Plan Review Details - Permit 06101156
Plan Review Stops For Permit 06101156
Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2010-09-13 Cont ID  
Sent By dwise Date 2010-09-13 Time 15:40 Rev Time 0.00
Received By dwise Date 2010-09-13 Time 15:40 Sent To  
Notes
2010-09-13 15:41:36APPROVED WITH PROVISO BY R. MCDOUGAL ON 12/15/2009

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2009-12-15 Cont ID  
Sent By rmcdouga Date 2009-12-15 Time 12:07 Rev Time 0.00
Received By rmcdouga Date 2009-12-15 Time 07:50 Sent To  
Notes
2009-12-15 16:08:00REVISION REQUIRED THE FOLLOWING ITEMS HAVE BEEN DEEMED
 DEFICIENT OR WERE NOTED TO BE MISSING UPON REVIEW:
  
 1) TRUSS DRAWINGS AND LAYOUT SIGNED SEALED AND DATED BY
 THE TRUSS ENGINEER AND REVIEWED BY THE DESIGNER OF
 RECORD OF THE STRUCTURE. MUST BE REVIEWED AND APPROVED
 PRIOR TO INSTALLATION. FBC 106.3.5
  
 2) TWO COPIES OF A KEY PLAN AND INSTALLATION SCHEDULE
 FOR THE ACCORDION SHUTTERS. SPECIFY THE OPENING
 LOCATIONS OF THE SHUTTERS, THE MOUNT TYPE, SPANS,
 FASTENERS, FASTENER SPACING, ETC. FBC 1609.1.2 NOTE: IF
 ALL OF THE REQUIRED INFORMATION IS SUBMITTED WITH THIS
 PERMIT THE SHUTTERS WILL BE INCLUDED WITH THIS PERMIT.
 IF NOT, A SEPARATE PERMIT AND FEES WILL BE REQUIRED AND
 THE C.O. WILL NOT BE ISSUED UNTIL THEY HAVE BEEN
 INSTALLED AND APPROVED.
  
 3) TWO COPIES OF PRODUCT APPROVALS FOR THE BULLET
 RESISTANT WINDOWS AND PAYMENT DRAWER ASSEMBLIES, THE
 ROOFING MATERIALS AND THE WALL MOUNTED LOUVER VENTS FOR
 ATTIC VENTILATION. DCA RULE 9B-72
  
 4) THE GLASS TYPE, MULLION TYPE AND ANCHOR TYPE OF THE
 STOREFRONT WINDOWS. THIS INFORMATION DETERMINES THE
 DESIGN PRESSURES FOR THE ASSEMBLIES. FBC 1604.9 THIS
 INFORMATION CAN BE PROVIDED WITH THE SHOP DRAWINGS FROM
 THE WINDOW COMPANY. THEY WILL NEED TO BE SUBMITTED AND
 APPROVED PRIOR TO INSTALLATION.
  
 5) THE HINGE OPTION AND IF THE STOREFRONT DOOR IS
 REINFORCED OR NOT. THIS INFORMATION DETERMINES DESIGN
 PRESSURES FOR THE ASSEMBLY. FBC 1604.9 THIS INFORMATION
 CAN BE PROVIDED WITH THE SHOP DRAWINGS.
  
  
  
2009-12-15 14:49:05TEMPORARY FAILED STATUS WILL REMAIN UNTIL A CONTRACTOR
 IS DETERMINED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2009-09-29 Cont ID  
Sent By rmcdouga Date 2009-09-29 Time 14:41 Rev Time 0.00
Received By rmcdouga Date 2009-09-29 Time 14:40 Sent To  
Notes
2009-09-29 16:19:242007 FBC W/2009 REVISIONS
 CONVENIENCE STORE WITH FUEL DISPENSING
  
 DENIED BY BUILDING
  
 1) ON SHEET S-1 THE COMPONENT AND CLADDING PRESSURES
 ARE INCORRECT FOR EXPOSURE C WITH A 20' MEAN ROOF
 HEIGHT. THE ONES LISTED ARE EXPOSURE 'B' PRESSURES.
 PLEASE CORRECT. FBC 1609.4.1
  
 2) ON SHEET S-2 THE NOTES AT THE BOTTOM OF THE PAGE
 LIST THE MEAN ROOF HEIGHT AS 30' AND THE BASIC WIND
 PRESSURE AS 29.85 PSF. THESE ARE INCORRECT. THE MEAN
 ROOF HEIGHT IS SPECIFIED AS 20' AND THE BASIC WIND
 PRESSURE FOR EXPOSURE C AS 38.38 ON SHEET S-1. PLEASE
 CORRECT. FBC 1609
  
 3) SUBMIT TRUSS DRAWINGS AND LAYOUT SIGNED SEALED AND
 DATED BY THE TRUSS ENGINEER AND REVIEWED BY THE
 DESIGNER OF RECORD OF THE STRUCTURE. MUST BE REVIEWED
 AND APPROVED PRIOR TO INSTALLATION. FBC 106.3.5
  
 4) SUBMIT TWO COPIES OF A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE ACCORDION SHUTTERS. SPECIFY THE
 OPENING LOCATIONS OF THE SHUTTERS, THE MOUNT TYPE,
 SPANS, FASTENERS, FASTENER SPACING, ETC. FBC 1609.1.2
 NOTE: IF ALL OF THE REQUIRED INFORMATION IS SUBMITTED
 WITH THIS PERMIT THE SHUTTERS WILL BE INCLUDED WITH
 THIS PERMIT. IF NOT, A SEPARATE PERMIT AND FEES WILL BE
 REQUIRED AND THE C.O. WILL NOT BE ISSUED UNTIL THEY
 HAVE BEEN INSTALLED AND APPROVED.
  
 5) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 BULLET RESISTANT WINDOWS AND PAYMENT DRAWER ASSEMBLIES.
 DCA RULE 9B-72
  
 6) ON THE PRODUCT APPROVALS FOR THE STOREFRONT WINDOWS,
 SPECIFY THE GLASS TYPE, MULLION TYPE AND ANCHOR TYPE BY
 CIRCLING THE APPROPRIATE ITEMS IN THE TABLES. THIS
 INFORMATION DETERMINES THE DESIGN PRESSURES FOR THE
 ASSEMBLIES. FBC 1604.9 THIS INFORMATION CAN BE PROVIDED
 WITH THE SHOP DRAWINGS FROM THE WINDOW COMPANY. THEY
 WILL NEED TO BE SUBMITTED AND APPROVED PRIOR TO
 INSTALLATION.
  
 7) ON THE PRODUCT APPROVALS FOR THE STOREFRONT DOOR
 SPECIFY THE HINGE OPTION AND IF REINFORCED OR NOT. THIS
 INFORMATION DETERMINES DESIGN PRESSURES FOR THE
 ASSEMBLY. FBC 1604.9 THIS INFORMATION CAN ALSO BE
 PROVIDED WITH THE SHOP DRAWINGS.
  
 8) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 ROOFING MATERIALS AND THE WALL MOUNTED LOUVER VENTS FOR
 ATTIC VENTILATION. DCA RULE 9B-72
  
 9) PLEASE RESPOND TO COMMENTS IN WRITING.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2009-07-24 Cont ID  
Sent By rmcdouga Date 2009-07-24 Time 14:26 Rev Time 0.00
Received By rmcdouga Date 2009-07-24 Time 14:26 Sent To  
Notes
2009-07-24 12:22:542007 FBC W/2009 REVISIONS
 CONVENIENCE STORE WITH FUEL DISPENSING
  
 DENIED BY BUILDING
  
 1) ON SHEET S-1 AND THE TOP OF SHEET S-2 THE EXPOSURE
 CATEGORY IS CORRECTLY SPECIFIED AS 'C'. HOWEVER, AT THE
 BOTTOM OF SHEET S-2 THE EXPOSURE 'B' IS SPECIFIED ON
 THE ROOF ZONE DETAIL. PLEASE CORRECT. FBC 1609.4.1
  
 2) THE COMPONENT AND CLADDING PRESSURES ON SHEET A-5 DO
 NOT CORRESPOND WITH THOSE ON SHEET S-1. THE PRESSURES
 ON A-5 ARE FOR EXPOSURE CATEGORY 'B'. PLEASE CORRECT.
 FBC 1609
  
 3) SUBMIT TRUSS DRAWINGS AND LAYOUT SIGNED SEALED AND
 DATED BY THE TRUSS ENGINEER AND REVIEWED BY THE
 DESIGNER OF RECORD OF THE STRUCTURE. MUST BE REVIEWED
 AND APPROVED PRIOR TO INSTALLATION. FBC 106.3.5
  
 4) SHEET A-1 AND S-2 OF THE PLANS SPECIFY IMPACT
 WINDOWS AND NO SHUTTERS. HOWEVER, THE PRODUCT APPROVALS
 THAT WERE SUBMITTED FOR THE STOREFRONTS ARE NOT IMPACT
 RATED AND PRODUCT APPROVALS FOR ACCORDION SHUTTERS WERE
 SUBMITTED. PLEASE CLARIFY. FBC 1609.1.2
  
 5) SUBMIT TWO COPIES OF A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE ACCORDION SHUTTERS. SPECIFY THE
 OPENING LOCATIONS OF THE SHUTTERS, THE MOUNT TYPE,
 SPANS, FASTENERS, FASTENER SPACING, ETC. FBC 1609.1.2
  
 6) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 BULLET RESISTANT WINDOWS AND PAYMENT DRAWER ASSEMBLIES.
 DCA RULE 9B-72
  
 7) ON THE PRODUCT APPROVALS FOR THE STOREFRONT WINDOWS,
 SPECIFY THE GLASS TYPE, MULLION TYPE AND ANCHOR TYPE BY
 CIRCLING THE APPROPRIATE ITEMS IN THE TABLES. THIS
 INFORMATION DETERMINES THE DESIGN PRESSURES FOR THE
 ASSEMBLIES. FBC 1604.9
  
 8) ON THE PRODUCT APPROVALS FOR THE STOREFRONT DOOR
 SPECIFY THE HINGE OPTION AND IF REINFORCED OR NOT. THIS
 INFORMATION DETERMINES DESIGN PRESSURES FOR THE
 ASSEMBLY. FBC 1604.9
  
 9) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 ROOFING MATERIALS AND THE WALL MOUNTED LOUVER VENTS FOR
 ATTIC VENTILATION. DCA RULE 9B-72
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2009-06-02 Cont ID  
Sent By rmcdouga Date 2009-06-02 Time 13:37 Rev Time 0.00
Received By rmcdouga Date 2009-06-02 Time 13:37 Sent To  
Notes
2009-06-02 14:54:262007 FBC W/2009 REVISIONS
 CONVENIENCE STORE WITH FUEL DISPENSING
  
  
 DENIED BY BUILDING
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) THE CODE THAT IS CURRENTLY IN EFFECT IS THE 2007
 FLORIDA BUILDING CODE WITH 2009 SUPPLEMENT. PLEASE
 CORRECT CODE NOTE ON SHEET SP-1.
  
 3) SPECIFY THE REQUIRED SOIL BEARING CAPACITY ON THE
 PLANS. FBC 1804.1
  
 4) PLEASE UPDATE THE STANDARDS SPECIFIED ON SHEETS S-1
 AND S-2 TO THE EDITIONS SPECIFIED IN CHAPTER 35 OF THE
 2007 FBC. ASCE 7-05, ACI 318-05, ACI 315-05, TMS 402-05
 AND TMS 602-05.
  
 5) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 EXTERIOR WINDOWS, DOORS, STOREFRONTS, MULLIONS, ROOFING
 MATERIAL, TRUSS CONNECTORS, IMPACT PROTECTION PRODUCTS,
 ETC. AS REQUIRED BY FAC RULE 9B-72.
  
 6) SUBMIT TRUSS DRAWINGS AND LAYOUT SIGNED, SEALED AND
 DATED BY THE TRUSS ENGINEER AND REVIEWED AND APPROVED
 BY THE DESIGNER OF RECORD FOR THE STRUCTURE. FBC
 106.3.5* CITY AMENDMENTS. NOTE: THE UPLIFT AT HIP
 GIRDER TRUSSES MAY EXCEED 1500#.
  
 7) SPECIFY THE REQUIRED SOIL BEARING CAPACITY ON THE
 PLANS. FBC 1804.1.
  
 8) THE ROOF VENTILATION NOTE ON A-4 SITES EXCEPTION #2
 TO FBC 1203.2. THIS EXCEPTION APPLIES TO UN-VENTED
 ATTICS SUCH AS THOSE USING SPRAY FOAM INSULATION
 APPLIED TO THE UNDERSIDE OF THE ROOF DECK. THE PLANS DO
 NOT INDICATE THIS TYPE OF ATTIC. SHOW COMPLIANCE WITH
 FBC 1203.2.
  
 9) 2603.4.1.3 WALK -IN COOLERS .
 IN NONSPRINKLERED BUILDINGS, FOAM PLASTIC HAVING A
 THICKNESS THAT DOES NOT EXCEED 4 INCHES (102 MM) AND A
 MAXIMUM FLAME SPREAD INDEX OF 75 IS PERMITTED IN WALK
 -IN COOLERS OR FREEZER UNITS WHERE THE AGGREGATE FLOOR
 AREA DOES NOT EXCEED 400 SQUARE FEET (37 M 2 ) AND THE
 FOAM PLASTIC IS COVERED BY A METAL FACING NOT LESS THAN
 0.032-INCH-THICK (0.81 MM) ALUMINUM OR
 CORROSION-RESISTANT STEEL HAVING A MINIMUM BASE METAL
 THICKNESS OF 0.016 INCH (0.41 MM). A THICKNESS OF UP TO
 10 INCHES (254 MM) IS PERMITTED WHERE PROTECTED BY A
 THERMAL BARRIER. THE WALK-IN COOLER SHOWN ON THE PLANS
 APPEARS TO BE LARGER THAN THE 400 SQFT ALLOWED. SHOW
 HOW WALK-IN COOLER COMPLIES. PROVIDE MANUFACTURER'S
 SPECIFICATIONS AND DETAILS.
  
 10) DOOR #S 3 AND 5 DO NOT HAVE THE MANEUVERING
 CLEARANCES REQUIRED BY FBC 11-4.13.6. A MINIMUM OF 18"
 IS REQUIRED ON THE PULL SIDE AT THE LATCH OF SIDE SWING
 DOORS.
  
 11) AS NOTED ON THE PLAN A SEPARATE PERMIT WILL BE
 REQUIRED FOR THE STAND ALONE CANOPY AT GAS PUMPS.
  
 12) THE LIFE SAFETY PLAN DOES NOT INDICATE THE TRAVEL
 DISTANCE FROM INSIDE THE WALK-IN COOLER TO THE ONE
 EXIT. THIS APPEARS TO BE A TRAVEL DISTANCE IN EXCESS OF
 75 FT, WHICH WOULD REQUIRE TWO EXITS. FBC 1019.2 AND
 1015.1
  
 13) ON LS-1, THE OCCUPANT LOAD FOR THE WALK-IN COOLER
 SHOULD BE INCLUDED IN THE TABLE AS A STORAGE OCCUPANCY.
 FBC TABLE 1004.1.1 AND TABLE 508.3
  
 14) THE WEST EXTERIOR WALL THAT IS LOCATED AT 6 FT FROM
 THE PROPERTY LINE IS REQUIRED TO HAVE A ONE HOUR FIRE
 RATING PER FBC TABLE 602. THE MAXIMUM AREA OF EXTERIOR
 WALL OPENINGS IS 10 PERCENT PER TABLE 704.8. PLEASE
 NOTE THIS ON PLANS.
  
 NOTE: FOR THE NORTH OR REAR WALL WHICH IS LOCATED ON AN
 ALLEY, THE FIRE SEPARATION DISTANCE IS MEASURED FROM
 THE FACE OF THE BUILDING TO THE CENTERLINE OF THE
 ALLEY, WHICH IS 16 FEET BASED ON THE SITE PLAN. THIS
 WALL IS NOT REQUIRED TO BE FIRE RATED BY TABLE 602 AND
 FOOTNOTE I OF TABLE 704.8 ALLOWS UNLIMITED UNPROTECTED
 OPENINGS.
  
 NOTE: ADDITIONAL COMMENTS MAY RESULT WHEN THESE
 COMMENTS ARE ADDRESSED, DUE TO THE AMOUNT OF MISSING
 INFORMATION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-11-14 Cont ID  
Sent By rmcdouga Date 2007-11-14 Time 10:41 Rev Time 0.00
Received By rmcdouga Date 2007-11-13 Time 17:33 Sent To  
Notes
2007-11-14 11:46:582004 FBC
 CONSTRUCT NEW CONVENIENCE STORE (PLAN REVIEW)
  
 DENIED BY BUILDING
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2)A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) COMPLIED.
  
 4) COMPLIED.
  
 5) FBC SECTION 1603.1.2 THAT WAS SPECIFIED UNDER DESIGN
 PARAMETERS ON SHEETS A2 AND A7 IS NOT THE APPROPRIATE
 SECTION. PLEASE CORRECT. SPECIFY CHAPTER 16.
  
 6) COMPLIED.
  
 7) PROVIDESURVEY/SITE PLANS INDICATING THE LOCATION
 OF THE STRUCTURE, DISTANCE TO PROPERTY LINES, DISTANCES
 TO OTHER STRUCTURES ON THE PROPERTY FOR DETERMINING
 FIRE SEPARATION DISTANCES. SEE FBC 702, 704.8 AND TABLE
 602. THE SURVEY THAT WAS SUBMITTED DOES NOT CORRESPOND
 WITH THE SITE PLANS. THE SITE PLAN IS NOT SIGNED AND
 SEALED.
  
