Plan Review Details - Permit 06101113
Plan Review Stops For Permit 06101113
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2007-02-20 Cont ID  
Sent By lursu Date 2007-02-20 Time 08:19 Rev Time 0.00
Received By lursu Date 2007-02-20 Time 08:19 Sent To  
Notes
2007-02-20 08:21:15THE SITE ADDRESS HAS BEEN CHANGED FROM MERRY PL TO
 CHEERFUL CT .
 PERMIT HAS BEEN CORRECTED IN THE SYSTEM.THE CORRECTION
 MUST APPEAR ON THE SITE PLANS TOO.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 2 Status P Date 2006-12-21 Cont ID  
Sent By lursu Date 2006-12-21 Time 10:10 Rev Time 0.00
Received By lursu Date 2006-12-21 Time 10:10 Sent To  
Notes
2006-12-21 10:10:40A NEW PARCEL CONTROL NUMBER WAS ISSUED BY THE PROPERTY
 APPRAISER'S OFFICE .THE PERMIT WAS ATTACHED TO THE
 VALID PCN FROM THE TEMPORARY PCN USED INITIALLY.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-12-06 Cont ID  
Sent By lursu Date 2006-12-06 Time 09:29 Rev Time 0.00
Received By lursu Date 2006-12-06 Time 09:29 Sent To  
Notes
2006-12-06 09:30:25ADDRESS HAVE BEEN CHANGED TO 1825 FOR BLDG F1 AND CLUB
 HOUSE = 1825 MERRY PL
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 14 Status P Date 2008-03-11 Cont ID  
Sent By jgomez Date 2008-03-11 Time 17:02 Rev Time 0.00
Received By jgomez Date 2008-03-11 Time 16:54 Sent To PC
Notes
2008-03-11 17:02:51ENTRY DOOR PRODUCT APPROVAL AND CONCRETE BLOCK WALL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 13 Status F Date 2008-03-03 Cont ID  
Sent By jgomez Date 2008-03-03 Time 13:51 Rev Time 0.00
Received By jgomez Date 2008-03-03 Time 13:50 Sent To  
Notes
2008-03-03 13:51:22SUBMITTAL BUILDING REVIEW CHECKLIST:
  
 1- OWES $60.00 REVISION FEES FORSOFFIT REVISION.
  
 2-DOOR PRODUCT APPROVAL NOA 02-0215.04 IS FOR
 "OUTSWING"DOORS.DRAWINGS SUBMITTED ARE FOR
 "INSWING" DOORS. DOWNLOAD CORRECT DRAWINGS FROM
 WEBSITE.
 REMAINDER: DESIGNER OF RECORD TO REVIEW AND APPROVE ALL
 PRODUCT APPROVALS PRIOR TO SUBMITTAL TO THIS OFFICE AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 ***NOTE: SUBMIT NOA ALONE . FLORIDA PRODUCT APPROVAL
 FL1190-R1 AND NOA 02--0215.04 DON'T CORRESPOND TO EACH
 OTHER.
  
 3- PROVIDE RINKER SPECIFICATIONS LETTER FOR 2 HOUR
 CONCRETE BLOCK AS REQUESTED ON PROVISO.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status P Date 2008-01-25 Cont ID  
Sent By jgomez Date 2008-01-25 Time 16:42 Rev Time 0.00
Received By jgomez Date 2008-01-25 Time 16:41 Sent To PC
Notes
2008-01-25 16:42:51REVISED TRUSS PACKAGE WITH TRUSSESREPAIR PACKAGE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status F Date 2008-01-02 Cont ID  
Sent By jgomez Date 2007-12-31 Time 15:47 Rev Time 0.00
Received By jgomez Date 2007-12-31 Time 15:47 Sent To  
Notes
2007-12-31 15:49:46TRUSS PACKAGE REVIEW:
  
 1-STRUCTURAL ENGINEER OF RECORD DOCUMENTS SUBMITTED:
 A)ALL LETTERS,DETAILS, ETC.NEED TO HAVETHE
 ENGINEER'S ORIGINALSEAL, SIGNATURE, DATE AND ALL
 ENGINEER'SINFORMATION AS REQUIRED BY FLORIDA
 ADMINISTRATIVE CODE SEC. 61G15-23.002 AND FLORIDA
 STATUTE CHAPTER 471.ALL DRAWINGS SUBMITTED WERE NOT
 SIGNED AND SEALED AND THEY ARE MISSING THE ENGINEER'S
 INFORMATION.
  
 B)THERE IS A THRESHOLD INSPECTOR ON THIS JOB.
 THEREFORE, NEED TO PROVIDE THREE SETS OF DRAWINGS AND
 DOCUMENTS.
  
 C) DETAILS SUBMITTEDARE THE ORIGINAL DRAWINGS.
 NEED TO PROVIDE THREE COPIES TO COMPLY WITH SECTION
 61G15-23.002(3)OF FLORIDA ADMINISTRATIVE CODE.
  
 2- TRUSS PACKAGE:
 A) ENGINEER'S SIGNATURE MUST BE ORIGINAL, NOT COPY.
 AS REQUIRED BY FLORIDA ADMINISTRATIVE CODE SEC.
 61G15-23.002.
  
 B) THERE IS ANOTHER ENGINEER TAKING RESPONSIBILITY
 FOR THE TRUSS PACKAGE DESIGNED BY THE RETIRED ENGINEER
 (SENG-CHAI TAN).NEW ENGINEER NEEDS TO ADHERE TO THE
 PROCEDURE FOR THE ADOPTION OF ANOTHER ENGINEER'S WORK
 SEC. 61G15-27.001. SEE ATTACHED COPY AND COMPLY WITH
 ALL THE REQUIREMENTS.
  
 C) PROVIDE THREE SETS OF TRUSS PACKAGES THAT COMPLY
 WITH ALL FLORIDA ADMINISTRATIVE CODE REQUIREMENTS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status F Date 2007-12-03 Cont ID  
Sent By jgomez Date 2007-12-03 Time 15:50 Rev Time 0.00
Received By jgomez Date 2007-12-03 Time 14:39 Sent To PC
Notes
2007-12-03 16:23:44TRUSS PACKAGE SECOND CHECKLIST:
  
 1- STRUCTURAL ENGINEER OF RECORD NEEDS TO REVISE PLANS
 AS REQUIRED TO SHOW THE DESIGN LOADS REQUIRED BY TABLE
 1607.1 FBC 2004.ALL FLOOR TRUSSES NEED TO BE DESIGNED
 FOR THE DISTRIBUTED AND CONCENTRATED LIVE LOADS.
 NEW REVISED DESIGN LOAD SCHEDULE PROVIDED BY THE
 STRUCTURAL ENGINEER SHOWSA TOTAL LIVE LOAD OF 50PSF
 (OFFICE USE). ACCORDING TO TABLE 1607.1 FBC 2004 NEED
 TO DESIGN FOR 80PSF LIVE LOAD AT CORRIDORS ABOVE FIRST
 FLOOR.ON THE OTHER HAND NEED TO CONSIDER THE 2,000
 LBS CONCENTRATED LOAD.
 IN ADDITION, STAIRS AND EXITS NEED TO BE DESIGNED FOR
 100 PSF. REVISE DESIGN LOAD SCHEDULEAS REQUIRED.
  
 2- RE-RUN CALCULATIONS ON TRUSS DRAWINGS SHOWING
 REVISED LOADINGS. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 3- ENGINEER OF RECORD TO REVIEW AND APPROVE COMPLETE
 REVISED TRUSS PACKAGE PRIOR TO SUBMITTAL TO THIS
 OFFICE.
  
 4- IF FLOOR TRUSSES ARE ALREADY INSTALLED, THEN
 ENGINEER ANALYSIS WILL BE REQUIRED TO SHOW COMPLIANCE
 WITH THE REVISED LOADING.SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004.
  
 5- ROOF TRUSS LAYOUT AT THE END WINGS OF THE BUILDING
 IS DIFFERENT THAN THE ONE SHOWN ON SHEET S-2. REVISE
 EITHER ONE AS REQUIRED TO MATCH EACH OTHER. (REPEAT
 COMMENT NOT ADDRESSED AT ALL).
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status F Date 2007-10-30 Cont ID  
Sent By jgomez Date 2007-10-30 Time 07:47 Rev Time 0.00
Received By jgomez Date 2007-10-30 Time 07:41 Sent To PC
Notes
2007-10-30 08:08:49TRUSS PACKAGE BUILDING REVIEW CHECKLIST.
  
 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72FOR STRUCTURAL CONNECTORS HU214-3AND HU210-2
 ATTACHED DIRECTLY TO MASONRY WALL TO VERIFY COMPLIANCE
 WITH THE CALCULATED LOADS FOR GIRDER TRUSS FG02,FG09
 (NOTE: FG09 IS A 5 PLY TRUSS), FG10 (NOTE: FG10IS A 4
 PLY TRUSS).FG06 (SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.ENGINEER OF RECORD TO REVIEW AND APPROVE IN
 WRITING ALL PRODUCT APPROVALS PRIOR TO SUBMITTAL TO
 THIS OFFICE. SEC. 106.3.3 CITY AMENDMENTSTO FBC
 2004.
  
 2- STRUCTURAL ENGINEER OF RECORD NEEDS TO REVISE PLANS
 AS REQUIRED TO SHOW THE DESIGN LOADS REQUIRED BY TABLE
 1607.1 FBC 2004 FOR ASSEMBLY PART OF THE BUILDING,
 INCLUDING THE BALCONY AREA.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 3- ALLFLOOR TRUSSES NEED TO BE DESIGNED PER TABLE
 1607.1 FBC 2004 FOR DISTRIBUTED AND CONCENTRATED LIVE
 LOADS FOR ASSEMBLY PORTION OF THE BUILDING. AND, FOR
 BALCONY AREAS. REVISE AS REQUIRED. NOTE: VERIFY THAT
 SPECIFIEDCONNECTORS MEET THE CALCULATED LOADS TO
 AVOID DELAYS OR CONFLICTS.
  
 4- IF FLOOR TRUSSES ARE ALREADY INSTALLED, THEN
 ENGINEER NEEDS TO PROVIDE COMPLETE ENGINEERING PACKAGE
 TO SHOW HOW TRUSSES ARE REINFORCED TO RESIST ALL LOADS
 REQUIRED BY TABLE 1607.1 FBC 2004.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 5- REVISED TRUSS PACKAGE TO BE REVIEWED AND APPROVED BY
 THE ENGINEER OF RECORD PRIOR TO SUBMITTAL TO THIS
 OFFICE.
  
