Plan Review Details - Permit 06101122
Plan Review Stops For Permit 06101122
Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status P Date 2009-01-08 Cont ID  
Sent By jgomez Date 2009-01-08 Time 16:09 Rev Time 0.00
Received By jgomez Date 2009-01-08 Time 16:09 Sent To PC
Notes
2009-01-08 16:09:43REVISED RAS 117 CALCULATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status F Date 2008-12-29 Cont ID  
Sent By jgomez Date 2008-12-29 Time 12:53 Rev Time 0.00
Received By jgomez Date 2008-12-29 Time 11:07 Sent To PC
Notes
2008-12-29 13:04:49BUILDING SUBMITTAL CHECKLIST:
  
 1- ENGINEER'S NAIL ENHANCING LETTER SUBMITTED FOR
 POLYGLASS MODIFIED BITUMEN ROOFING SYSTEM DOESN'T WORK
 FOR ZONE #3. ENGINEER TO PROVIDE THE CALCULATED DESIGN
 PRESSURES FOR ALL ZONES IN EXPOSURE "C" AS SPECIFIED ON
 LETTER SUBMITTED. AND, PROVIDE ACTUAL RAS 117
 CALCULATIONS. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004
 TO VERIFY COMPLIANCE WITH RAS 117 CALCULATIONS AND
 DESIGN PRESSURES OF SEC. R301 OF 2004 FLORIDA
 RESIDENTIAL CODE.
 NOTE: ENGINEER TO REVIEW SEC. 8.1 OF RAS 117 FOR
 MINIMUM FASTENER SEPARATION SPACING ALLOWED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2008-12-23 Cont ID  
Sent By jgomez Date 2008-12-23 Time 10:54 Rev Time 0.00
Received By jgomez Date 2008-12-23 Time 10:54 Sent To PC
Notes
2008-12-23 10:55:02ROOFING REVISION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2008-10-06 Cont ID  
Sent By jgomez Date 2008-10-06 Time 09:48 Rev Time 0.00
Received By jgomez Date 2008-10-06 Time 09:46 Sent To PC
Notes
2008-10-06 10:05:29RESIDENTIAL (R3) REVISION BUILDING REVIEW THIRD
 CHECKLIST:
  
 OLD COMMENT:
 1- STAIR DETAIL ON SHEET D-1 CALLS FOR 18 RISERS, WHILE
 FLOOR PLANS SHOW 17 RISERS. REVISE AS REQUIRED TO MATCH
 AND SHOW COMPLIANCE WITH SEC. R311.5.3.2 OF 2004
 FLORIDA RESIDENTIAL CODE. (REPEAT COMMENT).
  
 ***COMMENT BASED ON RESPONSE:
 NOW STAIRS SHOW 19 RISERS WITH 7 3/4" RISERS AND 10"
 TREADS. THIS STAIR RISER/TREAD RATION DOESN'T COMPLY
 WITH SEC. R311.5.3.2 OF 2004 RESIDENTIAL CODE. REVISE
 AS REQUIRED TO COMPLY WITH THIS CODE SECTION.
  
 OLD COMMENT:
 2- ENGINEER TO REVISE RAS 117 CALCULATIONS. (REPEAT
 COMMENT). FASTENERS CAN'T BE SPACED LESS THAN 4"O.C..
 SEE SEC. 8.1 OF RAS 117. 2 ROWS IN THE LAP WILL HAVE
 THE FASTENERS SPACED AT LESS THAN 4" O.C..
 PROVIDE CALCULATIONS SHOWING HOW THE 2 ROWS AT LAP AND
 THE 3 ROWS IN THE CENTER OF THE SHEET WILL SATISFY THE
 NAIL ENHANCEMENT CALCULATIONS TO RESIST THE
 CALCULATED DESIGN PRESSURES. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004 TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 ***COMMENT BASED ON RESPONSE:
 ENGINEER STILL SHOWS TWO ROWS AT THE LAP. THIS IS NOT
 ALLOWED BECAUSE FASTENERS CAN'T BE SPACED LESS THAN
 4"O.C..
 IN ADDITION, ENGINEER'S RESPONSE IN WRITING IS NOT
 CLEAR. PROVIDE DRAWING SHOWING THE NAILING SPACING AND
 NUMBER OF ROWS. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004 TO VERIFY COMPLIANCE WITH CALCULATED DESIGN
 PRESSURES OF SEC. R301 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 OLD COMMENT:
 3- PROVIDE COMPLETE PRODUCT APPROVAL REPORT. ONLY THE
 PAGE 43 OF 44 WAS SUBMITTED. SUBMIT THE FRONT COVER
 PAGES OF THE NOA , THE SHEET WHERE SELECTED ASSEMBLY IS
 SHOWN AND THE LAST PAGE OF THE NOA WITH THE GENERAL
 LIMITATIONS.
  
 ***COMMENT BASED ON RESPONSE:
 INFORMATION WAS NOT PROVIDED AT ALL.
  
 4- OWES $70.00. REVISION SUBMITTED HAS 9 DRAWINGS AND
 ONE ENGINEER LETTER/PRODUCT APPROVAL. REVISION FEES ARE
 $50.00 PLUS $10.00 PER PLAN/PAGE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2008-08-08 Cont ID  
Sent By jgomez Date 2008-08-08 Time 15:31 Rev Time 0.00
Received By jgomez Date 2008-08-08 Time 12:54 Sent To PC
Notes
2008-08-08 16:06:47RESIDENTIAL (R3) REVISION BUILDING REVIEW SECOND
 CHECKLIST:
  
 1- STAIR DETAIL ON SHEET D-1 CALLS FOR 18 RISERS, WHILE
 FLOOR PLANS SHOW 17 RISERS. REVISE AS REQUIRED TO MATCH
 AND SHOW COMPLIANCE WITH SEC. R311.5.3.2 OF 2004
 FLORIDA RESIDENTIAL CODE. (REPEAT COMMENT).
  
 2- ENGINEER TO REVISE RAS 117 CALCULATIONS. (REPEAT
 COMMENT). FASTENERS CAN'T BE SPACED LESS THAN 4"O.C..
 SEE SEC. 8.1 OF RAS 117. 2 ROWS IN THE LAP WILL HAVE
 THE FASTENERS SPACED AT LESS THAN 4" O.C..
 PROVIDE CALCULATIONS SHOWING HOW THE 2 ROWS AT LAP AND
 THE 3 ROWS IN THE CENTER OF THE SHEET WILL SATISFY THE
 NAIL ENHANCEMENT CALCULATIONS TO RESIST THE
 CALCULATED DESIGN PRESSURES. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004 TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 3- PROVIDE COMPLETE PRODUCT APPROVAL REPORT. ONLY THE
 PAGE 43 OF 44 WAS SUBMITTED. SUBMIT THE FRONT COVER
 PAGES OF THE NOA , THE SHEET WHERE SELECTED ASSEMBLY IS
 SHOWN AND THE LAST PAGE OF THE NOA WITH THE GENERAL
 LIMITATIONS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2008-06-24 Cont ID  
Sent By jgomez Date 2008-06-24 Time 16:57 Rev Time 0.00
Received By jgomez Date 2008-06-24 Time 16:57 Sent To PC
Notes
2008-06-24 16:58:26RESIDENTIAL (R3) BUILDINGG REVIEWREVISION CHECKLIST:
  
 1- PROVIDE SOIL TEST REPORT (2 COPIES) AFTER HOUSE AND
 POOL ARE REMOVED. ENGINEER OF RECORD TO REVIEW SOIL
 TEST REPORT TO VERIFY IF SOILS WILL MEET HIS DESIGN
 CRITERIA PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 2- IF BBQ GRILL IS NOT GOING TO BE INSTALLED, THEN,
 REVISE ORIGINAL DRAWINGS.
  