 8)SUBMIT ENERGY CALCULATIONS FOR THE STRUCTURE AS
 REQUIRED BY FBC 13-4.
  
 9)SUBMIT PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS,
 DOORS, STOREFRONTS, MULLIONS, ROOFING MATERIAL, IMPACT
 PROTECTION PRODUCTS, ETC.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE.
  
 10)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 11) SPECIFY HOW IMPACT PROTECTION OF OPENINGS WILL BE
 PROVIDED AS REQUIRED BY FBC 1609.1.4. IF STORM PANELS
 ARE TO BE USED, SUBMIT 2 COPIES OF PRODUCT APPROVALS, A
 KEY PLAN AND INSTALLATION SCHEDULE. SPECIFY THE MOUNT
 TYPE, ANCHORS, ANCHOR SPACING, ETC.
  
 12) SUBMIT TRUSS DRAWINGS AND LAYOUT SIGNED, SEALED AND
 DATED BY THE TRUSS ENGINEER AND REVIEWED AND APPROVED
 BY THE DESIGNER OF RECORD OF THE STRUCTURE. FBC
 106.3.5* CITY AMENDMENTS. NOTE: THE UPLIFT AT HIP
 GIRDER TRUSSES MAY EXCEED 1500#.
  
 13)SPECIFY THE ANCHOR TYPE, SIZE, EMBED DEPTH AND
 SIZE OF THE HOLES FOR THE ANCHORS FOR THE STEEL COLUMN
 BASE. SPECIFY THE WELD TYPE FOR THE COLUMN TO BASE
 ATTACHMENT. PROVIDE A DETAIL SPECIFYING THE COLUMN CAP
 FOR THE STEEL COLUMNS WITH FASTENERS, WELDS, ETC.
 INDICATED. THE STEEL COLUMN THICKNESS ON A-3 IS NOT
 LEGIBLE.
  
 14) COMPLIED.
  
 15)COMPLIED.
  
 16) THE ROOF ZONE FIGURE FOR THE HIP ROOF ON A7 IS
 INCORRECT. THE OUTSIDE CORNER AREAS OF THE HIP ROOF ARE
 ZONE 3 . SEE FBC FIGURE 1609.6.2.2 W/2006 REVISIONS
 (REVISED SHEETS).
  
 17)SHOW HOW WALK-IN COOLER COMPLIES WITH 2603.4
 THERMAL BARRIER. PROVIDE MANUFACTURER'S SPECIFICATIONS
 AND DETAILS.
 EXCEPT AS PROVIDED FOR IN SECTIONS 2603.4.1 AND 2603.8
 , FOAM PLASTIC SHALL BE SEPARATED FROM THE INTERIOR OF
 A BUILDING BY AN APPROVED THERMAL BARRIER OF 0.5-INCH
 (12.7 MM) GYPSUM WALLBOARD OR EQUIVALENT THERMAL
 BARRIER MATERIAL THAT WILL LIMIT THE AVERAGE
 TEMPERATURE RISE OF THE UNEXPOSED SURFACE TO NOT MORE
 THAN 250 DEGREES F (120 DEGREES C) AFTER 15 MINUTES OF
 FIRE EXPOSURE, COMPLYING WITH THE STANDARD
 TIME-TEMPERATURE CURVE OF ASTM E 119. THE THERMAL
 BARRIER SHALL BE INSTALLED IN SUCH A MANNER THAT IT
 WILL REMAIN IN PLACE FOR 15 MINUTES BASED ON FM 4880,
 UL 1040, NFPA 286 OR UL 1715. COMBUSTIBLE CONCEALED
 SPACES SHALL COMPLY WITH SECTION 717 .
 2603.4.1 THERMAL BARRIER NOT REQUIRED.
 THE THERMAL BARRIER SPECIFIED IN SECTION 2603.4 IS NOT
 REQUIRED UNDER THE CONDITIONS SET FORTH IN SECTIONS
 2603.4.1.1 THROUGH 2603.4.1.13 .
 2603.4.1.2 COOLER AND FREEZER WALLS.
 FOAM PLASTIC INSTALLED IN A MAXIMUM THICKNESS OF 10
 INCHES (254 MM) IN COOLER AND FREEZER WALLS SHALL: 1.
 HAVE A FLAME SPREAD INDEX OF 25 OR LESS AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450, WHERE
 TESTED IN A MINIMUM 4 INCH (102 MM) THICKNESS.
 2.HAVE FLASH IGNITION AND SELF-IGNITION
 TEMPERATURES OF NOT LESS THAN 600 DEGREES F AND 800
 DEGREES F (316 DEGREES C AND 427 DEGREES C),
 RESPECTIVELY.
 3.HAVE A COVERING OF NOT LESS THAN 0.032-INCH (0.8
 MM) ALUMINUM OR CORROSION-RESISTANT STEEL HAVING A BASE
 METAL THICKNESS NOT LESS THAN 0.0160 INCH (0.4 MM) AT
 ANY POINT.
 4.BE PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM.
 WHERE THE COOLER OR FREEZER IS WITHIN A BUILDING, BOTH
 THE COOLER OR FREEZER AND THAT PART OF THE BUILDING IN
 WHICH IT IS LOCATED SHALL BE SPRINKLERED.
 WALK IN COOLERS
 2603.4.1.3 WALK -IN COOLERS .
 IN NONSPRINKLERED BUILDINGS, FOAM PLASTIC HAVING A
 THICKNESS THAT DOES NOT EXCEED 4 INCHES (102 MM) AND A
 MAXIMUM FLAME SPREAD INDEX OF 75 IS PERMITTED IN WALK
 -IN COOLERS OR FREEZER UNITS WHERE THE AGGREGATE FLOOR
 AREA DOES NOT EXCEED 400 SQUARE FEET (37 M 2 ) AND THE
 FOAM PLASTIC IS COVERED BY A METAL FACING NOT LESS THAN
 0.032-INCH-THICK (0.81 MM) ALUMINUM OR
 CORROSION-RESISTANT STEEL HAVING A MINIMUM BASE METAL
 THICKNESS OF 0.016 INCH (0.41 MM). A THICKNESS OF UP TO
 10 INCHES (254 MM) IS PERMITTED WHERE PROTECTED BY A
 THERMAL BARRIER.
 SHOW HOW WALK-IN COOLER COMPLIES. PROVIDE
 MANUFACTURER'S SPECIFICATIONS AND DETAILS.
  
 18) SUBMIT SITE PLANS SHOWING ACCESSIBLE PARKING,
 ACCESSIBLE ROUTE TO THE BUILDING ENTRANCE, RAMPS, CURB
 CUTS, ETC. AS REQUIRED BY FBC 11-4.1.3. THE PLAN WITH
 THIS INFORMATION IS REQUIRED TO BE SIGNED AND SEALED BY
 A FLORIDA LICENSED ARCHITECT OR ENGINEER. SEE FS 471
 AND 481.
  
 19) COMPLIED.
  
 20)COMPLIED.
  
 21) COMPLIED.
  
 22) COMPLIED.
  
 23) COMPLIED.
  
 24) COMPLIED.
  
 25) A SEPARATE PERMIT WILL BE REQUIRED FOR THE STAND
 ALONE CANOPY AT GAS PUMPS.
  
 26) COMPLIED.
  
 27) ADDITIONAL COMMENTS MAY RESULT WHEN THESE COMMENTS
 ARE ADDRESSED, DUE TO THE AMOUNT OF MISSING
 INFORMATION.
  
 28) SPECIFY THE WIDTH OF THE STRUCTURE ON THE PLANS.
 FBC 106.1* CITY AMENDMENTS
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-03-28 Cont ID  
Sent By rmcdouga Date 2007-03-28 Time 14:25 Rev Time 0.00
Received By rmcdouga Date 2007-03-28 Time 11:24 Sent To  
Notes
2007-03-28 14:24:55DENIED BY BUILDING
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2)A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) THE CODE THAT IS CURRENTLY IN EFFECT IS THE 2004
 FLORIDA BUILDING CODE. PLEASE CORRECT GENERAL NOTE #1
 ON SHEET A-1.
  
 4) THE WRONG EDITION OF ASCE 7 IS SPECIFIED UNDER
 DESIGN PARAMETERS ON SHEETS A2 AND A7. THE EDITION
 REFERENCED BY THE 2004 FBC IS ASCE 7-02. PLEASE
 CORRECT.
  
 5) FBC SECTION 1606.1.7 THAT WAS SPECIFIED UNDER DESIGN
 PARAMETERS ON SHEETS A2 AND A7 IS NO LONGER IN THE
 CODE. PLEASE CORRECT.
  
 6) SPECIFY THE OCCUPANCY TYPE. SEE FBC 302.1.
  
 7) PROVIDESURVEY/SITE PLANS INDICATING THE LOCATION
 OF THE STRUCTURE, DISTANCE TO PROPERTY LINES, DISTANCES
 TO OTHER STRUCTURES ON THE PROPERTY FOR DETERMINING
 FIRE SEPARATION DISTANCES. SEE FBC 702, 704.8 AND TABLE
 602.
  
 8)SUBMIT ENERGY CALCULATIONS FOR THE STRUCTURE AS
 REQUIRED BY FBC 13-4.
  
 9)SUBMIT PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS,
 DOORS, STOREFRONTS, MULLIONS, ROOFING MATERIAL, IMPACT
 PROTECTION PRODUCTS, ETC.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE.
  
 10)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 11) SPECIFY HOW IMPACT PROTECTION OF OPENINGS WILL BE
 PROVIDED AS REQUIRED BY FBC 1609.1.4.
  
 12) SUBMIT TRUSS DRAWINGS AND LAYOUT SIGNED, SEALED AND
 DATED BY THE TRUSS ENGINEER AND REVIEWED AND APPROVED
 BY THE DESIGNER OF RECORD OF THE STRUCTURE. FBC
 106.3.5* CITY AMENDMENTS. NOTE: THE UPLIFT AT HIP
 GIRDER TRUSSES MAY EXCEED 1500#.
  
 13) PROVIDE DIMENSIONS TO INDICATE THE LOCATIONS OF THE
 STEEL COLUMNS SHOWN IN DETAIL 2 ON A-3 ON THE
 FOUNDATION PLAN. SPECIFY THE ANCHOR TYPE, SIZE, EMBED
 DEPTH AND SIZE OF THE HOLES FOR THE ANCHORS FOR THE
 STEEL COLUMN BASE. SPECIFY THE WELD TYPE FOR THE COLUMN
 TO BASE ATTACHMENT. PROVIDE A DETAIL SPECIFYING THE
 COLUMN CAP FOR THE STEEL COLUMNS WITH FASTENERS, WELDS,
 ETC. INDICATED.
  
 14) SPECIFY THE LOCATION AND SIZE OF THE ATTIC ACCESS
 REQUIRED BY FBC 1209.2.
  
 15)WALL SECTION 1 ON A-4 SPECIFIES ASPHALT ROOF
 SHINGLES AND THE ELEVATIONS SHOW A METAL ROOF. PLEASE
 CORRECT.
  
 16) THE ROOF ZONE FIGURE FOR THE HIP ROOF ON A7 IS
 INCORRECT. THE OUTSIDE CORNER AREAS OF THE HIP ROOF ARE
 ZONE 3 . SEE FBC FIGURE 1609.6.2.2 (REVISED SHEETS).
  
 17)SHOW HOW WALK-IN COOLER COMPLIES WITH 2603.4
 THERMAL BARRIER. PROVIDE MANUFACTURER'S SPECIFICATIONS
 AND DETAILS.
 EXCEPT AS PROVIDED FOR IN SECTIONS 2603.4.1 AND 2603.8
 , FOAM PLASTIC SHALL BE SEPARATED FROM THE INTERIOR OF
 A BUILDING BY AN APPROVED THERMAL BARRIER OF 0.5-INCH
 (12.7 MM) GYPSUM WALLBOARD OR EQUIVALENT THERMAL
 BARRIER MATERIAL THAT WILL LIMIT THE AVERAGE
 TEMPERATURE RISE OF THE UNEXPOSED SURFACE TO NOT MORE
 THAN 250 DEGREES F (120 DEGREES C) AFTER 15 MINUTES OF
 FIRE EXPOSURE, COMPLYING WITH THE STANDARD
 TIME-TEMPERATURE CURVE OF ASTM E 119. THE THERMAL
 BARRIER SHALL BE INSTALLED IN SUCH A MANNER THAT IT
 WILL REMAIN IN PLACE FOR 15 MINUTES BASED ON FM 4880,
 UL 1040, NFPA 286 OR UL 1715. COMBUSTIBLE CONCEALED
 SPACES SHALL COMPLY WITH SECTION 717 .
 2603.4.1 THERMAL BARRIER NOT REQUIRED.
 THE THERMAL BARRIER SPECIFIED IN SECTION 2603.4 IS NOT
 REQUIRED UNDER THE CONDITIONS SET FORTH IN SECTIONS
 2603.4.1.1 THROUGH 2603.4.1.13 .
 2603.4.1.2 COOLER AND FREEZER WALLS.
 FOAM PLASTIC INSTALLED IN A MAXIMUM THICKNESS OF 10
 INCHES (254 MM) IN COOLER AND FREEZER WALLS SHALL: 1.
 HAVE A FLAME SPREAD INDEX OF 25 OR LESS AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450, WHERE
 TESTED IN A MINIMUM 4 INCH (102 MM) THICKNESS.
 2.HAVE FLASH IGNITION AND SELF-IGNITION
 TEMPERATURES OF NOT LESS THAN 600 DEGREES F AND 800
 DEGREES F (316 DEGREES C AND 427 DEGREES C),
 RESPECTIVELY.
 3.HAVE A COVERING OF NOT LESS THAN 0.032-INCH (0.8
 MM) ALUMINUM OR CORROSION-RESISTANT STEEL HAVING A BASE
 METAL THICKNESS NOT LESS THAN 0.0160 INCH (0.4 MM) AT
 ANY POINT.
 4.BE PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM.
 WHERE THE COOLER OR FREEZER IS WITHIN A BUILDING, BOTH
 THE COOLER OR FREEZER AND THAT PART OF THE BUILDING IN
 WHICH IT IS LOCATED SHALL BE SPRINKLERED.
 WALK IN COOLERS
 2603.4.1.3 WALK -IN COOLERS .
 IN NONSPRINKLERED BUILDINGS, FOAM PLASTIC HAVING A
 THICKNESS THAT DOES NOT EXCEED 4 INCHES (102 MM) AND A
 MAXIMUM FLAME SPREAD INDEX OF 75 IS PERMITTED IN WALK
 -IN COOLERS OR FREEZER UNITS WHERE THE AGGREGATE FLOOR
 AREA DOES NOT EXCEED 400 SQUARE FEET (37 M 2 ) AND THE
 FOAM PLASTIC IS COVERED BY A METAL FACING NOT LESS THAN
 0.032-INCH-THICK (0.81 MM) ALUMINUM OR
 CORROSION-RESISTANT STEEL HAVING A MINIMUM BASE METAL
 THICKNESS OF 0.016 INCH (0.41 MM). A THICKNESS OF UP TO
 10 INCHES (254 MM) IS PERMITTED WHERE PROTECTED BY A
 THERMAL BARRIER.
 SHOW HOW WALK-IN COOLER COMPLIES. PROVIDE
 MANUFACTURER'S SPECIFICATIONS AND DETAILS.
  
 18) SUBMIT SITE PLANS SHOWING ACCESSIBLE PARKING,
 ACCESSIBLE ROUTE TO THE BUILDING ENTRANCE, RAMPS, CURB
 CUTS, ETC. AS REQUIRED BY FBC 11-4.1.3.
  
 19) ALL DOORS ON THE ACCESSIBLE ROUTESARE REQUIRED TO
 HAVE ADA COMPLIANT HARDWARE. SEE FBC 11-4.13.9.
  
 20)SHOW THE REQUIRED CLEAR FLOOR SPACE AT THE WATER
 CLOSET AND LAVATORY SPECIFY DIMENSIONS. SEE FBC
 11-4.16.2 AND 11-4.19.3.
  
 21) PROVIDE AN ACCESSIBLE COUNTER AS REQUIRED BY FBC
 11-7.2.
  
 22) DOOR 03DOES NOT HAVE THEMANEUVERING CLEARANCES
 REQUIRED BY FBC 11-4.13.6. A MINIMUM OF 18" IS REQUIRED
 ON THE PULL SIDE AT THE LATCH OF SIDE SWING DOORS.
  
 23) FBC 11-4.16.3 REQUIRES THE HEIGHT OF WATER CLOSETS
 TO BE 17" TO 19" MEASURED TO TOP OF THE TOILET SEAT.
 PLEASE CORRECT DETAIL 5 ON A-4.
  
 24) FBC 11-4.16.4 REQUIRES THE GRAB BAR BEHIND THE
 WATER CLOSET TO BE 36" MINIMUM.
  
 25) A SEPARATE PERMIT WILL BE REQUIRED FOR THE STAND
 ALONE CANOPY AT GAS PUMPS.
  
 26) THE FIRM'S LICENSE NUMBER IS REQUIRED TO BE IN THE
 TITLE BLOCK ON EACH SHEET OF THE PLANS. SEE FS 481 AND
 FAC 61G1-16.004.
  
