Plan Review Details - Permit 06101117
Plan Review Stops For Permit 06101117
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-12-21 Cont ID  
Sent By lursu Date 2006-12-21 Time 09:30 Rev Time 0.00
Received By lursu Date 2006-12-21 Time 09:30 Sent To  
Notes
2006-12-21 09:30:59A NEW PARCEL CONTROL NUMBER WAS ISSUED BY THE PROPERTY
 APPRAISER'S OFFICE .THE PERMIT WAS ATTACHED TO THE
 VALID PCN FROM THE TEMPORARY PCN USED INITIALLY.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2008-03-05 Cont ID  
Sent By jgomez Date 2008-03-05 Time 14:00 Rev Time 0.00
Received By jgomez Date 2008-03-05 Time 14:00 Sent To  
Notes
2008-03-05 14:01:49ENTRY DOOR NOA AND CONCRETE BLOCK LETTER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2008-03-03 Cont ID  
Sent By jgomez Date 2008-03-03 Time 11:09 Rev Time 0.00
Received By jgomez Date 2008-03-03 Time 11:09 Sent To PC
Notes
2008-03-03 11:10:20SUBMITTAL BUILDING REVIEW CHECKLIST:
  
 1- OWES $60.00 REVISION FEES FORSOFFIT REVISION.
  
 2-DOOR PRODUCT APPROVAL NOA 02-0215.04 IS FOR
 "OUTSWING"DOORS.DRAWINGS SUBMITTED ARE FOR
 "INSWING" DOORS. DOWNLOAD CORRECT DRAWINGS FROM
 WEBSITE.
 REMAINDER: DESIGNER OF RECORD TO REVIEW AND APPROVE ALL
 PRODUCT APPROVALS PRIOR TO SUBMITTAL TO THIS OFFICE AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 ***NOTE: SUBMIT NOA ALONE . FLORIDA PRODUCT APPROVAL
 FL1190-R1 AND NOA 02--0215.04 DON'T CORRESPOND TO EACH
 OTHER.
  
 3- PROVIDE RINKER SPECIFICATIONS LETTER FOR 2 HOUR
 CONCRETE BLOCK AS REQUESTED ON PROVISO.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2007-12-03 Cont ID  
Sent By jgomez Date 2007-12-03 Time 14:02 Rev Time 0.00
Received By jgomez Date 2007-12-03 Time 13:49 Sent To PC
Notes
2007-12-03 14:02:44TRUSS PACKAGE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2007-10-30 Cont ID  
Sent By jgomez Date 2007-10-30 Time 12:39 Rev Time 0.00
Received By jgomez Date 2007-10-30 Time 12:34 Sent To PC
Notes
2007-10-30 12:48:12TRUSS PACKAGE BUILDING REVIEW CHECKLIST.
  
 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72FOR STRUCTURAL CONNECTORS HU214-3AND HU210-2
 ATTACHED DIRECTLY TO MASONRY WALL TO VERIFY COMPLIANCE
 WITH THE CALCULATED LOADS FOR GIRDER TRUSS FG06.SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.ENGINEER OF
 RECORD TO REVIEW AND APPROVE IN WRITING PRODUCT
 APPROVAL PRIOR TO SUBMITTAL TO THIS OFFICE. SEC.
 106.3.3 CITY AMENDMENTSTO FBC 2004.
  
 2- TRUSSES FG01 AND FG05 WERE DESIGNED FOR 10PSF LOAD
 AT TCDL.STRUCTURAL PLANS CALL FOR 20PSF DEAD LOAD.
 REVISE AS REQUIRED.
  
 3- REVISED TRUSS PACKAGE TO BE REVIEWED AND APPROVED BY
 THE ENGINEER OF RECORD PRIOR TO SUBMITTAL TO THIS
 OFFICE.
  
 4- IF PROVIDING COVER OR INDEX SHEET TO AVOID SIGNING
 AND SEALING ALL INDIVIDUAL TRUSSES, THEN ALL
 INFORMATION REQUIRED BY SEC. 61G15-31003 SHALL BE
 SUBMITTED. THIS PACKAGE IS MISSING STRUCTURAL ENGINEER
 OF RECORD INFORMATION, PROPER IDENTIFICATION OF PROJECT
 (AND ADDRESS SHOWN IS NOT CORRECT) AND A CLEARNAMING
 AND NUMBERING SYSTEM.INDIVIDUAL SHEETS ARE NOT
 NUMBERED, WHICH ALLOWS TO MATCH INDEX SHEET.
  
 5- TRUSS LAYOUT IS NOT SIGNED AND SEALED AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTE.
  
 6- CLARIFY WHY THE ATTIC LIVE LOAD IS NONCONCURRENT
 WITH ANY OTHER LIVE LOADS IF FBC 2004 TABLE 1607.1
 REQUIRES ALL MINIMUM LIVE LOADS TO BE INCLUDED IN THE
 DESIGN.CLARIFY WHICH ARE THE OTHER NONCONCURRENT LIVE
 LOADS.SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 7- THIS PROJECT HAS A RESIDENT INSPECTOR, THEREFORE 3
 COMPLETE SETS OF TRUSS DRAWINGS ARE REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-08-06 Cont ID  
Sent By jgomez Date 2007-08-06 Time 10:14 Rev Time 0.00
Received By jgomez Date 2007-08-06 Time 10:08 Sent To  
Notes
2007-08-06 10:13:52PRODUCT APPROVAL REVISION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-07-10 Cont ID  
Sent By jgomez Date 2007-07-10 Time 11:00 Rev Time 0.00
Received By jgomez Date 2007-07-10 Time 11:00 Sent To PC
Notes
2007-07-10 11:01:19TRUSS PACKAGE CHECKLIST:
 1-A) ONLY TWO SETS WERE SUBMITTED. THIS TYPE OF
 PROJECT REQUIRES THREE COMPLETE SETS.THREE SIGNED AND
 SEALED SETS AS REQUIRED BY CHAPTER 471 FLORIDA STATUTE
 AND SEC. 61G15-23 OF FLORIDA ADMINISTRATIVE CODE.
  
 B) TRUSS ENGINEER TO PROVIDE ALL THREE SETS WITH
 ORIGINAL SIGNATURE. COPY OF SIGNATURE IS NOT ALLOWED BY
 CHAPTER 471 FLORIDA STATUTE.
  
 C) EVERY INDIVIDUALSHEETNEEDS TO HAVE
 ENGINEER'S ORIGINAL SEAL, SIGNATURE AND DATE.
 OTHERWISE, ENGINEER MAY WANT TO FOLLOW ALL CONDITIONS
 REQUIREDBY SEC. 61G15-31.003 FLORIDA ADMINISTRATIVE
 CODE TO COMPLY WITH THE SIGNING AND SEALING OF ALL
 SHEETS.INFORMATION SUBMITTED DOESN'T COMPLYWITH
 THIS SECTION.
  
  
 2- ENGINEER OF RECORD TO CHECK DETAILS GIVEN ON
 STRUCTURAL DRAWINGS FOR SUPPORT OF TRUSSES AT THE ENDS.
 TRUSS PACKAGE SHOWS DIFFERENT END CONNECTIONS.REVISE
 EITHER TRUSS PACKAGE OR ENGINEERED DRAWINGS AS REQUIRED
 TO MATCH. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-06-13 Cont ID  
Sent By jgomez Date 2007-06-13 Time 10:28 Rev Time 0.00
Received By jgomez Date 2007-06-13 Time 10:28 Sent To PC
Notes
2007-06-13 14:18:24REVISION CHECKLIST:
  
 1- THIS IS NOT A SUBMITTALBUT A REVISION ON
 PREVIOUSLY APPROVED PRODUCT APPROVALS. THEREFORE OWES
 $70.00 FOR REVISION FEES.
  