 3- PROVIDE CLEAR DETAILS AND SPECS FOR STAIRS TO SHOW
 COMPLIANCE WITH WINDERS DIMENSIONS OF SEC. R311.5.3.2
 OF 2004 FLORIDA RESIDENTIAL CODE AND LIVE LOADS AS
 REQUIRED BY TABLE R301.5. (REPEAT COMMENT). PROVIDE
 DETAILS WITHWRITTEN DIMENSIONS. ALSO,FLOOR PLANS
 SHOW 17 RISERS, WHILE STAIR SECTIONCALLS FOR 18
 RISERS.REVISE AS REQUIRED,ALSO, STAIRS ON 2ND FLOOR
 PLAN ARE SHOWN AS DOTTED LINES INSTEAD OF SOLID LINES.
 REVISE AS REQUIRED.
  
 REVISE SPECIFICATIONS FOR RAILING PICKETS AND MINIMUM
 TREAD SIZES SHOWN ON TYPICAL STAIR DETAIL ON SHEET D-1.
 SEE COMMENTS ON REVIEWED SET.EG: SPECS FOR PICKET
 SPACING SAYS THAT 4" SPHERE MAY PASS THRU INSTEAD OF
 MAY NOT PASS THRU.AND, SPECS FOR MINIMUM TREAD SIZE
 ARE NOT CLEAR. REVISE AS REQUIRED.
  
 4- SURVEY TO HAVE ORIGINAL SIGNATURE, NOT COPY AS
 REQUIRED BY SEC. 61G17-7.0025 FLORIDA ADMINISTRATIVE
 CODE.
  
 5-ENGINEER TO REVISE RAS 117 CALCULATIONS.
 FASTENERS CAN'T BE SPACED LESS THAN 4". O.C..SEE SEC.
 8.1 OF RAS 117 AND REVISE AS REQUIRED.
  
 6-ENERGY CALCULATIONS:
 A) REVISE CEILING INSULATION R-VALUE TO MATCH PLANS.
 NEED R-30. SEE PLANS.
  
 B) PROVIDE COMPLETE ENERGY CALCULATIONS. ONLY 2
 SHEETS WERE SUBMITTED.
  
 7- ENGINEER NEEDS TO REVISE DESIGN CRITERIA.ACCORDING
 TO SEC. R301.2.1.4(3) THIS BUILDING IS CONSIDERED TO BE
 EXPOSURE "C", NOT "B".REVISEINFORMATION ON SHEET
 S-2 AND WHERE THE DESIGN PRESSURES FOR OPENINGS ARE
 PROVIDED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-03-13 Cont ID  
Sent By jgomez Date 2008-03-13 Time 10:16 Rev Time 0.00
Received By jgomez Date 2008-03-13 Time 10:06 Sent To PC
Notes
2008-03-13 10:17:31IMPACT FEES PAID AND NOC RE-RECORDED.
 ***NOTE: SEE PROVISO DATED 2-5-08.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-03-13 Cont ID  
Sent By jgomez Date 2008-02-05 Time 13:09 Rev Time 0.00
Received By jgomez Date 2008-02-05 Time 13:09 Sent To PC
Notes
2008-02-05 13:50:08BUILDING REVIEW APPROVED WITH PROVISO:
 1- REVISE SOIL TEST REPORT TO REFLECT REVISED PROPOSED
 SCOPE OF WORK.
 2- PROVIDE MANUFACTURER SPECS FOR BBQ GRILL TO BE
 INSTALLED IN PORCH.PAGE III OF SPECSSUBMITTED DON'T
 ALLOWBBQ GRILL ON PORCH.
 3- PROVIDE CLEAR DETAILS AND SPECS FOR STAIRS TO SHOW
 COMPLIANCE WITH WINDERS DIMENSIONS OF SEC. R311.5.3.2
 OF 2004 FLORIDA RESIDENTIAL CODE AND LIVE LOADS AS
 REQUIRED BY TABLE R301.5.
 ALSO, REVISE CODE REFERENCES SHOWN ON TYPICAL STAIR
 DETAIL ON SHEET D-1. SEE SEC. R311.5 OF 2004 FLORIDA
 RESIDENTIAL CODE FOR PROPER CODE SECTIONS TO BE
 REFERENCED.
 4- SPECIFY DRAFSTOPPING ON SECOND FLOOR PLANAS
 REQUIRED BY SEC. R502.1.2 OF 2004 FLORIDA RESIDENTIAL
 CODE.
 5- THIS PROPERTY IS LOCATED ON FLOOD ZONE "C", NOT "B".
 REVISE SURVEY AS REQUIRED.
 6- PROVIDE COMPLETE WALL SECTION THRU BALCONY
 PROVIDINGCOMPLETE SPECSFOR FLOOR (INCLUDING BALCONY
 DECK)AND CEILINGS AS REQ'DBY SEC. 106.3.5.4 OF CITY
 AMENDMENTS TO FBC 2004 TO VERIFY COMPLIANCE WITH SEC.
 R301 OF 2004FLORIDA RESIDENTIAL CODE.
 7- PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS FOR POLYGLASS MODIFIED
 BITUMEN AS REQ'DBY GENERAL LIMITATION #7.SEE
 GENERAL LIMITATION #7 TO SEE WHO CAN PREPARE SUCH
 CALCULATIONS.
 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) PRODUCT APPROVAL FOR
 POLYGLASS MODIFIED BITUMEN AS REQ'DBY SEC. 106.3.3
 CITY AMENDMENTS TO FBC 2004.
 9- REVISE TYPO ON ENERGY CALCULATIONS ITEM 9(B).THERE
 IS NOT INSULATION R-219.
  
 ***NOTE: PROVIDE ABOVE INFORMATION PRIOR TO INSPECTIONS
 TO AVOID CONFLICTS ORDELAYS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-09-24 Cont ID  
Sent By shill Date 2007-09-24 Time 09:11 Rev Time 0.00
Received By shill Date 2007-09-24 Time 09:11 Sent To  
Notes
2007-09-24 09:14:21****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC EB
 FLORIDA BUILDING CODE 2004 EXISTING BUILDING CODE
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
  
 COMMENTS FROM PREVIOUS LISTS:
  
 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO
 PERMIT PICKUP, FS713.13.
  