 27) ADDITIONAL COMMENTS MAY RESULT WHEN THESE COMMENTS
 ARE ADDRESSED, DUE TO THE AMOUNT OF MISSING
 INFORMATION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-11-15 Cont ID  
Sent By rmcdouga Date 2006-11-15 Time 09:22 Rev Time 0.00
Received By rmcdouga Date 2006-11-15 Time 07:03 Sent To  
Notes
2006-11-15 13:43:43DENIED BY BUILDING
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT MUST
 BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) THE CODE THAT IS CURRENTLY IN EFFECT IS THE 2004
 FLORIDA BUILDING CODE. PLEASE CORRECT GENERAL NOTE #1
 ON SHEET A-1.
  
 4) SPECIFY THE CONSTRUCTION TYPE BASED ON THE 2004 FBC
 DESIGNATIONS. SPECIFY A OR B. SEE FBC TABLE 601.
  
 5) SPECIFY THE OCCUPANCY TYPE. SEE FBC 302.1.
  
 6) PROVIDE SURVEY/SITE PLANS INDICATING THE LOCATION OF
 THE STRUCTURE, DISTANCE TO PROPERTY LINES, DISTANCES TO
 OTHER STRUCTURES ON THE PROPERTY FOR DETERMINING FIRE
 SEPARATION DISTANCES. SEE FBC 702, 704.8 AND TABLE 602.
  
 7) PLEASE CLARIFY THE SCOPE OF WORK. THE APPLICATION
 INDICATES THAT THIS IS A REMODEL OF AN EXISTING
 BUILDING AND THE PLANS APPEAR TO BE FOR NEW
 CONSTRUCTION.
  
 8) IF THIS IS A REMODEL, SUBMIT A DEMO PLAN FOR THE
 EXISTING STRUCTURE.
  
 9) IF REMODEL, SPECIFY THE LEVEL OF ALTERATION FOR THE
 WORK AS SPECIFIED IN THE 2004 FBC EXISTING BUILDING
 CODE.
  
 10) SUBMIT ENERGY CALCULATIONS FOR THE STRUCTURE AS
 REQUIRED BY FBC 13-4.
  
 11) SPECIFY THE DESIGN DATA FOR THE STRUCTURE REQUIRED
 BY FBC 1603.1.4.
  
 12) SUBMIT PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS,
 DOORS, STOREFRONTS, MULLIONS, ROOFING MATERIAL, IMPACT
 PROTECTION PRODUCTS, ETC.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE.
  
 13) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 14) SPECIFY HOW IMPACT PROTECTION OF OPENINGS WILL BE
 PROVIDED AS REQUIRED BY FBC 1609.1.4.
  
 15) SUBMIT TRUSS DRAWINGS AND LAYOUT SIGNED, SEALED AND
 DATED BY THE TRUSS ENGINEER AND REVIEWED AND APPROVED
 BY THE DESIGNER OF RECORD OF THE STRUCTURE. FBC
 106.3.5* CITY AMENDMENTS. NOTE: THE UPLIFT AT HIP
 GIRDER TRUSSES MAY EXCEED 1500#.
  
 16) INDICATE WHERE ON THE FOUNDATION PLAN THE STEEL
 COLUMN IN DETAIL 2 ON A-3 IS LOCATED.
  
 17) SPECIFY THE LOCATION AND SIZE OF THE ATTIC ACCESS
 REQUIRED BY FBC 1209.2.
  
 18) WALL SECTION 1 ON A-4 SPECIFIES ASPHALT ROOF
 SHINGLES AND THE ELEVATIONS SHOW A METAL ROOF. PLEASE
 CORRECT.
  
 19) 2603.4 THERMAL BARRIER.
 EXCEPT AS PROVIDED FOR IN SECTIONS 2603.4.1 AND 2603.8
 , FOAM PLASTIC SHALL BE SEPARATED FROM THE INTERIOR OF
 A BUILDING BY AN APPROVED THERMAL BARRIER OF 0.5-INCH
 (12.7 MM) GYPSUM WALLBOARD OR EQUIVALENT THERMAL
 BARRIER MATERIAL THAT WILL LIMIT THE AVERAGE
 TEMPERATURE RISE OF THE UNEXPOSED SURFACE TO NOT MORE
 THAN 250?F (120?C) AFTER 15 MINUTES OF FIRE EXPOSURE,
 COMPLYING WITH THE STANDARD TIME-TEMPERATURE CURVE OF
 ASTM E 119. THE THERMAL BARRIER SHALL BE INSTALLED IN
 SUCH A MANNER THAT IT WILL REMAIN IN PLACE FOR 15
 MINUTES BASED ON FM 4880, UL 1040, NFPA 286 OR UL 1715.
 COMBUSTIBLE CONCEALED SPACES SHALL COMPLY WITH SECTION
 717 .
 2603.4.1 THERMAL BARRIER NOT REQUIRED.
 THE THERMAL BARRIER SPECIFIED IN SECTION 2603.4 IS NOT
 REQUIRED UNDER THE CONDITIONS SET FORTH IN SECTIONS
 2603.4.1.1 THROUGH 2603.4.1.13 .
 2603.4.1.2 COOLER AND FREEZER WALLS.
 FOAM PLASTIC INSTALLED IN A MAXIMUM THICKNESS OF 10
 INCHES (254 MM) IN COOLER AND FREEZER WALLS SHALL: 1.
 HAVE A FLAME SPREAD INDEX OF 25 OR LESS AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450, WHERE
 TESTED IN A MINIMUM 4 INCH (102 MM) THICKNESS.
 2. HAVE FLASH IGNITION AND SELF-IGNITION TEMPERATURES
 OF NOT LESS THAN 600?F AND 800?F (316?C AND 427?C),
 RESPECTIVELY.
 3. HAVE A COVERING OF NOT LESS THAN 0.032-INCH (0.8 MM)
 ALUMINUM OR CORROSION-RESISTANT STEEL HAVING A BASE
 METAL THICKNESS NOT LESS THAN 0.0160 INCH (0.4 MM) AT
 ANY POINT.
 4. BE PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM. WHERE
 THE COOLER OR FREEZER IS WITHIN A BUILDING, BOTH THE
 COOLER OR FREEZER AND THAT PART OF THE BUILDING IN
 WHICH IT IS LOCATED SHALL BE SPRINKLERED.
 WALK IN COOLERS
 2603.4.1.3 WALK -IN COOLERS .
 IN NONSPRINKLERED BUILDINGS, FOAM PLASTIC HAVING A
 THICKNESS THAT DOES NOT EXCEED 4 INCHES (102 MM) AND A
 MAXIMUM FLAME SPREAD INDEX OF 75 IS PERMITTED IN WALK
 -IN COOLERS OR FREEZER UNITS WHERE THE AGGREGATE FLOOR
 AREA DOES NOT EXCEED 400 SQUARE FEET (37 M 2 ) AND THE
 FOAM PLASTIC IS COVERED BY A METAL FACING NOT LESS THAN
 0.032-INCH-THICK (0.81 MM) ALUMINUM OR
 CORROSION-RESISTANT STEEL HAVING A MINIMUM BASE METAL
 THICKNESS OF 0.016 INCH (0.41 MM). A THICKNESS OF UP TO
 10 INCHES (254 MM) IS PERMITTED WHERE PROTECTED BY A
 THERMAL BARRIER.
 SHOW HOW WALK-IN COOLER COMPLIES. PROVIDE
 MANUFACTURER'S SPECIFICATIONS AND DETAILS.
  
 20) SUBMIT SITE PLANS SHOWING ACCESSIBLE PARKING,
 ACCESSIBLE ROUTE TO THE BUILDING ENTRANCE, RAMPS, CURB
 CUTS, ETC. AS REQUIRED BY FBC 11-4.1.3.
  
 21) ALL DOORS ON THE ACCESSIBLE ROUTES ARE REQUIRED TO
 HAVE ADA COMPLIANT HARDWARE. SEE FBC 11-4.13.9.
  
 22) SHOW THE REQUIRED CLEAR FLOOR SPACE AT THE WATER
 CLOSET AND LAVATORY SPECIFY DIMENSIONS. SEE FBC
 11-4.16.2 AND 11-4.19.3.
  
 23) PROVIDE AN ACCESSIBLE COUNTER AS REQUIRED BY FBC
 11-7.2.
  
 24) DOORS 03 AND 04 DO NOT HAVE THE MANEUVERING
 CLEARANCES REQUIRED BY FBC 11-4.13.6. A MINIMUM OF 18"
 IS REQUIRED ON THE PULL SIDE AT THE LATCH OF SIDE SWING
 DOORS.
  
 25) FBC 11-4.16.3 REQUIRES THE HEIGHT OF WATER CLOSETS
 TO BE 17" TO 19" MEASURED TO TOP OF THE TOILET SEAT.
 PLEASE CORRECT DETAIL 5 ON A-4.
  
 26) FBC 11-4.16.4 REQUIRES THE GRAB BAR BEHIND THE
 WATER CLOSET TO BE 36" MINIMUM.
  
 27) A SEPARATE PERMIT WILL BE REQUIRED FOR THE STAND
 ALONE CANOPY AT GAS PUMPS.
  
 28) ADDITIONAL COMMENTS MAY RESULT WHEN THESE COMMENTS
 ARE ADDRESSED, DUE TO THE AMOUNT OF MISSING
 INFORMATION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2010-09-13 Cont ID  
Sent By dwise Date 2010-09-13 Time 15:47 Rev Time 0.00
Received By dwise Date 2010-09-13 Time 15:46 Sent To  
Notes
2010-09-13 15:47:56APPROVED BY DEWEY PALMER ON 12/9/2009 PENDING LICENSED
 CONTRACTOR.DBW

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2009-12-09 Cont ID  
Sent By dpalmer Date 2009-12-09 Time 14:50 Rev Time 0.00
Received By dpalmer Date 2009-12-09 Time 14:50 Sent To  
Notes
2009-12-09 14:51:17STILL IN TEMPORARY FAILED STATUS UNTIL LICENSED
 CONTRACTOR IS SIGNED ON PERMIT APPLICATION.
 ELECTRICAL PLANS ALREADY STAMPED ON PREVIOUS REVIEW.

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2009-12-09 Cont ID  
Sent By dpalmer Date 2009-09-30 Time 14:33 Rev Time 0.00
Received By dpalmer Date 2009-09-30 Time 14:33 Sent To  
Notes
2009-12-09 14:34:02CONTRACTOR NOT YET SIGNED ON.
 PLANS STAMPED.

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2009-08-11 Cont ID  
Sent By dpalmer Date 2009-08-11 Time 10:04 Rev Time 0.00
Received By dpalmer Date 2009-08-11 Time 10:04 Sent To  
Notes
2009-08-11 10:04:15 
 ** DENIED REVIEW **
  
 1) NOTE: PERMIT HAS NOT YET BEEN APPLIED FOR BY
 LICENSED CONTRACTOR.
  
 2) NOTE: THE SUBMITTED CALCULATIONS NEED TO INCLUDE ALL
 EXTERIOR LIGHTING PER 13-415.AB.5, 13-415.AB.2.2. THIS
 WAS A SPECIFIC NOTE ON THE PREVIOUS REVIEW YET THE SAME
 ITEMS NEED TO BE ADDRESSED.
  
 ** AS PERMIT HAS BEEN APPLIED UNDER PERMIT APPLICATION
 AS *TBD* TO BE DETERMINED*, IF CALCULATIONS ARE
 SUBMITTED BACK AGAIN WITH THE SAME ITEMS FS
 553.80(2)(B)
  
 3) NOTE: PLANS ARE STILL SHOWING SOME LOCATIONS IN
 WHICH THERE ARE NOTES FOR 2008 GLITCHES TO THE 2007
 FBC. THERE ARE ONLY 2009 SUPPLEMENTS TO THE 2007 FBC.
  
 4) NOTE: PLEASE SUBMIT THE SPECS/MANUFACTURES CUT
 SHEETS ON MANUAL TRANSFER SWITCH. COULD NOT LOCATE ON
 THE SPECS SUBMITTED FOR THE DOUBLE THROW SWITCH AS THIS
 BEING LISTED AS A MANUAL TRANSFER SWITCH? THIS IS
 LEGALLY REQUIRED TRANSFER SWITCH PER STATUTES. IF THIS
 EQUIPMENT IS LISTED AS SUCH PLEASE PROVIDE.
 110.3,90.7,701.7, FS 526.143
  
 ** PLANS ARE NO LONGER RELEASED PER BUILDING DIRECTOR.
 A TIME WILL NEED TO BE SET UP TO BRING IN NEW REVISIONS
 AND CHANGE OUT SHEETS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2009-05-29 Cont ID  
Sent By dpalmer Date 2009-05-29 Time 08:28 Rev Time 0.00
Received By dpalmer Date 2009-05-29 Time 08:28 Sent To  
Notes
2009-05-29 08:28:49**DENIED 4TH REVIEW **
  
  
  
 ** THIS IS THE FIRST REVIEW UNDER PERMIT APPLICATION
 WHICH WAS ONLY MADE ON MAY 13, 2009
  
 ** PLANS ARE ALSO UNDER A COMPLETELY NEW DESIGN TEAM.
 ** SOME COMMENTS FROM PREVIOUS REVIEWS ALONG NOW WITH
 SOME NEW COMMENTS BASED ON NEW PLANS AND DOCUMENTS
 SUBMITTED.
 PLEASE SEE NOTES BELOW.
  
 1) NOTE: PLANS SUBMITTED AFTER MARCH 1ST, 2009 SHALL BE
 UNDER NEW CODES. PLANS STATE THE NEW 2007 FBC HOWEVER
 SOME REFERENCE 2008 GLITCHES AND SOME AREAS REFERENCE
 20007 GLITCHES. BASED ON THE ADOPTED CODES AND GLITCHES
 AS OF MARCH 1ST, 2009 THE CODE IS AS FOLLOWS.
 2007 FBC WITH 2009 GLITCHES.
 2005 NFPA-70 (ALREADY DONE)
 2006 NFPA-101
 2006 NFPA-1
  
 2) NOTE: PLEASE BE SURE THE SUBMITTED ENERGY
 CALCULATIONS COORDINATES WITH THE SUBMITTED PLANS.
 PREVIOUS REVIEWS STATED COMMENTS TO OTHER DESIGN TEAMS
 TO BE SURE THIS IS DONE.
 13-415.AB.5
  
 ** ONE EXAMPLE FOR METHOD *A* WHICH IS FOR *WHOLE*
 BUILDING COMPLIANCE IS THE EXTERIOR LIGHTING. THE INPUT
 DATA REPORT ONLY INCLUDES 7-32 WATT FIXTURES. HOW IS
 THIS POSSIBLE WHEN THE PLANS CLEARLY INDICATE OTHER
 FIXTURES SUCH AS CANOPY AND NEW SITE LIGHTING POLE
 LIGHTS WITH WATTAGES EXCEEDING 250W.
 PLEASE INCLUDE *ALL* FIXTURES ON PLANS AND LOCATION.
  
 IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE BE
 SURE TO CALL AND GO OVER WITH THIS PLANS EXAMINER.
  
 3) NOTE: PLEASE SEE 422.13 WAS STORAGE TYPE WATER
 HEATERS IN THE 2005 NEC ARE CONSIDERED CONTINUOUS LOADS
 WITH RESPECT TO LOAD CALCULATIONS FOR FEEDERS AND
 SERVICES.
 THIS WAS A REVISION FROM THE PREVIOUS 2002 CODE WHICH
 ONLY REQUIRED THE SIZING OF BRANCH CIRCUIT AND OCP TO
 BE SET AT 125%.
 PLEASE SEE COMMENTARY IN 2005 NEC HANDBOOK.
 ANY QUESTIONS PLEASE CALL.
  
 4) NOTE: PLEASE INDICATE LOADS FOR SHOW WINDOW
 RECEPTACLES PER 220.14G FOR BRANCH CIRCUIT SIZING AND
 220.43A FOR LOAD WHICH IS REQUIRED TO BE USED FOR
 SIZING SERVICE.
  
 5) NOTE: PLEASE SEE 600.5 WHICH REQUIRES THE SIGN
 CIRCUIT TO BE DEDICATED. THIS CIRCUIT IS NOT PERMITTED
 TO HAVE ANY OTHER ITEMS SUCH AS SOFFITS LIGHTS ETC ON
 THE SAME CIRCUIT.
 THE MINIMUM VA TO BE FIGURED FOR SIZING OF THIS CIRCUIT
 SHALL BE 1200VA. PLEASE ADJUST PLANS AND CALCULATIONS.
  
 6) NOTE: RISER SHOWS AN *EQUIPMENT GROUNDING CONDUCTOR*
 BEFORE THE FIRST MEANS OF DISCONNECT WHICH IS NOT
 PERMITTED. PLEASE SEE 250.6, 250.24. THE CODE REQUIRES
 THE NEUTRAL TO BE BONDED AT THE FIRST MEANS OF
 DISCONNECT. IF THERE IS AN EQUIPMENT GROUNDING
 CONDUCTOR INSTALLED FROM THE METER TO THIS FIRST MEANS
 OF DISCONNECT THEN THIS WOULD PARALLEL THE NEUTRAL THUS
 CREATING OBJECTIONABLE CURRENTS.
  