 6- IF PROVIDING COVER OR INDEX SHEET TO AVOID SIGNING
 AND SEALING ALL INDIVIDUAL TRUSSES, THEN ALL
 INFORMATION REQUIRED BY SEC. 61G15-31003 SHALL BE
 SUBMITTED. THIS PACKAGE IS MISSING STRUCTURAL ENGINEER
 OF RECORD INFORMATION, PROPER IDENTIFICATION OF PROJECT
 (AND ADDRESS SHOWN IS NOT CORRECT) AND A CLEARNAMING
 AND NUMBERING SYSTEM.INDIVIDUAL SHEETS ARE NOT
 NUMBERED, WHICH ALLOWS TO MATCH INDEX SHEET.
  
 7- TRUSS LAYOUT IS NOT SIGNED AND SEALED AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTE.
  
 8- CLARIFY WHY THE ATTIC LIVE LOAD IS NONCONCURRENT
 WITH ANY OTHER LIVE LOADS IF FBC 2004 TABLE 1607.1
 REQUIRES ALL MINIMUM LIVE LOADS TO BE INCLUDED IN THE
 DESIGN.CLARIFY WHICH ARE THE OTHER NONCONCURRENT LIVE
 LOADS.SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 9- THIS PROJECT HAS A RESIDENT INSPECTOR, THEREFORE 3
 COMPLETE SETS OF TRUSS DRAWINGS ARE REQUIRED.
  
 10- PROVIDE COMPLETE ENGINEERING SPECS FOR BOLTING
 CRITERIA OF 4 AND 5 PLY GIRDERS AS REQUIRED ON TRUSS
 LAYOUT NOTES. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 11- ROOF TRUSSLAYOUTAT THE END WINGS OF THE
 BUILDING IS DIFFERENTTHAN THAT ONE SHOWN ON SHEET
 S-2. REVISE AS REQUIRED.
  
 12- UNABLE TO READ TRUSS HANGER FOR GIRDER TRUSS C15GA,
 C13 AND C11 TO VERIFY COMPLIANCE OF CONNECTOR WITH
 CALCULATED LOADS. PROVIDE CLEAR SPECIFICATIONS. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2007-08-06 Cont ID  
Sent By jgomez Date 2007-08-06 Time 13:38 Rev Time 0.00
Received By jgomez Date 2007-08-06 Time 13:38 Sent To PC
Notes
2007-08-06 13:38:51PRODUCT APPROVAL REVISION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2007-07-25 Cont ID  
Sent By jgomez Date 2007-07-25 Time 18:50 Rev Time 0.00
Received By jgomez Date 2007-07-25 Time 18:50 Sent To PC
Notes
2007-07-25 18:50:21BUILDING REVISION CHECKLIST:
 1- ROOF VENT:
 A) ARCHITECT APPROVED ROOF VENT NOA 01-0614.05. THIS
 NOA EXPIRED ON 08/16/2006.DADE COUNTY NOA'S SHALL
 NOT BE VALID AFTER EXPIRATION DATE.SEE SECOND
 PARAGRAPH ON COVER PAGE OF NOA SUBMITTED.
  
 B)ARCHITECT'S NOTE: "CONTRACTOR RESPONSIBLE FOR
 PROVIDING REQ'D VENTING PER CALCULATIONS ON DRAWINGS".
 IT'S THE ARCHITECT'S RESPONSIBILITY TO VERIFY IFTHE
 NUMBER OFVENTS SHOWN ON PLANSMEET THE VENTING
 CALCULATIONS USING THE REVISED VENT,NOT THE
 CONTRACTOR.CONTRACTOR'SRESPONSIBILITYIS TO
 INSTALLNUMBER OF VENTS VENTSAS SPECIFIED ON PLANS.
 NOT TO MAKE CALCULATIONS.IF REVISEDVENT DOESN'T
 MEET THE VENTING CALCULATIONS, THEN REVISE PLANS AS
 REQUIRED.
  
 C) THERE ARE TWO DIFFERENT REVIEW STAMPS. ONE OF
 THEM IS CLEAR THAT IS THE ARCHITECT'S REVIEW STAMP.
 WHO'S REVIEW STAMP IS THE OTHER ONE.THE PURPOSE OF
 THE REVIEW STAMP IS TO DISCLOSE WHO REVIEW IT.
 OTHERWISE IT'S MEANINGLESS.
  
 ***NOTE: SAME COMMENT APPLIES TO SHINGLES PRODUCT
 APPROVAL.
  
 2- REVISION FEES ARE $50.00PLUS $10.00 PER ADDITIONAL
 PAGE. OWES $80.00.INFORMATION SUBMITTED IS REVISED
 SHEET A705, PLUS PRODUCT APPROVAL FOR SHINGLES, PLUS
 PRODUCT APPROVAL FOR ROOF VENT.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2007-07-09 Cont ID  
Sent By jgomez Date 2007-07-09 Time 16:58 Rev Time 0.00
Received By jgomez Date 2007-07-09 Time 14:09 Sent To PC
Notes
2007-07-09 16:58:59TRUSS PACKAGE CHECKLIST:
 1-A) ONLY TWO SETS WERE SUBMITTED. THIS TYPE OF
 PROJECT REQUIRES THREE COMPLETE SETS.THREE SIGNED AND
 SEALED SETS AS REQUIRED BY CHAPTER 471 FLORIDA STATUTE
 AND SEC. 61G15-23 OF FLORIDA ADMINISTRATIVE CODE.
  
 B) TRUSS ENGINEER TO PROVIDE ALL THREE SETS WITH
 ORIGINAL SIGNATURE. COPY OF SIGNATURE IS NOT ALLOWED BY
 CHAPTER 471 FLORIDA STATUTE.
  
 C) EVERY INDIVIDUALSHEETNEEDS TO HAVE
 ENGINEER'S ORIGINAL SEAL, SIGNATURE AND DATE.
 OTHERWISE, ENGINEER MAY WANT TO FOLLOW ALL CONDITIONS
 REQUIREDBY SEC. 61G15-31.003 FLORIDA ADMINISTRATIVE
 CODE TO COMPLY WITH THE SIGNING AND SEALING OF ALL
 SHEETS.INFORMATION SUBMITTED DOESN'T COMPLYWITH
 THIS SECTION.
  
  
 2- ENGINEER OF RECORD DESIGNED FLOOR TRUSSES TO BE
 RESTING ON TOP CHORD.TRUSS PACKAGE SHOWS FLOOR
 TRUSSES RESTING ON A TRUSS HANGER SUPPORTING TRUSS ON
 BOTTOM CHORD. REVISE EITHER TRUSS PACKAGE OR ENGINEERED
 DRAWINGS AS REQUIRED TO MATCH. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2007-06-13 Cont ID  
Sent By jgomez Date 2007-06-13 Time 16:47 Rev Time 0.00
Received By jgomez Date 2007-06-13 Time 16:47 Sent To PC
Notes
2007-06-13 16:47:54REVISION CHECKLIST:
  
 1- THIS IS NOT A SUBMITTALBUT A REVISION ON
 PREVIOUSLY APPROVED PRODUCT APPROVALS. THEREFORE OWES
 $80.00 FOR REVISION FEES.
  
 2- ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND
 APPROVED IN WRITING (NOT SIGNING AND SEALING) BY THE
 DESIGNER OF RECORDAS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004. PRODUCT APPROVALS SUBMITTED
 DON'T SHOWDESIGNER OF RECORD APPROVAL IN WRITING.
  
 3- SINGLE HUNG WINDOWS PRODUCT APPROVAL:
 A) PROVIDE CURRENT PRODUCT APPROVAL FL42-R4. (ONE
 SUBMITTED IS FL 42-R1).
  
 B) PROVIDE ONLY ALL THE TECHNICAL INFORMATION
 (DRAWINGS, SPECS, ETC) THAT WAS SUBMITTED TO OBTAIN THE
 FLORIDA PRODUCT APPROVAL. GO THE FLORIDA WEBSITE
 WWW.FLORIDABUILDING.ORG AND DOWNLOAD CORRESPONDING
 INFORMATION TO SPECIFIC MODEL TO BE INSTALLED.
  
 C) MAKE SURE ALL DRAWINGS ARE LEGIBLE.
  
 4- SLIDING GLASS DOORS:
 A) SAME COMMENTS AS FOR SINGLE HUNG WINDOWS APPLY.
  
 5- FIXED WINDOWS.
 A) SAME COMMENTS AS FOR SINGLE HUNG WINDOWS APPLY.
  
 6- SWING DOORS:
 A) PROVIDE CLEAR AND LEGIBLE DRAWINGS.
  
 B) PROVIDE PRODUCT APPROVAL FOR SIZE OF DOORS AS
 SPECIFIED ON PLANS.
  
 ***NOTE:
 RESUBMITTAL FEES FOR REVISIONS ARE THE SAME AS FOR THE
 FIRST TIME REVISIONS ARE SUBMITTED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status N Date 2007-03-28 Cont ID  
Sent By jgomez Date 2007-03-28 Time 12:44 Rev Time 0.00
Received By jgomez Date 2007-03-28 Time 12:38 Sent To  
Notes
2007-03-28 12:39:38CHANGE OF ADDRESS FROM 1825 CHEERFUL COURT TO 451
 CHEERFUL CT. WRITING NEW ADDRESS ON OFFICE SET.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-02-14 Cont ID  
Sent By jgomez Date 2007-02-13 Time 18:59 Rev Time 0.00
Received By jgomez Date 2007-02-13 Time 18:57 Sent To  
Notes
2007-02-13 18:58:01BUILDING REVIEW APPROVED WITH PROVISO:
 1- PROVIDE CORRECT DRAWINGS FOR ENTRY DOOR.NOA
 02-0215.04 SUBMITTED HAS THE "INSWING" DOOR DRAWINGS.
 THIS IS A DADE COUNTY PRODUCT APPROVAL DIVISION MISTAKE
 THAT WAS ALREADYREVISED. NOW WEBSITE HAS CORRECT
 "OUTSWING" DOOR DRAWINGS. PROVIDE 3 COPIES, REVIEWED
 AND APPROVED BY THE DESIGNER OF RECORD.
  