 2.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY
 PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.THE PLANS
 MUST BE STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION.PLEASE CALL 561-233-5025 FOR MORE
 INFORMATION.
  
 3.)INCLUDE FBC EB IN GOVERNING CODE.DECLARE LEVEL
 OF ALTERATION, FBC EB CHAPTER 3.
  
 4.-12.)ADDRESSED.
  
 13.)PROVIDE A SOILS INVESTIGATION REPORT, FBC
 R401.4.
  
 2ND REVIEW - THIS WAS NOT SUBMITTED.THE SOILS REPORT
 SHOULD ALSO ADDRESS THE EXISTING POOL AREA.
 3RD REVIEW - EITHER STRUCTURAL ENGINEER OR SOILS
 ENGINEER IS TO ADDRESS THE ISSUE OF BUILDING OVER THE
 EXISTING POOL.THE SOILS REPORT SUBMITTED IS FOR A 2
 STORY ADDITION AND WAS DONE IN 2005.PLEASE REVISE TO
 REFLECT CURRENT SCOPE OF WORK.
  
 14-23.)ADDRESSED.
  
 NEW COMMENT:
  
 FOR THE ROOF PRODUCT APPROVAL FL6568, PLEASE MARK THE
 METHOD OF ATTACHMENT YOU ARE USING.YOU MAY SPECIFY
 DIFFERENT METHODS FOR EACH ZONE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-07-09 Cont ID  
Sent By shill Date 2007-07-09 Time 16:59 Rev Time 0.00
Received By shill Date 2007-07-05 Time 10:25 Sent To  
Notes
2007-07-09 17:04:49****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC EB
 FLORIDA BUILDING CODE 2004 EXISTING BUILDING CODE FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
  
 COMMENTS FROM PREVIOUS LIST:
  
 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO
 PERMIT PICKUP, FS713.13.
  
 2.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY
 PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.THE PLANS
 MUST BE STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION.PLEASE CALL 561-233-5025 FOR MORE
 INFORMATION.
  
 3.)INCLUDE FBC EB IN GOVERNING CODE.DECLARE LEVEL
 OF ALTERATION, FBC EB CHAPTER 3.
  
 4.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER
 OF RECORD, FBC*106.3.3.
  
 2ND REVIEW - THIS MAY BE DONE WITH A SHOP DRAWING
 REVIEW STAMP OR A LETTER.
  
 5.)FLORIDA STATE OR LOCAL PRODUCT APPROVALS REQUIRED
 IN ADDITION TO THE NOAS SUBMITTED, FAC9B72.
 WWW.FLORIDABUILDING.ORG.THE FLORIDA STATE PRODUCT
 APPROVALS PROVIDED ARE EXPIRED; FBC2001 RATHER THAN
 FBC2004.PLEASE PRINT CURRENT APPROVALS.
  
 2001 APPROVALS WERE SUBMITTED FOR PGT PW701, WINDSOR
 DOOR (2004 REQUIRED).NONE PROVIDED FOR THE PGT
 MULLION.
  
 6.)ADDRESSED.
  
 7.)SHOW REQUIRED HEAD CLEARANCE FOR THE ATTIC ACCESS,
 R807.IT DOES NOT APPEAR TO BE COMPLIANT IN THIS
 LOCATION.
  
 2ND REVIEW -IT IS NOT CLEAR HOW THIS WAS ADDRESSED.
  
 8-10.)ADDRESSED.
  
 11.)SHOW DRAINAGE TO COMPLY WITH FBC R401.
  
 12.)DECLARE LEVEL OF ALTERATION, FBC EB CHAPTER 3.
  
 13.)PROVIDE A SOILS INVESTIGATION REPORT, FBC
 R401.4.
  
 2ND REVIEW - THIS WAS NOT SUBMITTED.THE SOILS REPORT
 SHOULD ALSO ADDRESS THE EXISTING POOL AREA.
  
 14-15.)ADDRESSED.
  
 16.)DOES THE GARAGE DOOR HAVE GLAZING?NOTE THAT
 GLAZING IS AN OPTION ON THE PRODUCT APPROVAL SUBMITTED
 BUT REQUIRES IMPACT PROTECTION.
  
 THIS MAY BE ADDRESSED BY WRITING "NO GLAZING" ON THE
 PRODUCT APPROVAL.IF YOU ARE USING THE GLAZING OPTION,
 IMPACT PROTECTION REQUIRED (WITH PRODUCT APPROVALS AND
 ATTACHED INSTALLATION SCHEDULE COMPLETED).
  
 17.)ADDRESSED.
  
 18.)CHANGES TO THE PLAN MUST BE DONE BY THE DESIGNER
 OF RECORD, CLOUDED, INITIALLED AND DATED.REVISIONS
 WERE DONE ON A1 AND A3 APPARENTLY BY SOMEONE OTHER THAN
 THE ENGINEER.
  
 2ND REVIEW - CHANGES WERE NOT CLOUDED.THIS REQUIRES
 AN ENTIRELY NEW PLAN REVIEW AND WILL CAUSE DELAYS. ALL
 REVISIONS/CHANGES TO THE PLAN ARE TO BE CLOUDED AND
 NUMBERED.
  
 19.)ELEVATIONS ON A1 SHOULD NOTE EXISTING AND
 ADDITION AREAS.
  
 20.)THE ADDING STRAP DETAIL S2 DOES NOT COMPLY WITH
 THE SIMPSON CATALOG.ADDRESS.CHECK ALL CONNECTORS.
  
 21.)SHEET D-2, HIB-91 HAS BEEN REPLACED BY TPI/WTCA
 BCSI 1-03.CHECK ALL REFERENCES.FOR INSTANCE,
 CONCRETE NOTE REFERS TO ACI 544.1R-82.THERE ARE OTHER
 EXPIRED REFERENCES.SEE FBC35.
  
 22.)GARAGE/RESIDENCE SEPARATION TO COMPLY WITH FBC
 R309.
  
 NEW COMMENT:
  
 23.)SEE ATTACHED FS553.80(2)9B).

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-01-05 Cont ID  
Sent By shill Date 2007-01-05 Time 16:14 Rev Time 0.00
Received By shill Date 2007-01-05 Time 16:14 Sent To  
Notes
2007-01-05 16:28:39****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
  
  
 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO
 PERMIT PICKUP, FS713.13.
  
 2.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY
 PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.THE PLANS
 MUST BE STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION.PLEASE CALL 561-233-5025 FOR MORE
 INFORMATION.
  
 3.)INCLUDE FBC EB IN GOVERNING CODE.DECLARE LEVEL
 OF ALTERATION, FBC EB CHAPTER 3.
  
 4.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER
 OF RECORD, FBC*106.3.3.
  