 2- ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND
 APPROVED IN WRITING (NOT SIGNING AND SEALING) BY THE
 DESIGNER OF RECORDAS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004. PRODUCT APPROVALS SUBMITTED
 DON'T SHOWDESIGNER OF RECORD APPROVAL IN WRITING.
  
 3- SINGLE HUNG WINDOWS PRODUCT APPROVAL:
 A) PROVIDE CURRENT PRODUCT APPROVAL FL42-R4. (ONE
 SUBMITTED IS FL 42-R1).
  
 B) PROVIDE ONLY ALL THE TECHNICAL INFORMATION
 (DRAWINGS, SPECS, ETC) THAT WAS SUBMITTED TO OBTAIN THE
 FLORIDA PRODUCT APPROVAL. GO THE FLORIDA WEBSITE
 WWW.FLORIDABUILDING.ORG AND DOWNLOAD CORRESPONDING
 INFORMATION TO SPECIFIC MODEL TO BE INSTALLED.
  
 C) MAKE SURE ALL DRAWINGS ARE LEGIBLE.
  
 4- SLIDING GLASS DOORS:
 A) SAME COMMENTS AS FOR SINGLE HUNG WINDOWS APPLY.
  
 5- SUBMIT ONLY THE PRODUCT APPROVALS THAT APPLY TO THIS
 BUILDING TO EXPEDITE REVIEW PROCESSAND AVOID
 UNNECESSARY FEES.THERE ARE PRODUCT APPROVALS FOR
 SWING DOORS THAT DON'T APPLY TO THIS BUILDING.
  
 ***NOTE:
 RESUBMITTAL FEES FOR REVISIONS ARE THE SAME AS FOR THE
 FIRST TIME REVISIONS ARE SUBMITTED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-02-26 Cont ID  
Sent By jgomez Date 2007-02-26 Time 18:49 Rev Time 0.00
Received By jgomez Date 2007-02-26 Time 18:49 Sent To  
Notes
2007-02-26 18:56:15BUILDING REVIEW APPROVED WITH PROVISO:
 1- PROVIDE CORRECT DRAWINGS FOR ENTRY DOOR.NOA
 02-0215.04 SUBMITTED HAS THE "INSWING" DOOR DRAWINGS.
 THIS IS A DADE COUNTY PRODUCT APPROVAL DIVISION MISTAKE
 THAT WAS ALREADYREVISED. NOW WEBSITE HAS CORRECT
 "OUTSWING" DOOR DRAWINGS. PROVIDE 3 COPIES, REVIEWED
 AND APPROVED BY THE DESIGNER OF RECORD.
  
 2-RINKER SPECIFICATIONS LETTER FOR 2 HOUR CONCRETE
 BLOCK: PROVIDE LETTER ADDRESSED TO THE CITY OF WEST
 PALM BEACH AND WITH CORRECT PROJECT NAME.THIS IS
 MERRY PLACE PROJECT, NOT BOCA DEVELOPMENT.
  
 3- DESIGNER OF RECORD TO PROVIDE COMPLETE
 SPECIFICATIONS/DETAILS FOR INSTALLATION OF HARDISOFFIT
 & CEMSOFFIT PANELS. SEE SHEET 3 OF 3 OF NOA 02-0729.02
 DRAWINGS SUBMITTED. SEC. 106.1.2 CITY AMENDMENTSTO
 FBC 2004.
  
 4- SUBMIT ALL TRUSS DRAWINGS FOR REVIEW PRIORTO
 CONSTRUCTION/INSTALLATION. TRUSS PACKAGE TO BE REVIEWED
 AND APPROVED BY DESIGNER OF RECORDPRIOR TO
 SUBMITTAL.
  
 5- PROVIDE COPY OFTHE RECORDED MERRY PLACE PLAT FOR
 CITY RECORDS.
  
 6- PROVIDE 3 COPIES OF APPROVED AND RECORDED SURVEY
 SHOWING UNITY OF TITLE REVISION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-12-05 Cont ID  
Sent By jgomez Date 2006-12-05 Time 11:19 Rev Time 0.00
Received By jgomez Date 2006-12-05 Time 11:19 Sent To  
Notes
2006-12-05 12:35:27BUILDING REVIEW CHECKLIST:
 1- NOTICE OF COMMENCEMENT AND IMPACT FEES STAMPED
 DRAWINGS AND PAID RECEIPTS WILL BE SUBMITTED LATER.
  
 2- REVISE ENERGY CALCULATIONS:
 A) CALCULATIONS NEED TO BE PERFORMED FOR THE WHOLE
 BUILDING, NOT FOR EACH UNIT. SEC. 13-600.0 METHOD A OF
 2004 FBC.
 B) NAME AND LICENSE # OF ENGINEER AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTES.
 C) PROVIDE COMPLETE INFORMATION FOR ITEM #8, FLOOR
 TYPES.
 D) INSULATION R VALUE SPECIFIED IN PROJECT MANUAL
 SPECS SEC. 07200 TO MATCH ENERGY CALCULATIONS.
 E) PROVIDE COMPLETE INFORMATION ON TOP OF FORM. NEED
 ADDRESS AND BUILDER NAME.
  
 3- NEED SIGNED AND SEALED SURVEYS SHOWING EXACT
 LOCATIONS OF BUILDINGS IN RELATIONSHIP WITH THE
 PROPERTY LINES AND OTHER BUILDINGS TO VERIFY COMPLIANCE
 WITH TABLES601, 602 FOR FIRE RESISTANCE AND TABLE
 704.8 FBC 2004 FOR OPENINGS ALLOWED.PROVIDE ALL
 DISTANCES BETWEEN BUILDINGS AND PROPERTY LINES AND MAKE
 SURE ALL BUILDINGS HAVE THE DIMENSIONS BETWEEN BUILDING
 SEPARATION FOR BUILDINGS ON SAME LOT. IF BUILDINGS ARE
 ON SAME LOT, THEN SPECIFY THE PROPOSED PROPERTY LINE
 BETWEEN THEM.BUILDINGS WITH IRREGULAR SHAPES NEED TO
 SHOW DIMENSIONS WITH CLOSEST DISTANCE TO ADJACENT
 BUILDINGS. EG: SOME BUILDINGS HAVE SETBACKS IN THE
 FOOTPRINT. MAKE SURE DISTANCES PROVIDED INCLUDE THE
 CLOSEST DISTANCE BETWEEN BUILDINGS. SITE PLAN SUBMITTED
 DOESN'T PROVIDE ALL THIS INFORMATION.
  
 4- SHOW ACCESSIBLE ROUTE FROM PARKING SPACE TO ALL
 APARTMENT ENTRANCES, RECREATIONAL AREAS AND PUBLIC
 BUILDINGS.WHERE ARE THE DRAWINGS?.
  
 5- INFORMATION REGARDING HANDICAPPED UNITS AND
 ADAPTABLE UNITS IS CONFUSING.ACCORDING TO FAIR
 HOUSING ACT,"ALL"GROUND FLOOR UNITS MUST BE
 "ACCESSIBLE"FROM THE PARKING SPACE TO THE UNIT
 ENTRANCE. THEN,ALL THE UNITS MUST BE "ADAPTABLE"PER
 FHA.INFORMATION ON SHEET A100 IS INDICATING THAT
 THERE ARE 9 ADAPTABLE UNITS ON ACCESSIBLE ROUTE.IF
 THE INTENTION IS TO GO BEYOND FHA AND TO HAVE FULLY
 HANDICAPPED UNITS, THEN CLARIFY THAT SUCH UNITS WILL BE
 FULLY HANDICAPPED UNITS, NOT ADAPTABLE.
  