 2-RINKER SPECIFICATIONS LETTER FOR 2 HOUR CONCRETE
 BLOCK: PROVIDE LETTER ADDRESSED TO THE CITY OF WEST
 PALM BEACH AND WITH CORRECT PROJECT NAME.THIS IS
 MERRY PLACE PROJECT, NOT BOCA DEVELOPMENT.
  
 3- DESIGNER OF RECORD TO PROVIDE COMPLETE
 SPECIFICATIONS/DETAILS FOR INSTALLATION OF HARDISOFFIT
 & CEMSOFFIT PANELS. SEE SHEET 3 OF 3 OF NOA 02-0729.02
 DRAWINGS SUBMITTED. SEC. 106.1.2 CITY AMENDMENTSTO
 FBC 2004.
  
 4- SUBMIT ALL TRUSS DRAWINGS FOR REVIEW PRIORTO
 CONSTRUCTION/INSTALLATION. TRUSS PACKAGE TO BE REVIEWED
 AND APPROVED BY DESIGNER OF RECORDPRIOR TO
 SUBMITTAL.
  
 5- PROVIDE ADDITIONAL PROJECT MANUAL. ONLY 2 COPIES
 FOUND IN THE SUBMITTAL.
  
 6- PROVIDE COPY OFTHE RECORDED MERRY PLACE PLAT FOR
 CITY RECORDS.
  
 6- PROVIDE 3 COPIES OF APPROVED AND RECORDED SURVEY
 SHOWING UNITY OF TITLE REVISION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-01-03 Cont ID  
Sent By jgomez Date 2007-01-03 Time 15:37 Rev Time 0.00
Received By jgomez Date 2007-01-03 Time 15:37 Sent To  
Notes
2007-01-03 16:06:44BUILDING REVIEW SECOND CHECKLIST:
 1- REVISE ENERGY CALCULATIONS:
 A) AS REQUESTED ON PREVIOUS CHECKLIST, CALCULATIONS
 NEED TO BE DONE FOR THE WHOLE BUILDING, NOT FOR EACH
 UNIT AS REQUIRED BY SEC. 13-600.0 METHOD A OF FBC
 2004.
  
  
 B) AS REQUESTED ON PREVIOUS CHECKLIST, ENGINEER TO
 PROVIDE ALL HIS INFORMATION AS REQUIREDBY CHAPTER 471
 FLORIDA STATUTES AND FLORIDA ADMINISTRATIVE CODE SEC.
 61G15-23.002.
  
 C) CALCULATIONS SUBMITTED FOR INDIVIDUAL UNITS HAVE
 THE FOLLOWING INCORRECT INFORMATION:
 * NUMBER OF BEDROOMS.
 ** SLAB ON GRADE TOTAL PERIMETER FEET.
 *** CLARIFY HOW ARE THESE CALCULATIONS DONE FOR
 WORST CASE SCENARIO IF THERE IS NOT SHEET SHOWING
 OPENINGS SUN EXPOSURE ORIENTATION.
  
 2- REVISION CLOUDS ON SHEET A004 DON'T ALLOW THE OTHER
 INFORMATION TO BE LEGIBLE.REVISE AS REQUIRED.
  
 3- SURVEY AND SITE PLAN SHOWN ON SHEETS A100, A101 AND
 A102 DON'T MATCH.ACCORDING TO THE RECORDED SURVEY,
 THERE IS AN ALLEY BY BUILDING C3. SITE PLAN SHOWS
 PARKING SPACES. REVISE AS REQUIRED. THIS COMMENT COULD
 NOT BE ADDREESED BEFORE BECASUE THIS IS THE FIRST TIME
 SURVEY IS SUBMITTED FOR REVIEW.
  
 4- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) UNIT ENTRY DOOR: DRAWINGS SUBMITTED ARE FOR
 "INSWING" DOORS. NEED DRAWINGS FOR "OUTSWING" DOORS.
  
 B) ALL USP OR SIMPSON CONNECTORS SPECIFIED ON PLANS
 AND DETAILS.PROVIDE FLORIDA PRODUCT APPROVAL COVER
 PAGE AND PAGE SHOWING THE CONNECTOR.
  
 C) 2 HOUR CONCRETE BLOCK AS REQUIRED BY UL WALL
 ASSEMBLY U905.
  
 D) CEMENTITIOUS PANELS AT ENTRY OVERHANGS. SEE
 DETAIL 11/A705.
  
 E) EXTERIOR DOOR PANEL FOR RECESSED GAS WATER
 HEATER.
  
 5- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004.
  
 6- NEED TO CONTACT HAROLD PISKURA, INSPECTION SERVICES
 MANAGER (561)805-6711, TO COORDINATE SPECIAL INSPECTOR
 SERVICES.
  
 7- PLEASE MAKE SURE ENERGY CALCULATIONS MATCH
 CORRESPONDING BUILDING ADDRESS, BUILDING TYPE, PERMIT
 NUMBER ETC.
  
 8- PROVIDE ENERGY CALCULATIONS FOR COMMERCIAL AREA. AS
 REQUIRED BY CHAPTER 13 FBC 2004.
  
 9- PROJECT MANUAL SPECS NEED TO HAVE COMPLETE
 ENGINEERING FIRM AND ENGINEER'S INFORMATION AS REQUIRED
 BY BY CHAPTER 471 FLORIDA STATUTES AND FLORIDA
 ADMINISTRATIVE CODE SEC. 61G15-23.002 AND REQUESTED ON
 PREVIOUS CHECKLIST.
  
 10- THE INTENTION OF THE CODE IS TO DETERMINE THE
 MAXIMUM NUMBER OF PEOPLE EXPECTED TO OCCUPY THE
 BUILDING OR ROOMS OR SPACES WITHIN THE BUILDING AT ANY
 GIVEN TIME AND UNDER ALL PROBABLE CONDITIONS. THIS IS A
 SAFETY ISSUE BECAUSE DEPENDING ON THE NUMBER OF PEOPLE
 ALL EGRESS REQUIREMENTS SHALL BE MET.THEATRE ROOM
 HAS SPACE FOR STANDING PEOPLE AND THEY NEED TO BE
 COUNTED ALSO.CHAIRS NEED TO BE PART OF THE CONTRACT
 FOR PROPER INSPECTIONS.NEED TO PROVIDE AISLE
 DIMENSIONS AND ALL NECESSARY INFORMATION TO REVIEW FOR
 CHAPTER 11 OF FBC 2004. OCCUPANCY LOAD CALCULATIONS
 NEED TO BE ESTABLISHED BY THE LARGEST NUMBER COMPUTED
 IN ACCORDANCE WITH SECTIONS 1004.1.1 THROUGH 1004.1.3.
 ACCORDING TO THIS SECTION TABLE 1004.1.2 FBC 2004 AND
 FLOOR PLANS, THE FLOOR AREA PER OCCUPANT SHALL BE
 CALCULATED FOR 5S.F. PROVIDE CALCULATIONS FOR NUMBER OF
 PEOPLE ON EACH ROOM OR SPACE TO VERIFY COMPLIANCE WITH
 TOTAL NUMBER OF PEOPLE.
  
 ***NOTE: ELECTRICAL PLANS CALL FOR CONFERENCE/MEETING
 ROOM. WHERE IS THIS ROOM LOCATED AT?.
  
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-12-06 Cont ID  
Sent By jgomez Date 2006-12-06 Time 18:31 Rev Time 0.00
Received By jgomez Date 2006-12-06 Time 18:31 Sent To  
Notes
2006-12-06 18:31:51BUILDING REVIEW CHECKLIST:
  
 1- NOTICE OF COMMENCEMENT AND IMPACT FEES STAMPED
 DRAWINGS AND PAID RECEIPTS WILL BE SUBMITTED LATER WHEN
 ISSUING PERMIT.
  
 2- REVISE ENERGY CALCULATIONS:
 A) CALCULATIONS NEED TO BE PERFORMED FOR THE WHOLE
 BUILDING, NOT FOR EACH UNIT. SEC. 13-600.0 METHOD A OF
 2004 FBC.
 B) NAME AND LICENSE # OF ENGINEER AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTES.
 C) PROVIDE COMPLETE INFORMATION FOR ITEM #8, FLOOR
 TYPES.
 D) INSULATION R VALUE SPECIFIED IN PROJECT MANUAL
 SPECS SEC. 07200 TO MATCH ENERGY CALCULATIONS.
 E) PROVIDE COMPLETE INFORMATION ON TOP OF FORM. NEED
 ADDRESS AND BUILDER NAME.
 F) OWNER/AGENT TO SIGN AND DATE ALL ENERGY FORMS.
 NOTE: THIS APPLIES TO ALL ENERGY FORMS FOR ALL
 BUILDINGS. CHECK ALL ENERGY FORMS TO BE SUBMITTED.
  
 3- NEED SIGNED AND SEALED SURVEYS SHOWING EXACT
 LOCATIONS OF BUILDINGS IN RELATIONSHIP WITH THE
 PROPERTY LINES AND OTHER BUILDINGS TO VERIFY COMPLIANCE
 WITH TABLES601, 602 FOR FIRE RESISTANCE AND TABLE
 704.8 FBC 2004 FOR OPENINGS ALLOWED.PROVIDE ALL
 DISTANCES BETWEEN BUILDINGS AND PROPERTY LINES AND MAKE
 SURE ALL BUILDINGS HAVE THE DIMENSIONS BETWEEN BUILDING
 SEPARATION FOR BUILDINGS ON SAME LOT. IF BUILDINGS ARE
 ON SAME LOT, THEN SPECIFY THE PROPOSED PROPERTY LINE
 BETWEEN THEM.BUILDINGS WITH IRREGULAR SHAPES NEED TO
 SHOW DIMENSIONS WITH CLOSEST DISTANCE TO ADJACENT
 BUILDINGS. EG: SOME BUILDINGS HAVE SETBACKS IN THE
 FOOTPRINT. MAKE SURE DISTANCES PROVIDED INCLUDE THE
 CLOSEST DISTANCE BETWEEN BUILDINGS. SITE PLAN SUBMITTED
 DOESN'T PROVIDE ALL THIS INFORMATION.
  
 4- ALL PROJECT MANUAL SPECIFICATIONS NEED TO BE SIGNED,
 SEALED AND DATED BY THE PROFESSIONAL IN CHARGE OF EACH
 SECTION. NEED ORIGINAL SEAL AND SIGNATUREAS REQUIRED
 BY CHAPTER 471 AND 481FLORIDA STATUTES.IN ADDITION
 ARCHITECTS AND ENGINEERS TO PROVIDE ALL THEIR
 INFORMATION AS REQUIRED BY FLORIDA ADMINISTRATIVE
 CODE.
  