 5.)FLORIDA STATE OR LOCAL PRODUCT APPROVALS REQUIRED
 IN ADDITION TO THE NOAS SUBMITTED, FAC9B72.
 WWW.FLORIDABUILDING.ORG.THE FLORIDA STATE PRODUCT
 APPROVALS PROVIDED ARE EXPIRED; FBC2001 RATHER THAN
 FBC2004.PLEASE PRINT CURRENT APPROVALS.
  
 6.)PROVIDE AREA CALCULATIONS ON THE PLAN; EXISTING,
 PROPOSED, NEW TOTALS FOR CONDITIONED AND UNCONDITIONED
 SPACE.
  
 7.)SHOW REQUIRED HEAD CLEARANCE FOR THE ATTIC ACCESS,
 R807.IT DOES NOT APPEAR TO BE COMPLIANT IN THIS
 LOCATION.
  
 8.)SMOKE DETECTORS REQUIRED FBC R313.
  
 9.)SHOW REQUIRED SAFETY GLAZING FBCR308.4.
  
 10.)SPECIFY WINDOW SIZE AND TYPE FOR REQUIRED
 EMERGENCY EGRESS, FBC R310.
  
 11.)SHOW DRAINAGE TO COMPLY WITH FBC R401.
  
 12.)DECLARE LEVEL OF ALTERATION, FBC EB CHAPTER 3.
  
 13.)PROVIDE A SOILS INVESTIGATION REPORT, FBC
 R401.4.
  
 14.)PROVIDE A SITE PLAN SHOWING THE EXISTING HOUSE
 AND THE PROPOSED ADDITION, FBC*106.3.5.
  
 15.)SIGN THE OWNER/AGENT LINE OF THE ENERGY CALCS,
 FBC13.
  
 16.)DOES THE GARAGE DOOR HAVE GLAZING?NOTE THAT
 GLAZING IS AN OPTION ON THE PRODUCT APPROVAL SUBMITTED
 BUT REQUIRES IMPACT PROTECTION.
  
 17.)PROVIDE INFORMATION IN REGARDS TO FASTENING FOR
 THE IMPACT PROTECTION.PROVIDE A KEY PLAN WITH
 INFORMATION FOR EACH OPENING.SEE ATTACHED FORM FOR A
 SUGGESTED FORMAT.IF ALL INFORMATION IS NOT PROVIDED
 PRIOR TO PERMIT ISSUANCE, A SEPARATE PERMIT WILL BE
 REQUIRED FOR THE SHUTTERS.
  
 18.)CHANGES TO THE PLAN MUST BE DONE BY THE DESIGNER
 OF RECORD, CLOUDED, INITIALLED AND DATED.REVISIONS
 WERE DONE ON A1 AND A3 APPARENTLY BY SOMEONE OTHER THAN
 THE ENGINEER.
  
 19.)ELEVATIONS ON A1 SHOULD NOTE EXISTING AND
 ADDITION AREAS.
  
 20.)THE ADDING STRAP DETAIL S2 DOES NOT COMPLY WITH
 THE SIMPSON CATALOG.ADDRESS.CHECK ALL CONNECTORS.
  
 21.)SHEET D-2, HIB-91 HAS BEEN REPLQCED BY TPI/WTCA
 BCSI 1-03.CHECK ALL REFERENCES.FOR INSTANCE,
 CONCRETE NOTE REFERS TO ACI 544.1R-82.THERE ARE OTHER
 EXPIRED REFERENCES.SEE FBC35.
  
 22.)GARAGE/RESIDENCE SEPARATION TO COMPLY WITH FBC
 R309.
  

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2008-12-29 Cont ID  
Sent By btrobaug Date 2008-12-29 Time 09:35 Rev Time 0.00
Received By btrobaug Date 2008-12-29 Time 09:08 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2008-08-06 Cont ID  
Sent By btrobaug Date 2008-08-06 Time 16:02 Rev Time 0.00
Received By btrobaug Date 2008-08-06 Time 16:02 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status N Date 2008-06-19 Cont ID  
Sent By btrobaug Date 2008-06-19 Time 17:00 Rev Time 0.00
Received By btrobaug Date 2008-06-16 Time 16:44 Sent To M
Notes
2008-06-19 17:06:28 
  
 ONE ELECTRICAL PLAN SUBMITTED IN ERROR, NO ELECTRICAL
 CHANGESPER JULIE MONDELL./WRT
2008-06-16 16:45:18 
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-01-09 Cont ID  
Sent By btrobaug Date 2008-01-09 Time 13:47 Rev Time 0.00
Received By btrobaug Date 2008-01-09 Time 13:11 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-08-16 Cont ID  
Sent By btrobaug Date 2007-08-16 Time 07:22 Rev Time 0.00
Received By btrobaug Date 2007-08-16 Time 06:42 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-06-04 Cont ID  
Sent By btrobaug Date 2007-06-04 Time 08:38 Rev Time 0.50
Received By btrobaug Date 2007-06-04 Time 07:28 Sent To M
Notes
2007-06-04 08:09:12 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW
  
 THE PLAN RESUBMITTED FOR REVIEW IS NOT THE SAME FLOOR
 PLAN AS PREVIOUSLY REVIEWED, SEE "OLD SET".
  
 1} THE OVEN AND DRYER CIRCUITS BOTH HAVE INCORRECTLY
 SIZED OVERCURRENT PROTECTION ON THE PANEL SCHEDULE,
 CIRCUITS 11,13 AN D15,17. ARTICLE 240.
  
 2} LOCATE THE METER AND MAIN DISCONNECT AND ALL SERVICE
 EQUIPMENT, ON THE PLAN, SHEET E-1.
  
 3} RECEPTACLES MUST BE ADDED TO THE ISLAND (KTTCHEN)
 FOR REQUIRED SPACING PER 210.52(C),
  
 4} THE WALL BETWEEN THE MASTER BATH AND THE GREAT ROOM
 IS MISSING, SHEET E-1.
  
 5} A GFI PROTCTED RECEPTACLE IS REQUIRED AT THE BACK OF
 THE DWELLING PER 210.52(E), 2108(A)(3).
  
 6} RECEPTACLES MUST BE ADDED TO COMPLY WITH 210.52 IN
 THE DINING ROOM, BEDROOMS #2 AND #3, AND THE MASTER
 BEDROOM. SEE REVIEWED PLAN.
  
 7} THE NOTE UNDER THE RISER DIAGRAM AND NOTE #6,
 ELECTRICAL NOTES,REGARDING SMOKE ALARM CIRCUITS,
 SHOULD INDICATE ARC FAULT CIRCUITS REQUIRED.
  
 8} THERE ARE 3 GARAGE DOOR OPENERS IN THE LOAD
 CALCULATION, AND ONLY 1 ON THE PANEL SCHEDULE AND IN
 THE GARAGE.PLEASE CORRELATE.
  