 7) NOTE: PLEASE COMPLETE CIRCUITS ON PLANS. ONE EXAMPLE
 IS EQUIPMENT IDENTIFIED AS SOUP COUNTER. IS THIS
 EQUIPMENT? OR IS THE SOUP WARMER THE ONLY APPLIANCE?
 PLEASE ALSO SEE TOILET HAND DRYER WHICH INDICATES
 CIRCUITS *B 19-20*. THIS PLACES CONDUCTORS ON THE SAME
 PHASE WHICH WILL NOT WORK.
 PER THE PANEL SCHEDULE THIS SHOULD BE 19-21.
 PLEASE BE SURE TO COORDINATE ALL.
 408.4, 310.16 ETC
 FBC 106.1.1, 106.5
  
 8) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE PROPOSED MANUAL TRANSFER SWITCH AS
 STATED ON PLANS. 701.7, 110.3, 90.7
  
 9) NOTE: PLEASE SEE 210.8B4 AS *ALL* OUTSIDE
 RECEPTACLES UNDER THE CHANGES IN THE 2005 NEC SHALL BE
 GFI PROTECTED. THIS INCLUDES ANY DEDICATED CIRCUITS FOR
 ITEMS SUCH AS ICE MACHINES ETC.
  
 10) NOTE: PLEASE INDICATE THE TYPE OF TIME CLOCK TO
 MEET 13-415.AB.1.4. THIS MUST BE ASTRONOMICAL WITH A
 MINIMUM OF 10HR PROGRAMMING BACK UP.
  
 11) NOTE: PLEASE SHOW ALL CLASS AND DIVISION LOCATIONS
 PER NEC 500,514.3.(B)(1) PLEASE ALSO SEE (2) UNDER SAME
 SECTION FOR ANY PROPOSED NG, OR LP.
  
 12) NOTE: PLEASE SEE 514.11 (A)(B)(C) ETC.
  
 13) NOTE: PLEASE INCLUDE ALL WIRING AND DETAILS FOR THE
 REST OF NEC 514. 514.4,514.7,514.9,514.16.
  
 14) NOTE: PLEASE SEE 225.31- 225.39 FOR DISCONNECTING
 MEANS FOR SEPARATE STRUCTURES.
  
  
 15) NOTE: PLEASE VERIFY SERVICE RISER. SERVICE IS SHOWN
 AS 600AMPS WITH A *600* AMP METER CAN. IS THIS NOT A CT
 TYPE OF INSTALLATION ? PLEASE CHECK WITH FPL AND
 MANUFACTURE. SEE FPL SERVICE STANDARDS.
  
 16) NOTE: PLEASE COORDINATE PLANS. THE PLANS SHOW AND
 NOTE THE SERVICE TO BE AN OVERHEAD TYPE YET RISER SHOWS
 THIS AS UNDERGROUND. WHICH ONE WILL IT BE?
 REVIEW CAN NOT BE DONE ON AN OVERHEAD SERVICE AS IT IS
 NOT SHOWN ON RISER.
 230,310.16 ETC
 FBC 106.1.2 FOR ADDITIONAL INFORMATION AND CLARITY OF
 PLANS.
  
  
  
  
  
  
 * IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-10-18 Cont ID  
Sent By dpalmer Date 2007-10-18 Time 14:50 Rev Time 0.00
Received By dpalmer Date 2007-10-18 Time 10:26 Sent To  
Notes
2007-10-18 15:41:22*** DENIED 3RD REVIEW *****
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW NOTES ARE
 STILL IN NEED OF ADDRESSING. THERE ARE ALSO SOME NEW
 COMMENTS ON SHEETS OTHER THAN THE ELECTRICAL BASED ON
 CHANGES TO PLANS.
  
 1) NOTE: PLEASE SEE AS STATED IN THE TWO PREVIOUS
 REVIEWS. THE PLANS ARE STILL ONLY SUBMITTED FOR *PLAN
 REVIEW *.
  
 ** PLEASE KNOW THIS IS STILL UNDER "PLAN REVIEW" ONLY.
 NO APPLICATION FOR PERMIT HAS YET BEEN MADE TO DATE.
 PLEASE KNOW THAT EVEN ONCE PLANS ARE CODE COMPLIANT,
 REVIEWS WILL STILL REMAIN IN *FAILED* STATUES UNTIL
 PERMIT APPLICATION IS MADE AND REVIEW OF LICENSING,
 APPLIED VALUES ETC FOR COMPLETE SCOPE OF WORK CAN BE
 DONE.
  
 2) NOTE: PLEASE SEE THE ARCHITECTURAL PLANS AND
 LANDSCAPE PLANS, ETC STILL NEED COORDINATION WITH ALL
 OTHER SHEETS AND TRADES.
 PLEASE SEE FOR EXAMPLE THE ELECTRICAL LIGHTING WHICH IS
 SHOWN ON LP DOES NOT CORRELATE WITH SITE PLANS.
 PLEASE SEE FOR EXAMPLE THE DETAILS OF WALKS/ACCESS ETC
 ON SITE PLAN DETAILS DO NOT MATCH WITH THE SITE PLAN
 ITSELF. PLEASE SEE COMMENTS FROM OTHER TRADES SUCH AS
 ZONING AS ANY CHANGES ON THESE SHEETS WILL HAVE AN
 AFFECT ON ELECTRICAL PLANS ALSO.
 PLEASE CORRELATE ELECTRICAL PLANS WITH SITE/LANDSCAPE
 PLANS AS THERE ARE LIGHTING FIXTURES FOR SITE ETC SHOWN
 ON LP WHICH ARE NO WHERE ON ELECTRICAL SHEETS.
 NO WIND LOAD INFORMATION, NO CIRCUITING, NO LOADS, ETC
 PLEASE CORRELATE ALL AND COMPLETE.
 FBC 106.1, 106.1.2, 106.3.5.1.2
 NEC 240, 310.16, 408.4
  
 3) NOTE: PLEASE SEE SEVERAL OF THE LANDSCAPE SHEETS ARE
 NOT SIGNED, DATED OR SEALED AS REQUIRED PER FS 481.321
 PLEASE ALSO SEE MISSING INFORMATION ON TITLE BLOCKS FOR
 PRINTED NAME AND LICENSE NUMBER FOR SAID DESIGNER.
  
 4) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT FOR
 THE ATS AND GENERATOR AS REQUESTED ON THE PREVIOUS TWO
 REVIEWS.
 THE SUB BASE FUEL TANK SPECS ARE ALSO REQUIRED AND WILL
 BE REVIEWED BY OTHER
 110.3, 90.7.
  
 5) NOTE: PLEASE SUBMIT THE FUEL CONSUMPTION ON THE
 GENERATOR AS PREVIOUSLY REQUESTED FOR HB 7121, HB 319,
 AND HB 965. CAN NOT LOCATE ANYWHERE ON PLANS THAT THE
 ON-SITE FUEL WILL SUPPLY THE REQUIRED 72HRS OF FUEL
 UNDER LOAD CONSUMPTION.
  
 6) NOTE: ONCE AGAIN THE GENERATOR IS STILL BEING SHOWN
 FOR 434AMPS, YET THIS CAN NOT BE CONFIRMED. THIS IS
 125KW AT 208V 3-PHASE. IF THIS IS 434AMPS, HOW IS IT
 THAT THE GENERATOR HAS A 400AMP BREAKER?
 PLEASE SEE COMMENT #4 ABOVE.
  
 7) NOTE: PLEASE SEE MISSING LIGHTING POWER
 DENSITIES/CALCULATIONS AS REQUIRED PER 13-415.2.
 PLEASE SEE EXTERIOR LIGHTING CALCULATIONS COULD STILL
 NOT BE LOCATED ON PLAN/ENERGY CALCULATIONS ETC.
 13-415.2.ABC.1.3
 ** INTERIOR IS ON PLANS AND IS OK.
 PLEASE SEE THAT NO ENERGY CALCULATIONS WERE SUBMITTED
 FOR REVIEW.?
 PLEASE SEE 13-415.1.AB.1.1
 PLEASE SEE 13-103.1.1.1 AS THE DESIGNERS OF RECORD
 SHALL SIGN, DATE AND SEAL SAID ENERGY CALCULATIONS AND
 OTHER INFORMATION AS REQUIRED UNDER CHAPTER 13. PLEASE
 BE SURE TO SEE THE 2006 REVISIONS TO THE 2004 FBC AS
 CHANGES WERE MADE.
  
 ** PLEASE KNOW AS THERE IS SOME INFORMATION STILL NOT
 YET SUBMITTED FOR REVIEW, COMPLETE REVIEW CAN NOT BE
 DONE.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-03-24 Cont ID  
Sent By dpalmer Date 2007-03-24 Time 14:18 Rev Time 0.00
Received By dpalmer Date 2007-03-24 Time 12:06 Sent To  
Notes
2007-03-24 14:20:49 
  
 ****** UNSAT 2ND REVIEW******
  
 ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1
 IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE
 ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY
 THE CITY OF WEST PALM BEACH.
  
  
 ** PLEASE KNOW THIS IS STILL UNDER "PLAN REVIEW" ONLY.
 NO APPLICATION FOR PERMIT HAS YET BEEN MADE TO DATE.
 PLEASE KNOW THAT EVEN ONCE PLANS ARE CODE COMPLIANT,
 REVIEWS WILL STILL REMAIN IN *FAILED* STATUES UNTIL
 PERMIT APPLICATION IS MADE AND REVIEW OF LICENSING,
 APPLIED VALUES ETC FOR COMPLETE SCOPE OF WORK CAN BE
 DONE.
  
 ** PLEASE SEE MANY ITEMS FROM PREVIOUS REVIEW NOTES
 WERE NOT DONE OR SUBMITTED.
 A COMPLETE REVIEW FOR CODE COMPLIANCE CAN NOT BE DONE
 AT THIS TIME AS THESE ITEMS ARE NOT SHOWN OR
 SUBMITTED.
 THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW NOT
 YET MADE.
  
  
 1) NOTE: PLEASE BE SURE THE PLANS, ELECTRICAL AND
 ARCHITECTURAL CONTAIN ALL THE REQUIRED CODES RELEVANT
 TO DESIGN.
  
 PLEASE KNOW THAT DEPENDING ON PERMIT APPLICATION IS
 FINALLY MADE, THIS WILL DETERMINE THE CODES IN WHICH
 THE PLANS ARE DESIGNED UNDER.
 PLEASE SEE THE ARCHITECTURAL PLANS INDICATE THE 2001
 FBC????
 PLEASE INCLUDE THE FOLLOWING AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS ( FOR ALL TRADES)
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72( IF APPLICABLE)
 2002 NFPA-110
 2003 NFPA-30A
 2002 NFPA-37
  
 2) NOTE: PLEASE SEE THE ARCHITECTURAL PLANS AND
 LANDSCAPE PLANS ARE MISSING ALL OF THE ELECTRICAL ,
 MECHANICAL AND GENERATOR EQUIPMENT FROM PLANS SHOWING
 ALL SET BACKS AND DISTANCES FROM BUILDING, PROPERTY
 LINES ETC.
 PLEASE KNOW THAT BASED ON THE ELECTRICAL PLANS SHOWING
 SOME OF THIS AND COORDINATION WITH THE ONLY *SITE*
 LAYOUT PROVIDED ON THE LANDSCAPE PLANS, THE GENERATOR
 DOES NOT APPEAR IT CAN BE LOCATED IN THE REAR OF
 BUILDING.
 PLEASE ALSO SEE THE MINIMUM REQUIREMENTS FOR ZONING
 SETBACKS AND PERMITTED DISTANCES FROM BUILDING AND
 PROPERTY LINES.
 PLEASE SEE THE MINIMUM DISTANCES/CLEARANCES FOR THE
 GENERATOR FROM BUILDING AND PROPERTY LINE WILL PLACE
 THIS UNIT TOO CLOSE TO BUILDING AND PROPERTY. A NEW
 LOCATION MAY BE REQUIRED.
 PLEASE SEE THE MECHANICAL COMMENTS, BUILDING COMMENTS.
  
 MORE INFORMATION ON ALL WILL BE REQUIRED. PLEASE SEE
 COMMENTS FOR GENERATOR.
 FBC 106.1.2
  
 3) NOTE: PLEASE SEE THE SEAL BEING USED BY THE
 LANDSCAPE ARCHITECT IS NOT OF SUFFICIENT SIZE. PLEASE
 SEE THE FAC 61G1-16.002
 61G1-16.002 DESCRIPTION OF SEAL.
 (1) THE SEAL SHALL CONTAIN THE NAME OF ONLY ONE
 ARCHITECT OR INTERIOR DESIGNER AND THE REGISTRATION
 NUMBER; THE SEAL OF THE ARCHITECT SHALL BE CIRCULAR,
 AND THE SEAL OF THE INTERIOR DESIGNER SHALL BE
 HEXAGONAL. BOTH SEALS SHALL BE AN IMPRESSION-TYPE METAL
 SEAL, APPROXIMATELY 2" IN DIAMETER WITH TWO CIRCULAR
 LINES BETWEEN WHICH LINES SHALL APPEAR, AT THE TOP, THE
 WORDS "STATE OF FLORIDA" AND AT THE BOTTOM THE WORDS
 "REGISTERED ARCHITECT" OR "LICENSED INTERIOR DESIGNER,"
 WHICHEVER IS APPLICABLE.
 (2) ANY INDIVIDUAL WHO IS BOTH A REGISTERED ARCHITECT
 AND A LICENSED INTERIOR DESIGNER MUST USE A SEAL WHICH
 CONTAINS BOTH THE ARCHITECT AND INTERIOR DESIGN
 REGISTRATION NUMBERS, IN SUCH A MANNER:
  
 4) NOTE: PLEASE SEE THE MISSING INFORMATION ON TITLE
 BLOCKS PER 61G1-16.004. PLEASE SEE MISSING THE PRINTED
 NAME, PRINTED LICENSE NUMBER AND MISSING FIRM LICENSE
 NUMBER. (ALSO KNOWN AS THE CERTIFICATE OF AUTHORIZATION
 NUMBER.
 PLEASE SEE FS 481.219
  
 5) NOTE: PLEASE SEE MISSING LIGHTING POWER
 DENSITIES/CALCULATIONS AS REQUIRED PER 13-415.2. A NOTE
 ON PLANS WHICH MENTIONS THE DESIGN MEETS THIS SECTIONS
 DOES NOT ALLEVIATE THE REQUIRED INFORMATION TO BE SHOWN
 ON RECORD SETS OF PLANS AS REQUIRED PER THE SAME
 SECTION OF THE FBC CHAPTER 13.
 PLEASE SEE THAT NO ENERGY CALCULATIONS WERE SUBMITTED
 FOR REVIEW.?
 PLEASE SEE 13-415.1.AB.1.1
 PLEASE SEE 13-103.1.1.1 AS THE DESIGNERS OF RECORD
 SHALL SIGN, DATE AND SEAL SAID ENERGY CALCULATIONS AND
 OTHER INFORMATION AS REQUIRED UNDER CHAPTER 13. PLEASE
 BE SURE TO SEE THE 2006 REVISIONS TO THE 2004 FBC AS
 CHANGES WERE MADE.
  
 6) NOTE: PLEASE SHOW AND INCLUDE A LAYOUT ON PLANS
 SHOWING ALL CLASS AND DIVISION LOCATIONS AS REQUIRED
 PER NEC 511, 500 AND NFPA-30A.
 PLEASE PROVIDE A DETAIL FOR THE SHUNT/EM STOP DEVICE
 HOW THESE ARE BEING CONNECTED TO THE FEEDS.
 PLEASE SEE THE PANEL SCHEDULES WHICH DO NOT INDICATE
 SHUNT TRIPS REQUIRED?
  
 7) NOTE: PLEASE SEE NFPA-96 AS THE ELECTRICAL UNDER
 HOODS SHALL ALSO CONTAIN SHUNT AND DETAIL TO BE SHOWN.
 PLEASE SEE COMMENTS FROM OTHER TRADES FOR MORE
 INFORMATION ON GAS AND HOODS.
  
 8) NOTE: PLEASE SEE THE CODE SECTION REFERENCED FOR THE
 GFI PROTECTION OF THE KITCHEN OUTLETS SEEMS TO BE A
 MISPRINT.
 PLEASE SEE 210.8B3
 PLEASE ALSO SHOW ALL OF THESE CIRCUITS WHICH WILL BE
 PROTECTED. PLEASE INDICATE ON PANEL SCHEDULE OR PLANS.
 STATING THE SECTION OF THE CODE IS ONLY PART OF WHAT IS
 NEEDED.
 FBC 106.1.2
  
 9) NOTE: PLEASE SEE HB 7121, HB 319, HB965 ETC THIS IS
 HOUSE BILL 7121 WHICH WAS JUST ADOPTED INTO LAW ON JULY
 1ST, 2006. PLEASE SEE FS 252, 526.143ETC, WHICH NOW
 REQUIRES ALL FUEL STATIONS UPON BEING NEW OR
 SUBSTANTIAL REMODEL, ETC INSTALL A COMPLETE EMERGENCY
 BACK UP GENERATOR SYSTEM.PLEASE PROVIDE THE MINIMUM
 AMOUNT OF FUEL, FUEL CONSUMPTION FOR ALL LOADS. PLEASE
 SEE THAT UNDER THE FS 526.143 STATES THE MINIMUM AMOUNT
 OF TIME REQUIRED FOR OPERATIONS OF GENERATOR WHICH IS
 72HRS.
 PLEASE SUBMIT ALL REQUIRED LOCATIONS PER NEC 500.
 PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT SHEETS FOR ALL
 EQUIPMENT, ATS, MTS, GEN, FUEL PRIME MOVER ETC. PLEASE
 INDICATE THE AMOUNT OF ONSITE FUEL. PLEASE SEE THE NEW
 FLORIDA STATUTES FOR THE REQUIRED TIMES AND AMOUNT OF
 ON SITE FUEL REQUIRED. PLEASE SEE HB AS NOTED. PLEASE
 SEE THE GENERATOR NOTE ON PLANS MENTIONS THE GENERATOR
 IS GOOD FOR 434 AMPS. PLEASE VERIFY HOW THIS IS
 POSSIBLE WITH A 125KW UNIT AT 3-PHASE, 120/208V? PLEASE
 ALSO SEE NOTE WHICH MENTIONS THAT THE GENERATOR
 MANUFACTURE IS TO PROVIDE CALCULATIONS WHICH WILL MEET
 THE INTENDED LOADS. PLEASE KNOW THAT THIS INFORMATION
 FOR THE MINIMUM DESIGN IS REQUIRED AT THIS TIME. PLEASE
 KNOW THIS IS AND WILL BE REQUIRED. 90.7, 110.3 ETC
 PLEASE KNOW THAT ONE THE SPECS ARE SUBMITTED THE REVIEW
 OF MANY ITEMS WILL BE ABLE TO BE DONE AT THAT TIME. **
 PLEASE SEE THAT AS THIS IS LEGALLY REQUIRED SYSTEM
 PLEASE BE SURE TO SEE ALL OF THE REQUIREMENTS UNDER
 NFPA-110, AND NEC 701.
  