 6- SHEET A004:
 A) MISSING UNIT MODEL TYPE IN PROJECT TABULATION
 CHART.
 B) BUILDING AND UNIT AREAS DON'T MATCH. SEE SHEET
 A004 AND SHEETS A203, A204, A205 AND A308. REVISE AS
 REQUIRED.NEED CORRECT AREAS TO ESTIMATE BUILDING
 VALUATION. SEC. 108.3 CITY AMENDMENTS TO FBC 2004.
 PROVIDE PORCHES, BALCONIES AND BUILDING AREAS.
  
 7- SHEET A101:
 A) HANDICAPPED PARKING FOR FAIR HOUSING UNITS AND
 CHAPTER 11 FBC 2004 CAN'T OVERLAP TO ACCOMPLISH TOTAL
 NUMBER OF REQUIRED PARKING SPACES.NEED TO PROVIDE
 SEPARATE HANDICAPPED PARKING FOR FAIR HOUSING UNITS AND
 PUBLIC ASSEMBLY AREAS.SEE TABLE ON SECTION 11-4.1.2
 FOR REQUIRED NUMBER OF PARKING SPACES. THIS COMMENT
 APPLIES TO BUILDINGS F AND C FOR MIXED USE BUILDINGS.
  
 B) PROVIDE DRAWINGS SHOWING PARKING SIZES AND
 ACCESSIBLE ROUTES FROM PARKING SPACES TO RESIDENTIAL
 UNITS AND PUBLIC ASSEMBLY BUILDINGS TO VERIFY
 COMPLIANCE WITH FAIR HOUSING ACT AND CHAPTER 11 FBC
 2004.
  
 C) SPECIFY IF PROVIDING VISITORS PARKING SPACES TO
 VERIFY COMPLIANCE WITH FAIR HOUSING ACT.
  
 8- OWNER TO PROVIDE LETTER CERTIFYING THAT NO FEDERAL
 MONIES ARE USED FOR THIS PROJECT. OTHERWISE,PROJECT
 NEEDS TO BE REVIEWED FOR SECTION 504 OF THE
 REHABILITATION ACT COMPLIANCE.
  
 9- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) SINGLE HUNG WINDOW. NOA 01-0629.08 IS EXPIRED.
 ALSO, NEED FLORIDA PRODUCT APPROVAL COVER PAGE. GO TO
 WWW.FLORIDABUILDING.ORG TO DOWNLOAD CORRESPONDING COVER
 PAGE. FLORIDA PRODUCT APPROVAL COVER PAGE APPLIES TO
 ALL PRODUCT APPROVALS. IF THERE IS NO FLORIDA PRODUCT
 APPROVAL, THEN SUBMIT THE DADE COUNTY NOA ONLY.
  
 B) UNIT ENTRY DOOR: DRAWINGS SUBMITTED ARE FOR
 "INSWING" DOORS. NEED DRAWINGS FOR "OUTSWING" DOORS.
  
 C) ALL USP OR SIMPSON CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING SPECIFIC CONNECTOR.
  
 D) SLIDING GLASS DOORS. PROVIDE FLORIDA PRODUCT
 APPROVAL COVER PAGE.
  
 E) ROOF SHINGLES. NEED FLORIDA PRODUCT APPROVAL
 COVER PAGE.
  
 F) RIDGE VENT. NEED FLORIDA PRODUCT APPROVAL COVER
 PAGE.
  
 G) 770-D ROOF LOUVER. NEED FLORIDA PRODUCT APPROVAL
 COVER PAGE.
  
 H) 2 HOUR CONCRETE BLOCK AS REQUIRED BY UL WALL
 ASSEMBLYU905.
  
 I) CEMENTITIOUS PANELS FOR ENTRY OVERHANGS. SEE
 DETAIL 11/A705.
  
 M) FALSE SKYLIGHT. SEE ELEVATIONS.
  
 N) EXTERIOR PANEL DOOR FOR HOT WATER HEATERS
 RECESSED IN CONCRETE BLOCK.
  
 10- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 11- SHEET A103:
 A) REVISE DETAIL 19 TO MATCH DETAIL 7/700.1. SHELVES
 HEIGHT 48" MAX.
  
 B) PROVIDE DETAILS/SPECS FOR GRAB BARS
 REINFORCEMENT. MATERIAL AND INSTALLATION. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
  
 12- SHEET A104:
 A) CLARIFY COMMON USE FACILITIES NOTE # 2A. WHAT'S
 THE QUESTION MARK FOR?.
 B) REVISE RESTROOMS NOTE # 5C. SEE FIGURE 30 ON
 CHAPTER 11 FBC 2004.
  
 13- SHEET 110:
 A) DETAIL 20: CLARIFY QUESTION MARKS ON CONCRETE
 BLOCK THICKNESS.
 B) DETAIL 18: REQUIRES 2X10 JOISTS AT 16" OC. REVISE
 UNDER STAIRS DETAILS TO MATCH THIS ASSEMBLY.
 C) UPDATE ASSEMBLY AND PENETRATION SCHEDULE.
 REFERENCE UL 2004, NOT UL 1999.
  
 14- SHEET A203:
 A) SPECIFY DOOR SIZE FOR DOOR LEADING TO MASTER
 BEDROOM.
  
 B) CLARIFY SQUARE FOOTAGE FOR UPPER FLOOR UNIT.
 ALSO, COORDINATE ALL THESE AREAS WITH GENERAL AREA
 TABULATION ON SHEET A004.
  
 C) PANTRIESWITH NARROW DOORS TO HAVE 18" MAX.
 DEPTH. SEE PAGE 7.17 FAIR HOUSING ACT.THIS COMMENT
 APPLIES TO ALL GROUND UNITS THROUGHOUT ENTIRE PROJECT.
 REVISE AS REQUIRED.
  
 D) CLOSET DOOR ON SECOND BEDROOM NEEDS TO COMPLY
 WITH FAIR HOUSING ACT. NEED WIDER DOORS TO ALLOW REACH
 AT THE ENDS OF CLOSET. SEE PAGE 3.14 FAIR HOUSING ACT
 AND REVISE AS REQUIRED. THIS COMMENT APPLIES TO ALL B1
 UNITS ON GROUND FLOOR.
  
 15- SHEET A204:
 A) CLOSET DOORS FOR SECONDARY BEDROOMS DON'T COMPLY
 WITH FAIR HOUSING ACT. SEE PAGE 3.15 OF FHA. NEED WIDER
 DOORS TO ALLOW REACH AT THE ENDS OF CLOSET. ALSO, DOOR
 TYPE SPECIFIED DON'T MATCH DOOR SCHEDULE.
  
 B) REVISESQUARE FOOTAGE AREAS. THEY CAN'T BE THE
 SAME.COORDINATE AREAS WITH TABULATION ON SHEET A004.
  
 16- SHEET A205:
 A) UNIT C1: CLOSET DOORS FOR SECONDARY BEDROOMS
 DON'T COMPLY WITH FAIR HOUSING ACT. SEE PAGE 3.15 OF
 FHA. NEED WIDER DOORS TO ALLOW REACH AT THE ENDS OF THE
 CLOSET. THIS ALSO APPLIES TO B1 UNITS AND ALL UNITS IN
 GROUND FLOOR. REVISE ALL CLOSET DOORS IN ALL UNITS AS
 REQUIRED.
  
 B) REVISE SQUARE FOOTAGE AREAS. THEY CAN'T BE THE
 SAME. COORDINATE WITH CHART ON SHEET A004.
  
 C) PROVIDE COMPLETE DETAILS AND SPECS FOR ROLL-IN
 SHOWERS.
  