 9} PROVIDE A PANEL SCHEDULE FOR THE 400 AMP MAIN. IT
 INDICATES A 400 AMP MAIN AND 2-200 AMP BREAKERS BUT IS
 AN 8 CIRCUIT PANEL. PROVIDE THE AIC RATING ALSO.110.9.
  
 PLEASE REMOVE ALL OLD OR VOIDED SHEETS AND REPLACE WITH
 CORRECTED ONES WHEN RESUBMITTING. INCLUDE THEM
 SEPARATELY TO EXPEDITE THE REVIEW PROCESS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-11-20 Cont ID  
Sent By btrobaug Date 2006-11-16 Time 16:42 Rev Time 1.00
Received By btrobaug Date 2006-11-16 Time 14:53 Sent To M
Notes
2006-11-16 16:42:11 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE OVEN AND DRYER CIRCUITS BOTH HAVE INCORRECTLY
 SIZED OVERCURRENT PROTECTION ON THE PANEL SCHEDULE,
 CIRCUITS 11,13 AN D15,17. ARTICLE 240.
  
 2} LOCATE THE METER AND MAIN DISCONNECT ON THE PLAN,
 SHEET E-1.
  
 3} NOTE #1 REFERS TO "IAW" PLEASE NOTE THAT THE STATE
 OF FLORIDA HAS ADOPTED NFPA 70 OR THE NEC. REMOVE THE
 REFERENCE.
  
 4} SMOKE DETECTORS MUST BE INSTALLED TO COMPLY WITH
 R313.1 RESIDENTIAL FLORIDA BUILDING CODE.
  
 5} THE GARAGE RECEPTACLES ARE REQUIRED TO BE GFI
 PROTECTED PER 210.8(A)(2).
  
 6} RECEPTACLES MUST BE ADDED TO THE KITCHEN COUNTER
 TOPS FOR REQUIRED SPACING PER 210.52(C),(INCLUDING
 THE ISLAND).
  
 7} THE BATHROOM OFF BEDROOM #2 AN DBEDROOM #3 MUST HAVE
 OUTLETS SPACED PER 210.52(D), AND GFI PROTECTED PER
 210.8(A)(1).
  
 8} A GFI PROTCTED RECEPTACLE IS REQUIRED AT THE BACK OF
 THE DWELLING PER 210.52(E), 2108(A)(3).
  
 THERE ARE RECEPTACLES PLACED OFF THE WALL IN THE DINING
 ROOM AND IN THE WALL AT TEH STORAGE CLOSET. PLEASE
 LOCATE WHERE INTENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2009-05-19 Cont ID  
Sent By mcruz Date 2009-05-19 Time 15:30 Rev Time 0.00
Received By mcruz Date 2009-05-14 Time 17:02 Sent To  
Notes
2009-05-14 17:03:18DRIVEWAY DRAWINGS SENT TO ZONING BOX.

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2009-01-08 Cont ID  
Sent By adarroug Date 2009-01-08 Time 08:32 Rev Time 0.00
Received By adarroug Date 2009-01-08 Time 08:32 Sent To B
Notes
2009-01-08 08:33:24TO "JGOMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2008-12-30 Cont ID  
Sent By adarroug Date 2008-12-30 Time 14:08 Rev Time 0.00
Received By adarroug Date 2008-12-30 Time 14:08 Sent To M
Notes
2008-12-30 14:10:08TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2008-12-22 Cont ID  
Sent By adarroug Date 2008-12-22 Time 11:17 Rev Time 0.00
Received By adarroug Date 2008-12-22 Time 11:17 Sent To B
Notes
2008-12-22 11:17:50TO "JGOMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2008-12-18 Cont ID  
Sent By adarroug Date 2008-12-18 Time 08:21 Rev Time 0.00
Received By adarroug Date 2008-12-18 Time 08:21 Sent To M
Notes
2008-12-18 08:21:26TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2008-12-15 Cont ID  
Sent By adarroug Date 2008-12-15 Time 10:49 Rev Time 0.00
Received By adarroug Date 2008-12-15 Time 10:49 Sent To E
Notes
2008-12-15 10:50:02TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-10-03 Cont ID  
Sent By adarroug Date 2008-10-03 Time 16:25 Rev Time 0.00
Received By adarroug Date 2008-10-03 Time 16:25 Sent To B
Notes
2008-10-03 16:25:37TO "JGOMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-08-01 Cont ID  
Sent By adarroug Date 2008-08-01 Time 09:02 Rev Time 0.00
Received By adarroug Date 2008-08-01 Time 09:02 Sent To E
Notes
2008-08-01 09:03:00TO "BTROBUAG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-06-12 Cont ID  
Sent By adarroug Date 2008-06-12 Time 08:52 Rev Time 0.00
Received By adarroug Date 2008-06-12 Time 08:52 Sent To E
Notes
2008-06-12 08:53:17TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-03-05 Cont ID  
Sent By adarroug Date 2008-03-05 Time 14:51 Rev Time 0.00
Received By adarroug Date 2008-03-05 Time 14:51 Sent To B
Notes
2008-03-05 14:52:11TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-01-07 Cont ID  
Sent By shill Date 2008-01-07 Time 16:58 Rev Time 0.00
Received By shill Date 2008-01-07 Time 16:58 Sent To Z
Notes
2008-01-07 16:59:02TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-08-08 Cont ID  
Sent By mmiller Date 2007-08-08 Time 18:58 Rev Time 0.00
Received By mmiller Date 2007-08-08 Time 18:58 Sent To Z
Notes
2007-08-08 18:58:39SENT TO ZONING BOX MMILLER

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-06-01 Cont ID  
Sent By adarroug Date 2007-06-01 Time 08:24 Rev Time 0.00
Received By adarroug Date 2007-06-01 Time 08:24 Sent To E
Notes
2007-06-01 08:24:39TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-05-24 Cont ID  
Sent By adarroug Date 2007-05-24 Time 14:36 Rev Time 0.00
Received By adarroug Date 2007-05-24 Time 14:36 Sent To Z
Notes
2007-05-24 14:36:52TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-11-08 Cont ID  
Sent By adarroug Date 2006-11-08 Time 13:27 Rev Time 0.00
Received By adarroug Date 2006-11-08 Time 13:27 Sent To E
Notes
2006-11-08 13:27:14TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-01-05 Cont ID  
Sent By shill Date 2007-01-05 Time 17:33 Rev Time 0.00
Received By shill Date 2006-11-01 Time 08:46 Sent To  
Notes
2006-11-01 08:47:08TO "Z" BOX

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2009-07-21 Cont ID  
Sent By rkussner Date 2009-07-21 Time 12:05 Rev Time 0.00
Received By rkussner Date 2009-07-21 Time 12:05 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 9 Status P Date 2009-01-10 Cont ID  
Sent By rregueir Date 2009-01-10 Time 12:19 Rev Time 0.00
Received By rregueir Date 2009-01-10 Time 12:19 Sent To PC
Notes
2009-01-10 12:20:05MECH A2 REVISION OK.

