Plan Review Details - Permit 06101137
Plan Review Stops For Permit 06101137
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-08-28 Cont ID  
Sent By jjohnsto Date 2007-08-28 Time 16:29 Rev Time 2.30
Received By jjohnsto Date 2007-08-28 Time 16:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-07-05 Cont ID  
Sent By jwitmer Date 2007-07-05 Time 14:49 Rev Time 0.77
Received By jwitmer Date 2007-07-05 Time 14:48 Sent To PC
Notes
2007-07-05 14:51:01BUILDING PLAN REVIEW
 PERMIT: 06101137
 ADD: 717 S OLIVE AVE
 CONT: SUPERIOR POOL & SPA
 TEL: (954) 578-1011
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)COMPLIED.
  
 3) 13-412.1.ABC.2.6.2 POOL COVERS.
 HEATED POOLS SHALL BE EQUIPPED WITH A VAPOR RETARDANT
 POOL COVER ON OR AT THE WATER SURFACE. POOLS HEATED TO
 MORE THAN 90?F (32?C) SHALL HAVE A POOL COVER WITH A
 MINIMUM INSULATION VALUE OF R -12.
 EXCEPTION: POOLS DERIVING OVER 60 PERCENT OF THE ENERGY
 FOR HEATING FROM SITE-RECOVERED ENERGY OR SOLAR ENERGY
 SOURCE.
  
 4) PLANS DO NOT SHOW AN ACCESSIBLE ROUTE TO THE
 POOL/SPA DECK AND POOL, ONLY STAIRS ARE EVIDENT? PLEASE
 INDICATE THE
 ACCESSIBLE PATH? 11-4.1.2.
  
 5 ) COMPLIED.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-11-21 Cont ID  
Sent By jwitmer Date 2006-11-21 Time 09:11 Rev Time 2.22
Received By jwitmer Date 2006-11-21 Time 09:11 Sent To  
Notes
2006-11-21 09:34:16BUILDING PLAN REVIEW
 PERMIT: 06101137
 ADD: 717 S OLIVE AVE
 CONT: SUPERIOR POOL & SPA
 TEL: (954) 578-1011
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) DISCREPANCY, PLEASE CORRECT THE ADDRESS OF THE
 PERMIT APPLICATION.
  
 3) 13-412.1.ABC.2.6.2 POOL COVERS.
 HEATED POOLS SHALL BE EQUIPPED WITH A VAPOR RETARDANT
 POOL COVER ON OR AT THE WATER SURFACE. POOLS HEATED TO
 MORE THAN 90?F (32?C) SHALL HAVE A POOL COVER WITH A
 MINIMUM INSULATION VALUE OF R -12.
 EXCEPTION: POOLS DERIVING OVER 60 PERCENT OF THE ENERGY
 FOR HEATING FROM SITE-RECOVERED ENERGY OR SOLAR ENERGY
 SOURCE.
  
 4) PLANS DO NOT SHOW AN ACCESSIBLE ROUTE TO THE
 POOL/SPA DECK AND POOL, ONLY STAIRS ARE EVIDENT? PLEASE
 INDICATE THE
 ACCESSIBLE PATH? 11-4.1.2.
  
 5) PERMIT FEES ARE TO BE PAID AT TIME OF
 APPLICATION.!!!
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-08-01 Cont ID  
Sent By dpalmer Date 2007-08-01 Time 16:28 Rev Time 0.00
Received By dpalmer Date 2007-08-01 Time 16:28 Sent To  
Notes
2007-08-01 16:28:19*** REDLINED PLANS***
  
 A NOTE PLACED ON PLANS BELOW PANEL SCHEDULES ON SHEET 3
 OF 10 MENTIONS THAT THE PANELS ARE FED W/#6 CONDUCTORS
 FED FROM TRANSFORMERS ETC.
 THIS NOTE CAN NOT POSSIBLY APPLY TO THESE PLANS AS IT
 DOES MATCH WITH BASE BUILDING PLANS OR EITHER OF THE
 TWO PANEL(S) OR SCHEDULE(S) PROVIDED.
 THIS NEEDS TO BE REVISED AT A LATE DATE BEFORE
 INSPECTIONS FOR FINALS.
 IF PLANS ARE RETURNED WITH COMMENTS FROM OTHER TRADES
 PLEASE ADDRESS.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-07-06 Cont ID  
Sent By dpalmer Date 2007-05-02 Time   Rev Time 0.00
Received By dpalmer Date 2007-05-02 Time   Sent To  
Notes
2007-07-06 07:23:54SEE NOTES UNDER 06100587