 5- SHOW ACCESSIBLE ROUTE FROM PARKING SPACE TO ALL
 APARTMENT ENTRANCES, RECREATIONAL AREAS AND PUBLIC
 BUILDINGS.
  
 6- INFORMATION REGARDING HANDICAPPED UNITS AND
 ADAPTABLE UNITS IS CONFUSING. ACCORDING TO FAIR HOUSING
 ACT "ALL" GROUND FLOOR UNITS MUST BE "ACCESSIBLE" FROM
 THE PARKING SPACE TO THE UNIT ENTRANCE. THEN, ALL THE
 UNITS MUST BE "ADAPTABLE".
 INFORMATION ON SHEET A100 IS INDICATING THAT THERE ARE
 9 "ADAPTABLE" UNITS ON ACCESSIBLE ROUTE (NOTE #4).IF
 THE INTENTION IS TO GO BEYOND FHA AND TO HAVE
 ACCESSIBLE UNITS, THEN CLARIFY AS REQUIRED.
  
 7- SHEET A004:
 A) OCCUPANCY LOAD CALCULATIONS NEED TO BE
 ESTABLISHED BY THE LARGEST NUMBER COMPUTED IN
 ACCORDANCE WITH SECTIONS 1004.1.1 THROUGH 1004.1.3.
 ACCORDING TO THIS SECTION,TABLE 1004.1.2 FBC 2004 AND
 FLOOR PLANS, THE FLOOR AREA PER OCCUPANT SHALL BE
 CALCULATED FOR 5S.F. PER PERSON. REVISE OCCUPANT LOAD
 CALCULATIONS AS REQUIRED. PROVIDE CALCULATIONS
 INDEPENDENTLY FOR EACH ROOM OR AREA.5S.F. PER AREA
 SHOULD BE CALCULATED FOR THEATRE,MULTI-PURPOSE ROOM
 AND LIBRARY AREA. THESE ARE AREAS THAT CAN BE USED FOR
 DIFFERENT PURPOSES. THEREFORE, THE LARGEST NUMBER OF
 PEOPLE NEED TO BE CALCULATED TO COVER ALL POSSIBLE
 USES.
  
 B) MISSING UNIT MODEL TYPE IN PROJECT TABULATION
 CHART.
 C) BUILDING AND UNIT AREAS DON'T MATCH. SEE SHEET
 A004 AND SHEETS A201,A203, A306, A801 AND A802.
 REVISE AS REQUIRED. NEED CORRECT AREAS TO ESTIMATE
 BUILDING VALUATION. SEC. 108.3 CITY AMENDMENTS TO FBC
 2004. PROVIDE PORCHES, BALCONIES AND BUILDING AREAS.
  
 8- SHEET A101:
 A) SPECIFY NUMBER OF PARKING SPACES REQUIRED BY
 ZONING FOR BUILDING F1 TO VERIFY COMPLIANCE OF
 HANDICAPPED SPACES PROVIDED AS REQUIRED BY CHAPTER 11
 FBC 2004.
  
 B) HANDICAPPED PARKING FOR FAIR HOUSING ACT UNITS
 AND CHAPTER 11 FBC 2004 CAN'T OVERLAP TO ACCOMPLISH
 TOTAL NUMBER OF REQUIRED PARKING SPACES. IDENTIFY
 HANDICAPPED PARKING SPACES FOR PUBLIC BUILDING AND FOR
 RESIDENTIAL UNITS.
  
 C) PROVIDE DRAWINGS SHOWING PARKING SIZES AND
 ACCESSIBLE ROUTEFROM PARKING SPACE TO PUBLIC ASSEMBLY
 BUILDING F1TO VERIFY COMPLIANCE WITH CHAPTER 11 FBC
 2004. ALSO, PROVIDE SAME INFORMATION FOR ALL
 RESIDENTIAL GROUND UNITS.
  
 D) SPECIFY IF PROVIDING VISITORS PARKING SPACES TO
 VERIFY COMPLIANCE WITH FAIR HOUSING ACT.
  
 9- OWNER TO PROVIDE LETTER CERTIFYING THAT NO FEDERAL
 MONIES ARE USED FOR THIS PROJECT. OTHERWISE,PROJECT
 NEEDS TO BE REVIEWED FOR SECTION 504 OF THE
 REHABILITATION ACT COMPLIANCE.
  
 10- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) SINGLE HUNG WINDOW. NOA 01-0629.08 IS EXPIRED.
 ALSO, NEED FLORIDA PRODUCT APPROVAL COVER PAGE. GO TO
 WWW.FLORIDABUILDING.ORG TO DOWNLOAD CORRESPONDING COVER
 PAGE. FLORIDA PRODUCT APPROVAL COVER PAGE APPLIES TO
 ALL PRODUCT APPROVALS. IF THERE IS NO FLORIDA PRODUCT
 APPROVAL, THEN SUBMIT THE DADE COUNTY NOA ONLY.
  
 B) UNIT ENTRY DOOR: DRAWINGS SUBMITTED ARE FOR
 "INSWING" DOORS. NEED DRAWINGS FOR "OUTSWING" DOORS.
  
 C) ALL USP OR SIMPSON CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING SPECIFIC CONNECTOR.
  
 D) 2 HOUR CONCRETE BLOCK AS REQUIRED BY UL WALL
 ASSEMBLYU905.
  
 E) EXTERIOR DOOR PANEL FOR RECESSED GAS WATER
 HEATER.
  
 F) FIXED WINDOWS: NEED PRODUCT APPROVAL FOR LARGE
 MISSILE IMPACT AS REQUIRED BY SEC. 1609.1.4. NOA
 02-0123.03 IS FOR SMALL MISSILE IMPACT RESISTANT
 WINDOWS. ALSO, PROVIDE FLORIDA COVER PAGE.
  
 G) ALUMINUM TUBE MULLIONS: NEED PRODUCT APPROVAL FOR
 LARGE MISSILE IMPACT. NOA 02-0501.04 SUBMITTED HAS NOT
 RATING FOR MISSILE IMPACT. ALSO, PROVIDE FLORIDA
 PRODUCT APPROVAL COVER PAGE.
  
 ***NOTE: FROM SUBMITTED NOA SPECIFY SPECIFIC FASTENING
 METHOD TO VERIFY COMPLIANCE WITH SEC. 1609 FBC 2004.
  
 H) SLIDING GLASS DOORS: PROVIDE FLORIDA PRODUCT
 APPROVAL COVER PAGE.
  
 I) LEASING/RES. SVC ENTRY DOORS: PROVIDE FLORIDA
 PRODUCT APPROVAL COVER PAGE.
  
 J) FRENCH DOORS: PROVIDE FLORIDA PRODUCT APPROVAL
 COVER PAGE.
  
 K) ROOF SHINGLES: PROVIDE FLORIDA PRODUCT APPROVAL
 COVER PAGE.
  
 L) RIDGE VENT: PROVIDE FLORIDA PRODUCT APPROVAL
 COVER PAGE.
  
 M) OFF RIDGE VENT: PROVIDE FLORIDA PRODUCT APPROVAL
 COVER PAGE.
  
 N) CEMENTITIOUS PANELS FOR ENTRY OVERHANGS. SEE
 DETAIL 11/A705.
  
 O) FALSE SKYLIGHT. SEE ELEVATIONS.
  
  
 11- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 12- SHEET A103:
 A) REVISE DETAIL 19 TO MATCH DETAIL 7/700.1. SHELVES
 HEIGHT 48" MAX.
  
 B) PROVIDE DETAILS/SPECS FOR GRAB BARS
 REINFORCEMENT. MATERIAL AND INSTALLATION. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
  
 13- SHEET A104:
 A) CLARIFY COMMON USE FACILITIES NOTE # 2A. WHAT'S
 THE QUESTION MARK FOR?.
 B) REVISE RESTROOMS NOTE # 5C. SEE FIGURE 30 ON
 CHAPTER 11 FBC 2004.
  
 14- SHEET 110:
 A) DETAIL 20: CLARIFY QUESTION MARKS ON CONCRETE
 BLOCK THICKNESS.
 B) UPDATE ASSEMBLY AND PENETRATIONS SCHEDULE.
 REFERENCE UL 2004, NOT UL 1999.
 C) DETAIL18: REQUIRES 2X10 JOISTS AT 16" O.C.
 REVISE UNDER STAIR DETAILS TO MATCH THIS ASSEMBLY.
  
 15- SHEET A201:CLARIFY SQUARE FOOTAGES.ALSO,
 COORDINATE ALL THESE AREAS WITH GENERAL AREA TABULATION
 ON SHEET A004.
  
 16- SHEET A203:
 A) SPECIFY DOOR SIZE FOR DOOR LEADING TO MASTER
 BEDROOM.
  
 B) CLARIFY ALL SQUARE FOOTAGES. GROSS AND NET AREAS
 AND COORDINATE WITH INFORMATION ON SHEET A004.
  
 C) PANTRIES WITH NARROW DOORS TO HAVE 18" MAX.
 DEPTH. SEE PAGE 7.17 FAIR HOUSING ACT.
  
 D) SECONDARY BEDROOM CLOSET DOOR NEEDS TO COMPLY
 WITH FAIR HOUSING ACT. NEED WIDER DOORS TO ALLOW
 REACHING AT THE ENDS OF CLOSET. SEE PAGE 3.14 FAIR
 HOUSING ACT AND REVISE AS REQUIRED.
  
 17- SHEET A306:
 A) GIVEN THE ROOF LAYOUT, VENTILATION CALCULATIONS
 NEED TO BE PERFORMED FOR EACH INDEPENDENT ROOF.NEED
 SEPARATE CALCS FOR MAIN ROOF ATASSEMBLYBUILDING,
 REAR PART OF ASSEMBLYBUILDING,ENTRY TOWER OF
 ASSEMBLY BUILDING AND EACH WING OF RESIDENTIAL UNITS.
 SEC. 1203 FBC 2004 AND SEC. 106.1.2 CITY AMENDMENTSTO
 FBC 2004.
  
 B) VENTILATION CALCULATIONS: COORDINATE SIZE OF
 RIDGE VENT. SEE RIDGE VENT PRODUCT APPROVAL FOR
 REQUIRED OPENING. REVISE CALCULATIONS AS REQUIRED.
 REVISE DETAIL 16/A705 AS REQUIRED TOO.
  