 17- SHEET A308:
 A) VENTILATION CALCULATIONS: COORDINATE SIZE OF
 RIDGE VENT. SEE RIDGE VENT PRODUCT APPROVAL FOR
 REQUIRED OPENING. REVISE CALCULATIONS AS REQUIRED.
 REVISE DETAIL 16/A705 AS REQUIRED.
  
 B) GENERAL ROOF NOTE #2 CALLS FOR DETAIL 14/A705.
 MISSING THAT DETAIL.
  
 18- SHEET A400:
 A) ALL DETAILS TO SPECIFY PRESSURE TREATED WOOD (OR
 ANY OTHER APPROVED METHOD TO ISOLATE WOOD WHEN IN
 CONTACT WITH CONCRETE OR CONCRTE BLOCK). SEC. 2304.11
 FBC 2004.
  
 B) ENLARGED ELEVATIONS DON'T CORRESPOND TO THIS
 BUILDING. REVISE AS REQUIRED.
  
 19- SHEET A408: ELEVATIONS DON'T MATCH FLOOR PLANS.
 REVISE AS REQUIRED.
  
 20- SHEET A500:
 A) SECTION 17: FLOOR ASSEMBLYL-521 AND INFORMATION
 ON TYPICAL FLOOR CONSTRUCTION ON SAME DRAWING DON'T
 MATCH. REVISE AS REQUIRED. ALSO, INFORMATION DOESN'T
 MATCH SPECIFICATION SHOWN ON SHEET A111.
 B) REVISEINFORMATION ON UL L-521 ON SHEET A111.
 SEE 2004 UL BOOK AND REVISE SPECS TO MATCH SUCH
 LISTING.
 C) SPECS ON WALL ASSEMBLY U905 DOESN'T MATCH
 INFORMATION SHOWN ON SAME DRAWING POINTING TO WALL
 AREAS. REVISE AS REQUIRED.
  
 D) PROVIDE INFORMATION THAT ADDRESSES MINIMUM LABELS
 OF SOUND INSULATION AS REQUIRED BY SEC. 1207.2 AND
 1207.3.
  
 E) PROVIDE FIREBLOCKING AT ROOF ASSEMBLY
 INTERSECTION. FLOOR ASSEMBLY NOTE ON DETAIL 17 CLEARLY
 SPECIFIES TO SEAL JOINTS AT WALL . THIS IS NOT
 SPECIFIED AT CEILING AREA.SEC. 717 FBC 2004.
  
 21- SHEET A501:MISSING DETAIL 14/ A705 SPECIFIED ON
 WALL SECTION 16 AND 18.
  
 22- SHEET A701.1:DETAIL 01: HOW IS THE FASTENER
 EMBEDED 1-1/4" IN TO THE BUCK IF THE BUCK IS ONLY 1X
 THICK. REVISE AS REQUIRED.
  
 23- SHEET A703: WOOD IN CONTACT WITH CONCRETE BLOCK TO
 BE PRESSURE TREATED. REVISE DETAILS 01 AND 06 AS
 REQUIRED.
  
 24- SHEET A705:
 A) DETAIL 02: REVISE FLASHING FASTENER SPACING AS
 REQUIRED BY ROOFING APPLICATION STANDARD RAS 111.
  
 B) REVISE DETAIL 16. SEE RIDGE VENT PRODUCT APPROVAL
 FOR RIDGE CUT OUT DIMENSION.
  
 C) PROVIDE COMPLETE STRUCTURAL DETAIL SHOWING
 INSTALLATION OF FALSE SKYLIGHT TO SHOW COMPLIANCE WITH
 SEC. 1609 FBC 2004.
  
 25- SHEET A706.1:
 A) DETAIL 00 (?): CHECK VENT HOOD SPECIFICATIONS FOR
 MIN. CLEARANCE REQUIRED FROM THE RANGE. PROVIDE VENT
 HOOD SPECS AND REVISE DETAIL AS REQUIRED.
  
 26- SHEET S-1:FOUNDATION PLAN STILL SHOWS A DROP AT
 THE ENTRANCE TO UNITS. ALL GROUND FLOOR UNITS NEED TO
 COMPLY WITH FAIR HOUSING ACT. REVISE AS REQUIRED.
  
 27- SHEET S-3: TRUSS TIE DOWN SCHEDULE. REVISE NOTE #6
 FOR CONNECTOR C (SIMPSON MGT). NEED 12" EMBEDMENT. SEE
 SIMPSON CATALOGUE.
  
 28- PROVIDE COMPLETE DETAILS AND SPECS FOR INSTALLATION
 OF RECESSED GAS WATER HEATERS NEXT TO AIR HANDLER
 UNITS. PROVIDE SPECS FOR WALL ASSEMBLY SEPARATING BOTH.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
 ***NOTE; THIS COMMENT APPLIES TO ALL UNITS.
  
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2007-02-27 Cont ID  
Sent By jgomez Date 2007-01-03 Time 09:11 Rev Time 0.00
Received By jgomez Date 2007-01-03 Time 09:11 Sent To  
Notes
2007-01-03 09:57:15BUILDING REVIEW SECOND CHECKLIST:
 1- REVISE ENERGY CALCULATIONS:
 A) AS REQUESTED ON PREVIOUS CHECKLIST, CALCULATIONS
 NEED TO BE DONE FOR THE WHOLE BUILDING, NOT FOR EACH
 UNIT AS REQUIRED BY SEC. 13-600.0 METHOD A OF FBC
 2004.
  
  
 B) AS REQUESTED ON PREVIOUS CHECKLIST, ENGINEER TO
 PROVIDE ALL HIS INFORMATION AS REQUIREDBY CHAPTER 471
 FLORIDA STATUTES AND FLORIDA ADMINISTRATIVE CODE SEC.
 61G15-23.002.
  
 C) CALCULATIONS SUBMITTED FOR INDIVIDUAL UNITS HAVE
 THE FOLLOWING INCORRECT INFORMATION:
 * NUMBER OF BEDROOMS.
 ** SLAB ON GRADE TOTAL PERIMETER FEET.
 *** CLARIFY HOW ARE THESE CALCULATIONS DONE FOR
 WORST CASE SCENARIO IF THERE IS NOT SHEET SHOWING
 OPENINGS SUN EXPOSURE ORIENTATION.
  
 2- REVISION CLOUDS ON SHEET A004 DON'T ALLOW THE OTHER
 INFORMATION TO BE LEGIBLE.REVISE AS REQUIRED.
  
 3- SURVEY AND SITE PLAN SHOWN ON SHEETS A100, A101 AND
 A102 DON'T MATCH.ACCORDING TO THE RECORDED SURVEY,
 THERE IS AN ALLEY BY BUILDING C3. SITE PLAN SHOWS
 PARKING SPACES. REVISE AS REQUIRED. THIS COMMENT COULD
 NOT BE ADDREESED BEFORE BECASUE THIS IS THE FIRST TIME
 SURVEY IS SUBMITTED FOR REVIEW.
  
 4- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) UNIT ENTRY DOOR: DRAWINGS SUBMITTED ARE FOR
 "INSWING" DOORS. NEED DRAWINGS FOR "OUTSWING" DOORS.
  
 B) ALL USP OR SIMPSON CONNECTORS SPECIFIED ON PLANS
 AND DETAILS.PROVIDE FLORIDA PRODUCT APPROVAL COVER
 PAGE AND PAGE SHOWING THE CONNECTOR.
  
 C) 2 HOUR CONCRETE BLOCK AS REQUIRED BY UL WALL
 ASSEMBLY U905.
  
 D) CEMENTITIOUS PANELS AT ENTRY OVERHANGS. SEE
 DETAIL 11/A705.
  
 E) EXTERIOR DOOR PANEL FOR RECESSED GAS WATER
 HEATER.
  
 5- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004.
  