 10) NOTE: PLEASE SE NOTE ON PLANS WHICH MENTIONS THAT
 THE CONTRACTOR IS REQUIRED TO THE TRANSFORMER WITH THE
 FPL SERVICE PLANNER FOR THE AVAILABLE FAULT CURRENT.
 PLEASE KNOW THAT THIS IS REQUIRED TO BE DONE AT THIS
 TIME. IT IS THE RESPONSIBILITY OF THE DESIGNER AND
 DESIGN TEAM.
 110.9
  
 11) NOTE: PLEASE KNOW THAT UNTIL THE MANUFACTURES
 SPECS/CUT SHEETS ARE SUBMITTED FOR THE SERVICE ENTRANCE
 ATS, REVIEW FOR THE CODE COMPLIANCE FOR 225.31-225.39,
 230.76, 230.79 CAN NOT BE DONE.
 701, 110.27.
  
 12) NOTE: PLEASE SEE RISER NOTES WHICH MENTIONS THE TWO
 DISCONNECTS ON THE LINE SIDE OF SUB PANELS AND ON THE
 LOAD SIDE OF THE GUTTER AS MAINS 1 OF 2 AND 2OF 2? HOW
 IS THIS POSSIBLE WHEN THE SERVICE MEANS OF DISCONNECTS
 ARE LOCATED IN THE ATS.
 OCP AT GENERATOR SHALL BE SHOWN.
 PLEASE SEE 445.13 WHICH MAY APPLY FOR THE MINIMUM
 SIZING OF THE CONDUCTORS.
 PLEASE SHOW ALL EQUIPMENT ON PLANS AT BUILDING
 INCLUDING BOTH MAINS.
 110.26
 FBC 106.1.2
  
 13) NOTE: PLEASE PROVIDE COMPLETED PLANS FOR THE SLAB
 DETAIL, ELEVATION OF THE UNIT AND SERVICE. EQUIPMENT IS
 PART OF A LEGALLY REQUIRED SYSTEM SEE LOCATIONS AND
 ELEVATIONS IN NFPA-110 CHAPTER 7
 THE LOCATION, ENCLOSURE AND GENERATOR SHALL BE
 PROTECTED FROM VANDALISM, FLOODS, ETC.
  
 14) NOTE: PLEASE SEE THAT FEES ARE OWED AS THE AMOUNT
 OF SHEETS SUBMITTED IS GREATER THAN THAT PLACED ON
 SUBMITTIAL SHEET.
  
 ** PLEASE KNOW AS THERE IS MUCH INFORMATION NOT YET
 SUBMITTED AND MANY CHANGES WHICH WILL BE REQUIRED ON
 PLANS, FURTHER COMMENTS MAY BE EXTENDED ON THE
 FOLLOWING REVIEW.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-03-24 12:47:49IN ELEC FOR REVIEW

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-11-04 Cont ID  
Sent By dpalmer Date 2006-11-04 Time 19:45 Rev Time 0.00
Received By dpalmer Date 2006-11-04 Time 18:46 Sent To  
Notes
2006-11-04 19:45:09*** UNSAT ***
  
  
 ** PLEASE KNOW THIS IS STILL UNDER "PLAN REVIEW" ONLY.
 NO APPLICATION FOR PERMIT HAS YET BEEN MADE TO DATE.
 PLEASE KNOW A CODE CHANGE FOR NFPA-70 IS COMING AND IF
 PERMIT IS NOT APPLIED FOR BEFORE STATE ADOPTS NEW CODE,
 THEN THE PLANS WILL BE REQUIRED TO CHANGE AS NEEDED.
 THE TENTATIVE DATE IS DEC 1ST, 2006
  
 1) NOTE:PLEASE SEE PLANS SEEM TO INDICATE A NEW STORE
 BEING CONSTRUCTED, HOWEVER THE "PLAN REVIEW" SUBMITTAL
 SHEET INDICATES A REMODEL??? THE SCOPE OF WORK IS
 UNCLEAR BASED ON PLANS SUBMITTED IN EITHER CASE.
  
 2) NOTE: PLEASE SEE FS 471.003(2)(H)2A, AS PLANS ARE
 REQUIRED TO BE DONE BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER.
 PLEASE ALSO SEE FS 471.025(3).
 THE ELECTRICAL SCOPE AS SHOWN MAY NOT BE DONE BY AN
 ARCHITECTURAL FIRM/ARCHITECT.
  
 3) NOTE: PLEASE KNOW THE PLANS SUBMITTED ARE NOT
 COMPLETE FOR CODE COMPLIANCE. PLEASE SEE ONLY SOME CODE
 ARTICLES BELOW ARE BEING GIVEN. PLEASEKNOW THERE IS A
 SUBSTANTIALLY AMOUNT OF CODE RELATED ITEMS NOT
 SUBMITTED OR SHOWN.
  
 A) PLEASE INDICATE AND SHOW ALL CIRCUITING ON PLANS AND
 CORRELATE WITH PANEL SCHEDULES TO BE SUBMITTED.
 240.4,310.16, 408.4
 FBC ADMINISTRATIVE SECTION AS ADOPTED BY THE CITY OF
 WEST PALM BEACH. 106.1.2, 106.3.5.1.2 ETC.
 PLEASE ALSO SEE 2002 NFPA-70, 2003 NFPA-101, 2002
 NFPA-72, NFPA-30A ETC ETC.
 B) PLEASE SUBMIT LOAD CALCULATIONS.NEC 220.
 C) PLEASE SEE NEC 511
 D) PLEASE SEE LS 101 7.8, 7.9 FOR MISSING EM/ EXT LTS,
 PLEASE ALSO SEE 700.12E FOR CIRCUITING.
 E) PLEASE SEE 250.6, 250.24B
 F) PLEASE SEE 250.110, 250.110
 G) PLEASE SEE 250.50
 H) PLEASE SEE 600.5, 220.3(B)(6)
 I) PLEASE SEE 210.62, 220.12A
 J) PLEASE SEE 210.8B3
 K) PLEASE SEE FBC CHAPTER 13(ALL APPLICABLE SECTIONS,
 TOO MANY TO LIST AT THIS TIME.
 L) PLEASE SEE 110.9, 240.12 FOR SELECTIVE COORDINATION
 DETAILS TO BE SUBMITTED.
 ETC.
  
 4) NOTE: PLEASE SEE HB 7121, HB 319, HB965 ETC THIS IS
 HOUSE BILL 7121 WHICH WAS JUST ADOPTED INTO LAW ON JULY
 1ST, 2006. PLEASE SEE FS 252 ETC, WHICH NOW REQUIRES
 ALL FUEL STATIONS UPON BEING NEW OR SUBSTANTIAL
 REMODEL, ETC INSTALL A COMPLETE EMERGENCY BACK UP
 GENERATOR SYSTEM. THIS WILL SUBSTANTIALLY CHANGE THE
 PLANS SUBMITTED.
 PLEASE SUBMIT SITE PLANS, ALL REQUIRED LOCATIONS PER
 NEC 500. PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT
 SHEETS FOR ALL EQUIPMENT, ATS, MTS, GEN, FUEL PRIME
 MOVER ETC ETC.
 PLEASE KNOW THIS IS AND WILL BE REQUIRED. 90.7, 110.3
 ETC
  
  
 ** PLEASE KNOW AS PLANS ARE NOT COMPLETE AT THIS TIME
 FOR A SUFFICIENT REVIEW, AND WILL BE CHANGING, THERE
 MAY BE FURTHER COMMENTS UPON THE NEXT REVIEW.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 7 Status P Date 2009-11-30 Cont ID  
Sent By   Date 2009-11-30 Time   Rev Time 5.00
Received By   Date 2009-11-30 Time   Sent To ENG
Notes
2009-11-30 14:48:14PLANS ARE APPROVED AS-NOTED THRU ESD DATED 11/30/09
 1) FOR EACH INLET , PROVIDE A 12" DIA WEEP HOLE AS
 SHOWN ON THE DETAIL ON SHT 3 OF 3. UNDER THE WEEP HOLE
 INSTALL HARDWARE CLOTH (SS) ON
 2' X 2' X 6" OF WASHED ROCK WRAPPED ALL AROUND WITH
 FABRIC.
 2) FOR EACH INLET , PROVIDE A POLLUTION CONTROL BAFFLE
 (PCB) AT EACH PIPE OUTLET TO EXFILTRATION TRENCH (6
 TOTAL ).
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  

Review Stop ENG ENGINEERING CSD
Rev No 6 Status F Date 2009-09-23 Cont ID  
Sent By mgonzale Date 2009-09-23 Time 10:54 Rev Time 1.00
Received By mgonzale Date 2009-09-23 Time 10:49 Sent To  
Notes
2009-09-23 10:54:14FAILED
  
 PLANS MUST BE SUBMITTED TO ENGINEERING DEPT FOR
 STORMWATER REVIEW.
 THIS IS A SEPARATE SUBMITTAL REQUIRED BY ENGINEERING
 DEPT TO COMPLY WITH NPDES CODES.
  
 INFORMATION ON SUBMITTAL CAN BE OBTAINED AT THE LINK
 BELOW:
 HTTP://WWW.CITYOFWPB.COM/ENGINEERING/ENG_FORMS.PHP
  
 DEVELOPMENT PERMIT PACKET MUST ACCOMPANY YOUR SUBMITTAL
 ALONG WITH THE REQUIRED DOCUMENTATION.
 SEE "ENGINEERING SERVICES DEPARTMENT STANDARD
 APPLICATION FOR DEVELOPMENT PERMIT"
  
 SUBMIT THE PERTINENT DOCUMENTS ATTENTION:
 BRIAN MOREE, CONSTRUCTION SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1098
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  

Review Stop ENG ENGINEERING CSD
Rev No 5 Status F Date 2009-07-27 Cont ID  
Sent By dlauderm Date 2009-07-27 Time 13:53 Rev Time 2.00
Received By dlauderm Date 2009-07-27 Time 12:37 Sent To  
Notes
2009-07-27 13:19:57FAILED
 DEAN LAUDERMILK, PROJECT COORDINATOR
 CSD: (561) 805-6716
 ESD: (561) 494-1083
 EMAIL: [email protected]
 TOO MANY CONTRADICTIONS TO APPROVE THE PLANS AS
 SUBMITTED.
 1. GREASE TRAP ON CIVIL PLAN (2 OF 3) DOES NOT MATCH
 PLUMBING PLAN (P-1 & P-2). NEITHER DESIGN MATCHES OUR
 STANDARD DETAIL, WHICH WAS NOT INCLUDED IN THE CIVIL OR
 PLUMBING PLANS.
 2. WATER SERVICE, METER AND BACKFLOW PREVENTER ARE TO
 REMAIN, PER CIVIL PLAN (2 OF 3), WHILE PLUMBING PLAN
 (P-2) SHOWS A NEW 1" SERVICE TO THE CITY MAIN.
 3. WATER SERVICE FROM BUILDING TO THE METER AND
 BACKFLOW PREVENTER ARE TO REMAIN, PER CIVIL PLAN (2 OF
 3), WHILE PLUMBING PLAN (P-2) SHOWS A NEW 1" SERVICE
 FROM THE BUILDING TO THE METER/BACKFLOW PREVENTER.
 4. IRRIGATION PLAN (IR-1) SHOWS METER AND BACKFLOW
 PREVENTER AT NW CORNER OF SITE, THERE IS NO WATER MAIN
 IN THE ALLEY, THE WATER METER NEEDS TO BE ON LAKE
 AVENUE. IS THE INTENTION TO INSTALL A SEPARATE 1"
 SERVICE FOR THE IRRIGATION SYSTEM? THE PLUMBING PLAN
 SHOWS NO TEE IN THE LINES AND NO BACKFLOW PREVENTER FOR
 THE IRRIGATION SYSTEM. ALL BACKFLOW PREVENTERS NEED TO
 BE INSTALLED BY A LICENSED PLUMBER, NOT AN IRRIGATION
 COMPANY.
 5. IRRIGATION PLAN (IR-1) SHOWS 5 ZONES, TWO OF THE
 ZONES ARE DESIGNED FOR MORE WATER THAN THE 1" WATER
 METER IS DESIGNED TO GIVE. THE MAXIMUM SAFE OPERATING
 RATE FOR A 1" METER IS 25 GPM. REDESIGN THE IRRIGATION
 SYSTEM ZONES SO THE MAXIMUM GPM RATE DOES NOT EXCEED 25
 GPM
 6. THE IRRIGATION SYSTEM WILL NEED A SEPARATE BACKFLOW
 PREVENTER WHICH IS CALLED OUT ON THE IRRIGATION PLAN
 BUT IS NOT SHOWN ON THE PLUMBING PLAN OR CIVIL PLAN.
 THE CIVIL PLAN (2 OF 3) SHOWS GATES ON THE EQUIPMENT
 ENCLOSURE OPENING TO THE EAST. THE APPROVED SITE PLAN
 AND THE BUILDING PLANS SHOWS THE GATE OPENING TO THE
 SOUTH (THE CORRECT WAY).
 7. THIS PLAN HAS NOT BE REVIEWED/APPROVED BY THE
 ENGINEERING DEPARTMENT. WHEN THE CORRECTIONS ARE MADE
 SUBMIT THE CIVIL PLAN AND THE STORMWATER CALCULATIONS
 TO THE ENGINEERING SERVICES, ATTENTION EMERY FABIAN,
 THE PROJECT COORDINATOR FOR THE PROJECT. THIS NEEDS TO
 BE DONE PRIOR TO TURNING IN THE PLANS FOR ANOTHER
 CONSTRUCTION SERVICES REVIEW. THE ESD STAMP (APPROVED)
 NEEDS TO BE ON THE PLAN.
  

Review Stop ENG ENGINEERING CSD
Rev No 4 Status F Date 2009-06-10 Cont ID  
Sent By mgonzale Date 2009-06-10 Time 11:10 Rev Time 1.00
Received By mgonzale Date 2009-06-10 Time 11:00 Sent To  
Notes
2009-06-10 11:10:35********* NOT APPROVED ***********
  
 SUPPLY THE FOLLWING TO CITY OF WEST PALM BEACH
 ENGINEERING DEPT FOR APPROVAL:
 SURFACE WATER QUALITY CALCULATIONS
 IMPERVIOUS AND PERVIOUS CALCULATIONS
 POLLUTION PREVENTION PLAN OR SUMMARY.
  
 A 1" DOMESTIC WATER METER IS SERVING YOU PROPERTY.
 SUGGESTION OF OBTAINING AN IRRGATION METER MAY BE
 SUITABLE AS
 THAT CONSUMPTION WILL NOT BE CHARGED SEWAGE AGAINST IT.
  
 ANY QUESTIONS, PLEASE CONTACT:
  
 ATTENTION: MANUEL GONZALEZ
 (561) 494-1085
 [email protected]
  
  
  
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2007-10-22 Cont ID  
Sent By rchokshi Date 2007-10-22 Time 15:33 Rev Time 0.00
Received By rchokshi Date 2007-10-22 Time 15:26 Sent To  
Notes
2007-10-22 15:33:30**** FAILED *****
  
  
 1. PLEASE SHOW ON DRAWINGS POLLUTION PREVENTION
 DETAILS,CLOTHES USED FOR SILT ETC., AND PLANS SHOWING
 SILT FENCE AROUND THE SITE.
  
 2. STORM WATER QUALITY CALCULATIONS MUST BE APPROVED
 FROM 45TH STREET, ENGINEERING BEFORE WE ISSUE A
 PERMIT.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2007-03-30 Cont ID  
Sent By rchokshi Date 2007-03-30 Time 14:26 Rev Time 0.00
Received By rchokshi Date 2007-03-30 Time 14:06 Sent To  
Notes
2007-03-30 14:26:29YOUR PLANS WERE REVIEWED IN REV 1 ON 11/17/06.YOU
 PROVIDED SEAL & SIGNED PLANS, NOW, FOR REV 2. YOU DID
 NOT PROVIDE EXPLANATIONS OF ITEMS WE LISTED IN REV 1,
 DATED 11/17/06
 PLEASE PROVIDE EXPLANATIONS & INFO ON THE DRAWINGS FOR
 EACH OF THE ITEMS WE ASKED FOR IN REV 1 DATED
 11/17/06.
 ALSO, PLEASE PROVIDE DETAIL CALCULATIONS FOR WATER
 QUALITY FOR BOTH CRITERIA EITHER 1" OR 2.5" CRITERIA
 FOR WATER QUALITY?? WE LIKE TO SEE BOTH CRITERIA
 CALCULATIONS, AND TAKE THE WORST CRITERIAFOR THE
 LENGTH OF DESIGNINGEXFILTRATIONS TRENCH. IN OTHER
 WORDS, DETAILEDCAL FORLENGTH OF EXFILTRATION TRENCH
 ETC.
  