 C) GENERAL ROOF NOTE #2 CALLS FOR DETAIL 14/A705.
 THERE IS NOT SHUCH DETAIL. REVISE AS REQUIRED.
  
 D) PLANS ARE REFERING TO DETAILS ON SHEETS A501 AND
 A502. SUCH SHEETS ARE MISSING.
  
 18- SHEET A400:
 A) ALL DETAILS TO SPECIFY PRESSURE TREATED WOOD (OR
 ANY OTHER APPROVED METHOD TO ISOLATE WOOD WHEN IN
 CONTACT WITH CONCRETE OR CONCRETE BLOCK). SEC. 2304.11
 FBC 2004.
  
 B) ENLARGED ELEVATIONS DON'T CORRESPOND TO THIS
 BUILDING. REVISE AS REQUIRED.
  
 19- SHEET A406:
 A) FRONT ELEVATION DOESN'T MATCH FLOOR PLAN. MISSING
 WINDOW ON FIRST FLOOR. REVISE AS REQUIRED.
  
 B) DETAIL SECTIONS KEYED TO SEE SHEET A501 AND A502.
 MISSING THOSE SHEETS.
  
 20- SHEET A500:
 A) SECTION 17:FLOOR ASSEMBLY L-521 AND INFORMATION
 ON TYPICAL FLOOR CONSTRUCTION ON SAME DRAWING DON'T
 MATCH. ALSO, INFORMATION DOESN'T MATCH SPECIFICATIONS
 SHOWN ON SHEET A111. REVISE AS REQUIRED.
  
 B) REVISE INFORMATION ON UL L-521 ON SHEET A111. SEE
 2004 UL BOOK AND REVISE SPECS TO MATCH SUCH LISTING.
  
 C) SPECS ON WALL ASSEMBLY U905 DON'T MATCH
 INFORMATION SHOWN ON SAME DRAWING POINTING TO WALL
 AREA. REVISE AS REQUIRED.
  
 D) PROVIDE INFORMATION THAT ADDRESSES MIN. LABELS OF
 SOUND INSULATION AS REQUIRED BY SEC. 1207.2 AND SEC.
 1207.3 FBC 2004.
  
 E) PROVIDE FIREBLOCKING AT ROOF ASSEMBLY
 INSTERSECTION. FLOOR ASSEMBLY NOTE ON DETAIL 17 CLEARLY
 SPECIFIES TO SEAL JOINTS AT WALL. THIS IS NOT SPECIFIED
 AT CEILING AREA. SEC 717 FBC 2004.
  
 21- SHEET A501: MISSING DETAIL 14/A705 SPECIFIED ON
 WALL SECTIONS 16 AND 18.
  
 22- SHEET A510:SPECIFY FIREBLOCKING AT ALL CONCEALED
 SPACES. SEC. 717 FBC 2004.
  
 23- SHEET A511: SPECIFY FIREBLOCKING AT ALL CONCEALED
 SPACES. SEC. 717 FBC 2004.
  
 24- SHEET A604:
 A) HANDRAILS ENDS TO COMPLY WITH SEC. 11-4.9.4 FBC
 2004. EXTENSIONS NEED TO BE STRAIGHT. NEED TO COMPLY
 ALSO WITH SEC. 11-4.4 FBC 2004.
  
 B) STAIRWAY LANDINGS SHALL NOT BE LESS THAN THE
 WIDTH OF THE STAIRWAYS. SEC. 1009.4 FBC 2004. REVISE AS
 REQUIRED.
  
 25- SHEETA701.1:DETAIL 01: HOW IS THE FASTENER
 EMBEDED 1-1/4" INTO THE BUCK IF THE BUCK IS ONLY 1X
 THICK. REVISE AS REQUIRED.
  
 26- SHEET A703: WOOD IN CONTACT WITH CONCRETE BLOCK TO
 BE PRESSURE TREATED. REVISE DETAILSAS REQUIRED.
  
 27- SHEET A705:
 A) DETAIL 02:REVISE FLASHING FASTENER SPACING AS
 REQUIRED BY ROOFING APPLICATION STANDARD RAS 111.
  
 B) REVISE DETAIL 16. SEE RIDGE VENT PRODUCT APPROVAL
 FOR RIDGE CUT OUT DIMENSION.
  
 C) PROVIDE COMPLETE STRUCTURAL DETAIL SHOWING
 INSTALLATION OF FALSE SKYLIGHT TO COMPLY WITH SEC. 1609
 FBC 2004.
  
 28- SHEET A706.1:
 A) DETAIL 00 (?): CHECKHOOD SPECIFICATIONS FOR
 MIN. CLEARANCE REQUIRED FROM THE RANGE. PROVIDEHOOD
 SPECS AND REVISE DETAIL AS REQUIRED.
  
 29- SHEET A801:
 A) PROVIDE SQUARE FOOTAGE INCLUDING ENTRY PORCH.
 COORDINATE WITH SHEET A004
  
 B) PROVIDE DETAILS FOR DRINKING FOUNTAIN TO VERIFY
 COMPLIANCE WITH SEC. 11-4.4 FBC 2004.
  
 C) PROVIDE ATTIC ACCESS AT ROOF ABOVE THEATRE. SEC.
 1209.2 FBC 2004.
  
 D) WIDTH OF STAIRS CAN'T BE REDUCED. REVISE AS
 REQUIRED. PROVIDE ALL DIMENSIONS.
  
 E) DOOR LEADING TO THE BREAK/FILE ROOM (FIRST FLOOR)
 DOESN'T COMPLY WITH CHAPTER 11 FBC 2004. SEE FIGURE 25
 (A). REVISE AS REQUIRED.
  
 30- SHEET A802:
 A) HANDRAILS DON'T COMPLY WITH SEC. 11-4.9.4 FBC
 2004. HANDRAILSNEED TO EXTEND IN THE SAME DIRECTION
 OF TRAVEL. REVISE AS REQUIRED AND COMPLY WITH SEC.
 11-4.4 FBC 2004 AS WELL.
  
 B) WIDTHOF STAIRS CAN'T BE REDUCED IN THE
 DIRECTION OF TRAVEL. REVISE AS REQUIRED.
  
 31- SHEET S-1: FOUNDATION PLAN STILL SHOWS A DROP AT
 THE ENTRANCE TO UNITS. REVISE AS REQUIRED.
  
 32- SHEET S-3: TRUSS TIE DOWN SCHEDULE. REVISE NOTE #6
 FOR CONNECTOR C (SIMPSON MGT). NEED 12" EMBEDMENT. SEE
 SIMPSON CATALOGUE.
  
 33- PROVIDE COMPLETE DETAILS AND SPECS FOR INSTALLATION
 OF RECESSED GAS WATER HEATER. PROVIDE DETAILS AND SPECS
 FOR WALL SEPARATING WATER HEATER AND AIR HANDLER UNIT.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-02-14 Cont ID  
Sent By dpalmer Date 2007-02-14 Time 11:12 Rev Time 0.00
Received By dpalmer Date 2007-02-14 Time 11:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-02-06 Cont ID  
Sent By dpalmer Date 2007-02-06 Time 11:36 Rev Time 0.00
Received By dpalmer Date 2007-02-06 Time 11:36 Sent To  
Notes
2007-02-06 11:37:24*** UNSAT ***
  
  
 1) NOTE: PLEASE SEE NOW A NEW ELECTRICAL SHEET E 306 IS
 BEING ADDED INTO THE SETS WITHOUT BEING SIGNED, DATED
 OR SEALED BY THE ENGINEER OF RECORD.
 PLEASE BE SURE ALL SHEETS CONTAIN A RAISED SEAL WHICH
 IS CLEAR AND VISIBLE ALONG WITH AN ORIGINAL SIGNATURE
 AND DATE AS REQUIRED PER FAC 61G15-23.002, 61G15-23.001
 AND FS 471.025.
  
 2) NOTE: PLEASE ALSO SEE THE TITLE BLOCKS INDICATE A
 REVISION *B*, HOWEVER A REV *B* COULD NOT BE LOCATED ON
 THE PLANS.
 PLEASE COORDINATE.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-12-17 Cont ID  
Sent By dpalmer Date 2006-12-17 Time 20:03 Rev Time 0.00
Received By dpalmer Date 2006-12-17 Time 19:39 Sent To  
Notes
2006-12-17 20:03:20PLANS OK, STAMPED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-11-26 Cont ID  
Sent By dpalmer Date 2006-11-26 Time 14:52 Rev Time 0.00
Received By dpalmer Date 2006-11-26 Time 13:47 Sent To  
Notes
2006-11-26 14:53:45MERRY PLACE
  
 1820 MERRY PLACE TYPE VI BLDG.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW AND SOME
 NEW NOTES DUE TO PLANS NOW BEING SUBMITTED WITH SOME
 ADDITIONAL INFORMATION.
  
 ********** UNSAT *************
  
 1) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.16 FOR
 THE MINIMUM REQUIRED CIRCUITING AND LOADS FOR THE
 DINING ROOM CIRCUIT(S). PLEASE ALSO SEE THAT NO OTHER
 ELECTRICAL DEVICES SUCH AS LIGHTING MAY BE PLACED ON
 SAID CIRCUIT.
 MUST BE 20A AND #12 AND ON ONE OR MORE OF THE CIRCUITS
 AS NOTED IN CODES ABOVE.
 PLEASE SEE THAT A DESIGNATED AREA AND THE LIKE SHALL BE
 INDICATED.
  
 2) NOTE: PLEASE BE SURE PLANS REFERENCE THE FOLLOWING
 CODES: NFPA-70 2002, NFPA-72 2002. THIS COULD NOT BE
 LOCATED ON PLANS AND IS REQUIRED.
  