 6- NEED TO CONTACT HAROLD PISKURA, INSPECTION SERVICES
 MANAGER (561)805-6711, TO COORDINATE SPECIAL INSPECTOR
 SERVICES.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-12-17 Cont ID  
Sent By dpalmer Date 2006-12-17 Time 17:53 Rev Time 0.00
Received By dpalmer Date 2006-12-17 Time 17:37 Sent To  
Notes
2006-12-17 17:53:33PLANS OK, STAMPED ALL THREE SETS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-11-26 Cont ID  
Sent By dpalmer Date 2006-11-26 Time 13:17 Rev Time 0.00
Received By dpalmer Date 2006-11-26 Time 13:12 Sent To  
Notes
2006-11-26 13:18:22MERRY PLACE
  
 1928 MERRY PLACE TYPE VIII BLDG.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW AND SOME
 NEW NOTES DUE TO PLANS NOW BEING SUBMITTED WITH SOME
 ADDITIONAL INFORMATION.
  
 ********** UNSAT *************
  
 1) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.16 FOR
 THE MINIMUM REQUIRED CIRCUITING AND LOADS FOR THE
 DINING ROOM CIRCUIT(S). PLEASE ALSO SEE THAT NO OTHER
 ELECTRICAL DEVICES SUCH AS LIGHTING MAY BE PLACED ON
 SAID CIRCUIT.
 MUST BE 20A AND #12 AND ON ONE OR MORE OF THE CIRCUITS
 AS NOTED IN CODES ABOVE.
 PLEASE SEE THAT A DESIGNATED AREA AND THE LIKE SHALL BE
 INDICATED.
  
 2) NOTE: PLEASE BE SURE PLANS REFERENCE THE FOLLOWING
 CODES: NFPA-70 2002, NFPA-72 2002. THIS COULD NOT BE
 LOCATED ON PLANS AND IS REQUIRED.
  
 3) NOTE: PLEASE SEE HOUSE LOADS WHICH SHALL INDICATE
 ALL CONTINUOUS LOADS SUCH AS LIGHTING AT 125%. 215.3,
 230.42 ETC
  
 4) NOTE:PLEASE SEE 410.8 FOR MINIMUM CLEARANCES
 PERMITTED IN STORAGE AREAS.
 (UNDER STAIRS) FIX TYPE "H". PLEASE KNOW, WHEN SHELVING
 IS NOT SHOWN, A MIN
 18" IS ASSUMED AND THE LIGHT FIXTURE AS SHOWN AND TYPE
 DESIGNATED SHALL MEET THE MIN CLEARANCES REQUIRED.
 PLEASE ADJUST
  
 5) NOTE: PLEASE SEE CALCULATIONS ALSO MENTIONS HEAT
 LOADS SHOWN AND BEING DONE AT 100%, YET THE KW RATINGS
 AS SHOWN DOES NOT CORRELATE WITH THE MECHANICAL PLANS
 OF 5KW?
 PLEASE ADJUST.
 220.21
  
 6) NOTE: PLEASE SEE THE HOUSE PANEL ON E-311 IS BEING
 SHOWN AS 100MLO AND THE RISER SHOWS THIS AS 60A MLO. IT
 IS KNOWN THAT A 60A BREAKER IS FEEDING THIS PANEL.
  
 7) NOTE: PLEASE SEE E202 WHICH INDICATES A KEYNOTE #7,
 HOWEVER UNDER KEYNOTES, THERE IS NO #7?
 PLEASE SEE THIS APPEARS TO BE A DISPOSAL, HOWEVER THERE
 IS NOTHING LISTED ON PANEL SCHEDULES OR IN LOAD
 CALCULATIONS?
 PLEASE CLARIFY WHAT THIS IS?
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
  
 **IF THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF
 THE NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE
 DO NOT HESITATEIN CONTACTING THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2006-12-05 Cont ID  
Sent By lmartine Date 2006-12-05 Time 13:35 Rev Time 0.00
Received By lmartine Date 2006-12-05 Time 13:34 Sent To  
Notes
2006-12-05 13:35:53SEE 06101116

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2006-11-22 Cont ID  
Sent By rchokshi Date 2006-11-22 Time 15:36 Rev Time 0.00
Received By rchokshi Date 2006-11-22 Time 15:36 Sent To  
Notes
2006-11-22 15:36:32WE DO NOT HAVE THE CIVIL DWGS FOR THIS PERMIT PROJECT
 BUT WE REVIEWED,MADE FOLLOWING COMMENTS TO EXPEDITE
 THE PERMITTING PROCESS: PLEASE PROVIDE FOLLOWING INFO
 IN YOUR CIVIL DRAWINGS FOR THIS PERMIT SITE:
 1.DID YOU MAKE ANY CHANGES IN STORM WATER/DRAINAGE
 SYSTEM FROM PREVIOUS MASTER PERMIT? PLEASE TELL US WHAT
 CHANGES YOU MADE IN WRITING AND MUST BE APPROVED FROM
 SFWMD ALSO. AND A COPY OF SFWMD.
 2. PLEASE SHOW STANDARDS NOTES OF CITY OF WPB ON CIVIL
 DRAWINGSFOR SIDEWALK WIDTH , ITS SLOPE, DRIVEWAY,
 PARKING, HANDICAP PARKING, PAINTPER CITY CODES ETC.,,
 MUST MEET PER ADA,,ETC.,
 3. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 4. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD ,
 SIDEWALK ELEVATION FOR THIS PERMIT PROJECT MUST MEET FL
 BLDG CODE, PLEASE SHOW ON THE DRAWINGS.,
 5. HOW YOU CONNECT TO THE ROOF DRAINS ? WHERE THE ROOF
 DRAINS GO?
 6. PLEASE SHOW ON DRAWINGS,POLLUTION PREVENTION
 DETAILS,CLOTHES USED FOR SILT ETC., PLANS SHOWING SILT
 FENCE AROUND THE SITE
 7. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED 8.
 ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND YOUR
 THIS BUILDING SITE FOR STORM WATER DRAIN.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-01-23 Cont ID  
Sent By mawillia Date 2007-01-23 Time 15:11 Rev Time 0.00
Received By mawillia Date 2007-01-23 Time 15:11 Sent To  
Notes
2007-01-23 15:12:36*****APPROVED*****
  
  
  
 COMMENTS FROM PREVIOUS FIRE PLAN REVIEW OF 12/02/2006
 HAVE BEEN ADDRESSED.SHEETS A408, E201, E202, AND E204
 WERE STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-12-02 Cont ID  
Sent By mawillia Date 2006-12-02 Time 17:36 Rev Time 0.00
Received By mawillia Date 2006-12-02 Time 17:36 Sent To  
Notes
2006-12-02 17:44:21*****DENIED*****
  
  
  
 1. NFPA 101 - 2003 EDITION AND THE FLORIDA FIRE
 PREVENTION CODE - 2004 EDITION SHALL BE REFERENCED.
  
 2.CONSTRUCTION OPERATIONS SHALL NOT INTERFERE OR
 HINDER EMERGENCY ACCESS TO THE SAID PROPERTY OR
 VICINITY THEREOF
  
 3.ON THE APPROPIATE ELEVATION DETAIL, SHOW/DISPLAY
 THE NUMERICAL ADDRESS OF THIS BUILDING FRONTING MERRY
 PLACE.AS PER WEST PALM BEACH CODE, THOSE NUMBERS
 SHALL BE NO LESS THAN 6" IN HEIGHT AND 1" IN WIDTH.
 INDIVIDUAL APARTMENT/UNIT SHALL BE NO LESS THAN 3" IN
 HEIGHT.
  
 4.THE ADDRESS OF THE STRUCTURE SHALL BE IN THE TITLE
 BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 5.FIRE EXTINGUISHERS ARE TO BE 2A-10BC RATED.
  