Review Stop M MECHANICAL (A/C)
Rev No 8 Status F Date 2008-12-20 Cont ID  
Sent By rregueir Date 2008-12-20 Time 13:52 Rev Time 0.00
Received By rregueir Date 2008-12-20 Time 13:51 Sent To PC
Notes
2008-12-20 13:52:08 
 ACTION: DENIED
  
 REVIEWED FOR COMPLIANCE WITH THE FOLLOWING:
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 TWO COPIES OF REVISED "A-2" WERE SUBMITTED FOR REVIEW.
 A REVIEW OF THESE PLANS CAN NOT BE COMPLETED AT THIS
 TIME FOR THE FOLLOWING REASONS:
  
 1. THE TWO COPIES SHOW DUCT DESIGNS WHICH DO NOT MATCH.
 EXAMPLE: ONE COPY SHOWS TWO SUPPLY DROPS IN THE KITCHEN
 WHILE THE OTHER COPY SHOWS NONE. EXAMPLE: THE HALF-BATH
 NEAR BEDROOM #3 SHOWS AN EXHAUST FAN ON ONE COPY BUT
 NOT THE OTHER. THESE ARE GIVEN AS EXAMPLES AND ARE NOT
 INTENDED TO BE AN EXHAUSTIVE LIST. CHECK ALL ASPECTS OF
 BOTH COPIES AND MAKE NECESSARY CORRECTIONS PRIOR TO
 RESUBMITTING (PERHAPS DRAWING THE PLAN ONCE AND COPYING
 IT RATHER THAN DRAWING IT TWICE WILL RESOLVE THIS
 PROBLEM). PLEASE PROVIDED TWO IDENTICAL PLANS SO ONE
 CAN BE INCORPORATED INTO THE PERMIT SET OF PLANS AND
 THE OTHER CAN BE USED IN THE FIELD FOR INSPECTIONS.
 FBCB 106.1.3.
  
 2. SEVERAL DUCTS ARE MISSING SIZES ON PLANS. THIS
 CONDITION VARIES FROM ONE PLAN TO THE OTHER. PLEASE
 PROVIDED TWO IDENTICAL PLANS SO ONE CAN BE INCORPORATED
 INTO THE PERMIT SET OF PLANS AND THE OTHER CAN BE USED
 IN THE FIELD FOR INSPECTIONS. FBCB 106.1.3.
  
 3. SOME OF THE DUCT SIZES ARE NOT LEGIBLE. PROVIDE
 PLANS OF SUFFICIENT CLARITY TO DESCRIBE THE SCOPE AND
 NATURE OF WORK PROPOSED IN ACCORDANCE WITH FBCB
 106.1.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2008-08-07 Cont ID  
Sent By tgordon Date 2008-08-07 Time 08:37 Rev Time 0.45
Received By tgordon Date 2008-08-07 Time 08:37 Sent To B
Notes
2008-08-07 08:40:24REVISION TO ENERGY CALCULATIONS AND COOLING LOAD
 CAL'S.
  
 NOTICE: MECHANICAL PLANS WILL NEED TO BE REVISED BEFORE
 ROUGH MECHANICAL INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2008-06-20 Cont ID  
Sent By tgordon Date 2008-06-20 Time 15:54 Rev Time 0.35
Received By tgordon Date 2008-06-20 Time 15:53 Sent To B
Notes
2008-06-20 16:05:12PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 REVISION TO ENERGY CALCULATIONS
 *** DENIED ***
 1) PLEASE SUBMIT THE COMPLETE SET OF THE REVISED ENERGY
 CALCULATIONS, PER 2004 FBC 13-600.3.A.
  
 2) PLEASE SUBMIT REVISED COOLING LOAD CALCULATIONS WITH
 THE THREE ZONES SERVED BY EACH SYSTEM NOW THAT THREE
 SYSTEMS ARE BEING INSTALLED, PER 2004 FBC
 13-607.1.ABC.1 AND 13-600.3.ABC.2.
  
 3) NOTICE: THE MECHANICAL PLANS WILL NEED TO BE REVISED
 BEFORE A MECHANICAL INSPECTION.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2008-01-16 Cont ID  
Sent By tgordon Date 2008-01-16 Time 08:35 Rev Time 0.40
Received By tgordon Date 2008-01-16 Time 08:35 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2008-01-09 Cont ID  
Sent By tgordon Date 2008-01-09 Time 15:26 Rev Time 1.15
Received By tgordon Date 2008-01-09 Time 15:26 Sent To P
Notes
2008-01-09 15:49:05PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) COULD NOT FIND A/C SYSTEM 1 & 2 IN THE ARI DIRECTORY
 WEB-SITE, PLEASE SUBMIT THE ARI REFERENCE NUMBER OR
 CERTIFICATE, SEE 2004 FBC 13-607.1.ABC.3.1.1.
  
 2) PLEASE SHOW AND SIZE THE SUPPLY AIR DUCT (FLEX) TO
 THE 10"X10" SUPPLY AIR GRILL IN THE KITCHEN, SEE 2004
 WPB AMEND. 106.3.5.4 (10).
  
 3) PLEASE LABEL THE CONDENSER UNITS 1, 2, & 3 ON THE
 MECHANICAL PLAN.
  
 4) AS BOTH AIR HANDLER UNITS ARE FEEDING THE SAME
 SUPPLY AND RETURN AIR DUCTS, PLEASE SUBMIT DETAILED
 MANUFACTURER'S SPECIFICATION'S AND INSTALLATION
 INSTRUCTIONS TO SUPPORT THIS DESIGN OR IF AN
 ENGINEERING SYSTEM, PLEASE SUBMIT THE COMPLETE
 ENGINEERING SIGNED AND SEALED BY THE ENGINEER, SEE 2004
 FBC/R M1401.1. AND WPB AMEND. 106.1.2.
  
 5) PLEASE SUBMIT MANUAL D CALCULATIONS TO SUPPORT THIS
 DESIGN, SEE 2004 FBC/R M1601.1.
  
 6) THE MECHANICAL PLANS NEED THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN ON
 THEM, SEE W.P.B. AMEND. 106.1.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-08-16 Cont ID  
Sent By tgordon Date 2007-08-16 Time 08:33 Rev Time 1.00
Received By tgordon Date 2007-08-16 Time 08:33 Sent To P
Notes
2007-08-16 09:09:26PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2005, 2006 REVISIONS, AND CHAPTER
 1 CITY OF WEST PALM BEACH AMENDMENTS.
  
 *** DENIED ***
 1) MECHANICAL PLANS NEED THE JOB ADDRESS, AND THE
 INFORMATION OF THE PERSON RESPONSIBLE FOR THE DESIGN ON
 THEM. SEE WPB AMEND. 106.1.3.
  
 2) MECHANICAL PLAN EQUIPMENT SUMMARY NEEDS THE TOTAL
 AND SENSIBLE BTU'S FOR THE SYSTEMS IN IT.
  