 PLEASE RESPOND EACH

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2006-11-17 Cont ID  
Sent By rchokshi Date 2006-11-17 Time 15:52 Rev Time 0.00
Received By rchokshi Date 2006-11-17 Time 15:43 Sent To  
Notes
2006-11-17 15:51:48I REVIEW ONLY THE FOLLOWING.SOPLEASE PROVIDE
 FOLLOWING INFO FOR COMPLETE REVIEW:
 1.NEEDS SEAL & SIGN FOR ALL CIVIL DWGSBYP.E.AS
 YOU PROVIDED
 2. PLEASE SHOW STANDARDS NOTES OF CITY OF WPB ON
 DRAWINGSFOR SIDEWALK WIDTH , ITS SLOPE, DRIVEWAY,
 PARKING, HANDICAP PARKING, PAINTPER CITY CODES ETC.,,
 MUST MEET PER ADA,,ETC.,
 3. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 4. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD ,
 SIDEWALK ELEVATION MUST MEET FL BLDG CODE, PLEASE SHOW
 ON THE DRAWINGS.
 5. PLEASE PROVIDE A COPY OF SFWMD PERMIT,& GEOTECHNICAL
 REPORT
 6.PLEASE SHOW STORM WATER CALCULATIONS, WHAT CRITERIA
 YOU ASSUMEDFOR RUNOFF CAL.,, LIKE 1" OVER ENTIRE SITE
 OR2.5"CRITERIA, ?PERVIOUS AREA, LIKE GREEN,
 LAKES, ETC,IMPERVIOUS AREA CAL.,
 7. WHAT IS THE SITE AREA, YOU ARE DEVELOPING FOR THIS
 PROJECT ONLY ? SO, WE CAN CHECK PERVIOUS, IMPERVIOUS
 CAL.
 8. HOW YOU CONNECT TO THE STORM WATER PIPES IN YOUR
 SITE? ITS DETAILS.PLEASE SHOW ALL STORM WATER PIPES
 AROUND YOUR SITE SO, WE CANSEE THE BEST PIPE TO
 CONNECT WITH THE STORM WATERFROM ALL OTHER STORM
 WATER PIPES. PLEASE SHOW DETAIL OF THE CONTROL
 STRUCTURES WITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC DID YOU USE EXFILTRATION TRENCH ?
 9. POLLUTION PREVENTION DETAILS,CLOTHES USED FOR SILT
 ETC., PLANS SHOWING SILT FENCE AROUND THE SITE
 10. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED
 11. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2009-10-14 Cont ID  
Sent By mawillia Date 2009-10-14 Time 15:30 Rev Time 0.00
Received By mawillia Date 2009-10-14 Time 15:11 Sent To  
Notes
2009-10-14 15:15:01*****APPROVED*****
  
  
 PLAN SHEET A-5, PREVIOUSLY (8/06/09) STAMPED,
 INITIALED, AND DATED ALONG WITH A-2, A-3, A-5, AND
 LS-1) WAS RE-STAMPED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2009-08-06 Cont ID  
Sent By mawillia Date 2009-08-06 Time 13:50 Rev Time 0.00
Received By mawillia Date 2009-08-06 Time 13:24 Sent To  
Notes
2009-08-06 13:29:14*****APPROVED*****
  
  
 PLAN SHEETS A-2, A-3, A-5, AND LS-1 WERE STAMPED,
 INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2009-05-29 Cont ID  
Sent By mawillia Date 2009-05-29 Time 15:20 Rev Time 0.00
Received By mawillia Date 2009-05-29 Time 15:06 Sent To  
Notes
2009-05-29 15:17:56*****PROVISO*****
  
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED, HOWEVER THE APPROPIATE PLAN SHEETS
 (A-2, A-3, A-5, LS-1, AND LS-2) TO BE FIRE-STAMPED
 PROVIDED THE FOLLOWING:
  
  
 1.) ON SHEET LS-1 IN THE PROJECT CODES, AMEND NFPA 101
 TO 2006 (NOT 2005) EDITION.
  
 2.) PERMIT CAN NOT BE ISSUED UNTIL A CONTRACTOR HAS
 BEEN DECLARED.
  
 3.) THE COMMENTS FROM THE OTHER TRADES HAVE BEEN
 SATISFIED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2007-10-25 Cont ID  
Sent By mawillia Date 2007-10-25 Time 13:17 Rev Time 0.00
Received By mawillia Date 2007-10-25 Time 12:45 Sent To  
Notes
2007-10-25 13:16:28****DENIED*****
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED:
  
  
 3.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 HINDER OR INTERFERE WITH EMERGENCY ACCESS TO THE
 PROPERTY OR VICINITY THEREOF.
  
 4.THE NUMERICAL ADDRESS OF THE JOB SITE SHALL BE IN
 THE TITLE BLOCK OF THE SUBMITTED PLAN SHEETS.NO
 ADDRESS ON SHEET SP-1, LS-1, LS-2, LP-1, C2 & C3, AND
 E-1
  
 8.SPECIFY ANY NEW WALL AND CEILING INTERIOR FINISH
 CLASSIFICATION IN TERMS OFCLASS "A"CLASS "B", OR
 CLASS "C".
  
 9.PROVIDE A LIFE SAFETY PLAN SHEET TO INCLUDE ALL
 COMMON PATHS OF TRAVEL TO THE EXIT(S) AND THE LOCATION
 OF FIRE EXTINGUISHERS AT DISTANCES WHICH SATISFY THE
 75' TRAVEL DISTANCE REQUIREMENT.
  
 NEW COMMENT
  
 A.THE INSTALLATION OF THE STANDBY GENERATOR WILL
 REQUIRE SEPARATE PLANS AND PERMIT, AND SHALL COMPLY
 WITH NFPA 110.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 SHEET INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-04-12 Cont ID  
Sent By mawillia Date 2007-04-12 Time 17:16 Rev Time 0.00
Received By mawillia Date 2007-04-12 Time 16:37 Sent To  
Notes
2007-04-12 17:16:37****DENIED*****
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED:
  
  
 1.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 HINDER OR INTERFERE WITH EMERGENCY ACCESS TO THE
 PROPERTY OR VICINITY THEREOF.
  
 4.THE NUMERICAL ADDRESS OF THE JOB SITE SHALL BE IN
 THE TITLE BLOCK OF THE SUBMITTED PLAN SHEETS.
  
 5.IN ADDITION TO SHOWING WHERE THE NUMERICAL ADDRESS
 WILL BE LOCATED AS ON SHEET A-2, SHOW WHAT THOSE
 NUMBERS WILL BE.
  
 8.SPECIFY THE WALL AND CEILING INTERIOR FINISH
 CLASSIFICATION ASCLASS "A"CLASS "B", OR CLASS "C".
  
 9.PROVIDE A LIFE SAFETY PLAN SHEET TO INCLUDE ALL
 COMMON PATHS OF TRAVEL TO THE EXIT(S) AND THE LOCATION
 OF FIRE EXTINGUISHERS AT DISTANCES WHICH SATISFY THE
 75' TRAVEL DISTANCE REQUIREMENT.
  
 NEW COMMENT
  
 A.THE INSTALLATION OF THE STANDBY GENERATOR WILL
 REQUIRE SEPARATE PLANS AND PERMIT, AND SHALL COMPLY
 WITH NFPA 110.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 SHEET INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-12-14 Cont ID  
Sent By mawillia Date 2006-12-14 Time 11:36 Rev Time 0.00
Received By mawillia Date 2006-12-14 Time 11:36 Sent To  
Notes
2006-12-14 12:11:15*****DENIED*****
  
  
  
 1.NFPA 101 (2003 EDITION) THE FLORIDA FIRE PREVENTION
 CODE (2004 EDITION) SHALL BE REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 HINDER OR INTERFERE WITH EMERGENCY ACCESS TO THE
 PROPERTY OR VICINITY THEREOF.
  
 4.THE NUMERICAL ADDRESS OF THE JOB SITE SHALL BE IN
 THE TITLE BLOCK OF THE SUBMITTED PLAN SHEETS.
  
 5.IN ADDITION TO SHOWING WHERE THE NUMERICAL ADDRESS
 WILL BE LOCATED AS ON SHEET A-2, SHOW WHAT THOSE
 NUMBERS WILL BE.
  
 6.EXIT AND EMERGENCY LIGHTS TO BE INSTALLED AND
 ARRANGED AS PER NFPA 101, 7.9 AND 7.10
  
 7.PROVIDE THE THE FOLLOWING BUILDING INFORMATION: A)
 CONSTRUCTION TYPEB) OCCUPANCY TYPEC) FIRE
 PROTECTION SYSTEM I.E. FIRE ALARM AND/ORFIRE
 SPRINKLERD) INTERIOR FINISH CLASSIFICATION
  
 8.IF THE BUILDING IS UNSPRINKLERED, INTERIOR FINISH
 SHALL BE CLASS "A" OR CLASS "B".
  
 9.PROVIDE A LIFE SAFETY PLAN SHEET TO INCLUDE ALL
 COMMON PATHS OF TRAVEL TO THE EXIT(S) AND THE LOCATION
 OF FIRE EXTINGUISHERS AT DISTANCES WHICH SATISFY THE
 75' TRAVEL DISTANCE REQUIREMENT.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 SHEET INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 5 Status P Date 2009-12-16 Cont ID  
Sent By kstevens Date 2009-12-16 Time 15:14 Rev Time 0.00
Received By kstevens Date 2009-12-16 Time 15:14 Sent To  
Notes
2009-12-16 15:15:08PLANS STILL CODE COMPLIANT. -- NO CONTRACTOR SIGNED ON
 AT THIS TIME.

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2009-08-05 Cont ID  
Sent By kstevens Date 2009-08-05 Time 15:49 Rev Time 0.00
Received By kstevens Date 2009-08-05 Time 15:50 Sent To  
Notes
2009-08-10 15:50:07PLANS ARE CODE COMPLIANT BUT WILL REMAIN IN FAILED
 STATUS PENDING APPLICATION FOR PERMIT BY LICENSED
 CONTRACTOR.

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2009-05-29 Cont ID  
Sent By kstevens Date 2009-05-29 Time 13:52 Rev Time 0.00
Received By kstevens Date 2009-05-29 Time 13:52 Sent To  
Notes
2009-05-29 13:53:58DENIED
 REFERENCE:
 FBC-2007 W/2009 SUPPLEMENTS
 FBC-2007 FUEL GAS
  
 1. THE FOLLOWING INFORMATION IS REQUIRED FOR THE
 SEPARAGE GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2007
 FUEL GAS CODE. -- THE SECTION FROM THE WALL TO THE
 METER IS NOT INDICATED.
  
 B. TYPE OF GAS, (LP OR NATURAL). -- NOT INDICATED ON
 PLANS. SITE PLANS SHOWS A 1000 GAL PROPANE TANK BUT
 NOTE ON SHT P-2 INDICATES TABLE 402.4(2) WHICH IS A
 NATURAL GAS TABLE. PLEASE CLARIFY.
  
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2007 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). -- TO BE VERIFIED WHEN
 COMMENT 8(A) IS ADDRESSED.
  
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2007 FUEL GAS CODE SEC 402.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2007-12-03 Cont ID  
Sent By kstevens Date 2007-12-03 Time 07:57 Rev Time 0.00
Received By kstevens Date 2007-12-03 Time 07:56 Sent To  
Notes
2007-12-03 07:59:05DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. SHT A-1 INDICATES GAS EQUIPMENT IN THE KITCHEN. A
 SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE FOLLOWING
 INFORMATION:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE CORRESPONDING LENGHTS OF
 EACH CUT SECTION HAVE NOT BEEN SUBMITTED, PLEASE
 CLARIFY THE MARKINGS ON THE RISER DIAGRAM.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 ****NO RESPONSE, NOT ADDRESSED.
 ******NO RESPONSE, NOT INDICATED ON RISER DIAGRAM OR
 ADJOINING NOTES.
  
 C. OK - LP
 D. OK
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ****NO RESPONSE, NOT ADDRESSED.
 ******NO RESPONSE, NOT ADDRESSED.
  
 F. OK
  
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. IF 2 PSI SHOW THE
 LOCATION OF THE REGULATORS, SUBMIT MANUF.
 SPECIFICATIONS FOR THE REGULATORS AND IF THE REGULATORS
 ARE VENTED, INDICATE THE MATERIAL OF THE VENT AND SHOW
 THE PIPING LOCATION.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE MANUF. SPECIFICATIONS DO
 NOT SET THE DELIVERY PRESSURE. PLEASE ADDRESS COMMENT.
  
 H. OK
  
 I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT MANUF. SHEETS NOT SUBMITTED.
  
 J. OK
  
 K. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE ISOMETRIC ON SHT P-1
 INDICATES AN ABOVE GROUND TANK, AND THE SITE PLAN AS
 WELL AS THE CIVIL SHEETS INDICATE AN UNDERGROUND TANK.
 PLEASE CORRELATE.
  
 L. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE UNION IS NOT SHOWN, AND
 MANUF. SPECIFICATION SHEETS ARE REQUIRED FOR THE ANSUL
 VALVE SHOWING THAT THE VALVE IS LISTED FOR OUTSIDE
 USE.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-04-09 Cont ID  
Sent By kstevens Date 2007-04-09 Time 18:06 Rev Time 0.00
Received By kstevens Date 2007-04-09 Time 18:06 Sent To  
Notes
2007-04-09 18:12:02DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 THIS WAS FROM THE PREVIOUS PLUMBING REVIEW:
  
 1. SHT A-1 INDICATES GAS EQUIPMENT IN THE KITCHEN. A
 SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE FOLLOWING
 INFORMATION:
 ****NO RESPONSE, NOT ADDRESSED.
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ****NO RESPONSE, NOT ADDRESSED.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 ****NO RESPONSE, NOT ADDRESSED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
 ****NO RESPONSE, NOT ADDRESSED.
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 ****NO RESPONSE, NOT ADDRESSED.
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ****NO RESPONSE, NOT ADDRESSED.
  
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
 ****NO RESPONSE, NOT ADDRESSED.
  
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. IF 2 PSI SHOW THE
 LOCATION OF THE REGULATORS, SUBMIT MANUF.
 SPECIFICATIONS FOR THE REGULATORS AND IF THE REGULATORS
 ARE VENTED, INDICATE THE MATERIAL OF THE VENT AND SHOW
 THE PIPING LOCATION.
 ****NO RESPONSE, NOT ADDRESSED.
  
 H. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
 ****NO RESPONSE, NOT ADDRESSED.
  
 I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****NO RESPONSE, NOT ADDRESSED.
  
 J. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 ****NO RESPONSE, NOT ADDRESSED.
  
 K. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 ****NO RESPONSE, NOT ADDRESSED.
  
 L. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 ****NO RESPONSE, NOT ADDRESSED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2009-12-01 Cont ID  
Sent By lmartine Date 2009-11-24 Time 10:47 Rev Time 0.00
Received By lmartine Date 2009-11-24 Time 10:47 Sent To  
Notes
2009-12-01 10:54:02C--4

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2009-09-15 Cont ID  
Sent By kstevens Date 2009-09-15 Time 17:27 Rev Time 0.00
Received By kstevens Date 2009-09-15 Time 17:27 Sent To  
Notes
2009-09-15 17:29:53SENT TO C-32.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-07-16 Cont ID  
Sent By rmcdouga Date 2009-07-16 Time 16:45 Rev Time 0.00
Received By rmcdouga Date 2009-07-16 Time 16:45 Sent To  
Notes
2009-07-16 16:45:27TO C25

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-05-14 Cont ID  
Sent By shill Date 2009-05-14 Time 11:58 Rev Time 0.00
Received By shill Date 2009-05-14 Time 11:57 Sent To  
Notes
2009-05-14 11:58:18TO COMMERCIAL BOARD #23
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-09-28 Cont ID  
Sent By adarroug Date 2007-09-28 Time 09:47 Rev Time 0.00
Received By adarroug Date 2007-09-28 Time 09:47 Sent To  
Notes
2007-10-18 08:59:43TO "COMM" BD#12
2007-09-28 09:48:01WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-23 Cont ID  
Sent By adarroug Date 2007-03-23 Time 09:00 Rev Time 0.00
Received By adarroug Date 2007-03-23 Time 09:00 Sent To  
Notes
2007-03-23 09:03:55TO "COMM" BD#16

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-01-03 Cont ID  
Sent By kstevens Date 2007-01-03 Time 09:55 Rev Time 0.00
Received By kstevens Date 2006-11-02 Time 10:34 Sent To  
Notes
2006-11-02 10:36:19TO "COMM" BD#6

Review Stop L LANDSCAPING
Rev No 2 Status P Date 2009-07-17 Cont ID  
Sent By rkussner Date 2009-07-17 Time 13:27 Rev Time 0.00
Received By rkussner Date 2009-07-17 Time 13:27 Sent To PC
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2009-05-29 Cont ID  
Sent By rkussner Date 2009-05-29 Time 14:04 Rev Time 0.00
Received By rkussner Date 2009-05-29 Time 14:04 Sent To  
Notes
2009-05-29 14:40:28***LANDSCAPE REVIEW FAILED***
  
 PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN WRITTEN
 FORMAT.
  