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-07-06 Cont ID  
Sent By dpalmer Date 2007-02-11 Time   Rev Time 0.00
Received By dpalmer Date 2007-02-11 Time   Sent To  
Notes
2007-07-06 07:24:12SEE NOTES UNDER 06100587

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-05-03 Cont ID  
Sent By dpalmer Date 2006-10-27 Time 08:39 Rev Time 0.00
Received By dpalmer Date 2006-10-27 Time 16:49 Sent To  
Notes
2007-05-03 08:40:04SEE REVIEWS ALL DONE UNDER 06100587

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status N Date 2007-08-21 Cont ID  
Sent By rbrown Date 2007-08-21 Time 11:08 Rev Time 0.00
Received By rbrown Date 2007-08-21 Time 11:08 Sent To  
Notes
2007-08-21 11:11:52PLANS REVIEWED FOR COMPLIANCE WITH NEC BY ELECTRICAL
 REVIEWER

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-06-14 Cont ID  
Sent By mcarsill Date 2007-06-14 Time 11:12 Rev Time 0.00
Received By mcarsill Date 2007-06-14 Time 11:11 Sent To  
Notes
2007-06-14 11:12:481. ELECTRIC FOR THE POOL, SPA. AND FOUNTAIN SHALL
 COMPLY WITH THE APPROPRIATE SECTION OF THE NATIONAL
 ELECTRIC CODE.
  
 2. WHEN COMPLETED, THE INSTALLATION SHALL BE IN A
 QAULITY MANNER.
  
 MIKE CARSILLO, BATTALION CHIEF OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-05-02 Cont ID  
Sent By adarroug Date 2008-05-02 Time 14:55 Rev Time 0.00
Received By adarroug Date 2008-05-02 Time 14:55 Sent To P
Notes
2008-05-02 14:56:02TO "P" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-07-23 Cont ID  
Sent By adarroug Date 2007-07-23 Time 14:55 Rev Time 0.00
Received By adarroug Date 2007-07-23 Time 14:55 Sent To  
Notes
2007-08-01 13:51:20TO "COMM" BD#18
2007-07-23 14:55:37WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-04-24 Cont ID  
Sent By adarroug Date 2007-04-24 Time 08:35 Rev Time 0.00
Received By adarroug Date 2007-04-24 Time 08:35 Sent To  
Notes
2007-05-02 13:30:09TO "COMM" BD#24
2007-04-24 08:36:04WAITING FOR "COMM" BD

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-05-20 Cont ID  
Sent By kstevens Date 2008-05-20 Time 10:15 Rev Time 0.00
Received By kstevens Date 2008-05-20 Time 10:15 Sent To  
Notes
2008-05-20 10:16:08SUBMITTAL APPROVED FOR COLLECTOR TANK

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-08-31 Cont ID  
Sent By kstevens Date 2007-08-31 Time 09:46 Rev Time 0.00
Received By kstevens Date 2007-08-31 Time 09:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-06-09 Cont ID  
Sent By kstevens Date 2007-06-09 Time 06:52 Rev Time 0.00
Received By kstevens Date 2007-06-09 Time 06:52 Sent To  
Notes
2007-06-09 06:54:37DENIED
 REFERENCE: FBC-2004 CHAPTER 4 SECTION 424.1
  
 ****FROM PREVIOUS REVIEW:
  
 1. SHT 7 OF 10. INDICATE THE LOCATION OF THE SPA JETS.
 (6 INDICATED ON THE SCHEDULE). SECTION 106.1.1.
 ****NO RESPONSE/NOT ADDRESSED
  
 2. SHT 8 OF 10. INDICATE THE LOCATION OF THE HOSE BIBB
 REQUIRED IN THE EQUIPMENT ROOM. SECTION 424.1.5.9.
 ****NO RESPONSE/NOT ADDRESSED
  
 3. SHT 8A OF 10. OVERFLOW FROM THE POOL AND SPA
 COLLECTING TANKS SHALL CONNECT TO THE STORM SYSTEM, NOT
 THE SANITARY. PLEASE INDICATE ON THE PLANS.
 ****NO RESPONSE/NOT ADDRESSED
  
 4. A SOLAR BLANKET WILL BE REQUIRED PER SECTION
 13-612.1.ABC.2.3.2. - MANUF. SPECIFICATION SHEETS DO
 NOT INDICATE IF THE REQUIREMENT CAN BE EXEMPT FROM THIS
 REQUIREMENT. (SEE SECTION BELOW).
  