 3) NOTE: PLEASE SEE HOUSE LOADS WHICH SHALL INDICATE
 ALL CONTINUOUS LOADS SUCH AS LIGHTING AT 125%. 215.3,
 230.42 ETC
 PLEASE SEE THE LIGHTING LOADS AS SHOWN DO NOT CORRELATE
 WITH THE NUMBER OF FIXTURES ON PLANS OR THE WATTAGE ON
 THE FIXTURE SCHEDULE. THE LOADS BEING SHOWN FOR
 INSTANCE FOR THE EXTERIOR LIGHTS IS LISTED AT 1000
 WATTS, HOWEVER AS THE FIXTURE TYPE ON PLANS SHOWS
 SEVENTEEN F-1 FIXTURES WHICH ARE 100 WATTS EACH THOSE
 ALONG EXCEED THE LOAD AS SHOWN ON PANEL SCHEDULE FOR
 THIS CIRCUIT.
 PLEASE SEE ALL INTERIOR LIGHTING FIXTURES AS SHOWN AND
 THE WATTAGE PER FIXTURE BASED ON FIXTURE SCHEDULE, THE
 NUMBER OF FIXTURES ON EACH CIRCUIT AND BE SURE ALL
 CORRELATE WITH THE PANEL SCHEDULE. PLEASE NOTE WITH
 RESPECT TO EMERGENCY AND/ EXITLIGHTS.
  
 4) NOTE:PLEASE SEE 410.8 FOR MINIMUM CLEARANCES
 PERMITTED IN STORAGE AREAS.
 (UNDER STAIRS) FIX TYPE "H". PLEASE KNOW, WHEN SHELVING
 IS NOT SHOWN, A MIN
 18" IS ASSUMED AND THE LIGHT FIXTURE AS SHOWN AND TYPE
 DESIGNATED SHALL MEET THE MIN CLEARANCES REQUIRED.
 PLEASE ADJUST
  
 5) NOTE: PLEASE SEE CALCULATIONS ALSO MENTIONS HEAT
 LOADS SHOWN AND BEING DONE AT 100%, YET THE KW RATINGS
 AS SHOWN DOES NOT CORRELATE WITH THE MECHANICAL PLANS
 OF 5KW?
 PLEASE ADJUST.
 220.21
  
 7) NOTE: PLEASE SEE E203 WHICH INDICATES A KEYNOTE #7,
 HOWEVER UNDER KEYNOTES, THERE IS NO #7?
 PLEASE SEE THIS APPEARS TO BE A DISPOSAL, HOWEVER THERE
 IS NOTHING LISTED ON PANEL SCHEDULES OR IN LOAD
 CALCULATIONS?
 PLEASE CLARIFY WHAT THIS IS?
  
 8) NOTE: PLEASE INDICATE CIRCUITING FOR THE EM/EXT
 LIGHTS AS REQUIRED PER 700.12E. PLEASE SEE NOTE #3
 ABOVE FOR LOADS.
 PLEASE BE SURE LIGHTING FIXTURES ARE WIRED AHEAD OF ANY
 LIGHTING CONTROL DEVICES.
  
 9) NOTE: PLEASE SEE THE MINIMUM LIGHTING LEVELS FOR
 EGRESS UNDER EMERGENCY POWER IS 1FT CANDLE IN ALL
 EGRESS PATHS. PLEASE ADD AN ADDITIONAL FIXTURE IN THE
 ENTRY/HALL WAY AREA TO BRING THE LESS THAN 1FT CANDLE
 AVERAGE SHOWN ON PLANS UP TO THE MIN LEVEL.
 NFPA-101 7.8, 7.9
  
 10) NOTE: PLEASE SEE CONTROL FOR PIT LIGHTS COULD NOT
 BE FOUND TO CONTAIN ANY AUTOMATED SHUT OFF AS REQUIRED.
  
 13-415.1.ABC.1.2
  
 11) NOTE: PLEASE SEE 13-415.1.AB.1, 13-415.2,
 13-415.2.ABC.1, FOR MAXIMUM LIGHTING POWER DENSITIES
 PERMITTED.
 COULD NOT LOCATE ANY ENERGY CALCULATIONS SUBMITTED WITH
 PLANS?
 PLEASE SEE SECTIONS ABOVE FOR LPD'S, WHICH CAN BE DONE
 ON THE PLANS ON A SMALL TABLE.
  
 12) NOTE: PLEASE 230.2, AT THIS TIME A SEPARATE SERVICE
 FOR THE ELEVATOR EQUIPMENT CAN NOT BE GRANTED AS THIS
 DOES NOT SEEM TO MEET THE EXCEPTIONS AS LISTED.
 PLEASE CLARIFY REQUIREMENTS FOR THIS, VOLTAGES, ETC.
 PLEASE KNOW, IF THE INFORMATION IS PROVIDED TO ALLOW
 THIS ADDITIONAL SERVICE, PLEASE BE SURE TO INDICATE THE
 BONDING AS REQUIRED TO THE MAIN SERVICE OF THE
 BUILDING.
 PLEASE KNOW WE ARE TAKING THIS IS A 3-PHASE SERVICE
 BASED ON THE 3-POLE MAIN AND CONDUCTORS AS LISTED,
 HOWEVER PLEASE INDICATE VOLTAGE ETC.
  
 13) NOTE: PLEASE INDICATE THE MAXIMUM TIMES PERMITTED
 ON THE TYPE OVER-RIDE DEVICES CHOSEN. (30 MINS FOR OC
 SENSOR TYPE AND 4HRS MAX FOR TIMER TYPES).
 13-415.1.ABC.1.1, .1.2
  
 14) NOTE: PLEASE SUBMIT AIC RATINGS FOR ALL SERVICE
 EQUIPMENT. 110.9, 240.12
 (MAIN FOR ELEVATOR SERVICE, IF PERMITTED)
  
 15) NOTE: PLEASE SEE THE ADDRESS ASSIGNED TO THE
 BUILDING AT ITS LOCATION HAS BEEN 1820; HOWEVER PLANS
 INDICATE 1824, PLEASE ADJUST AS REQUIRED.
 FAC 61G1-16.004
  
 *** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
  
 **IF THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF
 THE NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE
 DO NOT HESITATEIN CONTACTING THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2006-12-05 Cont ID  
Sent By lmartine Date 2006-12-05 Time 13:53 Rev Time 0.00
Received By lmartine Date 2006-12-05 Time 13:53 Sent To  
Notes
2006-12-05 13:54:23SEE 06101116

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2006-11-22 Cont ID  
Sent By rchokshi Date 2006-11-22 Time 16:39 Rev Time 0.00
Received By rchokshi Date 2006-11-22 Time 16:38 Sent To  
Notes
2006-11-22 16:38:57WE DO NOT HAVE THE CIVIL DWGS FOR THIS PERMIT PROJECT
 BUT WE REVIEWED,MADE FOLLOWING COMMENTS TO EXPEDITE
 THE PERMITTING PROCESS: PLEASE PROVIDE FOLLOWING INFO
 IN YOUR CIVIL DRAWINGS FOR THIS PERMIT SITE:
 1.DID YOU MAKE ANY CHANGES IN STORM WATER/DRAINAGE
 SYSTEM FROM PREVIOUS MASTER PERMIT? PLEASE TELL US WHAT
 CHANGES YOU MADE IN WRITING AND MUST BE APPROVED FROM
 SFWMD ALSO. AND A COPY OF SFWMD.
 2. PLEASE SHOW STANDARDS NOTES OF CITY OF WPB ON CIVIL
 DRAWINGSFOR SIDEWALK WIDTH , ITS SLOPE, DRIVEWAY,
 PARKING, HANDICAP PARKING, PAINTPER CITY CODES ETC.,,
 MUST MEET PER ADA,,ETC.,
 3. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 4. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD ,
 SIDEWALK ELEVATION FOR THIS PERMIT PROJECT MUST MEET FL
 BLDG CODE, PLEASE SHOW ON THE DRAWINGS.,
 5. HOW YOU CONNECT TO THE ROOF DRAINS ? WHERE THE ROOF
 DRAINS GO?
 6. PLEASE SHOW ON DRAWINGS,POLLUTION PREVENTION
 DETAILS,CLOTHES USED FOR SILT ETC., PLANS SHOWING SILT
 FENCE AROUND THE SITE
 7. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED 8.
 ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND YOUR
 THIS BUILDING SITE FOR STORM WATER DRAIN.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-01-23 Cont ID  
Sent By mawillia Date 2007-01-23 Time 17:41 Rev Time 0.00
Received By mawillia Date 2007-01-23 Time 17:41 Sent To  
Notes
2007-01-23 17:43:20*****APPROVED*****
  
  
  
 COMMENTS FROM PREVIOUS FIRE PLAN REVIEW OF 12/04/2006
 HAVE BEEN ADDRESSED.SHEETS A406, E201, E202, E306,
 AND FP306 WERE STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-12-04 Cont ID  
Sent By mawillia Date 2006-12-04 Time 11:56 Rev Time 0.00
Received By mawillia Date 2006-12-04 Time 11:56 Sent To  
Notes
2006-12-04 12:45:17****DENIED*****
  
  
  
 1.NFPA 101 - 2003 EDITION AND THE FLORIDA FIRE
 PREVENTION CODE - 2004 EDITION SHALL BE REFERENCED.
  
 2.CONSTRUCTION OPERATIONS SHALL NOT INTERFERE OR
 HINDER EMERGENCY ACCESS TO THE SAID PROPERTY OR
 VICINITY THEREOF
  
 3.ON THE APPROPIATE ELEVATION DETAIL, SHOW/DISPLAY
 THE NUMERICAL ADDRESS OF THIS BUILDING FRONTING MERRY
 PLACE.AS PER WEST PALM BEACH CODE, THOSE NUMBERS
 SHALL BE NO LESS THAN 6" IN HEIGHT AND 1" IN WIDTH.
 INDIVIDUAL APARTMENT/UNIT SHALL BE NO LESS THAN 3" IN
 HEIGHT.VERIFY WITH LILI URSA, MIS - GIS SUPPORT
 SPECIALIST, THAT THE NEW ADDRESS WILL BE 1825 MERRY
 PLACE.
  
 4.THE ADDRESS OF THE STRUCTURE SHALL BE IN THE TITLE
 BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 5.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE
 FIRE SPRINKLER SYSTEM.
  
 6.FIRE SPRINKLER SYSTEM SHALL BE MONITORED.
  
 7.SHOW DETAIL OF THE FIRE DEPARTMENT CONNECTION
 (FDC).THE FDC SHALL BE NO GREATER THAN 150 FEET TO
 THE NEAREST FIRE HYDRANT.
  
 8.IN ADDITION TO THE KNOX BOX ENTRY SYTEM FOR THE
 BUILDING AS NOTED ON SHEET A801-DETAIL 17,KNOX
 LOCKING CAPS ARE REQUIRED FOR NEW FIRE DEPARTMENT
 CONNECTIONS.
  
 9.INDICATE THE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHERS FOR THE LEASING OFFICE.
  