 6.AS PER NFPA 101 - 10.2.8.1 -2003 EDITION,
 INTERIOR FINISH FOR WALLS AND CEILINGS IN AN
 UNSPRINKLERED BUILDING SHALL BE CLASS "A" OR CLASS
 "B".
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2006-12-27 Cont ID  
Sent By kstevens Date 2006-12-27 Time 07:24 Rev Time 0.00
Received By kstevens Date 2006-12-27 Time 07:24 Sent To  
Notes
2006-12-27 07:25:34SEPARATE GAS PERMIT REQUIRED. - ALL PLANS/REQUIRED
 INFORMATION SHALL BE SUBMITTED AT THE TIME OF
 APPLICATION FOR GAS PERMIT

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-12-26 Cont ID  
Sent By kstevens Date 2006-11-22 Time 15:50 Rev Time 0.00
Received By kstevens Date 2006-11-21 Time 15:47 Sent To  
Notes
2006-12-26 15:53:16DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
  
 **********FROM PREVIOUS REVIEW**********
  
 1B. SEPARATE GAS PERMIT REQUIRED. SUBMIT THE FOLLOWING
 INFORMATION:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. AN ISOMETRIC IS REQUIRED FOR EACH GAS
 SYSTEM SHOWING THE PIPING FROM THE METER TO THE MOST
 REMOTEAPPLIANCE FOR EACH UNIT.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 H. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2008-02-28 Cont ID  
Sent By adarroug Date 2008-02-28 Time 15:56 Rev Time 0.00
Received By adarroug Date 2008-02-28 Time 15:56 Sent To B
Notes
2008-02-28 15:56:43TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2008-02-26 Cont ID  
Sent By adarroug Date 2008-02-26 Time 16:06 Rev Time 0.00
Received By adarroug Date 2008-02-26 Time 16:06 Sent To P
Notes
2008-02-26 16:06:50TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2008-02-19 Cont ID  
Sent By adarroug Date 2008-02-19 Time 09:06 Rev Time 0.00
Received By adarroug Date 2008-02-19 Time 09:03 Sent To P
Notes
2008-02-19 09:06:46TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2007-12-04 Cont ID  
Sent By adarroug Date 2007-12-04 Time 13:36 Rev Time 0.00
Received By adarroug Date 2007-12-04 Time 13:36 Sent To M
Notes
2007-12-04 13:37:05TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-11-26 Cont ID  
Sent By adarroug Date 2007-11-26 Time 12:20 Rev Time 0.00
Received By adarroug Date 2007-11-26 Time 12:20 Sent To B
Notes
2007-11-26 12:21:10TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-11-21 Cont ID  
Sent By adarroug Date 2007-11-21 Time 09:34 Rev Time 0.00
Received By adarroug Date 2007-11-21 Time 09:34 Sent To M
Notes
2007-11-21 09:34:43TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-11-15 Cont ID  
Sent By adarroug Date 2007-11-15 Time 10:13 Rev Time 0.00
Received By adarroug Date 2007-11-15 Time 10:13 Sent To M
Notes
2007-11-15 10:13:23TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-11-02 Cont ID  
Sent By adarroug Date 2007-11-02 Time 10:02 Rev Time 0.00
Received By adarroug Date 2007-11-02 Time 10:02 Sent To M
Notes
2007-11-02 10:02:36TO "TGORDON" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-08-03 Cont ID  
Sent By adarroug Date 2007-08-03 Time 08:19 Rev Time 0.00
Received By adarroug Date 2007-08-03 Time 08:19 Sent To B
Notes
2007-08-03 08:19:31TO "JGOMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-06-28 Cont ID  
Sent By shill Date 2007-06-28 Time 15:17 Rev Time 0.00
Received By shill Date 2007-06-28 Time 15:17 Sent To B
Notes
2007-06-28 15:18:06TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-06-04 Cont ID  
Sent By adarroug Date 2007-06-04 Time 11:50 Rev Time 0.00
Received By adarroug Date 2007-06-04 Time 11:50 Sent To B
Notes
2007-06-04 11:51:20TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-02-07 Cont ID  
Sent By adarroug Date 2007-02-07 Time 13:17 Rev Time 0.00
Received By adarroug Date 2007-02-07 Time 13:17 Sent To P
Notes
2007-02-07 13:19:02TO "KSTEVENS" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-12-18 Cont ID  
Sent By adarroug Date 2006-12-18 Time 15:38 Rev Time 0.00
Received By adarroug Date 2006-12-18 Time 15:38 Sent To  
Notes
2006-12-18 15:38:54TO "COMM" BD#28/PLANS ON RACK/12 ROLL AND 1 BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-12-05 Cont ID  
Sent By jgomez Date 2006-12-05 Time 13:05 Rev Time 0.00
Received By jgomez Date 2006-10-31 Time 10:10 Sent To  
Notes
2006-11-03 11:42:5411/3/06--SUBMITTAL ROUTED TO "COMM" BD#57 W/ ORIGINAL
 APPL. PACKAGE
  
  
2006-10-31 10:10:13(PLANS ROUTED TO INCOMING TODAY) TO "COMM" BD#57/PLANS
 ON RACK 14 ROLLS/1 BOX--EXPEDITED PERMIT

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2007-12-04 Cont ID  
Sent By tgordon Date 2007-12-04 Time 14:32 Rev Time 0.15
Received By tgordon Date 2007-12-04 Time 14:32 Sent To  
Notes
2007-12-04 14:33:00PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 MECHANICAL SUBMITTAL
 *** DENIED ***
 1) MECHANICAL PLANS WILL NEED TO BE REVISED TO SHOW
 THIS CHANGE AND THE CHANGES FROM THE PAST TWO
 SUBMITTALS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-11-30 Cont ID  
Sent By tgordon Date 2007-11-30 Time 15:03 Rev Time 0.15
Received By tgordon Date 2007-11-30 Time 15:03 Sent To  
Notes
2007-11-30 15:03:51RECEIVED SUBMITTAL STATING 8" FLEX DUCT BETWEEN TWO
 MIXING BOX'S

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-11-16 Cont ID  
Sent By tgordon Date 2007-11-16 Time 08:51 Rev Time 0.15
Received By tgordon Date 2007-11-16 Time 08:51 Sent To  
Notes
2007-11-16 08:51:28RECIVED SUBMITTAL TO CHANGE AN 11" FLEX DUCT TO 10".

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-11-05 Cont ID  
Sent By tgordon Date 2007-11-05 Time 12:00 Rev Time 0.30
Received By tgordon Date 2007-11-05 Time 12:00 Sent To  
Notes
2007-11-05 12:01:37MECH. REVISION TO PAGES M202, M203, AND M204.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-12-20 Cont ID  
Sent By tgordon Date 2006-12-20 Time 09:49 Rev Time 0.20
Received By tgordon Date 2006-12-20 Time 09:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-11-17 Cont ID  
Sent By tgordon Date 2006-11-17 Time 14:03 Rev Time 1.00
Received By tgordon Date 2006-11-17 Time 14:03 Sent To  
Notes
2006-11-17 14:05:36*** PROVISO ***
 1) UNITS(B1) UPPER AND LOWER, AND (C1) UPPER AND
 LOWER, RETURN AIR TRANSFER GRILLS TO MASTER BEDROOM
 SUITE NEED TO BE 14"X 8", SEE 2004 FBC/M 601.4.
  
 2) CLOTHES DRYER VENTS MAY NOT EXCEED THE
 MANUFACTURER'S SPECIFICATION'S, PLANS SHOW THAT UNIT
 (B1) UPPER, LOWER, AND ACCESSIBLE MAY EXCEED.
  