 1. PURSUANT TO SECTION 94-444 (B), OUTDOOR MECHANICAL
 EQUIPMENT SHALL NOT BE PERMITTED UNLESS APPROPRIATE
 SCREENING IS PROVIDED. THE EQUIPMENT ENCLOSURE SHALL
 OPEN TO THE REAR (NORTH SIDE) OF THE STRUCTURE. THE
 CORNER ON THE SOUTH SIDE SHALL BE CUT OUT AND LANDCAPED
 WITH VERTICAL LANDSCAPE ELEMENTS SUCH AS A PALM
 GROUPING WITH UNDERPLANTING.
  
 2. PURSUANT TO SECTION 94-443 (C)(2), SHADE TREES SHALL
 BE PLANTED AT 30 FOOT INTERVALS IN THE REQUIRED
 LANDSCAPE BUFFER THAT SEPARATES THE VEHICULAR USE AREA
 FROM ADJACENT RIGHTS-FOF-WAY. AN ADDITIONAL TREE IS
 REQUIRED ALONG THE SOUTH PERIMETER OF THE SITE ON THE
 EAST SIDE OF THE EAST ACCESS POINT.
  
 3. TREES IN TERMINAL LANDSCAPE ISLANDS SHALL BE
 CENTERED WITHIN THE ISLAND TO PROVIDE SHADE OVER THE
 PARKING STALL. PLEASE ADD TWO ADDITIONAL SABAL PALMS OR
 A SHADE TREE IN THE LANDSCAPE ISLAND ON THE EAST SIDE
 OF THE EQUIPMENT ENCLOSURE. OTHERWISE, THE THREE PALMS
 COULD BE SHIFTED TOWARD THE SOUTH AND AN ADDITIONAL
 PERIMETER SILVER BUTTONWOOD TREE CAN BE ADDED ALONG THE
 NORTH PERIMETER OF THE SITE. THE SPACING OF THE TREES
 ALONG THE NORTH PERIMETER CANNOT EXCEED 30 FEET. THE
 TREES SHALL BE EQUALLY SPACED.
  
 4. THE BLACK OLIVE TREE ALONG THE WEST PERIMETER SHALL
 BE REMOVED AND REPLACED. IT IS NOT A FLORIDA #1 GRADE
 TREE AND IS IN POOR HEALTH.
  
 5, IN KEEPING WITH XERISCAPE GUIDELINES, GROUND COVER
 SHALL BE PLANTED IN THE SMALL AREAS THROUGHOUT THE SITE
 INSTEAD OF SOD. THE PLANTING WILL REQUIRE LESS WATER
 AND MAINTENANCE THAN SOD.
  
 6, THE PROPOSED HEDGE ALONG THE EAST PERIMETER OF THE
 SITE SHALL BE PLANTED ALONG THE INTERIOR PERIMETER OF
 THE LANDSCAPE BUFFER WITH GROUND COVER PLANTED ALONG
 THE STREET SIDE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.
  

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2009-10-01 Cont ID  
Sent By rregueir Date 2009-10-01 Time 09:43 Rev Time 0.00
Received By rregueir Date 2009-09-30 Time 16:10 Sent To  
Notes
2009-10-01 09:44:18SEPARATE PLANS AND APPLICATIONS REQUIRED FOR THE
 FOLLOWING:
  
 -HOOD
 -HOOD SUPPRESSION
 -WALK-IN COOLER
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2009-06-09 Cont ID  
Sent By rregueir Date 2009-06-09 Time 17:03 Rev Time 0.00
Received By rregueir Date 2009-06-09 Time 15:41 Sent To  
Notes
2009-06-09 17:03:38SEE EXCEPTIONS NOTED ON PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-10-23 Cont ID  
Sent By tgordon Date 2007-10-23 Time 11:27 Rev Time 0.45
Received By tgordon Date 2007-10-23 Time 11:27 Sent To  
Notes
2007-10-23 11:50:32PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *FOR PLAN REVIEW ONLY NOT FOR PERMIT*
 *** DENIED ***
  
 1) AS NOTED IN LAST TWO REVIEWS 11-3-06 AND 4-2-07 NOTE
 #5. THE TWO AUXILIARY DRAIN LINES (EM) NEED TO
 DISCHARGE TO A CONSPICUOUS LOCATION, PER 2004 FBC/M
 307.2.3, PLEASE CORRECT. (THE BACK OF THE BUILDING IS
 NOT A CONSPICUOUS LOCATION).
  
 2) AS NOTED IN LAST TWO REVIEWS 11-3-06 AND 4-2-07 NOTE
 #6. PLEASE SUBMIT ENERGY CALCULATIONS, PER 2004 FBC
 13-101.1.1. (BE ADVISED A COMPLETE REVIEW CAN NOT BE
 DONE WITHOUT THIS).
  
 3) AS NOTED IN LAST TWO REVIEWS 11-3-06 AND 4-2-07 NOTE
 #7. PLEASE SUBMITCOOLING LOAD CALCULATIONS, PER 2004
 FBC 13-407.1.ABC.1. (BE ADVISED A COMPLETE REVIEW CAN
 NOT BE DONE WITHOUT THIS).
  
 4) PLEASE SIZE THE RETURN AIR DUCT TO OFFICE, SEE W.P.B
 AMEND. 106.3.5.4 (10).
  
 5) PLEASE SIZE THE TWO FRESH AIR DUCTS TO THE AHU'S,
 SEE W.P.B. AMEND. 106.3.5.4 (10).
  
 6) THE A/C EQUIPMENT LISTING IS SHOWING THE TWO SAME
 SYSTEMS, BUT WITH DIFFERENT SENSIBLE, LATENT, AND TOTAL
 BTU,S PLEASE CORRECT OR EXPLAIN, SEE W.P.B. AMEND.
 106.3.5.4 (10).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-04-02 Cont ID  
Sent By tgordon Date 2007-04-02 Time 08:04 Rev Time 0.30
Received By tgordon Date 2007-04-02 Time 08:04 Sent To  
Notes
2007-04-02 08:16:22*FOR PLAN REVIEW ONLY NOT FOR PERMIT*
 *** DENIED ***
  
 1) ALL OF THE FOLLOWING CORRECTIONS WERE REQUESTED IN
 THE LAST REVIEW 11-3-06 AND STILL NEED TO BE
 CORRECTED.
  
 2) NEED TO SHOW THE SIZES OF THE A/C AIR DUCTS, SUPPLY
 TRUNK LINE, RETURN TRUNK LINE, AND HALF THE SUPPLY
 BRANCH LINES, SEE YELLOW HIGH LIGHTS ON MECH. PLANS.
  
 3) NEED THE SIZE OF THE RETURN AIR GRILLS.
  
 4) PROVIDE RETURN AIR TO THE OFFICE, PER 2004 FBC/M
 601.4.
  
 5) THE TWO AUXILIARY DRAIN LINES (EM) NEED TO DISCHARGE
 TO A CONSPICUOUS LOCATION, PER 2004 FBC/M 307.2.3,
 PLEASE CORRECT.
  
 6) PLEASE SUBMIT ENERGY CALCULATIONS, PER 2004 FBC
 13-101.1.1.
  
 7) PLEASE SUBMITCOOLING LOAD CALCULATIONS, PER 2004
 FBC 13-407.1.ABC.1 .
  
 8) NEED THE JOB ADDRESS ON EACH PLAN.
  
 9) NEED TO SHOW AN EQUIPMENT LISTING ON MECHANICAL
 PLANS WITH A/C EQUIPMENT MANUFACTURES NAME,MODEL
 NUMBERS, TOTAL AND SENSIBLE BTU'S, SEER, AND ALL OTHER
 PERTINENT INFORMATION FOR THE A/C SYSTEMS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-11-03 Cont ID  
Sent By tgordon Date 2006-11-03 Time 11:44 Rev Time 0.45
Received By tgordon Date 2006-11-03 Time 11:44 Sent To  
Notes
2006-11-03 12:15:26*FOR PLAN REVIEW ONLY NOT FOR PERMIT*
 *** DENIED ***
 1) SHOW THE LOCATION OF THE TWO A/C CONDENSER UNITS AND
 THE ONE WALK IN COOLER CONDENSER UNIT ON THE MECHANICAL
 PLANS.
  
 2) NEED TO SHOW THE SIZES OF THE A/C AIR DUCTS, SUPPLY
 TRUNK LINE, RETURN TRUNK LINE, AND HALF THE SUPPLY
 BRANCH LINS, SEE HIGH LIGHTS ON MECH. PLANS.
  
 3) NEED THE SIZE OF THE RETURN AIR GRILLS.
  
 4) PROVIDE RETURN AIR TO THE OFFICE, PER 2004 FBC/M
 601.4.
  
 5) THE TWO AUXILIARY DRAIN LINES (EM) NEED TO DISCHARGE
 TO A CONSPICUOUS LOCATION, PER 2004 FBC/M 307.2.3,
 PLEASE CORRECT.
  
 6) PLEASE SUBMIT ENERGY CALCULATIONS, PER 2004 FBC
 13-101.1.1.
  
 7) PLEASE SUBMITCOOLING LOAD CALCULATIONS, PER 2004
 FBC 13-407.1.ABC.1 .
  
 8) NEED THE JOB ADDRESS ON EACH PLAN.
  
 9) NEED TO ALSO SHOW THE SENSIBLE BTU'S AND CFM'S FOR
 THE A/C SYSTEMS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 7 Status P Date 2009-12-16 Cont ID  
Sent By kstevens Date 2009-12-16 Time 15:14 Rev Time 0.00
Received By kstevens Date 2009-12-16 Time 15:14 Sent To  
Notes
2009-12-16 15:14:48PLANS STILL CODE COMPLIANT. -- NO CONTRACTOR SIGNED ON
 AT THIS TIME.

Review Stop P PLUMBING
Rev No 6 Status F Date 2009-09-22 Cont ID  
Sent By kstevens Date 2009-09-22 Time 09:23 Rev Time 0.00
Received By kstevens Date 2009-09-22 Time 09:23 Sent To  
Notes
2009-09-22 09:25:41IRRIGATION PLANS APPROVED WITH PROVISO: DOUBLE DETECTOR
 NOT APPROVED. AN RPZV BACKFLOW IS REQUIRED AND SHALL BE
 INSTALLED BY A LICENSED PLUMBING CONTRACTOR. PER CILB
 PBC. PLANS WILL REMAIN IN FAILED STATUS UNTIL BLD-COM
 PERMIT IS APPLIED FOR BY LICENSED CONTRACTOR.

Review Stop P PLUMBING
Rev No 5 Status F Date 2009-08-05 Cont ID  
Sent By kstevens Date 2009-08-05 Time 15:47 Rev Time 0.00
Received By kstevens Date 2009-08-05 Time 15:48 Sent To  
Notes
2009-08-10 15:49:26PLANS ARE CODE COMPLIANT BUT WILL REMAIN IN FAILED
 STATUS PENDING APPLICATION FOR PERMIT BY LICENSED
 CONTRACTOR.

Review Stop P PLUMBING
Rev No 4 Status F Date 2009-05-29 Cont ID  
Sent By kstevens Date 2009-05-29 Time 13:15 Rev Time 0.00
Received By kstevens Date 2009-05-29 Time 13:15 Sent To  
Notes
2009-05-29 13:52:26DENIED
 REFERENCE:
 FBC-2007 W/2009 SUPPLEMENTS
 FBC-2007 PLUMBING
 FBC-2007 FUEL GAS
 FBC-2007 BUILDING
 FBC-2007 CHAPTER 1 (ADMIN)
 FBC-2007 CHAPTER 11
  
  
 1. SHT SP-1 CODE REFERENCE SHALL INCLUDE THE 2009
 SUPPLEMENTS. SECTION 106.1.1.
  
 2. SHT A-2 THE FILTERS REFERENCED SHALL MEET THE
 REQUIREMENTS OF NSF-42. PLEASE SUBMIT MANUF.
 SPECIFICATIONS FOR THE FILTERS. SECTIONS 106.1.2 &
 611.1.
  
 3. SHT A-2 ROOM FINISH SCHEDULE FOR THE TOILET ROOM
 INDICATES PANTED WALLS. WALLS WITHIN 2 FEET OF THE
 WATER CLOSET SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 SURFACE. PAINTED SURFACES DOES NOT MEET THE "HARD"
 REQUIREMENT. SECTION 1210.2.
  
 4. SHT A-2 TOILET ROOM ELEVATIONS. PLEASE INCLUDE THE
 REQUIRMENT FOR SECTION 11-4.16.5 FLUSH CONTROLS.
  
 5. SHT A-4 GUTTER FOR FLAT ROOF, (TOTAL AREA WITH
 VERTICAL WALL CONTRIBUTION 1102 FS), REQUIRES A 7INCH
 GUTTER AT .5 % SLOPE OR 6 INCH AT 1& SLOPE. TABLE
 1106.6. PLEASE INDICATE SLOPE REQUIRED ON GUTTER OR
 INDICATE 7 INCH GUTTER.
  
 6. SHT A-4 GUTTERS SHALL BE SIZED BY TABLE 1106.6. ROOF
 PLAN NOTES #5 INDICATES 1106.7. THIS IS FOR OVERFLOW
 SCUPPERS. PLEASE UPDATE TABLE REFERENCE FOR GUTTERS.
  
 7. SHT P-2 SANITARY ISOMETRIC RISER DIAGRAM. MINIMUM 4"
 PIPE IS REQUIRED UPSTREAM OF THE 1ST HAND SINK, (BY THE
 KITCHEN). THE FIXTURE UNIT COUNT IS 41 FU AT THAT
 POINT. TABLE 710.1(1).
  
 8 THE FOLLOWING INFORMATION IS REQUIRED FOR THE
 SEPARAGE GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2007
 FUEL GAS CODE. -- THE SECTION FROM THE WALL TO THE
 METER IS NOT INDICATED.
  
 B. TYPE OF GAS, (LP OR NATURAL). -- NOT INDICATED ON
 PLANS. SITE PLANS SHOWS A 1000 GAL PROPANE TANK BUT
 NOTE ON SHT P-2 INDICATES TABLE 402.4(2) WHICH IS A
 NATURAL GAS TABLE. PLEASE CLARIFY.
  
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2007 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). -- TO BE VERIFIED WHEN
 COMMENT 8(A) IS ADDRESSED.
  
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2007 FUEL GAS CODE SEC 402.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-12-03 Cont ID  
Sent By kstevens Date 2007-12-03 Time 06:58 Rev Time 0.00
Received By kstevens Date 2007-12-01 Time 14:25 Sent To  
Notes
2007-12-03 07:42:39DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 FROM PREVIOUS REVIEW:
 ******FROM PREVIOUS REVIEWS.
  
 1.OK
  
 2. SUBMIT A DETAIL FOR THE TOILET ROOM. SHOW COMPLIANCE
 WITH SECTIONS 11-4.16, 11-4.19, 11-4.22 AND ALL
 SUBSECTIONS.
 ****NO RESPONSE, NOT ADDRESSED.
 SHOW THE FOLLOWING:
 ____FOR W/C'S:
 A. OK
 B. OK
 C. OK
 D. 11-4.16.5 FLUSH CONTROLS
 ******RESPONSE NOTED, NOT ADDRESSED
 E. OK
 ____FOR LAVS:
 A. OK
 B. 11-4.19.5 FAUCETS
 ******RESPONSE NOTED, NOT ADDRESSED
  
 3. OK
 4. OK
 5. OK
 6. OK
  
 7. SHT P-1 THE GREASE PLUMBING RISER DOES NOT MEET
 CODE. THE 3 COMPARTMENT SINK AND THE HAND SINK ARE NOT
 VENTED. (MISLABELED AS LAVS). ALSO EQUIPMENT AND
 FIXTURES UTILIZED FOR THE STORAGE, PREPARATION AND
 HANDLING OF FOOD SHALL DISCHARGE THROUGH AN INDIRECT
 PIPE BY MEANS OF AN AIR GAP. (A FLOOR SINK WOULD BE
 REQUIRED). SECTIONS 802.1.1 AND 901.2.1.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT A RUNNING TRAP IS NOT
 APPROVED AND A SEPARATE FLOOR SINK IS REQUIRED FOR THE
 3 COMPARTMENT SINK. (SEE RED LINE CORRECTION EXAMPLE
 SHOWN ON ONE SET OF PLANS). THE MOP SINK AND ICE MAKER
 DRAINAGE IS NOT SHOWN ON THE RISER DIAGRAM. FLOOR
 DRAINS ARE NOT APPROVED INDIRECT WASTE RECEPTORS. A
 FLOOR SINK OR HUB DRAIN IS REQUIRED PER SECTIONS 802.3
 & 802.3.2. FLOOR SINKS SHALL BE INSTALLED UNDER THE
 FIXTURE SO THEY WILL NOT BECOME A TRIPPING HAZARD.
  
 8. SUBMIT A WATER RISER DIAGRAM. SHOW ALL PIPE SIZES,
 VALVES, AND REQUIRED WATER HAMMER ARRESTORS, (ICE
 MACHINE). SECTIONS 106.3.5.1.3 & 604.9.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT ALL PIPE SIZES ARE NOT SHOWN,
 AND PLEASE CLARIFY MARKINGS ON THE RISER DIAGRAM.
  