 10. WILL THIS BUILDING HAVE A FIRE ALARM SYSTEM IN
 CONJUNCTION WITH THE FIRE SPRINKLER SYSTEM?
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2006-12-28 Cont ID  
Sent By kstevens Date 2006-12-28 Time 16:33 Rev Time 0.00
Received By kstevens Date 2006-12-28 Time 16:32 Sent To  
Notes
2006-12-28 16:34:08SEPARATE GAS PERMIT REQUIRED. GAS PLANS/REQUIREMENTS
 SHALL BE SUBMITTED WITH THE GAS APPLICATION.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-11-20 Cont ID  
Sent By kstevens Date 2006-11-20 Time 16:34 Rev Time 0.00
Received By kstevens Date 2006-11-20 Time 16:40 Sent To  
Notes
2006-12-28 16:40:42DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1B. SEPARATE GAS PERMIT REQUIRED. SUBMIT THE FOLLOWING
 INFORMATION:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. AN ISOMETRIC IS REQUIRED FOR EACH GAS
 SYSTEM SHOWING THE PIPING FROM THE METER TO THE MOST
 REMOTEAPPLIANCE FOR EACH UNIT.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 H. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2008-03-05 Cont ID  
Sent By adarroug Date 2008-03-05 Time 16:15 Rev Time 0.00
Received By adarroug Date 2008-03-05 Time 16:15 Sent To B
Notes
2008-03-05 16:15:33TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2008-02-28 Cont ID  
Sent By adarroug Date 2008-02-28 Time 15:53 Rev Time 0.00
Received By adarroug Date 2008-02-28 Time 15:53 Sent To B
Notes
2008-02-28 15:54:32TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2008-02-19 Cont ID  
Sent By adarroug Date 2008-02-19 Time 08:53 Rev Time 0.00
Received By adarroug Date 2008-02-19 Time 08:53 Sent To P
Notes
2008-02-19 08:53:17TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2008-01-23 Cont ID  
Sent By adarroug Date 2008-01-23 Time 12:13 Rev Time 0.00
Received By adarroug Date 2008-01-23 Time 12:13 Sent To B
Notes
2008-01-23 12:13:58TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2007-12-28 Cont ID  
Sent By spalmer Date 2007-12-28 Time 10:36 Rev Time 0.00
Received By spalmer Date 2007-12-28 Time 10:36 Sent To B
Notes
2007-12-28 10:37:39TO JULIO GOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2007-12-04 Cont ID  
Sent By adarroug Date 2007-12-04 Time 13:34 Rev Time 0.00
Received By adarroug Date 2007-12-04 Time 13:34 Sent To M
Notes
2007-12-04 13:34:49TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-11-21 Cont ID  
Sent By adarroug Date 2007-11-21 Time 12:05 Rev Time 0.00
Received By adarroug Date 2007-11-21 Time 12:05 Sent To B
Notes
2007-11-21 12:06:19TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-11-21 Cont ID  
Sent By adarroug Date 2007-11-21 Time 09:39 Rev Time 0.00
Received By adarroug Date 2007-11-21 Time 09:39 Sent To M
Notes
2007-11-21 09:40:05TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-11-15 Cont ID  
Sent By adarroug Date 2007-11-15 Time 10:11 Rev Time 0.00
Received By adarroug Date 2007-11-15 Time 10:11 Sent To M
Notes
2007-11-15 10:11:27TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-10-25 Cont ID  
Sent By adarroug Date 2007-10-25 Time 09:42 Rev Time 0.00
Received By adarroug Date 2007-10-25 Time 09:42 Sent To M
Notes
2007-10-25 09:43:06TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-08-03 Cont ID  
Sent By adarroug Date 2007-08-03 Time 08:30 Rev Time 0.00
Received By adarroug Date 2007-08-03 Time 08:30 Sent To B
Notes
2007-08-03 08:30:38TO "JGOMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-06-28 Cont ID  
Sent By shill Date 2007-06-28 Time 15:11 Rev Time 0.00
Received By shill Date 2007-06-28 Time 15:11 Sent To B
Notes
2007-06-28 15:11:51TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-06-04 Cont ID  
Sent By adarroug Date 2007-06-04 Time 11:58 Rev Time 0.00
Received By adarroug Date 2007-06-04 Time 11:58 Sent To B
Notes
2007-06-04 11:58:47TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-02-05 Cont ID  
Sent By adarroug Date 2007-02-05 Time 16:54 Rev Time 0.00
Received By adarroug Date 2007-02-05 Time 16:54 Sent To P
Notes
2007-02-05 16:54:46TO "KSTEVENS" DESK/RESUB--EXPEDITED PERMIT"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-12-18 Cont ID  
Sent By adarroug Date 2006-12-18 Time 15:31 Rev Time 0.00
Received By adarroug Date 2006-12-18 Time 15:31 Sent To  
Notes
2006-12-18 15:32:01TO "COMM" BD#28/PLANS ON RACK/12 ROLL AND 1 BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-12-06 Cont ID  
Sent By jgomez Date 2006-12-06 Time 18:32 Rev Time 0.00
Received By jgomez Date 2006-10-31 Time 10:07 Sent To  
Notes
2006-11-03 11:46:2211/3/06--SUBMITTAL ROUTED TO "COMM" BD#57 W/ ORIGINAL
 APPL. PACKAGE
2006-10-31 10:07:49(PLANS ROUTED TO INCOMING TODAY) TO "COMM" BD#57/PLANS
 ON RACK 14 ROLLS/1 BOX--EXPEDITED PERMIT

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2007-12-04 Cont ID  
Sent By tgordon Date 2007-12-04 Time 14:28 Rev Time 0.20
Received By tgordon Date 2007-12-04 Time 14:28 Sent To  
Notes
2007-12-04 14:29:16PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 MECHANICAL SUBMITTAL
 *** DENIED ***
 1) MECHANICAL PLANS WILL NEED TO BE REVISED TO SHOW
 THIS CHANGE AND THE CHANGES FROM THE PAST TWO
 SUBMITTALS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-11-30 Cont ID  
Sent By tgordon Date 2007-11-30 Time 14:57 Rev Time 0.15
Received By tgordon Date 2007-11-30 Time 14:57 Sent To  
Notes
2007-11-30 14:58:04RECEIVED SUBMITTAL STATING 8" FLEX DUCT BETWEEN TWO
 MIXING BOX'S

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-11-16 Cont ID  
Sent By tgordon Date 2007-11-16 Time 08:44 Rev Time 0.15
Received By tgordon Date 2007-11-16 Time 08:44 Sent To  
Notes
2007-11-16 08:45:18RECIVED SUBMITTAL TO CHANGE AN 11" FLEX DUCT TO 10".

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-11-01 Cont ID  
Sent By tgordon Date 2007-11-01 Time 13:51 Rev Time 0.30
Received By tgordon Date 2007-11-01 Time 13:51 Sent To  
Notes
2007-11-01 13:53:14REVISION TO MECH. PLANS PAGE M201, M202, AND M203.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-12-20 Cont ID  
Sent By tgordon Date 2006-12-20 Time 11:36 Rev Time 0.30
Received By tgordon Date 2006-12-20 Time 11:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-11-20 Cont ID  
Sent By tgordon Date 2006-11-20 Time 11:22 Rev Time 1.30
Received By tgordon Date 2006-11-20 Time 11:22 Sent To  
Notes
2006-11-20 11:49:35*** DENIED ***
 1) NEED TO SHOW HOW MANY CFM'S OF OUTDOOR AIR IS GOING
 TO AHU 6 AND 7 FOR THE LEASING OFFICE, PLEASE SEE 2004
 FBC/M 401.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-02-23 Cont ID  
Sent By kstevens Date 2008-02-23 Time 18:53 Rev Time 0.00
Received By kstevens Date 2008-02-23 Time 18:53 Sent To  
Notes
2008-02-23 18:54:10REVISION OK--SHT P306

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-02-05 Cont ID  
Sent By kstevens Date 2007-02-05 Time 18:55 Rev Time 0.00
Received By kstevens Date 2007-02-05 Time 18:55 Sent To  
Notes
2007-02-05 18:56:41PROVISO:SEPARATE PLANS & GAS REQUIREMENTS REQUIRED AT
 THE TIME OF APPLICATION FOR THE GAS PERMIT

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-12-29 Cont ID  
Sent By kstevens Date 2006-12-29 Time 07:04 Rev Time 0.00
Received By kstevens Date 2006-12-28 Time 18:46 Sent To  
Notes
2006-12-29 08:36:45DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHTS P306, P403, AND FP306 SHOW CONFLICTING
 INFORMATION. SHT P306 INDICATES A 3" FIRE LINE ENTERING
 THE BUILDING AND CONNECTING TO THE DISTRIBUTION PIPING
 FOR THE BUILDING. SHT P403 BUILDING WATER RISER
 INDICATES THIS SAME LINE TO BE 1-1/2". SHT FP306
 INDICATES A SEPARATE FIRE SPRINKLER LINE AND STATES
 "FIRE LINE, SEE CIVIL FOR CONT.". PLEASE CLARIFY AND
 CORRELATE THE WATER RISER, THE FLOOR PLAN AND THE FIRE
 PROTECTION SHEETS.
  
 2. IF THE FIRE LINE IS TO BE CONNECTED TO THE
 DISTRIBUTION POTABLE WATER IN THE BUILDING, BACKFLOW
 PROTECTION IS REQUIRED UNDER SECTION 608. PLEASE
 INDICATE THE METHOD OF PROTECTION AND VERIFY
 ACCEPTABILITY OF THE SAME WITH THE FIRE PLAN REVIEWER.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-11-20 Cont ID  
Sent By kstevens Date 2006-11-20 Time 14:01 Rev Time 0.00
Received By kstevens Date 2006-11-20 Time 14:00 Sent To  
Notes
2006-11-20 15:14:58DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 NOTE: FIRST PLAN REVIEW FOR APPLICATION
  
 **********FROM PREVIOUS REVIEW**********
  
 1. SHEETS DELETED. WILL BE SUBMITTED AT THE TIME OF
 APPLICATION SUBMITTAL PER RESPONSE.
  
 2. OK
  
 3. SHT A104 DETAIL 06 SINKS SHALL COMPLY
 WITH SECTION 11-4.24.7 FAUCETS. PLEASE
 INDICATE COMPLIANCE ON DETAIL.
 ****RESPONSE NOTED. NOTE REFERENCED INDICATES
 COMPLIANCE WITH LAVS, BUT NOT SINKS. PLEASE INDICATE
 FAUCET TYPE TO BE SUBMITTED FOR BOTH THE LAVS AND THE
 SINKS. (LEVER- OPERATED, PUSH-TYPE ETC).
  
