRES THE SIGN | | | CIRCUIT TO BE DEDICATED. THIS CIRCUIT IS NOT PERMITTED | | | TO HAVE ANY OTHER ITEMS SUCH AS SOFFITS LIGHTS ETC ON | | | THE SAME CIRCUIT. | | | THE MINIMUM VA TO BE FIGURED FOR SIZING OF THIS CIRCUIT | | | SHALL BE 1200VA. PLEASE ADJUST PLANS AND CALCULATIONS. | | | | | | 6) NOTE: RISER SHOWS AN *EQUIPMENT GROUNDING CONDUCTOR* | | | BEFORE THE FIRST MEANS OF DISCONNECT WHICH IS NOT | | | PERMITTED. PLEASE SEE 250.6, 250.24. THE CODE REQUIRES | | | THE NEUTRAL TO BE BONDED AT THE FIRST MEANS OF | | | DISCONNECT. IF THERE IS AN EQUIPMENT GROUNDING | | | CONDUCTOR INSTALLED FROM THE METER TO THIS FIRST MEANS | | | OF DISCONNECT THEN THIS WOULD PARALLEL THE NEUTRAL THUS | | | CREATING OBJECTIONABLE CURRENTS. | | | | | | 7) NOTE: PLEASE COMPLETE CIRCUITS ON PLANS. ONE EXAMPLE | | | IS EQUIPMENT IDENTIFIED AS SOUP COUNTER. IS THIS | | | EQUIPMENT? OR IS THE SOUP WARMER THE ONLY APPLIANCE? | | | PLEASE ALSO SEE TOILET HAND DRYER WHICH INDICATES | | | CIRCUITS *B 19-20*. THIS PLACES CONDUCTORS ON THE SAME | | | PHASE WHICH WILL NOT WORK. | | | PER THE PANEL SCHEDULE THIS SHOULD BE 19-21. | | | PLEASE BE SURE TO COORDINATE ALL. | | | 408.4, 310.16 ETC | | | FBC 106.1.1, 106.5 | | | | | | 8) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT | | | SHEETS FOR THE PROPOSED MANUAL TRANSFER SWITCH AS | | | STATED ON PLANS. 701.7, 110.3, 90.7 | | | | | | 9) NOTE: PLEASE SEE 210.8B4 AS *ALL* OUTSIDE | | | RECEPTACLES UNDER THE CHANGES IN THE 2005 NEC SHALL BE | | | GFI PROTECTED. THIS INCLUDES ANY DEDICATED CIRCUITS FOR | | | ITEMS SUCH AS ICE MACHINES ETC. | | | | | | 10) NOTE: PLEASE INDICATE THE TYPE OF TIME CLOCK TO | | | MEET 13-415.AB.1.4. THIS MUST BE ASTRONOMICAL WITH A | | | MINIMUM OF 10HR PROGRAMMING BACK UP. | | | | | | 11) NOTE: PLEASE SHOW ALL CLASS AND DIVISION LOCATIONS | | | PER NEC 500,514.3.(B)(1) PLEASE ALSO SEE (2) UNDER SAME | | | SECTION FOR ANY PROPOSED NG, OR LP. | | | | | | 12) NOTE: PLEASE SEE 514.11 (A)(B)(C) ETC. | | | | | | 13) NOTE: PLEASE INCLUDE ALL WIRING AND DETAILS FOR THE | | | REST OF NEC 514. 514.4,514.7,514.9,514.16. | | | | | | 14) NOTE: PLEASE SEE 225.31- 225.39 FOR DISCONNECTING | | | MEANS FOR SEPARATE STRUCTURES. | | | | | | | | | 15) NOTE: PLEASE VERIFY SERVICE RISER. SERVICE IS SHOWN | | | AS 600AMPS WITH A *600* AMP METER CAN. IS THIS NOT A CT | | | TYPE OF INSTALLATION ? PLEASE CHECK WITH FPL AND | | | MANUFACTURE. SEE FPL SERVICE STANDARDS. | | | | | | 16) NOTE: PLEASE COORDINATE PLANS. THE PLANS SHOW AND | | | NOTE THE SERVICE TO BE AN OVERHEAD TYPE YET RISER SHOWS | | | THIS AS UNDERGROUND. WHICH ONE WILL IT BE? | | | REVIEW CAN NOT BE DONE ON AN OVERHEAD SERVICE AS IT IS | | | NOT SHOWN ON RISER. | | | 230,310.16 ETC | | | FBC 106.1.2 FOR ADDITIONAL INFORMATION AND CLARITY OF | | | PLANS. | | | | | | | | | | | | | | | | | | | | | * IMPORTANT ** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2007-10-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-10-18 |
Time |
14:50 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-10-18 |
Time |
10:26 |
Sent To |
|
|
| Notes |
| 2007-10-18 15:41:22 | *** DENIED 3RD REVIEW ***** | | | | | | ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW NOTES ARE | | | STILL IN NEED OF ADDRESSING. THERE ARE ALSO SOME NEW | | | COMMENTS ON SHEETS OTHER THAN THE ELECTRICAL BASED ON | | | CHANGES TO PLANS. | | | | | | 1) NOTE: PLEASE SEE AS STATED IN THE TWO PREVIOUS | | | REVIEWS. THE PLANS ARE STILL ONLY SUBMITTED FOR *PLAN | | | REVIEW *. | | | | | | ** PLEASE KNOW THIS IS STILL UNDER "PLAN REVIEW" ONLY. | | | NO APPLICATION FOR PERMIT HAS YET BEEN MADE TO DATE. | | | PLEASE KNOW THAT EVEN ONCE PLANS ARE CODE COMPLIANT, | | | REVIEWS WILL STILL REMAIN IN *FAILED* STATUES UNTIL | | | PERMIT APPLICATION IS MADE AND REVIEW OF LICENSING, | | | APPLIED VALUES ETC FOR COMPLETE SCOPE OF WORK CAN BE | | | DONE. | | | | | | 2) NOTE: PLEASE SEE THE ARCHITECTURAL PLANS AND | | | LANDSCAPE PLANS, ETC STILL NEED COORDINATION WITH ALL | | | OTHER SHEETS AND TRADES. | | | PLEASE SEE FOR EXAMPLE THE ELECTRICAL LIGHTING WHICH IS | | | SHOWN ON LP DOES NOT CORRELATE WITH SITE PLANS. | | | PLEASE SEE FOR EXAMPLE THE DETAILS OF WALKS/ACCESS ETC | | | ON SITE PLAN DETAILS DO NOT MATCH WITH THE SITE PLAN | | | ITSELF. PLEASE SEE COMMENTS FROM OTHER TRADES SUCH AS | | | ZONING AS ANY CHANGES ON THESE SHEETS WILL HAVE AN | | | AFFECT ON ELECTRICAL PLANS ALSO. | | | PLEASE CORRELATE ELECTRICAL PLANS WITH SITE/LANDSCAPE | | | PLANS AS THERE ARE LIGHTING FIXTURES FOR SITE ETC SHOWN | | | ON LP WHICH ARE NO WHERE ON ELECTRICAL SHEETS. | | | NO WIND LOAD INFORMATION, NO CIRCUITING, NO LOADS, ETC | | | PLEASE CORRELATE ALL AND COMPLETE. | | | FBC 106.1, 106.1.2, 106.3.5.1.2 | | | NEC 240, 310.16, 408.4 | | | | | | 3) NOTE: PLEASE SEE SEVERAL OF THE LANDSCAPE SHEETS ARE | | | NOT SIGNED, DATED OR SEALED AS REQUIRED PER FS 481.321 | | | PLEASE ALSO SEE MISSING INFORMATION ON TITLE BLOCKS FOR | | | PRINTED NAME AND LICENSE NUMBER FOR SAID DESIGNER. | | | | | | 4) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT FOR | | | THE ATS AND GENERATOR AS REQUESTED ON THE PREVIOUS TWO | | | REVIEWS. | | | THE SUB BASE FUEL TANK SPECS ARE ALSO REQUIRED AND WILL | | | BE REVIEWED BY OTHER | | | 110.3, 90.7. | | | | | | 5) NOTE: PLEASE SUBMIT THE FUEL CONSUMPTION ON THE | | | GENERATOR AS PREVIOUSLY REQUESTED FOR HB 7121, HB 319, | | | AND HB 965. CAN NOT LOCATE ANYWHERE ON PLANS THAT THE | | | ON-SITE FUEL WILL SUPPLY THE REQUIRED 72HRS OF FUEL | | | UNDER LOAD CONSUMPTION. | | | | | | 6) NOTE: ONCE AGAIN THE GENERATOR IS STILL BEING SHOWN | | | FOR 434AMPS, YET THIS CAN NOT BE CONFIRMED. THIS IS | | | 125KW AT 208V 3-PHASE. IF THIS IS 434AMPS, HOW IS IT | | | THAT THE GENERATOR HAS A 400AMP BREAKER? | | | PLEASE SEE COMMENT #4 ABOVE. | | | | | | 7) NOTE: PLEASE SEE MISSING LIGHTING POWER | | | DENSITIES/CALCULATIONS AS REQUIRED PER 13-415.2. | | | PLEASE SEE EXTERIOR LIGHTING CALCULATIONS COULD STILL | | | NOT BE LOCATED ON PLAN/ENERGY CALCULATIONS ETC. | | | 13-415.2.ABC.1.3 | | | ** INTERIOR IS ON PLANS AND IS OK. | | | PLEASE SEE THAT NO ENERGY CALCULATIONS WERE SUBMITTED | | | FOR REVIEW.? | | | PLEASE SEE 13-415.1.AB.1.1 | | | PLEASE SEE 13-103.1.1.1 AS THE DESIGNERS OF RECORD | | | SHALL SIGN, DATE AND SEAL SAID ENERGY CALCULATIONS AND | | | OTHER INFORMATION AS REQUIRED UNDER CHAPTER 13. PLEASE | | | BE SURE TO SEE THE 2006 REVISIONS TO THE 2004 FBC AS | | | CHANGES WERE MADE. | | | | | | ** PLEASE KNOW AS THERE IS SOME INFORMATION STILL NOT | | | YET SUBMITTED FOR REVIEW, COMPLETE REVIEW CAN NOT BE | | | DONE. | | | | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | | DELAYS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-03-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-03-24 |
Time |
14:18 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-03-24 |
Time |
12:06 |
Sent To |
|
|
| Notes |
| 2007-03-24 14:20:49 | | | | | | | ****** UNSAT 2ND REVIEW****** | | | | | | ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1 | | | IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE | | | ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY | | | THE CITY OF WEST PALM BEACH. | | | | | | | | | ** PLEASE KNOW THIS IS STILL UNDER "PLAN REVIEW" ONLY. | | | NO APPLICATION FOR PERMIT HAS YET BEEN MADE TO DATE. | | | PLEASE KNOW THAT EVEN ONCE PLANS ARE CODE COMPLIANT, | | | REVIEWS WILL STILL REMAIN IN *FAILED* STATUES UNTIL | | | PERMIT APPLICATION IS MADE AND REVIEW OF LICENSING, | | | APPLIED VALUES ETC FOR COMPLETE SCOPE OF WORK CAN BE | | | DONE. | | | | | | ** PLEASE SEE MANY ITEMS FROM PREVIOUS REVIEW NOTES | | | WERE NOT DONE OR SUBMITTED. | | | A COMPLETE REVIEW FOR CODE COMPLIANCE CAN NOT BE DONE | | | AT THIS TIME AS THESE ITEMS ARE NOT SHOWN OR | | | SUBMITTED. | | | THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW NOT | | | YET MADE. | | | | | | | | | 1) NOTE: PLEASE BE SURE THE PLANS, ELECTRICAL AND | | | ARCHITECTURAL CONTAIN ALL THE REQUIRED CODES RELEVANT | | | TO DESIGN. | | | | | | PLEASE KNOW THAT DEPENDING ON PERMIT APPLICATION IS | | | FINALLY MADE, THIS WILL DETERMINE THE CODES IN WHICH | | | THE PLANS ARE DESIGNED UNDER. | | | PLEASE SEE THE ARCHITECTURAL PLANS INDICATE THE 2001 | | | FBC???? | | | PLEASE INCLUDE THE FOLLOWING AT A MINIMUM. | | | 2004 FBC W/ 2006 REVISIONS ( FOR ALL TRADES) | | | 2005 NFPA-70 | | | 2003 NFPA-101 | | | 2002 NFPA-72( IF APPLICABLE) | | | 2002 NFPA-110 | | | 2003 NFPA-30A | | | 2002 NFPA-37 | | | | | | 2) NOTE: PLEASE SEE THE ARCHITECTURAL PLANS AND | | | LANDSCAPE PLANS ARE MISSING ALL OF THE ELECTRICAL , | | | MECHANICAL AND GENERATOR EQUIPMENT FROM PLANS SHOWING | | | ALL SET BACKS AND DISTANCES FROM BUILDING, PROPERTY | | | LINES ETC. | | | PLEASE KNOW THAT BASED ON THE ELECTRICAL PLANS SHOWING | | | SOME OF THIS AND COORDINATION WITH THE ONLY *SITE* | | | LAYOUT PROVIDED ON THE LANDSCAPE PLANS, THE GENERATOR | | | DOES NOT APPEAR IT CAN BE LOCATED IN THE REAR OF | | | BUILDING. | | | PLEASE ALSO SEE THE MINIMUM REQUIREMENTS FOR ZONING | | | SETBACKS AND PERMITTED DISTANCES FROM BUILDING AND | | | PROPERTY LINES. | | | PLEASE SEE THE MINIMUM DISTANCES/CLEARANCES FOR THE | | | GENERATOR FROM BUILDING AND PROPERTY LINE WILL PLACE | | | THIS UNIT TOO CLOSE TO BUILDING AND PROPERTY. A NEW | | | LOCATION MAY BE REQUIRED. | | | PLEASE SEE THE MECHANICAL COMMENTS, BUILDING COMMENTS. | | | | | | MORE INFORMATION ON ALL WILL BE REQUIRED. PLEASE SEE | | | COMMENTS FOR GENERATOR. | | | FBC 106.1.2 | | | | | | 3) NOTE: PLEASE SEE THE SEAL BEING USED BY THE | | | LANDSCAPE ARCHITECT IS NOT OF SUFFICIENT SIZE. PLEASE | | | SEE THE FAC 61G1-16.002 | | | 61G1-16.002 DESCRIPTION OF SEAL. | | | (1) THE SEAL SHALL CONTAIN THE NAME OF ONLY ONE | | | ARCHITECT OR INTERIOR DESIGNER AND THE REGISTRATION | | | NUMBER; THE SEAL OF THE ARCHITECT SHALL BE CIRCULAR, | | | AND THE SEAL OF THE INTERIOR DESIGNER SHALL BE | | | HEXAGONAL. BOTH SEALS SHALL BE AN IMPRESSION-TYPE METAL | | | SEAL, APPROXIMATELY 2" IN DIAMETER WITH TWO CIRCULAR | | | LINES BETWEEN WHICH LINES SHALL APPEAR, AT THE TOP, THE | | | WORDS "STATE OF FLORIDA" AND AT THE BOTTOM THE WORDS | | | "REGISTERED ARCHITECT" OR "LICENSED INTERIOR DESIGNER," | | | WHICHEVER IS APPLICABLE. | | | (2) ANY INDIVIDUAL WHO IS BOTH A REGISTERED ARCHITECT | | | AND A LICENSED INTERIOR DESIGNER MUST USE A SEAL WHICH | | | CONTAINS BOTH THE ARCHITECT AND INTERIOR DESIGN | | | REGISTRATION NUMBERS, IN SUCH A MANNER: | | | | | | 4) NOTE: PLEASE SEE THE MISSING INFORMATION ON TITLE | | | BLOCKS PER 61G1-16.004. PLEASE SEE MISSING THE PRINTED | | | NAME, PRINTED LICENSE NUMBER AND MISSING FIRM LICENSE | | | NUMBER. (ALSO KNOWN AS THE CERTIFICATE OF AUTHORIZATION | | | NUMBER. | | | PLEASE SEE FS 481.219 | | | | | | 5) NOTE: PLEASE SEE MISSING LIGHTING POWER | | | DENSITIES/CALCULATIONS AS REQUIRED PER 13-415.2. A NOTE | | | ON PLANS WHICH MENTIONS THE DESIGN MEETS THIS SECTIONS | | | DOES NOT ALLEVIATE THE REQUIRED INFORMATION TO BE SHOWN | | | ON RECORD SETS OF PLANS AS REQUIRED PER THE SAME | | | SECTION OF THE FBC CHAPTER 13. | | | PLEASE SEE THAT NO ENERGY CALCULATIONS WERE SUBMITTED | | | FOR REVIEW.? | | | PLEASE SEE 13-415.1.AB.1.1 | | | PLEASE SEE 13-103.1.1.1 AS THE DESIGNERS OF RECORD | | | SHALL SIGN, DATE AND SEAL SAID ENERGY CALCULATIONS AND | | | OTHER INFORMATION AS REQUIRED UNDER CHAPTER 13. PLEASE | | | BE SURE TO SEE THE 2006 REVISIONS TO THE 2004 FBC AS | | | CHANGES WERE MADE. | | | | | | 6) NOTE: PLEASE SHOW AND INCLUDE A LAYOUT ON PLANS | | | SHOWING ALL CLASS AND DIVISION LOCATIONS AS REQUIRED | | | PER NEC 511, 500 AND NFPA-30A. | | | PLEASE PROVIDE A DETAIL FOR THE SHUNT/EM STOP DEVICE | | | HOW THESE ARE BEING CONNECTED TO THE FEEDS. | | | PLEASE SEE THE PANEL SCHEDULES WHICH DO NOT INDICATE | | | SHUNT TRIPS REQUIRED? | | | | | | 7) NOTE: PLEASE SEE NFPA-96 AS THE ELECTRICAL UNDER | | | HOODS SHALL ALSO CONTAIN SHUNT AND DETAIL TO BE SHOWN. | | | PLEASE SEE COMMENTS FROM OTHER TRADES FOR MORE | | | INFORMATION ON GAS AND HOODS. | | | | | | 8) NOTE: PLEASE SEE THE CODE SECTION REFERENCED FOR THE | | | GFI PROTECTION OF THE KITCHEN OUTLETS SEEMS TO BE A | | | MISPRINT. | | | PLEASE SEE 210.8B3 | | | PLEASE ALSO SHOW ALL OF THESE CIRCUITS WHICH WILL BE | | | PROTECTED. PLEASE INDICATE ON PANEL SCHEDULE OR PLANS. | | | STATING THE SECTION OF THE CODE IS ONLY PART OF WHAT IS | | | NEEDED. | | | FBC 106.1.2 | | | | | | 9) NOTE: PLEASE SEE HB 7121, HB 319, HB965 ETC THIS IS | | | HOUSE BILL 7121 WHICH WAS JUST ADOPTED INTO LAW ON JULY | | | 1ST, 2006. PLEASE SEE FS 252, 526.143ETC, WHICH NOW | | | REQUIRES ALL FUEL STATIONS UPON BEING NEW OR | | | SUBSTANTIAL REMODEL, ETC INSTALL A COMPLETE EMERGENCY | | | BACK UP GENERATOR SYSTEM.PLEASE PROVIDE THE MINIMUM | | | AMOUNT OF FUEL, FUEL CONSUMPTION FOR ALL LOADS. PLEASE | | | SEE THAT UNDER THE FS 526.143 STATES THE MINIMUM AMOUNT | | | OF TIME REQUIRED FOR OPERATIONS OF GENERATOR WHICH IS | | | 72HRS. | | | PLEASE SUBMIT ALL REQUIRED LOCATIONS PER NEC 500. | | | PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT SHEETS FOR ALL | | | EQUIPMENT, ATS, MTS, GEN, FUEL PRIME MOVER ETC. PLEASE | | | INDICATE THE AMOUNT OF ONSITE FUEL. PLEASE SEE THE NEW | | | FLORIDA STATUTES FOR THE REQUIRED TIMES AND AMOUNT OF | | | ON SITE FUEL REQUIRED. PLEASE SEE HB AS NOTED. PLEASE | | | SEE THE GENERATOR NOTE ON PLANS MENTIONS THE GENERATOR | | | IS GOOD FOR 434 AMPS. PLEASE VERIFY HOW THIS IS | | | POSSIBLE WITH A 125KW UNIT AT 3-PHASE, 120/208V? PLEASE | | | ALSO SEE NOTE WHICH MENTIONS THAT THE GENERATOR | | | MANUFACTURE IS TO PROVIDE CALCULATIONS WHICH WILL MEET | | | THE INTENDED LOADS. PLEASE KNOW THAT THIS INFORMATION | | | FOR THE MINIMUM DESIGN IS REQUIRED AT THIS TIME. PLEASE | | | KNOW THIS IS AND WILL BE REQUIRED. 90.7, 110.3 ETC | | | PLEASE KNOW THAT ONE THE SPECS ARE SUBMITTED THE REVIEW | | | OF MANY ITEMS WILL BE ABLE TO BE DONE AT THAT TIME. ** | | | PLEASE SEE THAT AS THIS IS LEGALLY REQUIRED SYSTEM | | | PLEASE BE SURE TO SEE ALL OF THE REQUIREMENTS UNDER | | | NFPA-110, AND NEC 701. | | | | | | 10) NOTE: PLEASE SE NOTE ON PLANS WHICH MENTIONS THAT | | | THE CONTRACTOR IS REQUIRED TO THE TRANSFORMER WITH THE | | | FPL SERVICE PLANNER FOR THE AVAILABLE FAULT CURRENT. | | | PLEASE KNOW THAT THIS IS REQUIRED TO BE DONE AT THIS | | | TIME. IT IS THE RESPONSIBILITY OF THE DESIGNER AND | | | DESIGN TEAM. | | | 110.9 | | | | | | 11) NOTE: PLEASE KNOW THAT UNTIL THE MANUFACTURES | | | SPECS/CUT SHEETS ARE SUBMITTED FOR THE SERVICE ENTRANCE | | | ATS, REVIEW FOR THE CODE COMPLIANCE FOR 225.31-225.39, | | | 230.76, 230.79 CAN NOT BE DONE. | | | 701, 110.27. | | | | | | 12) NOTE: PLEASE SEE RISER NOTES WHICH MENTIONS THE TWO | | | DISCONNECTS ON THE LINE SIDE OF SUB PANELS AND ON THE | | | LOAD SIDE OF THE GUTTER AS MAINS 1 OF 2 AND 2OF 2? HOW | | | IS THIS POSSIBLE WHEN THE SERVICE MEANS OF DISCONNECTS | | | ARE LOCATED IN THE ATS. | | | OCP AT GENERATOR SHALL BE SHOWN. | | | PLEASE SEE 445.13 WHICH MAY APPLY FOR THE MINIMUM | | | SIZING OF THE CONDUCTORS. | | | PLEASE SHOW ALL EQUIPMENT ON PLANS AT BUILDING | | | INCLUDING BOTH MAINS. | | | 110.26 | | | FBC 106.1.2 | | | | | | 13) NOTE: PLEASE PROVIDE COMPLETED PLANS FOR THE SLAB | | | DETAIL, ELEVATION OF THE UNIT AND SERVICE. EQUIPMENT IS | | | PART OF A LEGALLY REQUIRED SYSTEM SEE LOCATIONS AND | | | ELEVATIONS IN NFPA-110 CHAPTER 7 | | | THE LOCATION, ENCLOSURE AND GENERATOR SHALL BE | | | PROTECTED FROM VANDALISM, FLOODS, ETC. | | | | | | 14) NOTE: PLEASE SEE THAT FEES ARE OWED AS THE AMOUNT | | | OF SHEETS SUBMITTED IS GREATER THAN THAT PLACED ON | | | SUBMITTIAL SHEET. | | | | | | ** PLEASE KNOW AS THERE IS MUCH INFORMATION NOT YET | | | SUBMITTED AND MANY CHANGES WHICH WILL BE REQUIRED ON | | | PLANS, FURTHER COMMENTS MAY BE EXTENDED ON THE | | | FOLLOWING REVIEW. | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | 2007-03-24 12:47:49 | IN ELEC FOR REVIEW |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-11-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-11-04 |
Time |
19:45 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-11-04 |
Time |
18:46 |
Sent To |
|
|
| Notes |
| 2006-11-04 19:45:09 | *** UNSAT *** | | | | | | | | | ** PLEASE KNOW THIS IS STILL UNDER "PLAN REVIEW" ONLY. | | | NO APPLICATION FOR PERMIT HAS YET BEEN MADE TO DATE. | | | PLEASE KNOW A CODE CHANGE FOR NFPA-70 IS COMING AND IF | | | PERMIT IS NOT APPLIED FOR BEFORE STATE ADOPTS NEW CODE, | | | THEN THE PLANS WILL BE REQUIRED TO CHANGE AS NEEDED. | | | THE TENTATIVE DATE IS DEC 1ST, 2006 | | | | | | 1) NOTE:PLEASE SEE PLANS SEEM TO INDICATE A NEW STORE | | | BEING CONSTRUCTED, HOWEVER THE "PLAN REVIEW" SUBMITTAL | | | SHEET INDICATES A REMODEL??? THE SCOPE OF WORK IS | | | UNCLEAR BASED ON PLANS SUBMITTED IN EITHER CASE. | | | | | | 2) NOTE: PLEASE SEE FS 471.003(2)(H)2A, AS PLANS ARE | | | REQUIRED TO BE DONE BY A FLORIDA REGISTERED | | | PROFESSIONAL ENGINEER. | | | PLEASE ALSO SEE FS 471.025(3). | | | THE ELECTRICAL SCOPE AS SHOWN MAY NOT BE DONE BY AN | | | ARCHITECTURAL FIRM/ARCHITECT. | | | | | | 3) NOTE: PLEASE KNOW THE PLANS SUBMITTED ARE NOT | | | COMPLETE FOR CODE COMPLIANCE. PLEASE SEE ONLY SOME CODE | | | ARTICLES BELOW ARE BEING GIVEN. PLEASEKNOW THERE IS A | | | SUBSTANTIALLY AMOUNT OF CODE RELATED ITEMS NOT | | | SUBMITTED OR SHOWN. | | | | | | A) PLEASE INDICATE AND SHOW ALL CIRCUITING ON PLANS AND | | | CORRELATE WITH PANEL SCHEDULES TO BE SUBMITTED. | | | 240.4,310.16, 408.4 | | | FBC ADMINISTRATIVE SECTION AS ADOPTED BY THE CITY OF | | | WEST PALM BEACH. 106.1.2, 106.3.5.1.2 ETC. | | | PLEASE ALSO SEE 2002 NFPA-70, 2003 NFPA-101, 2002 | | | NFPA-72, NFPA-30A ETC ETC. | | | B) PLEASE SUBMIT LOAD CALCULATIONS.NEC 220. | | | C) PLEASE SEE NEC 511 | | | D) PLEASE SEE LS 101 7.8, 7.9 FOR MISSING EM/ EXT LTS, | | | PLEASE ALSO SEE 700.12E FOR CIRCUITING. | | | E) PLEASE SEE 250.6, 250.24B | | | F) PLEASE SEE 250.110, 250.110 | | | G) PLEASE SEE 250.50 | | | H) PLEASE SEE 600.5, 220.3(B)(6) | | | I) PLEASE SEE 210.62, 220.12A | | | J) PLEASE SEE 210.8B3 | | | K) PLEASE SEE FBC CHAPTER 13(ALL APPLICABLE SECTIONS, | | | TOO MANY TO LIST AT THIS TIME. | | | L) PLEASE SEE 110.9, 240.12 FOR SELECTIVE COORDINATION | | | DETAILS TO BE SUBMITTED. | | | ETC. | | | | | | 4) NOTE: PLEASE SEE HB 7121, HB 319, HB965 ETC THIS IS | | | HOUSE BILL 7121 WHICH WAS JUST ADOPTED INTO LAW ON JULY | | | 1ST, 2006. PLEASE SEE FS 252 ETC, WHICH NOW REQUIRES | | | ALL FUEL STATIONS UPON BEING NEW OR SUBSTANTIAL | | | REMODEL, ETC INSTALL A COMPLETE EMERGENCY BACK UP | | | GENERATOR SYSTEM. THIS WILL SUBSTANTIALLY CHANGE THE | | | PLANS SUBMITTED. | | | PLEASE SUBMIT SITE PLANS, ALL REQUIRED LOCATIONS PER | | | NEC 500. PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT | | | SHEETS FOR ALL EQUIPMENT, ATS, MTS, GEN, FUEL PRIME | | | MOVER ETC ETC. | | | PLEASE KNOW THIS IS AND WILL BE REQUIRED. 90.7, 110.3 | | | ETC | | | | | | | | | ** PLEASE KNOW AS PLANS ARE NOT COMPLETE AT THIS TIME | | | FOR A SUFFICIENT REVIEW, AND WILL BE CHANGING, THERE | | | MAY BE FURTHER COMMENTS UPON THE NEXT REVIEW. | | | | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