 3) NEED TO SIZE ALL THE RETURN AIR GRILLS ON THE
 MECHANICAL PLAN.
  
 4) THE 10X8" SUPPLY AIR GRILL IN BEDROOM #3 HAS TWO 7"
 SUPPLY AIR DUCTS GOING TO IT. PLEASE CORRECT.
  
 5) SHOW THE LOCATION OF THE CLOTHES DRYER VENT AND WERE
 IT WILL TERMINATE AT ON MECHANICAL PLAN, SEE FBC RES. M
 501.2.
  
 6) PROVIDE COMBUSTION AIR CALCULATIONS FOR GAS CLOSE
 DRYER AND COMBUSTION AIR TO LAUNDRY ROOM IF REQUIRED,
 SEE FBC RES. G2407.1.
  
 7) ELECTRICAL PLAN SHOWS THE TWO A/C CONDENSER UNITS
 SIDE BY SIDE, THE MECHANICAL PLAN SHOWS THEM AT
 DIFFERENT SIDES OF THE HOUSE, THE PLANS MUST COINCIDE
 PLEASE CORRECT.
  
 8) SUBMIT DETAILED MANUFACTURER'S SPECIFICATION'S AND
 INSTALLATION INSTRUCTIONS FOR THE GAS COOK-TOP IN THE
 LANAI AS IT MAY REQUIRE AN APPROVED EXHAUST HOOD, SEE
 FBC RES. M1504.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL: [email protected].

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-06-08 Cont ID  
Sent By tgordon Date 2007-06-08 Time 09:44 Rev Time 0.30
Received By tgordon Date 2007-06-08 Time 09:43 Sent To P
Notes
2007-06-08 09:52:22*** DENIED ***
 ** ALL OF THE BELOW CORRECTIONS WERE REQUESTED IN THE
 LAST REVIEW 11-20-07 AND STILL NEED TO BE CORRECTED.**
  
 1) MECHANICAL PLAN ARE DIFFICULT TO READ THEIR IS TO
 MUCH FLOOR PLAN DETAIL ON THEM. CONSTRUCTION DOCUMENTS
 SHALL BE OF SUFFICIENT CLARITY. PLEASE SUBMIT BETTER
 MECHANICAL PLANS. PER 2004 FBC 106.1.1.
 .
 2) THE MECHANICAL PLANS NEED TO BE SEALED BY THE
 ENGINEER JOHN M. AVERKAMP AS HIS NAME AND INFORMATION
 IS IN THE TITLE BLOCK, PER FAC 61G15-23.002 .
  
 3) PLEASE SHOW AN EQUIPMENT LISTING WITH ALL PERTINENT
 INFORMATION ON THE MECHANICAL PLANS.
  
 4) WAS NOTE 6, NEED ATTIC ACCESS WITH-IN 6 FEET OF AHU
 #1, PER 2004 FBC/R M1305.1.3, PLEASE SHOW ACCESS ON
 MECHANICAL AND BUILDING PLANS.
  
 5) WAS NOTE 7, PLEASE SHOW ON MECHANICAL PLANS THE
 LOCATION OF THE A/C CONDENSER UNITS, AND BATHROOM
 EXHAUST FANS.
  
 6) SEE ATTACHED NOTICE FS 553.80(2)(B) REGARDING FOUR
 TIMES THE FEE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-11-20 Cont ID  
Sent By btrobaug Date 2006-11-20 Time 09:19 Rev Time 0.30
Received By tgordon Date 2006-11-20 Time 15:41 Sent To B
Notes
2006-11-20 15:58:31*** DENIED ***
 1) MECHANICAL PLAN ARE DIFFICULT TO READ. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY. PER 2004 FBC
 106.1.1.
 .
 2) THE MECHANICAL PLANS NEED TO BE SEALED BY THE
 ENGINEER JOHN M. AVERKAMP AS HIS NAME AND INFORMATION
 IS IN THE TITLE BLOCK, PER FAC 61G15-23.002 .
  
 3) PLEASE SHOW AN EQUIPMENT LISTING WITH ALL PERTINENT
 INFORMATION ON THE MECHANICAL PLANS.
  
 4) PLANS SHOW 3,061 SQUARE FEET UNDER AIR, ENERGY
 CAL'S. AND MANUAL J CAL'S. SHOW 3,361 SQUARE FEET UNDER
 AIR THE TWO MUST COINCIDE, PLEASE CORRECT ENERGY CAL'S.
 AND MANUAL J CAL'S.
  
 5) ONE 8" SUPPLY AIR DUCT IS GOING OUT-SIDE TO THE
 COVERED PATIO KITCHEN, PLEASE CORRECT.
  
 6) NEED ATTIC ACCESS WITH-IN 6 FEET OF AHU #1, PER 2004
 FBC/R M1305.1.3, PLEASE SHOW ACCESS ON MECHANICAL AND
 BUILDING PLANS.
  
 7) PLEASE SHOW ON MECHANICAL PLANS THE LOCATION OF THE
 A/C CONDENSER UNITS, AND BATHROOM EXHAUST FANS.
  
 8) PLEASE SUBMIT A COMPLETE MANUAL J CALCULATION, PER
 2004 FBC 13-607.1.ABC.1. NOT JUST A SUMMARY PAGE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-01-11 Cont ID  
Sent By jleech Date 2008-01-11 Time 07:49 Rev Time 0.00
Received By jleech Date 2008-01-11 Time 07:39 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-09-12 Cont ID  
Sent By jleech Date 2007-09-12 Time 07:49 Rev Time 0.00
Received By jleech Date 2007-09-12 Time 07:49 Sent To B
Notes
2007-09-12 07:51:21DENIED;
 SANITARY RISER DIAGRAM, MISSING MASTER BATHROOM.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-06-26 Cont ID  
Sent By jleech Date 2007-06-26 Time 13:11 Rev Time 0.00
Received By jleech Date 2007-06-26 Time 13:11 Sent To B
Notes
2007-06-26 13:19:40DENIED;
 PLUMBING RISER DIAGRAMIS TO CODE, BUT PLANSMUST BE
 SIGNED AND DATED BY THE PERSON TAKING RESPONSABILITY
 FOR DRAWINGS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-11-20 Cont ID  
Sent By jleech Date 2006-11-20 Time 08:58 Rev Time 0.00
Received By jleech Date 2006-11-20 Time 08:58 Sent To M
Notes
2006-11-20 09:09:05DENIED;
 1. PERSON RESPONSIBLE FOR DRAWINGS MUST PRINT AND SIGN
 DRAWINGS.
 2. RISER DIAGRAM DOES NOT MATCH FLOOR PLAN AND CANNOT
 BE INSTALLED AS DRAWN.
 3. AUTOMATIC CLOTHES WASHER NOT SHOWN ON RISER DIAGRAM.
 THE BRANCH DRAIN IS REQUIRED TO BE 3" SECTION 406.3 AND
 A CLEANOUT REQUIRED AT 48"
 ABOVE FINISH FLOOR.
 4. CHANGE NOTE 14 TO WATER HAMMER ARRESTORS.
 5. OUTSIDE SHOWER NOT PERMITED TO TIE INTO DRAINAGE
 SYSTEM. RUN TO DRYWELL OR GRASSY AREA.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 5 Status P Date 2009-05-19 Cont ID  
Sent By mcruz Date 2009-05-19 Time 15:38 Rev Time 0.00
Received By mcruz Date 2009-05-19 Time 15:38 Sent To  
Notes
2009-05-19 15:30:17APPROVAL FOR DRIVEWAY.