 3) AHU CLOSET DOORS NEED TO BE LOUVERED OR GRILLS NEED
 TO BE INSTALLED FOR RETURN AIR, SEE 2004 FBC/M 601.4.
  
 4) LAUNDRY ROOM DOORS NEED TO BE LOUVERED OR GRILLS
 NEED TO BE INSTALLED FOR COMBUSTION AIR, SEE 2004 FBC/M
 701.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 5 Status   Date 2008-02-23 Cont ID  
Sent By kstevens Date   Time   Rev Time  
Received By kstevens Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2008-02-23 Cont ID  
Sent By kstevens Date 2008-02-23 Time 18:09 Rev Time 0.00
Received By kstevens Date 2008-02-23 Time 18:09 Sent To  
Notes
2008-02-23 18:11:54REVISIONDENIED
 REFERENCE: FBC-2004 PLUMBING
  
 1. SHT P308. SEE PROVISO ON PLANS ISSUED WITH PERMIT.
 DELETE CLEANOUT AS REQUIRED. SECTION 706.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-02-09 Cont ID  
Sent By kstevens Date 2007-02-09 Time 07:38 Rev Time 0.00
Received By kstevens Date 2007-02-09 Time 07:06 Sent To  
Notes
2007-02-09 07:42:36PASSED/PROVISO:
 DELETE THE CLEANOUT DOWNSTREAM OF THE FIRST (4S) RISER
 IN THE BUILDING. THIS CLEANOUT IS SHOWN INCORRECTLY AND
 DOES NOT GUIDE THE SEWAGE OR WASTE WITH THE FLOW AS
 REQUIRED IN SECTION 706.3. A REVISION WILL BE REQUIRED
 FOR SHEETS P308 AND P402.

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-12-26 Cont ID  
Sent By kstevens Date 2006-12-26 Time 17:18 Rev Time 0.00
Received By kstevens Date 2006-12-26 Time 17:18 Sent To  
Notes
2006-12-26 17:29:10DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 NOTE: FIRST PLAN REVIEW FOR APPLICATION
  
 **********FROM PREVIOUS REVIEW**********
  
 1. SHEETS DELETED. WILL BE SUBMITTED AT THE TIME OF
 APPLICATION SUBMITTAL PER RESPONSE.
  
 2. OK
  
 3. OK
 4. OK
 5. DELETED
 6. OK. NOT REQUIRED THIS BUILDING.
 7. OK
 8.OK
 9.OK
 10. OK
 11. OK. NOT REQUIRED THIS BUILDING.
 12. OK. NOT REQUIRED THIS BUILDING.
 13. OK. (UNIT LOCATION ONLY)
 14. OK. NOT REQUIRED THIS BUILDING.
 15. OK. NOT REQUIRED THIS BUILDING.
 16. OK. NOT REQUIRED FOR THIS BUILDING.
 17. OK. NOT REQUIRED FOR THIS BUILDING. (CHANGE FINISH
 SCHEDULE)
 18. OK. NOT REQUIRED FOR THIS BUILDING
 19. OK. NOT REQUIRED FOR THIS BUILDING.
 20. OK. NOT REQUIRED FOR THIS BUILDING.
 21. OK. NOT REQUIRED FOR THIS BUILDING.
 22. OK. NOT REQUIRED FOR THIS BUILDING.
 23. OK
 24. OK
 25. OK. NOT REQUIRED FOR THIS BUILDING
 26. OK
  
 27. SUBMIT A BUILDING DRAIN SANITARY
 RISER DIAGRAM ISOMETRIC THAT REFLECTS
 THE FLOOR PLAN FOR EACH BUILDING.
 SECTION 106.1.5.1.3. SHOW ALL PIPE
 SIZES, RISER LOCATIONS, TRAPS, VENTS,
 AND DFU'S AS THEY ACCUMULATE IN THE
 SYSTEM.
 ****RESPONSE NOTED. SHOW CLEANOUTS REQUIRED BY SECTIONS
 708.3.1, 708.3.3 7 & 708.3.4. RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. TWO RISERS SHOWN AS 2S ON THE
 FLOOR PLAN ARE SHOWN AS 3S ON THE RISER DIAGRAM. THE
 CLEANOUT DOWNSTREAM OF THE FIRST RISER DOES NOT MEET
 THE CODE SECTION 706.3 FITTING INSTALLATION REQUIRED TO
 GUIDE THE WASTE & SEWAGE IN THE DIRECTION OF FLOW. THE
 CLEANOUT ALSO DOES NOT REFLECT THE FLOOR PLAN. SECTION
 106.1.1.
 ****RESPONSE NOTED, BUT THE TWO RISERS STILL DO NOT
 REFLECT THE FLOOR PLAN AND THE CLEANOUT STILL DOES NOT
 COMPLY WITH SECTION 706.3. NOW THE CLEANOUT WILL HAVE
 TO BE CHANGED ON THE FLOOR PLAN ALSO. SHT P308.
  
 28. OK
 29. OK. NOT REQUIRED THIS BUILDING
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 SUBMIT ONE SET OF PLANS FROM FIRST
 REVIEW FOR COMPARISON TO EXPEDITE 2ND
 REVIEW.
  
 **************NEW COMMENTS**************
  
 1B. OK
 2B. OK
 3B. OK
 4B. OK
 5B. OK
 6B. SEPARATE GAS PERMIT REQUIRED. SUBMIT THE FOLLOWING
 INFORMATION:ALL INFORMATION WIIL BE SUBMITTED AT THE
 TIME OF APPLICATION FOR THE GAS PERMIT.
  
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-12-05 Cont ID  
Sent By kstevens Date 2006-11-22 Time 13:07 Rev Time 0.00
Received By kstevens Date 2006-11-21 Time 16:31 Sent To  
Notes
2006-11-21 17:24:50DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 NOTE: FIRST PLAN REVIEW FOR APPLICATION
  
 **********FROM PREVIOUS REVIEW**********
  
 1. SHEETS DELETED. WILL BE SUBMITTED AT THE TIME OF
 APPLICATION SUBMITTAL PER RESPONSE.
  
 2. OK
  
 3. SHT A104 DETAIL 06 SINKS SHALL COMPLY
 WITH SECTION 11-4.24.7 FAUCETS. PLEASE
 INDICATE COMPLIANCE ON DETAIL.
 ****RESPONSE NOTED. NOTE REFERENCED INDICATES
 COMPLIANCE WITH LAVS, BUT NOT SINKS. PLEASE INDICATE
 FAUCET TYPE TO BE SUBMITTED FOR BOTH THE LAVS AND THE
 SINKS. (LEVER- OPERATED, PUSH-TYPE ETC).
  
 4. SHT A104 GENERAL NOTES II(5)(C) GRAB
 BAR HEIGHTS SHALL BE 33" MIN. TO 36"
 MAX. PAGE 6.5 FHA DESIGN MANUAL.
 ****RESPONSE NOTED. NOTE WASNOT CORRECTED.
  
 5. DELETED
  
 6. OK. NOT REQUIRED THIS BUILDING.
  
 7.SHT A201 DETAIL 07 SUPERIMPOSE THE CLEAR FLOOR
 SPACE FOR THE W/C AS REQUIRED ON PAGE 7.43.
 ****RESPONSE NOTED. SHT A201 NOT REQUIRED THIS
 BUILDING. (REQUIRED FOR SHTS A203, A204 & A205).
  
 8.SHTS A201 THRU A205 INDICATE SPECIFICATION "A" OR
 "B" AS REQUIRED ON PAGES 7.34 & 7.35 OF THE FHA DESIGN
 MANUAL.
 ****RESPONSE NOTED. NO ACTION TAKEN. (INDICATE ON
 PLANS).
  