7 |
Status |
P |
Date |
2009-11-30 |
|
|
Cont ID |
|
| Sent By |
|
Date |
2009-11-30 |
Time |
|
Rev Time |
5.00 |
| Received By |
|
Date |
2009-11-30 |
Time |
|
Sent To |
ENG |
|
| Notes |
| 2009-11-30 14:48:14 | PLANS ARE APPROVED AS-NOTED THRU ESD DATED 11/30/09 | | | 1) FOR EACH INLET , PROVIDE A 12" DIA WEEP HOLE AS | | | SHOWN ON THE DETAIL ON SHT 3 OF 3. UNDER THE WEEP HOLE | | | INSTALL HARDWARE CLOTH (SS) ON | | | 2' X 2' X 6" OF WASHED ROCK WRAPPED ALL AROUND WITH | | | FABRIC. | | | 2) FOR EACH INLET , PROVIDE A POLLUTION CONTROL BAFFLE | | | (PCB) AT EACH PIPE OUTLET TO EXFILTRATION TRENCH (6 | | | TOTAL ). | | | | | | MANUEL JULIAN GONZALEZ | | | ENGINEERING PROJECT COORDINATOR | | | ENGINEERING SERVICES DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 | | | DIRECT: (561) 494-1085 | | | FAX: (561) 494-1116 | | | MOBILE: (561) 644-7301 | | | EMAIL: [email protected] | | | WWW.WPB.ORG/ENGINEERING | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
6 |
Status |
F |
Date |
2009-09-23 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
2009-09-23 |
Time |
10:54 |
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
2009-09-23 |
Time |
10:49 |
Sent To |
|
|
| Notes |
| 2009-09-23 10:54:14 | FAILED | | | | | | PLANS MUST BE SUBMITTED TO ENGINEERING DEPT FOR | | | STORMWATER REVIEW. | | | THIS IS A SEPARATE SUBMITTAL REQUIRED BY ENGINEERING | | | DEPT TO COMPLY WITH NPDES CODES. | | | | | | INFORMATION ON SUBMITTAL CAN BE OBTAINED AT THE LINK | | | BELOW: | | | HTTP://WWW.CITYOFWPB.COM/ENGINEERING/ENG_FORMS.PHP | | | | | | DEVELOPMENT PERMIT PACKET MUST ACCOMPANY YOUR SUBMITTAL | | | ALONG WITH THE REQUIRED DOCUMENTATION. | | | SEE "ENGINEERING SERVICES DEPARTMENT STANDARD | | | APPLICATION FOR DEVELOPMENT PERMIT" | | | | | | SUBMIT THE PERTINENT DOCUMENTS ATTENTION: | | | BRIAN MOREE, CONSTRUCTION SUPERVISOR | | | ENGINEERING SERVICES DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 | | | DIRECT: (561) 494-1098 | | | FAX: (561) 494-1116 | | | EMAIL: [email protected] | | | WWW.WPB.ORG/ENGINEERING | | | | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
5 |
Status |
F |
Date |
2009-07-27 |
|
|
Cont ID |
|
| Sent By |
dlauderm |
Date |
2009-07-27 |
Time |
13:53 |
Rev Time |
2.00 |
| Received By |
dlauderm |
Date |
2009-07-27 |
Time |
12:37 |
Sent To |
|
|
| Notes |
| 2009-07-27 13:19:57 | FAILED | | | DEAN LAUDERMILK, PROJECT COORDINATOR | | | CSD: (561) 805-6716 | | | ESD: (561) 494-1083 | | | EMAIL: [email protected] | | | TOO MANY CONTRADICTIONS TO APPROVE THE PLANS AS | | | SUBMITTED. | | | 1. GREASE TRAP ON CIVIL PLAN (2 OF 3) DOES NOT MATCH | | | PLUMBING PLAN (P-1 & P-2). NEITHER DESIGN MATCHES OUR | | | STANDARD DETAIL, WHICH WAS NOT INCLUDED IN THE CIVIL OR | | | PLUMBING PLANS. | | | 2. WATER SERVICE, METER AND BACKFLOW PREVENTER ARE TO | | | REMAIN, PER CIVIL PLAN (2 OF 3), WHILE PLUMBING PLAN | | | (P-2) SHOWS A NEW 1" SERVICE TO THE CITY MAIN. | | | 3. WATER SERVICE FROM BUILDING TO THE METER AND | | | BACKFLOW PREVENTER ARE TO REMAIN, PER CIVIL PLAN (2 OF | | | 3), WHILE PLUMBING PLAN (P-2) SHOWS A NEW 1" SERVICE | | | FROM THE BUILDING TO THE METER/BACKFLOW PREVENTER. | | | 4. IRRIGATION PLAN (IR-1) SHOWS METER AND BACKFLOW | | | PREVENTER AT NW CORNER OF SITE, THERE IS NO WATER MAIN | | | IN THE ALLEY, THE WATER METER NEEDS TO BE ON LAKE | | | AVENUE. IS THE INTENTION TO INSTALL A SEPARATE 1" | | | SERVICE FOR THE IRRIGATION SYSTEM? THE PLUMBING PLAN | | | SHOWS NO TEE IN THE LINES AND NO BACKFLOW PREVENTER FOR | | | THE IRRIGATION SYSTEM. ALL BACKFLOW PREVENTERS NEED TO | | | BE INSTALLED BY A LICENSED PLUMBER, NOT AN IRRIGATION | | | COMPANY. | | | 5. IRRIGATION PLAN (IR-1) SHOWS 5 ZONES, TWO OF THE | | | ZONES ARE DESIGNED FOR MORE WATER THAN THE 1" WATER | | | METER IS DESIGNED TO GIVE. THE MAXIMUM SAFE OPERATING | | | RATE FOR A 1" METER IS 25 GPM. REDESIGN THE IRRIGATION | | | SYSTEM ZONES SO THE MAXIMUM GPM RATE DOES NOT EXCEED 25 | | | GPM | | | 6. THE IRRIGATION SYSTEM WILL NEED A SEPARATE BACKFLOW | | | PREVENTER WHICH IS CALLED OUT ON THE IRRIGATION PLAN | | | BUT IS NOT SHOWN ON THE PLUMBING PLAN OR CIVIL PLAN. | | | THE CIVIL PLAN (2 OF 3) SHOWS GATES ON THE EQUIPMENT | | | ENCLOSURE OPENING TO THE EAST. THE APPROVED SITE PLAN | | | AND THE BUILDING PLANS SHOWS THE GATE OPENING TO THE | | | SOUTH (THE CORRECT WAY). | | | 7. THIS PLAN HAS NOT BE REVIEWED/APPROVED BY THE | | | ENGINEERING DEPARTMENT. WHEN THE CORRECTIONS ARE MADE | | | SUBMIT THE CIVIL PLAN AND THE STORMWATER CALCULATIONS | | | TO THE ENGINEERING SERVICES, ATTENTION EMERY FABIAN, | | | THE PROJECT COORDINATOR FOR THE PROJECT. THIS NEEDS TO | | | BE DONE PRIOR TO TURNING IN THE PLANS FOR ANOTHER | | | CONSTRUCTION SERVICES REVIEW. THE ESD STAMP (APPROVED) | | | NEEDS TO BE ON THE PLAN. | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
4 |
Status |
F |
Date |
2009-06-10 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
2009-06-10 |
Time |
11:10 |
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
2009-06-10 |
Time |
11:00 |
Sent To |
|
|
| Notes |
| 2009-06-10 11:10:35 | ********* NOT APPROVED *********** | | | | | | SUPPLY THE FOLLWING TO CITY OF WEST PALM BEACH | | | ENGINEERING DEPT FOR APPROVAL: | | | SURFACE WATER QUALITY CALCULATIONS | | | IMPERVIOUS AND PERVIOUS CALCULATIONS | | | POLLUTION PREVENTION PLAN OR SUMMARY. | | | | | | A 1" DOMESTIC WATER METER IS SERVING YOU PROPERTY. | | | SUGGESTION OF OBTAINING AN IRRGATION METER MAY BE | | | SUITABLE AS | | | THAT CONSUMPTION WILL NOT BE CHARGED SEWAGE AGAINST IT. | | | | | | ANY QUESTIONS, PLEASE CONTACT: | | | | | | ATTENTION: MANUEL GONZALEZ | | | (561) 494-1085 | | | [email protected] | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
F |
Date |
2007-10-22 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2007-10-22 |
Time |
15:33 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2007-10-22 |
Time |
15:26 |
Sent To |
|
|
| Notes |
| 2007-10-22 15:33:30 | **** FAILED ***** | | | | | | | | | 1. PLEASE SHOW ON DRAWINGS POLLUTION PREVENTION | | | DETAILS,CLOTHES USED FOR SILT ETC., AND PLANS SHOWING | | | SILT FENCE AROUND THE SITE. | | | | | | 2. STORM WATER QUALITY CALCULATIONS MUST BE APPROVED | | | FROM 45TH STREET, ENGINEERING BEFORE WE ISSUE A | | | PERMIT. | | | | | | PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR | | | PERMITTING PROCESS | | | | | | RASIK CHOKSHI805-6723 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
F |
Date |
2007-03-30 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2007-03-30 |
Time |
14:26 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2007-03-30 |
Time |
14:06 |
Sent To |
|
|
| Notes |
| 2007-03-30 14:26:29 | YOUR PLANS WERE REVIEWED IN REV 1 ON 11/17/06.YOU | | | PROVIDED SEAL & SIGNED PLANS, NOW, FOR REV 2. YOU DID | | | NOT PROVIDE EXPLANATIONS OF ITEMS WE LISTED IN REV 1, | | | DATED 11/17/06 | | | PLEASE PROVIDE EXPLANATIONS & INFO ON THE DRAWINGS FOR | | | EACH OF THE ITEMS WE ASKED FOR IN REV 1 DATED | | | 11/17/06. | | | ALSO, PLEASE PROVIDE DETAIL CALCULATIONS FOR WATER | | | QUALITY FOR BOTH CRITERIA EITHER 1" OR 2.5" CRITERIA | | | FOR WATER QUALITY?? WE LIKE TO SEE BOTH CRITERIA | | | CALCULATIONS, AND TAKE THE WORST CRITERIAFOR THE | | | LENGTH OF DESIGNINGEXFILTRATIONS TRENCH. IN OTHER | | | WORDS, DETAILEDCAL FORLENGTH OF EXFILTRATION TRENCH | | | ETC. | | | | | | PLEASE RESPOND EACH |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2006-11-17 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2006-11-17 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2006-11-17 |
Time |
15:43 |
Sent To |
|
|
| Notes |