 4. SHT A104 GENERAL NOTES II(5)(C) GRAB
 BAR HEIGHTS SHALL BE 33" MIN. TO 36"
 MAX. PAGE 6.5 FHA DESIGN MANUAL.
 ****RESPONSE NOTED. NOTE WASNOT CORRECTED.
  
 5. DELETED
  
 6. SHT A104 GENERAL NOTES: II(4)(G) SINK
 SHALL HAVE FORWARD APPROACH PER SECTION
 11-4.24.5. SHOW ON DETAIL.
 ****RESPONSE NOTED. COMMENT NOT ADDRESSED
  
 7.SHT A201 DETAIL 07 SUPERIMPOSE THE CLEAR FLOOR
 SPACE FOR THE W/C AS REQUIRED ON PAGE 7.43.
 ****RESPONSE NOTED. NO ACTION TAKEN. (ALSO REQUIRED FOR
 SHT A203).
  
 8.SHTS A201 THRU A205 INDICATE SPECIFICATION "A" OR
 "B" AS REQUIRED ON PAGES 7.34 & 7.35 OF THE FHA DESIGN
 MANUAL.
 ****RESPONSE NOTED. NO ACTION TAKEN. (INDICATE ON
 PLANS).
  
 9.OK.RESPONSE UNDERSTOOD. 7% OF 100 UNITS EQUALS
 9.1 UNITS. 10 UNITS WILL BE REQUIRED TO BE ACCESSIBLE.
  
 10. SHT A203 AND A204 UNITS B1 & C1
 LOWER FLOOR REQUIRED TO MEET FHA-98
 DESIGN REQUIREMENTS 2ND BATHROOMS ARE
 EXEMPT ONLY FROM MANEUVERING AND CLEAR
 FLOOR SPACE IF SPECIFICATION "B" AND
 SHALL SHOW THE BACKING AS WELL AS THE
 SPACING FOR THE WATER CLOSET. (33"
 OPENING, 15"/18" BETWEEN THE FIXTURES).
 PLEASE SHOW ON PLANS. IF SPECIFICATION
 'A" THEN BATHROOM SHALL COMPLY WITH ALL REQUIREMENTS OF
 FHA DESIGN MANUAL.
 ****RESPONSE NOTED. NO ACTION TAKEN.- ALSO COMPLY
 WITH COMMENT 7 FOR THE CLEAR FLOOR SPACE FOR THE W/C.
  
 11. OK. NOT REQUIRED THIS BUILDING.
 12. OK. NOT REQUIRED THIS BUILDING.
 13. OK. (UNIT LOCATION ONLY)
 14. OK. NOT REQUIRED THIS BUILDING.
 15. OK. NOT REQUIRED THIS BUILDING.
 16. OK. NOT REQUIRED FOR THIS BUILDING.
  
 17. SHT A700.1 FINISH SCHEDULE FOR
 LEASING OFFICE AND COMMUNITY RESOURCE.
 PLEASE INDICATE HOW PTD. GYP. BD. MEETS
 THE REQUIREMENT OF SECTION 1210.2.
 ****RESPONSE NOTED. FINISH SCHEDULE NOT CHANGED.
  
 18. SHT A801 A DRINKING FOUNTAIN IS
 REQUIRED PER TABLE 403.1. SUBMIT A
 DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.15 AND ALL SUBSECTION, AS WELL AS
 SECTION 11-4.1.3(10)(A) PROVISIONS FOR
 THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING IF THE DINKING FOUNTAIN IS NOT
 A "HI/LOW" TYPE.
 ****RESPONSE NOTED. NO ACTION TAKEN.
  
 19. OK. NOT REQUIRED FOR THIS BUILDING.
  
 20. SHTS A802 DETAILS 04 & 09 INDICATE
 THE CENTERLINE OF THE W/C 18" OFF THE
 WALL, AND THE CENTERLINE OF THE LAV TO
 BE MIN. 15" OFF THE WALL (TO BE CENTERED
 ON THE 30" WIDTH OF THE CLEAR FLOOR
 SPACE). SECTIONS 11-4.16.2, 11-4.19.3
 AND FIG. 28.
 ****RESPONSE NOTED, BUT THESE REQUIREMENTS ARE FOR
 CHAPTER 11 AS THE TOILET ROOM IS NOT FOR FAIR HOUSING.
 PLEASE INDICATE THE MEASUREMENTS AS REQUESTED ON THE
 DETAIL FOR THAT TOILET ROOM. ALSO SHOW THE CLEAR FLOOR
 SPACE REQUIRED IN SECTION 11-4.16..2.
  
 21. SHT A810 A DRINKING FOUNTAIN IS
 REQUIRED PER TABLE 403.1. SUBMIT A
 DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.15 AND ALL SUBSECTIONS AS WELL AS
 SECTION 11-4.1.3(10)(A). A SERVICE SINK
 IS REQUIRED FOR THE STORAGE OCCUPANCY.
 TABLE 403.1.
 ****RESPONSE NOTED. NOT ACTION TAKEN.
  
 22. OK. NOT REQUIRED FOR THIS BUILDING.
  
 23 SHTS P301 THRU P310 PLAN KEY NOTES #7
 PRESSURE RELIEF VALVE IS INDICATED AS
 RUNNING UNDER THE SLAB. THE RELIEF VALVE
 DISCHARGE LINE SHALL NOT HAVE ANY
 TRAPPED SECTIONS PER SECTION 504.6.1.
 ****RESPONSE NOTED. SHT P301 NOT SUBMITTED THIS
 BUILDING. NO CLARIFICATION SHOWN.
  
 24. OK
 25. OK. NOT REQUIRED FOR THIS BUILDING
 26. OK
  
 27. SUBMIT A BUILDING DRAIN SANITARY
 RISER DIAGRAM ISOMETRIC THAT REFLECTS
 THE FLOOR PLAN FOR EACH BUILDING.
 SECTION 106.1.5.1.3. SHOW ALL PIPE
 SIZES, RISER LOCATIONS, TRAPS, VENTS,
 AND DFU'S AS THEY ACCUMULATE IN THE
 SYSTEM.
 ****RESPONSE NOTED. HORIZONTAL BUILDING DRAIN ISOMETRIC
 RISER DIAGRAM NOT SUBMITTED. ONLY RESIDENTIAL UNIT
 RISER DIAGRAMS FOUND.
  
 28. SUBMIT A WATER RISER DIAGRAM FOR
 EACH BUILDING. SHOW ALL PIPE SIZES,
 VALVES. RISER CONNECTIONS, AND INDICATE
 BLDG. SHUTOFF VALVE AS WELL AS INDICATE
 THE RPZV BACKFLOW REQUIRED FOR EACH
 BUILDING. SECTIONS 106.1.5.1.3 AND
 SECTION 608.13.2.
 ****RESPONSE NOTED. NO RISER FROM METER TO UNITS
 SUBMITTED. ONLY UNIT RISER SHOWN.
  
 29. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 SUBMIT ONE SET OF PLANS FROM FIRST
 REVIEW FOR COMPARISON TO EXPEDITE 2ND
 REVIEW.
  
 **************NEW COMMENTS**************
  
 1B. SHTS A100 & A101 PLANS INDICATE 7% OF THE UNITS
 SHALL BE ACCESSIBLE. 130 UNITS PROVIDED. 7% IS 9.1
 UNITS. ANY FRACTION OF UNITS SHALL BE ROUNDED OFF
 UPWARDS. 10 ACCESSIBLE UNITS REQUIRED. CHART INDICATES
 BLDG "D" 1 REQUIRED/1 PROVIDED, BUT 1 IS INDICATED IN
 BOTH BLDGS.D1/V & D2/VIII, PLEASE CLARIFY. BLDG "E"
 INDICATES 1 REQUIRED/1PROVIDED, BUT 1 IS INDICATED IN
 BOTHBLDGS. E1/V & E2/V. PLEASE CLARIFY. BLDG "F"
 INDICATES 2 REQUIRED/2PROVIDED, BUT ONLY SHOWS 1
 PROVIDED. PLEASE CLARIFY.PLEASE CORRELATE
 INFORMATION, CORRECT AMOUNT OF UNITS AND CHART. SECTION
 106.1.1.
  
 2B. SHT A200 HANDICAP ACCESSIBLE UNIT PLANS NOTES
 LEGEND.NOTES 1, 2, 5,INDICATE "ADAPTABLE". IF UNITS
 ARE TO BE ACCESSIBLE, THEY SHALL BE FULLY ACCESSIBLE AT
 THE TIME THEY ARE BUILT. NOT ADAPTABLE IN THE FUTURE.
 IF THE UNITS ARE TO BE FHA-98 COMPLIANT, THE COMPLETE
 UNIT CAN BE ADAPTABLE.
 NOTE "B" AT THE BOTTOM READS FAIR HOUSING ACT OF 1996.
 PLEASE INDICATE 1998 AMENDMENTS. NOTE FUTHER STATES
 "UNITS HEREIN DESIGNATED AS ACCESSIBLE SHALL BE FULLY
 ADA ADAPTABLE IN ADDITION TO FAIR HOUSING COMPLIANT".
 THIS IS NOT CORRECT. A UNIT IS EITHER FHA-98 ADAPTABLE
 OR FULLY ACCESSIBLE.
  
 3B. SHT A200UNIT PLANS GENERAL NOTES 6 INDICATES 7%
 TO BE FULLY "ADAPTABLE" PLEASE CLARIFY.
  
 4B. SEPARATE GAS PERMIT REQUIRED. SUBMIT THE FOLLOWING
 INFORMATION:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. AN ISOMETRIC IS REQUIRED FOR EACH GAS
 SYSTEM SHOWING THE PIPING FROM THE METER TO THE MOST
 REMOTEAPPLIANCE FOR EACH UNIT.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 H. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2006-11-16 Cont ID  
Sent By ajones Date 2006-11-16 Time 10:30 Rev Time 0.00
Received By ajones Date 2006-11-16 Time 10:30 Sent To  
Notes
2006-11-16 10:31:13LANDSCAPING PLANS SHALL BE APPROVED BEFORE A CO IS
 ISSUED.