 9.OK.RESPONSE UNDERSTOOD. 7% OF 100 UNITS EQUALS
 9.1 UNITS. 10 UNITS WILL BE REQUIRED TO BE ACCESSIBLE.
  
 10. SHT A203 AND A204 UNITS B1 & C1
 LOWER FLOOR REQUIRED TO MEET FHA-98
 DESIGN REQUIREMENTS 2ND BATHROOMS ARE
 EXEMPT ONLY FROM MANEUVERING AND CLEAR
 FLOOR SPACE IF SPECIFICATION "B" AND
 SHALL SHOW THE BACKING AS WELL AS THE
 SPACING FOR THE WATER CLOSET. (33"
 OPENING, 15"/18" BETWEEN THE FIXTURES).
 PLEASE SHOW ON PLANS. IF SPECIFICATION
 'A" THEN BATHROOM SHALL COMPLY WITH ALL REQUIREMENTS OF
 FHA DESIGN MANUAL.
 ****RESPONSE NOTED. NO ACTION TAKEN.- ALSO COMPLY
 WITH COMMENT 7 FOR THE CLEAR FLOOR SPACE FOR THE W/C.
  
 11. OK. NOT REQUIRED THIS BUILDING.
 12. OK. NOT REQUIRED THIS BUILDING.
 13. OK. (UNIT LOCATION ONLY)
 14. OK. NOT REQUIRED THIS BUILDING.
 15. OK. NOT REQUIRED THIS BUILDING.
 16. OK. NOT REQUIRED FOR THIS BUILDING.
 17. OK. NOT REQUIRED FOR THIS BUILDING. (CHANGE FINISH
 SCHEDULE)
 18. OK. NOT REQUIRED FOR THIS BUILDING
 19. OK. NOT REQUIRED FOR THIS BUILDING.
 20. OK. NOT REQUIRED FOR THIS BUILDING.
 21. OK. NOT REQUIRED FOR THIS BUILDING.
 22. OK. NOT REQUIRED FOR THIS BUILDING.
  
 23. SHTS P301 THRU P310 PLAN KEY NOTES #7
 PRESSURE RELIEF VALVE IS INDICATED AS
 RUNNING UNDER THE SLAB. THE RELIEF VALVE
 DISCHARGE LINE SHALL NOT HAVE ANY
 TRAPPED SECTIONS PER SECTION 504.6.1.
 ****RESPONSE NOTED. SHT P301 NOT SUBMITTED THIS
 BUILDING. NO CLARIFICATION SHOWN.
  
 24. OK
 25. OK. NOT REQUIRED FOR THIS BUILDING
 26. OK
  
 27. SUBMIT A BUILDING DRAIN SANITARY
 RISER DIAGRAM ISOMETRIC THAT REFLECTS
 THE FLOOR PLAN FOR EACH BUILDING.
 SECTION 106.1.5.1.3. SHOW ALL PIPE
 SIZES, RISER LOCATIONS, TRAPS, VENTS,
 AND DFU'S AS THEY ACCUMULATE IN THE
 SYSTEM.
 ****RESPONSE NOTED. SHOW CLEANOUTS REQUIRED BY SECTIONS
 708.3.1, 708.3.3 7 & 708.3.4. RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. TWO RISERS SHOWN AS 2S ON THE
 FLOOR PLAN ARE SHOWN AS 3S ON THE RISER DIAGRAM. THE
 CLEANOUT DOWNSTREAM OF THE FIRST RISER DOES NOT MEET
 THE CODE SECTION 706.3 FITTING INSTALLATION REQUIRED TO
 GUIDE THE WASTE & SEWAGE IN THE DIRECTION OF FLOW. THE
 CLEANOUT ALSO DOES NOT REFLECT THE FLOOR PLAN. SECTION
 106.1.1.
  
 28. OK
 29. OK. NOT REQUIRED THIS BUILDING
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 SUBMIT ONE SET OF PLANS FROM FIRST
 REVIEW FOR COMPARISON TO EXPEDITE 2ND
 REVIEW.
  
 **************NEW COMMENTS**************
  
 1B. SHTS A100 & A101 PLANS INDICATE 7% OF THE UNITS
 SHALL BE ACCESSIBLE. 130 UNITS PROVIDED. 7% IS 9.1
 UNITS. ANY FRACTION OF UNITS SHALL BE ROUNDED OFF
 UPWARDS. 10 ACCESSIBLE UNITS REQUIRED. CHART INDICATES
 BLDG "D" 1 REQUIRED/1 PROVIDED, BUT 1 IS INDICATED IN
 BOTH BLDGS.D1/V & D2/VIII, PLEASE CLARIFY. BLDG "E"
 INDICATES 1 REQUIRED/1PROVIDED, BUT 1 IS INDICATED IN
 BOTHBLDGS. E1/V & E2/V. PLEASE CLARIFY. BLDG "F"
 INDICATES 2 REQUIRED/2PROVIDED, BUT ONLY SHOWS 1
 PROVIDED. PLEASE CLARIFY.PLEASE CORRELATE
 INFORMATION, CORRECT AMOUNT OF UNITS AND CHART. SECTION
 106.1.1.
  
 2B. SHT A200 HANDICAP ACCESSIBLE UNIT PLANS NOTES
 LEGEND.NOTES 1, 2, 5,INDICATE "ADAPTABLE". IF UNITS
 ARE TO BE ACCESSIBLE, THEY SHALL BE FULLY ACCESSIBLE AT
 THE TIME THEY ARE BUILT. NOT ADAPTABLE IN THE FUTURE.
 IF THE UNITS ARE TO BE FHA-98 COMPLIANT, THE COMPLETE
 UNIT CAN BE ADAPTABLE.
 NOTE "B" AT THE BOTTOM READS FAIR HOUSING ACT OF 1996.
 PLEASE INDICATE 1998 AMENDMENTS. NOTE FUTHER STATES
 "UNITS HEREIN DESIGNATED AS ACCESSIBLE SHALL BE FULLY
 ADA ADAPTABLE IN ADDITION TO FAIR HOUSING COMPLIANT".
 THIS IS NOT CORRECT. A UNIT IS EITHER FHA-98 ADAPTABLE
 OR FULLY ACCESSIBLE.
  
 3B. SHT A200UNIT PLANS GENERAL NOTES 6 INDICATES 7%
 TO BE FULLY "ADAPTABLE" PLEASE CLARIFY.
  
 4B. SHT P402 SANITARY RISER 1S DOES NOT REFLECT THE
 FLOOR PLANS FOR 3 BDRM (C1) UPPER FLOOR, LOWER FLOOR OR
 ACCESSIBLE, NOR DOES IT REFLECT THE FLOOR PLAN FORTHE
 2 BDRM (B1) ACCESSIBLE. PLEASE CORRELATE RISERS AND
 FLOOR PLAN.SECTION 106.1.1.
  
 5B. SHT P403 RISER 3W UNIT B1 SECOND FLOOR DOES NOT
 REFLECT THE FLOOR PLAN AT THE WASHER BOX. PLEASE
 CORRELATE WATER RISERS AND THE FLOOR PLANS. SECTION
 106.1.1.
  
 6B. SEPARATE GAS PERMIT REQUIRED. SUBMIT THE FOLLOWING
 INFORMATION:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. AN ISOMETRIC IS REQUIRED FOR EACH GAS
 SYSTEM SHOWING THE PIPING FROM THE METER TO THE MOST
 REMOTEAPPLIANCE FOR EACH UNIT.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 H. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2006-11-16 Cont ID  
Sent By ajones Date 2006-11-16 Time 10:25 Rev Time 0.00
Received By ajones Date 2006-11-16 Time 10:25 Sent To  
Notes
2006-11-16 10:25:35LANDSCAPING PLANS SHALL BE APPROVED BEFORE A CO IS
 ISSUED.