| 2006-11-17 15:51:48 | I REVIEW ONLY THE FOLLOWING.SOPLEASE PROVIDE | | | FOLLOWING INFO FOR COMPLETE REVIEW: | | | 1.NEEDS SEAL & SIGN FOR ALL CIVIL DWGSBYP.E.AS | | | YOU PROVIDED | | | 2. PLEASE SHOW STANDARDS NOTES OF CITY OF WPB ON | | | DRAWINGSFOR SIDEWALK WIDTH , ITS SLOPE, DRIVEWAY, | | | PARKING, HANDICAP PARKING, PAINTPER CITY CODES ETC.,, | | | MUST MEET PER ADA,,ETC., | | | 3. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE | | | DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION | | | MUST BE ACCESSIBLE FOR PICKUP TRUCK. | | | 4. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD , | | | SIDEWALK ELEVATION MUST MEET FL BLDG CODE, PLEASE SHOW | | | ON THE DRAWINGS. | | | 5. PLEASE PROVIDE A COPY OF SFWMD PERMIT,& GEOTECHNICAL | | | REPORT | | | 6.PLEASE SHOW STORM WATER CALCULATIONS, WHAT CRITERIA | | | YOU ASSUMEDFOR RUNOFF CAL.,, LIKE 1" OVER ENTIRE SITE | | | OR2.5"CRITERIA, ?PERVIOUS AREA, LIKE GREEN, | | | LAKES, ETC,IMPERVIOUS AREA CAL., | | | 7. WHAT IS THE SITE AREA, YOU ARE DEVELOPING FOR THIS | | | PROJECT ONLY ? SO, WE CAN CHECK PERVIOUS, IMPERVIOUS | | | CAL. | | | 8. HOW YOU CONNECT TO THE STORM WATER PIPES IN YOUR | | | SITE? ITS DETAILS.PLEASE SHOW ALL STORM WATER PIPES | | | AROUND YOUR SITE SO, WE CANSEE THE BEST PIPE TO | | | CONNECT WITH THE STORM WATERFROM ALL OTHER STORM | | | WATER PIPES. PLEASE SHOW DETAIL OF THE CONTROL | | | STRUCTURES WITH ELEVATIONS, NOTCHES, BLEEDING | | | ELEVATION, ETC DID YOU USE EXFILTRATION TRENCH ? | | | 9. POLLUTION PREVENTION DETAILS,CLOTHES USED FOR SILT | | | ETC., PLANS SHOWING SILT FENCE AROUND THE SITE | | | 10. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH | | | STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED | | | 11. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND | | | YOUR SITE FOR STORM WATER DRAIN. | | | | | | PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR | | | PERMITTING PROCESS | | | | | | RASIK CHOKSHI805-6723 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
6 |
Status |
P |
Date |
2009-10-14 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-10-14 |
Time |
15:30 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-10-14 |
Time |
15:11 |
Sent To |
|
|
| Notes |
| 2009-10-14 15:15:01 | *****APPROVED***** | | | | | | | | | PLAN SHEET A-5, PREVIOUSLY (8/06/09) STAMPED, | | | INITIALED, AND DATED ALONG WITH A-2, A-3, A-5, AND | | | LS-1) WAS RE-STAMPED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2009-08-06 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-08-06 |
Time |
13:50 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-08-06 |
Time |
13:24 |
Sent To |
|
|
| Notes |
| 2009-08-06 13:29:14 | *****APPROVED***** | | | | | | | | | PLAN SHEETS A-2, A-3, A-5, AND LS-1 WERE STAMPED, | | | INITIALED, AND DATED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
F |
Date |
2009-05-29 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-05-29 |
Time |
15:20 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-05-29 |
Time |
15:06 |
Sent To |
|
|
| Notes |
| 2009-05-29 15:17:56 | *****PROVISO***** | | | | | | | | | THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE | | | BEEN ADDRESSED, HOWEVER THE APPROPIATE PLAN SHEETS | | | (A-2, A-3, A-5, LS-1, AND LS-2) TO BE FIRE-STAMPED | | | PROVIDED THE FOLLOWING: | | | | | | | | | 1.) ON SHEET LS-1 IN THE PROJECT CODES, AMEND NFPA 101 | | | TO 2006 (NOT 2005) EDITION. | | | | | | 2.) PERMIT CAN NOT BE ISSUED UNTIL A CONTRACTOR HAS | | | BEEN DECLARED. | | | | | | 3.) THE COMMENTS FROM THE OTHER TRADES HAVE BEEN | | | SATISFIED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2007-10-25 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-10-25 |
Time |
13:17 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-10-25 |
Time |
12:45 |
Sent To |
|
|
| Notes |
| 2007-10-25 13:16:28 | ****DENIED***** | | | THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE | | | PLAN REVIEW STILL NEED TO BE ADDRESSED: | | | | | | | | | 3.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT | | | HINDER OR INTERFERE WITH EMERGENCY ACCESS TO THE | | | PROPERTY OR VICINITY THEREOF. | | | | | | 4.THE NUMERICAL ADDRESS OF THE JOB SITE SHALL BE IN | | | THE TITLE BLOCK OF THE SUBMITTED PLAN SHEETS.NO | | | ADDRESS ON SHEET SP-1, LS-1, LS-2, LP-1, C2 & C3, AND | | | E-1 | | | | | | 8.SPECIFY ANY NEW WALL AND CEILING INTERIOR FINISH | | | CLASSIFICATION IN TERMS OFCLASS "A"CLASS "B", OR | | | CLASS "C". | | | | | | 9.PROVIDE A LIFE SAFETY PLAN SHEET TO INCLUDE ALL | | | COMMON PATHS OF TRAVEL TO THE EXIT(S) AND THE LOCATION | | | OF FIRE EXTINGUISHERS AT DISTANCES WHICH SATISFY THE | | | 75' TRAVEL DISTANCE REQUIREMENT. | | | | | | NEW COMMENT | | | | | | A.THE INSTALLATION OF THE STANDBY GENERATOR WILL | | | REQUIRE SEPARATE PLANS AND PERMIT, AND SHALL COMPLY | | | WITH NFPA 110. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | SHEET INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2007-04-12 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-04-12 |
Time |
17:16 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-04-12 |
Time |
16:37 |
Sent To |
|
|
| Notes |
| 2007-04-12 17:16:37 | ****DENIED***** | | | THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE | | | PLAN REVIEW STILL NEED TO BE ADDRESSED: | | | | | | | | | 1.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED. | | | | | | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 3.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT | | | HINDER OR INTERFERE WITH EMERGENCY ACCESS TO THE | | | PROPERTY OR VICINITY THEREOF. | | | | | | 4.THE NUMERICAL ADDRESS OF THE JOB SITE SHALL BE IN | | | THE TITLE BLOCK OF THE SUBMITTED PLAN SHEETS. | | | | | | 5.IN ADDITION TO SHOWING WHERE THE NUMERICAL ADDRESS | | | WILL BE LOCATED AS ON SHEET A-2, SHOW WHAT THOSE | | | NUMBERS WILL BE. | | | | | | 8.SPECIFY THE WALL AND CEILING INTERIOR FINISH | | | CLASSIFICATION ASCLASS "A"CLASS "B", OR CLASS "C". | | | | | | 9.PROVIDE A LIFE SAFETY PLAN SHEET TO INCLUDE ALL | | | COMMON PATHS OF TRAVEL TO THE EXIT(S) AND THE LOCATION | | | OF FIRE EXTINGUISHERS AT DISTANCES WHICH SATISFY THE | | | 75' TRAVEL DISTANCE REQUIREMENT. | | | | | | NEW COMMENT | | | | | | A.THE INSTALLATION OF THE STANDBY GENERATOR WILL | | | REQUIRE SEPARATE PLANS AND PERMIT, AND SHALL COMPLY | | | WITH NFPA 110. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | SHEET INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2006-12-14 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2006-12-14 |
Time |
11:36 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2006-12-14 |
Time |
11:36 |
Sent To |
|
|
| Notes |
| 2006-12-14 12:11:15 | *****DENIED***** | | | | | | | | | | | | 1.NFPA 101 (2003 EDITION) THE FLORIDA FIRE PREVENTION | | | CODE (2004 EDITION) SHALL BE REFERENCED. | | | | | | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 3.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT | | | HINDER OR INTERFERE WITH EMERGENCY ACCESS TO THE | | | PROPERTY OR VICINITY THEREOF. | | | | | | 4.THE NUMERICAL ADDRESS OF THE JOB SITE SHALL BE IN | | | THE TITLE BLOCK OF THE SUBMITTED PLAN SHEETS. | | | | | | 5.IN ADDITION TO SHOWING WHERE THE NUMERICAL ADDRESS | | | WILL BE LOCATED AS ON SHEET A-2, SHOW WHAT THOSE | | | NUMBERS WILL BE. | | | | | | 6.EXIT AND EMERGENCY LIGHTS TO BE INSTALLED AND | | | ARRANGED AS PER NFPA 101, 7.9 AND 7.10 | | | | | | 7.PROVIDE THE THE FOLLOWING BUILDING INFORMATION: A) | | | CONSTRUCTION TYPEB) OCCUPANCY TYPEC) FIRE | | | PROTECTION SYSTEM I.E. FIRE ALARM AND/ORFIRE | | | SPRINKLERD) INTERIOR FINISH CLASSIFICATION | | | | | | 8.IF THE BUILDING IS UNSPRINKLERED, INTERIOR FINISH | | | SHALL BE CLASS "A" OR CLASS "B". | | | | | | 9.PROVIDE A LIFE SAFETY PLAN SHEET TO INCLUDE ALL | | | COMMON PATHS OF TRAVEL TO THE EXIT(S) AND THE LOCATION | | | OF FIRE EXTINGUISHERS AT DISTANCES WHICH SATISFY THE | | | 75' TRAVEL DISTANCE REQUIREMENT. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | SHEET INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
5 |
Status |
P |
Date |
2009-12-16 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-12-16 |
Time |
15:14 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-12-16 |
Time |
15:14 |
Sent To |
|
|
| Notes |
| 2009-12-16 15:15:08 | PLANS STILL CODE COMPLIANT. -- NO CONTRACTOR SIGNED ON | | | AT THIS TIME. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
4 |
Status |
F |
Date |
2009-08-05 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-08-05 |
Time |
15:49 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-08-05 |
Time |
15:50 |
Sent To |
|
|
| Notes |
| 2009-08-10 15:50:07 | PLANS ARE CODE COMPLIANT BUT WILL REMAIN IN FAILED | | | STATUS PENDING APPLICATION FOR PERMIT BY LICENSED | | | CONTRACTOR. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2009-05-29 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-05-29 |
Time |
13:52 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-05-29 |
Time |
13:52 |
Sent To |
|
|
| Notes |
| 2009-05-29 13:53:58 | DENIED | | | REFERENCE: | | | FBC-2007 W/2009 SUPPLEMENTS | | | FBC-2007 FUEL GAS | | | | | | 1. THE FOLLOWING INFORMATION IS REQUIRED FOR THE | | | SEPARAGE GAS PERMIT: | | | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2007 | | | FUEL GAS CODE. -- THE SECTION FROM THE WALL TO THE | | | METER IS NOT INDICATED. | | | | | | B. TYPE OF GAS, (LP OR NATURAL). -- NOT INDICATED ON | | | PLANS. SITE PLANS SHOWS A 1000 GAL PROPANE TANK BUT | | | NOTE ON SHT P-2 INDICATES TABLE 402.4(2) WHICH IS A | | | NATURAL GAS TABLE. PLEASE CLARIFY. | | | | | | C. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2007 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). -- TO BE VERIFIED WHEN | | | COMMENT 8(A) IS ADDRESSED. | | | | | | D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2007 FUEL GAS CODE SEC 402.2. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2007-12-03 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-12-03 |
Time |
07:57 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-12-03 |
Time |
07:56 |
Sent To |
|
|
| Notes |