 13-612.1.ABC.2.3.2 COVERS REQUIRED.
 SPAS AND HEATED SWIMMING POOLS SHALL BE EQUIPPED WITH A
 COVER DESIGNED TO MINIMIZE HEAT LOSS.
 EXCEPTION : OUTDOOR POOLS DERIVING OVER 70 PERCENT OF
 THE ENERGY FOR HEATING FROM NONDEPLETABLE ON
 SITE-RECOVERED SOURCES COMPUTED OVER AN OPERATING
 SEASON ARE EXEMPT FROM THIS REQUIREMENT.
 ****NO RESPONSE/NOT ADDRESSED
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-12-07 Cont ID  
Sent By kstevens Date 2006-12-07 Time 11:35 Rev Time 0.00
Received By kstevens Date 2006-12-07 Time 11:35 Sent To Z
Notes
2006-12-07 11:36:16DENIED
 REFERENCE: FBC-2004 CHAPTER 4 SECTION 424.1
  
 1. SHT 7 OF 10. INDICATE THE LOCATION OF THE SPA JETS.
 (6 INDICATED ON THE SCHEDULE). SECTION 106.1.1.
  
 2. SHT 8 OF 10. INDICATE THE LOCATION OF THE HOSE BIBB
 REQUIRED IN THE EQUIPMENT ROOM. SECTION 424.1.5.9.
  
 3. SHT 8A OF 10. OVERFLOW FROM THE POOL AND SPA
 COLLECTING TANKS SHALL CONNECT TO THE STORM SYSTEM, NOT
 THE SANITARY. PLEASE INDICATE ON THE PLANS.
  
 4. A SOLAR BLANKET WILL BE REQUIRED PER SECTION
 13-612.1.ABC.2.3.2. - MANUF. SPECIFICATION SHEETS DO
 NOT INDICATE IF THE REQUIREMENT CAN BE EXEMPT FROM THIS
 REQUIREMENT. (SEE SECTION BELOW).
  
 13-612.1.ABC.2.3.2 COVERS REQUIRED.
 SPAS AND HEATED SWIMMING POOLS SHALL BE EQUIPPED WITH A
 COVER DESIGNED TO MINIMIZE HEAT LOSS.
 EXCEPTION : OUTDOOR POOLS DERIVING OVER 70 PERCENT OF
 THE ENERGY FOR HEATING FROM NONDEPLETABLE ON
 SITE-RECOVERED SOURCES COMPUTED OVER AN OPERATING
 SEASON ARE EXEMPT FROM THIS REQUIREMENT.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2007-08-03 Cont ID  
Sent By aaponte Date 2007-08-03 Time 13:53 Rev Time 0.00
Received By aaponte Date 2007-08-03 Time 13:53 Sent To  
Notes
2007-08-03 13:56:37APPROVAL FOR SPA ONLY. LOCATION AND POOL DECK DESIGN
 SHALL FOLLOW APPROVAL ON MAIN BUILDING PERMIT.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-05-11 Cont ID  
Sent By astelly Date 2007-05-11 Time 13:23 Rev Time 0.00
Received By astelly Date 2007-05-11 Time 13:23 Sent To  
Notes
2007-05-11 13:32:13AMY F. STELLY
 URBAN DESIGN
 822-1440
  
 PLEASE SUBMIT A ROOF TERRACE PLAN SHOWING
 1. TOTAL GROSS ROOF AREA
 2. PERCENTAGE OF LANDSCAPED AREA
 3. PERCENTAGE OF GROSS AREA FOR COVERED STRUCTURES. AS
 PER ARTICLE IV, SEC. 94-109(C)(5)G.2, WHIRLPOOLS AND
 POOLS MUST BE SURROUNDED BY A 5-FOOT MINIMUM WALKWAY.
 SUPPORTING RESTROOM FACILITIES MUST BE INCLUDED IN THE
 CALCULATIONS FOR COVERED STRUCTURES.
 PLEASE INDICATE HEIGHT OFTERRACE'S SURROUNDING
 PARAPET WALL ON DRAWINGS.