 9. OK
  
 10. SHT A-1 INDICATES GAS EQUIPMENT IN THE KITCHEN. A
 SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE FOLLOWING
 INFORMATION:
 ****NO RESPONSE, NOT ADDRESSED.
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE CORRESPONDING LENGHTS OF
 EACH CUT SECTION HAVE NOT BEEN SUBMITTED, PLEASE
 CLARIFY THE MARKINGS ON THE RISER DIAGRAM.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 ****NO RESPONSE, NOT ADDRESSED.
 ******NO RESPONSE, NOT INDICATED ON RISER DIAGRAM OR
 ADJOINING NOTES.
  
 C. OK - LP
 D. OK
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ****NO RESPONSE, NOT ADDRESSED.
 ******NO RESPONSE, NOT ADDRESSED.
  
 F. OK
  
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. IF 2 PSI SHOW THE
 LOCATION OF THE REGULATORS, SUBMIT MANUF.
 SPECIFICATIONS FOR THE REGULATORS AND IF THE REGULATORS
 ARE VENTED, INDICATE THE MATERIAL OF THE VENT AND SHOW
 THE PIPING LOCATION.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE MANUF. SPECIFICATIONS DO
 NOT SET THE DELIVERY PRESSURE. PLEASE ADDRESS COMMENT.
  
 H. OK
  
 I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT MANUF. SHEETS NOT SUBMITTED.
  
 J. OK
  
 K. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE ISOMETRIC ON SHT P-1
 INDICATES AN ABOVE GROUND TANK, AND THE SITE PLAN AS
 WELL AS THE CIVIL SHEETS INDICATE AN UNDERGROUND TANK.
 PLEASE CORRELATE.
  
 L. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE UNION IS NOT SHOWN, AND
 MANUF. SPECIFICATION SHEETS ARE REQUIRED FOR THE ANSUL
 VALVE SHOWING THAT THE VALVE IS LISTED FOR OUTSIDE
 USE.
  
 **********NEW COMMENTS**********
  
 1B. PLEASE SEE ELECTRICAL COMMENTS #3 & #4 CONCERNING
 TITLE BLOCKS, SEALS, PRINTED NAMES REQUIRE BY THE
 FLORIDA ADMINISTRATIVE CODE AND THE FLORIDA STATUTES.
 ******NO RESPONSE, AND THE SP-1 SHEET IS NOT SIGNED,
 SEALED, OR DATED. SHT LS-1 SEAL IS NOT APPROVED. PER
 FAC 61G1-16.002 & FS 481.306. SHTS LS-1 & LS-2 ARE NOT
 SIGNED, SEALED OR DATED.
  
 *****NEW COMMENTS 3RD REVIEW*****
  
 1C. SHT P-1 SHOWS THE CLEANOUTS AT THE GREASE LINE &
 SANT. LINES NEAR THE GREASE INTERCEPTOR & THE BUILDING
 SEWER LOCATED UNDER AN A/C COMPRESSOR & IN A WALL.
 CLEANOUTS SHALL BE ACCESSIBLE PER TABLE 708.9. ALSO THE
 A/C UNITS ARE LOCATED OVER THE TOP OF THE GREASE
 INTERCEPTOR WHICH ALSO REQUIRES ACCESS TO SERVICE.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 2C. SHT P-1 WATER ISOMETRIC RISER DIAGRAM DOES NOT SHOW
 WATER SUPPLY TO THE MOP SINK NOR TO THE ICE MAKER,
 (WHICH REQUIRES A WATER HAMMER ARRESTOR). PLEASE
 CLARIFY. SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-04-09 Cont ID  
Sent By kstevens Date 2007-04-09 Time 17:39 Rev Time 0.00
Received By kstevens Date 2007-04-09 Time 17:39 Sent To  
Notes
2007-04-09 17:50:33DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 FROM PREVIOUS REVIEW:
  
 1. SHT C-1 INDICATES "NEW CONVENIENCE STORE/PROPOSED
 BUILDING", BUT NOTES ON SHT A-1 INDICATE AN EXISTING
 BUILDING. PLEASE CLARIFY. SECTION 106.1.1.
 ****NO RESPONSE, NOT ADDRESSED.
  
 2. SUBMIT A DETAIL FOR THE TOILET ROOM. SHOW COMPLIANCE
 WITH SECTIONS 11-4.16, 11-4.19, 11-4.22 AND ALL
 SUBSECTIONS.
 ****NO RESPONSE, NOT ADDRESSED.
 SHOW THE FOLLOWING:
 ____FOR W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.3 HEIGHT
 C. 11-4.16.4 GRAB BARS
 D. 11-4.16.5 FLUSH CONTROLS
 E. 11-4.16.6 DISPENSERS
 ____FOR LAVS:
 A. 11-4.19.4 EXPOSED PIPES & SURFACES
 B. 11-4.19.5 FAUCETS
  
 3. A GREASE INTERCEPTOR MAY BE REQUIRED. PLEASE CONTACT
 LYNN MASSON, ENVIRONMENTAL COMPLIANCE MANAGER, PHONE
 NUMBER (561) 822-2271, FAX (561) 822-2279, OR E-MAIL
 [email protected]. WASTE ORD. 3434.
 ****NO RESPONSE, NOT ADDRESSED.
  
 4. PER TABLE 403.1 A DRINKING FOUNTAIN IS REQUIRED.
 PLEASE INDICATE THE LOCATION ON THE FLOOR PLAN. SUBMIT
 A DETAIL SHOWING COMPLIANCE WITH SECTION 11-4.15 AND
 ALL SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING. SHOW DRINKING FOUNTAIN ON THE SANT. AND WATER
 RISER DIAGRAMS.
 ****NO RESPONSE, NOT ADDRESSED.
  
 5. SHT A-1 GENERAL NOTES #1. THE CODE ADOPTED IS
 FBC-2004 NOT FBC-2001 AS INDICATED. PLEASE UPDATE YOUR
 NOTES TO REFLECT THE CODE IN EFFECT.
 ****NO RESPONSE, NOT ADDRESSED.
  
 6. SHT P-1THE SANITARY PLUMBING RISER DOES NOT MEET
 CODE. HORIZONTAL DRY VENTS ARE NOT APPROVED. SECTION
 905.3. - THE 3" VENT UPSTREAM OF THE W/C IS NOT
 REQUIRED. THE 2" VENT AT THE LAV IS SUFFICIENT. ****NO
 RESPONSE, NOT ADDRESSED.
  
 7. SHT P-1 THE GREASE PLUMBING RISER DOES NOT MEET
 CODE. THE 3 COMPARTMENT SINK AND THE HAND SINK ARE NOT
 VENTED. (MISLABELED AS LAVS). ALSO EQUIPMENT AND
 FIXTURES UTILIZED FOR THE STORAGE, PREPARATION AND
 HANDLING OF FOOD SHALL DISCHARGE THROUGH AN INDIRECT
 PIPE BY MEANS OF AN AIR GAP. (A FLOOR SINK WOULD BE
 REQUIRED). SECTIONS 802.1.1 AND 901.2.1.
 ****NO RESPONSE, NOT ADDRESSED.
  
 8. SUBMIT A WATER RISER DIAGRAM. SHOW ALL PIPE SIZES,
 VALVES, AND REQUIRED WATER HAMMER ARRESTORS, (ICE
 MACHINE). SECTIONS 106.3.5.1.3 & 604.9.
 ****NO RESPONSE, NOT ADDRESSED.
  
 9. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE TO
 THE BUILDING. SECTION 608.13.2.
 ****NO RESPONSE, NOT ADDRESSED.
  
 10. SHT A-1 INDICATES GAS EQUIPMENT IN THE KITCHEN. A
 SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE FOLLOWING
 INFORMATION:
 ****NO RESPONSE, NOT ADDRESSED.
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ****NO RESPONSE, NOT ADDRESSED.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 ****NO RESPONSE, NOT ADDRESSED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
 ****NO RESPONSE, NOT ADDRESSED.
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 ****NO RESPONSE, NOT ADDRESSED.
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ****NO RESPONSE, NOT ADDRESSED.
  
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
 ****NO RESPONSE, NOT ADDRESSED.
  
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. IF 2 PSI SHOW THE
 LOCATION OF THE REGULATORS, SUBMIT MANUF.
 SPECIFICATIONS FOR THE REGULATORS AND IF THE REGULATORS
 ARE VENTED, INDICATE THE MATERIAL OF THE VENT AND SHOW
 THE PIPING LOCATION.
 ****NO RESPONSE, NOT ADDRESSED.
  
 H. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
 ****NO RESPONSE, NOT ADDRESSED.
  
 I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****NO RESPONSE, NOT ADDRESSED.
  
 J. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 ****NO RESPONSE, NOT ADDRESSED.
  
 K. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 ****NO RESPONSE, NOT ADDRESSED.
  
 L. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 ****NO RESPONSE, NOT ADDRESSED.
  
 **********NEW COMMENTS**********
  
 1B. PLEASE SEE ELECTRICAL COMMENTS #3 & #4 CONCERNING
 TITLE BLOCKS, SEALS, PRINTED NAMES REQUIRE BY THE
 FLORIDA ADMINISTRATIVE CODE AND THE FLORIDA STATUTES.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-01-03 Cont ID  
Sent By kstevens Date 2007-01-03 Time 08:35 Rev Time 0.00
Received By kstevens Date 2007-01-03 Time 08:35 Sent To  
Notes
2007-01-03 09:53:04DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHT C-1 INDICATES "NEW CONVENIENCE STORE/PROPOSED
 BUILDING", BUT NOTES ON SHT A-1 INDICATE AN EXISTING
 BUILDING. PLEASE CLARIFY. SECTION 106.1.1.
  
 2. SUBMIT A DETAIL FOR THE TOILET ROOM. SHOW COMPLIANCE
 WITH SECTIONS 11-4.16, 11-4.19, 11-4.22 AND ALL
 SUBSECTIONS.
  
 3. A GREASE INTERCEPTOR MAY BE REQUIRED. PLEASE CONTACT
 LYNN MASSON, ENVIRONMENTAL COMPLIANCE MANAGER, PHONE
 NUMBER (561) 822-2271, FAX (561) 822-2279, OR E-MAIL
 [email protected]. WASTE ORD. 3434.
  
 4. PER TABLE 403.1 A DRINKING FOUNTAIN IS REQUIRED.
 PLEASE INDICATE THE LOCATION ON THE FLOOR PLAN. SUBMIT
 A DETAIL SHOWING COMPLIANCE WITH SECTION 11-4.15 AND
 ALL SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING. SHOW DRINKING FOUNTAIN ON THE SANT. AND WATER
 RISER DIAGRAMS.
  
 5. SHT A-1 GENERAL NOTES #1. THE CODE ADOPTED IS
 FBC-2004 NOT FBC-2001 AS INDICATED. PLEASE UPDATE YOUR
 NOTES TO REFLECT THE CODE IN EFFECT.
  
 6. SHT P-1THE SANITARY PLUMBING RISER DOES NOT MEET
 CODE. HORIZONTAL DRY VENTS ARE NOT APPROVED. SECTION
 905.3. - THE 3" VENT UPSTREAM OF THE W/C IS NOT
 REQUIRED. THE 2" VENT AT THE LAV IS SUFFICIENT.
  
 7. SHT P-1 THE GREASE PLUMBING RISER DOES NOT MEET
 CODE. THE 3 COMPARTMENT SINK AND THE HAND SINK ARE NOT
 VENTED. (MISLABELED AS LAVS). ALSO EQUIPMENT AND
 FIXTURES UTILIZED FOR THE STORAGE, PREPARATION AND
 HANDLING OF FOOD SHALL DISCHARGE THROUGH AN INDIRECT
 PIPE BY MEANS OF AN AIR GAP. (A FLOOR SINK WOULD BE
 REQUIRED). SECTIONS 802.1.1 AND 901.2.1.
  
 8. SUBMIT A WATER RISER DIAGRAM. SHOW ALL PIPE SIZES,
 VALVES, AND REQUIRED WATER HAMMER ARRESTORS, (ICE
 MACHINE). SECTIONS 106.3.5.1.3 & 604.9.
  
 9. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE TO
 THE BUILDING. SECTION 608.13.2.
  
 10. SHT A-1 INDICATES GAS EQUIPMENT IN THE KITCHEN. A
 SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE FOLLOWING
 INFORMATION:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. IF 2 PSI SHOW THE
 LOCATION OF THE REGULATORS, SUBMIT MANUF.
 SPECIFICATIONS FOR THE REGULATORS AND IF THE REGULATORS
 ARE VENTED, INDICATE THE MATERIAL OF THE VENT AND SHOW
 THE PIPING LOCATION.
  
 H. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 J. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 K. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 L. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop X PERMIT EXTENSION
Rev No 1 Status N Date 2010-07-22 Cont ID  
Sent By rbrown Date 2010-07-22 Time 18:55 Rev Time 0.00
Received By rbrown Date 2010-07-22 Time 18:55 Sent To  
Notes
2010-07-22 18:55:53PERMIT APPLICATION EXTENDED UNTIL 9/16/10. LETTER IN
 FILE.

Review Stop Z ZONING
Rev No 5 Status P Date 2009-09-21 Cont ID  
Sent By kdfreema Date 2009-09-21 Time 13:39 Rev Time 0.00
Received By kdfreema Date 2009-09-21 Time 13:39 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2009-06-11 Cont ID  
Sent By kdfreema Date 2009-06-11 Time 11:02 Rev Time 0.00
Received By kdfreema Date 2009-06-11 Time 11:02 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2007-10-25 Cont ID  
Sent By kdfreema Date 2007-10-25 Time 16:05 Rev Time 0.00
Received By kdfreema Date 2007-10-25 Time 16:05 Sent To  
Notes
2007-10-25 16:52:13***FAILED***
  
 1. PLEASE PROVIDE A RESPONSE TO ALL COMMENTS IN
 WRITING.
  
 2. A LETTER FROM THE CITY'S ENGINEERING SERVICES
 DEPARTMENT MUST BE PROVIDED APPROVING THE NEW DUMPSTER
 APPROACH CONFIGURATION.
  
 3. THE DUMPSTER ENCLOSURE MUST BE LANDSCAPED ON ITS
 EAST SIDE.
  
 4. THE GENERATOR ENCLOSURE MUST BE LANDSCAPED ON ITS
 SOUTH AND EAST SIDES.
  
 5. THE GENERATOR ENCLOSURE DOORS MAY NOT OPEN INTO THE
 HANDICAP ACCESS AISLE.
  
 6. ALL PARKING ROWS MUST BE TERMINATED WITH A SHADE
 TREE.
  
 7. PLEASE CORRECT THE PARKING LOT STRIPING DETAIL TO
 CONFORM TO THE CITY OF WPB REQUIREMENTS.
  
 8. ENSURE THAT SPECIES SYMBOLS ARE CONSISTENT ACROSS
 SPECIES.
  
 9. MAKE SURE THAT ALL PLANT COUNTS ARE CONSISTENT
 ACROSS THE TABLE, NUMBER OF SYMBOLS SHOWN, AND NUMBER
 CALLED OUT ON THE PLANS.
  
 10. PLEASE FOLLOW THE FPL RIGHT TREE RIGHT PLACE
 GUIDELINES WITH RESPECT TO TREE SELECTION. THE COCONUT
 PALMS AT THE NORTHEAST AND SOUTHEAST CORNERS OF THE LOT
 ARE UNDER OVERHEAD POWERLINES, PLEASE REPLACE THEM WITH
 LOWER TREES.
  
 11. PLEASE CLARIFY WHERE ALL OF THE EXISTING PLANT
 MATERIAL TO BE REUSED IS LOCATED. NOTE THAT ALL
 MATERIAL TO BE REUSED MUST BE FLORIDA #1 OR GREATER.
  
 12. THE PARALLEL PARKING SPACES SHOWN AT THE SOUTHEAST
 CORNER ARE TOO SHORT; THE MINIMUM LENGTH IS 22 FEET.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1435
 OR [email protected] WITH QUESTIONS.

Review Stop Z ZONING
Rev No 2 Status F Date 2007-03-27 Cont ID  
Sent By kdfreema Date 2007-03-27 Time 10:06 Rev Time 0.00
Received By kdfreema Date 2007-03-27 Time 10:06 Sent To  
Notes
2007-03-27 10:52:05**FAILED**
  
 1. ALL SURVEYS MUST BEAR AN ORIGINAL SIGNATURE AND
 RAISED SEAL.
  
 2. NO SITE PLAN WAS PROVIDED.
  
 3. THE PROPOSED GENERATOR AS WELL AS ALL EXTERIOR
 MECHANICAL EQUIPMENT MUST BE SHOWN ON BOTH THE SITE
 PLAN AND LANDSCAPE PLAN.
  
 4. PLEASE NOTE THAT ALTHOUGH THE ZONING CODE ALLOWS
 GENERATORS TO BE PLACED AS CLOSE TO 1 FOOT FROM THE
 PROPERTY LINE IN THIS ZONING DISTRICT, OTHER TRADES MAY
 REQUIRE A GREATER SEPARATION DISTANCE.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1435
 WITH ANY QUESTIONS.

Review Stop Z ZONING
Rev No 1 Status F Date 2009-07-27 Cont ID  
Sent By kdfreema Date 2006-11-16 Time 11:10 Rev Time 0.00
Received By kdfreema Date 2006-11-16 Time 11:10 Sent To  
Notes
2006-11-16 11:17:54**FAILED**
  
 COPIES OF YOUR SITE PLAN, LANDSCAPE PLAN, AND PROPERTY
 SURVEY SHALL BE PROVIDED.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT (561)822-1435
 WITH QUESTIONS.
  