| 2007-12-03 07:59:05 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | | | | 1. SHT A-1 INDICATES GAS EQUIPMENT IN THE KITCHEN. A | | | SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE FOLLOWING | | | INFORMATION: | | | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. | | | ****NO RESPONSE, NOT ADDRESSED. | | | ******RESPONSE NOTED, BUT THE CORRESPONDING LENGHTS OF | | | EACH CUT SECTION HAVE NOT BEEN SUBMITTED, PLEASE | | | CLARIFY THE MARKINGS ON THE RISER DIAGRAM. | | | | | | B. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | | ****NO RESPONSE, NOT ADDRESSED. | | | ******NO RESPONSE, NOT INDICATED ON RISER DIAGRAM OR | | | ADJOINING NOTES. | | | | | | C. OK - LP | | | D. OK | | | | | | E. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). | | | ****NO RESPONSE, NOT ADDRESSED. | | | ******NO RESPONSE, NOT ADDRESSED. | | | | | | F. OK | | | | | | G. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. IF 2 PSI SHOW THE | | | LOCATION OF THE REGULATORS, SUBMIT MANUF. | | | SPECIFICATIONS FOR THE REGULATORS AND IF THE REGULATORS | | | ARE VENTED, INDICATE THE MATERIAL OF THE VENT AND SHOW | | | THE PIPING LOCATION. | | | ****NO RESPONSE, NOT ADDRESSED. | | | ******RESPONSE NOTED, BUT THE MANUF. SPECIFICATIONS DO | | | NOT SET THE DELIVERY PRESSURE. PLEASE ADDRESS COMMENT. | | | | | | H. OK | | | | | | I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | ****NO RESPONSE, NOT ADDRESSED. | | | ******RESPONSE NOTED, BUT MANUF. SHEETS NOT SUBMITTED. | | | | | | J. OK | | | | | | K. CLEARLY INDICATE ON THE PLAN IF THE | | | LP TANK IS ABOVE OR BELOW GROUND, AND | | | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES | | | PER NFPA 58. IF THE TANK | | | IS BELOW GROUND THE CONTAINER SHALL BE | | | SECURILY ANCHORED PER NFPA 58 SECTION | | | 3-2.2.7(H). | | | ****NO RESPONSE, NOT ADDRESSED. | | | ******RESPONSE NOTED, BUT THE ISOMETRIC ON SHT P-1 | | | INDICATES AN ABOVE GROUND TANK, AND THE SITE PLAN AS | | | WELL AS THE CIVIL SHEETS INDICATE AN UNDERGROUND TANK. | | | PLEASE CORRELATE. | | | | | | L. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. | | | ****NO RESPONSE, NOT ADDRESSED. | | | ******RESPONSE NOTED, BUT THE UNION IS NOT SHOWN, AND | | | MANUF. SPECIFICATION SHEETS ARE REQUIRED FOR THE ANSUL | | | VALVE SHOWING THAT THE VALVE IS LISTED FOR OUTSIDE | | | USE. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2007-04-09 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-04-09 |
Time |
18:06 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-04-09 |
Time |
18:06 |
Sent To |
|
|
| Notes |
| 2007-04-09 18:12:02 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | | | | THIS WAS FROM THE PREVIOUS PLUMBING REVIEW: | | | | | | 1. SHT A-1 INDICATES GAS EQUIPMENT IN THE KITCHEN. A | | | SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE FOLLOWING | | | INFORMATION: | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | B. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | C. TYPE OF GAS, (LP OR NATURAL). | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | D. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | | 402.4(33). | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | E. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | F. SUBMIT CALCULATIONS FOR COMBUSTION | | | AIR (IF APPLICABLE) PER FBC-2004 FUEL | | | GAS CODE SECTION 304. | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | G. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. IF 2 PSI SHOW THE | | | LOCATION OF THE REGULATORS, SUBMIT MANUF. | | | SPECIFICATIONS FOR THE REGULATORS AND IF THE REGULATORS | | | ARE VENTED, INDICATE THE MATERIAL OF THE VENT AND SHOW | | | THE PIPING LOCATION. | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | H. SUBMIT A DETAIL SHOWING THE TYPE, | | | LOCATION, SIZE AND TERMINATION OF THE | | | GAS VENTS PER FBC-2004 FUEL GAS CODE | | | SECS. 502 THRU 505. | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | J. CLEARLY SHOW THE LOCATION AND CAP- | | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | | OR ASME), THE DISTANCE OF THE TANK FROM | | | THE BUILDING AND ADJACENT PROPERTY LINES | | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | | INGS, AND THE LOCATION OF ANY BUILDING | | | OPENINGS BELOW THE RELIEF VALVE OF THE | | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | K. CLEARLY INDICATE ON THE PLAN IF THE | | | LP TANK IS ABOVE OR BELOW GROUND, AND | | | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES | | | PER NFPA 58. IF THE TANK | | | IS BELOW GROUND THE CONTAINER SHALL BE | | | SECURILY ANCHORED PER NFPA 58 SECTION | | | 3-2.2.7(H). | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | L. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2009-12-01 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2009-11-24 |
Time |
10:47 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2009-11-24 |
Time |
10:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2009-09-15 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-09-15 |
Time |
17:27 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-09-15 |
Time |
17:27 |
Sent To |
|
|
| Notes |
| 2009-09-15 17:29:53 | SENT TO C-32. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2009-07-16 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-07-16 |
Time |
16:45 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-07-16 |
Time |
16:45 |
Sent To |
|
|
| Notes |
| 2009-07-16 16:45:27 | TO C25 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2009-05-14 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2009-05-14 |
Time |
11:58 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2009-05-14 |
Time |
11:57 |
Sent To |
|
|
| Notes |
| 2009-05-14 11:58:18 | TO COMMERCIAL BOARD #23 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-09-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-09-28 |
Time |
09:47 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-09-28 |
Time |
09:47 |
Sent To |
|
|
| Notes |
| 2007-10-18 08:59:43 | TO "COMM" BD#12 | | 2007-09-28 09:48:01 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-03-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-03-23 |
Time |
09:00 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-03-23 |
Time |
09:00 |
Sent To |
|
|
| Notes |
| 2007-03-23 09:03:55 | TO "COMM" BD#16 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-01-03 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-01-03 |
Time |
09:55 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-11-02 |
Time |
10:34 |
Sent To |
|
|
| Notes |
| 2006-11-02 10:36:19 | TO "COMM" BD#6 |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
2 |
Status |
P |
Date |
2009-07-17 |
|
|
Cont ID |
|
| Sent By |
rkussner |
Date |
2009-07-17 |
Time |
13:27 |
Rev Time |
0.00 |
| Received By |
rkussner |
Date |
2009-07-17 |
Time |
13:27 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
F |
Date |
2009-05-29 |
|
|
Cont ID |
|
| Sent By |
rkussner |
Date |
2009-05-29 |
Time |
14:04 |
Rev Time |
0.00 |
| Received By |
rkussner |
Date |
2009-05-29 |
Time |
14:04 |
Sent To |
|
|
| Notes |
| 2009-05-29 14:40:28 | ***LANDSCAPE REVIEW FAILED*** | | | | | | PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN WRITTEN | | | FORMAT. | | | | | | 1. PURSUANT TO SECTION 94-444 (B), OUTDOOR MECHANICAL | | | EQUIPMENT SHALL NOT BE PERMITTED UNLESS APPROPRIATE | | | SCREENING IS PROVIDED. THE EQUIPMENT ENCLOSURE SHALL | | | OPEN TO THE REAR (NORTH SIDE) OF THE STRUCTURE. THE | | | CORNER ON THE SOUTH SIDE SHALL BE CUT OUT AND LANDCAPED | | | WITH VERTICAL LANDSCAPE ELEMENTS SUCH AS A PALM | | | GROUPING WITH UNDERPLANTING. | | | | | | 2. PURSUANT TO SECTION 94-443 (C)(2), SHADE TREES SHALL | | | BE PLANTED AT 30 FOOT INTERVALS IN THE REQUIRED | | | LANDSCAPE BUFFER THAT SEPARATES THE VEHICULAR USE AREA | | | FROM ADJACENT RIGHTS-FOF-WAY. AN ADDITIONAL TREE IS | | | REQUIRED ALONG THE SOUTH PERIMETER OF THE SITE ON THE | | | EAST SIDE OF THE EAST ACCESS POINT. | | | | | | 3. TREES IN TERMINAL LANDSCAPE ISLANDS SHALL BE | | | CENTERED WITHIN THE ISLAND TO PROVIDE SHADE OVER THE | | | PARKING STALL. PLEASE ADD TWO ADDITIONAL SABAL PALMS OR | | | A SHADE TREE IN THE LANDSCAPE ISLAND ON THE EAST SIDE | | | OF THE EQUIPMENT ENCLOSURE. OTHERWISE, THE THREE PALMS | | | COULD BE SHIFTED TOWARD THE SOUTH AND AN ADDITIONAL | | | PERIMETER SILVER BUTTONWOOD TREE CAN BE ADDED ALONG THE | | | NORTH PERIMETER OF THE SITE. THE SPACING OF THE TREES | | | ALONG THE NORTH PERIMETER CANNOT EXCEED 30 FEET. THE | | | TREES SHALL BE EQUALLY SPACED. | | | | | | 4. THE BLACK OLIVE TREE ALONG THE WEST PERIMETER SHALL | | | BE REMOVED AND REPLACED. IT IS NOT A FLORIDA #1 GRADE | | | TREE AND IS IN POOR HEALTH. | | | | | | 5, IN KEEPING WITH XERISCAPE GUIDELINES, GROUND COVER | | | SHALL BE PLANTED IN THE SMALL AREAS THROUGHOUT THE SITE | | | INSTEAD OF SOD. THE PLANTING WILL REQUIRE LESS WATER | | | AND MAINTENANCE THAN SOD. | | | | | | 6, THE PROPOSED HEDGE ALONG THE EAST PERIMETER OF THE | | | SITE SHALL BE PLANTED ALONG THE INTERIOR PERIMETER OF | | | THE LANDSCAPE BUFFER WITH GROUND COVER PLANTED ALONG | | | THE STREET SIDE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT | | | KUSSNER @ (561) 822-1462. | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2009-10-01 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-10-01 |
Time |