Review Stop Z ZONING
Rev No 4 Status P Date 2008-01-08 Cont ID  
Sent By choops Date 2008-01-08 Time 14:33 Rev Time 0.00
Received By choops Date 2008-01-08 Time 14:33 Sent To E
Notes
2008-01-08 14:38:39***APPROVED - RESUB #3***
  
 PROVISO:BUILDING SHALL NOT EXCEED 30' (MEASURED FROM
 GRADE TO THE MIDPOINT OF THE ROOF'S PITCH).THE
 BUILDING IS ALLOWED AN EXTRA 10% IN HEIGHT FOR
 ACCESSORIES, ALLOWING THE CUPOLA NOT TO EXCEED 33'
 (MEASURED FROM GRADE TO THE TOP OF THE CUPOLA'S ROOF).
 THE LOT SHALL MEET THE MINIMUM LANDSCAPING REQUIREMENTS
 FOUND IN SECTION 94-442 AND 94-445 OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS.
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 3 Status F Date 2007-08-13 Cont ID  
Sent By choops Date 2007-08-13 Time 08:34 Rev Time 0.00
Received By choops Date 2007-08-13 Time 08:34 Sent To E
Notes
2007-08-13 09:11:13***FAILED******RESUB #2***
  
  
 1)***EXTENSION OF VARIANCE HAS EXPIRED.WORK
 REQUIRED TO COMMENCE BY NOVEMBER 5, 2006 AS PER THE ZBA
 FINAL ORDER***VARIANCE WAS FOR EXTENSION OF
 GARAGE...NOT ENTIRE HOUSE.MUST OBTAIN A NEW VARIANCE
 IF PROPOSED WORK IS TO CONTINUE.FOR VARIANCE
 INFORMATION CONTACT THE PLANNING DEPARTMENT
 (561)822-1435.
  
 NOTE: THE FOLLOWING COMMENTS ARE FOR YOUR INFORMATION:
  
 2)CLARIFY SCOPE OF WORK, SURVEY SHOWS PROPOSED SITE
 WALL.IF INSTALLING A SITE WALL, PROVIDE AN EASEMENT
 CONSENT FORM FROM THE CITY OF WEST PALM BEACH
 DEPARTMENT OF PUBLIC UTILITIES.ALL ELEVATIONS SHALL
 BE MEASURED FROM GRADE.
  
 3)PROPOSED STRUCTURE DOES NOT MEET SETBACK
 REQUIREMENTS SET FORTH IN THE APPROVED VARIANCE.THE
 ZONING BOARD OF APPEALS APPROVED A 12 FT. VARIANCE FROM
 THE REQUIRED 25 FT. SETBACK.THE REMAINING SETBACK
 REQUIREMENT IS A MINIMUM OF 13 FEET FROM THE SOUTH
 OLIVE AVE SIDE.SURVEY SHOWS PROPOSED STRUCTURE AT 9.2
 FT.PLAN SP-1 INDICATES PROPOSED STRUCTURE AT 12 FT.
 FROM SIDE PROPERTY LINE.PLANS MUST BE
 CONSISTENT...PLANS MUST SHOW COMPLIANCE WITH THE
 MINIMUM REQUIRED SETBACKOF 13 FT.
  
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720

Review Stop Z ZONING
Rev No 2 Status F Date 2007-05-29 Cont ID  
Sent By choops Date 2007-05-29 Time 10:08 Rev Time 0.00
Received By choops Date 2007-05-29 Time 10:08 Sent To I
Notes
2007-05-29 10:13:24***FAILED***
  
  
 1)THIS IS A DOUBLE FRONTAGE LOT.THE FRONT SETBACK
 REQUIREMENT FROM BOTH WORTH COURT SOUTH & SOUTH OLIVE
 AVE IS 25 FT..THE CORNER SIDE SETBACK REQUIREMENT IS
 12.5 FT. FROM WORTH CT.THE PROPOSED BUILDING DOES NOT
 MEET THE TWO FRONT SETBACK REQUIREMENTS.
  
 2)POOL NOT INCLUDED IN THIS PERMIT.
  
 3)PLEASE SHOW ALL OVERHANG DIMENSIONS FROM WALL TO
 OUTERMOST POINT OF ROOF.
  
 4)PLEASE PROVIDE SETBACK DIMENSIONS FROM POOL
 EQUIPMENT AND ANY MOVED A/C EQUIPMENT TO PROPERTY
 LINES.
  
  
 CHRIS HOOPS
 ZONING TECHNICIAN
 561-805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2006-11-07 Cont ID  
Sent By mmclean Date 2006-11-07 Time 16:16 Rev Time 0.00
Received By mmclean Date 2006-11-07 Time 16:16 Sent To I
Notes
2006-11-07 16:39:21DENIED,
 1. THE SURVEY SUBMITTED DOES NOT SHOW THE COMPLETE
 PROPERTY. THE PROPERTY IS A DOUBLE FRONTAGE LOT AND
 CORNER LOT. S. OLIVE DOES NOT SHOW ON THE SURVEYS. 2.
 PLEASE SUBMIT THE EXISTING SURVEY THAT SHOW THE
 STRUCTURE WITH SETBACKS BEFORE THE PROPOSED
 CONSTRUCTION.
 3. WITH A DOUBLE FRONTAGE LOT, STRUCTURE MUST MEET THE
 REQUIRED FRONT SETBACK OF 25FT. ON S. OLIVE AVE & WORTH
 COURT S. SURVEY SUBMITTED DOES NOT SHOW THE STRUCTURE
 AT 25FT.
 4. THE SURVEY SUBMITTED SHOWS THE STRUCTURE AS A
 COMPLETE PROPOSED STRUCTURE, AS PLANS AND APPLICATION
 STATES PORTION OF HOUSE TO BE RE-CONSTRUCT. PLEASE
 CLARIFY. PLEASE SHOW THE PROPOSED WORK ON THE EXISTING
 SURVEYS WITH SETBACKS.
 5. PLEASE SHOW THE A/C UNIT (EXTERIOR) ON THE TWO COPY
 OF SURVEYS.
 6. THE PROPOSED COVERED PATIO IS NOT SHOWN CLEARLY ON
 FLOOR PLAN.
  
 NOTE: THE FLOOR PLANS MUST SHALL ALL INTERIOR ACCESS.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720
  