09:43 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-09-30 |
Time |
16:10 |
Sent To |
|
|
| Notes |
| 2009-10-01 09:44:18 | SEPARATE PLANS AND APPLICATIONS REQUIRED FOR THE | | | FOLLOWING: | | | | | | -HOOD | | | -HOOD SUPPRESSION | | | -WALK-IN COOLER | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2009-06-09 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-06-09 |
Time |
17:03 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-06-09 |
Time |
15:41 |
Sent To |
|
|
| Notes |
| 2009-06-09 17:03:38 | SEE EXCEPTIONS NOTED ON PLANS. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2007-10-23 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-10-23 |
Time |
11:27 |
Rev Time |
0.45 |
| Received By |
tgordon |
Date |
2007-10-23 |
Time |
11:27 |
Sent To |
|
|
| Notes |
| 2007-10-23 11:50:32 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *FOR PLAN REVIEW ONLY NOT FOR PERMIT* | | | *** DENIED *** | | | | | | 1) AS NOTED IN LAST TWO REVIEWS 11-3-06 AND 4-2-07 NOTE | | | #5. THE TWO AUXILIARY DRAIN LINES (EM) NEED TO | | | DISCHARGE TO A CONSPICUOUS LOCATION, PER 2004 FBC/M | | | 307.2.3, PLEASE CORRECT. (THE BACK OF THE BUILDING IS | | | NOT A CONSPICUOUS LOCATION). | | | | | | 2) AS NOTED IN LAST TWO REVIEWS 11-3-06 AND 4-2-07 NOTE | | | #6. PLEASE SUBMIT ENERGY CALCULATIONS, PER 2004 FBC | | | 13-101.1.1. (BE ADVISED A COMPLETE REVIEW CAN NOT BE | | | DONE WITHOUT THIS). | | | | | | 3) AS NOTED IN LAST TWO REVIEWS 11-3-06 AND 4-2-07 NOTE | | | #7. PLEASE SUBMITCOOLING LOAD CALCULATIONS, PER 2004 | | | FBC 13-407.1.ABC.1. (BE ADVISED A COMPLETE REVIEW CAN | | | NOT BE DONE WITHOUT THIS). | | | | | | 4) PLEASE SIZE THE RETURN AIR DUCT TO OFFICE, SEE W.P.B | | | AMEND. 106.3.5.4 (10). | | | | | | 5) PLEASE SIZE THE TWO FRESH AIR DUCTS TO THE AHU'S, | | | SEE W.P.B. AMEND. 106.3.5.4 (10). | | | | | | 6) THE A/C EQUIPMENT LISTING IS SHOWING THE TWO SAME | | | SYSTEMS, BUT WITH DIFFERENT SENSIBLE, LATENT, AND TOTAL | | | BTU,S PLEASE CORRECT OR EXPLAIN, SEE W.P.B. AMEND. | | | 106.3.5.4 (10). | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2007-04-02 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-04-02 |
Time |
08:04 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2007-04-02 |
Time |
08:04 |
Sent To |
|
|
| Notes |
| 2007-04-02 08:16:22 | *FOR PLAN REVIEW ONLY NOT FOR PERMIT* | | | *** DENIED *** | | | | | | 1) ALL OF THE FOLLOWING CORRECTIONS WERE REQUESTED IN | | | THE LAST REVIEW 11-3-06 AND STILL NEED TO BE | | | CORRECTED. | | | | | | 2) NEED TO SHOW THE SIZES OF THE A/C AIR DUCTS, SUPPLY | | | TRUNK LINE, RETURN TRUNK LINE, AND HALF THE SUPPLY | | | BRANCH LINES, SEE YELLOW HIGH LIGHTS ON MECH. PLANS. | | | | | | 3) NEED THE SIZE OF THE RETURN AIR GRILLS. | | | | | | 4) PROVIDE RETURN AIR TO THE OFFICE, PER 2004 FBC/M | | | 601.4. | | | | | | 5) THE TWO AUXILIARY DRAIN LINES (EM) NEED TO DISCHARGE | | | TO A CONSPICUOUS LOCATION, PER 2004 FBC/M 307.2.3, | | | PLEASE CORRECT. | | | | | | 6) PLEASE SUBMIT ENERGY CALCULATIONS, PER 2004 FBC | | | 13-101.1.1. | | | | | | 7) PLEASE SUBMITCOOLING LOAD CALCULATIONS, PER 2004 | | | FBC 13-407.1.ABC.1 . | | | | | | 8) NEED THE JOB ADDRESS ON EACH PLAN. | | | | | | 9) NEED TO SHOW AN EQUIPMENT LISTING ON MECHANICAL | | | PLANS WITH A/C EQUIPMENT MANUFACTURES NAME,MODEL | | | NUMBERS, TOTAL AND SENSIBLE BTU'S, SEER, AND ALL OTHER | | | PERTINENT INFORMATION FOR THE A/C SYSTEMS. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2006-11-03 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-11-03 |
Time |
11:44 |
Rev Time |
0.45 |
| Received By |
tgordon |
Date |
2006-11-03 |
Time |
11:44 |
Sent To |
|
|
| Notes |
| 2006-11-03 12:15:26 | *FOR PLAN REVIEW ONLY NOT FOR PERMIT* | | | *** DENIED *** | | | 1) SHOW THE LOCATION OF THE TWO A/C CONDENSER UNITS AND | | | THE ONE WALK IN COOLER CONDENSER UNIT ON THE MECHANICAL | | | PLANS. | | | | | | 2) NEED TO SHOW THE SIZES OF THE A/C AIR DUCTS, SUPPLY | | | TRUNK LINE, RETURN TRUNK LINE, AND HALF THE SUPPLY | | | BRANCH LINS, SEE HIGH LIGHTS ON MECH. PLANS. | | | | | | 3) NEED THE SIZE OF THE RETURN AIR GRILLS. | | | | | | 4) PROVIDE RETURN AIR TO THE OFFICE, PER 2004 FBC/M | | | 601.4. | | | | | | 5) THE TWO AUXILIARY DRAIN LINES (EM) NEED TO DISCHARGE | | | TO A CONSPICUOUS LOCATION, PER 2004 FBC/M 307.2.3, | | | PLEASE CORRECT. | | | | | | 6) PLEASE SUBMIT ENERGY CALCULATIONS, PER 2004 FBC | | | 13-101.1.1. | | | | | | 7) PLEASE SUBMITCOOLING LOAD CALCULATIONS, PER 2004 | | | FBC 13-407.1.ABC.1 . | | | | | | 8) NEED THE JOB ADDRESS ON EACH PLAN. | | | | | | 9) NEED TO ALSO SHOW THE SENSIBLE BTU'S AND CFM'S FOR | | | THE A/C SYSTEMS. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
7 |
Status |
P |
Date |
2009-12-16 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-12-16 |
Time |
15:14 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-12-16 |
Time |
15:14 |
Sent To |
|
|
| Notes |
| 2009-12-16 15:14:48 | PLANS STILL CODE COMPLIANT. -- NO CONTRACTOR SIGNED ON | | | AT THIS TIME. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
F |
Date |
2009-09-22 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-09-22 |
Time |
09:23 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-09-22 |
Time |
09:23 |
Sent To |
|
|
| Notes |
| 2009-09-22 09:25:41 | IRRIGATION PLANS APPROVED WITH PROVISO: DOUBLE DETECTOR | | | NOT APPROVED. AN RPZV BACKFLOW IS REQUIRED AND SHALL BE | | | INSTALLED BY A LICENSED PLUMBING CONTRACTOR. PER CILB | | | PBC. PLANS WILL REMAIN IN FAILED STATUS UNTIL BLD-COM | | | PERMIT IS APPLIED FOR BY LICENSED CONTRACTOR. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
F |
Date |
2009-08-05 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-08-05 |
Time |
15:47 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-08-05 |
Time |
15:48 |
Sent To |
|
|
| Notes |
| 2009-08-10 15:49:26 | PLANS ARE CODE COMPLIANT BUT WILL REMAIN IN FAILED | | | STATUS PENDING APPLICATION FOR PERMIT BY LICENSED | | | CONTRACTOR. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2009-05-29 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-05-29 |
Time |
13:15 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-05-29 |
Time |
13:15 |
Sent To |
|
|
| Notes |
| 2009-05-29 13:52:26 | DENIED | | | REFERENCE: | | | FBC-2007 W/2009 SUPPLEMENTS | | | FBC-2007 PLUMBING | | | FBC-2007 FUEL GAS | | | FBC-2007 BUILDING | | | FBC-2007 CHAPTER 1 (ADMIN) | | | FBC-2007 CHAPTER 11 | | | | | | | | | 1. SHT SP-1 CODE REFERENCE SHALL INCLUDE THE 2009 | | | SUPPLEMENTS. SECTION 106.1.1. | | | | | | 2. SHT A-2 THE FILTERS REFERENCED SHALL MEET THE | | | REQUIREMENTS OF NSF-42. PLEASE SUBMIT MANUF. | | | SPECIFICATIONS FOR THE FILTERS. SECTIONS 106.1.2 & | | | 611.1. | | | | | | 3. SHT A-2 ROOM FINISH SCHEDULE FOR THE TOILET ROOM | | | INDICATES PANTED WALLS. WALLS WITHIN 2 FEET OF THE | | | WATER CLOSET SHALL HAVE A SMOOTH, HARD, NONABSORBENT | | | SURFACE. PAINTED SURFACES DOES NOT MEET THE "HARD" | | | REQUIREMENT. SECTION 1210.2. | | | | | | 4. SHT A-2 TOILET ROOM ELEVATIONS. PLEASE INCLUDE THE | | | REQUIRMENT FOR SECTION 11-4.16.5 FLUSH CONTROLS. | | | | | | 5. SHT A-4 GUTTER FOR FLAT ROOF, (TOTAL AREA WITH | | | VERTICAL WALL CONTRIBUTION 1102 FS), REQUIRES A 7INCH | | | GUTTER AT .5 % SLOPE OR 6 INCH AT 1& SLOPE. TABLE | | | 1106.6. PLEASE INDICATE SLOPE REQUIRED ON GUTTER OR | | | INDICATE 7 INCH GUTTER. | | | | | | 6. SHT A-4 GUTTERS SHALL BE SIZED BY TABLE 1106.6. ROOF | | | PLAN NOTES #5 INDICATES 1106.7. THIS IS FOR OVERFLOW | | | SCUPPERS. PLEASE UPDATE TABLE REFERENCE FOR GUTTERS. | | | | | | 7. SHT P-2 SANITARY ISOMETRIC RISER DIAGRAM. MINIMUM 4" | | | PIPE IS REQUIRED UPSTREAM OF THE 1ST HAND SINK, (BY THE | | | KITCHEN). THE FIXTURE UNIT COUNT IS 41 FU AT THAT | | | POINT. TABLE 710.1(1). | | | | | | 8 THE FOLLOWING INFORMATION IS REQUIRED FOR THE | | | SEPARAGE GAS PERMIT: | | | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2007 | | | FUEL GAS CODE. -- THE SECTION FROM THE WALL TO THE | | | METER IS NOT INDICATED. | | | | | | B. TYPE OF GAS, (LP OR NATURAL). -- NOT INDICATED ON | | | PLANS. SITE PLANS SHOWS A 1000 GAL PROPANE TANK BUT | | | NOTE ON SHT P-2 INDICATES TABLE 402.4(2) WHICH IS A | | | NATURAL GAS TABLE. PLEASE CLARIFY. | | | | | | C. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2007 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). -- TO BE VERIFIED WHEN | | | COMMENT 8(A) IS ADDRESSED. | | | | | | D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2007 FUEL GAS CODE SEC 402.2. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2007-12-03 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-12-03 |
Time |
06:58 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-12-01 |
Time |
14:25 |
Sent To |
|
|
| Notes |
| 2007-12-03 07:42:39 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 FUEL GAS | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | | | | FROM PREVIOUS REVIEW: | | | ******FROM PREVIOUS REVIEWS. | | | | | | 1.OK | | | | | | 2. SUBMIT A DETAIL FOR THE TOILET ROOM. SHOW COMPLIANCE | | | WITH SECTIONS 11-4.16, 11-4.19, 11-4.22 AND ALL | | | SUBSECTIONS. | | | ****NO RESPONSE, NOT ADDRESSED. | | | SHOW THE FOLLOWING: | | | ____FOR W/C'S: | | | A. OK | | | B. OK | | | C. OK | | | D. 11-4.16.5 FLUSH CONTROLS | | | ******RESPONSE NOTED, NOT ADDRESSED | | | E. OK | | | ____FOR LAVS: | | | A. OK | | | B. 11-4.19.5 FAUCETS | | | ******RESPONSE NOTED, NOT ADDRESSED | | | | | | 3. OK | | | 4. OK | | | 5. OK | | | 6. OK | | | | | | 7. SHT P-1 THE GREASE PLUMBING RISER DOES NOT MEET | | | CODE. THE 3 COMPARTMENT SINK AND THE HAND SINK ARE NOT | | | VENTED. (MISLABELED AS LAVS). ALSO EQUIPMENT AND | | | FIXTURES UTILIZED FOR THE STORAGE, PREPARATION AND | | | HANDLING OF FOOD SHALL DISCHARGE THROUGH AN INDIRECT | | | PIPE BY MEANS OF AN AIR GAP. (A FLOOR SINK WOULD BE | | | REQUIRED). SECTIONS 802.1.1 AND 901.2.1. | | | ****NO RESPONSE, NOT ADDRESSED. | | | ******RESPONSE NOTED, BUT A RUNNING TRAP IS NOT | | | APPROVED AND A SEPARATE FLOOR SINK IS REQUIRED FOR THE | | | 3 COMPARTMENT SINK. (SEE RED LINE CORRECTION EXAMPLE | | | SHOWN ON ONE SET OF PLANS). THE MOP SINK AND ICE MAKER | | | DRAINAGE IS NOT SHOWN ON THE RISER DIAGRAM. FLOOR | | | DRAINS ARE NOT APPROVED INDIRECT WASTE RECEPTORS. A | | | FLOOR SINK OR HUB DRAIN IS REQUIRED PER SECTIONS 802.3 | | | & 802.3.2. FLOOR SINKS SHALL BE INSTALLED UNDER THE | | | FIXTURE SO THEY WILL NOT BECOME A TRIPPING HAZARD. | | | | | | 8. SUBMIT A WATER RISER DIAGRAM. SHOW ALL PIPE SIZES, | | | VALVES, AND REQUIRED WATER HAMMER ARRESTORS, (ICE | | | MACHINE). SECTIONS 106.3.5.1.3 & 604.9. | | | ****NO RESPONSE, NOT ADDRESSED. | | | ******RESPONSE NOTED, BUT ALL PIPE SIZES ARE NOT SHOWN, | | | AND PLEASE CLARIFY MARKINGS ON THE RISER DIAGRAM. | | | | | | 9. OK | | | | | | 10. SHT A-1 INDICATES GAS EQUIPMENT IN THE KITCHEN. A | | | SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE FOLLOWING | | | INFORMATION: | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. | | | ****NO RESPONSE, NOT ADDRESSED. | | | ******RESPONSE NOTED, BUT THE CORRESPONDING LENGHTS OF | | | EACH CUT SECTION HAVE NOT BEEN SUBMITTED, PLEASE | | | CLARIFY THE MARKINGS ON THE RISER DIAGRAM. | | | | | | B. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | | ****NO RESPONSE, NOT ADDRESSED. | | | ******NO RESPONSE, NOT INDICATED ON RISER DIAGRAM OR | | | ADJOINING NOTES. | | | | | | C. OK - LP | | | D. OK | | | | | | E. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). | | | ****NO RESPONSE, NOT ADDRESSED. | | | ******NO RESPONSE, NOT ADDRESSED. | | | | | | F. OK | | | | | | G. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. IF 2 PSI SHOW THE | | | LOCATION OF THE REGULATORS, SUBMIT MANUF. | | | SPECIFICATIONS FOR THE REGULATORS AND IF THE REGULATORS | | | ARE VENTED, INDICATE THE MATERIAL OF THE VENT AND SHOW | | | THE PIPING LOCATION. | | | ****NO RESPONSE, NOT ADDRESSED. | | | ******RESPONSE NOTED, BUT THE MANUF. SPECIFICATIONS DO | | | NOT SET THE DELIVERY PRESSURE. PLEASE ADDRESS COMMENT. | | | | | | H. OK | | | | | | I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | ****NO RESPONSE, NOT ADDRESSED. | | | ******RESPONSE NOTED, BUT MANUF. SHEETS NOT SUBMITTED. | | | | | | J. OK | | | | | | K. CLEARLY INDICATE ON THE PLAN IF THE | | | LP TANK IS ABOVE OR BELOW GROUND, AND | | | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES | | | PER NFPA 58. IF THE TANK | | | IS BELOW GROUND THE CONTAINER SHALL BE | | | SECURILY ANCHORED PER NFPA 58 SECTION | | | 3-2.2.7(H). | | | ****NO RESPONSE, NOT ADDRESSED. | | | ******RESPONSE NOTED, BUT THE ISOMETRIC ON SHT P-1 | | | INDICATES AN ABOVE GROUND TANK, AND THE SITE PLAN AS | | | WELL AS THE CIVIL SHEETS INDICATE AN UNDERGROUND TANK. | | | PLEASE CORRELATE. | | | | | | L. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. | | | ****NO RESPONSE, NOT ADDRESSED. | | | ******RESPONSE NOTED, BUT THE UNION IS NOT SHOWN, AND | | | MANUF. SPECIFICATION SHEETS ARE REQUIRED FOR THE ANSUL | | | VALVE SHOWING THAT THE VALVE IS LISTED FOR OUTSIDE | | | USE. | | | | | | **********NEW COMMENTS********** | | | | | | 1B. PLEASE SEE ELECTRICAL COMMENTS #3 & #4 CONCERNING | | | TITLE BLOCKS, SEALS, PRINTED NAMES REQUIRE BY THE | | | FLORIDA ADMINISTRATIVE CODE AND THE FLORIDA STATUTES. | | | ******NO RESPONSE, AND THE SP-1 SHEET IS NOT SIGNED, | | | SEALED, OR DATED. SHT LS-1 SEAL IS NOT APPROVED. PER | | | FAC 61G1-16.002 & FS 481.306. SHTS LS-1 & LS-2 ARE NOT | | | SIGNED, SEALED OR DATED. | | | | | | *****NEW COMMENTS 3RD REVIEW***** | | | | | | 1C. SHT P-1 SHOWS THE CLEANOUTS AT THE GREASE LINE & | | | SANT. LINES NEAR THE GREASE INTERCEPTOR & THE BUILDING | | | SEWER LOCATED UNDER AN A/C COMPRESSOR & IN A WALL. | | | CLEANOUTS SHALL BE ACCESSIBLE PER TABLE 708.9. ALSO THE | | | A/C UNITS ARE LOCATED OVER THE TOP OF THE GREASE | | | INTERCEPTOR WHICH ALSO REQUIRES ACCESS TO SERVICE. | | | PLEASE CLARIFY. SECTION 106.1.1. | | | | | | 2C. SHT P-1 WATER ISOMETRIC RISER DIAGRAM DOES NOT SHOW | | | WATER SUPPLY TO THE MOP SINK NOR TO THE ICE MAKER, | | | (WHICH REQUIRES A WATER HAMMER ARRESTOR). PLEASE | | | CLARIFY. SECTION 106.1.1. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2007-04-09 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-04-09 |
Time |
17:39 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-04-09 |
Time |
17:39 |
Sent To |
|
|
| Notes |
| 2007-04-09 17:50:33 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 FUEL GAS | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | | | | FROM PREVIOUS REVIEW: | | | | | | 1. SHT C-1 INDICATES "NEW CONVENIENCE STORE/PROPOSED | | | BUILDING", BUT NOTES ON SHT A-1 INDICATE AN EXISTING | | | BUILDING. PLEASE CLARIFY. SECTION 106.1.1. | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | 2. SUBMIT A DETAIL FOR THE TOILET ROOM. SHOW COMPLIANCE | | | WITH SECTIONS 11-4.16, 11-4.19, 11-4.22 AND ALL | | | SUBSECTIONS. | | | ****NO RESPONSE, NOT ADDRESSED. | | | SHOW THE FOLLOWING: | | | ____FOR W/C'S: | | | A. 11-4.16.2 CLEAR FLOOR SPACE | | | B. 11-4.16.3 HEIGHT | | | C. 11-4.16.4 GRAB BARS | | | D. 11-4.16.5 FLUSH CONTROLS | | | E. 11-4.16.6 DISPENSERS | | | ____FOR LAVS: | | | A. 11-4.19.4 EXPOSED PIPES & SURFACES | | | B. 11-4.19.5 FAUCETS | | | | | | 3. A GREASE INTERCEPTOR MAY BE REQUIRED. PLEASE CONTACT | | | LYNN MASSON, ENVIRONMENTAL COMPLIANCE MANAGER, PHONE | | | NUMBER (561) 822-2271, FAX (561) 822-2279, OR E-MAIL | | | [email protected]. WASTE ORD. 3434. | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | 4. PER TABLE 403.1 A DRINKING FOUNTAIN IS REQUIRED. | | | PLEASE INDICATE THE LOCATION ON THE FLOOR PLAN. SUBMIT | | | A DETAIL SHOWING COMPLIANCE WITH SECTION 11-4.15 AND | | | ALL SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A) | | | PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR | | | STOOPING. SHOW DRINKING FOUNTAIN ON THE SANT. AND WATER | | | RISER DIAGRAMS. | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | 5. SHT A-1 GENERAL NOTES #1. THE CODE ADOPTED IS | | | FBC-2004 NOT FBC-2001 AS INDICATED. PLEASE UPDATE YOUR | | | NOTES TO REFLECT THE CODE IN EFFECT. | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | 6. SHT P-1THE SANITARY PLUMBING RISER DOES NOT MEET | | | CODE. HORIZONTAL DRY VENTS ARE NOT APPROVED. SECTION | | | 905.3. - THE 3" VENT UPSTREAM OF THE W/C IS NOT | | | REQUIRED. THE 2" VENT AT THE LAV IS SUFFICIENT. ****NO | | | RESPONSE, NOT ADDRESSED. | | | | | | 7. SHT P-1 THE GREASE PLUMBING RISER DOES NOT MEET | | | CODE. THE 3 COMPARTMENT SINK AND THE HAND SINK ARE NOT | | | VENTED. (MISLABELED AS LAVS). ALSO EQUIPMENT AND | | | FIXTURES UTILIZED FOR THE STORAGE, PREPARATION AND | | | HANDLING OF FOOD SHALL DISCHARGE THROUGH AN INDIRECT | | | PIPE BY MEANS OF AN AIR GAP. (A FLOOR SINK WOULD BE | | | REQUIRED). SECTIONS 802.1.1 AND 901.2.1. | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | 8. SUBMIT A WATER RISER DIAGRAM. SHOW ALL PIPE SIZES, | | | VALVES, AND REQUIRED WATER HAMMER ARRESTORS, (ICE | | | MACHINE). SECTIONS 106.3.5.1.3 & 604.9. | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | 9. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE TO | | | THE BUILDING. SECTION 608.13.2. | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | 10. SHT A-1 INDICATES GAS EQUIPMENT IN THE KITCHEN. A | | | SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE FOLLOWING | | | INFORMATION: | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | B. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | C. TYPE OF GAS, (LP OR NATURAL). | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | D. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | | 402.4(33). | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | E. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | F. SUBMIT CALCULATIONS FOR COMBUSTION | | | AIR (IF APPLICABLE) PER FBC-2004 FUEL | | | GAS CODE SECTION 304. | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | G. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. IF 2 PSI SHOW THE | | | LOCATION OF THE REGULATORS, SUBMIT MANUF. | | | SPECIFICATIONS FOR THE REGULATORS AND IF THE REGULATORS | | | ARE VENTED, INDICATE THE MATERIAL OF THE VENT AND SHOW | | | THE PIPING LOCATION. | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | H. SUBMIT A DETAIL SHOWING THE TYPE, | | | LOCATION, SIZE AND TERMINATION OF THE | | | GAS VENTS PER FBC-2004 FUEL GAS CODE | | | SECS. 502 THRU 505. | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | J. CLEARLY SHOW THE LOCATION AND CAP- | | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | | OR ASME), THE DISTANCE OF THE TANK FROM | | | THE BUILDING AND ADJACENT PROPERTY LINES | | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | | INGS, AND THE LOCATION OF ANY BUILDING | | | OPENINGS BELOW THE RELIEF VALVE OF THE | | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | K. CLEARLY INDICATE ON THE PLAN IF THE | | | LP TANK IS ABOVE OR BELOW GROUND, AND | | | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES | | | PER NFPA 58. IF THE TANK | | | IS BELOW GROUND THE CONTAINER SHALL BE | | | SECURILY ANCHORED PER NFPA 58 SECTION | | | 3-2.2.7(H). | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | L. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | **********NEW COMMENTS********** | | | | | | 1B. PLEASE SEE ELECTRICAL COMMENTS #3 & #4 CONCERNING | | | TITLE BLOCKS, SEALS, PRINTED NAMES REQUIRE BY THE | | | FLORIDA ADMINISTRATIVE CODE AND THE FLORIDA STATUTES. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-01-03 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-01-03 |
Time |
08:35 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-01-03 |
Time |
08:35 |
Sent To |
|
|
| Notes |
| 2007-01-03 09:53:04 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 FUEL GAS | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | | | | 1. SHT C-1 INDICATES "NEW CONVENIENCE STORE/PROPOSED | | | BUILDING", BUT NOTES ON SHT A-1 INDICATE AN EXISTING | | | BUILDING. PLEASE CLARIFY. SECTION 106.1.1. | | | | | | 2. SUBMIT A DETAIL FOR THE TOILET ROOM. SHOW COMPLIANCE | | | WITH SECTIONS 11-4.16, 11-4.19, 11-4.22 AND ALL | | | SUBSECTIONS. | | | | | | 3. A GREASE INTERCEPTOR MAY BE REQUIRED. PLEASE CONTACT | | | LYNN MASSON, ENVIRONMENTAL COMPLIANCE MANAGER, PHONE | | | NUMBER (561) 822-2271, FAX (561) 822-2279, OR E-MAIL | | | [email protected]. WASTE ORD. 3434. | | | | | | 4. PER TABLE 403.1 A DRINKING FOUNTAIN IS REQUIRED. | | | PLEASE INDICATE THE LOCATION ON THE FLOOR PLAN. SUBMIT | | | A DETAIL SHOWING COMPLIANCE WITH SECTION 11-4.15 AND | | | ALL SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A) | | | PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR | | | STOOPING. SHOW DRINKING FOUNTAIN ON THE SANT. AND WATER | | | RISER DIAGRAMS. | | | | | | 5. SHT A-1 GENERAL NOTES #1. THE CODE ADOPTED IS | | | FBC-2004 NOT FBC-2001 AS INDICATED. PLEASE UPDATE YOUR | | | NOTES TO REFLECT THE CODE IN EFFECT. | | | | | | 6. SHT P-1THE SANITARY PLUMBING RISER DOES NOT MEET | | | CODE. HORIZONTAL DRY VENTS ARE NOT APPROVED. SECTION | | | 905.3. - THE 3" VENT UPSTREAM OF THE W/C IS NOT | | | REQUIRED. THE 2" VENT AT THE LAV IS SUFFICIENT. | | | | | | 7. SHT P-1 THE GREASE PLUMBING RISER DOES NOT MEET | | | CODE. THE 3 COMPARTMENT SINK AND THE HAND SINK ARE NOT | | | VENTED. (MISLABELED AS LAVS). ALSO EQUIPMENT AND | | | FIXTURES UTILIZED FOR THE STORAGE, PREPARATION AND | | | HANDLING OF FOOD SHALL DISCHARGE THROUGH AN INDIRECT | | | PIPE BY MEANS OF AN AIR GAP. (A FLOOR SINK WOULD BE | | | REQUIRED). SECTIONS 802.1.1 AND 901.2.1. | | | | | | 8. SUBMIT A WATER RISER DIAGRAM. SHOW ALL PIPE SIZES, | | | VALVES, AND REQUIRED WATER HAMMER ARRESTORS, (ICE | | | MACHINE). SECTIONS 106.3.5.1.3 & 604.9. | | | | | | 9. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE TO | | | THE BUILDING. SECTION 608.13.2. | | | | | | 10. SHT A-1 INDICATES GAS EQUIPMENT IN THE KITCHEN. A | | | SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE FOLLOWING | | | INFORMATION: | | | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. | | | | | | B. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | | | | | C. TYPE OF GAS, (LP OR NATURAL). | | | | | | D. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | | 402.4(33). | | | | | | E. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). | | | | | | F. SUBMIT CALCULATIONS FOR COMBUSTION | | | AIR (IF APPLICABLE) PER FBC-2004 FUEL | | | GAS CODE SECTION 304. | | | | | | G. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. IF 2 PSI SHOW THE | | | LOCATION OF THE REGULATORS, SUBMIT MANUF. | | | SPECIFICATIONS FOR THE REGULATORS AND IF THE REGULATORS | | | ARE VENTED, INDICATE THE MATERIAL OF THE VENT AND SHOW | | | THE PIPING LOCATION. | | | | | | H. SUBMIT A DETAIL SHOWING THE TYPE, | | | LOCATION, SIZE AND TERMINATION OF THE | | | GAS VENTS PER FBC-2004 FUEL GAS CODE | | | SECS. 502 THRU 505. | | | | | | I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | | | J. CLEARLY SHOW THE LOCATION AND CAP- | | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | | OR ASME), THE DISTANCE OF THE TANK FROM | | | THE BUILDING AND ADJACENT PROPERTY LINES | | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | | INGS, AND THE LOCATION OF ANY BUILDING | | | OPENINGS BELOW THE RELIEF VALVE OF THE | | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | | | | K. CLEARLY INDICATE ON THE PLAN IF THE | | | LP TANK IS ABOVE OR BELOW GROUND, AND | | | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES | | | PER NFPA 58. IF THE TANK | | | IS BELOW GROUND THE CONTAINER SHALL BE | | | SECURILY ANCHORED PER NFPA 58 SECTION | | | 3-2.2.7(H). | | | | | | L. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
X |
PERMIT EXTENSION |
| Rev No |
1 |
Status |
N |
Date |
2010-07-22 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2010-07-22 |
Time |
18:55 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2010-07-22 |
Time |
18:55 |
Sent To |
|
|
| Notes |
| 2010-07-22 18:55:53 | PERMIT APPLICATION EXTENDED UNTIL 9/16/10. LETTER IN | | | FILE. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
5 |
Status |
P |
Date |
2009-09-21 |
|
|
Cont ID |
|
| Sent By |
kdfreema |
Date |
2009-09-21 |
Time |
13:39 |
Rev Time |
0.00 |
| Received By |
kdfreema |
Date |
2009-09-21 |
Time |
13:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2009-06-11 |
|
|
Cont ID |
|
| Sent By |
kdfreema |
Date |
2009-06-11 |
Time |
11:02 |
Rev Time |
0.00 |
| Received By |
kdfreema |
Date |
2009-06-11 |
Time |
11:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2007-10-25 |
|
|
Cont ID |
|
| Sent By |
kdfreema |
Date |
2007-10-25 |
Time |
16:05 |
Rev Time |
0.00 |
| Received By |
kdfreema |
Date |
2007-10-25 |
Time |
16:05 |
Sent To |
|
|
| Notes |
| 2007-10-25 16:52:13 | ***FAILED*** | | | | | | 1. PLEASE PROVIDE A RESPONSE TO ALL COMMENTS IN | | | WRITING. | | | | | | 2. A LETTER FROM THE CITY'S ENGINEERING SERVICES | | | DEPARTMENT MUST BE PROVIDED APPROVING THE NEW DUMPSTER | | | APPROACH CONFIGURATION. | | | | | | 3. THE DUMPSTER ENCLOSURE MUST BE LANDSCAPED ON ITS | | | EAST SIDE. | | | | | | 4. THE GENERATOR ENCLOSURE MUST BE LANDSCAPED ON ITS | | | SOUTH AND EAST SIDES. | | | | | | 5. THE GENERATOR ENCLOSURE DOORS MAY NOT OPEN INTO THE | | | HANDICAP ACCESS AISLE. | | | | | | 6. ALL PARKING ROWS MUST BE TERMINATED WITH A SHADE | | | TREE. | | | | | | 7. PLEASE CORRECT THE PARKING LOT STRIPING DETAIL TO | | | CONFORM TO THE CITY OF WPB REQUIREMENTS. | | | | | | 8. ENSURE THAT SPECIES SYMBOLS ARE CONSISTENT ACROSS | | | SPECIES. | | | | | | 9. MAKE SURE THAT ALL PLANT COUNTS ARE CONSISTENT | | | ACROSS THE TABLE, NUMBER OF SYMBOLS SHOWN, AND NUMBER | | | CALLED OUT ON THE PLANS. | | | | | | 10. PLEASE FOLLOW THE FPL RIGHT TREE RIGHT PLACE | | | GUIDELINES WITH RESPECT TO TREE SELECTION. THE COCONUT | | | PALMS AT THE NORTHEAST AND SOUTHEAST CORNERS OF THE LOT | | | ARE UNDER OVERHEAD POWERLINES, PLEASE REPLACE THEM WITH | | | LOWER TREES. | | | | | | 11. PLEASE CLARIFY WHERE ALL OF THE EXISTING PLANT | | | MATERIAL TO BE REUSED IS LOCATED. NOTE THAT ALL | | | MATERIAL TO BE REUSED MUST BE FLORIDA #1 OR GREATER. | | | | | | 12. THE PARALLEL PARKING SPACES SHOWN AT THE SOUTHEAST | | | CORNER ARE TOO SHORT; THE MINIMUM LENGTH IS 22 FEET. | | | | | | PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1435 | | | OR [email protected] WITH QUESTIONS. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2007-03-27 |
|
|
Cont ID |
|
| Sent By |
kdfreema |
Date |
2007-03-27 |
Time |
10:06 |
Rev Time |
0.00 |
| Received By |
kdfreema |
Date |
2007-03-27 |
Time |
10:06 |
Sent To |
|
|
| Notes |
| 2007-03-27 10:52:05 | **FAILED** | | | | | | 1. ALL SURVEYS MUST BEAR AN ORIGINAL SIGNATURE AND | | | RAISED SEAL. | | | | | | 2. NO SITE PLAN WAS PROVIDED. | | | | | | 3. THE PROPOSED GENERATOR AS WELL AS ALL EXTERIOR | | | MECHANICAL EQUIPMENT MUST BE SHOWN ON BOTH THE SITE | | | PLAN AND LANDSCAPE PLAN. | | | | | | 4. PLEASE NOTE THAT ALTHOUGH THE ZONING CODE ALLOWS | | | GENERATORS TO BE PLACED AS CLOSE TO 1 FOOT FROM THE | | | PROPERTY LINE IN THIS ZONING DISTRICT, OTHER TRADES MAY | | | REQUIRE A GREATER SEPARATION DISTANCE. | | | | | | PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1435 | | | WITH ANY QUESTIONS. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2009-07-27 |
|
|
Cont ID |
|
| Sent By |
kdfreema |
Date |
2006-11-16 |
Time |
11:10 |
Rev Time |
0.00 |
| Received By |
kdfreema |
Date |
2006-11-16 |
Time |
11:10 |
Sent To |
|
|
| Notes |
| 2006-11-16 11:17:54 | **FAILED** | | | | | | COPIES OF YOUR SITE PLAN, LANDSCAPE PLAN, AND PROPERTY | | | SURVEY SHALL BE PROVIDED. | | | | | | PLEASE CONTACT KELLY FREEMAN, PLANNER, AT (561)822-1435 | | | WITH QUESTIONS. | | | |
|
|
|